DIAGRAMS 7
Contents
2TJM10 2TJM10
EF
9 10 1 2
P1
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1
A B C (2) (4)
transformers
S2 S2 S2
P2
2TJM10 2TJM10
OC A
5 6 1 2
IDMT O/C
(23) (24) (1) (3)
EF 3 4
8 7 IDMT O/C & EF
(2) (4)
EF
(26) (25) 11 12
OC IDMT EF
9 10 (5) (7)
Line current P1
transformers (27) (28)
S1 S1 S1 case earth C
A B C
S2 S2 S2
P2
Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.
1
7 DIAGRAMS
2TJM11 2TJM11
IDMT Inst
EF EF IDMT
9 10 1 2
P1 IDMT & Inst
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1 IDMT & Inst
A B C (2) (4)
transformers Inst
S2 S2 S2
P2
2TJM11 2TJM11
IDMT Inst
OC OC A-IDMT
5 6 1 2
IDMT & Inst O/C
(23) (24) (1) (3)
IDMT Inst
EF EF 3 4
8 7 IDMT O/C & EF
(2) (4)
A-Inst
(26) IDMT Inst (25)
9 OC OC 10
P1
(27) (28)
Line current case earth
transformers S1 S1 S1 C-IDMT
A B C
S2 S2 S2
P2
C-Inst
EF-IDMT
11 12
IDMT & Inst EF
(5) (7)
EF-Inst
Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.
Figure 4 2TJM11 IDMT and Instantaneous Overcurrent and Earth Fault Protection
2
DIAGRAMS 7
OC OC OC
10 9 10 9 10 9
5 6 5 6 5 6
P1
Line current
S1 S1 S1 case earth case earth case earth
transformers
A B C
S2 S2 S2
P2
C Phase B
Rotation Voltage Transformer
A
A A A
1 2 1 2 1 2
3 4 3 4 3 4
Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.
3
7 DIAGRAMS
OC OC OC
10 9 10 9 10 9
5 6 5 6 5 6
P1
Line current
S1 S1 S1 case earth case earth case earth
transformers
A B C
S2 S2 S2
P2
C Phase B
Rotation Voltage Transformer
A
VL Vn
Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.
Figure 6 2TJM12 showing Directional Earth Fault 12.5 Lagging Power Factor
and Directional Overcurrent (with 90 connection, 0 power factor)
4
DIAGRAMS 7
2TJM20 2TJM20
EF
9 10 1 2
P1
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1
A B C (2) (4)
transformers
S2 S2 S2
P2
2TJM21 2TJM21
IDMT Inst
EF EF IDMT
9 10 1 2
P1 IDMT & Inst
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1 IDMT & Inst
A B C (2) (4)
transformers Inst
S2 S2 S2
P2
2TJM21 2TJM21
IDMT Inst
OC OC A-IDMT
5 6 1 2
IDMT & Inst O/C
(23) (24) (1) (3)
IDMT Inst
EF EF 3 4 IDMT & Inst
8 7 O/C & EF
(2) (4)
A-Inst
(26) IDMT Inst (25)
9 OC OC 10
P1
(27) (28)
Line current case earth
transformers S1 S1 S1 C-IDMT
A B C
S2 S2 S2
P2
C-Inst
EF-IDMT
11 12
IDMT & Inst EF
(5) (7)
Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing. EF-Inst
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.
Figure 9 2TJM21 IDMT and Instantaneous Overcurrent and Earth Fault Protection
5
7 DIAGRAMS
P2 Note:
Circuit breaker trip coil circuit must
be connected to terminals 1 and 2
9 OC OC 10
P1 OC
(27) (28)
Line current case earth
S1 S1 S1 EF
transformers
A B C Inst
S2 S2 S2
OC
P2
3 4
IDMT & Inst O/C & EF
(2) (4)
OC-Inst
11 12
Inst O/C & EF
(5) (7)
EF-Inst
Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets) OC-Inst
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.
Figure 12 2TJM31 IDMT and Instantaneous Overcurrent and Earth Fault Protection
6
DIAGRAMS 7
P2 Note:
Reed relay must be connected in series
with circuit breaker trip coil.
Figure 13 2TJM60 IDMT Earth Fault Protection, with Series Operated Reed Relay
2TJM60
OC MCAA2
2 1
-
(13) (14)
Circuit Breaker
Trip
3 4 Coil
+ -
(1) (3)
5 6
(2) (4)
Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.
Figure 14 Alternative Connections for Fig.13 with Internal MCAA Repeat Relay