Professional Documents
Culture Documents
Operation
&
Maintenance
Manual
TM
CUSTOMER SERVICE................................................................................................................................ 5
CONTACT INFORMATION ........................................................................................................................................................................5
ORDER INFORMATION ..............................................................................................................................................................................5
INTRODUCTION ....................................................................................................................................... 6
SAFETY........................................................................................................................................................ 6
THEORY OF OPERATION........................................................................................................................ 7
STORAGE.................................................................................................................................................... 7
INITIAL FREIGHT RECEIPT AND INSPECTION .................................................................................. 8
INSTALLATION ......................................................................................................................................... 8
UNPACKING ...............................................................................................................................................................................................8
LIFTING ........................................................................................................................................................................................................8
LOCATION ..................................................................................................................................................................................................8
MOUNTING.................................................................................................................................................................................................8
VENTILATION .............................................................................................................................................................................................9
ELECTRICAL PREPARATION .....................................................................................................................................................................10
PIPE CONNECTIONS AND SIZING ..........................................................................................................................................................11
INLET PIPING .............................................................................................................................................................................................11
COOLING WATER PIPING (WATER COOLED SYSTEMS ONLY).............................................................................................................12
ELECTRICAL CONTROLS (IF INCLUDED) ......................................................................................... 13
DEKKER CONTROLLER.......................................................................................................................... 13
DEKKER CONTROLLER OVERVIEW .....................................................................................................................................................13
DEKKER CONTROLLER KEYPAD ..........................................................................................................................................................14
SECURITY ACCESS LEVELS .......................................................................................................................................................................16
START UP PROCEDURES ...................................................................................................................... 22
SHUT DOWN PROCEDURE .................................................................................................................. 27
SEQUENCE OF OPERATION................................................................................................................. 27
SYSTEM ALARM CONDITIONS ............................................................................................................ 28
MAINTENANCE ....................................................................................................................................... 30
PUMP BEARING LUBRICATION................................................................................................................................................................30
PUMP BEARING LUBRICATING SCHEDULE.............................................................................................................................................30
MOTOR BEARING LUBRICATION (WHERE REQUIRED) ........................................................................................................................31
MOTOR BEARING LUBRICATING SCHEDULE ........................................................................................................................................31
INLET FILTER (IF INSTALLED) ...................................................................................................................................................................32
SEAL FLUID ................................................................................................................................................................................................32
MATERIAL SAFETY DATA SHEETS AVAILABLE UPON REQUEST ............................................................................................................32
OIL CHANGE PROCEDURE .....................................................................................................................................................................33
STANDARD SYSTEM CAPACITIES ............................................................................................................................................................35
Order information
When calling for service, parts or system information always have the pump or system model number and
serial number(s) ready. Refer to the bill of lading or the gold-colored system information plate attached to
the system.
Parts should be purchased from the nearest authorized DEKKER representative or from the vacuum pump
system supplier. If for any reason parts cannot be obtained in this manner, contact the factory directly.
SAFETY
All products offered by DEKKER have been designed and manufactured for safe operation. However, the
responsibility for safe operation rests with those who use and maintain these products. Your safety
department should establish a safety program based on OSHA, federal, state and local codes. It is important
that due consideration be given to hazards which arise from the presence of electrical power, hot liquids,
harmful gases and rotating equipment. Proper installation and care of protective devices is essential to safe
system operation. These safety procedures are to be used in conjunction with the instructions contained in
this manual.
STORAGE
Keep the system in a cool dry environment and close the seal fluid isolation valve as shown on page 21.
Plug all open ports to keep out dirt and foreign objects. Every 2 - 3 months rotate the impeller by rotating
the shaft by hand 2 turns.
INSTALLATION
The design of the piping system, foundation layout and plant location are the responsibility of the purchaser.
DEKKER Vacuum Technologies, Inc. and its representatives may offer advice but cannot assume
responsibility for operation and installation design.
Please consult an authorized dealer or a specialist skilled in the design of plant layout, system piping design
and foundation design. The installer should carefully read this manual before installing the equipment.
DEKKER or your local dealer can provide start up assistance in most instances at reasonable cost.
Unpacking
Upon receipt of pump or system, immediately inspect for signs of damage. Carefully remove
packing or crating from around pump or system. Be sure to keep equipment in upright position.
Lifting
Lift the equipment carefully and with weight evenly distributed. DEKKER is not responsible for equipment
that has been damaged through mishandling or dropping. Use of DEKKER provided lifting points will ensure
proper handling.
Location
Install the unit in a well ventilated and dust free area. The pump or system should be a minimum distance of
3 feet from surrounding walls to allow for checking fluid level, temperatures, pressures and general
servicing.
Mounting
The pump or system must be installed on a level surface in a horizontal position. The foundation must be
designed to support the total unit weight, without any settlement or crushing, be rigid and substantial
enough to absorb any equipment vibration, maintain true alignment with any drive mechanism, and must
permanently support the system baseplate at all points. The vacuum system must be leveled and secured
with foundation bolts. Foundation bolts must be of adequate size to withstand the mechanical stresses
exerted on it.
Please note that the pump/motor coupling and V-belt units will need to be realigned
prior to start-up, with the exception of monoblock units.
Ventilation
Locate the vacuum system in an area with sufficient airflow and accessibility. To prevent excessive ambient
temperature rise it is imperative to provide adequate ventilation. Cooling is an important aspect of reliable
equipment operation and it is therefore important to install the unit in a reasonably cool area where the
temperature does not exceed 104F (40C). For higher ambient temperatures contact the factory.
For water-cooled vacuum systems it is necessary to check cooling water supply. A proper, consistent
water flow must be maintained for adequate cooling.
Normal system operating temperature is between 140 - 185 F. Minimum oil temperature should not be
below 45F.
Model No. HP Fact. 200V 230V 460V Tol. 200V 230V 460V 200V 230V 460V 200V 230V 460V 200V 230V 460V
VMX0203KA1 15 1.3 48.3 42 21 10% 6 6 10 3/4" 3/4" 1/2" 90 80 40 84.5 73.5 36.7
VMX0303KA1 20 1.25 62.1 54 27 10% 4 6 10 1 3/4" 1/2" 110 100 50 109 94.5 47.2
VMX0303KA1-20 20XP 1.15 62.1 54 27 10% 4 6 10 1 3/4" 1/2" 110 100 50 109 94.5 47.2
VMX0453KA1 25 1.3 78.2 68 34 10% 3 4 8 1 1 1/2" 140 120 60 137 119 59.5
VMX0453KA1-20 25XP 1.15 78.2 68 34 10% 3 4 8 1 1 1/2" 140 120 60 137 119 59.5
VMX0553KA1 40 1.3 120 104 52 10% 0 1 6 1.25 1.25 3/4" 220 190 100 210 182 91
VMX0553KA1-20 40XP 1.15 120 104 52 10% 0 1 6 1.25 1.25 3/4" 220 190 100 210 182 91
VMX0753KA1 50 1.28 150 130 65 10% 0 0 4 1.5 1.5 1 270 230 115 262 227 114
VMX1003KA1 60 1.15 177 154 77 10% 0 0 3 2 1.5 1 320 270 140 310 269 135
VMX1103KA1 75 1.15 221 192 96 10% 300 0 1 2 2 1.25 390 340 180 387 336 168
VMX1203KA1 100 1.15 285 248 124 10% 500 350 0 2.5 2.5 1.25 510 440 230 499 434 217
NOTES: 1. Based on no more than three single insulated conductors rated 0-2000 volts. 6. If fuse is not a standard size, choose the next higher standard size.
2. Conduit sizes shown at 9.6% Fill does include ground conductor if required (over 60 amperes). 7. If disconnect is not a standard size, choose the next higher standard size.
3. Wire sizes are based on NEC Table 310.15.b.16 @ 75 deg. C rated conductors.
4. Approved trade size conduit or metal tubing.
5. Above information is general information. Per NEC tables please confirm motor FLA does not exceed FLC
Note: Fuse and disconnect sizes are for vacuum pump only. For main disconnect and fuse sizes for systems
with a circulation pump and fan, multiply the FLC of the vacuum pump motor by 175% then add the FLC for
the circulation pump and fan to get the fuse size. Disconnect must be sized to fit fuse.
All system wiring is performed at the factory if a control panel is supplied. Check area classification to ensure
all electrical enclosures comply with code. Required customer wiring is minimal, but should be done by a
qualified electrician in compliance with OSHA, National Electric Code and any other applicable local electrical
code concerning switches, fused disconnects, etc. DEKKER includes a wiring diagram in the control panel for
use by the installer. DEKKER recommends a main disconnect switch be fitted between the vacuum system and
the incoming power.
After the electrical wiring connections are completed check the incoming voltage to make sure the incoming
voltage is the same as the vacuum system voltage. Line voltage should be within the voltage tolerance as
specified on the motor or to local code. Check the system for proper motor rotation. The direction of
rotation is always clockwise when looking at the shaft of the pump and is marked by an arrow on the motor or
pump housing. Jog the motor by pressing the ON button and then the OFF button. If the rotation is incorrect
switch any two of the three main power leads on the contactor inside the control panel. Failure to do so could
result in serious equipment damage.
WARNING: For NFPA 99 hospital and generator applications, please shut down the vacuum
pumps prior to generator testing. The rapid stop and restart may cause damage to the pump
and/or motor and cause damage to electrical panel and related components.
Inlet and Discharge Maximum Number of Systems Running, based on SCFM at 15"
Pipe Diameter HgV
(Inches) 1 2 3 4 5 6 7 8 9 10 11 12
DV0020B 1 1 1.25 1.25 1.25 1.5 1.5 2 2 2 2 2.5
DV0035B 1 1.25 1.5 1.5 2 2 2.5 2.5 2.5 3 3 3
DV0060B 1.25 1.5 2 2.5 2.5 3 3 3 4 4 4 4
DV0080B 1.25 2 2 2.5 3 3 4 4 4 4 4 6
DV0100B 1.25 2 2.5 3 3 4 4 4 4 6 6 6
DV0150B 1.5 2.5 3 4 4 4 6 6 6 6 6 6
PUMP MODEL
DV0200B 2 3 4 4 6 6 6 6 6 6 8 8
DV0300B 2.5 4 6 6 6 6 8 8 8 8 8 8
DV0450B 3 4 6 6 6 8 8 8 8 10 10 10
DV0550B 4 6 6 8 8 8 10 10 10 10 12 12
DV0650B 4 6 6 8 8 10 10 10 10 12 12 12
DV0750B 4 6 8 8 8 10 10 12 12 12 12 14
DV1000B 6 6 8 10 10 10 12 12 14 14 16 16
DV1100B 6 8 8 10 10 12 12 14 14 16 16 16
DV1200B 6 8 8 10 10 12 12 14 16 16 16 18
Inlet Piping
Note: Install a temporary screen at the pump inlet flange at first start-up to protect the unit against
carryover of pipe debris and welding slag. The screen must be removed after the initial run in period.
Inlet piping should be at least the size of the pump inlet. Install the system as close as possible to the
process to minimize losses due to the length of the suction line. If the system has to be installed further
away from the process, be sure the inlet piping is properly sized to minimize the overall line pressure drop.
For more information consult your dealer or call the factory.
Pump systems operating in parallel on a common manifold must each have a manual or automatic shut-off
valve and a suitable check valve installed in the suction line close to the pump suction flange. This allows
DEKKER Controller
DEKKER Controller Overview
DEKKERs Controller is standard on the Vmax models. The DEKKER Controller provides for system
control as well as monitoring of system status. Service functions include display of spare parts list,
maintenance schedules, and service history, along with logging of fault conditions.
The DEKKER Controller includes a 4-line large-font liquid crystal display, a durable Lexan membrane
keypad, and multiple status LEDs. Communication between controllers is via RS-485 for multi-machine
systems. An Ethernet port provides for remote monitoring and control via TCP/IP protocols and can be
enhanced with the use of DEKKERs OnDek Software (optional and purchased separately). Input and
output (I/O) includes 9 digital (24VDC) inputs and 7 dry relay contact outputs. Analog I/O includes 2 RTD
(Resistance Temperature Detectors) inputs, four 0-10VDC/4-20mA inputs, one 0-10VDC output, and one
4-20mA output. Power input to the controller is 24VDC.
Refer to the most current DEKKER Controller Manual for more detailed information.
6) HAND/AUTO BUTTON
ALTERNATES BETWEEN HAND AND
AUTO MODES 13) RUN STATUS LED
GREEN = SYSTEM RUNNING
ORANGE = STANDBY/AUTO MODE
RED = SYSTEM STOPPED
7) POWER ON LED
RED=CONTROLLER POWER ON
8) POWER ON BUTTON
TURNS CONTROLLER
ON AND OFF
= ESC
= PROG 2
= MAINT 3
With Basic Access (default), the user is able to clear Faults, but is unable to make any parameter changes.
Operator Access [022] adds the ability to make operating parameter changes (Program>Setpoint menu)
and the ability to transfer
sfer data from the controller.
The Security Access Level is changed by entering a Password. To enable Operator Access,
Access first press and
hold the ESCAPE button for two seconds. The screen will display Password. Enter the password 22 by
pressing the PROG button twice (See Number Dia Diagram
gram Above) followed by the ENTER BUTTON.
Service Access [033] allows the ability to make operating parameter changes (Programs>Setpoint menu)
add field options (Programs>Programs>Options menu), and update service history (Maint(x5)>Service
(Maint
History menu).
The Security Access Level is changed by entering a Password. To enable Service Access,
Access first press and
hold the ESCAPE button for two seconds. The screen will display Pa
Password.
ssword. Enter the password 33
33 by
pressing the MAINT button twice (See Number Dia Diagram Above) followed by the ENTER BUTTON.
To restore Basic Access,, press and hold the ESCAPE button for two seconds. The screen will display the
words Access Locked. Basic Access is also restored upon powering the controller off and on.
Note: Once the DEKKER Controller
ontroller has no activity for 5 minutes it will default back to Basic Access any
changes after the password times out will required password to be rere-entered.
The UP-ARROW / + button and the DOWN-ARROW / - button can be used to move the right arrow
cursor to the desired parameter. Pressing the ENTER button will select that parameter for change. The
value will begin to flash. Use the ARROW buttons to change the value. Press the ENTER button to save
the new value.
Vac Cut In (Optional)
When in the Auto mode, a vacuum level at or below this value will cause the vacuum system to turn ON.
This value can be displayed in units of Torr (mm HgA) or HgV (inches of Hg vacuum). See menu item
Vacuum Unit on the next page for changing units.
Vac Cut Out (Optional)
When in the Auto Mode, a vacuum level at, or above (deeper) this value, will cause the vacuum system to
turn OFF. This value can be displayed in units of Torr (mm HgA) or HgV (inches of Hg vacuum). See
menu item Vacuum Unit on the next page for changing units.
Min Run Time
When in the Auto mode, short cycling is prevented by the minimum run time feature. The setting for this
feature is 10 minutes. At the end of the minimum run time, and if Vac Cut Out has been achieved, the
pump will stop and the Run Status light will change from green to orange indicating STANDBY. The ON
light will remain green during Standby. Run times less than 10 minutes may shorten the life of the motor or
pump from frequent cycling on and off.
Temp Warn
If the pump is running, or in standby mode, and the discharge temperature reaches this value, the warning
message High Discharge Temp will be displayed. In addition, the Run Status light will be orange and will
flash on and off. The pump will not be shut down by this warning condition. Standard Warning is 210F
Note: The Security Access level must be changed from Basic (default) to allow changes within the Options
menu. Refer to Security Access Levels above for instructions on enabling Service Access.
To enable any of the following options, you must also enter a 9 digit Keycode, as detailed in the following section.
Pressing the PROG button twice displays the following Options menu:
Inlet Filter
Hi Level Sw
Low Level Sw
Circ Pump
Relief Valve
Temp Valve
Solenoid
Temp Switch
Aux Temp
Differential
Back Pressure
No# of Units
To enter a key code, the user must enable Service Access by entering the appropriate security password as
described on page 15. Once password is entered go to the Options menu under PROG, choose the option to
be enabled and press the ENTER pushbutton on the DEKKER Controller. The key code is a nine digit number
with the first two numbers as zeroes. After the two leading zeroes, enter the seven remaining numbers that
are supplied by DEKKER in the option kit that was sent for the upgrade. After using the UP-ARROW / +
button and the DOWN-ARROW / - button on the DEKKER Controller to scroll to the appropriated digit,
press the ENTER button to accept each digit of the key code. The key code will look similar to the following;
001234567. Once the key code is accepted, the N/A changes to YES.
Please contact local dealer or factory with any questions on available options and the benefits of each option.
Maintenance Menu
Pressing the MAINT button once will display information similar to the following:
Pressing the MAINT button twice will display the following information:
Spare Parts List
The Spare Parts List includes recommended parts and their corresponding DEKKER part numbers. The
UP and DOWN ARROW buttons can be used to navigate through the list. Contact DEKKER After
Sales Support or your local distributor for additional information or to order parts.
Pressing the MAINT button three times will display the following information:
Recommended Maintenance Schedule and Intervals
Run Hours
The Run Hours are the total number of run hours on the vacuum system
Service History
Pressing the MAINT button five times will display the following information:
Service History
Important details about your DEKKER systems service history can be accessed under this menu.
In order to have the Service History record a service event, Service Access must be enabled via
proper password. Once in the service history menu, when the hours to next service is set to the
appropriate level, the change will be recorded by date and time.
For systems with MFG Date PRE 10/2015, use the ports labeled RS485 to Daisy Chain the units.
Communication cable will be RS485 with RJ45 Jack.
Use the UP / DOWN ARROWS to navigate through the displayed faults. Press the ENTER button to
select FAULT HISTORY DETAIL. Use the UP / DOWN ARROWS to scroll through the DETAIL. A
typical DETAIL is shown below:
To view up to DETAIL for each minute prior to a FAULT, press ENTER while viewing a FAULT
HISTORY DETAIL. Press ENTER again for the next prior minute DETAIL.
To exit FAULT HISTORY DETAIL, press the LOG button to return the FAULT HISTORY LOG. Or,
press ESC to return to the main status screen, e.g., STOPPED / AUTO.
Notes:
1. Use approximately 130% of above values to tension a new set of belts.
2. Use closest sheave diameter for sizes not shown.
Run Stop
8 With the pump shut off, check fluid level again.
The fluid level should be at the FILL LINE on the
sight gauge. Add fluid if necessary.
Warning: Never
ever remove the oil fill plug
while the pump is running.
SEQUENCE OF OPERATIO
OPERATION
The following sequence of operation is a description of how the Vmax oil-sealed
sealed vacuum pump system with
the DEKKER Controller should operate. The description is general to cover both simplex to multiplex
(more than one pump) systems. It is assumed that all start
start-up
up procedures have been followed. Ensure that
pump reservoirs are filled with oil (See Start
Start-Up Procedures, page 21). ). Make sure that the
th seal fluid
isolation valve is in the open position. If unsure about the function of one of the electrical controls
mentioned below, see the "Electrical Controls" section ((page 12)) for a description of the component.
compone If any
of the below do not occur, see the "Troubleshooting section (page 39).
Once the power connection to the system has been made, the following should occur:
If disconnects or circuit breakers are installed on the control panel, and are turned to the ON position,
the system will be energized by pushing the POWER pushbutton.. The POWER ON indicating LED on
the controller will be illuminated.
If HAND-OFF-AUTO pushbutton is set to the HAND mode (Orange LED manual operation), push ON
pushbutton and the pump(s)
mp(s) will immediately start. The Power On LED, the Pump On LED, and the
Run Status LED that are on the contr
controller should light up to indicate power is to the panel and the
The setpoints are set in this manner so that if pump 1 (lead pump) cannot satisfy demand and the
vacuum level drops below 21"HgV, the lag pump 2 (lag pump) will start-up when the vacuum level
reaches 19"HgV and stops at 23 HgV.
All multiplex systems are supplied with "automatic alternation" and "frequent stop/start protection"
unless otherwise specified.
"Automatic alternation" allows the pumps to operate equally (even run time) by alternating each
pump whenever the pump(s) shut down. When alternation occurs, the "lead" pump becomes the "lag"
pump and the "lag" pump becomes the "lead" pump. Lead pump is selected as pump with lowest run
hours in order to evenly balance run hours.
"Frequent stop/start protection" is used to allow the pump(s) to operate a minimum amount of
time. The time period is factory-set at 10 minutes. This allows the pump(s) to warm up and eliminate
frequent starting of the pump(s) which can cause premature coupling failure and breakdown of
electrical components. The pump(s) will continue to operate after the vacuum level has been satisfied.
If the possibility exists that the pump could work with a closed suction, a relief valve must be installed
to prevent hydraulic knock / cavitation.
This is a fault condition and must be cleared and then reset before the system can be started. Refer to the
section on resetting faults for details.
High DP Inlet Fltr Warning (Optional) If the differential pressure across the inlet filter exceeds
recommended levels, a warning message Hi DP Inlt Fltr will be displayed. Inlet filter should be
replaced at this point and the warning will clear.
High Back Pressure Warning If the back pressure on the discharge exceeds recommended
levels, a warning message Hi Backpress will be displayed. Separator element and discharge piping
should be inspected for blockage.
"Low Fluid Level" Fault (Optional) If the LOW OIL LEVEL Fault is on LCD display, the affected
pump will shut down. The back-up pump(s) will continue to operate unless a similar condition occurs
in those pump(s).
"Hi Fluid Level" Fault (Optional) If the Hi OIL LEVEL Fault is on LCD display, the affected pump
will shut down. The back-up pump(s) will continue to operate unless a similar condition occurs in
those pump(s).
Motor Overload Fault If the pumps motor overload has tripped due to excessive amperage
draw, the system will shut down and the display will indicate Motor Overload fault on the LCD.
The Maxima-K series of large capacity single-stage liquid ring vacuum pumps require lubricating every 1500
hours of operation. Grease fittings are located inside the finger guard of each bearing housing. There are
two grease fittings on the non-drive end of the pump.
Use a good quality high temperature lithium based grease of #2 consistency. Typical products are Texaco
Premium RB and Chevron SR1 #2.
Clean the area and replace the pipe plug with a grease fitting as generally they are not equipped with a
grease fitting. Remove the grease drain plug, located at the lower portion of each motor face (typically a
plastic plug), and loosen any hardened grease that may block the drain. Add the recommended volume of
the previously described grease using a hand operated grease gun. Run the motor for two hours. Replace
the pipe plug in grease drain.
Mixing of lubricants is not recommended due to possible incompatibility. Signs of incompatibility are
extreme soupiness from the grease relief drain or from the shaft opening. If changing a lubricant, grease and
then re-grease after 100 hours of service.
Frequency/volume of greasing is based on service conditions, speed and frame size. See Motor Bearing
Lubrication Schedule table below.
Standard conditions: 8 hour day operation, normal or light loading, clean environment at a 100 F
maximum ambient temperature.
Severe conditions: 24 hour operation or shock loading, vibration, dirty or dusty environment.
Extreme conditions: heavy shock, vibration, or dust. See table below for lubricating details.
Motor Bearing Lubrication Schedule
Lubrication Frequency Ball Bearings
Roller bearings divide time by 2
NEMA Standard Severe Extreme
Pump Model
Frame Conditions Conditions Conditions
DV0035-150 182-215 3 years 1 year 6 months
DV0200-550 254-365 2 years 6-12 months 3 months
-- 404-449 1 year 6 months 1-3 months
-- ALL 6 months 3 months 1 month
Lubrication
Volume
Pump NEMA Volume
Model Frame (Cubic inches)
DV0030-150 182-215 0.5
DV0200-450 254-286 1.0
DV0550 324-365 1.5
-- 404-449 2.5
CAUTION: Be careful not to allow accumulated foreign material to fall in the pump suction
opening when removing the filter cartridge. Horizontal filter installation is recommended to
prevent this. Filters must be disposed of properly as they might contain toxic substances
carried over from the process.
Seal Fluid
The system(s) are shipped with our specially formulated Vmaxol seal fluid. These fluids are specifically
designed for use in our Vmax systems, providing low viscosity, excellent water separating qualities, anti-
foaming and low oxidation. We recommend that our Vmaxol sealing fluids be used for obtaining ultimate
performance from your Vmax vacuum pump system and to guarantee the extended 3-year warranty
period.
VMX0203 VMX0553
A. Pump Drain (Ball Valve)
B. Y-Strainer (Hex Plug/Mesh Screen)
C. Inner Shell Drain (Pipe/Hex Plug/Ball Valve)
D. Outer Shell Drain (90 Degree Brass Push-Lock Fitting) Sight Glass does not read from this Outer Shell.
Before adding oil when you see it low in the sight glass, check for carried-over oil here!
E. Heat Exchanger Drain (Hex Plug/Ball Valve)
Oil Fill
(Reservoir)
Prime
Pump
D C
B
A E
A E
B Oil Fill
(Reservoir) C
D
VMX0036
A. Pump Drain (Typically Plugged)
B. Y-Strainer
Strainer (Hex Plug/Mesh Screen)
C. Main Tank Drain (Ball Valve)
D. Separator Scavenge Line Drain (90 Degree Brass Push
Push-Lock Fitting) Not Shown; Under Separator Element
Housing
E. Heat Exchanger. Disconnect Hoses/Piping to Drain
Prime
Oil Fill Pump
(Reservoir)
E D
A
B
Also make sure to include your contact information with email address. After the analysis is complete,
DEKKER will provide a report of the condition of the oil, along with recommendations.
Send to:
DEKKER Vacuum Technologies, Inc.
935 S. Woodland Ave.
Michigan City, IN 46360
United States
ATTN: After Sales
Separator Element
The separator elements are located in the separator reservoir. The purpose of the separator element is to
remove the oil from the discharge air. Replace the element every 10,000 hours or once a year. Earlier
replacement may be necessary when the back pressure is higher than 4 psig as displayed on the DEKKER
Controller. High back pressure is a result of dirt build-up on the separator element due to oil varnish or
contaminated inlet gas stream. Replacement may vary depending on application.
NOTE: Thread-in style filters are installed hand-tight as an oil filter. Do not over-tighten with a wrench.
Protective Devices
The following protective devices are available to protect the unit from being damaged and to help with
maintenance:
High Temperature Warning: will signal when the temperature of the oil is exceeding the warning
level. The DEKKER Controller will warn that the unit is approaching high temperature shut-down
level. The unit will not shutdown but will flash warning on the DEKKER Controller LCD. The
temperature is read using an RTD and once the warning programming parameter is reached the
warning will trigger. The temperature will need to drop below the warning trigger for the message to
go away.
High Temperature Shutdown: will signal when the temperature of the oil is exceeding the shut-
down level. The DEKKER Controller will shut the unit down and the High Disch Temp shutdown will
appear on the DEKKER Controller LCD. The unit will not restart until the alarm condition is
acknowledged and is reset. The temperature is read using an RTD and once shutdown programming
parameter is reached the shutdown will occur.
WARNING: Before attempting any repairs, disconnect all power from the system by
switching off the main breaker or disconnect switch. This will prevent the system from
automatically starting from a vacuum setpoints.
Start-Stop Problems:
System will not start in HAND or AUTO position: (Vmax)
1. DEKKER Controller not powered ON.
a. The POWER button must be pressed to ON.
b. When powered ON, the red LED above the POWER button will be lighted.
c. The LCD display should be showing the main screen with the message Stopped, or
Standby.
d. The display can be switched to the main screen by pressing the ESC button.
e. The HAND/AUTO LIGHT will be either Red for Hand, or green for Auto mode.
f. The OFF light and the RUN status light will be red when the system is STOPPED.
2. No main AC power. Confirm that the main AC power disconnect is ON and supplying power to the
control panel. This can be measured with an AC voltmeter at the power supply terminals in the
control panel. Refer to the electrical control panel diagram supplied with the system. If main AC
power is not present at the power supply, verify incoming AC voltage on the motor contactor.
3. No 24VDC power. The DEKKER Controller operates on 24VDC. Using a DC voltmeter confirm the
presence of this voltage at the power input terminals on the controller circuit board connector. Facing the
back of the DEKKER Controller, this is the upper connector on the right side of the board. The lowermost
terminal on this connector is +24VDC while the next terminal above is GND/-24VDC. If 24VDC is not
present at the controller terminals, next check at the + and 24VDC terminals on the power supply. If
24VDC is present at the power supply but not at the controller, check the associated fuse within the control
panel.
4. Check if the disconnects or circuit breaker is switched on.
5. Check the overload setting on the starter and fuses.
6. Check the small auxiliary contactor on the face of the main contactor. A loose connection or debris can cause
faulty operation. Remove, clean, and reattach. Tighten wires.
7. Check alarm reset, light should be off.
8. Ensure that the proper voltage is supplied and that the wire size is correct.
9. Check electrical control panel (if installed). Make sure that all wires are tight. Wires may vibrate loose during
shipment or operation.
10. Check low oil level switch (if installed). Add oil to reservoir if needed.
11. Check if the pump has seized by rotating the coupling by hand (disconnect power first). If a rubbing
noise or binding is observed, contact authorized dealer.
12. Check the high temperature setting on DEKKER Controller Program Menu, which should be set for
225oF.
13. Check if pump operates against high back pressure (> 4 psig), if so replace oil separator element.
14. If a remote start switch is installed; remove the switch, re-install the jumper on terminal 27, and disable
the System Option.
Vacuum Problems:
System operates, but does not achieve desired vacuum level: (Vmax)
1. Stop system and disconnect power.
2. Check if the inlet valve is open and inlet filter is clean.
3. Ensure that no lines are open to the atmosphere, causing loss of vacuum.
4. Check for leaks in piping systems, using conventional leak detection methods.
5. Ensure that the oil level is correct and that the pump is primed and filled with oil to the shaft centerline only.
6. Check if the oil isolation valve is open.
7. Check if the oil solenoid valve (if installed) is working.
8. Check the vacuum setpoints, refer to page 17.
9. Check setting of vacuum relief valve (if installed) and adjust as needed.
10. Check if the motor rotation is correct. Rotation should be clockwise (facing pump from motor side)
and marked by an arrow on the motor or pump housing. If incorrect, switch any two of the three
main power leads on the contactor inside the control panel.
Overheating Problems:
System overheats or operates above 200oF: (Vmax)
1. Stop system and disconnect power.
2. Check the oil cooler and fan. Clean cooler externally with compressed air. Ensure that 12" of space is
available in front of the cooler and that the ambient temperature is below 110 F.
3. Check if the oil isolation valve is open.
4. Check if the oil solenoid valve (if installed) is working.
5. Ensure that the oil level is correct and that the pump is primed and filled with oil to the shaft centerline only.
6. Check if the temperature control valve (if installed) is working and that oil is flowing through the cooler.
Caution, the oil will be HOT!
7. Clean oil strainer.
8. Check if oil cooler is blocked internally with solids passed through from the process, clean if necessary.
Unit overheats on start-up in low ambient temperatures: (Vmax)
1. Stop system and disconnect power
2. Oil tends to thicken in temperatures of 45F and below. Place heat tape and insulation on the fluid seal
line from the heat- exchanger to the pump inlet.
3. Also insulate the seal-fluid solenoid valve (if installed) or change oil to synthetic fluid contact local dealer
of factory for more information.
Oil Problems:
System uses excessive oil or produces an oil-mist: (Vmax)
1. Stop system and disconnect power.
2. Check the oil return line from the separator for blockage to ensure that oil flows from separator to vacuum
pump.
3. Check if pump operates against high back pressure (> 4 psig), if so replace oil separator element.
4. Normal and continuous operating vacuum level should be 15 Hg or higher. If not, consult authorized dealer.
5. Check for an excessive amount of water vapor carried over from the process in the oil reservoir by slowly
draining from separator drain. Remove all excess water.