CS - SERIES
For Air Conditioning Installations
and Industrial Ventilation Plants
GENERAL CHARACTERISTICS
Summary of the CS Series range availability

Air Volume
From 0.39 m3/s (1400 m3/h) to 23
m3/sec (83000 m3/h), 21 unit sizes.

Total Air Pressure Development


CS
Up to 800 Pa - Forward blade Fan Class I
Up to 1000 Pa - Backward blade Fan Class II
All fans are double inlet type and with
belt drive.
series
Electric Motor
The electric motor is normally installed
inside the fan section, in the air stream.

Air Treatment
Heating - Low pressure hot water
- Medium/High pressure hot water
- Saturated steam
- Electric
Cooling - Mains or well water
- Recirculated brine
- Recirculated chilled water
- Direct expansion refrigeration

Humidification
Water spray type : with single or double
bank water spray nozzles .
Choice of once through to waste water or
pump recirculated water.

Filtration
Medium Air Intake
Efficiency: Disposable flat or pleated Fresh air With inlet rain louvre or
panel type cowl, bird screen or
Washable flat or pleated damper with duct type,
panel type damper with counter flange
Bag or rigid cartridge type
Automatic roll filter Air mixing With dampers for return
High air and fresh air
efficiency: Standard or rigid bag
filters of various lengths Air mixing
and dust holding capacity and exhaust With dampers for exhaust,
return and fresh air
Absolute Standard or large air volume

Activated
carbon: Cell or cartridge type
TECHNICAL DATA

Temperature
tw C Inlet water temperature
tw C Outlet water temperature

Air ts
ts
tu
C
C
C
Inlet air temperature - dry bulb
Outlet air temperature - dry bulb
Inlet air temperature - wet bulb
tu C Outlet air temperature - wet bulb
Handling tvs
te
C
C
Saturated steam temperature
Evaporating temperature

Pressure
Units ps
pd
Pa
Pa
Static pressure
Dynamic pressure
pt Pa Total pressure
pvs bar Actual saturated steam pressure

Enthalpy
J cal/kg Total heat air inlet
J cal/kg Total heat air outlet

Humidity
x g/kg Absolute humidity air inlet
x g/kg Absolute humidity air outlet
UR % Relative humidity

Vol./Q.ty
V m3 /h Air volume
m3 /s Air volume
Vw I/h Water quantity

tw C Water temperature difference


t C Air temperature difference
pw mH2O Water pressure drop
p Pa Air pressure drop
J cal/kg Total heat difference
Technical Manual presents basic x g/kg Absolute humidity difference
information to select our standard range
of CS Series Air Handling Units. Velocity
cu m/s Air velocity
Our manual is divided into two sections.
cw m/s Water velocity

Section 1 REFERENCE DATA Capacity


provides basic information enabling the Q Kcal/h Heating capacity
unit size to be selected, the modular Q KFrig/h Cooling capacity
components to be chosen and the
technical characteristics and construction Others
Lpa db Sound level
features to be summarised.
N kw Power installed
n rpm Revolutions speed
Section 2 TECHNICAL DATA kw % Efficiency
provides technical information in the Fbp By-pass factor
form of data sheet to enable more PD2 kg/m2 Dynamic moment
detailed selection to be performed to
Note:
meet the precise specification The unit performances and all section diagrams are
requirements. referred to following standard air conditions:
- Air temperature + 15 C
- Air specific weight 1,225 kg/m3
- Atmospheric pressure 760 mm Hg
SELECTION DIAGRAM

830
The unit size selection is made 100 680
on the basis of two parameters:
the Air volume
550
the Coil Face air velocity
450
Each model is identified by a very
simple nomenclature: for example 370
50
CS-200 corresponds to the air
volume of 20000 m 3 /h at 2,5 300
m/s coil face velocity. 40
250
The Selection Diagram shows 30
the possibility of achieving smaller 200
or greater air volumes for the 25 165
same unit by varying the coil face
velocity. 20
135
This enables selection to be
AIR VOLUME (x103) m3/h

15 110
optimised in terms of cost,
dimensions, noise criteria, power,

UNIT SIZE CS
90
etc.
73
10
60
49
40
5
32
4
26
3 21

17
2 14

1
2 2,5 3 3,5
AIR VELOCITY (m/s)
UNIT SECTIONS

General description of unit casing

The casing of the CS series Air Handling Units


is composed of :
Self supporting frame in extruded aluminium
profiles anodised natural colour assembled by
corners to give accurate alignment and easily
cleaneable corrosion resistant structure.
Sandwich type double skin panels 23 mm
thickness with internal thermal insulation of
special high density acoustic insulation.
The external and internal sheet metal faces of
the panel can be selected from:
- Galvanized sheet steel 0.6 mm thick .
- Plastic coated galvanized sheet steel 0.6 mm
thick .
- External and internal faces can be of different
materials.
- Galvanized screws inserted in nylon sleeves are
used to fix the panel to the frame and air
tightness is assured by an exclusive rubber seal
under the panel.
- Inspection and access doors constructed of
sandwich panels as described above fixed to the On request the CS series can be equipped with:
casing frame by air tightening hinges and - Bulkhead lights with or without external switch
closed with nylon handles of design with a - Filter manometers .
progressive threaded closing device. The unit support is provided by :
Mechanically secured exclusive rubber door - Strong steel profiles with holes for unit lifting.
seal ensures air tightness . - Drain pan with sandwich panel insulation.
All units can be easily supplied in separate divided
sections or completely knocked down for
transport, site, space or erection requirements.

Air mixing box

Complete with up to 3 dampers to provide


mixing control of fresh, recirculated and exhaust
air streams.
The dampers are available in:
- Extruded aluminium profile blade
- Extruded aluminium with tight shut off edge
seal
Complete with :
- Opposed blades
- Shaft
- Hand operation levers
- Extension for connection of actuator motor or
piston
The damper blades are gear wheel driven .
UNIT SECTIONS

Filter section
See our separate Filter catalogue

Air treatment section


The heating and cooling coils for the treatment of
the air are housed in section and are of finned
block type, having the following standard
characteristics:
- Copper tube and aluminium fins .
- Tube pitch 60 and 30 mm .
- Rows pitch 30 mm .
- Fins pitch 2.0, 2.5, and 3.0 mm.
- (4 and 6 mm for special application).
- Tube diameter 5/8.
- Coil framework galvanised sheet steel.
- Connections - threaded.
- Electric heaters with multi-stage sheathed.
elements with plain surface or extended fin
surface dependent on duty.

Fan section
Forward blade and backward blade fans .
The fans are always of belt drive, double inlet
type, manufactured in galvanized steel sheet, with
steel shaft and ball bearings.

The fan drive is effected through belts of


trapezoidal shape.
The motor pulley is made from aluminium or cast
iron .
Fixed and variable pulleys are available .

The complete fan motor assembly will be


mounted on a base constructed of extruded
aluminium profiles and mounted on vibration
isolators .
Standard vibration isolators are of rubber, with
spring type available on request.

The anti-vibration connection mounted between


the fan outlet and the casing is made of an
aluminium profile frame with self-extinguishing
cloth.

The foregoing characteristics apply also to the


return air and exhaust air fan sections.
The units with twin fans operating in parallel are
equipped with non-return dampers to prevent air
re-circulation in the case of one fan not running.
UNIT SECTIONS

Accessories

We provide as accessories the optional and


complementary equipment described as follows:

Sound Attenuators
See our separate Sound Attenuators catalogue .

Germicidal Lamps Section


This section is specifically designed for specific
application requirements.
The internal walls are provided with reflecting
surface, manufactured in aluminium, plain or
white painted finish.
The tube shape lamps are installed in the
required number.

Internal Lighting System


Normally the internal lighting is required for the
filter section, the Humidifier section and the fan
section .
WATER COOLING COILS
Selection of coils
With chilled water coils, the number of rows The number of rows is found by following the
necessary to satisfy the requested cooling tracing on the diagrams for the example selection
capacity can be immediately determined by the as a function of air inlet conditions, selected unit
following diagrams, for water 5/10C and 7/12C size, air velocity through the coil, fins pitch and in
respectively. relation to the required cooling capacity.

Selection diagram5/10C

5 6
0,5
8
J-
En 0,3 3R
10 tha
lpy

coil by-pass factor


10 12 Cal/k
g
4R
14
tu c

16
18 20 u.r. % 5R
15 100 0,1
90 6R
5

80 7R
0,05
20 70
R
8
60
0,02
25 3 m m m
10

50
2m m 3m
2,5
Air velocity

2,5
m/s

40
20
15

25

30
2
35 40 ts C

K Cal/h
900
1000
1000
1000 1000
500 1000
400 500
500
300 400 500 500
0 400 500
83 300
400 400
0 300 400
68 200 300 300
0 300
55 200
0 200
450 200 200
370 100 200
300
100
250 100
20 100 100
Unit size CS

5 100
16 50
3 5 40 50
1 50
0 40 50 50
110 30 40 50
9 40 40
30 40
73 30
20 30
60 30
30
20 20
49 20 20
40 20
32 10
26 10 10
10 10
21 10
50
17
40 50
14 50
50
30 40 50
40 50
40 40
30 40
30
3 2,5 22 2,5 3
v. coil Fins pitch 3R 4R 5R 6R 7R 8R
m/s mm
WATER COOLING COILS

Selection diagram 7/12C

5 6
0,5
8
J-
10 En
tha 0,3 3 R
10 lpy

coil by-pass factor


12 Cal/k
g
14 4R
tu c

16
18 20 u.r. % 5R
15 100 0,1
90 6R
5

80
0,05 7R
20 70
R
8
60
0,02
25
10

50 3 m m m
2m m 3m
2,5
Air velocity

2,5
m/s
20

40
25
15

30
35 40 ts C 2

K Cal/h
1000
1000
1000
1000 1000 1000
500
500
400 500
400 500 500
300 400 500
300 400 400 400
0 300
83 200 300 300
200 300
80
6 200
5 0 200 200
5 200
5 0 100
4
0 100
370 100
30 100
Unit size CS

0 100 100
250
20 50
50
5 40
16 40 50 50 50
5 50
13 30 40 40
0 30 40 40
11 0 30 30
9 20 30 30
73 20
60 20 20 20 20
49
40 10
10
32 10 10
26 10 10
21 50
50
17 40 50
40 50 50
14 30 40 50
30 40 40 40
3 3,5 22 2,5 3
v. coil Fins pitch 3R 4R 5R 6R 7R 8R
m/s mm
FANS
Determination of CS pressure drops Arrangements for fans
Position of fan outlet for air distribution ducts
To determine fan characteristics it is absolutely
necessary to calculate the pressure drops,
expressed in Pa, of the different sections forming
the unit and to add them to the required external
pressure drop .
It will result :

Air intake louvres


Mixing box with air dampers
Filter cells
Roll filters
Bag filters
Spray humidifier
Evaporating package humidifier
Preheating coil
Dynamic Pressure
Reheating coil Dynamic Pressure and outlet air velocity are
Precooling coil calculated on the full air discharge area including
After cooling coil that of the cut- off area, and therefore ducted outlet
Electric coil conditions. In the case of free outlet the velocity
Other coil pressure is higher and the new value is obtained by
Plenum multiplying the velocity pressure of the ducted outlet
Absolute filters
from the curves, by the correction factor K shown in
the table Nr. 2 below.
Other
Required external pressure drop Tab. 2
TOTAL Pa
ADN = 1.38
RDN = 1.6
Noise Lw (A) as catalogue
- octive band spectrum
The noise level shown on each diagram refers to the Lw = Lw (A) + Lw rel. dB (tab. 3- 4)
sound power (A filter) and the data on the inlet side - Sound pressure level
has been measured in accordance with AMCA a) free field
STANDARD 300 pict. 2 - configuration Lp (A) = Lw (A) - (20log10 d) -11
A. The noise levels of the fans are determined as b) room conditions
follows: Lp (A) = Lw (A) - (20log10 d) - 7
- Sound power level-(A scale): where d = is a distance of fan

ADN Correction factor for frequence analysis Tab. 3


Lw (rel)
Ventilatore / Fans HZ 63 125 250 500 1000 2000 4000 8000
180/200/225 -0.6 -0.2 0 -2.7 -5.3 -8.8 -13.5 -17.6
250/280/315/355 -3.7 -3.6 0 -1.3 -5.7 -9.6 -13.2 -19.5
400/450/500/560 +2 +2.2 +1.3 -4.3 -5.6 -7.8 -14.3 -19.1
630/710/800/900/1000 +5.4 +6 -0.7 -4.4 -4.6 -11.5 -15.4 -22.5

RDN Correction factor for frequence analysis Tab. 4


Lw (rel)
Ventilatore / Fans HZ 63 125 250 500 1000 2000 4000 8000
160/180/200/225 -9 -3.9 -1.2 -4.7 -5.6 -6.6 -9 -12.8
250/280 -7.1 -2.2 -1.5 -8.7 -4.7 -8.8 -9.2 -13
315/355 -3.2 -1.5 -3 -5.7 -5.7 -7.7 -8.4 -13.5
400/450/500 +2.8 +2.7 +0.3 -2.1 -7.1 7.8 -11.3 -16.7
560/630/710 +3.2 +1.7 +1.3 -3.8 -6.8 -9.1 -13.4 -19.9
800/900/1000 +5.5 +1.9 +1.9 -3.4 -6.2 -11.3 -16.8 23.5
Forward Blade Fan NICOTRA

ADN 160
160 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

TOTAL EFF. %
TOTAL PRESSURE

24 31 39 45 49 43 27
2500
2 3
2000 KW
1.5

1 4700
.8
4200
1000 .6

95 3500
.4

.3
3000
500 90
.2
2600
400 .15

85 2200
300 .1

80 1800
200 .05

1600

75 1400
L w(A) in dB (A)
100
1200
80
.05 .1 .2 .3 .4 .5 1 2 m3/ s
volume

x1000 .2 .3 .4 .5 1 2 3 4 5 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 180
180 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

TOTAL EFF. %
TOTAL PRESSURE

22 28 36 44 52 47 32
2500

KW
3
2000
2

1.5
4000

1
3500
1000 .8
95
.6 3000

.4 2700

90
.3 2400
500

400 .2 2100
85
.15
300 1800
PRESSIONE TOTAL E

.1
1600
80
200
1400
.05
75
1200

Lw(A) in dB (A)
100
1000
80
.05 .1 .2 .3 .4 .5 1 2 3 m3/ s
volume

x1000 .2 .3 .4 .5 1 2 3 4 5 10 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 200
200 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

TOTAL EFF. %
TOTAL PRESSURE

29 35 42 47 52 52 39
3500
3000
KW
3 4
3800
2000 2

1.5
3200

1 2900
.8
2600
1000
.6
95 2300
.4
2000
.3
500 90 1800
.2
400 1600
.15
85
300 1400
.1

1200
200 80
.05
1000
75
Lw(A) in dB (A)
100 800

80
.05 .1 .2 .3 . 4 .5 1 2 4 m3/ s
volume

x1000 .2 .3 .4 .5 1 2 3 4 5 10 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 225
225 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

TOTAL EFF. %
TOTAL PRESSURE

26 32 38 44 52 55 34
3500
3000
KW 3
4
2
2000 3400
1.5
3000
1
.8 2600
1000
.6 2300

.4 2000
95
.3
1800
500
.2 1600
400 90
.15
1400
300
.1
85 1200

200
.05
1000
80
900

Lw(A) in dB (A)
800
100

80
.05 .1 .2 .3 . 4 .5 1 2 3 4 5m3/ s
volume

x1000 .3 .5 1 2 3 4 5 10 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 250
250 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

22 30 39 48 56 54 39
3500
3000
KW 7.5
5
4 3000
2000 2800
3

2 2400

1.5 2200

1000 2000
1
1800
.8
95
.6 1600

500 .4 1400
90
400 .3
1200

300 .2
85
.15 1000

200 900
.1
80
800

700
Lw(A) in dB (A)
100

80
.08 .2 .3 .4 .5 1 2 3 4 6 m3/ s
volume

x1000 .3 .5 1 2 3 4 5 10 20 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 280
280 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

29 37 44 51 58 59 42
3500
3000
KW 11
5.5 7.5
2700
4
2500
2000 3

2 2100

1.5
1800
1000
1
1600
.8

.6 1400
95

500 .4 1200

400 .3 90
1000
.2
300
.15 85
800
200 .1
700
80

600
Lw(A) in dB (A)
100

80
.1 .2 .3 .4 .5 1 2 3 4 5 8 m3/ s
volume

x1000 .5 1 2 3 4 5 10 20 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 315
315 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

29 36 43 50 57 60 47
3500
3000 2400
KW
8 11

5.5 2100
2000
4 1900

3 1700

2 1500
1000
1.5
1300

1 95
.8 1100

500 .6 1000
90
400 900
.4

.3 800
300 85
700
.2

200
80 600

.1
500
Lw (A) in dB (A)
100

80
.15 .3 .4 .5 1 2 3 4 5 10
m3/ s
volume

x1000 1 2 3 4 5 10 20 30 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 355
355 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

39 46 53 58 62 61 46
3500
3000
KW 15
7.5 10 2000
5
2000 1800
4

3 1600

2 1400

1000 1.5
1200

1
.8 1000
.6 95 900
500

400 .4 800

.3 90
300 700

.2
600
85
200

500

Lw (A) in dB (A)
100

80
.2 .3 .4 .5 1 2 3 4 5 10 14
m3/ s
volume

x1000 1 2 3 4 5 10 20 30 40 50 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 400
400 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

34 43 52 61 67 62 46
3500
3000
KW
15
10 1800
7. 5
2000 6 1600
1500
4

3 1300

1000
2
1100
1.5
1000

1 900
95
500 .8
800
400 .6
90 700
.4
300
.3 600
85
200 .2
500

80
.1
Lw (A) in dB (A) 400
100

80
.2 .5 1 2 3 4 5 10 16 m3/ s
volume

x1000 1 2 3 4 5 10 20 30 40 50 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 450
450 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

38 45 53 60 66 61 47
2500
15
2000 KW 8 11 1500
1400
6

4 1200

1000 3
1000
2
900
1.5
95 800
500 1
.8 700
400
90
.6
600
300
.4
85
.3 500
200

.2
80
400

Lw (A) in dB (A) 350


100

80
.25 .4 .5 1 2 3 4 5 10 18 m3/ s
volume

x1000 1 2 3 4 5 10 20 30 40 50 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 500
500 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3
N/m2

RPM
Pa

K TOTAL EFF. %
TOTAL PRESSURE

40 49 57 64 66 56 39
2500

2000 KW
15
11
8

6 1300
1200
4
1000 1100
3
1000

2 900

1.5
800
500 95

1 700
400
.8

300 90
.6 600

.4
200 500
85
.3

.2
400
80
Lw (A) in dB (A)
100 350

80
.4 1 2 3 4 5 10 20 25 m3/ s
volume

x1000 2 3 4 5 10 20 30 40 50 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 560
560 mm WHEEL DIAMETER

LR K2 = 1.2 Kg/ m3
N/m2

RPM
Pa

K TOTAL EFF. %
TOTAL PRESSURE

38 46 55 64 68 60 44
3500
3000
KW 37
25
18.5
15
2000 1300
10 1200
8 1100
6 1000
1000
900
4
100
3 800

2 700
95
500
1.5
400 600
1
90
300 .8
500
.6
450
85
200 .4 400
.3
350
80
Lw (A) in dB (A)
300
100

80
.5 1 2 3 4 5 10 20 32 m3/ s
volume

x1000 2 3 4 5 10 20 30 40 50 100 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 630
630 mm WHEEL DIAMETER

LR K2 = 1.2 Kg/ m3
N/m2

RPM
Pa

K TOTAL EFF. %
TOTAL PRESSURE

36 46 56 64 68 59 42
3500
3000
KW 45
30
2000 18. 5
1100
15
1000
10
900
8
1000 6 800

4 700
100
3
600
500
2
95
400 1.5 500

450
300 1 90
.8 400

.6
200 350
85
.4
300

80 Lw (A) in dB (A)
100 250

80
.6 1 2 3 4 5 10 20 30 45 m3/ s
volume

x1000 3 4 5 10 20 30 40 50 100 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 710
710 mm WHEEL DIAMETER

LR K2 = 1.2 Kg/ m3
N/m2

RPM
Pa

K TOTAL EFF. %
TOTAL PRESSURE

35 44 54 64 69 60 43
2500

KW
45
2000 30
18.5
15 900
850
10
750
8
1000 700
6

600
4
100
3
500 500
2
400 95 450
1.5
400
300
1
90 350
.8

200 .6
300
85

250
Lw (A) in dB (A)
100

80
.8 2 3 4 5 10 20 30 45 m3/ s
volume

x1000 5 10 20 30 40 50 100 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 800
800 mm WHEEL DIAMETER

K = 1.2 Kg/ m3
N/m2

RPM
Pa

K2 TOTAL EFF. %
TOTAL PRESSURE

38 46 54 63 70 62 44
2500

2000 KW 45
22 30
800
750
15

650
1000 10
600
8
550
6 100
500
4
500 450
3 95
400 400
2
300 350
1.5 90

1 300
200
.8
85
250
.5

80 Lw (A) in dB (A)
100 200

80
1 2 3 4 5 10 20 30 40 m3/ s
55
volume

x1000 4 5 10 20 30 40 50 100 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 900
900 mm WHEEL DIAMETER

GIRI / m
K = 1.2 Kg/ m3

RPM
N/m2
Pa

K2 TOTAL EFF. %
TOTAL PRESSURE

35 44 53 63 70 66 48
2500

2000 KW 75
30 50
40
700
20 650

15
1000 550
10
500
8
100 450
6
400
500 4
95
400 3 350

300 2 300
90
1.5

250
200
1
85

.6 200

80 Lw (A) in dB (A)
100 170

80
1 2 3 4 5 10 20 30 40 70 m3/ s
volume

x1000 5 10 20 30 40 50 100 200 m3/h

1 2 3 4 5 10 20 30 40 50 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Forward Blade Fan NICOTRA

ADN 1000
1000 mm WHEEL DIAMETER

GIRI / m
K = 1.2 Kg/ m3

RPM
N/m2
Pa

K2 TOTAL EFF. %
TOTAL PRESSURE

29 38 49 61 70 67 51
2500

2000 KW 75
50 650
37
600
30
550
20 500
1000
15 450

10 100 400
8
500 350
6

400 95
4 300

300 3
90 250
2
200
1.5
85 200
1

Lw (A) in dB (A) 160


100

80
1.4 3 4 5 10 20 30 40 50 80 m3/ s
volume

x1000 10 20 30 40 50 100 200 m3/h

1 2 3 4 5 10 20 30 40 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 180
180 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

TOTAL EFF. %
TOTAL PRESSURE

33 46 57 60 54 41 27
3500
3000
KW 1.5

2000 1
.8
.6

1000 .4
.3

.2
7500
.15 90
500 6800
400 .1
6000
85
300 5500
5000

200 80 4500

4000
75 3500
100
3000
70

2500

50 65
Lw(A) in dB (A)
2000

30
.05 .1 .2 .3 . 4 .5 1 2 2 . 6 m3/ s
volume

x1000 .2 .3 .4 .5 1 2 3 4 5 m3/h

1 2 3 4 5 10 20 30 40 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 200
200 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

TOTAL EFF. %
TOTAL PRESSURE

42 51 58 62 61 54 43
3500
3000 3
KW
2

2000 1.5

1
.8

.6 7000
1000

.4 90
6000
.3 5500

85 5000
500 .2

.15 4500
400
80 4000
300
3500

75
200 3000

70 2500
Lw(A) in dB (A)
100 2200

80
.1 .2 .3 .4 .5 1 2 2 . 6 m3/ s
volume

x1000 .4 .5 1 2 3 4 5 m3/h

2 3 4 5 10 20 30 m/s
air outlet velocity

2 5 10 50 100 500 Pa
velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 225
225 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

TOTAL EFF. %
TOTAL PRESSURE

41 51 59 65 64 54 40
3500
4
3000
KW 3

2000 2

1.5

1
.8
1000 6300
5800
95
.4
5000
.3
500 4500
90
.2
400 4000

300 85 3500

3000
200 80
2600

2300
75
Lw(A) in dB (A)
100 2000

80
.14 .2 .3 .4 .5 1 2 3 4 m3/ s
volume

x1000 .6 1 2 3 4 5 10 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 250
250 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

36 48 60 68 67 56 42
3500
3000
KW 4

3
2000
2

1.5

1
1000
.8
5400
.6

.4 4600
90
500 .3
4000
400
3600
85
300 3200

80 2800
200

2400
75

Lw(A) in dB (A) 2000


100

80
.16 .2 .3 .4 .5 1 2 3 4 5 m3/ s
volume

x1000 .6 1 2 3 4 5 10 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 280
280 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

45 56 65 70 68 59 47
3500
5.5
3000
KW
4

3
2000
2

1.5

1 4700
1000 95
.8 4300

.6 4000

3600
90
.4
500 3200
.3
400 85 2800
.2

300
2400
80

200 2000

75 1800

1600
Lw(A) in dB (A)
100 70 1400
80
.2 .3 .4 .5 1 2 3 4 5 m3/ s
volume

x1000 1 2 3 4 5 10 m3/h

2 3 4 5 10 20 30 m/s
air outlet velocity

2 5 10 50 100 500 Pa
velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 315
315 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

47 58 67 72 69 58 43
3500
3000 5.5
KW 7.5
4
2000 3

1.5

1000 4300
1
100
.8 4000

.6
3500
95 3200
500 .4

.3
400 2800
90
300 2400

85
200 2000

1800

80 1600
Lw (A) in dB (A)
100 1400

80
.25 .4 .5 1 2 3 4 5 6 8 m3/ s
volume

x1000 1 2 3 4 5 10 20 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 355
355 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

50 61 70 74 70 59 44
3500
10
3000
KW 5.5
7.5
4
2000
3

1.5
4000
1000
1 3800

.8 100
3300
.6

500 .4 2800
95

400 .3
2400

300 90
2000

1800
200
85
1600

1400
80 Lw (A) in dB (A)
100
1200
80
.25 .4 .5 1 2 3 4 5 10 m3/ s
volume

x1000 1 2 3 4 5 10 20 30 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 400
400 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

49 61 72 76 71 58 42
3500
3000
11
KW 7. 5

5
2000
4

2
1000 1.5 3400
3100
1 100
.8 2800
2600
500 .6
95 2300
400 .4
2000
300 90
1800

1600
200
85
1400

1200
80 Lw (A) in dB (A)
100

80 1000
.4 1 2 3 4 5 10 14 m3/ s
volume

x1000 2 3 4 5 10 20 30 40 50 m3/ h

2 3 4 5 10 20 30 40 50 m/ s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 450
450 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3

RPM
N/m2
Pa

K TOTAL EFF. %
TOTAL PRESSURE

56 65 73 77 74 62 44
3500
10
3000
KW 7. 5 15

5
2000
4

2
1000 3100
1. 5
2800
1 100
.8 2500

500 .6 2200
95
400 2000
.4
1800
300 90
1600

200 1400
85

1200

1100
80 Lw (A) in dB (A)
100 1000

80 900
.4 1 2 3 4 5 10 16 m3/ s
volume

x1000 2 3 4 5 10 20 30 40 50 m3/ h

2 3 4 5 10 20 30 40 m/ s
air outlet velocity

1 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 500
500 mm WHEEL DIAMETER

LR = 1.2 Kg/ m3
N/m2

RPM
Pa

K TOTAL EFF. %
TOTAL PRESSURE

58 67 74 77 73 64 52
3500
15
3000
KW
11

8
2000
6

4
2800
3
1000 2500
100 2300
2

1.5 2100

95
1 1800
500
.8
400 1600
.6
90
300 1400

85 1200
200

1000
80
900
Lw (A) in dB (A)
100 800

80
.7 1 2 3 4 5 10 18 m3/ s
volume

x1000 3 4 5 10 20 30 40 50 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 560
560 mm WHEEL DIAMETER

LR K2 = 1.2 Kg/ m3
N/m2

RPM
Pa

K TOTAL EFF. %
TOTAL PRESSURE

62 70 76 77 73 62 47
3500
3000 18.5
KW 25
15 30

2000 10
8

2600
4
1000
3 2300

2 100 2000

1.5 1800
500
1 95 1600
400
.8
1400
300 .6
90
1200

200
85 1000

850
Lw (A) in dB (A)
80
100

80 700
1 2 3 4 5 10 20 25 m3/ s
volume

x1000 5 10 20 30 40 50 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

3 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 630
630 mm WHEEL DIAMETER

LR K2 = 1.2 Kg/ m3
N/m2

RPM
Pa

K TOTAL EFF. %
TOTAL PRESSURE

58 67 75 79 78 69 54
3500
25
3000
KW 30 40
18.5
15
2000
10
8
2300
6
2000
1000 4
100 1800
3
1600
2
95 1400
500 1.5

400 1 1200
.8 90
300
.6 1000

85 900
200
800

80 700
Lw (A) in dB (A)
100 600
80
1 2 3 4 5 10 20 30 m3/ s
volume

x1000 5 10 20 30 40 50 100 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 710
710 mm WHEEL DIAMETER

LR K2 = 1.2 Kg/ m3
N/m2

RPM
Pa

K TOTAL EFF. %
TOTAL PRESSURE

69 74 78 79 75 65 51
3500
25
3000 45
KW 22
35
15
2000
10
8
2000
6 105
1000
4 1700

3 100 1500

2
1300
500
1.5 95 1200
400 1100
1
1000
300
90
900

200 800
85
700

Lw (A) in dB (A) 600


100

80
1. 4 2 3 4 5 10 20 30 40 m3/ s
volume

x1000 6 10 20 30 40 50 100 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 800
800 mm WHEEL DIAMETER

K = 1.2 Kg/ m3
N/m2

RPM
Pa

K2 TOTAL EFF. %
TOTAL PRESSURE

62 70 76 79 74 63 46
3500
3000
KW
25
22 35 45
2000
15

10
8

1000 6 1600

4 105
1400
3 1300
1200
500 2 100
1100
400 1.5 1000

300 1 95 900

800

200 90 700

600
85
Lw (A) in dB (A)
100
500
80
1.6 3 4 5 10 20 30 40 50 m3/ s
volume

x1000 6 10 20 30 40 50 100 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 900
900 mm WHEEL DIAMETER

GIRI / m
K = 1.2 Kg/ m3

RPM
N/m2
Pa

K2 TOTAL EFF. %
62 69 76 79 78 70 57
TOTAL PRESSURE

3500
3000 40
KW 75
30 50

2000 20 60

15
1600
1500
10
105
8
1000 1300
6 1200
100 1100
4
1000
3
500
900
95
400 2
800
1.5
300 700
90
1

600
200
85

500

80 Lw (A) in dB (A)
100
400
80
2 3 4 5 10 20 30 40 60 m3/ s
volume

x1000 10 20 30 40 50 100 200 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
Backward Blade Fan NICOTRA

RDN 1000
1000 mm WHEEL DIAMETER

GIRI / m
K = 1.2 Kg/ m3

RPM
N/m2
Pa

K2 TOTAL EFF. %
TOTAL PRESSURE

58 69 77 79 74 59 42
3500
3000 50 60
KW
37 75

2000 25
20

15

1000 10
1350
8

6 1200
105

1050
4
500
3 100 900
400
2 800
300
95
700

200 600
90

500
85 Lw (A) in dB (A) 450
100

80 400
2.4 4 5 10 20 30 40 50 80 m3/ s
volume

x1000 10 20 30 40 50 100 200 m3/h

2 3 4 5 10 20 30 40 m/s
air outlet velocity

2 5 10 50 100 500 1000 Pa


velocity pressure N/m2
Installation type: free inlet , ducted outlet
Effects of appurtenances in airstream not included
Power rating kw does not include drive Losses
DESCRIPTION

APPLICATIONS
The double inlet TA series centrifugal fans, forward 3TA/R: available up to size 18/18, single shaft with
curvedblade fanwheels, are naturally suited for venti- two lateral bearings.
lating and air conditioning systems, both civil and in- The performance of these fans, if compared
dustrial applications , for heating and cooling units to single fans, is approximately the follo-
and warm air generators. wing:
This centrifugal fan series is projected for handling Delivery : x3
clean air. Discharge volumes up to 100.000 cu m/h. Pressure : x1
Static pressures up to 150 mm H2 O RPM : x 1,08
Temperatures up to 70 Power : x 3,25
Max allowable fan RPM : x 0,7
CONSTRUCTION DETAILS
The fans of this series are produced with particular ACCESSORIES
care and structurally very rugged. a) BASE SUPPORTS in pre-drilled heavy duty steel
The SCROLLS are made of stamped steel plates. Ca- plate, ready for mounting in any position around
sing sides, cut from a single plate, are electrically wel- the ventilator scroll in the TA/S version.
ded to the scroll. A deflector plate is fixed with self Supplied with fasteners and assembly hardware.
tapping screws to the diffuser. b) MOTOR SUPPORT, to be mounted in a number of
The DOUBLE SECTION FANWHEELS aer sheet con- positions around the fan scroll in the TA/S version,
struction with forward curved plates. Disks and rims with axial and tangential motor adjustments, and
are well oversized. Blades are beaded or riveted to regulation of transmission tension. Supplied with
disks and rims. Each fanwheel is carefully balanced, necessary fasteners.
both statically and dinamically. c) FIXED PULLEYS IN ALUMINIUM for ventilator fan
SHAFT and BEARINGS are produced with particular shaft mounting, one groove for section A,trapezoi-
care, as far as dimensions and quality are concerned. dal belts, in aluminium for 100 - 130 - 150 - 180
The supports of all ball bearings are prelubrified,as to pitch diameters.
guarantee, under normal working and environmental d) VARIABLE PITCH PULLEYS IN ALUMINIUM for
conditions, a troubleless and longlasting operation. motor shaft mounting,one grove for section A and
The FRAMES of the TA/R series are constructed with B, trapezoidal belts, as to allow for an about 30%
steel bars, so as to form a frame cube and are electri- fan RPM regulation, when motor is stopped.
cally welded. In aluminium for the following pitch diameters:
from 60 to 75 mm,
FINISHES
from 70 to 85 mm and
Zinc plated finish: for high corrosion resistance. from 92 to 113 for section "A" belts
Special finish: series TA/R with aluminium scroll.
from 63 to 79 mm,
from 73 to 95 mm and
TYPES AVAILABLE
from 100 to 130 for section "B " belts
The following types of series TA centrifugal fans are
N.B.: section " A " = 13x8 mm
produced and available:
section " B " = 17x11 mm
TA/S: includes 11 types, from 7/7 to 18/18, with
e) MOTOR MOUNTS for fan case mounted motors in
discharge capacities of up to 18.000 cu m/h
the TA/R and 2 TA/R versions,with motor axial and
and static heads of up to 80 mm H2 O
tangential adjustments.
These models have been designed to meet
Supplied with necessary fasteners.
maximum simplicity and economy require-
ments, without giving up precision or f) VIBRATION DAMPER, produced from a glass- neo-
strength. prene material fastened two galvanized steel
strips.
TA/R: available in 20 sizes from 7/7 to 30/28 with
Maximum operating temperature allowed is 95C.
discharge capacities of up to 60.000 cu m/
To be mounted when the fan has to be thouroughly
h, and static heads of up to 80 mm H2 O for
insulated from ducts, as to avoid all interferences
1stclass fans and 150 mm H2 O for 2nd class
and subsequent noises and vibrations.
fans (see characteristic diagrams).
The fans of this series are mounted in a fra- g) DRIVE SAFETY GUARD CARTERS - The employ-
me,allowing for orientation in 4 directions. ment of safety carter guards to be mounted as belt-
drive protection is recommended as to eliminate
2TA/R: available up to size 30/28, single shaft with
whatever risk of injuries to personnel.
two lateral bearings.
h) COMMON MOTOR AND FAN MOUNTING
Performance of these fans, in comparison
BASE.
to single fans is approximately the follo-
wing: i) BASE VIBRATION DAMPERS to cut down transmis-
Delivery :x2 sion of vibrations between the fan and the suppor-
Pressure :x1 ting frame.
RPM : x 1,05 Thus, the fan is completely insulated from its foun-
Power : x 2,15 dations.
Max allowable fan RPM : x 0,7
EXAMPLE

HOW TO USE THE DIAGRAMS


a) Performance curves refer to double intake fans. b) Sample of calculation.
The following information is reported on the per- Assuming a double intake centrifugal fan has to be
formance charts: selected to meet the following requirements:
discharge volume in cu m/h - logarithmic scale volume (Q) : 3.400 cu m/h
discharge volume in cv m/sec - logarithmic scale static head (p. st.) 35 mm H2O
static pressure in mm H2 O logarithmic scale
velocity pressure in mm H2 O - logarithmic scale
outlet velocity in m/sec. - logarithmic scale
1st and 2nd class boundary Starting from point A, corresponding to the 3.400
delivery -pressure curves cu m/h required, continue upwards vertically and
cross at point X the horizontal line draw to B, in cor-
delivery-pressure curves
respondence to a static head pressure of 35 mm
revolutions per minute RPM logarithmic scale H2O
brake horsepower curves On the TA 10/10 diagram the following fan cha-
racteristics can be directly read off:
noise level curves
revolutions per minute n = 1170 R.P.M.
fan wheel diameter
brake hors power P inst = 0,75 metric H.P.
number of blades
total efficency T = 0,65
peripheral speed
discharge velocity VU = 10 m/s
blade surface
velocity pressure P din = 6 mm H2O
RPM speed limits for the two classes
noise level LA = 72 dBA
maximum installed power
fan weight

Revolutions per minute Brake horsepower-metric H.P. Noise level dBA


t = 0,64 t = 0,67
Hst [mm H2O] x 9,81 = [Pa]

t = 0,58
se

Hst mm H2O
as

150 2400
Cl

2200
2a

2000
100 100
90 1800 90
80 80
se

1700
70 Hd 70
as

1600
Cl

60 1500 60
1a

7,5
1400 50
50
1300 5,5
90
40 1200 40
4
B X
1100
30 3 30

85
l1

1000
ri a

2
900
Gi

w]

20 20
1,5
[K

800 80
=

15
35

15 1
0,7

700
0,75
X
]

75
.V.

10 10
H [mm H2O] x 9,81 = [Pa]
[C

600 0,5 9
9
ITA

8 8
RB

7 500 0,33 7
SO

70 Hd
6 6
AS

0,25
5
A

5
NZ

60
TE

4 65 4
PO

0,10

3 3
1.000 1.500 2.000 3.000A 4.000 5.000 6.000 8.000 10.000 Q m3/h

0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 15 2 3 Q m3/sec.


3 4 5 6 7 8 9 10 15 20 30 Vu. m/sec.
0,3 0,4 0,5 1 1,5 2 3 4 5 10 15 20 30 40 50 100
Hd [mm H O] x 9,81 = [Pa]
2
TA 7-7
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,60 t = 0,65
Hst [mm H2O] x 9,81 = [Pa]

Hst mm H2O
150

t = 0,58

100
90
80
70 2400

60 2200
2000
50
1900
1800 40
40
1700
1600
30 1500 30
1400 Hd
1300
1

l1

20 1200 20

w]
85
ri a

0,75

[K
1100
Gi

=
15 15

35
1000 0,5
80
0,7
900 X
10 0,33 10
]

H [mm H2O] x 9,81 = [Pa]


.V.

9 800 9
[C

0,25 75 8
8
ITA

7 7
700
RB

6
SO

6
AS

70 5
5 0,1
A
NZ

4 4
TE
PO

60
3 55 0,05 3
400 600 800 1.000 1.500 2.000 3.000 4.000 Q m3/h

0,09 0,1 0,15 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 Q m3/sec.
2 3 4 5 6 7 8 9 10 15 20 Vu. m/sec.

0,2 0,3 0,4 0,5 1 1,5 2 3 4 5 10 15 20 30 40

Hd [mm H2O] x 9,81 = [Pa]

Fanwheel diameter 200 mm


Number of blades 40 Ht = Total pressure
PD (kgxm )
2 2
0.08
Peripheral velocity n x 0.0105 m/s
Hst = Statics pressure
Blade surface 0.046 m2
Max. allowable fan I class II class
RPM 2.400 Hd =Dynamics pressure
Max. installed power TA-S: 1.5
(metric H.P.) TA-R: 1.5
Ht = Hst + Hd

t = Total efficiency Revolutions per minute


Fan net weight TA-S: 5 kg Brake horsepower - metric H.P.
TA-R: 6 kg Noise level dBA
TA 9-9
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,65 t = 0,68
Hst [mm H2O] x 9,81 = [Pa]

Hst mm H2O

sse
150

Cla
2600
t = 0,58

2a
2400
100 2200
90
80 2.000
sse

70 1900 70
1800
Cla

60 1700 60
1a

50 1600 Hd 50
1500 4 90
40 1400 40
3
1300
30 30
1200
2 85
1100

1,5
l1

20
ri a

20

w]
1.000

[K
Gi

1 80

=
15 900 15

35
0,75

0,7
800
75 X
]
10 0,5 10
.V.

H [mm H2O] x 9,81 = [Pa]


700 9
9
[C

8 8
ITA

0,33
7 600 7
RB

70
0,25
SO

6 6
AS

5 500 5
A
NZ

65
4 4
TE

0,10
PO

60 3
3
600 1.000 1.500 2.000 3.000 4.000 5.000 6.000 Q m3/h

0,15 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,5 2 Q m3/sec.

2 3 4 5 6 7 8 9 10 15 20 Vu. m/sec.
0,2 0,3 0,4 0,5 1 1,5 2 3 4 5 10 15 20 30 40

Hd [mm H2O] x 9,81 = [Pa]

Fanwheel diameter 250 mm


Number of blades 33 Ht = Total pressure
PD (kgxm )
2 2
0.12
Peripheral velocity n x 0.0131 m/s
Hst = Statics pressure
Blade surface 0.078 m2
Max. allowable fan I class II class
RPM 2.000 2.400 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-S: 3
TA-R: 3 5.6 Ht = Hst + Hd
2TA-R: 4 5.5
3TA-R: 4
t = Total efficiency Revolutions per minute
Fan net weight TA-S: 8kg TA-R: 9kg Brake horsepower - metric H.P.
2TA-R: 30kg 3TA-R: 48kg Noise level dBA
TA 10-10
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,64 t = 0,67
Hst [mm H2O] x 9,81 = [Pa]

t = 0,58

se
Hst mm H2O
2400

as
150

Cl
2200

2a
2000
100 100
90 1800 90
80 1700 80
se

Hd 70
as

70 1600
Cl

1500 60
1a

60 7,5
1400 50
50 5,5
1300 90
40 1200 40
4
1100 3
30 30
85

1000
l1
ri a

2
900
Gi

w]
20 20
1,5

[K
=
800 80

35
15 15
1

0,7
700
0,75 X
]
.V.

10 75 10

H [mm H2O] x 9,81 = [Pa]


[C

9 600 0,5 9
ITA

8 8
RB

7 0,33 7
500
SO

70 6
6
AS

0,25
A

5 5
NZ

60
TE

4 65 4
PO

0,10

3 3
1.000 1.500 2.000 3.000 4.000 5.000 6.000 8.000 10.000 Q m3/h

0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 15 2 3 Q m3/sec.

3 4 5 6 7 8 9 10 15 20 30 Vu. m/sec.

0,3 0,4 0,5 1 1,5 2 3 4 5 10 15 20 30 40 50 100


Hd [mm H2O] x 9,81 = [Pa]

Fanwheel diameter 280 mm


Number of blades 39 Ht = Total pressure
PD (kgxm )
2 2
0.16
Peripheral velocity n x 0.0146 m/s
Hst = Statics pressure
Blade surface 0.0955 m2
Max. allowable fan I class II class
RPM 1.800 2.200 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-S: 3
TA-R: 3 5.5 Ht = Hst + Hd
2TA-R: 4 5.5
3TA-R: 4
t = Total efficiency Revolutions per minute
Fan net weight TA-S: 9kg TA-R: 11kg Brake horsepower - metric H.P.
2TA-R: 36kg 3TA-R: 55kg Noise level dBA
TA 12-12
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,62 t = 0,68
Hst [mm H2O] x 9,81 = [Pa]

Hst mm H2O

e
t=

ss
150

cl a
1900 0,63

2a
1800
1700
100 1600
90
80 1500
e

1400
ss

70 70
cl a

1300
60 60
1a

1200
50 50
1100
40 Hd 40
1000 75
l1 ,

5,5
30 30
ri a

900
Gi

4
85
800 3
20 20

w]
700 2

[K
15 15

=
1,5 80

35
600

0, 7
10 65 1 ]X 10

H [mm H2O] x 9,81 = [Pa]


.V.
9 75 9
0,75
[C

8 0,35 8
ITA

7 7
RB

0,5
6 6
SO

70
AS

5 5
ZA

4 4
N
TE
PO

3 3
1.000 1.500 2.000 3.000 4.000 5.000 6.000 8.000 10.000 Q m3/h

0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,5 2 2,5 3 Q m3/sec.

2 3 4 5 6 7 8 9 10 15 20 Vu. m/sec.

0,2 0,3 0,4 0,5 1 1,5 2 3 4 5 10 15 20 30

Hd [mm H2O] x 9.81 = [Pa]

Fanwheel diameter 330 mm


Number of blades 45 Ht = Total pressure
PD (kgxm )
2 2
0.4
Peripheral velocity n x 0.0173 m/s
Hst = Statics pressure
Blade surface 0.135 m2
Max. allowable fan I class II class
RPM 1.500 1.800 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-S: 4
TA-R: 5.5 7.5 Ht = Hst + Hd
2TA-R: 7.5 10
3TA-R: 10
t = Total efficiency Revolutions per minute
Fan net weight TA-S: 16kg TA-R: 22kg Brake horsepower - metric H.P.
2TA-R: 56kg 3TA-R: 96kg Noise level dBA
TA 15-15
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,64 t = 0,69 t = 0,64


Hst [mm H2O] x 9,81 = [Pa]

Hst mm H2O

se
as
150
1700

Cl
2a
1600
1500
100 1400
90 90
1300 80
80
se

70 1200 70
as

Hd
Cl

60 1100 60
1a

50 1000 15 50
90
40 900 10 40

l1

800 7,5
ri a

30 30
Gi

5,5 85
700

w]
4

[K
20 20

=
600 3 80

35
0,7
15 15
2
500 ]X
.V.
1,5 75
[C

10 10
ITA

H [mm H2O] x 9,81 = [Pa]


9 1 9
RB

8 8
SO

60 0,75
7 70 7
AS

6 0,35 6
A

0,5
NZ

5 5
TE

65
PO

4 4

3 3
1.500 2.000 3.000 4.000 5.000 6.000 8.000 10.000 15.000 20.000 Q m3/h

0,5 0,6 0,7 0,8 0,9 1 1,5 2 2,5 3 4 5 6 Q m3/sec.


3 4 5 6 7 8 9 10 15 20 2,5 30 Vu. m/sec.
0,3 0,4 0,5 1 1,5 2 2,5 3 4 5 10 15 20 30 40

Hd [mm H2O] x 9,81 = [Pa]

Fanwheel diameter 395 mm


Number of blades 51 Ht = Total pressure
PD (kgxm )
2 2
0.9
Peripheral velocity n x 0.0206 m/s
Hst = Statics pressure
Blade surface 0.190 m2
Max. allowable fan I class II class
RPM 1.300 1.700 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-S: 5.5
TA-R: 7.5 10 Ht = Hst + Hd
2TA-R: 10 15
3TA-R: 15
t = Total efficiency Revolutions per minute
Fan net weight TA-S: 22kg TA-R: 30kg Brake horsepower - metric H.P.
2TA-R: 80kg 3TA-R: 139kg Noise level dBA
TA 18-18
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,64 t = 0,69 t = 0,65


Hst [mm H2O] x 9,81 = [Pa]

Hst mm H2O
150

se
as
1300
Cl
2a
1200
100 100
90 1100 90
80 80
1000 Hd
70 70
se

25
as

60 900 60
20
Cl
1a

50 800 50
15
40 40
700

10
l1

90
ri a

30 7,5 30

w]
Gi

600

[K
5,5

=
85

35
20 4 20

0,7
500

]X
15 3 15
.V.
80
[C

400
ITA

65 2
RB

10 0,75 1,5 10

H [mm H2O] x 9,81 = [Pa]


SO

9 70 75 9
AS

8 8
1
A

7 7
NZ

6
TE

6
PO

5 5

4 4

3 3
3.000 4.000 5.000 6.000 8.000 10.000 15.000 20.000 30.000 40.000 Q m3/h

0,9 1 1,5 2 2,5 3 4 5 6 7 8 9 10 Q m3/sec.

4 5 6 7 8 9 10 15 20 25 30 40 Vu. m/sec.

1 1,5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 100

Hd [mm H2O] x 9,81 = [Pa]

Fanwheel diameter 470 mm


Number of blades 53 Ht = Total pressure
PD (kgxm )
2 2
2.3
Peripheral velocity n x 0.0246 m/s
Hst = Statics pressure
Blade surface 0.267 m2
Max. allowable fan I class II class
RPM 1.000 1.300 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-S: 5.5
TA-R: 7.5 10 Ht = Hst + Hd
2TA-R: 15 25
3TA-R: 20
t = Total efficiency Revolutions per minute
Fan net weight TA-S: 38kg TA-R: 53kg Brake horsepower - metric H.P.
2TA-R: 126kg 3TA-R: 200kg Noise level dBA
TA 20-20
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,68 t = 0,69 t = 0,64


200
Hst [mm H2O] x 9,81 = [Pa]

se
Hst mm H2O

as
150 1300

Cl
2a
1200
1100
100
90 1000
se

80 80
as

900 70
70
Cl

Hd
1a

60 800 60
50 50
700
40 25 40
20 95
600
30 15 30

l1
ri a

500 10
Gi

90

w]
20 20
7,5

[K
=
15 5,5 15

35
400

0,7
85
4 ]
X
.V.

10 3 10

H [mm H2O] x 9,81 = [Pa]


[C

9 300 9
ITA

80 8
8 65 2
RB

7 7
SO

1,5
6 6
AS

75
A

5 1 5
NZ

70
TE

4 0,75 4
PO

3 3
3.000 4.000 6.000 8.000 10.000 15.000 20.000 30.000 40.000 Q m3/h

0,9 1 1,5 2 2,5 3 4 5 6 7 8 9 10 Q m3/sec.

2 3 4 5 6 7 8 9 10 15 20 25 30 Vu. m/sec.

0,3 0,4 0,5 1 1,5 2 2,5 3 4 5 10 15 20 25 30 40 50 60


Hd [mm H2O] x 9,81= [Pa]

Fanwheel diameter 512 mm


Number of blades 42 Ht = Total pressure
PD (kgxm )
2 2
4.3
Peripheral velocity n x 0.0268 m/s
Hst = Statics pressure
Blade surface 0.397 m2
Max. allowable fan I class II class
RPM 1.000 1.200 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-R: 15 20
2TA-R: 20 25 Ht = Hst + Hd

t = Total efficiency Revolutions per minute


Fan net weight TA-R: 98kg Brake horsepower - metric H.P.
2TA-R: 200kg Noise level dBA
TA 22-22
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,68 t = 0,68 t = 0,63


Hst [mm H2O] x 9,81 = [Pa]

Hst mm H2O

se
150

as
1200

Cl
2a
1100
100 1000
90
80 900
se

70 70
as

800
Cl

60 Hd 60
1a

50 700 40 50

40 30 40
600 25

l1

20 95
ri a

30 30
500
Gi

15

10 90

w]
20 20

[K
400
7,5

=
15 15

35
5,5

0,7
85
300 4 X
]
.V.

10 10
[C

H [mm H2O] x 9,81 = [Pa]


3 9
9
ITA

80
8 8
RB

7 2 7
SO

6 1,5
AS

6
200 75
A

5
NZ

5
1
TE

4 4
PO

65 0,75
70
3 3
4.000 6.000 8.000 10.000 15.000 20.000 30.000 40.000 60.000 Q m3/h
1,5 2 2,5 3 4 5 6 7 8 9 10 15 Q m3/sec.
3 4 5 6 7 8 9 10 15 20 25 30 Vu. m/sec.

0,4 0,5 1 1,5 2 3 4 5 10 15 20 30 40 50


Hd [mm H2O] x 9,81= [Pa]

Fanwheel diameter 575 mm


Number of blades 48 Ht = Total pressure
PD (kgxm )
2 2
5.8
Peripheral velocity n x 0.03 m/s
Hst = Statics pressure
Blade surface 0.480 m2
Max. allowable fan I class II class
RPM 900 1.100 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-R: 15 20
2TA-R: 20 30 Ht = Hst + Hd

t = Total efficiency Revolutions per minute


Fan net weight TA-R: 104kg Brake horsepower - metric H.P.
2TA-R: 225kg Noise level dBA
TA 25-25
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,67 t = 0,69
Hst [mm H2O] x 9,81 = [Pa]

t = 0,62
Hst mm H2O
150 1000

se
as
Cl
900

2a
100
90 800
80 80
70 700 70
se

60 60
as

Hd
Cl

50 600 50
40
1a

40 30 40
500 25 95
30 20 30

l1

15
ri a

400 90
Gi

20 20

w]
10

[K
15 7,5

=
15
85

35
300 5,5

X
0,7
10 4 ] 10

H [mm H2O] x 9,81 = [Pa]


.V.
9 80 9
[C

8 3 8
ITA

7 7
RB

2
SO

6 200 75 6
AS

5 5
A
NZ

65
4 1 4
TE

70
PO

3 3
4.000 6.000 8.000 10.000 15.000 20.000 30.000 40.000 50.000 Q m3/h
1,5 2 2,5 3 4 5 6 7 8 9 10 15 Q m3/sec.

2 3 4 5 6 7 8 9 10 15 20 25 Vu. m/sec.
0,2 0,3 0,4 0,5 1 1,5 2 3 4 5 10 15 20 25 30 40

Hd[mm H2O] x 9,81= [Pa]

Fanwheel diameter 665 mm


Number of blades 54 Ht = Total pressure
PD (kgxm )
2 2
9.8
Peripheral velocity n x 0.0347 m/s
Hst = Statics pressure
Blade surface 0.630 m2
Max. allowable fan I class II class
RPM 800 1.000 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-R: 15 25
2TA-R: 25 40 Ht = Hst + Hd

t = Total efficiency Revolutions per minute


Fan net weight TA-R: 145kg Brake horsepower - metric H.P.
2TA-R: 295kg Noise level dBA
TA 28-28
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,69 t = 0,67
Hst [mm H2O] x 9,81 = [Pa]

se
Hst mm H2O

as
150

Cl
2a
800

100
700
90

se
t = 0,62

as
80

Cl
70 1a 600
60 550 60
50 Hd
500 50

40 450 40
30 90
30 400 25 30

l1

20
ri a

350
Gi

15 85
20 20
300
10
15 15

H [mm H2O] x 9,81 = [Pa]


7,5
80

w] A
250 = BIT
5,5
35 OR
[K
10 10
0,7 SS

9 4 9
] ZA A

8 75 8
200 3
[C TEN

7 65 7
X
PO
.V.

6 6
2 70
5 5
5 6 7 8 9 10 15 20 30 40 50 60 Q m3/h x 1000

1,5 2 2,5 3 4 5 6 7 8 9 10 15 20 Q m3/sec.

2 2,5 3 4 5 6 7 8 9 10 15 20 25 Vu. m/sec.

0,3 0,4 0,5 1 1,5 2 3 4 5 6 7 8 9 10 15 20 30 40

Hd[mm H2O] x 9,81= [Pa]

Fanwheel diameter 720 mm


Number of blades 60 Ht = Total pressure
PD (kgxm )
2 2
13
Peripheral velocity n x 0.0375 m/s
Hst = Statics pressure
Blade surface 0.757 m2
Max. allowable fan I class II class
RPM 700 800 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-R: 20 30
2TA-R: 30 40 Ht = Hst + Hd

t = Total efficiency Revolutions per minute


Fan net weight TA-R: 175kg Brake horsepower - metric H.P.
2TA-R: 340kg Noise level dBA
TA 30-28
CHARACTERISTIC CURVES

Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t =0,67 t =0,69 t =0,61


Hst [mm H2O] x 9.81 = [Pa]

Hst mm H2O

e
ss
150
800

la
2aC
750
700
100 100
90 650 90
80 600 80
e

70 Hd 70
ss

550
la

60 60
1aC

500
50 50
450 40
40 40
95
400 30
30 25 30
350 20
90

w]
15

[K

l1

20 20

5=
ri a

300
Gi

10

,73
15 85 15
x0
250 7,5 V.]
.

5,5
[C

10 80 10

H [mm H2O] x 9.81 = [Pa]


ITA

9 200 4 9
RB

8 8
3
SO

7 7
AS

6 75 6
2
A

150
NZ

5 5
TE
PO

4 4
70
1
65
3 3
8.000 10.000 15.000 20.000 30.000 40.000 60.000 80.000 100.000 Q m3/h

2 2,5 3 4 5 6 7 8 9 10 15 20 25 30 Q m3/sec.

3 4 5 6 7 8 9 10 15 20 25 30 Vu. m/sec.

0,4 0,5 1 1,5 2 3 4 5 6 7 8 9 10 15 20 30 40 50


Hd [mm H2O] x 9.81 = [Pa]

Fanwheel diameter 780 mm


Number of blades 66 Ht = Total pressure
PD (kgxm )
2 2
18
Peripheral velocity n x 0.0407 m/s
Hst = Statics pressure
Blade surface 0.813 m2
Max. allowable fan I class II class
RPM 600 800 Hd =Dynamics pressure
Max. installed power I class II class
(metric H.P.) TA-R: 20 30
2TA-R: 30 40 Ht = Hst + Hd

t = Total efficiency Revolutions per minute


Fan net weight TA-R: 215kg Brake horsepower - metric H.P.
2TA-R: 395kg Noise level dBA
AIR HANDLING UNIT - Sections dimensions and Weight

Fresh
air intake Mixing Droplet
with louver Mixing and Panel Bag Coil Electric eliminator
and damper box exhaust box filter filter heater and humidifier

L1 L2 L3 L4 L5 L6 L7 L8 L9

Width Hight L1 L2 L3 L4 L5 L6 L7
1:4R 5:6R 7:8R
Unit Size B C Length Weight Length Weight Length Weight Length Weight Length Weight Length Weight Length Weight Length Weight Length Weight

CS - 14 720 x 550 100 24 350 28 750 50 240 7 650 22 350 23 450 28 550 34 300
CS - 17 720 x 610 100 27 350 31 750 54 240 9 650 29 350 26 450 31 550 39 300
CS - 21 800 x 800 100 30 350 38 750 62 240 10 650 33 350 31 450 38 550 46 300
CS - 26 800 x 800 100 33 350 40 950 67 240 12 650 39 350 37 450 44 550 54 300
CS - 32 900 x 850 100 40 350 50 950 80 240 13 650 43 350 46 450 53 550 64 300
CS - 40 1000 x 850 100 44 350 55 950 89 240 15 650 49 350 53 450 64 550 80 300
CS - 49 1120 x 850 100 48 350 61 1050 98 240 17 650 55 350 61 450 75 550 90 300

2 kw = kg
CS - 60 1280 x 1060 100 58 350 70 1050 110 240 20 650 65 350 70 450 85 550 105 300
CS - 73 1280 x 1120 150 62 350 75 1050 120 250 22 650 71 350 81 450 100 550 125 300
CS - 90 1400 x 1240 150 70 350 90 1250 150 250 25 650 80 350 88 450 110 550 140 300
CS - 110 1520 x 1420 150 78 350 105 1250 180 250 28 650 89 350 98 450 125 550 155 300
CS - 135 1600 x 1480 150 92 350 125 1450 210 250 32 650 100 350 110 450 137 550 177 300
CS - 165 1700 x 1480 150 110 350 145 1450 240 250 36 650 112 350 132 450 165 550 200 300
CS - 200 1960 x 1600 150 150 350 160 1650 270 250 42 650 135 350 153 450 192 550 240 300
CS - 250 2240 x 1660 500 190 450 185 1650 400 250 49 650 160 350 200 450 230 550 270 300
CS - 300 2400 x 1840 500 230 550 275 1850 435 250 58 650 180 350 215 450 265 550 320 300
CS - 370 2600 x 2020 500 270 650 350 2000 525 250 70 650 220 350 250 450 320 550 400 300
CS - 450 3340 x 1940 700 310 650 410 2300 640 270 82 650 260 350 274 450 350 550 450 300
CS - 550 3550 x 2180 700 360 650 500 2300 750 270 95 650 300 350 332 450 425 550 560 300
CS - 680 4020 x 2300 700 420 650 630 2300 900 270 110 650 345 350 423 450 540 550 675 300
CS - 830 4380 x 2540 700 500 650 780 2900 1080 270 130 650 410 350 520 450 670 550 800 300
Absolute Sound Supply
filter Multizone attenuator air plenum

Fan

B1
L101 L102 L11 L12 L13 L14

L8 L9 L 10 1 L 10 2 L 11 L 12 B1 L 13 L 14
50 % 75 % 92 %
Length Weight Length Weight Length Weight Length Weight Length Weight Length Weight Length Weight Length Hight Weight Length Weight

200 18 800 51 1250 110 1650 135 800 47 800 47 1050 75 1000 800 - 700 35
200 20 800 58 1250 122 1650 150 900 52 900 52 1050 80 1000 900 - 700 40
200 22 800 63 1250 135 1650 162 900 56 900 56 1050 85 1100 900 - 700 45
200 25 800 70 1250 150 1650 177 900 60 900 60 1050 100 1100 1100 - 700 48
200 28 800 80 1250 170 1650 200 1000 70 1000 70 1050 110 1200 1100 - Length as required 700 50
200 32 800 92 1250 185 1650 220 1100 80 1150 80 1150 130 1200 1200 170 900 65
200 37 800 116 1250 225 1650 265 1100 97 1150 97 1150 135 1350 1200 200 900 70
200 44 800 120 1250 250 1650 290 1100 110 1150 110 1150 180 1350 1200 225 900 80
200 51 800 135 1250 280 1650 315 1250 122 1300 122 1150 180 1500 1400 250 900 80
200 57 800 145 1250 295 1650 350 1250 160 1300 160 1200 200 1500 1500 300 900 95
200 62 800 157 1250 325 1650 390 1400 205 1500 205 1200 240 1650 1600 330 900 110
200 70 800 178 1250 370 1650 435 1400 237 1500 237 1200 250 1650 1800 365 900 120
200 78 800 208 1250 425 1650 485 1600 318 1700 318 1300 270 1900 1900 400 900 120
200 95 800 235 1250 480 1650 540 1750 395 1850 395 1300 310 1900 2000 445 900 130
200 110 800 280 1250 600 1650 700 1900 440 2150 440 1300 320 2200 2000 485 900 135
200 130 800 320 1250 750 1650 850 2050 540 2350 540 1500 400 2350 2200 530 1200 180
200 152 800 380 1250 820 1650 960 2150 660 2400 660 1500 450 2500 2600 595 1200 200
200 170 800 440 1250 950 1650 1100 2200 800 2400 800 1600 510 2700 2400 680 1200 220
200 210 800 520 1250 1100 1650 1250 1850 910 2000 910 1600 550 2900 2600 790 1200 230
200 260 800 610 1250 1450 1650 1450 2050 1100 2150 1100 1600 625 3100 2700 935 1200 290
200 300 800 700 1250 1700 1650 1700 2150 1300 2400 1300 1600 760 3300 3000 1075 1200 310
AIR HANDLING UNIT
Installation, Operation & Maintenance Instructions

Installation of Air Handling Unit: The transmission of vibrations through the water
system should be avoided as it causes work
Units do not present particular difficulties of hardening of the copper pipe and subsequent failure.
installation and we believe that the following Drain pipe work should be trapped/siphoned .
information is sufficient.
In humidification system with a pump, check:
Positioning Pump rotation direction
Client base/foundations must be even and leveled Water level in the pan
to avoid tension on the panels and frames when Water filters position
coupling sections together . Pan tightness which could have suffered during
transportation
Normally it is not necessary to use vibration Check humidification operation and water tightness
isolators exterior to the unit. of the whole unit when running.
However, if a particular problem arises, we The electric supply to fan motor must be in accordance
recommend client consults an anti-vibration with local regulations.
specialist . In this
instance, it is necessary to provide all water During fan starting, it is necessary to check :
pipe connections with proper flexible joints and to That the fan rotates freely in the correct direction
use flexible connections on air inlets and outlets. and the locking devices which were fitted as
It is important to ensure that the position for the protection during transportation have been
(AHU) permits easy service and sufficient room for removed .
component replacement . The whole fan section, for any damage which may
have occurred during transportation and which
Air duct connections could cause unnecessary vibration or unit failure.
It is important to ensure that any flexible joint can Do not keep the inspection door open when fan is
operate effectively after connecting the unit to the in operation, as this will cause motor overload.
ductwork. Measure the power absorbed by the motor which
should normally be designed for approximately 80%
Coil water connections of the motor rating .
Coil must be connected with the heating or cooling
water flowing counter to the treated air . Assembly of absolute filters and active carbon
The water inlet is to be piped up to the bottom cells
connection and the water outlet to the top It is advisable to assemble the filter cells after the
connection. (AHU) has been running for several hours.
The other two outlets must be closed as shown in By doing this, the ducts are clean from dust and
figure. debris accumulated during installation.
Only after several hours of operation, should absolute
or active carbon filter cells be installed.

AIR
FLOW

As for the steam and direct expansion coils, the


instructions on the data plates are to be followed.
An air vent should be installed in the pipework to
each water coil .
When tightening coil connections, ensure that the coil
pipe is held rigid, thus avoiding damage to header .
Handling for transportation Maintenance Instructions
1) Units which are provided with support feet : Normal Maintenance
Unit handling can be effected by fork lift truck or 1 Mixing Box Air Dampers: It is recommended
ropes as shown in figure that the drive levers are cleaned and greased
annually.
2 Air filters: To be checked and replaced
periodically according to the dust content of the
air .
3 Metal Filter Cell: To be cleaned with hot water
and cleansing agents, or with a caustic soda bath.
It will be necessary to spray the cells with mineral
oil to ensure efficient operation .
4 Washable Synthetic Material Cells: These filter
cells may be cleaned as follows:
- By simple shaking
- By vacuum cleaner, in this case it is more
effective if the suction device is positioned on
the air inlet side.
- By water spray, (avoiding strong pressure jets)
2) Units which are provided with a profile base in and spraying from the air inlet side.
which there are holes for hooks to take tubes or - By water spray, (avoiding strong pressure jets)
lifting ropes are handled as shown in figure . and spraying from the air inlet side.
5 Auto Roll and Bag Filters: Follow specific
factory maintenance instructions
6 Absolute Filters: Check cells are correctly
assembled on frame and airtight.
The cells are not washable.
Follow factory service instructions.
7 Air treatment Coils: It is advisable to purge the
pipe of air occasionally. To avoid fouling, it is
advisable to clean each coil with water jets at the
beginning of summer and winter seasons.
If this proves insufficient we suggest the use of a
brush or a proprietary brand of chemical agent to
be applied as instructed .
8 Humidification Section: With pump and spray
header we recommend every month :
- To clean the nozzles and check that the spray
forms a regular cone .
- To clean the copper/stainless steel mesh water
filter with a brush .
- To clean the pan from slimy impurities using
water jet and brush every six months .

Evaporating package when cleaning, the following


instructions apply :
- Stop the pump, shut the check valve and wait
for the air flow to dry the evaporating package.
- To remove slimy deposits wash down the
package with water.
- Take off and clean the water filter with a
common brush.
- Wash the pan and overflow pipe.
AIR HANDLING UNIT
Installation, Operation & Maintenance Instructions

9 Fan section: 10 Motor


Warning: Before opening the fan motor assembly - Ambient temperature, changing with
make sure that the main power switch has been seasons but not exceeding 40 degrees
isolated centigrade.
- Voltage, 220/380 V, 380/660 V
Check belt drive tension after the first week of - Check if the data on the name-plate
operation and adjust if necessary as follows : the requirements.
- Loosen the electric motor from the main base. - Motor should be earthed properly. There
- Move the motor until the belt tension can be is an earthing device at the low right part
seen to give about 2 cm deflection between the of the terminal box
two pulleys . - There are 6 terminals on the terminal
Excessive tension of the belts causes damage plate marked with : U1, V1, W1, U2, V2,
to the bearings. W2 respectively. Connection should be
- Check that the fan and motor shafts are parallel done according to the diagram on the
and the pulleys are correctly aligned. name-plate .
- Fans provided with open bearing housing need When power phase sequences A, B, C are
to be lubricated periodically. corresponding to mounting marks of U1,
- Check that all fixing screws are correctly tight V1, W1 respectively, looking from the end
after first week of operations, retighten if of the main shaft, the rotating of motor is
necessary and to be checked periodically each regarded as clockwise.
month . If changing the phase sequence, the
rotation of the motor is counter to its
original one. Check motor rotation before
test-run.
- Abnormal sound or vibration should not
occur during operation. The temperature
of bearings should not exceed 95 degrees
centigrade.

11 Various checks
Check for air leaks from panels and
inspection doors.
Check the condition of the electric cables.

12 Safety provisions
All the units are provided with the following
safety devices:
Fan access door with locking handles.
Upon request belt guard for fan/motor
drive protection.
Sheet of
A.H.U ORDER FORM QU. No.
CUSTOMER QTY.
MODEL CS UNIT No.
FINISH
External Plastified Galvanized
Internal Plastified Galvanized
INSULATION
Double skin Insulated single skin
Uninsulated single skin Thickness (mm)

SUPPLY FAN
Capacity (mt3/hr) Internal Static Pressure (Pa)
External Static Pressure (Pa)
Air Orientation A B C D E F Inspection Door R L
RETURN FAN
Capacity (mt3/hr) Internal Static Pressure (Pa)
Inspection Door R L External Static Pressure (Pa)
COOLING COIL SECTION
Chilled Water Direct Expansion
Load (B.T.U/KW) Header Side R L
Air Side
Entering Temp. (DB) (F/C) Leaving Temp. (DB) (F/C)
Ent. Relative Humidity (%) Leav. Relative Humidity (%)
Air pressure Drop (in. wg./Pa)
Water Side
Water Flow (GPM - L/S) W. Press. Drop (in. wg./Pa)
Entering W. Temp. (F/C) Leaving W. Temp. (F/C)
Refrigerant side
Suction Temp. (F/C)
HEATING SECTION
Hot Water Steam Electric Heater
Hot Water Coil
Load (B.T.U./K.Cal.) Header side R L
Entering Air Temp. (DB) (F/C) Leav. Air Temp. (DB) (F/C)
Water Flow (GPM - L/S)
Entering W. Temp. (F/C) Leaving W. Temp.
Steam
Load (B.T.U./K.Cal.) Header side R L
Entering Air Temp. (DB) (F/C) Leav. Air Temp. (DB) (F/C)
Electric Heater
Capacity (KW) No. of steps
Voltage (volt) No. of phase

HUMIDIFICATION SECTION
Water (Lit./hr) Relative Humidity

FILTER SECTION
Pre-Filter Bag Filter Absolute Filter
efficiency (%) Efficiency (%) Efficiency (%)
SOUND ATTENUATORS SECTION
Supply S.A.
Insertion Loss (db) at 250 Hz Max Pressure Drop (Pa)
Return S.A.
Insertion, Loss (db) at 250 Hz Max Pressure Drop (Pa)

ADDITIONAL SECTIONS