STEEL BEAM DESIGN

The flow chart below can be used as a guide to design a steel beam
member.

HJ ROSLAN BIN KOLOP 1


PUSAT PENGAJIAN DIPLOMA
1.0 Initial Section Selection

Since bending is the critical mode of failure for most beam,


therefore bending theory is used for initial section selection.

To avoid bending failure:

Design moment < Moment capacity of section


M < Mc (1)

where Mc = pyS (2)

py = design strength of steel


S = plastic modulus of section

Combine (1) and (2) give:

S > M/py

Select from steel tables for S greater than the calculated


value.

2.0 Classification of Section

The selected section is classified for the purpose of:

1. To identify if the section can sustain the formation of


plastic hinge thick flange and web.

HJ ROSLAN BIN KOLOP 2


PUSAT PENGAJIAN DIPLOMA
Thin flange and slender web usually fail by local buckling
before yield stress is achieved.
2. To know the moment capacity or the section moment of
resistance.

Clause 3.5.2 : Four classes of section.

Class 1 : Plastic cross sections. Plastic hinge can be developed


with significant rotation capacity(see graph below). If plastic
design method is used in structural analysis, this class must be
used.

HJ ROSLAN BIN KOLOP 3


PUSAT PENGAJIAN DIPLOMA
Class 2 : Compact. Full plastic moment capacity can be
developed, but local buckling may prevent the development of
plastic hinge with sufficient rotation capacity to permit plastic
design.

Class 3 : Semi-compact. Can develop elastic moment capacity


but local buckling prevent the development of full plastic
moment.

Class 4: Slender. Slender element subjected to compression due


to moment or axial load. Local buckling prevent full elastic
moment capacity to develop.

Limiting width to thickness ration for elements for the above


classes are given in Table 11, BS5950.

HJ ROSLAN BIN KOLOP 4


PUSAT PENGAJIAN DIPLOMA
Once the section has been classified, the various strength check
can be carried out to assess its suitability.

CONTOH

Semak kelas keratan 305 x 102 x 33 UB,py=275 N/mm2

Dari Jadual Keluli, B=102.4mm, T=10.8mm,t=6.6mm


d = (275.8 2x7.6) =260.6
b= 102.4/2 = 51.2mm
Dari jadual 7, BS5950
= (275/275)0.5 = 1

b/T = 51.3/10.8 = 4.8 < 9


d/t = 260.6/6.6 = 39.5 <80

HJ ROSLAN BIN KOLOP 5


PUSAT PENGAJIAN DIPLOMA
Berdasarkan jadual di atas keratan adalah plastik.

3.0 Strength Check:

Shear

Clause 4.2.3 : The shear force, Fv, should not exceed the shear
capacity, Pv

Fv Pv .(3)

Where Pv = 0.6 pyAv ..(4)

(Assuming that the web carries the shear force alone)

Av = shear area ( = tD for I, H and channel section)

HJ ROSLAN BIN KOLOP 6


PUSAT PENGAJIAN DIPLOMA
Clause 4.2.3: when buckling ratio (d/t) > 70 (see equation 4.4)
web should be additionally checked for shear buckling.

MOMENT CHECK

(1) Low shear and Moment Capacity

Clause 4.2.1.1 : At critical points the combination of


(i) maximum moment and co-existent shear
(ii) maximum shear and co-existent moment
should be checked.

If shear force Fv < 0.6Pv, this is called low shear load.

If 0.6Pv < Fv <Pv then this is called high shear load.

HJ ROSLAN BIN KOLOP 7


PUSAT PENGAJIAN DIPLOMA
For low shear load, the moment capacity of the section is
calculated using clause 4.2.5.2 :

For Class 1 Plastic or Class 2 compact, the moment capacity is:

Mc = py S 1.2 py Z .(5)

py - design strength of the steel


S - plastic modulus
Z - section modulus

Additional check i.e ( Mc 1.2pyZ) is to guard against plastic


deformation under serviceability loads and is applicable to
simply supported and cantilever beams. Other beam the limit
is 1.5pyZ.

For class 3 Semi-compact:

Mc = py Z . (6)
Or Mc = pySeff 1.2pyZ .(7)

Seff effective plastic modulus (clause 3.5.6)

For class 4 Slender,


Mc = pyZeff .(8)

Zeff - effective section modulus (clause 3.6.2)

Note: Nearly all sections in grade S275 steel are plastic, only a
few sections in higher strength are semi compact. No British
rolled UB section in pure bending are slender or plastic/compact
flanges and semi-compact webs]

HJ ROSLAN BIN KOLOP 8


PUSAT PENGAJIAN DIPLOMA
EXAMPLE 1

A simply supported UB steel beam of 10 m span support loads as shown


below. Assuming that the beam is laterally supported find the suitable UB
cross section that suits the shear and bending moment requirement.

5m 30 kN (imposed load)
5kN/m (dead load)
5 kN/m (imposed load)

10m
RA RB

Answer:

1. Calculate the design shear and bending moment.

Total design load = (1.6 x 30) + (1.4 x 5 + 1.6x5)10


= 48 + 15 x 10 = 198 kN

Due to symmetry,
RA = RB= 198/2 = 99 kN

Mid span moment, M = Wl/4 + wl2/8


= (48x10) + (15x102)
4 8
= 120 + 187.5 = 307.5 kNm

HJ ROSLAN BIN KOLOP 9


PUSAT PENGAJIAN DIPLOMA
2. Initial cross-section

Assume py = 275 N/mm2

Sx > M/py = 307.5 x 106/275 = 1.118 x 106 mm3 = 1118 cm3

From steel table, the following cross-section can be used:

1. 356 x 171 x 67 UB : Sx = 1210 cm3


2. 406 x 178 x 60 UB : Sx= 1200 cm3
3. 457 x 152 x 60 UB: Sx = 1290 cm3

Selection is based on economy or engineering consideration. If


lighter section is required that section no. 3 is chosen. If depth
consideration is important than section No. 1 is chosen.

Say we select section No. 2


406 x 178 x 60 UB : Sx= 1200 cm3

3. Classification

Strength classification: T = 12.8(<16mm) therefore py=275


N/mm2 (Table 9) dan = (275/py)1/2 = 1 (Table 11)

Section classification:
b/T = 6.95 < 9 plastic (Table 11)
d/t = 46.2 < 80 plastic (Table 11)

Therefore the section 406 x 178 x 60 (UB) is class 1 plastic.

HJ ROSLAN BIN KOLOP 10


PUSAT PENGAJIAN DIPLOMA
4. Shear Force

d/t = 46.2 <70 therefore check on shear buckling is not required.


(clause 4.2.3)

The capacity of section, Pv = 0.6pyA = 0.6 pytD


= 0.6 x 275 x 7.9 x 406.4
= 523 kN>99(Fv)

(Reaction), Fv (99kN) < 0.6Pv

= 0.6 x 523 = 314 kN


(Low shear case) Clause 4.2.5

5. Momen lentur

Since the condition is low shear,


Mc = py S = 275 x 1200 x 103
= 327 kNm
< 1.2pyZ
=1.2x275x1060x103 = 349.8 kNm OK

Design moment not including self weight = 307.5 kNm.

Bending moment due to self weight :

Msw = 1.4(60x9.81/103)102/8 = 10.3 kNm

Total moment (r/b) = 307.5 + 10.3 = 317.8 kNm < 327 kNm.

Therefore the section is suitable.

HJ ROSLAN BIN KOLOP 11


PUSAT PENGAJIAN DIPLOMA
(2) High Shear and Moment Capacity

Fv > 0.6Pv (high shear load), then the moment carrying


capacity of the section is reduced.
This is because the web cannot take the full tensile or
compressive stresses associated with bending moment as well as
a substantial shear stress due to shear load.

Clause 4.2.5.3: Moment capacity should be calculated using:

Class 1 plastic and compact:


Mc = py (S Sv)

Where, =[ 2(Fv/Pv 1]2

Sv = tD2/4 (plastic modulus of shear area)

Note: The effect of factor is to reduce the moment carrying


capacity of the web as the shear load rises from 50 to 100% of
the web shear capacity. However, the resulting moment
capacity is negligible when Fv < 0.6Pv.

EXAMPLE 2

A steel cantilever beam is encased in a concrete wall and is


subjected to the load shown. Choose a suitable UB that fulfill
the criteria for of moment and shear.
450 kN (total dead load)
270 kN (total imposed load)

1m

HJ ROSLAN BIN KOLOP 12


PUSAT PENGAJIAN DIPLOMA
A

Solution:

Design shear (Fv) = (1.4x450) + (1.6x270) = 1062 kN

Design momen at A = Wl/2 = 1062x1/2 = 531 kNm

Initial sizing:
Assume py=275 N/mm2

Sx > M/py = 531x106/275 = 1931 cm3

From Table of steel properties, the suitable size are:

1. 457x191x89 UB: Sx = 2010 cm3,.


2. 533 x 210 x 82 UB: Sx = 2060 cm3,

Classification of section shown that the section is plastic.

Shear strength :

Try section No.2, Pv = 0.6pytD = 0.6 x 275 x 9.6 x 528.3


= 837 kN < 1062 (Fv) kN not OK.

Try a new section where the shear strength is more critical


than the bending strength.

Try 610 x 229 x 113 UB:Sx=3290 cm3,py=265,plastic

Pv = 0.6 x 265 x 607.3 x 11.2


= 1081 kN > Fv O.K

HJ ROSLAN BIN KOLOP 13


PUSAT PENGAJIAN DIPLOMA
But,

Fv > 0.6x1081(Pv)=648.6 kN high shear Clause 4.2.6

Calculate Moment capacity from clause 4.2.5.3:

=[ 2(Fv/Pv 1]2 = {2(1062/1081) 1}2 =0.93

Mc = py(Sx -Sv )

= 265[3290x103 (11.2 x 607.32/4)0.93] =617 kNm

Moment from self weight: Mbk =1.4(113x9.81/103)12/2 = 0.8


kNm

Total moment, Mj =Mbk + M = 531 + 0.8 =532 kNm < Mc

Therefore the section is suitable

Deflection

Check for maximum deflection using combination of


unfactored imposed serviceability loading.

Clause 2.5.2 and Table 8 outlined recommended limits to these


deflections to avoid significant damage to the structure and
finishes. Standard formula or other method such as Area-
moment, Macaulay etc can be used to calculate deflection.

HJ ROSLAN BIN KOLOP 14


PUSAT PENGAJIAN DIPLOMA
Standard formula:

CONTOH 3

Calculate the deflection of the beam in example 1 and 2.

From Example 1.

mak = 5wL4/384EI + WL3/48EI

= 5x5x104 + 30x103
384x205x106x21500x10-8 48x205x106x21500x10-8
= 0.0148 + 0.0142 = 0.029 m = 29 mm

From Table 4.5, the maximum allowable is span/360 = 10


000/360 = 27.8 mm for beam carrying plaster and brittle
finishing. It can been seen that the calculated deflection is
HJ ROSLAN BIN KOLOP 15
PUSAT PENGAJIAN DIPLOMA
bigger than the allowable deflection therefore deeper cross-
section is recommended.

If other than the specified beam is used, the allowable


deflection is span/200.

= 10000/200 = 50 mm which is OK.

From example 2,

mak = wL4/8EI = 270 x 14


8 x 205 x106x 87400 x10-8
= 0.00019 m = 0.19mm

From Table 4.5, the allowable deflection is span/180


= 1000/180 = 5.6mm

Deflection OK

HJ ROSLAN BIN KOLOP 16


PUSAT PENGAJIAN DIPLOMA
WEB BEARING AND WEB BUCKLING

Clause 4.5. The web bearing capacity and web buckling


resistance should be performed when unstiffened webs are
subjected to high concentration locals loads or reactions that
act through the web and flange of the beam.

Stiffeners should be provided if the strength of the


unstiffened web is not sufficient.

Web Bearing Resistance

Figure below shows how concentrated load transmitted


through the flange/web connection in the span, and at supports
when the distance to the end of the member from the end of the
stiff bearing is zero.

HJ ROSLAN BIN KOLOP 17


PUSAT PENGAJIAN DIPLOMA
Clause 4.5.2.1 gives the bearing resistance Pbw calculated at the
flange/web connection for unstiffened web as:

Pbw = (b1 + nk) tpyw

Where:

b1 _ stiff bearing length

Clause 4.5.1.3 (Fig 13) shows cases of stiff bearing length that
can be calculated using the formula given.

HJ ROSLAN BIN KOLOP 18


PUSAT PENGAJIAN DIPLOMA
n as shown in Fig (a): n =5 except at the end of a
member and n = 2 + 0.6be/k 5 at the end of the
member.
be Distance to the end of the member from the end of the
stiff bearing Fig (b).
k = (T + r) from rolled I or H sections
T thickness of the flange
t web thickness
pyw design strength of web

The formula is a simple check to ensure the stress at critical


point on flange/web connection is less than the strength of
steel.

Check also the contact stresses between load or support and


flange do not exceed py.

HJ ROSLAN BIN KOLOP 19


PUSAT PENGAJIAN DIPLOMA
Web buckling

Clause 4.5.3.1 : provided the distance e from the concentrated


load or reaction from the nearer end of the member is at least
0.7d, and if the flange through which the load or reaction is
applied is effectively restrained against both:
(a) rotation relative to the web
(b) lateral movement relative to the other flange (Fig
below)

the buckling resistance of an unstiffened web is given by:

Px = 25tPbw /(b1 + nk)d

Or if e < 0.7d, the buckling resistance of unstiffened web is


given by:

Px = (e + 0.7d).25t.Pbw/ 1.4d(b1 + nk)d

If the flange is not restrained against rotation and/or lateral


movement the buckling resistance of the web is reduced to:

HJ ROSLAN BIN KOLOP 20


PUSAT PENGAJIAN DIPLOMA
Pxr = 0.7d.Px/Le

Where Le is the effective length of the web determine using


Table 22.

Example:

Check web bearing and buckling for Example 1, assuming the


beam sits on stiff bearing length, b1 of 100 mm at each end.
(406x178x60, d = 360.4, r =10.2, T=12.8,t=7.9)

Ans:

Bearing capacity:
Pbw = (b1 + nk) tpyw
= (100 + 2 x 23) 7.8 x 275
= 313 kN > 99 kN OK

where k = T + r = 12.8 + 10.2 = 23 mm


n = 2 + 0.6be/k = 2 (since be =0)

Contact Stress At Supports

Pcs = (b1 x 2(r + T))py = (100 x 46) x 275


= 1265 kN > 99 kN OK

HJ ROSLAN BIN KOLOP 21


PUSAT PENGAJIAN DIPLOMA
Web Buckling at Support

Since e (=50mm) < 0.7d = 0.7 x 360.5 = 252 mm, buckling


resistance of web is:
Px = (e + 0.7d).25t.Pbw/ 1.4d(b1 + nk)d

= (50 + 252) x 25 x 1 x 7.8 x 313


1.4 x 360.5 (100 + 2 x 23) 360.5
= 159 kN> 99 kN OK

No web stiffners are required at supports.

Example

Compute the bearing capacity, Pbw and the buckling capacity,


Px of unstiffened web of a beam subjected to a concentrated
load of 200 kN as shown below. Assume steel grade of S275.

HJ ROSLAN BIN KOLOP 22


PUSAT PENGAJIAN DIPLOMA
Solutions:

For 305 x 127 UB 37,


t = 7.2 mm
T=10.7 mm
r = 8.9 mm (root radius)

For 686x 254 UB 170 section


t = 14.5 mm
T= 23.7 mm
r = 15.2 mm
d = 615 mm

HJ ROSLAN BIN KOLOP 23


PUSAT PENGAJIAN DIPLOMA
CHECK WEB BEARING

Bearing capacity for web, Pbw = (b1 + nk) tpyw

where b1 = t + 1.6r + 2T (FIG. 13 for secondary beam)


= 7.2 + 1.6x8.9 + 2x10.7 = 42.8 mm

n=5 (except at end of member)

k = T + r = 23.7 + 15.2 = 38.9 mm


Pbw = (b1 + nk) tpyw
= (42.8 + 5x38.9)x14.5 x 275 x 10-6
= 946 kN > 200 kN OK

Buckling Capacity Check

Since e > 0.7d, use Px = 25tPbw /(b1 + nk)d


= 25 x 1 x 14.5 x 946 / (42.8 + 5x38.9)615
= 898 kN > 200 kN OK

No stiffeners is needed.

HJ ROSLAN BIN KOLOP 24


PUSAT PENGAJIAN DIPLOMA
Tutorial

Q1 The beam shown below is fully restrained along its length


and has a stiff bearing of 75 mm at the supports. The beam
supports a secondary beam at the centre of its length. The
characteristic loads acting on the beams are shown. Design
the beam using S275 steel. The secondary beam is supported
by a bearing plate which has 50 mm stiff bearing length on
the top flange of the beam.

Q2 The figure below shows a layout plan of a floor. The floor


slabs are of precast concrete. The characteristic loadings on
the floor are as follows:

Self weight = 3.5 kN/m2


Floor finishing = 1.0 kN/m2
Imposed load = 3.0 kN/m2

Design beam 2/A-C using S275 steel assuming the beam is


fully restrained. The beam is supported by angles

HJ ROSLAN BIN KOLOP 25


PUSAT PENGAJIAN DIPLOMA
120x120x15 mm at both ends. The self-weight of the beam is
assumed as 0.7 kN/m.

(i) Assume a trial section.


(ii) Classify the section
(iii) Check the shear capacity at support
(iv) Check moment capacity
5wd L4 Wi a 2 b 2

(v) Check deflection given: 384 EI 3EIL

(vi) Check bearing and buckling at support.

HJ ROSLAN BIN KOLOP 26


PUSAT PENGAJIAN DIPLOMA
HJ ROSLAN BIN KOLOP 27
PUSAT PENGAJIAN DIPLOMA