Professional Documents
Culture Documents
Manual
Absolute Pressure and
Gauge Pressure Transmitters
EJ510, EJ530,
EJX610A and EJX630A
IM 01C25F01-01E
IM 01C25F01-01E
13th Edition
i
Contents
1. Introduction................................................................................................ 1-1
Regarding This Manual................................................................................................. 1-1
Trademarks ................................................................................................................... 1-2
1.1 Safe Use of This Product ................................................................................. 1-2
1.2 Warranty.............................................................................................................. 1-3
1.3 ATEX Documentation........................................................................................ 1-4
2. Handling Cautions..................................................................................... 2-1
2.1 Model and Specifications Check...................................................................... 2-1
2.2 Unpacking........................................................................................................... 2-1
2.3 Storage................................................................................................................ 2-1
2.4 Selecting the Installation Location ................................................................. 2-1
2.5 Pressure Connection......................................................................................... 2-2
2.6 Waterproofing of Cable Conduit Connections............................................... 2-2
2.7 Restrictions on Use of Radio Transceivers.................................................... 2-2
2.8 Insulation Resistance and Dielectric Strength Test....................................... 2-2
2.9 Installation of an Explosion-Protected Instrument........................................ 2-3
2.9.1 FM Approval........................................................................................ 2-4
2.9.2 CSA Certification................................................................................. 2-6
2.9.3 ATEX Certification............................................................................... 2-8
2.9.4 IECEx Certification............................................................................ 2-12
2.10 EMC Conformity Standards............................................................................ 2-15
2.11 Pressure Equipment Directive (PED)............................................................ 2-16
2.12 Safety Requirement Standards...................................................................... 2-16
3. Component Names................................................................................... 3-1
4. Installation.................................................................................................. 4-1
4.1 Precautions ....................................................................................................... 4-1
4.2 Mounting ............................................................................................................ 4-1
4.3 Rotating Transmitter Section............................................................................ 4-2
4.4 Changing the Direction of Integral Indicator ................................................. 4-2
IM 01C25F01-01E
iii
8. Maintenance............................................................................................... 8-1
8.1 Overview............................................................................................................. 8-1
8.2 Calibration Instruments Selection................................................................... 8-1
8.3 Calibration.......................................................................................................... 8-1
8.4 Disassembly and Reassembly......................................................................... 8-3
8.4.1 Replacing the Integral Indicator.......................................................... 8-3
8.4.2 Replacing the CPU Board Assembly.................................................. 8-4
8.4.3 Cleaning and Replacing the Capsule Assembly...........................8-4
8.5 Troubleshooting................................................................................................. 8-5
8.5.1 Basic Troubleshooting........................................................................ 8-6
8.5.2 Troubleshooting Flowcharts................................................................ 8-6
8.5.3 Alarms and Countermeasures............................................................ 8-8
9. General Specifications............................................................................. 9-1
9.1 Standard Specifications.................................................................................... 9-1
9.2 Model and Suffix Codes.................................................................................... 9-5
9.3 Optional Specifications .............................................................................. 9-8
9.4 Dimensions....................................................................................................... 9-10
Revision Information
IM 01C25F01-01E
<1. Introduction> 1-1
1. Introduction
Thank you for purchasing the DPharp EJX and EJA
Differential Pressure and pressure transmitter. NOTE
Your transmitter was precisely calibrated at the Unless otherwise stated, the illustrations in this
factory before shipment. To ensure both safety and manual are of the EJ530 gauge pressure
efficiency, please read this manual carefully before transmitter.
you operate the instrument. Users of the EJ510, EJX610A and EJX630A
should bear in mind that certain features of their
NOTE instrument will differ from those shown in the
illustrations of the EJ530.
This manual describes the hardware
configurations of the transmitters listed in below.
For information on the software configuration
and operation, please refer to either
Regarding This Manual
IM 01C25T03-01E for the BRAIN communication This manual should be provided to the end
type, or IM 01C25T01-06EN for the HART user.
communication type. The contents of this manual are subject to
For FOUNDATION Fieldbus protocol type, please change without prior notice.
refer to IM 01C25T02-01E. All rights reserved. No part of this manual may
For PROFIBUS PA protocol type, please refer to be reproduced in any form without Yokogawas
IM 01C25T04-01EN. written permission.
Model Style code Yokogawa makes no warranty of any kind with
EJX510A S2 regard to this manual, including, but not limited
EJX530A S2 to, implied warranty of merchantability and
EJX610A S1 fitness for a particular purpose.
EJX630A S1
EJA510E S1 If any question arises or errors are found, or if
EJA530E S1 any information is missing from this manual,
please inform the nearest Yokogawa sales
To ensure correct use of this instrument, read office.
both the hardware and software manuals
The specifications covered by this manual are
thoroughly before use.
limited to those for the standard type under the
specified model number break-down and do not
cover custom-made instruments.
WARNING
Please note that changes in the specifications,
When using the transmitters in a Safety construction, or component parts of the
Instrumented Systems (SIS) application, refer instrument may not immediately be reflected
to Appendix 1 in either IM 01C25T01-06EN for in this manual at the time of change, provided
the HART protocol or IM 01C25T03-01E for the that postponement of revisions will not cause
BRAIN protocol. The instructions and procedures difficulty to the user from a functional or
in this section must be strictly followed in order to performance standpoint.
maintain the transmitter for this safety level. Yokogawa assumes no responsibility for this
product except as stated in the warranty.
If the customer or any third party is harmed by
NOTE the use of this product, Yokogawa assumes
no responsibility for any such harm owing to
When describing the model name like EJ510
any defects in the product which were not
or EJ530, it shows the applicability for
predictable, or for any indirect damages.
both EJX510A and EJA510E or EJX530A and
EJA530E.
IM 01C25F01-01E
<1. Introduction> 1-2
The following safety symbols are used in this 1.1 Safe Use of This Product
manual:
For the safety of the operator and to protect the
instrument and the system, please be sure to follow
this manuals safety instructions when handling this
WARNING instrument. If these instructions are not heeded,
Indicates a potentially hazardous situation which, the protection provided by this instrument may be
if not avoided, could result in death or serious impaired. In this case, Yokogawa cannot guarantee
injury. that the instrument can be safely operated. Please
pay special attention to the following points:
(a) Installation
CAUTION This instrument may only be installed by an
Indicates a potentially hazardous situation which, engineer or technician who has an expert
if not avoided, may result in minor or moderate knowledge of this device. Operators are not
injury. It may also be used to alert against unsafe allowed to carry out installation unless they
practices. meet this condition.
With high process temperatures, care must
be taken not to burn yourself by touching the
IMPORTANT instrument or its casing.
Indicates that operating the hardware or software Never loosen the process connector nuts when
in this manner may damage it or lead to system the instrument is installed in a process. This can
failure. lead to a sudden, explosive release of process
fluids.
When draining condensate from the pressure
NOTE detector section, take appropriate precautions
to prevent the inhalation of harmful vapors and
Draws attention to information essential for
the contact of toxic process fluids with the skin
understanding the operation and features.
or eyes.
When removing the instrument from a
Direct current hazardous process, avoid contact with the fluid
and the interior of the meter.
Functional grounding terminal
All installation shall comply with local installation
Caution requirements and the local electrical code.
This symbol indicates that the operator must
(b) Wiring
refer to an explanation in the users manual
in order to avoid the risk of injury or death of The instrument must be installed by an
personnel or damage to the instrument. engineer or technician who has an expert
knowledge of this instrument. Operators are not
permitted to carry out wiring unless they meet
Trademarks
this condition.
DPharp, EJX, EJA, FieldMate and BRAIN
Before connecting the power cables, please
TERMINAL are registered trademarks of
confirm that there is no current flowing through
Yokogawa Electric Corporation. Company
the cables and that the power supply to the
names and product names used in this material
instrument is switched off.
are registered trademarks or trademarks of their
respective owners.
In this manual, trademarks or registered
trademarks are not marked with or .
IM 01C25F01-01E
<1. Introduction> 1-3
(c) Operation 1.2 Warranty
Wait 5 min. after the power is turned off, before The warranty shall cover the period noted on
opening the covers. the quotation presented to the purchaser at the
time of purchase. Problems occurring during
(d) Maintenance
the warranty period shall basically be repaired
Please carry out only the maintenance free of charge.
procedures described in this manual. If you If any problems are experienced with this
require further assistance, please contact the instrument, the customer should contact the
nearest Yokogawa office. Yokogawa representative from which this
Care should be taken to prevent the build up of instrument was purchased or the nearest
dust or other materials on the display glass and Yokogawa office.
the name plate. To clean these surfaces, use a If a problem arises with this instrument,
soft, dry cloth. please inform us of the nature of the problem
and the circumstances under which it
(e) Explosion Protected Type Instrument
developed, including the model specification
Users of explosion proof instruments should and serial number. Any diagrams, data and
refer first to section 2.9 (Installation of an other information you can include in your
Explosion Protected Instrument) of this manual. communication will also be helpful.
The use of this instrument is restricted to those The party responsible for the cost of fixing the
who have received appropriate training in the problem shall be determined by Yokogawa
device. following an investigation conducted by
Take care not to create sparks when accessing Yokogawa.
the instrument or peripheral devices in a The purchaser shall bear the responsibility for
hazardous location. repair costs, even during the warranty period, if
the malfunction is due to:
(f) Modification
Yokogawa will not be liable for malfunctions or - Improper and/or inadequate maintenance by
damage resulting from any modification made the purchaser.
to this instrument by the customer. - Malfunction or damage due to a failure
(g) Product Disposal to handle, use, or store the instrument in
accordance with the design specifications.
The instrument should be disposed of in
- Use of the product in question in a location
accordance with local and national legislation/
not conforming to the standards specified by
regulations.
Yokogawa, or due to improper maintenance
(h) Authorized Representative in EEA of the installation location.
- Failure or damage due to modification or
In relation to the CE Marking, The
repair by any party except Yokogawa or an
authorised representative for this product
approved representative of Yokogawa.
in the EEA (European Economic Area) is:
- Malfunction or damage from improper
Yokogawa Europe B.V. Euroweg 2, 3825 HD
relocation of the product in question after
Amersfoort,The Netherlands
delivery.
- Reason of force majeure such as fires,
earthquakes, storms/floods, thunder/
lightening, or other natural disasters, or
disturbances, riots, warfare, or radioactive
contamination.
IM 01C25F01-01E
<1. Introduction> 1-4
1.3 ATEX Documentation
This is only applicable to the countries in European Union.
GB SK
CZ
DK
I LT
E LV
EST
NL
PL
SF
SLO
P
BG
RO
S
M
GR
IM 01C25F01-01E
<2. Handling Cautions> 2-1
2. Handling Cautions
This chapter provides important information on how 2.2 Unpacking
to handle the transmitter. Read this carefully before
using the transmitter. Keep the transmitter in its original packaging to
prevent it from being damaged during shipment.
The transmitters are thoroughly tested at the Do not unpack the transmitter until it reaches the
factory before shipment. When taking delivery of an installation site.
instrument, visually check them to make sure that
no damage occurred during shipment.
Also check that all transmitter mounting hardware
2.3 Storage
shown in figure 2.1 is included. If the transmitter The following precautions must be observed when
is ordered without the mounting bracket and the storing the instrument, especially for a long period.
process connector, the transmitter mounting (a) Select a storage area which meets the following
hardware will not be included. After checking the conditions:
transmitter, carefully repack it in its box and keep it It is not exposed to rain or subject to water
there until you are ready to install it. seepage/leaks.
U-bolt nut (L) Vibration and shock are kept to a minimum.
It has an ambient temperature and relative
humidity within the following ranges.
Ambient temperature:
40* to 85C without integral indicator
30* to 80C with integral indicator
* 15C when /HE is specified.
Mounting bracket
Relative humidity:
0% to 100% R.H.
Preferred temperature and humidity:
U-bolt nut (S)
approx. 25C and 65% R.H.
(b) When storing the transmitter, repack it carefully
U-bolt (S)
in the packaging that it was originally shipped
with.
U-bolt (L)
(c) If the transmitter has been used, thoroughly
F0201.ai
clean the chambers inside the cover flanges, so
Figure 2.1 Transmitter Mounting Hardware
that there is no process fluid remaining inside.
Before placing it in storage, also make sure that
the pressure-detector is securely connected to
2.1 Model and Specifications the transmitter section.
Check
The model name and specifications are written on 2.4 Selecting the Installation
the name plate attached to the case. Location
The transmitter is designed to withstand severe
environmental conditions. However, to ensure
that it will provide years of stable and accurate
performance, take the following precautions when
selecting the installation location.
F0202.ai
IM 01C25F01-01E
<2. Handling Cautions> 2-2
(a) Ambient Temperature 2.6 Waterproofing of Cable
Avoid locations subject to wide temperature
variations or a significant temperature gradient.
Conduit Connections
If the location is exposed to radiant heat from Apply a non-hardening sealant to the threads
plant equipment, provide adequate thermal to waterproof the transmitter cable conduit
insulation and/or ventilation. connections. (See figure 6.8, 6.9 and 6.10.)
(b) Ambient Atmosphere
Do not install the transmitter in a corrosive 2.7 Restrictions on Use of Radio
atmosphere. If this cannot be avoided, there
must be adequate ventilation as well as Transceivers
measures to prevent the leaking of rain water
and the presence of standing water in the IMPORTANT
conduits. Although the transmitter has been designed to
(c) Shock and Vibration resist high frequency electrical noise, if a radio
Although the transmitter is designed to be transceiver is used near the transmitter or its
relatively resistant to shock and vibration, an external wiring, the transmitter may be affected
installation site should be selected where this is by high frequency noise pickup. To test this, start
kept to a minimum. out from a distance of several meters and slowly
approach the transmitter with the transceiver
(d) Installation of Explosion-protected Transmitters
while observing the measurement loop for noise
An explosion-protected transmitters is
effects. Thereafter use the transceiver outside
certified for installation in a hazardous area
the range where the noise effects were first
containing specific gas types. See subsection
observed.
2.9 Installation of an Explosion-Protected
Transmitters.
IM 01C25F01-01E
<2. Handling Cautions> 2-3
Insulation Resistance Test 2.9 Installation of an Explosion-
1) Short-circuit the + and SUPPLY terminals Protected Instrument
in the terminal box. In case of 1 to 5 V output,
short-circuit the SUPPLY+, SUPPLY and A NOTE
(VOUT +) terminals.
2) Turn OFF the insulation tester. Then connect For FOUNDATION Fieldbus explosion protected
the insulation tester plus (+) lead wire to the type, please refer to IM 01C22T02-01E.
shorted SUPPLY terminals and the minus () For PROFIBUS PA explosion protected type,
leadwire to the grounding terminal. please refer to IM 01C25T04-01EN.
3) Turn ON the insulation tester power and
measure the insulation resistance. The voltage If a customer makes a repair or modification to
should be applied as briefly as possible to verify an intrinsically safe or explosionproof instrument
that the insulation resistance is at least 20 M. and the instrument is not restored to its original
4) After completing the test and being very careful condition, its intrinsically safe or explosionproof
not to touch exposed conductors disconnect the construction may be compromised and the
insulation tester and connect a 100 k resistor instrument may be hazardous to operate. Please
between the grounding terminal and the short- contact Yokogawa before making any repair or
circuiting SUPPLY terminals. Leave this resistor modification to an instrument.
connected at least one second to discharge any
static potential. Do not touch the terminals while CAUTION
it is discharging.
This instrument has been tested and certified
Dielectric Strength Test
as being intrinsically safe or explosionproof.
1) Short-circuit the + and SUPPLY terminals Please note that severe restrictions apply to this
in the terminal box. In case of 1 to 5 V output, instruments construction, installation, external
short-circuit the SUPPLY+, SUPPLY and A wiring, maintenance and repair. A failure to abide
(VOUT +) terminals. by these restrictions could make the instrument a
2) Turn OFF the dielectric strength tester. Then hazard to operate.
connect the tester between the shorted
SUPPLY terminals and the grounding terminal.
Be sure to connect the grounding lead of the
WARNING
dielectric strength tester to the ground terminal.
3) Set the current limit on the dielectric strength Maintaining the safety of explosionproof
tester to 10 mA, then turn ON the power and equipment requires great care during mounting,
gradually increase the test voltage from 0 to wiring, and piping. Safety requirements also
the specified voltage. place restrictions on maintenance and repair.
4) When the specified voltage is reached, hold it Please read the following sections very carefully.
for one minute.
5) After completing this test, slowly decrease the
voltage to avoid any voltage surges.
WARNING
The range setting switch must not be used in a
hazardous area.
IM 01C25F01-01E
<2. Handling Cautions> 2-4
Note 2. Entity Parameters
IMPORTANT Intrinsically Safe Apparatus Parameters
For combined approval types [Groups A, B, C, D, E, F and G]
Once a device of multiple approval type is Vmax = 30 V Ci = 6 nF
installed, it should not be re-installed using any Imax = 200 mA Li = 0 H
other approval types. Apply a permanent mark Pmax = 1 W
in the check box of the selected approval type * Associated Apparatus Parameters
on the certification label on the transmitter to (FM approved barriers)
distinguish it from unused approval types. Voc 30 V Ca > 6 nF
Isc 200 mA La > 0 H
Pmax 1W
IMPORTANT
Intrinsically Safe Apparatus Parameters
All the blind plugs which accompany the EJX/ [Groups C, D, E, F and G]
EJA-E transmitters upon shipment from the Vmax = 30 V Ci = 6 nF
factory are certified by the applicable agency Imax = 225 mA Li = 0 H
in combination with the transmitters. The plugs Pmax = 1 W
which are marked with the symbols Ex on
their surfaces are certified only in combination * Associated Apparatus Parameters
with the EJX/EJA-E series transmitters. (FM approved barriers)
Voc 30 V Ca > 6 nF
Isc 225 mA La > 0 H
2.9.1 FM Approval Pmax 1 W
IM 01C25F01-01E
<2. Handling Cautions> 2-5
Note 4. Maintenance and Repair Output signal: 4 to 20 mA
The instrument modification or parts 15 mA (FOUNDATION Fieldbus and
replacement by other than authorized PROFIBUS PA type)
representative of Yokogawa Electric 1 to 5 V (Low Power type)
Corporation is prohibited and will void
Note 2. Wiring
Factory Mutual Intrinsically safe and
All wiring shall comply with National Electrical
Nonincendive Approval.
Code ANSI/NFPA70 and Local Electrical
[Intrinsically Safe] Codes.
Hazardous Location Nonhazardous Location When installed in Division 1, FACTORY
Class I, II, III, Division 1, SEALED, CONDUIT SEAL NOT
Groups A, B, C, D, E, F, G REQUIRED.
Class 1, Zone 0 in Wiring connection for output signal code Q
Hazardous (Classified) General
Locations AEx ia IIC (Low Power type) shall follow the diagram
Purpose
Pressure Transmitters Safety Barrier Equipment below.
+ + + + Pressure Transmitters
Supply SUPPLY +
Voltmeter
A Power Supply
F0203-1.ai
+ +
[Nonincendive]
Hazardous Location Nonhazardous Location SUPPLY
Class I, II, Division 2,
Groups A, B, C, D, F, G Three-Wire Connection
Class 1, Zone 2, Group IIC, Pressure Transmitters
in Hazardous (Classified)
General SUPPLY +
Locations
Purpose Voltmeter
Pressure Transmitters Equipment A Power Supply
+ + + +
Supply
Not Use
Safety Barrier SUPPLY
F0203-2.ai
Four-Wire Connection
F0211.ai
b. FM Explosionproof Type
Caution for FM explosionproof type. Note 3. Operation
Keep the WARNING nameplate attached to
Note 1. EJX/EJA-E Series pressure transmitters the transmitter.
with optional code /FF1 are applicable for WARNING: OPEN CIRCUIT BEFORE
use in hazardous locations. REMOVING COVER. FACTORY SEALED,
Applicable Standard: FM3600, FM3615, CONDUIT SEAL NOT REQUIRED.
FM3810, ANSI/NEMA 250 INSTALL IN ACCORDANCE WITH THE
Explosionproof for Class I, Division 1, USERS MANUAL IM 01C25.
Groups B, C and D. Take care not to generate mechanical
Dust-ignitionproof for Class II/III, Division 1, sparking when accessing to the instrument
Groups E, F and G. and peripheral devices in a hazardous
Enclosure: Type 4X location.
Temperature Class: T6
Ambient Temperature: 40 to 60C
Supply Voltage: 42 V dc max.
32 V dc max. (FOUNDATION Fieldbus and
PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
IM 01C25F01-01E
<2. Handling Cautions> 2-6
Note 4. Maintenance and Repair [For CSA E60079]
The instrument modification or parts Applicable Standard: CAN/CSA E60079-11,
replacement by other than authorized CAN/CSA E60079-15, IEC 60529:2001
representative of Yokogawa Electric Ex ia IIC T4, Ex nL IIC T4
Corporation is prohibited and will void Ambient Temperature: 50* to 60C
* 15C when /HE is specified.
Factory Mutual Explosionproof Approval.
Max. Process Temp.: 120C
c. FM Intrinsically Safe Type/FM Enclosure: IP66/IP67
Explosionproof Type
Note 2. Entity Parameters
EJX/EJA-E Series pressure transmitters with Intrinsically safe ratings are as follows:
optional code /FU1 or /V1U1 can be selected Maximum Input Voltage (Vmax/Ui) = 30 V
the type of protection (FM Intrinsically Safe Maximum Input Current (Imax/Ii) = 200 mA
or FM Explosionproof) for use in hazardous Maximum Input Power (Pmax/Pi) = 0.9 W
locations. Maximum Internal Capacitance (Ci) = 10 nF
Note 1. For the installation of this transmitter, Maximum Internal Inductance (Li) = 0 H
once a particular type of protection is Type "n" or Nonincendive ratings are as
selected, any other type of protection follows:
cannot be used. The installation must be in Maximum Input Voltage (Vmax/Ui) = 30 V
accordance with the description about the Maximum Internal Capacitance (Ci) = 10 nF
type of protection in this instruction manual. Maximum Internal Inductance (Li) = 0 H
Installation Requirements
Note 2. In order to avoid confusion, unnecessary Uo Ui, Io Ii, Po Pi,
marking is crossed out on the label other Co Ci + Ccable, Lo Li + Lcable
than the selected type of protection when Voc Vmax, Isc Imax,
the transmitter is installed. Ca Ci + Ccable, La Li + Lcable
2.9.2 CSA Certification Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
a. CSA Intrinsically Safe Type
Note 3. Installation
Caution for CSA Intrinsically safe and In any safety barreir used output current
nonincendive type. (Following contents refer to must be limited by a resistor 'R' such that
DOC No. ICS013-A13) Io=Uo/R or Isc=Voc/R.
Note 1. EJX/EJA-E Series differential, gauge, The safety barrier must be CSA certified.
and absolute pressure transmitters with Input voltage of the safety barrier must be
optional code /CS1 are applicable for use less than 250 Vrms/Vdc.
in hazardous locations Installation should be in accordance with
Certificate: 1606623 Canadian Electrical Code Part I and Local
[For CSA C22.2] Electrical Code.
Applicable Standard: C22.2 No.0, C22.2 Dust-tight conduit seal must be used when
No.0.4, C22.2 No.25, C22.2 No.94, C22.2 installed in Class II and III environments.
No.157, C22.2 No.213, C22.2 No.61010-1, The instrument modification or parts
C22.2 No.61010-2-030, C22.2 No.60079-0 replacement by other than authorized
Intrinsically Safe for Class I, Division 1, representative of Yokogawa Electric
Groups A, B, C & D, Class II, Division 1, Corporation and Yokogawa Corporation
Groups E, F & G, Class III, Division 1 of America is prohibited and will void
Nonincendive for Class I, Division 2, Groups Canadian Standards Intrinsically safe and
A, B, C & D, Class II, Division 2, Groups F & nonincendive Certification.
G, Class III, Division 1
Enclosure: Type 4X
Temp. Code: T4
Amb. Temp.: 50* to 60C
* 15C when /HE is specified.
Process Temperature: 120C max.
IM 01C25F01-01E
<2. Handling Cautions> 2-7
[Intrinsically Safe] Output Signal: 4 to 20 mA dc
Hazardous Location Nonhazardous Location 15 mA (FOUNDATION Fieldbus and
Group IIC, Zone 0 PROFIBUS PA type)
Class I, II, III, Division 1, 1 to 5 V (Low Power type)
Groups A, B, C, D, E, F, G General
Purpose
Safety Barrier
Note 2. Wiring
Pressure Transmitters Equipment
+ + + + All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Supply
Codes.
In hazardous location, wiring shall be in
F0204-1.ai
conduit as shown in the figure.
[Nonincendive] WARNING:
Hazardous Location Nonhazardous Location A SEAL SHALL BE INSTALLED WITHIN
Group IIC, Zone 2 50cm OF THE ENCLOSURE.
Class I, II, Division 2,
CSA Certified
UN SCELLEMENT DOIT TRE INSTALL
Groups A, B, C, D, F, G
Equipment MOINS DE 50cm DU BOTIER.
Class III, Division 1.
([nL] or WARNING:
Pressure Transmitters nonincendive)
WHEN INSTALLED IN CL.I, DIV 2, SEAL
+ +
NOT REQUIRED.
Supply UNE FOIS INSTALL DANS CL I, DIV 2,
Not Use
Safety Barrier AUCUN JOINT N'EST REQUIS.
F0204-2.ai Non-Hazardous Hazardous Locations Division 1
Locations
b. CSA Explosionproof Type Non-hazardous
Location
Equipment 50 cm Max.
Caution for CSA explosionproof type.
Note 1. EJX/EJA-E Series pressure transmitters
with optional code /CF1 are applicable for 42 V DC Max. Conduit
use in hazardous locations: 4 to 20 mA DC Sealing Fitting
Signal
Certificate: 2014354 Transmitter
F0205-1.ai
Applicable Standard: C22.2 No.0,
C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, Non-Hazardous Hazardous Locations Division 2
C22.2 No.30, C22.2 No.94, Locations
IM 01C25F01-01E
<2. Handling Cautions> 2-8
Pressure Transmitters Note 1. For the installation of this transmitter,
SUPPLY +
once a particular type of protection is
Voltmeter selected, any other type of protection
A Power Supply cannot be used. The installation must be in
+ +
accordance with the description about the
type of protection in this instruction manual.
SUPPLY Note 2. In order to avoid confusion, unnecessary
Three-Wire Connection marking is crossed out on the label other
than the selected type of protection when
Pressure Transmitters
the transmitter is installed.
SUPPLY +
A
Voltmeter 2.9.3 ATEX Certification
Power Supply
+ +
(1) Technical Data
a. ATEX Intrinsically Safe Ex ia
SUPPLY
Four-Wire Connection
Caution for ATEX Intrinsically safe type.
F0212.ai
Note 1. EJX/EJA-E Series pressure transmitters
Note 3. Operation with optional code /KS21 for potentially
WARNING: explosive atmospheres:
AFTER DE-ENERGIZING, DELAY 5 No. DEKRA 11ATEX0228 X
MINUTES BEFORE OPENING. Applicable Standard:
APRS POWER-OFF, ATTENDRE 5 EN 60079-0:2009, EN 60079-11:2007,
MINUTES AVANT D'OUVRIR. EN 60079-26:2007, EN 61241-11:2006
WARNING: Type of Protection and Marking code:
WHEN AMBIENT TEMPERATURE 65C, Ex ia IIC T4 Ga
USE THE HEAT-RESISTING CABLES Ex ia IIIC T85 C T100 C T120 C Db
90C. Group: II
QUAND LA TEMPRATURE AMBIANTE Category: 1G, 2D
65C, UTILISEZ DES CBLES Ambient Temperature for EPL Ga:
RSISTANTES LA CHALEUR 90C. 50 to 60C
Ambient Temperature for EPL Db:
Take care not to generate mechanical
30* to 60C
sparking when accessing to the instrument
* 15C when /HE is specified.
and peripheral devices in a hazardous
Process Temperature (Tp.): 120C max.
location.
Maximum Surface Temperature for EPL Db:
Note 4. Maintenance and Repair T85C (Tp.: 80C)
The instrument modification or parts T100C (Tp.: 100C)
replacement by other than authorized T120C (Tp.: 120C)
representative of Yokogawa Electric Enclosure: IP66 / IP67
Corporation and Yokogawa Corporation of
Note 2 Electrical Data
America is prohibited and will void Canadian
In type of explosion protection intrinsic safety
Standards Explosionproof Certification.
Ex ia IIC or Ex ia IIIC, only for connection to a
c CSA Intrinsically Safe Type/CSA certified intrinsically safe circuit with following
Explosionproof Type maximum values:
EJX/EJA-E Series pressure transmitters with Ui = 30 V
optional code /CU1 or /V1U1 can be selected Ii = 200 mA
the type of protection (CSA Intrinsically Safe Pi = 0.9 W
or CSA Explosionproof) for use in hazardous (Linear Source)
locations. Maximum internal capacitance; Ci = 27.6 nF
Maximum internal inductance; Li = 0 H
IM 01C25F01-01E
<2. Handling Cautions> 2-9
Note 3. Installation b. ATEX Flameproof Type
Refer to the control drawing. All wiring shall
Caution for ATEX flameproof type.
comply with local installation requirements.
[Control Drawing] Note 1. EJX/EJA-E Series pressure transmitters
with optional code /KF22 for potentially
Hazardous Location Nonhazardous Location
explosive atmospheres:
Pressure Transmitters No. KEMA 07ATEX0109 X
+ + Applicable Standard: EN 60079-0:2009,
Supply Safety Barrier *1
EN 60079-1:2007, EN 60079-31:2009
Type of Protection and Marking Code:
Ex d IIC T6...T4 Gb, Ex tb IIIC T85C Db
Group: II
F0206.ai Category: 2G, 2D
*1: In any safety barriers used the output current must be Enclosure: IP66/IP67
limited by a resistor R such that Io=Uz/R.
Temperature Class for gas-poof:
Note 4. Maintenance and Repair T6, T5, and T4
The instrument modification or parts Ambient Temperature for gas-proof:
replacement by other than authorized 50 to 75C (T6), 50 to 80C (T5), and
representative of Yokogawa Electric 50 to 75C (T4)
Corporation is prohibited and will void Maximum Process Temperature (Tp.) for
DEKRA Intrinsically safe Certification. gas-proof:
85C (T6), 100C (T5), and 120C (T4)
Note 5. Special Conditions for Safe Use
Maximum Surface Temperature for dust-
proof:
WARNING
T85C (Tamb.: 30* to 75C, Tp.: 85C)
* 15C when /HE is specified.
In the case where the enclosure of the
Pressure Transmitter is made of aluminium, Note 2. Electrical Data
if it is mounted in an area where the use of Supply voltage: 42 V dc max.
category 1 G apparatus is required, it must 32 V dc max. (FOUNDATION Fieldbus and
be installed such, that, even in the event of PROFIBUS PA type)
rare incidents, ignition sources due to impact 9 to 28 V dc, 27 mW (Low Power type)
and friction sparks are excluded. Output signal: 4 to 20 mA
Electrostatic charge may cause an exlosion 15 mA (FOUNDATION Fieldbus and
hazard. Avoid any actions that cause the PROFIBUS PA type)
generation of electrostatic charge, such as 1 to 5 V (Low Power type)
rubbing with a dry cloth on coating face of Note 3. Installation
the product. All wiring shall comply with local installation
In case of the enclosure of the Pressure requirement.
Transmitter with paint layers, if it is mounted Cable glands, adapters and/or blanking
in an area where the use of category 2D elements with a suitable IP rating shall
apparatus is required, it shall be installed in be of Ex d IIC/Ex tb IIIC certified by ATEX
such a way that the risk from electrostatic and shall be installed so as to maintain the
discharges and propagating brush specific degree of protection (IP Code) of the
discharges caused by rapid flow of dust is equipment.
avoided. Wiring connection for output signal code Q
To satisfy IP66 or IP67, apply waterproof (Low Power type) shall follow the diagram
glands to the electrical connection port. below.
When the lightning protector option is
specified, the apparatus is not capable
of withstanding the 500V insulation test
required by EN60079-11. This must be taken
into account when installing the apparatus.
IM 01C25F01-01E
<2. Handling Cautions> 2-10
Pressure Transmitters c. ATEX Intrinsically Safe Type/ATEX
SUPPLY +
Flameproof Type
Voltmeter
A Power Supply
EJX/EJA-E Series pressure transmitters with
+ + optional code /KU22 or /V1U1 can be selected
the type of protection ATEX Flameproof,
Intrinsically Safe. Ex ia, or Ex ic for use in
SUPPLY hazardous area.
Three-Wire Connection Note 1. For the installation of this transmitter,
Pressure Transmitters once a particular type of protection is
SUPPLY + selected, any other type of protection
A
Voltmeter cannot be used. The installation must be in
Power Supply
accordance with the description about the
+ +
type of protection in this users manual.
Note 2. For combined approval types Once a
SUPPLY device of multiple approval type is installed,
Four-Wire Connection it should not be re-installed using any
other approval types. Apply a permanent
F0213.ai
IM 01C25F01-01E
<2. Handling Cautions> 2-11
Note 3. Maintenance and Repair (3) Installation
The instrument modification or parts
replacement by other than authorized
WARNING
representative of Yokogawa Electric
Corporation is prohibited and will void ATEX All wiring shall comply with local installation
intrinsically safe. requirements and the local electrical code.
[Control drawing] There is no need for conduit seal in Division
Hazardous Area Nonhazardous Area 1 and Division 2 hazardous locations
because this product is sealed at the factory.
+
Pressure Associated
Transmitters Apparatus
(4) Operation
F0207.ai WARNING
Note 4. Specific Conditions of Use OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
WARNING THIS USERS MANUAL
Take care not to generate mechanical
Electrostatic charge may cause an explosion sparking when access to the instrument and
hazard. Avoid any actions that cause the peripheral devices in a hazardous location.
generation of electrostatic charge, such as
rubbing with a dry cloth on coating face of
the product. (5) Maintenance and Repair
When the lightning protector option is
specified, the apparatus is not capable WARNING
of withstanding the 500V insulation test
required by EN60079-11. This must be taken The instrument modification or parts replacement
into account when installing the apparatus. by other than an authorized Representative of
Yokogawa Electric Corporation is prohibited and
will void the certification.
(2) Electrical Connection
A mark indicating the electrical connection type
is stamped near the electrical connection port.
These marks are as followed.
Screw Size Marking
ISO M20 1.5 female M
ANSI 1/2 NPT female N or W
F0208.ai
IM 01C25F01-01E
<2. Handling Cautions> 2-12
(6) Name Plate 2.9.4 IECEx Certification
Name plate EJX Series pressure transmitters with optional
code /SU21 can be selected the type of
protection (IECEx Intrinsically Safe Ex ia, Ex ic
or flameproof) for use in hazardous locations.
EJX Series pressure transmitters with optional
code /SS26 can be selected the type of
Tag plate for flameproof type
protection (IECEx intrinsically safe Ex ia or Ex
ic) for use in hazardous locations.
No. KEMA 07ATEX0109 X
Ex d IIC T6...T4 Gb, Ex tb IIIC T85C Db
Enlcosure : IP66/IP67
TEMP. CLASS T6 T5 T4
WARNING
a. IECEx Intrinsically Safe Ex ia
Caution for IECEx Intrinsically safe Ex ia.
POTENTIAL ELECTROSTATIC
F0209.ai
with optional code /SU21 are applicable for
MODEL: Specified model code. use in hazardous locations
STYLE: Style code. No. IECEx DEK 11.0081X
SUFFIX: Specified suffix code. Applicable Standard: IEC 60079-0:2011,
SUPPLY: Supply voltage. IEC 60079-11:2011, IEC 60079-26:2006
OUTPUT: Output signal. Ex ia IIC T4 Ga
MWP: Maximum working pressure. Ambient Temperature: 50 to 60C
CAL RNG: Specified calibration range. Max. Process Temp.: 120C
NO.: Serial number and year of production*1.
TOKYO 180-8750 JAPAN: Note 2. Electrical Data
The manufacturer name and the address*2. Maximum Input Voltage (Ui) = 30 V
Maximum Input Current (Ii) = 200 mA
*1: The first digit in the three numbers next to the nine
letters of the serial number appearing after NO. Maximum Input Power (Pi) = 0.9 W
on the nameplate indicates the year of production. (linear source)
The following is an example of a serial number for a
product that was produced in 2010: Maximum Internal Capacitance (Ci) = 27.6 nF
91K819857 032 Maximum Internal Inductance (Li) = 0 H
Note 3. Installation
The year 2010 In any safety barrier used output current
*2: 180-8750 is a zip code which represents the must be limited by a resistor R such that
following address.
Io=Uz/R.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
The safety barrier must be IECEx certified.
*3: The identification number of Notified Body.
IM 01C25F01-01E
<2. Handling Cautions> 2-13
Input voltage of the safety barrier must be Ex ic IIC T4 Gc
less than 250 Vrms/Vdc. Ambient Temperature: 30* to 60C
* -15 C when /HE is specified.
The instrument modification or parts
replacement by other than authorized Max. Process Temp.: 120C
representative of Yokogawa Electric IP Code: IP66
Corporation is prohibited and will void IECEx Overvoltage Category: I
certification. Note 2. Electrical Data
[Ex ia] Maximum Input Voltage (Ui) = 30 V
Hazardous Location Nonhazardous Location Maximum Internal Capacitance (Ci) = 27.6 nF
Group IIC, Zone 0 Maximum Internal Inductance (Li) = 0 H
EJX/EJA-E Series IECEx certified Note 3. Installation
Pressure Transmitters Safety Barrier
The pressure transmitter is allowed to
+ +
be installed in nL systems, on condition
Supply
that the output parameters of nL source
(associated energy-limited apparatus)
(*1) are suitable to the above mentioned input
*1: When using non isolation barrier, parameters of the pressure transmitter and
connect (*1) to IS barrier system. F0215.ai
the cable parameters.
Note 4. Specific Condition of Use Cable glands, adapters and/or blanking
elements shall be of Ex n, Ex e or Ex
WARNING d and shall be installed so as to maintain
the specified degree of protection of the
Electrostatic charge may cause an explosion equipment.
hazard. Avoid any actions that cause the The instrument modification or parts
generation of electrostatic charge, such as replacement by other than authorized
rubbing with a dry cloth on coating face of representative of Yokogawa Electric
the product. Corporation is prohibited and will void IECEx
In the case where the enclosure of the certification.
pressure transmitter is made of aluminum, [Ex ic]
if it is mounted in an area where the use of Hazardous Location Nonhazardous Location
EPL Ga equipment is required, it shall be
EJX/EJA-E Series Associated apparatus
installed in such a way that , even in the Pressure Transmitters
event of rare incidents, ignition sources due
+ +
to impact and friction sparks are excluded. Supply
When the lightning protector option is
specified, the apparatus is not capable
F0216.ai
of withstanding the 500 V insulation test
required by IEC 60079-11. This must be Note 4. Specific Condition of Use
taken into account when installing the
apparatus. WARNING
Electrostatic charge may cause an explosion
b. IECEx Intrinsically Safe Ex ic hazard. Avoid any actions that cause the
Caution for IECEx Intrinsically safe Ex ic. generation of electrostatic charge, such as
rubbing with a dry cloth on coating face of
Note 1. EJX/EJA-E series pressure transmitters
the product.
with optional code /SU21 are applicable for
The apparatus is not capable of dielectric
use in hazardous locations
strength tests required by IEC 60079-11.
No. IECEx DEK 13.0061X
This must be taken into account when
Applicable Standard: IEC 60079-0:2011,
installing the apparatus.
IEC 60079-11:2011
IM 01C25F01-01E
<2. Handling Cautions> 2-14
c. IECEx Intrinsically Safe Type / type n [Intrinsically Safe]
Caution for IECEx Intrinsically safe and type n. Hazardous Location Nonhazardous Location
Group IIC, Zone 0
Note 1. EJX Series differential, gauge, and General
IECEx certified Purpose
absolute pressure transmitters with Pressure Transmitters Safety Barrier Equipment
optional code /SU2 are applicable for use + + + +
in hazardous locations
Supply
No. IECEx CSA 05.0005
Applicable Standard: IEC 60079-0:2000,
IEC 60079-11:1999, IEC 60079-15:2001 F0210-1.ai
IM 01C25F01-01E
<2. Handling Cautions> 2-15
Note 2. Wiring Note 4. Maintenance and Repair
In hazardous locations, the cable entry The instrument modification or parts
devices shall be of a certified flameproof replacement by other than authorized
type, suitable for the conditions of use and representative of Yokogawa Electric
correctly installed. Corporation is prohibited and will void IECEx
Unused apertures shall be closed with Certification.
suitable flameproof certified blanking Electrical Connection
elements. A mark indicating the electrical connection
Wiring connection for output signal code Q type is stamped near the electrical
(Low Power type) shall follow the diagram connection port. These marks are as
below. followed.
Pressure Transmitters
Screw Size Marking
SUPPLY +
Voltmeter ISO M20 1.5 female M
A Power Supply
ANSI 1/2 NPT female N or W
+ +
SUPPLY
Three-Wire Connection
Location of the mark
Pressure Transmitters
SUPPLY + F0208.ai
Voltmeter
A Power Supply
+ +
2.10 EMC Conformity Standards
EN 61326-1 Class A, Table2 (For use in
SUPPLY industrial locations)
Four-Wire Connection EN 61326-2-3
F0214.ai
EN 61326-2-5 (for Fieldbus)
Note 3. Operation
WARNING: CAUTION
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING. To meet EMC regulations, Yokogawa
WARNING: recommends that customers run signal wiring
WHEN THE AMBIENT TEMP.65C, USE through metal conduits or use shielded twisted-
HEAT-RESISTING CABLE AND CABLE pair cabling when installing EJX/EJA-E series
GLAND 90C. transmitters in a plant.
Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Electrostatic charge may cause an explosion
hazard. Avoid any actions that cause the
generation of electrostatic charge, such as
rubbing with a dry cloth on coating face of the
product.
IM 01C25F01-01E
<2. Handling Cautions> 2-16
2.11 Pressure Equipment (3) Operation
Directive (PED)
CAUTION
(1) General
The temperature and pressure of fluid should
EJX/EJA-E Series pressure transmitters are be maintained at levels that are consistent
categorized as piping under the pressure with normal operating conditions.
accessories section of directive 97/23/EC, The ambient temperature should be
which corresponds to Article 3, Paragraph 3 of maintained at a level that is consistent with
PED, denoted as Sound Engineering Practice normal operating conditions.
(SEP). Please take care to prevent water hammer
EJ510-D, EJ530-D, EJX610A-D, and the like from inducing excessive
and EJX630A-D can be used above 200 pressures in pipes and valves. If phenomena
bar and therefore considered as a part of a are likely, install a safety valve or take
pressure retaining vessel where category III, some other appropriate measure to prevent
Module H applies. These models with option pressure from exceeding PS.
code /PE3 conform to that category. Take appropriate measures at the device or
(2) Technical Data system level to protect transmitters if they
are to be operated near an external heat
Models without /PE3 source.
Article 3, Paragraph 3 of PED, denoted as
Sound Engineering Practice (SEP).
Models with /PE3
Module: H
2.12 Safety Requirement
Type of Equipment: Pressure Accessory-Vessel Standards
Type of fluid: Liquid and Gas
Applicable standard: EN 61010-1,
Group of fluid: 1 and 2
EN 61010-2-30, C22.2 No.61010-1,
Capsule PS*1 PS.V C22.2 No.61010-2-030
Model V(L) Category*2
code (bar) (bar.L)
Article 3, (1) Pollution Degree 2
EJ510 A, B, C 100 0.1 10
Paragraph 3
EJX610A D 700 0.1 70 "Pollution degree" describes the degree to
(SEP)
EJ510,
which a solid, liquid, or gas which deteriorates
EJX610A dielectric strength or surface resistivity is
D 700 0.1 70 III
with code / adhering. " 2 " applies to normal indoor
PE3
atmosphere. Normally, only non-conductive
A, B, C 100 0.1 10 Article 3,
EJ530,
Paragraph 3 pollution occurs. Occasionally, however,
EJX630A D 700 0.1 70 (SEP) temporary conductivity caused by condensation
EJ530, must be expected.
EJX630A
D 700 0.1 70 III
with code / (2) Installation Category I
PE3
"Overvoltage category (Installation category)"
*1: PS is maximum pressure for vessel itself based on
Pressure Equipment Directive 97/23/EC. Refer to describes a number which defines a transient
General Specification for maximum working pressure of a overvoltage condition. It implies the regulattion
transmitter.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
for impulse withstand voltage. " I " applies to
on Pressure Equipment Directive 97/23/EC electrical equipment which is supplied from the
circuit when appropriate transient overvoltage
control means (interfaces) are provided.
(3) Altitude of installation site:
Max. 2,000 m above sea level
(4) Indoor/Outdoor use
IM 01C25F01-01E
<3. Component Names> 3-1
3. Component Names
External indicator
conduit connection (Note 1)
Conduit
connection
(Note 2) Zero-
Slide switch adjustment
screw
Integral
indicator (Note 1)
Mounting screw
CPU assembly
Range-setting
switch (Note 1) Burnout direction switch
(See section 7.5)
BO H L
Transmitter section
WR E D
Amplifier Cover
Write protection switch
NO YES
Burnout Direction HIGH LOW Write Protection
(Write enabled) (Write disabled)
F0301.ai
Note 1: See subsection 9.2, Model and Suffix Codes, for details.
Note 2: Applicable for BRAIN/HART communication type. Set the switches as shown in the figure above to set the burn-out direction
and write protection. The Burnout switch is set to the H side for delivery (unless option code /C1 or /C2 is specified in the order),
and the hardware write protection switch is set to E side.The setting of the switches can be confirmed via communication. An
external zero adjustment screw can only be disabled by communication. To disable the screw, set a parameter before activating
the hardware write protect function. See each communication manual.
IM 01C25F01-01E
<4. Installation> 4-1
4. Installation
4.1 Precautions Vertical pipe mounting
IMPORTANT
When welding piping during construction,
take care not to allow welding currents to
flow through the transmitter.
Mounting bracket
Do not step on this instrument after U-bolt (L)
installation. U-bolt (S)
For the EJ530 and EJX630A whose
capsule code is A, B or C, the pipe of the
U-bolt nut (L)
atmospheric opening is located on the Horizontal pipe mounting
pressure detecting section. The opening
must not face upward. See subsection 5.1.1. Mounting bracket
D capsule of EJ530 and EJX630A is
of sealed gauge reference and the change
in atomospheric pressure may affect the 50 mm (2-inch) pipe
measurement.
Gasket
F0402.ai
IM 01C25F01-01E
<4. Installation> 4-2
Transmitter section
IMPORTANT
Tighten the hexagonal nut part of the capsule
assembly. See Figure 4.3.
Setscrew
Capsule assembly
Pressure-detector section
Stopper
F0404.ai
IMPORTANT
Do not rotate the transmitter section more than
the above limit.
IM 01C25F01-01E
<5. Installing Impulse Piping> 5-1
downwards for all the models. Figure 5.2 Process Pressure Tap Angle
(For Horizontal Piping)
The pipe (open to atmosphere) is positioned horizontal.
IM 01C25F01-01E
<5. Installing Impulse Piping> 5-2
(3) Impulse Piping Slope Tap valve
The impulse piping must be routed with only an
upward or downward slope. Even for horizontal Union or flange
routing, the impulse piping should have a slope of
at least 1/10 to prevent condensate (or gases) from
accumulating in the pipes. Stop valve
IM 01C25F01-01E
<6. Wiring> 6-1
6. Wiring
6.1 Wiring Precautions 6.3 Connections of External
IMPORTANT Wiring to Terminal Box
Lay wiring as far as possible from electrical Terminal Configuration
noise sources such as large capacity
transformers, motors, and power supplies.
Remove the electrical connection dust cap
before wiring.
All threaded parts must be treated with
waterproofing sealant. (A non-hardening
silicone group sealant is recommended.)
To prevent noise pickup, do not pass signal
and power cables through the same ducts. Terminal 1 Terminal 3
Materials VOUT +
3
2
1 to 5 V DC with HART communication
terminals
IM 01C25F01-01E
<6. Wiring> 6-2
6.3.1 Power Supply Wiring Connection Connect the BT200 or HART Communicator to the
SUPPLY + and terminals. (Use hooks.)
IMPORTANT Transmitter terminal box Power supply
Connecting with the commercial AC power +
supply will damage the device. Be sure to use
the DC power supply in the predetermined Ignore the polarity since the
range. BT200 is AC-coupled to the
terminal box.
BT200 F0603.ai
Connect the power supply wiring to the SUPPLY +
Figure 6.4 BT200 Connection
and terminals. When /AL is specified, also refer to
subsection 6.3.5.
1 to 5 V output, HART
Transmitter terminal box Connect the HART communicator or configuration
+ tool to the SUPPLY - and VOUT (+) terminals. (Use
Power supply
hooks.)
Load resistance is not necessary
Power supply Transmitter terminal box Voltmeter
for 1 to 5 V output.
F0601.ai + +
Figure 6.2 Power Supply Wiring Connection USB
FieldMate Modem
F0604.ai
IM 01C25F01-01E
<6. Wiring> 6-3
6.3.5 Status Output Connection (2) 4 to 20 mA output, Intrinsically Safe Type
When option code /AL is specified, connect the With the intrinsically safe type, a safety barrier must
external wiring as shown in Figure 6.5. be included in the loop.
To configure and activate the process alarm Hazardous Location Nonhazardous Location
function and status output, it is necessary to set
Transmitter terminal box
some parameters. Refer to each communication Distributor
manual for procedures. (Power supply unit)
Transmitter
24V DC
terminal box Shielded cable Receiver
+ instrument
Distributor
250
Receiver Receiver
instrument instrument
F0606.ai F0617.ai
Figure 6.9 Connection between Transmitter and Figure 6.11 Connection between Transmitter,
Distributor Distributer and Receiver
IM 01C25F01-01E
<6. Wiring> 6-4
Four wire connection (2) Flameproof Type
Fasten the negative side wiring of both power
Wire cables through a flameproof packing adapter,
supply and signal line to the SUPPLY - terminal.
or use a flameproof metal conduit.
Hazardous Location Nonhazardous Location
Wiring cable through flameproof packing
Transmitter terminal box adapter.
Distributor
(Power supply unit) Apply a non-hardening sealant to the terminal
box connection port and to the threads on the
flameproof packing adapter for waterproofing.
Flameproof packing
adapter
(1) General-use Type and Intrinsically Safe Flameproof metal conduit wiring
Type A seal fitting must be installed near the terminal
box connection port for a sealed construction.
With the cable wiring, use a metallic conduit or
Apply a non-hardening sealant to the threads of
waterproof glands.
the terminal box connection port, flexible metal
Apply a non-hardening sealant to the terminal conduit and seal fitting for waterproofing.
box connection port and to the threads on the
Gas sealing device
flexible metal conduit for waterproofing. Non-hazardous area
Flameproof flexible
metal conduit
Hazardous area
Flexible metal conduit Apply a non-hardening
Flameproof
Apply a non-hardening heavy-gauge sealant to the threads of
Wiring metal steel conduit these fittings for
conduit sealant to the threads for
waterproofing. waterproofing
IM 01C25F01-01E
<6. Wiring> 6-5
6.5 Grounding
Grounding is always required for the proper
operation of transmitters. Follow the domestic
electrical requirements as regulated in each
country. For a transmitter with a built-in lightning
protector, grounding should satisfy ground
resistance of 10 or less.
Ground terminals are located on the inside and
outside of the terminal box. Either of these terminals
may be used.
Ground terminal
(inside)
Ground terminal
(outside)
F0611.ai
600
External E10.5
R= Communication
load 0.0244
applicable range
resistance BRAIN and HART
R ()
250
IM 01C25F01-01E
<7. Operation> 7-1
NOTE
Tee
Check that the process pressure tap valves,
Union or flange
drain valves, and stop valves are closed.
Drain valve
(a) Follow the procedures below to introduce
Drain plug
process pressure into the impulse piping and
F0701.ai
transmitter.
Figure 7.1 Liquid Flow Measurement
1) Open the tap valve (main valve) to fill the (Gauge Pressure Transmitters)
impulse piping with process fluid.
2) Gradually open the stop valve to introduce
process fluid into the transmitter pressure- Confirming that Transmitter is Operating
detector section. Properly
3) Confirm that there is no pressure leak in
Using the BT200
the impulse piping, transmitter, or other
components. IMPORTANT
(b) Turn ON power and connect the communicator.
Analog output may change temporally in
Open the terminal box cover, and connect
connecting with BRAIN terminal due to
the communicator to the SUPPLY + and
an initial current flowed to it. To prevent
terminals.
communication signal affecting the upper
(c) Using the communicator, confirm that the system, it is recommended to install a low-
transmitter is operating properly. Check pass filter (approximately 0.1s).
parameter values or change the setpoints as Communication signal is superimposed on
necessary. analog output signal. It is recommended
See IM 01C25T03-01E (BRAIN to set a low-pass filter (approximately
communication) or IM 01C25T01-06EN (HART 0.1s) to the receiver in order to reduce the
communication) for communicator operation. output effect from communication signal.
If the transmitter is equipped with an integral Before online-communication, confirm that
indicator, its indication can be used to confirm communication signal does not give effect on
that the transmitter is operating properly. the upper system.
PARAM
C60:SELF CHECK
ERROR
communication error
IM 01C25F01-01E
<7. Operation> 7-2
Using the integral indicator
If the wiring system is faulty, the display stays
IMPORTANT
blank. Do not turn off the power to the transmitter
If the transmitter is faulty, an error code is immediately after performing a zero point
displayed. adjustment. Powering off within 30 seconds of
performing this procedure will return the zero
point to its previous setting.
NOTE
Before performing this adjustment, make sure
Self-diagnostic error on the integral indicator
(Faulty transmitter) that the external zero adjustment function has
F0703.ai
NOT been disabled by a parameter setting.
Figure 7.3 Integral Indicator with Error Code
The parameters related to the following items are Figure 7.4 External Zero-adjustment Screw
set at factory as specified in order.
Calibration range The zero-adjustment screw is located inside the
Integral indicator display cover.
Software damping (optional)
Other parameters like following are shipped with the (1) When you can obtain the Low Range Value
default setting. from the actual measured value of 0% (0
Low-cut kPa, atmospheric pressure);
Process alarm setting
For pressure measurement using gauge pressure
Signal characterizer
transmitters, follow the steps below before
Write protection
performing zero point adjustment.
To confirm or change the values, see IM 01C25T01-
06EN or 01C25T03-01E. 1) Close the tap valve (main valve).
2) Loosen the fill plug so that the pressure applied
7.2 Zero Point Adjustment to the transmitter is only the head of the seal
liquid.
After completing preparations for operating the 3) Adjust the zero point at this status.
transmitter, adjust the zero point. 4) After the adjustment, close the fill plug and then
Zero point adjustment can be done by turning the gradually open the tap valve.
transmitters zero-adjustment screw or by using Use a slotted screwdriver to turn the zero-
the communicator. This section describes the adjustment screw. Turn the screw clockwise
procedure for the zero-adjustment screw. For the to increase the output or counterclockwise to
communicator procedure, see the communication decrease the output. The zero point adjustment can
manual. be made with a resolution of 0.01% of the setting
range. Since the degree of the zero adjustment
varies with the screw turning speed, turn the screw
slowly to make a fine adjustment and quickly to
make a rough adjustment.
IM 01C25F01-01E
<7. Operation> 7-3
(2) When you cannot obtain the Low Range 7.4 Shutting Down the
Value from the actual measured value of 0%;
Transmitter
Adjust the transmitter output to the actual measured
Shut down the transmitter as follows.
value obtained by a digital manometer or a glass
Steps 2) and 3) are specific to the differential
gauge.
pressure transmitters.
[Example]
1) Turn off the power.
The measuring range of 50 to 250 kPa; the actual 2) Close the stop valve.
measured value of 130 kPa. 3) Open the equalizing valve.
4) Close the high pressure stop valve.
13050
Actual measured value= x100=40.0% 5) Close the tap valves.
25050
(=10.4mA)
NOTE
Turn the screw to match the output signal to the
actual measured value. Whenever shutting down the transmitter for a
long period, remove any process fluid that is
in the transmitter pressure-detector section.
7.3 Starting Operation
The equalizing valve must be left OPEN.
After completing the zero point adjustment, follow
the procedures below to start operation. Steps
1) and 2) are specific to the differential pressure
7.5 Local Parameter Setting
transmitters.
1) Confirm the operating status. If the output
WARNING
signal exhibits wide fluctuations (hunting) due to
periodic variation in the process pressure, use The local push button on the integral indicator
the communicator to dampen the transmitter must not be used in a hazardous area. When it is
output signal. Confirm the hunting using a necessary to use the push button, operate it in a
receiving instrument or the integral indicator, non- hazardous location.
and set the optimum damping time constant.
2) After confirming the operating status, perform
the following. IMPORTANT
IMPORTANT Do not turn off the power to the transmitter
immediately after performing parameter
Remove the communicator from the terminal
setting. Powering off within 30 seconds of
box, and confirm that none of the terminal
performing this procedure will return the
screws are loose.
parameter to its previous setting.
Close the terminal box cover and the
The parameter of Ext SW must beEnabled
amplifier cover. Screw each cover in tightly
to perform this configuration. See the users
until it will not turn further.
manual IM 01C25T (HART/BRAIN) for the
There are two covers that must be locked
setting procedure.
on the ATEX Flameproof type transmitters.
The Local Parameter Setting function
An Allen head bolt (shrouding bolt) under
is available with HART or BRAIN
the edge of each cover is used to lock the
communication type.
cover. When the shrouding bolt is driven
LCD update will be slower at low ambient
counterclockwise with an Allen wrench, the
temperature, and it is recommended to use
bolt rotates upward and locks the cover. (See
LPS function at temperatures above -10
section 8.4.) After locking the covers, confirm
degrees C.
that they are secure and cannot be opened
by hand.
Tighten the zero-adjustment cover mounting
screw to secure the cover.
Tighten the zero-adjustment cover mounting
screw to secure the cover.
IM 01C25F01-01E
<7. Operation> 7-4
7.5.1 Local Parameter Setting (LPS) Overview
Parameter configuration by the external adjustment screw and push button (integral indicator code E) offers
easy and quick setup for parameters of Tag number, Unit, LRV, URV, Damping,Output mode (linear/square
root), Display out 1, and Re-range by applying actual pressure (LRV/URV). There is no effect on measurement
signal (analog output or communication signal) when Local Parameter Setting is carried out.
Integral indicator
External adjustment
screw cover
Push-button
F0705.ai F0706.ai
Figure 7.5 External Adjustment Screw Figure 7.6 Range Setting Switch (push button)
screw
Process
Measurement Zero adjustment
Display push
Activate LPS mode
push
*
1. Tag Number Edit Tag number Save/Cancel the value
*
2. Press Unit Select Press unit Save/Cancel the value
push *
3. Press LRV Edit Press LRV Save/Cancel the value
*
4. Press URV Edit Press URV Save/Cancel the value
push *
5. Damping Time Edit Damping time Save/Cancel the value
*
6. Output Mode Select Output mode Save/Cancel the value
push *
7. Display Out1 Edit Display Out1 Save/Cancel the value
push
9. URV-Apply Press Set URV Save/Cancel the value
Process
Measurement
Display
F0707.ai
*: Note that the above 1 to 7 parameter configurations are available with the software revision (SOFT REV)2.03 or later.
Software revision can be checked via a field communicator (HART/BRAIN) or DTM. Please refer to IM 01C25T01 for HART
parameter Software rev and IM 01C25T03 for BRAIN SOFT REV.
Figure 7.7
IM 01C25F01-01E
<7. Operation> 7-5
7.5.2 Activating Local Parameter Setting
Press the push button on the integral indicator to activate the Local Parameter Setting mode. The transmitter
will exit automatically from the Local Parameter Setting mode if no operation is carried out for 10 minutes.
push
push
push
push
push
push
push
push
push Process
Measurement
Display
F0708.ai
*: [Software revision: 2.03] Up to 6 characters are shown in the bottom line. To review after the 7th character, turn the external
adjustment screw and press the push button six times or more.
[Software revision: 3.01 or later] The display automatically scrolls to show all the characters.
To configure each parameter value, turn the external adjustment screw on each parameter screen after
activating the Local Parameter Setting mode.
To cancel the Local Parameter Setting configuration, please refer to 7.5.11 Save or Cancel and 7.5.12 Abort
Configuration.
IM 01C25F01-01E
<7. Operation> 7-6
7.5.4 Tag Number Configuration
Tag Number is edited by turning the external adjustment screw. Up to 8 alphanumeric characters for HART or
16 alphanumeric characters for BRAIN can be set.
Save ?/
Cancel ?
Blinking Blinking
Set all other
characters in the
Go to the next Character same way
Change the first Character
screw
push
F0709.ai
Save ?/
Cancel ?
Blinking Blinking
[Available pressure units]
Select by the push button
kPa bar inH2O@4degC(39.2degF)
Torr mbar inH2O@20degC(68degF)
atm g/cm2 inHg
MPa kg/cm2 ftH2O@4degC(39.2degF)
screw hPa Pa ftH2O@20degC(68degF)
push mmHg mmH2O@4degC(39.2degF)
psi mmH2O@20degC(68degF)
In addition to the above units, mmAq@4degC,
mmAq@20degC, mmWG@4degC and mmWG@20degC
are available for BRAIN communication type.
F0710.ai
IM 01C25F01-01E
<7. Operation> 7-7
7.5.7 Damping Time Constant Configuration
The damping time constant for the amplifier assembly can be set. Quick Response Parameter is automatically
set to ON when the damping time constant is set to less than 0.5 seconds. Damping time constant is rounded off
to two decimal places.
Save ?/
Cancel ?
push
F0711.ai
IM 01C25F01-01E
<7. Operation> 7-8
7.5.11 Save or Cancel 7.5.12.2 Abort Configuration (Parameter)
At the end of each parameter setting, select Save To exit the configuration while editing the value,
or Cancel by the external adjustment screw hold down the button for over 2 seconds and select
and press the push button to save or cancel the Save or Cancel.
configuration.
Save or Cancel
Proccess Value
F0714.ai
IM 01C25F01-01E
<8. Maintenance> 8-1
8. Maintenance
8.1 Overview 8.3 Calibration
Use the procedure below to check instrument
WARNING operation and accuracy during periodic
maintenance or troubleshooting.
Since the accumulated process fluid may be
toxic or otherwise harmful, take appropriate care 1) Connect the instruments as shown in figure 8.1
to avoid contact with the body or inhalation of and warm up the instruments for at least ten
vapors when draining condensate or venting gas minutes.
from the transmitter pressure-detector section
and even after dismounting the instrument from IMPORTANT
the process line for maintenance.
To adjust the transmitter for highest
accuracy, make adjustments with the
Maintenance of the transmitter is easy due to its power supply voltage and load resistance
modular construction. This chapter describes the including leadwire resistances set close to
procedures for calibration, adjustment, and the the conditions under which the transmitter is
disassembly and reassembly procedures required installed.
for component replacement. If the measurement range 0% point is
Transmitters are precision instruments. Please 0 kPa or shifted in the positive direction
carefully and thoroughly read the following sections (suppressed zero), the reference pressure
for information on how to properly handle them should be applied as shown in the figure.
while performing maintenance. If the measurement range 0% point is shifted
in the negative direction (elevated zero), the
IMPORTANT reference pressure should be applied using
a vacuum pump.
As a rule, maintenance of this transmitter
should be done in a shop that has all the 2) Apply reference pressures of 0%, 50%,
necessary tools. and 100% of the measurement range to the
The CPU assembly contains sensitive parts transmitter. Calculate the errors (differences
that can be damaged by static electricity. between digital voltmeter readings and
Take precautions such as using a grounded reference pressures) as the pressure is
wrist strap when handling electronic parts or increased from 0% to 100% and is decreased
touching the board circuit patterns. Also be from 100% to 0%, and confirm that the errors
sure to place the removed CPU assembly are within the required accuracy.
into a bag with an antistatic coating.
IM 01C25F01-01E
<8. Maintenance> 8-2
Table 8.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Power supply Model SDBT or SDBS distributor 4 to 20 mA DC signal
Load resistor Model 2792 standard resistor [250 0.005%, 3 W]
Load adjustment resistor [100 1%, 1 W]
Voltmeter Model 2501 A digital multimeter
Accuracy (10V DC range): (0.002% of rdg + 1 dgt)
Digital Model MT220 precision digital manometer Select a manometer having
manometer 1) For 10 kPa class a pressure range close to
Accuracy: (0.015% of rdg + 0.015% of F.S.) . . . . for 0 to 10 kPa that of the transmitter.
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: 0.02% of rdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
3) For 700 kPa class
Accuracy: (0.02% of rdg + 3digits) . . . . . . . . . . . . for 100 to 700 kPa
5 digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: (0.02% of rdg + 10 digits) . . . . . . . . . . for 0 to 3000 kPa
(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: (0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs
Pressure Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 kPa Requires air pressure
generator {2500 mmH2O} supply.
Accuracy: 0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O} Select the one having a
Accuracy: 0.03% of setting pressure range close to that
of the transmitter.
Pressure Model 6919 pressure regulator (pressure pump) Prepare the vacuum pump
source Pressure range: 0 to 133 kPa {1000 mmHg} for negative pressure
ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% or higher level, use proper
instruments for required level or contact Yokogawa representatives from which the instrument was purchased or the nearest
Yokogawa office.
IM 01C25F01-01E
<8. Maintenance> 8-3
8.4 Disassembly and 8.4.1 Replacing the Integral Indicator
Reassembly
CAUTION
This section describes procedures for disassembly
and reassembly for maintenance and component Cautions for Flameproof Type Transmitters
replacement. Users are prohibited by law from modifying the
Always turn OFF power and shut off and release construction of a flameproof type transmitter.
pressures before disassembly. Use proper tools for This would invalidate the agency approval for the
all operations. Table 8.2 shows the tools required. use of the transmitter in a rated area.
It follows that the user is prohibited from using
Table 8.2 Tools for Disassembly and Reassembly a flameproof type transmitter with its integral
Tool Quantity Remarks indicator removed, or from adding an integral
Phillips 1 JIS B4633, No. 2 indicator to a transmitter. If such modification is
screwdriver absolutely required, contact Yokogawa.
Slotted 1
screwdriver
This subsection describes the procedure for
Allen wrenches 3 JIS B4648
One each, nominal 3, 4 and replacing an integral indicator. (See figure 8.3)
2.5 mm Allen wrenches
Wrench 1 Width across flats, 17 mm Removing the Integral Indicator
Torque wrench 1
1) Remove the cover.
Adjustable 1
wrench 2) While supporting the integral indicator with one
Socket wrench 1 Width across flats, 16 mm hand, loosen its two mounting screws.
Socket driver 1 Width across flats, 5.5 mm 3) Dismount the LCD board assembly from the
Tweezers 1 CPU assembly.
When doing this, carefully pull the LCD board
assembly straight forward so as not to damage
CAUTION the connector pins between it and the CPU
assembly.
Precautions for ATEX Flameproof Type
Attaching the Integral Indicator
Transmitters
Flameproof type transmitters must be, as 1) Align both the LCD board assembly and CPU
a rule, removed to a non-hazardous area assembly connectors and engage them.
for maintenance and be disassembled and 2) Insert and tighten the two mounting screws.
reassembled to the original state. 3) Replace the cover.
On the flameproof type transmitters the two Output terminal cable
covers are locked, each by an Allen head bolt
(shrouding bolt). When a shrouding bolt is
driven clockwise by an Allen wrench, it is going
in and cover lock is released, and then the Press
cover can be opened. forward
Shrouding Bolt
F0803.ai
Shrouding Bolt F0802.ai Figure 8.3 Removing and Attaching LCD Board
Figure 8.2 Shrouding Bolts Assembly and CPU Assembly
IM 01C25F01-01E
<8. Maintenance> 8-4
8.4.2 Replacing the CPU Board Assembly
NOTE
This subsection describes the procedure for
replacing the CPU assembly. (See figure 8.3) Confirm that the zero-adjustment screw pin is
placed properly in the groove on the bracket prior
Removing the CPU Assembly to tightening the two bosses. If it is not, the zero-
1) Remove the cover. If an integral indicator is adjustment mechanism will be damaged.
mounted, refer to subsection 8.4.1 and remove
the indicator. 5) Replace the cover.
2) Turn the zero-adjustment screw to the position
8.4.3 Cleaning and Replacing the Capsule
(where the screw head slot is horizontal) as
Assembly
shown in figure 8.3.
3) Disconnect the output terminal cable (cable This subsection describes the procedures for
with brown connector at the end). When doing cleaning and replacing the capsule assembly. (See
this, lightly press the side of the CPU assembly figure 8.4.)
connector and pull the cable connector to
disengage.
4) Use a socket driver (width across flats, 5.5mm) CAUTION
to loosen the two bosses.
Cautions for Flameproof Type Transmitters
5) Carefully pull the CPU assembly straight
Users are prohibited by law from modifying the
forward to remove it.
construction of a flameproof type transmitter. If
6) Disconnect the flat cable (cable with white
you wish to replace the capsule assembly with
connector at the end) that connects the CPU
one of a different measurement range, contact
assembly and the capsule.
Yokogawa.
The user is permitted, however, to replace a
NOTE capsule assembly with another of the same
Be careful not to apply excessive force to the measurement range. When doing so, be sure to
CPU assembly when removing it. observe the following.
The replacement capsule assembly must
have the same part number as the one being
Mounting the CPU Assembly replaced.
1) Connect the flat cable (with white connector) The section connecting the transmitter and
between the CPU assembly and the capsule. capsule assembly is a critical element in
2) Connect the output terminal cable (with brown preservation of flameproof performance, and
connector). must be checked to verify that it is free of
dents, scratches, and other defects.
NOTE After completing maintenance, be sure to
securely tighten the setscrews that fasten the
Make certain that the cables do not get pinched transmitter section and pressure-detector
between the case and the edge of the CPU section together.
assembly.
IM 01C25F01-01E
<8. Maintenance> 8-5
Removing the Capsule Assembly Transmitter section
IMPORTANT
Hexagon
Exercise care as follows when cleaning the head screw
3) Remove the hexagon-head screw and the Figure 8.4 Removing and Mounting the Pressure-
stopper. detector Section
4) Separate the transmitter section and capsule
assembly.
5) Clean the capsule assembly or replace with a 8.5 Troubleshooting
new one.
If any abnormality appears in the measured values,
Reassembling the Capsule Assembly use the troubleshooting flow chart below to isolate
and remedy the problem. Since some problems
1) Insert the capsule assembly to the transmitter
have complex causes, these flow charts may
section. Reattach the sopper with the hexagon-
not identify all. If you have difficulty isolating or
head screw.
correcting a problem, contact Yokogawa service
2) Tighten the two setscrews. (Tighten the screws
personnel.
to a torque of 1.5 Nm)
3) Install the CPU assembly according to
subsection 8.4.2.
4) After completing reassembly, adjust the zero
point and recheck the parameters.
IM 01C25F01-01E
<8. Maintenance> 8-6
8.5.1 Basic Troubleshooting 8.5.2 Troubleshooting Flowcharts
First determine whether the process variable
The following sorts of symptoms indicate that transmitter
is actually abnormal or a problem exists in the may not be operating properly.
Example : There is no output signal.
measurement system. Output signal does not change even though
process variable is known to be varying.
If the problem is in the measurement system, Output value is inconsistent with value
isolate the problem and decide what corrective inferred for process variable.
action to take.
This transmitter is equipped with a self-diagnostic Connect communicator and check self-diagnostics.
function which will be useful in troubleshooting,
and the transmitter equipped with an integral
indicator will show an alarm code as a result of self- Does the self-diagnostic YES
diagnosis. indicate problem location?
Inspect the NO
Measurement system problem Are power
process system. NO
supply voltage and load
resistance correct?
Isolate problem in
measurement system. YES Refer to Section 6.6 for rated voltage
and load resistance.
YES
Environmental conditions Transmitter itself Is there any pressure leak?
Is there
Check/correct operating continuity through the NO
conditions. transmitter loop wiring?
F0805.ai Do the loop numbers
match?
Figure 8.5 Basic Flow and Self-Diagnostics
Find/correct broken conductor or
YES
wiring error.
IM 01C25F01-01E
<8. Maintenance> 8-7
Connect a communicator and check self-diagnostics. Connect a communicator and check self-diagnostics.
Is impulse piping NO
Are valves opened or NO
connected correctly?
closed correctly?
Is transmitter
installed where there is YES
Is impulse piping NO
to high pressure and low marked variation in
pressure side correct? temperature?
Were appropriate NO
Is zero point NO instruments used for
adjusted correctly? calibration?
NO
Contact Yokogawa service personnel. Is output adjusted correctly?
F0807.ai
IM 01C25F01-01E
<8. Maintenance> 8-8
8.5.3 Alarms and Countermeasures
Table 8.3 Alarm Message Summary
Output Operation
Indicator Cause Countermeasure
during Error
None
AL. 01 Sensor problem. Outputs the signal (Hold, High, or Replace capsule when error
CAP. ERR Capsule temperature sensor Low) set with parameter. keeps appearing even after
problem. restart.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor Outputs the signal (Hold, High, or Replace amplifier.
AMP. ERR problem. Low) set with parameter.
Amplifier EEPROM problem.
Amplifier problem.
AL. 10 Input is outside measurement Outputs high range limit value or Check input or replace capsule
PRESS range limit of capsule. low range limit value. when necessary.
AL. 11 Static pressure exceeds limit. Continues to operate and output.
ST. PRSS
AL. 12 Capsule temperature is outside Use heat insulation or make
CAP. TMP range (50 to 130C). lagging to keep temperature
AL. 13 Amplifier temperature is outside within range.
AMP. TMP range (50 to 95C)
AL. 30 Output is outside upper or lower Outputs high range limit value or Check input and range setting,
RANGE range limit value. low range limit value. and change them as needed.
AL. 31 Static pressure exceeds specified Continues to operate and
SP. RNG range. output.
AL. 35 *1 Input pressure exceeds specified Check input.
P. HI threshold.
AL. 36 *1
P. LO
AL. 39 *1 Detected temperature exceeds
TMP. HI specified threshold.
AL. 40 *1
TMP. LO
AL. 50 Specified value is outside of setting Holds output immediately before Check setting and change them
P. LRV range. error occurred. as needed.
AL. 51
P. URV
AL. 52
P. SPN
AL. 53 Continues to operate and output. Check input.
P. ADJ
AL. 60 Specified values or settings to Continues to operate and output. Check setting and change
SC. CFG define signal characterizer function them as needed.
do not satisfy the condition.
AL. 79 Displayed value exceeds limit.
OV. DISP
*1: These alarms may appear only when process alarm function is activated.
IM 01C25F01-01E
<9. General Specifications> 9-1
9. General Specifications
9.1 Standard Specifications EJX610A (Values are absolute pressure)
Measurement
MPa psi (/D1) bar (/D3) kgf/cm2(/D4)
Refer to IM 01C25T02-01E for FOUNDATION Span/Range
Fieldbus communication type and IM 01C25T04- A
Span 2 to 200 kPa 0.3 to 29 0.02 to 2 0.02 to 2
01EN for PROFIBUS PA communication type for Range 0 to 200 kPa 0 to 29 0 to 2 0 to 2
the items marked with . Span 0.01 to 2 1.5 to 290 0.1 to 20 0.1 to 20
B
Range 0 to 2 0 to 290 0 to 20 0 to 20
Span 0.05 to 10 7.3 to 1450 0.5 to 100 0.5 to 100
Performance Specifications C
Range 0 to 10 0 to 1450 0 to 100 0 to 100
50.8 to
See General Specifications sheet for each model. D
Span 0.35 to 70
10150
3.5 to 700 3.5 to 700
Range 0 to 70 0 to 10150 0 to 700 0 to 700
Functional Specifications
EJA530E
Measurement
Span & Range Limits MPa psi(/D1) bar(/D3) kgf/cm2(/D4)
Span/Range
EJX530A Span
10 to 200
1.45 to 29 0.1 to 2 0.1 to 2
Measurement kPa
MPa psi(/D1) bar(/D3) kgf/cm2(/D4) A
Span/Range -100 to
Range -14.5 to 29 -1 to 2 -1 to 2
Span 8 to 200kPa 1.16 to 29 0.08 to 2 0.08 to 2 200 kPa
A -100 to Span 0.1 to 2 14.5 to 290 1 to 20 1 to 20
Range -14.5 to 29 -1 to 2 -1 to 2 B
200 kPa Range -0.1 to 2 -14.5 to 290 -1 to 20 -1 to 20
Span 0.04 to 2 5.8 to 290 0.4 to 20 0.4 to 20 Span 0.5 to 10 72.5 to 1450 5 to 100 5 to 100
B C
Range -0.1 to 2 -14.5 to 290 -1 to 20 -1 to 20 Range -0.1 to 10 -14.5 to 1450 -1 to 100 -1 to 100
Span 0.2 to 10 29 to 1450 2 to 100 2 to 100 Span 5 to 50* 720 to 7200* 50 to 500* 50 to 500*
C D
Range -0.1 to 10 -14.5 to 1450 -1 to 100 -1 to 100 Range -0.1 to 50* -14.5 to 7200* -1 to 500* -1 to 500*
Span 1 to 50 145 to 7200 10 to 500 10 to 500 *: 70 MPa, 10150 psi, 700 bar or 700 kgf/cm2 when /HG is
D
Range -0.1 to 50 -14.5 to 7200 -1 to 500 -1 to 500 specified.
*: 70 MPa, 10150 psi, 700 bar or 700 kgf/cm2 when /HG is
EJX630A specified.
Measurement
MPa psi (/D1) bar (/D3) kgf/cm2(/D4)
Span/Range
Span 2 to 200 kPa 0.3 to 29 0.02 to 2 0.02 to 2
A -100 to 200
Range -14.5 to 29 -1 to 2 -1 to 2
kPa
Span 0.01 to 2 1.5 to 290 0.1 to 20 0.1 to 20
B
Range -0.1 to 2 -14.5 to 290 -1 to 20 -1 to 20
Span 0.05 to 10 7.3 to 1450 0.5 to 100 0.5 to 100
C
Range -0.1 to 10 -14.5 to 1450 -1 to 100 -1 to 100
50.8 to
Span 0.35 to 70 3.5 to 700 3.5 to 700
10150
D
-14.5 to
Range -0.1 to 70 -1 to 700 -1 to 700
10150
IM 01C25F01-01E
<9. General Specifications> 9-2
Output Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display
For 4 to 20 mA output
and Bar graph.
(Output signal code D, E and J)
The indicator is configurable to display one or
Two wire 4 to 20 mA DC output with digital
up to four of the following variables periodically.;
communications, linear or square root
Pressure in %, Scaled pressure, pressure in
programmable. BRAIN or HART FSK protocol
Engineering unit.
are superimposed on the 4 to 20 mA signal.
See Setting When Shipped for factory setting.
Output range: 3.6 mA to 21.6 mA
Output limits conform to NAMUR NE43 can be Burst Pressure Limits
pre-set by option C2 or C3. EJ510 and EJ530
Capsule Pressure
For 1 to 5 V output
(Output signal code Q) A, B, C 30 MPa (4350 psi)
Three or four wire low power 1 to 5 V DC output D* 132 MPa (19100 psi)
with HART, linear or square root programmable. *: 182 MPa (26300 psi) for EJA510E and EJA530E when
/HG is specified.
HART protocol is superimposed on the 1 to 5 V
DC signal. EJX610A and EJX630A
Output range: 0.9 V to 5.4 V DC Capsule Pressure
A, B, C 50 MPa (7200 psi)
Failure Alarm
D 182 MPa (26300 psi)
For 4 to 20 mA output
(Output signal code D, E and J)
Analog output status at CPU failure and Normal Operating Condition
hardware error; (Selected features may affect limits.)
Up-scale: 110%, 21.6 mA DC or more
Ambient Temperature Limits
(standard)
40 to 85C (40 to 185F)
Down-scale: 5%, 3.2 mA DC or less
30 to 80C (22 to 176F) with LCD display
For 1 to 5 V output
Process Temperature Limits
(Output signal code Q)
40 to 120C (40 to 248F)
Analog output status at CPU failure and
hardware error; Ambient Humidity Limits
Up-scale: 110%, 5.4 V DC or more 0 to 100% RH
(standard) Working Pressure Limits (Silicone oil)
Down-scale: 5%, 0.8 V DC or less
Maximum Pressure Limits
Damping Time Constant (1st order)
Amplifier damping time constant is adjustable Pressure
Capsule EJ510 EJ530
from 0 to 100.00 seconds and added to
A 200 kPa abs (29 psia) 200 kPa (29 psig)
response time.
Note: For BRAIN protocol type, when amplifier damping B 2 MPa abs (290 psia) 2 MPa (290 psig)
is set to less than 0.5 seconds, communication C 10 MPa abs (1450 psia) 10 MPa (1450 psig)
may occasionally be unavailable during the D* 50 MPa abs (7200 psia) 50 MPa (7200 psig)
operation, especially while output changes
dynamically. The default setting of damping *: 70 MPa(10150 psi) for EJA510E and EJA530E when
ensures stable communication. /HG is specified.
Pressure
Update Period Capsule EJX610A EJX630A
45 ms A 200 kPa abs (29 psia) 200 kPa (29 psi)
Zero Adjustment Limits B 2 MPa abs (290 psia) 2 MPa (290 psi)
Zero can be fully elevated or suppressed, within C 10 MPa abs (1450 psia) 10 MPa (1450 psi)
D 70 MPa abs (10150 psia) 70 MPa (10150 psi)
the lower and upper range limits of the capsule.
Minimum Pressure Limit
External Zero Adjustment
External Zero is continuously adjustable with See graph below
0.01% incremental resolution of span. Re-range
can be done locally using the digital indicator
with range-setting switch.
IM 01C25F01-01E
<9. General Specifications> 9-3
100(750) Pressure
Capsule EJX610A EJX630A
A 4 MPa abs (580 psia) 4 MPa (580 psi)
B 16 MPa abs (2300 psia) 16 MPa (2300 psi)
10(75)
C 25 MPa abs (3600 psia) 25 MPa (3600 psi)
D 105 MPa abs (15200 psia) 105 MPa (15200 psi)
Working 2.7(20)
pressure Applicable range
1(7.5) Supply & Load Requirements
kPa abs
(mmHg abs)
For output signal code D, E, and J.
0.13(1) (Optional features or approval codes may
0.1(0.75) affect electrical requirements.)
With 24 V DC supply, up to a 550 load can be
used. See graph below.
0.013(0.1)
0.01(0.075)
-40 0 40 80 120
(-40) (32) (104) (176) (248)
600
85 (185) E-10.5
Process temperature C(F) R=
F0901.ai
External 0.0244 Digital
load Communication
Figure 9.1 Working Pressure and Process range
resistance
Temperature [For EJ510 and BRAIN and HART
EJX610A]
250
R ()
Atmospheric
100(14.5)
pressure
Working
pressure 10.5 16.6 25.2 42
kPa abs Power supply voltage E (V DC)
(psia) F0903.ai
Applicable range
10(1.4) Figure 9.3 Relationship Between Power Supply
Voltage and External Load Resistance
2.7(0.38)
Supply Voltage
IM 01C25F01-01E
<9. General Specifications> 9-4
Load for 4 to 20 mA output EMC Conformity Standards
(Output signal code D, E and J) EN 61326-1 Class A, Table2 (For use in
0 to 1290 for operation industrial locations)
250 to 600 for digital communication EN 61326-2-3
EN 61326-2-5 (for Fieldbus)
Output Load for 1 to 5 V output
(Output signal code Q) Immunity influence during the test
1 M or greater (meter input impedance) Pressure: Output shift is specified within 1% of
1/20 Max span.
Communication Requirements
Static pressure: Output shift is specified within
(Safety approvals may affect electrical
2% of 1MPa span.
requirements.)
Status Output Line*: Continues to operate
BRAIN without reversal.
*: Only for /AL option.
Communication Distance
Up to 2 km (1.25 miles) when using CEV Condition for EMC test for FOUNDATION fieldbus
polyethylene-insulated PVC-sheathed cables. type: The shield of the cable and the case
Communication distance varies depending on are connected with a capacitor of 10nF.
type of cable used.
Physical Specifications
Load Capacitance
0.22 F or less Wetted Parts Materials
IM 01C25F01-01E
<9. General Specifications> 9-5
9.2 Model and Suffix Codes
Model Suffix Codes Description
EJX510A ...................... Absolute pressure transmitter
EJX530A ...................... Gauge pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC Output with digital communication (BRAIN protocol)
signal -E . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC Output with digital communication (HART protocol)
-J . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol,
refer to IM 01C25T04-01EN)
Measurement A . . . . . . . . . . . . . . . . . . . 8 to 200 kPa (1.16 to 29 psi)
span (capsule) B . . . . . . . . . . . . . . . . . . . 0.04 to 2 MPa (5.8 to 290 psi)
C . . . . . . . . . . . . . . . . . . . 0.2 to 10 MPa (29 to 1450 psi)
D . . . . . . . . . . . . . . . . . . . 1 to 50 MPa (145 to 7200 psi)
Wetted parts Process connector Diaphragm Others
material S . . . . . . . . . . . . . . . . . 316L SST Hastelloy C-276 *1 316L SST
H . . . . . . . . . . . . . . . . . Hastelloy C-276 *1 Hastelloy C-276 *1 Hastelloy C-276 *1
Process 4 . . . . . . . . . . . . . . . 1/2 NPT female
connections 7 . . . . . . . . . . . . . . . 1/2 NPT male
8 . . . . . . . . . . . . . . . G1/2 DIN 16 288 male *2
9 . . . . . . . . . . . . . . . M201.5 DIN 16 288 male *2
N . . . . . . . . . . . . . Always N
-0 . . . . . . . . . . . . Always 0
Amplifier housing 1 . . . . . . . . . . Cast aluminum alloy
2 . . . . . . . . . . ASTM CF-8M Stainless steel*4
3 . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
Electrical connection 0 . . . . . . . . G1/2 female, one electrical connection without blind plugs
2 . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . G1/2 female, two electrical connections with a blind plug
7 . . . . . . . . 1/2 NPT female, two electrical connections with a blind plug
9 . . . . . . . . M20 female, two electrical connections with a blind plug
A . . . . . . . . G1/2 female, two electrical connections with a 316SST blind plug
C . . . . . . . . 1/2 NPT female, two electrical connections with a 316SST blind plug
D . . . . . . . . M20 female, two electrical connections with a 316SST blind plug
Integral indicator D . . . . . . Digital indicator*5
E . . . . . . Digital indicator with the range setting switch (push button)*3
N . . . . . . None
Mounting bracket F . . . . . 304 SST 2-inch pipe mounting
L . . . . . 316 SST 2-inch pipe mounting
N . . . . . None
Optional codes / Optional specification
The marks indicate the most typical selection for each specification. Example: EJX530A-DAS4N-012NN/.
*1: Hastelloy C-276 or ASTM N10276.
*2: Not applicable for combination of capsule code D and wetted parts material code H.
*3: Not applicable for output signal code F.
*4: Not applicable for electrical connection code 0, 5, 7 and 9.
*5: Not applicable for output signal code G.
IM 01C25F01-01E
<9. General Specifications> 9-6
The marks indicates the most typical selection for each specification. Example: EJX630A-DAS4N-012NN/.
*1: Hastelloy C-276 or ASTM N10276.
*2: Not applicable for combination of capsule code D and wetted parts material code H.
*3: Not applicable for output signal code F.
*4: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant
facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid
can contaminate the userfs process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite,
and high-temperature steam (150C [302F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*5: Not applicable for electrical connection code 0, 5, 7 or 9.
*6: Material of a blind plug is aluminum alloy or 304 SST.
*7: Not applicable for output signal code G.
IM 01C25F01-01E
<9. General Specifications> 9-7
IM 01C25F01-01E
<9. General Specifications> 9-8
9.3 Optional Specifications
Item Description Code
Factory Mutual (FM) FM Explosionproof *1
Explosionproof for Class I, Division 1, Groups B, C and D
FF1
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
Hazardous (classified) locations, indoors and outdoors (NEMA 4X)
FM Intrinsically safe *1*3
Intrinsically Safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1,Groups E, F and G and Class III, Division 1 Hazardous Locations. FS1
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups F and G, Hazardous Locations.
Combined FF1 and FS1 *1*2 FU1
ATEX ATEX Flameproof *1
II 2G, 2D Ex d IIC T6...T4 Gb, Ex tb IIIC T85C Db KF22
Special fastener: ClassA2-50(A4-50) or more
ATEX Intrinsically safe Ex ia *1*2
KS21
II 1G, 2D Ex ia IIC T4 Ga, Ex ia IIIC T85C T100C T120C Db
Combined KF22, KS21 and ATEX Intrinsically safe Ex ic *1*3
KU22
Ex ic: II 3G Ex ic IIC T4 Gc
Canadian Standards CSA Explosionproof *1
Association (CSA) [For CSA C22.2]
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
[For CSA E60079]
CF1
Flameproof for Zone1, Ex d IIC T6...T4 Enclosure IP66/IP67
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
CSA Intrinsically safe *1 *2
[For CSA C22.2]
Intrinsically safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1, Groups E,F and G, Class III, Division 1
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups F and G, Class III, Division 1
CS1
[For CSA E60079]
Ex ia IIC T4, Ex nL IIC T4
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
Combined CF1 and CS1 *1*2 CU1
IECEx IECEx flameproof *1
Flameproof for Zone1, Ex d IIC T6...T4 Gb SF2
Special fastener: ClassA2-50(A4-50) or more
IECEx Intrinsically safe, type n and flameproof *1*2
Intrinsically safe and type n
Ex ia IIC T4, Ex nL IIC T4
SU2
Flameproof
Flameproof for Zone1, Ex d IIC T6...T4 Gb
Special fastener: ClassA2-50(A4-50) or more
IECEx Intrinsically safe and flameproof *1*2
Intrinsically safe
Ex ia IIC T4 Ga, Ex ic IIC T4 Gc
SU21
Flameproof
Flameproof for Zone1, Ex d IIC T6...T4 Gb
Special fastener: ClassA2-50(A4-50) or more
Combination of Approval Combination of KU22, FU1 and CU1 V1U1
IM 01C25F01-01E
<9. General Specifications> 9-9
Item Description Code
High Accuracy type *19 High accuracy HAC
Painting Color change Amplifier cover only P
Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Anti-corrosion coating*3 X2
316 SST exterior parts *4 316 SST name plate, tag plate and zero adjustment screw HC
Fluoro-rubber O-ring All O-rings of amplifier housing. Lower limit of ambient temperature: 15C (5F) HE
Lightning protector Transmitter power supply voltage:
10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type, 9 to 32 V DC for
Fieldbus communication type.) A
Allowable current: Max. 6000 A (140 s), Repeating 1000 A (140 s) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Status output *5 Transistor output (sink type)
AL
Contact rating: 10.5 to 30 VDC, 120 mA DC(max) Low level: 0 to 2 VDC
Oil-prohibited use Degrease cleansing treatment. K1
Degrease cleansing treatment with fluorinated oilfilled capsule.
K2
Operating temperature 20 to 80C( 4 to 176F)
Capsule fill fluid Fluorinated oil filled in capsule
K3
Operating temperature 20 to 80C( 4 to 176F)
Calibration units *6 P calibration (psi unit) D1
(See Table for Span and
bar calibration (bar unit) D3
Range Limits.)
M calibration (kgf/cm2 unit) D4
Output limits and failure Failure alarm down-scale: Output status at CPU failure and hardware error is
C1
operation *7 5%, 3.2 mA DC or less. *21
NAMUR NE43 Compliant Failure alarm down-scale: Output status at CPU
C2
Output signal limits: failure and hardware error is 5%, 3.2 mA DC or less.
3.8 mA to 20.5 mA *22 Failure alarm up-scale: Output status at CPU
C3
failure and hardware error is 110%, 21.6 mA or more.
Gold-plated diaphragm *15 Surface of isolating diaphragm is gold plated, effective for hydrogen permeation. A1
Wired tag plate 304 SST tag plate wired onto transmitter N4
Data configuration at Data configuration for HART Software damping, Descriptor, Message
CA
factory *8 communication type
Data configuration for BRAIN Software damping
CB
communication type
Advanced diagnostics *16 Multi-sensing process monitoring
Impulse line blockage detection *17 DG6
Heat trace monitoring
European Pressure PED 97/23/EC
Equipment Directive *18 Category: III, Module: H, Type of Equipment; Pressure Accessory-Vessel, PE3
Type of Fluid; Liquid and gas, Group of Fluid: 1 and 2
Material Certificate *9 Process connector M15
Pressure test/ Test Pressure: 200 kPa (2 kgf/cm2) *10 T05
Leak test certificate Test Pressure: 2 MPa (20 kgf/cm2) *11 T06
Test Pressure: 10 MPa (100 kgf/cm2) *12 Nitrogen(N2) Gas or Water *14 T07
Retention time: one minute
Test Pressure: 50 MPa (500 kgf/cm2) *13 T08
Test Pressure: 70 MPa (10150 psi) *20 T15
High pressure-proof Maximum working pressure: 70MPa.
HG
structure*
Contact Yokogawa representative for the codes indicated as -.
*1: Applicable for Electrical connection code 2, 4, 7, and 9.
*2: Not applicable for option code /AL.
*3: Not applicable with color change option.
*4: This specification is included when amplifier case code 2 is specified.
*5: Check/External indicator terminals cannot be used when this option code is specified. Not applicable for output signal code F.
*6: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1, D3, and D4.
*7: Applicable for output signal codes D, E and J. The hardware error indicates faulty amplifier or capsule.
*8: Also see Ordering Information.
IM 01C25F01-01E
<9. General Specifications> 9-10
*9: Material traceability certification, per EN 10204 3.1B.
*10: Applicable for capsule code A.
*11: Applicable for capsule code B.
*12: Applicable for capsule code C.
*13: Applicable for capsule code D of EJ510 and EJ530.
*14: Pure nitrogen gas or pure water is used for oil-prohibited use (option codes K1 and K2).
*15: Applicable for wetted parts material code S.
*16: Applicable only for output signal code -E and -J.
*17: The change of pressure fluctuation is monitored and then detects the impulse line blockage. See TI 01C25A31-01E for detailed
technical information required for using this function.
*18: Applicable for measurement span code D. If compliance with category III is needed, specify this option code.
*19: Applicable for EJX630A, EJA510E and EJA530E.
Not applicable for the combination of measurement span code A and wetted parts material code H.
Not applicable for option code K2, K3 or A1.
When specified range value includes minus value for A capsule, the accuracy shall be the standard accuracy even if high accuracy
option (/HAC) is specified.
*20: Applicable for capsule code D of EJX610A and EJX630A. Applicable also for EJA510E and EJA530E with /HG.
*21: Output status at CPU failure and hardware error is 5%, 0.8V DC or less for output signal code Q.
*22: The 1 to 5 V voltage output corresponding to 4 to 20 mA current output is applied to output signal code Q which is non-compliant to
NAMUR NE43.
*23: Applicable for capsule code D of EJA510E and EJA530E.
9.4 Dimensions
(2.76)
70
126(4.96)
110(4.33)
54
159(6.26)
(2.13)
(6.50)
165
6
(0.24)
Ground terminal
Open to
Electrical connection atmosphere*1
for code 5, 9, A, and D.
(6.77)
172
6
5(0.20)
(0.24)
F0904.ai
IM 01C25F01-01E
<9. General Specifications> 9-11
IM 01C25F01-01E
i
Revision Information
Title : Absolute Pressure and Gauge Pressure Transmitters
EJ510, EJ530, EJX610A and EJX630A
Manual No. : IM 01C25F01-01E
IM 01C25F01-01E