You are on page 1of 2

1. In a balanced 2-phase voltage system, the phase voltage are 120volts, what is the line to line voltage?

a. 120volts b.170 volts c. 240 volts d. 60 volts


2. The three phase rural distribution system has a phase to neutral voltage is 7967 volts, what is the line to line voltage?
a.13200 volts b. 7967 volts c. 11000 volts d. 13800 volts
3. A balanced three phase wye connected source has using positive phase sequence, Vca=230 Vrms with 90 degrees angle. Determine
Vbc.
a. 230+j0V b. -199-j115V c. -115-j199V d. j230V
4. A balanced three phase wye connected source has using negative phase sequence, Vab=381Vrms with 60 degrees angle.
Determine Vcn
a. 190.5-j110V b. -110+j110V c. -190.5-j110V d. j220V
5. The wye connected three phase ABC voltage source has Vc=24Vrms with -240 degrees angle. Find the line to line voltage Vab.
a. 208+j120 b. 360+j208 c. 208-j120 d. 360-j208
6. three equal resistors of 100 ohms are connected in delta across 240 volts, 3 phase lines. What is the total power with the same
resistors wye connected from the same supply?
a. 240W b. 100W c. 1728W d. 576W
7. Three 100 ohms resistors are connected in wye across 480 volts, 3 phase source. If one of the resistor is open, what is the power
absorbed by the two resistors?
a. 1152W b. 1536W c. 768W d. 2305W
8. three identical resistance connected in delta carry a line current of 300Amp. If the same resistances are connected in wye across the
same supply, what is the line current?
a. 150A b. 600A c. 300A d. 100A
9. A circuit consisting of three resistor rated: 10ohms, 15ohms and 20ohms are connected in wye. What would be the resistances of the
of the equivalent delta connected load?
a. 33, 23 & 15 ohms b. 30, 40 & 50ohms c. 70, 44.4 & 36.7ohms d. 65, 43.3 & 32.5ohms
10. Three capacitors, each having a capacitance of 75F are connected in star to 400V, 3ph, 50hz supply. Calculate the delta
equivalent capacitance so that when they are connected in the same supply, the line current will remain the same.
a. 150F b. 25F c. 225F d. 75F
11. A balance delta connected load of 4.j3 ohms per phase is connected to a 3phase 230 V supply. What is the line current?
a. 80A b. 46A c. 23A d. 33A
12. The metering of a 3 phase inductive load indicated the following values: 4000kW, 34.5kV, 80% pf. What is the kVA?
a. 3000 b. 4000 c. 5000 d. 7000
13. A balanced wye connected load of impedance 8+j6 ohms is connected to a three phase balanced source of 400 volts 60Hz. Find
the power per phase/
a. 4267W b. 12800W c. 5333W d. 3198W
14. the phase b voltage and the phase b current of a balance 3-phase system are: V=220sin(wt+210) and I=10sin(wt-180). What is
the power of the system?
a. 5716W b. 3810W c. 1905W d. 3300W

15. A balanced delta connected load draws 10Amp line current and 3 kW at 220V. The reactance of each phase of the load in ohms
is.
a. 30 b. 23.5 c. 38.1 d. 20
16. A three phase source of 230V supplies the following three phase loads. 20kW at 90% power factor leading, 50kW at 80% power
factor lagging and 10 kW at unity power factor. What is the total kVA and current?
a. 85.7 & 225A b. 94.7 & 182.8A c. 84.7 & 212.6A d. 84.7 & 92.88A
17. Three identical impedances of 15 cis 60 ohms are connected in star to a 3phase, 3wire, 240V system. The lines between the
supply and the load have impedances of 2+j1 ohms. Find the magnitude of the line voltage at the load.
a. 220V b. 185V c. 240V d. 213V
18. A balanced delta connected load of impedance 13.5+j9 ohms are connected to a three phase balanced source of 4160volts 60Hz
through a line with 0.5 ohm resistance and 2 ohms reactance. With Van=2400<0, find the line B current using ABC sequence.
a. 87.8+j327.8A b. 69.3-j52A c. -327.8-j87.8A d. 240-j240A
19. A balanced 3phase, 3 wire, 240V,60Hz source supplies power to a star connected load Za=10+j0, Zb=10+j10 and Zc=10+j0.
What is the line current?
a. 11.53A b. 10.02A c. 15.93A d. 16.97A
20. The power input to a 100hp, 480 volts, 85% efficiency and 75% power factor 3phase motor at full load is measured by two
wattmeter connected at lines A&C. What are the readings in kW?
a. 66.23 & 21.55 b. 69.5 & 18.26 c. 87.76 & 11.7 d. 67.89 & 30.4
21. A three phase induction motor takes 3000kW at 80% pf. Two wattmeters are used to measure the power, Wa & Wc. Wa reading is..
a. 2000 b. 3000 c. 2150 d. 2500
22. In a balanced 3 phase, 208 volts circuit, the line current is 100A. The power is measured by two wattmeter method, one reads 18
kW and the other is 9kW. What is the pf of the load?
a. 0.8 b. 0.5 c. 0.866 d. 0.95
23. An unbalanced wye connected loads on a 3 phase 4-wire system consist of Z1=10+j5, Z2=8+j4 and Z3=20+j0. The wye connected
generator load has balanced voltage to neutral to 120 volts. What is the wattmeter reading at Z1?
a. 720W b. 3312W c. 1440W d. 1152W
24. It is required to increase the power factor of a 750kW three phase balanced load from 70% lagging to 90% lagging. The line voltage
is 6900V, 60Hz. Specify the capacitor required to increase the power factor of this wye connected load in micro-farad per phase.
a. 20.45 b. 22.39 c. 22.39 d. 17.22
25. A 3phase 150hp, 480 V synchronous motor with rated efficiency of 90% is operating at rated load. It is in parallel with 3phase
balanced load of 400kW at 0.75 pf lagging. In order to improve to pf to 0.95 lagging, the excitation of the motor was increased.
Calculate the operating power factor of the motor.
a. 0.65 b. 0.38 c. 0.57 d, 0.82
26. A 7.5hp wound-rotor, 3phase induction motor draws a line current of 18.4A at 230V line when operating at rated output and
efficiency of 85%. Applying artificial neutral method of measuring 3-phase power using only one wattmeter, What is the wattmeter
reading?
a. 3179W b. 2126W c. 2119W d. 1590W
27. What is 1+A+A^2 in rectangular form?
a. 0.5+j0.866 b. -0.5-j0.866 c. 0+j1.732 d. 0
28. The three phase unbalanced current are: Ia=10cis(-30)A, ib=0 and Ic=10cis150A. Find the negative sequence current of phase b.
a. 8.66cis30 b. 5.77cis(-60) c. -5.77 d. 5.77cis60
29. Given the following phase current: Ia=5cis45p.u Ib=3cis(-90)p.u and Ic=3cis150p.u. Determine the positive sequence
symmetrical components of current for phase A.
a. 3.635cis276.8p.u b. 3.635cis36.8p.u c. 3.635cis156.8p.u d. 0.748cis65.3p.u
30. The line currents of unbalance delta connected load are: Ia=50cis0, Ib=40cis240 and Ic=45.8cis130.9. Determine the phase B
zero sequence component.
a. zero b. 45-j2.9 c. 16+j7.25 d. 5-j2.9

You might also like