You are on page 1of 6

Back

CB2
AUTOMATIC BATTERY CHARGER WITH CONSTANT
VOLTAGE AND CURRENT

SUITABLE FOR LEAD BATTERIES FROM 12 TO 24Vdc.

Automatic battery charger for complete and holding charge for all
batteries, lead and nichel cadmium.
Bitension, immediately adaptable to batteries from 12V and 24V
Versatile and easy to manage.
Electronic control of voltage and current of charge.
Alarm signals in case of failure

FILE VERSIONE DATA LINGUA PAGINA


CB2PCITA B/03 29/09/05 ING 1 of 6
FUNCTIONING

The CB2 automatic battery charger set even with mains variation within a
controls the voltage of the battery range of +/- 15%.
connected. If this voltage is lower than In addition to this, this battery charger is
1.7 V./c, it stops the complete charge and equipped with safety protections against
outputs a min. reset current. mains overvoltages up to 4 KV. The
As soon as 1.7 V/c min. voltage is delivery of dangerous voltages to the
reached, this charger activate the max. output and damages are prevented.
complete charge set and self-adjusted. The CB2-B battery charger controls the
When 2 V/c charge is reached, a gradual current and charge voltage accurately,
decrease of current starts until the 2.25 thus assuring a battery long life. In fact, if
V/c charge is complete (see fig. 1). these values are not controlled, the
When the battery is charged, CB2 overcurrent and overvoltage would cause
accurately limits the holding current by the electrolyte resolution to oxygen and
compensating the battery self-discharge hydrogen. In this way, the high quantity of
and possible consumption of the circuits oxygen would oxidize the inner plates,
connected. During its functioning, the thus reducing its capacity and sulphation
charger holds accurately the parameters life. In order to avoid these drawbacks,
CB2 carries out the following functions:

In order to avoid any problem the CB2-C has got the following functions:
Complete charge of flat batteries with current limitation and protection against short
circuits;
Automatic current reduction during the charge voltage increase;
Charge current stop as soon as each cell reaches 2.25 V. (figure 1);
Automatic compensation of the battery self-discharge and of other possible
consumption;
Protection against 1.65 V./c self-discharge with signaling and battery charger stop
(figure 1);

FUNCTIONAL DIAGRAM
fe
A = Ampere
V/e = Volts/cell

CHARGING
CURRENT

VOLTS / CELL V/c

FILE VER. DATE LANGUAGE PAGE


CB2PCING B/03 29/09/05 ING 2 of 6
SIGNALINGS

pilot lamp: charge connected;


pilot lamp: holding charge;
pilot lamp: alarm;
pilot lamp: connection to 24V.

INSTALLATION AND USE


CB2-B carries out the 12 V. and 24 V. battery recharge. Since the equipment is delivered
with the battery charger set to 12 V., in order to recharge 24 V. batteries, it is necessary to
change the position of jumpers (A, B, C, D) inside the battery charger (figure 2).

Figure 2

SETTING TO 12 V SETTING TO 24V

The connection of "A" and "B" jumpers to 24 V is signalled by led "24V POWER".

!!!CAUTION!!!
Since the connection state of C and D jumpers is not signalled externally,
before supplying CB2-B with power, you are required to check the correct setting of
jumpers.

RATING TRIMMERS

RIMMER DESCRIPTION RANGE


P1 Max. current adjustment to 12 V 13 - 6A
P2 Max. voltage adjustment to 12 V 15 - 10V
P3 Max. voltage adjustment to 24V 30-22V
P4 Max. current adjustment to 24V 11-4A
P5 Overdischarge alarm level adjustment 13-9V

FILE VER. DATE LANGUAGE PAGE


CB2PCING B/03 29/09/05 ING 3 of 6
FUNCTIONAL BLOCK DIAGRAM

0 +B

220 TRANS. OVERDISCHARGE


SIGNALING
380

STARTING VOLTAGE
CIRCUITS CONTROL ALARM
BATTERY
CURRENT
LIMITATION

-B

Sh

INSTALLATION

It is necessary to install CB2-B so as to facilitate the convective circulation of the air --


which is heated by the dissipator --in order to allow a correct cooling of the power circuits
(figure 5).

UP

NO
YES

AIR

figure 5

FILE VER. DATE LANGUAGE PAGE


CB2PCING B/03 29/09/05 ING 4 of 6
FIXING DIMENSIONS

Dimensions in millimetres

WIRING DIAGRAM

Overdischarge alarm relay

alarm battery
+ battery
- battery

phase

phase
neutral
phase phase

figure

FILE VER. DATE LANGUAGE PAGE


CB2PCING B/03 29/09/05 ING 5 of 6
FUSE CAPACITY
POWER F1 F2 A 12V F2 A 24V
CB2-B 150VA 3A 8A 6A
CB2-B 250VA 3A 16A 8A

TECHNICAL FEATURES
MAX. POWER CONSUMED 150VA 250VA
POWER SUPPLY VOLTAGE 220/380V 220/380V

FREQUENCY 50/60HZ 50/60HZ

INSULATION VOLTAGE >3KV >3KV

BATTERY VOLTAGE 12V 24V 12V 24V

MAX. CURRENT 8A 5A 13A 8A

ALLARM LEVEL 10V 20V 10V 20V

MAX. ALARM CURRENT 100 mA 100mA

WORKING TEMPERATURE -20; +50 C

WAVE FORM DOUBLE HALF WAVE

PROTECTION AGAINST OVERLOAD, SHORT CIRCUIT AND POLARITY INVERSION


IN COMPLIANCE WITH
14.6
CEI AND EIC
DIMENSIONS ( WITH NO
110x120x150 110x120x190
FASTENING WING SCREWS)
WEIGHT 4400g 6500g

ORDER CODES:
CB2/150 Automatic battery charger 12V 9A-24V 5A 150VA
CB2/250 Automatic battery charger 12V 15A- 24V 9A 250VA

FILE VER. DATE LANGUAGE PAGE


CB2PCING B/03 29/09/05 ING 6 of 6