SPECIFICATION & DATASHEET JINDAL INDIA THERMAL POWER LIMITED

FOR 400kV CIRCUIT BREAKER (2 x 600MW THERMAL POWER PROJECT)

SPECIFICATION & DATASHEET FOR 400kV CIRCUIT BREAKER

Index of Revisions

4 01.07.2011 GDP KSH KSH Revised as per JITPL/TCE Comments


3 23.06.2011 KSH KSH RGK Revised as per JITPL/TCE Comments
2 20.01.2011 KSH KSH RGK Revised as per JITPL/TCE Comments
1 17.01.2011 KSH KSH RGK Revised as per JITPL/TCE Comments
Rev. Date Prepared Checked Approved Details of Revision

Owner
JINDAL INDIA THERMAL POWER LIMITED
Project
2 x 600 MW THERMAL POWER PROJECT

Consultant
TATA CONSULTING ENGINEERS
Coord. by 07.12.2010 KSH Document Number
Checked by 07.12.2010 KSH SIEM-JITPL.5404A-EL-4-2051 Siemens Limited,
Aurangabad.
Dept. Revision Version
Approved by 07.12.2010 KSH
EFIF 0 0

DOC. No. - SIEM-JITPL.5404A-EL-4-2051 Rev 4 Ver 0 Date 01.07.2011 Page 1of 9


Project JINDAL INDIA THERMAL POWER LIMITED
SD Consultant TATA CONSULTING ENGINEERS
(2 x 600 MW THERMAL POWER PROJECT)
SPECIFICATION & DATASHEET JINDAL INDIA THERMAL POWER LIMITED
FOR 400kV CIRCUIT BREAKER (2 x 600MW THERMAL POWER PROJECT)

Clause Title

1.0 Datasheet

DOC. No. - SIEM-JITPL.5404A-EL-4-2051 Rev 4 Ver 0 Date 01.07.2011 Page 2 of 9


Project JINDAL INDIA THERMAL POWER LIMITED
SD Consultant TATA CONSULTING ENGINEERS
(2 x 600 MW THERMAL POWER PROJECT)
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers

Guaranteed Technical Particulars

Product :- 420kV, 3150A, 50kA SF6 Circuit Breaker

Sr. No. Particulars Guaranteed Values

1 Name of manufacturer Siemens Ltd


2 Type of Circuit Breaker Outdoor type, Live tank SF6
3 Manufacturer's type and designation 3AP2 FI
4 Standard applicable IEC 62271-100, 60694
5 Rated voltage 420kV
6 Rated frequency 50Hz
7 Normal current rating under site
conditions of 50 deg. C ambient air
temperature
a Under standard conditions 3150A
b Under site conditions. 3150A
8 Altitude of installation above sea level Max 1000 m
9 Seismic withstand 0.5g
10 No. of poles of circuit breaker Three
11 Temperature rise in current carrying parts Within limits specified by IEC
at rated current and the maximum 62271-100
temperature attained by any part over an
ambient of 50 deg. C
12 Breaking capacity
a Symmetrical 50kA
b Asymmetrical 58.5kA
13 Percentage D.C. component 50%
14 Rated short-circuit making current 125 kAp
15 Rated small inductive breaking current 0 25 Amp (Magnetizing
Current of No-Load Transformer)
16 a Rated transient recovery voltage for short 480kVp
line faults kVp
b Rate of rise of recovery voltage for short 2.00
line faults (kV/microsec)
17 a Rated transient recovery voltage for 624kVp
terminal faults kVp
b Rate of rise of recovery voltage for terminal 2
faults (kV/microsec)
c First pole to clear factor 1.3
18 a Rated out of phase (asynchronous) 12.5kA
breaking current
b Rated transient recovery voltage for out of 857kVp
phase kVp
19 Type of devices, if any, used to limit the Not required
RRRV
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers

Guaranteed Technical Particulars

20 Maximum over voltage on switching Test not specified as per IEC


transformer on no load and corresponding 61233 clause 2.2, However,
charging current. breaker is suitable for this
application (value 0-25 A, 2.5
pu)
21 Reactor loaded transformer interrupting >=30 A/<=2.0 p.u. ; >=100
capacity and corresponding surge OV A/<=1.5 p.u.
22 Number of breaks in series per pole. Two
23 Rated operating sequence O-0.3 sec-CO-3 min-CO
24 Short time current rating for following
duration :
a For one sec. 50 kA
b For three sec. 50 kA
25 a Opening time 28 +/- 3 m sec
b Normal voltage of opening 220V DC
c Voltage range (%) 70 - 110%
26 a Closing or make time 65 +/- 6 m sec
b Normal voltage of closing 220V DC
c Voltage range (%) 85 - 110%
27 Difference in the instant of closing of <=3 ms
contacts between poles
28 Difference in the instant of opening of <=2 ms
contacts between poles
29 Total break time in milli second : Max. 60 msec
30 Maximum arcing time in any test duties 25 m sec
31 Is the breaker suitable for single phase / 3 1 Phase and 3 Phase auto
phase reclosing reclosing, Electrically Gang
operated
32 Minimum dead time for :
a 3 phase reclosing 300 m sec
b Single phase reclosing 300 m sec
c Limits of adjustment of dead time for 3 Not applicable
phase closing
d Limits of adjustment of dead time for 1 Not applicable
phase closing
33 CAPACITY
Data on transient recovery voltage : 100% 60% 30% 10%
a Amplitude factor 1.4 1.5 1.54 1.53
b First pole to clear factor 1.3 1.3 1.3 1.5
c Natural frequency As per IEC 62271-100
d Rate of rise of recovery voltage kV/sec. 2.0 3.0 5.0 7.0
34 Maximum line charging breaking current 600A
35 Maximum Cable charging breaking 400A
current
36 Maximum single Capacitor bank charging 400A
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers

Guaranteed Technical Particulars

breaking current
37 a Rated back to back capacitor bank Not applicable
breaking current
b Rated capacitor bank inrush making Not applicable
current
38 Maximum breaking capacity under L75 = 37.5kA, L90 = 45kA
Kilometric faults & rated TRV Rated TRV - 480kVp
Characteristic
39 Dry one minute power frequency
withstand test voltage for complete circuit
breaker :
a Between terminals with circuit breaker 610
contacts open (kVrms) (0.55 X 610kV across each
break)
b Phase to earth & between phases (kVrms) 520
40 1.2/50 full wave impulse withstand
voltage for complete circuit breaker
a Between terminals with circuit breaker 1425 (+240)
contacts open.(kVp)
b Phase to earth & between phases (kVp) 1425
41 250/2500 micro second switching surge
withstand test voltage
a Between phase to earth (KVp) 1050
b Between phases (KVp) 1050
c Across isolating distance (kVp) Not applicable
42 a Radio Interference Voltage (Micro-Volts) < 1000
b Corona Extinction voltage (kV) > 320 kVrms
43 a Total length of break per phase / arc 140.5 mm
length (Distance between pin and tube
contact)
b Total length of contact travel 150 mm

SF6 gas and related devices details :


44 Standard to which SF6 gas complies. IEC 60376
45 Quantity of SF6 gas per breaker 39 Kg
46 Quantity of SF6 per pole (m3) at rated 13 Kg
pressure.
47 Whether breakers are dispatched filled
Gas filling at site, Gas filling
with SF6 or required to be filled at site.
device will be supplied along
with spares.
48 Guaranteed maximum leakage rate per < 1% pa
year.
49 Rated pressure of SF6 in operating 6.0 Bar @ 20 Deg C
chamber
50 Rated alarm pressure of SF6 5.2 Bar @ 20 Deg C
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers

Guaranteed Technical Particulars

51 Limits of pressure at which breaker 5.0 Bar @ 20 Deg C


operate correctly or Lockout pressure
52 Whether 20% spare SF6 gas. Stored in Yes
unused gas cylinders, included in
proposal.

General
53 Minimum clearances in air
a Between phases 6525 mm
b Live part and earth 3400 mm
c Lowest line terminal to ground 8000 mm
54 Normal pressure of SF6 gas inside circuit 6.0 bar at 20 deg c
breaker
55 Minimum operating pressure of SF6 gas above 5.0 bar at 20 degc
56 a Density monitor Settings (Adjustable / Non adjustable
Non adjustable)
b Voltage and power supply system for As per control supply voltage
which the temp. compensating gas
pressure switch (density monitor) and
other pressure switches are suitable
57 Pressure at which gas pressure will give :
a Alarm 5.2 bar at 20 deg C
b Tripping impulse At 5.0 bar at 20 degC if
specified by the client
c Lockout 5.0 bar at 20 deg C
58 Minimum time interval between each As per operating sequence O-
make/break operation (ms) 0.3 Sec.-CO-3 min.-CO
59 Maximum pressure of SF6 gas developed Within safe limits
in the arcing chamber at rated breaking
capacity (kg/sq.cm)
60 Chemical composition of the absorbent MOS 13X
61 Recommended interval for renewal of 6000 Nos. operations
absorbent for circuit breakers operating in
tropical condition.
62 No. of operations breaker is capable of 6000 Nos. operations
performing without inspection,
replacement of contacts and other main
parts with normal current breaking
63 No. of operations breaker is capable of 18 operations
performing without inspection,
replacement of fault current breaking
capacity
64 No. of operation at rated current after 50 kA
which routine inspection of breaker is
necessary contacts and other main parts
at 100% rated Guaranteed no. of opening
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers

Guaranteed Technical Particulars

operation, the Breaker is capable of


performing

a At full rupturing capacity 18


b At 50% rated rupturing capacity 90
c At 100% rated current 6000
d At 50% rated current 6000
e No. of no load (mechanical) operations 10000
65 a Weight of complete breakers 5400 Kg approx, Without
support structure
b Weight of heaviest part of breaker (kg) 1350 Kg approx.
66 Static loading of the circuit breaker Static horizontal force
Horizontally: - 1750N.
Transversal:-1250N.
67 Shipping dimension of the largest package Please refer enclosed
in mm instruction manual.

Breaker Contacts :
68 Type of main contacts Contact Multilam, Multilam,
Heat Cylinder
69 Type of arcing contacts Pin, Finger contact
70 Whether main contacts silver plated Yes
71 Thickness of silver plating Adequate
72 Material of contact Main contact Copper
Chromium Alloy.
Arcing contact Copper
tungsten alloy.
73 Contact pressure As per Design requirement
74 Auxiliary contact :
a Type of auxiliary contact Rotary
b Material of auxiliary contact Silver Plated Brass
c Contact silver plated or not Yes
d Thickness of silver plating Sufficient
75 No. of auxiliary switch / multiplied
contacts, operating with all individual
poles of a breaker
a which are closed when breaker is closed 20
b which are open when breaker is closed 19
76 No. of spare auxiliary contacts wired up to
the terminals
a Opening 6
b Closing 6
c Those adjustable with respect to position Auxiliary switch is rotary type
of main contact and all above contacts are pre-
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers

Guaranteed Technical Particulars

adjusted in the factory.

d Continuous rating of contacts 10 A


e Breaking capacity of contacts 220V DC -2.0 A (Resistive-
Inductive load); 110V DC -
4.0A (Resistive-Inductive load)
77 Type of operating mechanism
a Opening Spring
b Closing Spring
c Numbers of drive mechanisms Three
d Whether the circuit breaker is trip free of Trip free
fixed trip and whether it is with lockout
preventing closing
e Tripping and closing control circuit voltage 110V DC or 220V DC
f No. of trip coils Two nos. per pole
g No. of close coils One no. per pole
h Power required for trip coil at 110/220V 1300 W
DC
i Power required for closing coil at 300 W
110/220V DC
78 For stored energy mechanism
Spring charging motor:
a Manufacturer's name & address KPT/Agni/Equivalent ( as per
approved vendor list)
b Equipment driven by the motor Closing spring
c Motor type Universal
d Type of duty Short time duty
e Applicable standard IS 996
f Power required for motor 1000 Watts
g Rated voltage 220V DC / 240V AC
h Motor current
i) Starting current 23.5 +/- 3
ii) Continuous current 8.5 +/- 1.5
i Time required for the motor to charge the 15 sec. Max
spring fully (sec.)

79 Circuit Breaker - Control cabinate


a Manufacturer's Name Siemens Ltd
b Indoor/Outdoor application Outdoor
c Ambient air temperature (oC) As per IEC 62271-100
d Thickness of sheet steel (mm) CR 2.0
e Degree of protection provided IP 55

80 Bushing or insulator :
a Make of insulator Aditya Birla / Modern /
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers

Guaranteed Technical Particulars

Insulators & Electricals


Company
b Type Hollow porcelain
c Applicable standards IEC 60233
d Dimension Chamber - 4380 mm; Support
- 3840 mm
e Numbers of support insulators Three
f Creepage distance
-Interrupter Chamber 13020 mm
-Support Insulator 13020 mm
g Rated voltage (kV) 420kV
h Power frequency withstand voltage for 1 520 kVrms
minute (kVrms) dry and wet
i 1.2/50 micro sec. impulse withstand Part of CB
voltage (kVp)
j 250/2500 micro sec. switching impulse Part of CB
withstand voltage (kV p) dry and wet
k Corona Extinction voltage (kV) > 320 kVrms (Part of CB)
l Insulation class. C - 120