You are on page 1of 11

PROJECT : - 1x 63 MW TPP AT KORBA,CHATTISGARH

CLIENT :- S V POWER PVT LTD


CLIENT'S CONSULTANT :- DESEIN PVT LTD
E-BOP CONTRACTOR :- ABB LTD,FARIDABAD

LIGHTNING PROTECTION CALCULATION FOR TG BLDG.AB-BC BAY


( REFERENCE : IS 2309 )
Symbol / Formulae /
Description / Parameter Value Unit
References
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
i) Input Data :-
a) Dimensions of Building / Structure
Length of the Building L ( Refer the Relevant Layout = 60.00 m
Width of the Building W Drawings of the Building / = 28.00 m
Height of the Building H Structure ) = 23.00 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N ( Refer Fig. 1 of IS 2309 ) = 100 No. of Days / Year
( Refer Clause 8.1.2 of
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 9.2 Nos./km2/year
IS 2309 )
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
( Type of
Weighting Factor B B ( Refer Table 1B of IS 2309 ) = 0.8
Construction )
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
(L x W) + 2 (L x H) +
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac = = 7389.06 Meter2
2(W x H) + 3.14 H2
Probable Number of Strikes to Building / Structure per Year
P = Ac x Ng x 10-6 times/year = 0.067979 Times per year
( Refer Clause 8.1.2 of IS 2309 )
Overall Multiplying Factor = AxBxCxDxE = 0.096000
Overall Multiplying = 0.006526
Overall Risk Factor Calculated Rf-C =
Factor x P ie 6.5260E-03
iii) Maximum Acceptable Overall Risk Factor:-
( Refer Clauses 8.1.3 & = 0.000001
Maximum Acceptable Overall Risk Factor Rf-A
8.1.6 of IS 2309 ) ie 1.000E-06
iv) Result / Conclusion :-
Since Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
(Applicable if Provision for Lightning Protection is needed)
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = ( L x W ) = 1680 Meter2
Perimeter of Structure P = 2(L+W) = 176 Meter
i) For Base Area (Ab) < 100m 2

a) Number of Down Conductors Required = For Ab < 100m2 = 1 Nos


ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
Number of Down Conductors Required = 1+(Ab-100)/300 = 6 Nos
c) Based on Parimeter of Structure:-
Number of Down Conductors Required = P/30 = 6 Nos.
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Hence, Required Number of Down Conductors = 6 Nos.

Rev. Date Drg/Doc. No. Remarks Prepared Reviewed Approved


REVISION
DETAILS

R0 12.10.2009 3VYN855200 First Submission HK KVP KVP


PROJECT : - 1x70 MW TPP AT KORBA,CHATTISGARH
CLIENT :- RRVUNL
CONSULTANT :- DCPL, New Delhi
BOP CONTRACTOR :- Indure, New Delhi

LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR CW PUMP HOUSE

Symbol / Formulae /
Description / Parameter Value Unit
References
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
i) Input Data :-
a) Dimensions of Building / Structure
Length of the Building L ( Refer the Relevant Layout = 43.62 m
Width of the Building W Drawings of the Building / = 12.20 m
Height of the Building H Structure ) = 17.53 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N ( Refer Fig. 1 of IS 2309 ) = 27 No. of Days / Year
( Refer Clause 8.1.2 of
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km2/year
IS 2309 )
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
( Type of
Weighting Factor B B ( Refer Table 1B of IS 2309 ) = 0.2
Construction )
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
(L x W) + 2 (L x H) +
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac = = 3452.79 Meter2
2(W x H) + 3.14 H2
Probable Number of Strikes to Building / Structure per Year
P = Ac x Ng x 10-6 times/year = 0.017264 Times per year
( Refer Clause 8.1.2 of IS 2309 )
Overall Multiplying Factor = AxBxCxDxE = 0.024000
Overall Multiplying = 0.000414
Overall Risk Factor Calculated Rf-C =
Factor x P ie 4.1434E-04
iii) Maximum Acceptable Overall Risk Factor:-
( Refer Clauses 8.1.3 & = 0.000001
Maximum Acceptable Overall Risk Factor Rf-A
8.1.6 of IS 2309 ) ie 1.000E-06
iv) Result / Conclusion :-
Since Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
(Applicable if Provision for Lightning Protection is needed)
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = ( L x W ) = 532.10 Meter2
Perimeter of Structure P = 2(L+W) = 111.63 Meter
i) For Base Area (Ab) < 100m 2

a) Number of Down Conductors Required = For Ab < 100m2 = 1 Nos


ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
Number of Down Conductors Required = 1+(Ab-100)/300 = 2 Nos
c) Based on Parimeter of Structure:-
Number of Down Conductors Required = P/30 = 4 Nos.
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Hence, Required Number of Down Conductors = 2 Nos.

Rev. Date Drg/Doc. No. Remarks Prepared Reviewed Approved


REVISION
DETAILS

R0 30.06.2009 3VYN855200 First Submission RK PS PAS


PROJECT : - 1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
CLIENT :- RRVUNL
CONSULTANT :- DCPL, New Delhi
BOP CONTRACTOR :- Indure, New Delhi

LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR CW TREATMENT AREA

Symbol / Formulae /
Description / Parameter Value Unit
References
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
i) Input Data :-
a) Dimensions of Building / Structure
Length of the Building L ( Refer the Relevant Layout = 40.23 m
Width of the Building W Drawings of the Building / = 30.23 m
Height of the Building H Structure ) = 5.00 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N ( Refer Fig. 1 of IS 2309 ) = 27 No. of Days / Year
( Refer Clause 8.1.2 of
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km2/year
IS 2309 )
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
( Type of
Weighting Factor B B ( Refer Table 1B of IS 2309 ) = 0.2
Construction )
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
(L x W) + 2 (L x H) +
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac = = 1999.25 Meter2
2(W x H) + 3.14 H2
Probable Number of Strikes to Building / Structure per Year
P = Ac x Ng x 10-6 times/year = 0.009996 Times per year
( Refer Clause 8.1.2 of IS 2309 )
Overall Multiplying Factor = AxBxCxDxE = 0.024000
Overall Multiplying = 0.000240
Overall Risk Factor Calculated Rf-C =
Factor x P ie 2.3991E-04
iii) Maximum Acceptable Overall Risk Factor:-
( Refer Clauses 8.1.3 & = 0.000001
Maximum Acceptable Overall Risk Factor Rf-A
8.1.6 of IS 2309 ) ie 1.000E-06
iv) Result / Conclusion :-
Since Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
(Applicable if Provision for Lightning Protection is needed)
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = ( L x W ) = 1216.15 Meter2
Perimeter of Structure P = 2(L+W) = 140.92 Meter
i) For Base Area (Ab) < 100m 2

a) Number of Down Conductors Required = For Ab < 100m2 = 1 Nos


ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
Number of Down Conductors Required = 1+(Ab-100)/300 = 5 Nos
c) Based on Parimeter of Structure:-
Number of Down Conductors Required = P/30 = 5 Nos.
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Hence, Required Number of Down Conductors = 5 Nos.

Rev. Date Drg/Doc. No. Remarks Prepared Reviewed Approved


REVISION
DETAILS

R0 30.06.2009 3VYN855200 First Submission RK PS PAS


PROJECT : - 1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
CLIENT :- RRVUNL
CONSULTANT :- DCPL, New Delhi
BOP CONTRACTOR :- Indure, New Delhi

LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR RAW WATER PUMP HOUSE

Symbol / Formulae /
Description / Parameter Value Unit
References
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
i) Input Data :-
a) Dimensions of Building / Structure
Length of the Building L ( Refer the Relevant Layout = 33.30 m
Width of the Building W Drawings of the Building / = 8.60 m
Height of the Building H Structure ) = 10.70 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N ( Refer Fig. 1 of IS 2309 ) = 27 No. of Days / Year
( Refer Clause 8.1.2 of
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km2/year
IS 2309 )
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
( Type of
Weighting Factor B B ( Refer Table 1B of IS 2309 ) = 0.2
Construction )
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
(L x W) + 2 (L x H) +
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac = = 1542.54 Meter2
2(W x H) + 3.14 H2
Probable Number of Strikes to Building / Structure per Year
P = Ac x Ng x 10-6 times/year = 0.007713 Times per year
( Refer Clause 8.1.2 of IS 2309 )
Overall Multiplying Factor = AxBxCxDxE = 0.024000
Overall Multiplying = 0.000185
Overall Risk Factor Calculated Rf-C =
Factor x P ie 1.8510E-04
iii) Maximum Acceptable Overall Risk Factor:-
( Refer Clauses 8.1.3 & = 0.000001
Maximum Acceptable Overall Risk Factor Rf-A
8.1.6 of IS 2309 ) ie 1.000E-06
iv) Result / Conclusion :-
Since Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
(Applicable if Provision for Lightning Protection is needed)
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = ( L x W ) = 286.38 Meter2
Perimeter of Structure P = 2(L+W) = 83.8 Meter
i) For Base Area (Ab) < 100m 2

a) Number of Down Conductors Required = For Ab < 100m2 = 1 Nos


ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
Number of Down Conductors Required = 1+(Ab-100)/300 = 2 Nos
c) Based on Parimeter of Structure:-
Number of Down Conductors Required = P/30 = 3 Nos.
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Hence, Required Number of Down Conductors = 2 Nos.

Rev. Date Drg/Doc. No. Remarks Prepared Reviewed Approved


REVISION
DETAILS

R0 30.06.2009 3VYN855200 First Submission RK PS PAS


PROJECT : - 1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
CLIENT :- RRVUNL
CONSULTANT :- DCPL, New Delhi
BOP CONTRACTOR :- Indure, New Delhi

LIGHTNING PROTECTION CALCULATION ( Reference : IS 2309 ) for RWPH MCC Room

Description / Parameter Symbol / Formulae / References Value Unit


A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
i) Input Data :-
a) Dimensions of Building / Structure
Length of the Building L ( Refer the Relevant Layout = 22.80 m
Width of the Building W Drawings of the Building / = 9.81 m
Height of the Building H Structure ) = 5.00 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N ( Refer Fig. 1 of IS 2309 ) = 27 No. of Days / Year
(Refer Clause 8.1.2 of
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km2/year
IS 2309)
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
( Type of
Weighting Factor B B ( Refer Table 1B of IS 2309 ) = 0.2
Construction )
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
(L x W) + 2 (L x H) +
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac = = 628.27 Meter2
2(W x H) + 3.14 H2
Probable Number of Strikes to Building / Structure per Year
P = Ac x Ng x 10-6 times/year = 0.003141 Times per year
( Refer Clause 8.1.2 of IS 2309 )
Overall Multiplying Factor = AxBxCxDxE = 0.024000
Rf-C Overall Multiplying Factor = 0.000075
Overall Risk Factor Calculated =
xP ie 7.5392E-05
iii) Maximum Acceptable Overall Risk Factor:-
Rf-A ( Refer Clauses 8.1.3 & = 0.000001
Maximum Acceptable Overall Risk Factor
8.1.6 of IS 2309 ) ie 1.000E-06
iv) Result / Conclusion :-
Since Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
(Applicable if Provision for Lightning Protection is needed)
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = ( L x W ) = 223.67 Meter2
Perimeter of Structure P = 2(L+W) = 65.22 Meter
i) For Base Area (Ab) < 100m 2

a) Number of Down Conductors Required = For Ab < 100m2 = 1 Nos


ii) For Base Area (Ab) > 100m 2

b) Based on Base Area of Structure:-


Number of Down Conductors Required = 1+(Ab-100)/300 = 1 Nos
c) Based on Parimeter of Structure:-
Number of Down Conductors Required = P/30 = 2 Nos.
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Hence, Required Number of Down Conductors = 1 Nos.

Rev. Date Drg/Doc. No. Remarks Prepared Reviewed Approved


REVISION
DETAILS

R0 30.06.2009 3VYN855200 First Submission RK PS PAS


PROJECT : - 1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
CLIENT :- RRVUNL
CONSULTANT :- DCPL, New Delhi
BOP CONTRACTOR :- Indure, New Delhi

LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR PRIMARY CRUSHER HOUSE

Description / Parameter Symbol / Formulae / References Value Unit


A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
i) Input Data :-
a) Dimensions of Building / Structure
Length of the Building L ( Refer the Relevant Layout = 23.00 m
Width of the Building W Drawings of the Building / = 21.50 m
Height of the Building H Structure ) = 21.70 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N ( Refer Fig. 1 of IS 2309 ) = 27 No. of Days / Year
(Refer Clause 8.1.2 of
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km2/year
IS 2309)
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
( Type of
Weighting Factor B B ( Refer Table 1B of IS 2309 ) = 0.2
Construction )
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
(L x W) + 2 (L x H) +
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac = = 3904.39 Meter2
2(W x H) + 3.14 H2
Probable Number of Strikes to Building / Structure per Year
P = Ac x Ng x 10-6 times/year = 0.019522 Times per year
( Refer Clause 8.1.2 of IS 2309 )
Overall Multiplying Factor = AxBxCxDxE = 0.024000
Rf-C Overall Multiplying Factor = 0.000469
Overall Risk Factor Calculated =
xP ie 4.6853E-04
iii) Maximum Acceptable Overall Risk Factor:-
( Refer Clauses 8.1.3 & = 0.000001
Maximum Acceptable Overall Risk Factor Rf-A
8.1.6 of IS 2309 ) ie 1.000E-06
iv) Result / Conclusion :-
Since Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
(Applicable if Provision for Lightning Protection is needed)
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = ( L x W ) = 494.50 Meter2
Perimeter of Structure P = 2(L+W) = 89 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = For Ab < 100m2 = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
Number of Down Conductors Required = 1+(Ab-100)/300 = 2 Nos
c) Based on Parimeter of Structure:-
Number of Down Conductors Required = P/30 = 3 Nos.
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Hence, Required Number of Down Conductors = 2 Nos.

Rev. Date Drg/Doc. No. Remarks Prepared Reviewed Approved


REVISION
DETAILS

R0 30.06.2009 3VYN855200 First Submission RK PS PAS


PROJECT : - 1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
CLIENT :- RRVUNL
CONSULTANT :- DCPL, New Delhi
BOP CONTRACTOR :- Indure, New Delhi

LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR SECONDARY CRUSHER HOUSE

Description / Parameter Symbol / Formulae / References Value Unit


A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
i) Input Data :-
a) Dimensions of Building / Structure
Length of the Building L ( Refer the Relevant Layout = 38.00 m
Width of the Building W Drawings of the Building / = 17.40 m
Height of the Building H Structure ) = 24.20 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N ( Refer Fig. 1 of IS 2309 ) = 27 No. of Days / Year
(Refer Clause 8.1.2 of
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km2/year
IS 2309)
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
( Type of
Weighting Factor B B ( Refer Table 1B of IS 2309 ) = 0.2
Construction )
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
(L x W) + 2 (L x H) +
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac = = 5181.47 Meter2
2(W x H) + 3.14 H2
Probable Number of Strikes to Building / Structure per Year
P = Ac x Ng x 10-6 times/year = 0.025907 Times per year
( Refer Clause 8.1.2 of IS 2309 )
Overall Multiplying Factor = AxBxCxDxE = 0.024000
Rf-C Overall Multiplying Factor = 0.000622
Overall Risk Factor Calculated =
xP ie 6.2178E-04
iii) Maximum Acceptable Overall Risk Factor:-
Rf-A ( Refer Clauses 8.1.3 & = 0.000001
Maximum Acceptable Overall Risk Factor
8.1.6 of IS 2309 ) ie 1.000E-06
iv) Result / Conclusion :-
Since Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
(Applicable if Provision for Lightning Protection is needed)
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = ( L x W ) = 661.20 Meter2
Perimeter of Structure P = 2(L+W) = 110.8 Meter
i) For Base Area (Ab) < 100m 2

a) Number of Down Conductors Required = For Ab < 100m2 = 1 Nos


ii) For Base Area (Ab) > 100m 2

b) Based on Base Area of Structure:-


Number of Down Conductors Required = 1+(Ab-100)/300 = 3 Nos
c) Based on Parimeter of Structure:-
Number of Down Conductors Required = P/30 = 4 Nos.
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Hence, Required Number of Down Conductors = 3 Nos.

Rev. Date Drg/Doc. No. Remarks Prepared Reviewed Approved


REVISION
DETAILS

R0 30.06.2009 3VYN855200 First Submission RK PS PAS


PROJECT : - 1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
CLIENT :- RRVUNL
CONSULTANT :- DCPL, New Delhi
BOP CONTRACTOR :- Indure, New Delhi

LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR WAGON TIPPLER AREA

Description / Parameter Symbol / Formulae / References Value Unit


A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
i) Input Data :-
a) Dimensions of Building / Structure
Length of the Building L ( Refer the Relevant Layout = 41.00 m
Width of the Building W Drawings of the Building / = 18.00 m
Height of the Building H Structure ) = 19.00 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N ( Refer Fig. 1 of IS 2309 ) = 27 No. of Days / Year
(Refer Clause 8.1.2 of
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km2/year
IS 2309)
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
( Type of
Weighting Factor B B ( Refer Table 1B of IS 2309 ) = 0.8
Construction )
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
(L x W) + 2 (L x H) +
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac = = 4113.54 Meter2
2(W x H) + 3.14 H2
Probable Number of Strikes to Building / Structure per Year
P = Ac x Ng x 10-6 times/year = 0.020568 Times per year
( Refer Clause 8.1.2 of IS 2309 )
Overall Multiplying Factor = AxBxCxDxE = 0.096000
Rf-C Overall Multiplying Factor = 0.001974
Overall Risk Factor Calculated =
xP ie 1.9745E-03
iii) Maximum Acceptable Overall Risk Factor:-
( Refer Clauses 8.1.3 & = 0.000001
Maximum Acceptable Overall Risk Factor Rf-A
8.1.6 of IS 2309 ) ie 1.000E-06
iv) Result / Conclusion :-
Since Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
(Applicable if Provision for Lightning Protection is needed)
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = ( L x W ) = 738.00 Meter2
Perimeter of Structure P = 2(L+W) = 118 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = For Ab < 100m2 = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
Number of Down Conductors Required = 1+(Ab-100)/300 = 3 Nos
c) Based on Parimeter of Structure:-
Number of Down Conductors Required = P/30 = 4 Nos.
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Hence, Required Number of Down Conductors = 3 Nos.

Rev. Date Drg/Doc. No. Remarks Prepared Reviewed Approved


REVISION
DETAILS

R0 30.06.2009 3VYN855200 First Submission RK PS PAS


PROJECT : - 1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
CLIENT :- RRVUNL
CONSULTANT :- DCPL, New Delhi
BOP CONTRACTOR :- Indure, New Delhi

LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR DRIVE HOUSE

Description / Parameter Symbol / Formulae / References Value Unit


A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
i) Input Data :-
a) Dimensions of Building / Structure
Length of the Building L ( Refer the Relevant Layout = 15.50 m
Width of the Building W Drawings of the Building / = 8.50 m
Height of the Building H Structure ) = 5.00 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N ( Refer Fig. 1 of IS 2309 ) = 27 No. of Days / Year
(Refer Clause 8.1.2 of
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km2/year
IS 2309)
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
( Type of
Weighting Factor B B ( Refer Table 1B of IS 2309 ) = 0.2
Construction )
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
(L x W) + 2 (L x H) +
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac = = 450.25 Meter2
2(W x H) + 3.14 H2
Probable Number of Strikes to Building / Structure per Year
P = Ac x Ng x 10-6 times/year = 0.002251 Times per year
( Refer Clause 8.1.2 of IS 2309 )
Overall Multiplying Factor = AxBxCxDxE = 0.024000
Rf-C Overall Multiplying Factor = 0.000054
Overall Risk Factor Calculated =
xP ie 5.4030E-05
iii) Maximum Acceptable Overall Risk Factor:-
Rf-A ( Refer Clauses 8.1.3 & = 0.000001
Maximum Acceptable Overall Risk Factor
8.1.6 of IS 2309 ) ie 1.000E-06
iv) Result / Conclusion :-
Since Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
(Applicable if Provision for Lightning Protection is needed)
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = ( L x W ) = 131.75 Meter2
Perimeter of Structure P = 2(L+W) = 48 Meter
i) For Base Area (Ab) < 100m 2

a) Number of Down Conductors Required = For Ab < 100m2 = 1 Nos


ii) For Base Area (Ab) > 100m 2

b) Based on Base Area of Structure:-


Number of Down Conductors Required = 1+(Ab-100)/300 = 1 Nos
c) Based on Parimeter of Structure:-
Number of Down Conductors Required = P/30 = 2 Nos.
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Hence, Required Number of Down Conductors = 1 Nos.

Rev. Date Drg/Doc. No. Remarks Prepared Reviewed Approved


REVISION
DETAILS

R0 30.06.2009 3VYN855200 First Submission RK PS PAS