You are on page 1of 57

Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

A single copy of this

Steel Construction Institute

publication is licensed to

dewhurst
on
27/10/2006

This is an uncontrolled copy


Dewhurst MacFarlane & Partners

This is an uncontrolled copy. Ensure use of the most current version of this document
by searching the Construction Information Service at www.tionestop.com
P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

SCI PUBLICATION P341


Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Guidance on meeting
the Robustness Requirements in

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Approved Document A
(2004 Edition)

A G J Way MEng, CEng, MICE

Published by:
The Steel Construction Institute
Silwood Park
Ascot
Berkshire SL5 7QN

Tel: 01344 623345


Fax: 01344 622944
P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/
2005 The Steel Construction Institute

Apart from any fair dealing for the purposes of research or private study or criticism or review, as permitted under the
Copyright Designs and Patents Act, 1988, this publication may not be reproduced, stored or transmitted, in any form or by
any means, without the prior permission in writing of the publishers, or in the case of reprographic reproduction only in
accordance with the terms of the licences issued by the UK Copyright Licensing Agency, or in accordance with the terms
of licences issued by the appropriate Reproduction Rights Organisation outside the UK.

Enquiries concerning reproduction outside the terms stated here should be sent to the publishers, The Steel Construction
Institute, at the address given on the title page.

Although care has been taken to ensure, to the best of our knowledge, that all data and information contained herein are
accurate to the extent that they relate to either matters of fact or accepted practice or matters of opinion at the time of
publication, The Steel Construction Institute, the authors and the reviewers assume no responsibility for any errors in or
misinterpretations of such data and/or information or any loss or damage arising from or related to their use.

Publications supplied to the Members of the Institute at a discount are not for resale by them.

Publication Number: SCI P341

ISBN 1 85942 163 6

British Library Cataloguing-in-Publication Data.

A catalogue record for this book is available from the British Library.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc ii Printed 01/07/05


Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SC

Disproportionate collapse,
the revised Building Regulations
and steel building design
Since 1st December 2004, all buildings must be designed to
avoid disproportionate collapse

New Publication New One Day Course


Guidance on meeting the 15% discount
Swindon - 18th October
Robustness Requirements on publication Manchester - 9th November
until 31/12/05
in Approved Document A Southampton - 1st February
The 2004 Amendments to the ABOUT THE COURSE
Building Regulations (for England This one day course provides a solid introduction in the
and Wales) include important design of steel framed buildings to avoid disproportionate
changes to Part A (Structure). collapse in accordance with the recently amended Building
The 2004 edition of Approved Regulations and the Approved Document A (2004 edition).
Document A specifies four
The course content includes an introduction to the
distinct classes of building each of
concepts of disproportionate collapse, structural integrity
which must have a different set
and robustness, an explanation of all the regulatory and
of structural provisions for the
BS 5950 requirements, strategies for compliance and
prevention of disproportionate
workshops which enable delegates to apply some of the
collapse. This new publication
theory learnt during the course.
provides designers with the
necessary guidance to enable them to ensure compliance WHO SHOULD ATTEND ?
with the disproportionate collapse requirements of the Practising engineers who need a general introduction or
revised regulations. update on robustness and the issues which need to be
considered when designing to avoid disproportionate
THE PUBLICATION INCLUDES SECTIONS ON: collapse.
Building classification including non-standard cases such This course comprises a set of lectures supplemented by
as mixed use. a number of interactive worked examples to ensure that
basic ideas are understood.
The regulatory requirements for each building class.
Handouts for this course will include a copy of the SCI
Practical details for meeting the requirements of each
publication Guidance on meeting the Robustness Requirement
building class.
in approved Document A.
Design guidance for each building class including which
clauses of BS 5950-1:2000 are applicable. This one day course provides 7 hours CPD.
A worked example demonstrating the design COST
calculations required for a Class 2B building. Members: 220.00 + VAT = 258.50
Non Members: 280.00 + VAT = 329.00
COST
15% discount on publication (valid until 31/12/05)
Members: 12.75 (list price 15.00) TO ORDER AND ENROL
Non Members: 25.50 (list price 30.00) T: 01344 872776
E: orders@steel-sci.com

See other courses and publications on our website at www.steel-sci.org/courses


The Steel Construction Institute, Silwood Park, Ascot, Berkshire SL5 7QN Tel: 01344 623345
P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

FOREWORD

Under the 2004 Amendment of the Building Regulations 2000, the changes to Part A
(Structure) include important changes to the limits on application for buildings designed
to avoid disproportionate collapse. The guidance given in the revised Approved
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Document A on how to meet the requirements to avoid disproportionate collapse has also
changed.

This publication provides designers of hot-rolled steel framed buildings with the

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
necessary guidance to enable them to ensure compliance with the disproportionate
collapse requirements of the Regulations.

The author is indebted to his colleagues at the SCI for their input and advice, in
particular to Charles King and Tom Cosgrove. In addition, a number of other
individuals have contributed to this guide and their input is gratefully acknowledged:
Stuart Alexander WSP Group
Professor D Blockley University of Bristol
Roger Davies Gifford & Partners Ltd

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Chris Dolling Corus Construction and Industrial
Geoff Harding Office of the Deputy Prime Minister
Roger Pope Consultant
David Moore The British Constructional Steelwork Association Ltd

The preparation of this guide was funded entirely by Corus Construction and Industrial,
and their support is gratefully acknowledged.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc iii Printed 01/07/05


Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc


iv
P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Printed 01/07/05
To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/
This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Contents
Page No.
FOREWORD iii

SUMMARY vi
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

1 INTRODUCTION 1
1.1 Robustness, Integrity, Disproportionate collapse, and Tying 1
1.2 The Building Regulations Part A and Approved Document A 1
1.3 BS 5950 2

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
1.4 Eurocode 1 2
1.5 Disproportionate collapse 2

2 CLASSIFICATION OF BUILDINGS 4
2.1 Introduction 4

3 CLASS 1 BUILDINGS 11
3.1 The requirements for Class 1 buildings 11
3.2 How BS 5950-1:2000 applies to Class 1 buildings 11
3.3 Practical solutions for Class 1 buildings 12

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


4 CLASS 2A BUILDINGS 13
4.1 The requirements for Class 2A buildings 13
4.2 How BS 5950-1:2000 applies to Class 2A buildings 13
4.3 Practical solutions for Class 2A buildings 13

5 CLASS 2B BUILDINGS 15
5.1 The requirements for Class 2B buildings 15
5.2 How BS 5950-1:2000 applies to Class 2B buildings 17
5.3 Practical solutions for Class 2B buildings 26

6 CLASS 3 BUILDINGS 27
6.1 The requirements for Class 3 buildings 27
6.2 Risk Assessment 27
6.3 Critical Situations for Design 28
6.4 Hazards 28
6.5 Risk Reduction Measures 29
6.6 Sources of further guidance 30
6.7 Unclassified Buildings 31

7 REFERENCES 32

APPENDIX A WORKED EXAMPLE 35


A.1 Introduction 36
A.2 Member sizes 39
A.3 Disproportionate collapse checks using fin plate
beam-to-column connections 40
A.4 Disproportionate collapse checks using flexible end plate
beam-to-column connections 43

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc v Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

SUMMARY

This publication provides guidance on designing hot-rolled steel framed buildings to avoid
disproportionate collapse. Consideration of disproportionate collapse is required for all
buildings in order to satisfy Requirement A3 of Part A of the Building Regulations.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Guidance for each of the four classes of building specified in Approved Document A
(2004 edition) is provided. The guidance includes explanation of the requirements,
advice on which Clauses of BS 5950-1:2000 are applicable to each building type, and

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
practical guidance concerning tying of the structural frame to provide robustness.

A worked example of the calculations for a Class 2B building is also included.

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc vi Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

1 INTRODUCTION

1.1 Robustness, Integrity, Disproportionate


collapse, and Tying
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

The terms robustness, integrity, disproportionate collapse, and tying are


often used in the same context, their inter-relationships and meanings are often
confusing. The situation is not helped by the fact that British Standards and the
Building Regulations use a combination of these terms.

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
The Building Regulations require that buildings should not be susceptible to
disproportionate collapse. Approved Document A states this can be achieved by
ensuring that the building is sufficiently robust and offers providing ties
as one method for satisfying the requirement.

In BS 5950-1:2000, under a heading of Structural integrity Clause 2.4.5


recommends that certain clauses should be satisfied to reduce the risk of
localized damage spreading. Two of the clauses to be followed are Tying
of buildings and Avoidance of disproportionate collapse.

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


A structure with robustness and integrity will be less susceptible to
disproportionate collapse. Providing sufficient tying between the structural
elements is one method of ensuring integrity.

The requirements of the regulations and the recommendations of standards are


explained in the following Sections of this publication.

1.2 The Building Regulations Part A and Approved


Document A
In June 2004 the Building Regulations[1] of England and Wales were amended.
The amendments change several aspects of the Regulations but this publication
is only concerned with the impact of changes to Part A (Structure) of Schedule
1. The revised Approved Document A Structure[2], which gives guidance on
how the regulations can be satisfied, was published by the ODPM in June 2004.
The amended Building Regulations relating to Part A and the 2004 edition of
Approved Document A came into effect on 1 December 2004.

The only significant effect on the design of steel framed buildings resulting from
the 2004 amendments to Part A of the Building Regulations is the change to the
limit of application of Requirement A3 (Disproportionate Collapse). There is
no change to the actual Requirement A3, which is stated below.

Disproportionate Collapse
A3. The building shall be constructed so that in the event of an accident
the building will not suffer collapse to an extent disproportionate to the
cause.

The previous regulations (before the 2004 edition) imposed a limit on the
application of requirement A3. The limit was as stated below.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 1 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Requirement A3 applies only to a building having five or more storeys


(each basement level being counted as one storey) excluding a storey
within the roof space where the slope of the roof does not exceed 70o to
the horizontal.

This limit has been removed in the current regulations. Therefore,


Requirement A3 now applies to all buildings.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Approved Document A (2004 edition) gives guidance on how requirement A3


should be applied to different types and sizes of building. The following
Sections of this publication will expand on and explain the information given in

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Approved Document A.

Note: The equivalent regulations for disproportionate collapse in Scotland and


in Northern Ireland currently continue to require disproportionate
collapse only to be considered for buildings of five or more storeys.

1.3 BS 5950
The current version of BS 5950-1[3] is the 2000 edition (incorporating
Corrigendum No.1), which was written with the 1991 version of the Building

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Regulations and the corresponding Approved Document A in mind. Therefore,
the 2004 edition of Approved Document A and BS 5950-1:2000 are not readily
compatible on the issue of avoidance of disproportionate collapse.

BS 5950-1 will be amended to reflect the changes to the regulations relating to


disproportionate collapse. However, this process will take time and any
amendment is not expected until Autumn 2005 at the earliest. In the meantime,
the guidance given in this publication will explain how BS 5950-1:2000 may be
used with Approved Document A (2004).

Guidance on Structural integrity for light gauge steel structures (designed to


BS 5950-5) is provided in Advisory Desk note AD280[4].

1.4 Eurocode 1
EN1991-1-7 (Eurocode 1 Actions on structures, Part 1-7 General actions,
accidental actions) has not yet been published and is currently only available as
a pre-standard[5]. However, much of the philosophy behind EN1991-1-7 is the
same as that of the Building Regulations Requirement A3 and the guidance
given in Section 5 of Approved Document A.

EN1991-1-7 recognises that no structure can be expected to resist all actions


arising from an extreme cause and that residual risk will be present in practice.
It requires that there is a reasonable probability that the structure will not be
damaged to an extent disproportionate to the original cause. Localised damage
due to accidental action is acceptable.

1.5 Disproportionate collapse


Regulatory requirements to avoid disproportionate collapse were first introduced
following the progressive partial collapse of a block of flats at Ronan Point,
Newham, London, in 1968. A gas explosion in a flat on the 18th floor knocked

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 2 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

out load-bearing precast concrete wall panels, the floors above collapsed due to
the lack of support from below, and the impact of the collapsing floors caused
further collapses all the way to the ground. As can be seen from Figure 1.1 a
reasonably typical gas explosion in one flat caused an entire corner of the
building to collapse. Ronan Point and other collapses are described in
References 6 and 7.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/
Figure 1.1 Partial collapse of a concrete structure due to a gas explosion
(Ronan Point 1968)

The Building Regulations require that all buildings are designed to avoid
disproportionate collapse. The phenomenon of progressive collapse is not
mentioned in the regulations. However, if a building is susceptible to
progressive collapse, it will almost certainly result in disproportionate collapse,
as the case at Ronan Point illustrates. The collapse at Ronan Point was both
progressive and disproportionate.

The primary approach to avoid disproportionate collapse of steel framed


buildings is to provide both horizontal and vertical tying of the frame elements
to ensure whole frame action.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 3 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

2 CLASSIFICATION OF BUILDINGS

2.1 Introduction
Approved Document A (2004 Edition)[2] sets out different required levels of
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

robustness for different types and sizes of buildings. There are four classes of
building; Class 1, Class 2A, Class 2B and Class 3. The robustness
requirements are progressively more stringent from Class 1 to Class 3. This
reflects the fact that a building with a higher classification is likely to have more

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
severe consequences (e.g. potential loss of life) associated with any given
collapse. Other factors have also been taken into account in the classification
process such as socio-economic factors: hospitals generally have higher
classifications than other buildings of the same size.

Table 11 in Approved Document A (reproduced here as Table 2.1) defines the


class of the building. Another way of presenting this information is the
flowchart in Figure 2.1, which will lead the designer to the classification
appropriate to his building.

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 4 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Table 2.1 Building Classification


Class Building type and occupancy
1 Houses not exceeding 4 storeys.
Agricultural buildings
Buildings into which people rarely go, provided no part of the building is
closer to another building, or area where people do go, than a distance of
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

1.5 times the building height


2A 5 storey single occupancy houses
Hotels not exceeding 4 storeys
Flats, apartments and other residential buildings not exceeding 4 storeys

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Offices not exceeding 4 storeys
Industrial buildings not exceeding 3 storeys
Retailing premises not exceeding 3 storeys of less than 2000 m2 floor
area in each storey
Single storey educational buildings
All buildings not exceeding 2 storeys to which members of the public are
admitted and which contain floor areas not exceeding 2000 m2 at each
storey
2B Hotels, flats, apartments and other residential buildings greater than 4

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


storeys but not exceeding 15 storeys
Educational buildings greater than 1 storey but not exceeding 15 storeys
Retailing premises greater than 3 storeys but not exceeding 15 storeys
Hospitals not exceeding 3 storeys
Offices greater than 4 storeys but not exceeding 15 storeys
All buildings to which members of the public are admitted which contain
floor areas exceeding 2000 m2 but less than 5000 m2 at each storey
Car parking not exceeding 6 storeys
3 All buildings defined above as Class 2A and 2B that exceed the limits on
area and/or number of storeys
Grandstands accommodating more than 5000 spectators
Buildings containing hazardous substances and/or processes
Note 1: For buildings intended for more than one type of use the Class should be that
pertaining to the most onerous type.
Note 2: In determining the number of storeys in a building, basement storeys may be
excluded provided such basement storeys fulfil the robustness requirements of Class
2B buildings.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 5 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

BUILDING TYPE BUILDING CLASS

Agricultural Class 1

Class 1
Is building height times Yes
Building where 1.5 less than the distance
people rarely go Class 2A
to another building or area
where people go? No
Class 1
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

No
Is building multi
Yes
occupancy? Yes Class 2A
Is building less than or
Residential
equal to 4 storeys? Yes
No Is building 5 storey single Yes Class 2B
occupancy housing?
No Is building less than or

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Class 3
equal to 15 storeys? No
Yes
Is building less than or Class 2A
Hotel or Office
equal to 4 storeys?
Yes
No Is building less than or
equal to 15 storeys? Class 2B
Yes No
Is building less than or Class 3
Industrial
equal to 3 storeys?
No Class 2A

Class 3
Is building less than or
Yes
equal to 3 storeys and Class 2A
Retail
less than 2000 m2 floor
area in each storey? Does building have less Yes
Class 2B

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


than 2000 m2 floor area in
Yes each storey?
No No
Is building less than or Class 3
equal to 15 storeys?
No
Class 2A
Yes
Educational Is building single storey? Class 2B
Yes
No Is building less than or
equal to 15 storeys? Class 3
No
Yes
Class 2B
Is building less than or
Hospital
equal to 3 storeys?
No Class 3

Yes Class 2B
Is building less than or
Car park
equal to 6 storeys?
No
Class 3

Class 2A
Is building less than or Yes
equal to 2 storeys and
Public Class 2B
less than 2000 m2 floor
Yes
area in each storey? Is floor area less than
No Class 3
5000 m2 in each storey?
No
Yes Class 2B
Is capacity less than or
Grandstand
equal to 5000 spectators? Class 3
No

Class 3
Building containing
hazardous
substance and/or
processes

Note 1: For buildings intended for more than one type of use the Class should be that pertaining to the
most onerous type.
Note 2: In determining the number of storeys in a building, basement storeys may be excluded provided
such basement storeys fulfil the robustness requirements for Class 2B buildings.

Figure 2.1 Flowchart for building classification

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 6 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

The following Sections provide further guidance on building classification for


some specific situations. The NHBC has also produced some guidance[8] on
building classification, which is available from their website, www.nhbc.co.uk.

2.1.2 Mezzanine floors


Each situation needs to be judged on its own merits. As an approximate guide a
mezzanine floor should only be considered as a storey if it is greater than 20%
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

of the building footprint. Guidance on the design of mezzanine floors for lateral
stability is provided in Advisory Desk note AD267[9].

2.1.3 Habitable roof spaces

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Habitable areas of roof space should be included as a storey irrespective of the
slope of the roof.

2.1.4 Buildings with a varying number of storeys


For buildings with varying numbers of storeys that fall into more than one class,
the robustness measures for the more onerous class may need to continue until a
structural discontinuity (such as a movement joint) is reached. However, each
case should be considered on its merits, even where the only areas of more
onerous class are common parts such as stairwells.

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Example
Figure 2.2 shows a block of flats partly of 4 storeys and partly of 5 storeys.
Class 2B robustness measures should be applied to the 5-storey areas and
extending to a suitable structural discontinuity in the 4-storey area and Class 2A
robustness measures may be applied to the remaining 4-storey area.

2A 2B

Movement
joint

Flats Flats

Figure 2.2 Classification of 4 and 5 storey flats

2.1.5 Mixed use buildings


For buildings intended for more than one type of use the class should be that
pertaining to the most onerous type. Where different occupancies are in
horizontally adjacent parts of the same building, the same approach to
robustness measures may be adopted as described in Section 2.1.4 for buildings
with varying numbers of storeys,. i.e. the robustness measures for the more
onerous class may need to continue horizontally until a structural discontinuity
(such as a movement joint) is reached. Each case should be considered on its
merits.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 7 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

The following series of examples illustrate the classification of mixed use


buildings.

Examples
2 storeys of flats over 1 storey of retailing premises (as shown in Figure 2.3)
should be considered as 3 storeys of retailing premises. Therefore, apply Class
2A robustness measures to the whole building, or apply Class 2B robustness
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

measures to the whole building if floor area of retailing premises is 2000m or


more.

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
2A, or 2B if retail
Flats premises>2,000 m

Shop

Figure 2.3 Classification of 2 storey flats over 1 storey retail

2 storeys of flats over 2 storeys of retailing premises (as shown in Figure 2.4)

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


should be taken as 4 storeys of retailing premises. Therefore, apply Class 2B
robustness measures to the whole building.

Flats
2B
Shop

Shop

Figure 2.4 Classification of 2 storey flats over 2 storey retail

Figure 2.5 shows 4 storeys of flats adjacent to 5 storeys of offices. Class 2B


robustness measures should be applied to the 5-storey office area and extending
to a suitable structural discontinuity in the 4-storey residential area and Class 2A
robustness measures should be applied to the remaining 4-storey residential
area.

2A 2B

Movement
joint

Flats Offices

Figure 2.5 Classification of 4 storey flats attached to 5 storey offices

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 8 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

2.1.6 Buildings with basements


To qualify as a basement storey for the purpose of building classification, the
distance between external ground level and the top surface of the basement floor
should be at least 1.2 m for a minimum of 50% of the plan area of the building.

The minimum robustness measures required to the part of the building above the
basement depend on the total number of storeys and the robustness measures
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

applied to the basement storey.

In determining the number of storeys for classification, basement storeys may


be excluded if such basement storeys fulfil the robustness requirements of Class

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
2B buildings.

The basement can be for habitable accommodation or parking. The following


examples illustrate the appropriate robustness measures to be applied.

Examples
Figure 2.6 shows examples of single occupancy houses over basements and the
classes of robustness measures to be applied.

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


2A 2B
1 or
2A
1

2B 2B

3 storey over 4 storey over 5 storey over 6 storey over


basement basement basement basement

Figure 2.6 Classification of single occupancy houses over basements

Figure 2.7 shows examples of flats above basements and the classes of
robustness measure to be applied.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 9 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

3
2B

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Flats Flats Flats Flats
2A 2B
Flats
2A

2B

3 storey over 4 storey over 5 storey over 15 storey over 16 storey over
basement basement basement basement basement

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Figure 2.7 Classification of flats over basements

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 10 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

3 CLASS 1 BUILDINGS

3.1 The requirements for Class 1 buildings


Class 1 buildings are low consequence buildings such as small residential
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

properties, agricultural buildings and buildings where people rarely go.


Therefore, the robustness requirements for Class 1 buildings are modest.
Approved Document A states in Clause 5.1.b:

For Class 1 buildings - Provided the building has been designed and

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
constructed in accordance with the rules given in this Approved
Document, or other guidance referenced under Section 1, for meeting
compliance with requirement A1 and A2 in normal use, no additional
measures are likely to be necessary.

This requirement means that provided the structural steel frame of the building
has been designed to BS 5950-1[3] then this is sufficient and no further action to
avoid disproportionate collapse is required. However, the guidance of
Approved Document A includes the words no additional measures are likely
to be necessary. This is a reminder that, in designing to avoid

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


disproportionate collapse, it is important to consider each individual structure
using engineering judgement together with BS 5950 and Approved Document A
rather than simply assume that no potential collapse scenarios need to be
considered.

3.2 How BS 5950-1:2000 applies to Class 1


buildings
BS 5950-1 states that Clause 2.4.5.2 Tying of buildings should be applied to all
buildings (which includes Class 1) and recommends that:
Columns should be tied in two directions, approximately at right angles, at
each principal floor level
All ties (along the edges of the building and along each column line) and
their end connections should be capable of resisting a factored tensile load
of at least 75 kN
Horizontal ties should also be provided at roof level, except where
steelwork only supports cladding that weighs not more than 0.7 kN/m2 and
that carries only imposed roof loads and wind loads.

Figure 3.1 shows which members need to be designed as ties under


Clause 2.4.5.2 of BS 5950-1. In practice, the required tying capacity of 75 kN
is achieved by any reasonable member and connection, see Section 3.3.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 11 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Beams between columns


are ties
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Secondary beams
are not ties

Figure 3.1 Ties required in Class 1 buildings

3.3 Practical solutions for Class 1 buildings

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


As stated in BS 5950 members that are required to be horizontal ties, as defined
in Section 3.2, should have a tension capacity of at least 75 kN. This is easily
satisfied for any hot-rolled section with a cross-section area of 3 cm2 or higher.

The end connections of horizontal ties should also have tension capacities of at
least 75 kN. All the standard connections for simply supported beams given in
SCI publication P212[10] can carry at least 75 kN in tension.

Bolt capacities for M16 and M20 8.8 bolts in S275 steel are shown in
Table 3.1. All reasonable connections will have at least two bolts (and usually
more), which will provide the necessary connection capacity.

Table 3.1 Bolt capacities for grade 8.8 bolts in S275 steel
Bolt Diameter Nominal tension Shear capacity Bearing capacity
capacity (8 mm plate)
M16 70 kN 58.9 kN 58.9 kN
M20 110 kN 91.9 kN 73.6 kN
Note: Tabulated capacities are calculated in accordance with BS 5950-1:2000,
Clause6.3

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 12 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

4 CLASS 2A BUILDINGS

4.1 The requirements for Class 2A buildings


Class 2A buildings are medium consequence buildings such as low rise flats,
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

offices, hotels, industrial buildings and relatively small public buildings. The
robustness requirements for Class 2A buildings are given in Approved
Document A, Clause 5.1.c as:

For Class 2A buildings - Provide effective horizontal ties, or effective

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
anchorage of suspended floors to walls, as described in the Codes and
Standards listed under paragraph 5.2 for framed and load-bearing wall
construction.

The guidance in Approved Document A for Class 2A buildings does not


mention notional removal of members if effective horizontal ties are not
provided. This is in contrast to the requirements for Class 2B buildings, see
Section 5.1. If effective horizontal ties or anchorage of floors to walls can not
be provided (for whatever reason) then an acceptable approach may be to re-
classify the building as Class 2B and use the notional removal of members

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


approach (see Section 5.2).

4.2 How BS 5950-1:2000 applies to Class 2A


buildings
BS 5950-1, Clause 2.4.5.2, which applies to all buildings, requires horizontal
ties to have a minimum capacity of 75 kN as explained in Section 3.2. For
steel framed buildings designed to BS 5950-1 there is no difference between the
robustness provisions for Class 1 and Class 2A buildings.

The tying requirements of BS 5950-1 for Class 1 and Class 2A buildings are
thus the same, as were the requirements for buildings with less than or equal to
four storeys under the 1991 Building Regulations.

4.3 Practical solutions for Class 2A buildings


As explained in Section 3.3, ordinary beam connections are easily able to meet
the requirement for tying.

4.3.1 Floor systems


Although there are no requirements in the Building Regulations or in BS 5950-1
to tie the floor system (such as precast units or steel deck with in-situ concrete)
to the structural frame in Class 2A buildings, there are obvious benefits in terms
of structural robustness, practicality, safety during construction and mobilising
floor diaphragm action.

Fixing of decking
Decking sheets should be fixed to the top of the supporting structure. All
fixings (e.g. shot-fired pins) should be made through the troughs in the decking.
Fixings should be at approximately 300 mm centres (or in every trough) along
the end supports and at 600 mm centres (or in alternate troughs) along the

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 13 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

internal supports. As an absolute minimum, each sheet should be connected at


least twice to each permanent support.

The fixings, together with welded shear studs (if present), normally provide
lateral restraint to the beams during the construction stages.

Further advice on fixing of decking and types of fixing is provided in SCI


Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

publication P300[11].

Fixing of precast units


Detailed guidance for fixing and tying of precast units is provided in Section

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
5.2.5. Further guidance regarding precast units is given in SCI publication
P287[12].

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 14 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

5 CLASS 2B BUILDINGS

5.1 The requirements for Class 2B buildings


Class 2B buildings are high consequence buildings and as such the robustness
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

requirements are significantly more stringent than those for Class 2A buildings.
Typical Class 2B buildings include residential, office and retail buildings
between four and fifteen storeys, hospitals less than four storeys and car parks
less than seven storeys. The robustness requirements for Class 2B buildings are

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
given in Approved Document A, Clause 5.1.d. However, The typographical
presentation in Approved Document A is misleading as it gives the impression
that horizontal ties are invariably required. The ODPM intend to reprint the
Approved Document to clarify the intention. The following is the text as it is
expected to be reprinted.

For Class 2B buildings:


Provide effective horizontal ties, as described in the Codes and
Standards listed under paragraph 5.2 for framed and load-bearing wall
construction, together with effective vertical ties, as defined in the

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Codes and Standards listed under paragraph 5.2, in all supporting
columns and walls,
or alternatively
a) Check that upon the notional removal of each supporting column and
each beam supporting one or more columns, or any nominal length
of load-bearing wall (one at a time in each storey of the building)
that the building remains stable and that the area of floor at any
storey at risk of collapse does not exceed 15% of the floor area of
that storey or 70 m2, whichever is smaller, and does not extend
further than the immediate adjacent storeys (see Diagram 25).

Where the notional removal of such columns (or beams supporting one
or more columns) and lengths of walls would result in an extent of
damage in excess of the above limit, then such elements should be
designed as a "key element" as defined in paragraph 5.3 below.

Note: The requirements for Class 2B buildings are very similar to the
requirements for buildings over four storeys given in the 1992 Edition
of Approved Document A.

The principle of providing horizontal ties notionally allows for the removal of
the support provided by a column and the remaining beam members to support
the loads by forming catenaries, as shown in Figure 5.1. The robustness rules
are not meant to fully describe systems of structural mechanics but are
considered as prescriptive rules intended to produce structures that perform
adequately in accidental circumstances.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 15 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Column removed

Figure 5.1 Concept of horizontal ties

In summary, Class 2B buildings either require a) horizontal and vertical ties, or


b) a check can be carried out to ensure that the removal of any single
supporting member will not cause an unreasonable area of the structure to fall
down i.e. will not cause disproportionate collapse. The rest of the building is
only required to remain stable and not necessarily serviceable for use. If the
removal of any supporting member would cause disproportionate collapse then it
should be designed as a key element. The limiting area for disproportionate

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


collapse is shown in Diagram 25 of Approved Document A (reproduced here as
Figure 5.2). The limit of 70 m2 given in Approved Document A can be quite
limiting with regard to many practical span arrangements in steel structures.
The recommended limit given in prEN 1991-1-7[5] is more generous at 200 m2.

The scope of this publication only covers hot-rolled steel-framed buildings;


therefore, the requirements concerning load-bearing walls are not discussed
here.

Area at risk of collapse


limited to 15% of the
floor area of that storey
or 70 m, whichever is
the less, and does not
extend further than the
immediate adjacent
storeys.

Column
notionally
removed

Plan Section
Note:
Three storeys may be affected by the notional removal of one column section but no more than
two floors.

Figure 5.2 Maximum allowable area at risk of collapse (reproduced


from Approved Document A, Diagram 25)

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 16 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

5.2 How BS 5950-1:2000 applies to Class 2B


buildings
All buildings now need to be designed to avoid disproportionate collapse.
However, Class 2B buildings can be considered to be specially designed to
avoid disproportionate collapse and therefore Clause 2.4.5.3 of BS 5950-1[3] is
applicable, as is Clause 2.4.5.4 for the design of key elements, if required. The
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

requirements of Clause 2.4.5.3 and its sub-clauses a) to e) are described in the


following Sections. As explained in Section 1.3, BS 5950-1 is being amended
and reworded to clarify which clauses are applicable in conformance with the
new regulations.

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
In BS 5950-1, there are three possible routes that can be adopted for designing
to avoid disproportionate collapse:
Provision of tying
Notional removal
Key element design.

BS 5950-1, Clause 2.4.5.3 states that if any of the first three sub-clauses a) to
c) are not met then, the building should be checked, each storey in turn, to

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


ensure that disproportionate collapse would not be precipitated by the notional
removal, one at a time, of each column (or beam supporting one or more
columns). The guidance for Class 2B buildings in light of the 2004 edition of
Approved Document A may be re-expressed as:
1) If any of the sub-clauses a), b) or c) are not met, then each storey in turn
should be checked to ensure that disproportionate collapse would not be
precipitated by the notional removal, one at a time, of each column (or
transfer beam).
2) If sub-clause d) is not met then, each storey in turn should be checked to
ensure that disproportionate collapse would not be precipitated by the
notional removal, one at a time, of each element of the systems providing
resistance to horizontal forces.
3) If heavy floor or roof units are used, sub-clause e) should be satisfied.

Clause 2.4.5.3 of BS 5950-1 further states


If the notional removal of a column, or of an element of a system
providing resistance to horizontal forces, would risk the collapse of a
greater area [than 15% of the floor area or 70 m2], that column or
element should be designed as a key element, as recommended in
Clause 2.4.5.4.

The design process for considering the notional removal of elements is


described in Section 5.2.6.

The requirements of BS 5950-1 for Class 2B buildings are essentially the same
as the requirements were for buildings with greater than four storeys under the
1991 Building Regulations.

Appendix A presents a fully worked example for the tying checks and design to
avoid disproportionate collapse for a Class 2B building.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 17 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

5.2.1 General Tying


Clause 2.4.5.3 a) General tying, describes which horizontal members should be
designed as ties and the tensile loads that the ties and their end connections
should be capable of resisting. General tying is notionally intended to enable
beams to bridge damaged areas of structure by hanging as catenaries (as shown
in Figure 5.1). Examination of the equations in Clause 2.4.5.3 shows that the
tying force is generally equal to the shear reaction, but is not less than 75 kN.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Figure 5.3 indicates which members need to be considered as ties under


Clause 2.4.5.3 a).

In the next revision to BS 5950-1 it is likely that there will be a reduction factor

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
that may be applied to the required tying capacities of horizontal ties and their
connections. Table 5.1 shows the values proposed at the time of writing for the
reduction factor n. The proposed tying capacity requirements are:

- for internal ties: 0.5(1.4 gk + 1.6 qk) st L n but not less than 75 kN
- for edge ties: 0.25(1.4 gk + 1.6 qk) st L n but not less than 75 kN

Where

gk is the specified dead load per unit area of the floor or roof

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


L is the span
qk is the specified imposed floor or roof load per unit area
st is the mean transverse spacing of the ties adjacent to that being
checked
n is a factor related to the number of storeys in the structure see
Table 5.1.

Table 5.1 Proposed reduction factors for required tie capacities


Number of storeys in building Reduction factor, n
5 or more 1.0
4 0.75
3 0.50
2 0.25
1 0
Note: In determining the number of storeys in a building, basement storeys may be
excluded provided such basement storeys fulfil the robustness requirements of Class
2B buildings.

The use of a reduction factor recognises that for lower rise buildings there are
fewer floors potentially available to collapse onto the structure below.

In Class 1 and Class 2A buildings, only the beams along the column lines need
to be designed for general tying. For Class 2B buildings, the members which
may be ties when designing to avoid disproportionate collapse are shown in
Figure 5.3. The beams not on the column lines (e.g. A to B) do not have to be
designed as ties provide that the beams on the column lines are designed for the
additional share of tying force.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 18 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

A
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
B
All beams may be ties

Figure 5.3 Members which may be ties in Class 2B buildings

Frequently, ties may be discontinuous, or have no anchor at the end distant to


the column. Two examples are shown in Figure 5.3, where at points A and B,
there is no reaction to the tie force assumed in the beam. The connection is

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


simply designed for the applied tie force. This situation is also common at
external columns, where only the local design of the connection is considered.
The column itself is not designed to resist the tying force.

5.2.2 Edge columns


Tying to edge columns is required to ensure that the edge columns cannot
become separated from the building. Clause 2.4.5.3 b) Tying of edge columns,
states that ties connected to edge columns should be capable of resisting the
larger of the following forces:
The design loads for general tying specified in Clause 2.4.5.3 a)
1% of the factored vertical dead and imposed load in the column at that
level.

By observation, 1% of the factored load in the column only becomes the more
critical load if there are a great many storeys (100 storeys if all floors are
identical, and this would then be a Class 3 building). Columns carrying transfer
trusses or similar massive loads may have high axial loads, and 1% of the
factored axial load should always be considered in such cases.

For any member also acting as a restraint to a column, a force of 1% of the


column load needs to be resisted by the restraint members in each restraint
direction, in accordance with Clause 4.7.1.2 of BS 5950-1.

5.2.3 Vertical tying


Vertical tying is provided by the tension capacity of column splices as required
by Clause 2.4.5.3 c) Continuity of columns. This clause requires that all
column splices should be capable of resisting an axial tension equal to the
largest factored vertical dead and imposed load reaction applied to the column at
a single floor level located between that column splice and the next column
splice down (or to the base). When applying this clause it is the largest total
reaction applied to the column at a floor level that should be used (i.e. the
reactions from all the beams connected to the column at that floor level).

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 19 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

The intention of providing vertical ties in addition to horizontal ties is to share


the floor loads among all the floors, recognising that some floors are not as
heavily loaded as others. This provides an additional level of robustness that
will assist the remaining structure support the loads after an accidental event, as
shown by Figure 5.4. If the column splice in Figure 5.4 did not have sufficient
tying capacity, the displacement of beams A and B would be significantly
greater and the beams could potentially collapse.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Splice

A B

Column removed

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Figure 5.4 Concept of horizontal and vertical ties

In practice, providing vertical tying should not be an onerous obligation, as


most splices designed for adequate stiffness and robustness during erection are
likely to be sufficient to carry the axial tying force. SCI publication P212[10] has
details of standard splices, and quotes axial tension capacities to simplify the
design checks. Either bearing or non-bearing column splices (as shown in
Figure 5.5) can be used to satisfy the vertical tying requirements. Non-bearing
splices will generally have higher tension capacities because they require thicker
cover plates and more bolts for normal design.

Division
plate

Air gap

Bearing Non-bearing
Figure 5.5 Column splice details

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 20 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Table 5.2 gives indicative tensile axial capacities for standard bearing-type
column splices with cover plates.

Table 5.2 Typical bearing type column splice tensile capacities (with
flange cover plates)
Upper Column Lower Column Tensile Capacity (kN)
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

203 UC 203 UC 736


254 UC 254 UC 736
305 UC 305 UC 1588
203 UC 254 UC 500

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
The capacities quoted in Table 5.2 are limited by bolt shear, and adding
additional bolts can easily increase capacities. Detailed design checks for
bearing and non-bearing column splices are provided in SCI publication P212[10].

Note: It is likely to be more difficult to provide the necessary tensile capacities


with cap and base type column splices.

5.2.4 Bracing systems


Clause 2.4.5.3 d) Resistance to horizontal forces requires at least two sets of

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


bracing (or other system for resisting horizontal force) in each orthogonal
direction. No substantial part of the structure can be braced by only one set of
bracing in the direction being considered. Thus, for buildings designed to avoid
disproportionate collapse, the bracing arrangement in Figure 5.6 would not be
satisfactory.

3 sets of bracing in Y direction


1 set of bracing in X direction

X
Figure 5.6 Unsatisfactory bracing arrangement for Class 2B buildings

BS 5950-1 allows moment resisting joints, cantilever columns, shear walls and
stair and lift cores, as well as triangulated bracing, to be used as systems for
resisting horizontal force.

5.2.5 Floor units


Clause 2.4.5.3 e) Heavy floor units requires that precast concrete or other heavy
floor or roof units are effectively anchored in the direction of their span, either
to each other over a support, or directly to their supports as, recommended in
BS 8110. The tying forces between floor units may be calculated from
BS 8110-1:1997 [13] Clause 3.12.3.4.

The intention of this clause is to prevent floor units simply falling through the
steel frame if the steelwork is moved or removed, or the floor units are uplifted
as a result of accidental loading (e.g. explosion).

BS 5950-1 only requires anchorages in the direction of the span of the precast
units, as the steel beams provide ties in the orthogonal direction.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 21 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying of the floor units to the beams may be necessary for purposes other than
reducing sensitivity to disproportionate collapse, such as to mobilise floor
diaphragm action against wind loading. Further guidance on the use and design
of precast units is provided in SCI publication P287[12].

Tying across internal supports


If the precast units have a structural topping, it may be possible to use the
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

reinforcement in the topping to carry the tie forces, as shown in Figure 5.7 a),
or to provide additional reinforcing bars. Alternatively, it may be possible to
expose the voids in the pre-cast planks and place reinforcing bars between the
two units prior to concreting, as shown in Figure 5.7 b).

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Reinforcement in topping Reinforcement in core
with concrete infill

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


a) With structural topping b) Without structural topping

Figure 5.7 Tying precast units

Special measures will be needed where precast planks are placed on shelf
angles, as shown in Figure 5.8, and with Slimflor construction, unless the tie
forces can be carried through the reinforcement in topping, above the top flange
of the steelwork. When it is not possible to use reinforcement in the topping,
straight reinforcement bars tying the precast units together are usually detailed
to pass through holes in the steel beam web.

Reinforcing
bar

Figure 5.8 Precast units on shelf angles

Tying to edge beams


Anchorage is best accomplished by exposing the voids in the plank, and placing
U-shaped bars around studs welded to the steelwork, as shown in Figure 5.9(a).
In this Figure, the studs have been provided in order to achieve adequate
anchorage (not for composite design of the edge beam in this case). Other,
more complicated solutions involve castellation of the plank edge (often on site),
so that the plank fits around the stud, and similar U-bars located in the voids
prior to concreting (Figure 5.9(b)).

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 22 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

U-bar U-bar
Plank castellated
around shear studs

Minimum flange Minimum flange


Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

width = 230 mm width = 120 mm

(a) (b)

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Figure 5.9 Tying of precast planks to edge beams

It should be noted that loading a beam on only one side produces significant
torsion in the beam itself, which may well be the critical design case. The
eccentricity must be accounted for in design of the member and its connections.

In some circumstances, the floor units cantilever past the edge beam. Tying in
these situations is not straightforward, and a solution should be developed in
collaboration with the frame supplier and floor unit manufacturer.

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


5.2.6 Notional removal of members
The notional removal of members or elements is required if BS 5950-1[3] Clause
2.4.5.3 b), c) or d) are not satisfied, as described in Section 5.2.

It is recognised that in the event of an incident, it is unlikely that the structure


will be subjected to its full design load. Therefore, the load cases below should
be used when checking for the consequences of notional removal of members.

Design load when not considering overturning:


= 1.05 (1.0 Dead load + 0.33 Imposed Load + 0.33 Wind Load)

Design load for overturning (Dead load is assumed to be supplying a restoring


moment):
= 0.90 Dead load + 1.05 (0.33 Imposed Load + 0.33 Wind Load)

Note: If the building being considered is used predominately for storage, or


the imposed load is of a permanent nature, the full imposed load should
be used.

If the notional removal of any element would result in the collapse of an area
greater than 70 m2 or 15% of that floor (or roof) area, that element should be
designed as a key element, as recommended in Clause 2.4.5.4.

Notional removal of columns


To determine the consequences of the notional removal of a column, the beams
supported by the removed column (and their end connections) may be checked
in catenary action. Additional support provided by the column section above
the section which is notionally removed (see Figure 5.4), may be taken into
account. However, in determining the magnitude of this support, the designer
should consider the strength of the members connections and the resistance of
the structure supporting that member. In most cases the notional removal of a
column section will cause the supported beams to collapse. In this situation the

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 23 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

floors below should be checked for the debris loading from the collapsed floors.
It is not necessary to consider the impact loading of the debris. The load
combinations given above may be used with the dead load component modified
to include the debris.

Notional removal of elements of the system for resisting horizontal


forces
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

If the notional removal of any element of the system for resisting horizontal
forces causes that system to fail (e.g. because a mechanism forms), then that
part of the building stabilised solely by the system should be considered to have
collapsed. In most cases this is likely to constitute disproportionate collapse.

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Providing redundancy in the bracing (e.g. cross-bracing in which both members
can resist forces in compression) may be used to increase the robustness of the
system. Also note that at least two bracing systems are required, see
Section 5.2.4.

If a system for resisting horizontal forces is moment resisting connections (i.e.


frame action), then each element of the frame with a moment resisting joint is
part of that system and should be notionally removed, one at a time.

If the system for resisting horizontal forces is a concrete core, then each storey

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


high segment of wall forming part of the core should be considered as an
element of that system and notionally removed, one at a time. The length of
load-bearing wall to be considered as one element, is defined in Approved
Document A, as 2.25 times the storey height or the length between lateral
supports (e.g. returns), whichever is greater.

If the system for resisting horizontal forces is triangulated bracing (as shown in
Figure 5.10), then each element of the bracing system should be notionally
removed, one at a time. This includes the beam and column members forming
part of the bracing truss.

Figure 5.10 Triangulated bracing elements

5.2.7 Key elements


Approved Document A states in Clause 5.3 that a key element:
Should be capable of sustaining an accidental design loading of 34
kN/m2 applied in the horizontal and vertical directions (in one direction
at a time) to the member and any attached components (e.g. cladding

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 24 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

etc.) having regard to the ultimate strength of such components and their
connections. Such accidental design loading should be assumed to act
simultaneously with 1/3 of all normal characteristic loading (i.e. wind
and imposed loading).

From this requirement and from BS 5950-1 it can be determined that the design
load for a key element is:
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

= 1.0 Accidental load + 1.05 (1.0 Dead load + 0.33 Imposed


Load + 0.33 Wind Load)

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
For the value of accidental loading to be applied, BS 5950-1 refers to
BS 6399-1[14], where the accidental loading is also given as 34 kN/m2.
BS 5950-1 recommends that any other structural component that provides
lateral restraint vital to the stability of a key element should also be designed
as a key element. The design of a key element is demonstrated in the worked
example in Appendix A.

When considering the accidental loading on a large area (e.g. on a floor slab
supported by a transfer beam), it is reasonable to limit the area that is subjected
to the 34 kN/m2 load because a blast pressure is unlikely to be this high on all

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


the surfaces of a large enclosed space. The maximum area is not defined in the
code or in Approved Document A, but could be inferred from the length of
load-bearing wall to be considered (Approved Document A, Section 5.3), which
is 2.25 times the storey height, say 2.25 2.9 = 6.5 m. Therefore, a
maximum area that would be subjected to the 34 kN/m2 could be a 6.5 6.5 m
square.

For the design of a key element, it is necessary to consider what components,


or proportion of components, will remain attached to the element in the event of
an incident. The application of engineering judgement will play a major part in
this process. For framed construction the walls and cladding will normally be
non-structural. Therefore, it is likely that the majority of these will become
detached from the key element during an incident, as shown in Figure 5.11.
For the column member key element shown in Figure 5.11, an accidental load
of 34 kN/m2 should be applied over a width of B for accidental loading about
the major axis. The column section should be checked for the combination of
moments and axial load using the design load case given above. The accidental
loading about the minor axis over a width of D (in this case) also needs to be
considered. The accidental loading should only be considered as acting in one
direction at a time and there is no requirement to consider a diagonal loading
case i.e. at angle to the major and minor axes.

Part of component
Part of component that is detached
that remains attached D Key element
from key element
to key element during an incident
after an incident

Plan view
Figure 5.11 Component attached to a key element (column)

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 25 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Determining the width B is very subjective. An estimation of what will


remain attached to the key element (during a loading of 34 kN/m2) will
obviously depend on what is attached and how it is fixed to the element.

If BS 5950-1 Clause 2.4.5.3 is satisfied either by the provision of tying or by


notional removal, no members of the building need to be designed as key
elements.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

5.3 Practical solutions for Class 2B buildings


5.3.1 Connections

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
In most situations, horizontal ties will require end connections that have tying
capacities similar to their shear load. Table 5.3 gives approximate tying
capacities for commonly used nominally pinned connections. Exact tying
capacities for these connections can be obtained from P212[10].

Table 5.3 Typical simple connection tying capacities


Connection type Tying capacity
(as a percentage of its shear capacity)
Fin Plate 100 210 %

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Double Angle Cleat 60 230 %
Flexible End Plate 40 140 % (see note*)
*Note: Percentages given are for connections with end plates of 10 mm and 12 mm thick.
Standard end plates are 8 mm or 10 mm, but to improve tying capacities end plates of
10 mm or 12 mm may be used. These can still be considered as simple connections
(i.e. nominal pins) for the analysis and design.

When the tying capacities of the connections given in Table 5.3 are used in
combination with the tying reduction factors given in Table 5.1, it can be seen
that all standard fin plate and angle cleat connections will be sufficient for
buildings up to three storeys.

Tying capacities do not need to be provided entirely by the steel frame. For
example, in composite construction a certain amount of the required horizontal
tying can be provided by the concrete slab reinforcement, provided that it is
designed and detailed for this purpose. SCI publication P213[15] provides
guidance on utilising slab reinforcement in the connection design.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 26 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

6 CLASS 3 BUILDINGS

6.1 The requirements for Class 3 buildings


Class 3 buildings are very high consequence buildings such as grandstands
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

(with capacity for over 5000 spectators), buildings greater than 15 storeys,
hospitals over three storeys and buildings containing hazardous substances
and/or processes. The requirements for Class 3 buildings given in Approved
Document A, Clause 5.1.e are different in nature to those for the other classes

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
of building (see below).

For Class 3 buildings - A systematic risk assessment of the building


should be undertaken taking into account all the normal hazards that
may reasonably be foreseen, together with any abnormal hazards.

Critical situations for design should be selected that reflect the


conditions that can reasonably be foreseen as possible during the life of
the building. The structural form and concept and any protective
measures should then be chosen and the detailed design of the structure
and its elements undertaken in accordance with the recommendations

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


given in the Codes and Standards given in paragraph 5.2.

Despite stating the need for a risk assessment and the selection of critical
situations for design, this guidance is vague and provides the designer with little
assistance on what is actually required or how to proceed. The following
Sections provide direction to the designer and sources of further information. It
is important that the degree of complexity of the risk assessment is appropriate
for the building being considered. When dealing with Class 3 buildings, the
designer needs to use applied common sense to ensure that there are no weak
links in the building which, if damaged, would result in substantial and
disproportionate damage.

The ODPM intend to produce specific guidance on dealing with Class 3


buildings. It is not known when this guidance is likely to be published.

Although not specifically stated in Approved Document A, all the provisions of


robustness that are recommended for Class 2B Buildings should also be applied
to Class 3 Buildings, unless there are specific reasons why they are not
appropriate.

It must be remembered that the objective is to design against disproportionate


collapse, not against collapse from any cause. If the event is sufficiently large
then a total collapse of the building may not be considered as disproportionate
(see reference 7 for further discussion).

6.2 Risk Assessment


The purpose of a risk assessment is to determine whether there are any
unacceptable risks and if so to suggest steps to mitigate the risks. The basic
steps required for a risk assessment are given below:

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 27 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

1. Identify hazards (see Section 6.4) to form the basis of a risk register.
This is an absolute minimum for Class 3 buildings, to demonstrate that
the possible hazards have at least been thought about by the designer.
2. Determine or estimate the severity of the consequences of each hazard.
3. Assess the likelihood of each hazard occurring.
4. Estimate the risk of each hazard. The risk is usually expressed as a
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

function of the severity and the likelihood for each hazard.


5. Evaluate which hazards have unacceptable levels of risk.
6. Propose risk mitigation measures for any unacceptable risks.

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
The hierarchy of risk control is a) to prevent the hazard from occurring, b) to
reduce the probability of the hazard occurring, and c) to reduce the severity of
the consequences. Further guidance is provided in Section 6.5.

6.3 Critical situations for design


The guidance given in Approved Document A states that critical situations for
design should be considered. This consideration is partly covered by the
creation of a risk register (step 1, Section 6.2). However, having identified the

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


possible hazards, their possible effects on the building need to be addressed and
whether or not they are likely to cause disproportionate collapse.

The effect on the building of hazards will be difficult to judge accurately


because by their very nature they are unexpected actions. A possible solution to
this problem could be to consider the effect on the building of the notional
removal of a group of columns, provided that a hazard which could cause this
can be foreseen. For example, a building at the bottom of a railway
embankment could be hit by a derailed locomotive causing the removal of more
than one external column. If this damage caused disproportionate collapse to
part of the building, then action would need to be taken (see Section 6.5). It
could also be argued that a Class 3 Building should not be located where such
an incident is possible.

Determining whether collapse is disproportionate, is not a straightforward issue.


The only guidance which is given in Approved Document A is for the notional
removal of one column where damage not exceeding 70 m2 or 15% of the floor
area (whichever is less) is considered proportionate. Therefore, if a hazard
causes the removal of two columns, it seems reasonable to double this limit and
so forth for more columns up to the recommended 200 m2 limit from prEN
1991-1-7[5].

6.4 Hazards
Hazards are events that cause undesired affects i.e. harm to people, loss of life,
damage to property or environmental damage. However, Part A of the Building
Regulations is mainly concerned with the safety of people in and around
buildings. Hazards may be accidental or deliberate. Approved Document A
states that normal and abnormal hazards should be considered.
Reference 16 includes a list of possible hazards that may be considered, along
with proposals for designing to comply with the guidance in Approved
Document A.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 28 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Abnormal hazards can be considered as hazards that are specific to certain


buildings, either because of their location (e.g. train impact, rock fall) or due to
their political, commercial or historical importance (e.g. terrorist attack).
Normal hazards can be considered as non building-specific hazards (e.g. gas
explosion, vehicle impact, design error). The categorisation of hazards as
normal or abnormal is largely immaterial, provided that all the reasonably
foreseeable hazards are considered.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

In addition to the disproportionate collapse considerations, it may be a


requirement of certain buildings that they are designed to resist specific hazards
(e.g. earthquakes, terrorist explosions). Buildings constructed in seismic zones

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
should be designed to resist the affects of earthquakes using the appropriate
design code (e.g. Eurocode 8[17]). Comprehensive guidance for designing
buildings to resist terrorist explosions is given in SCI publication P244[18]. Any
hazard that has been specifically addressed outside the disproportionate collapse
requirements need not be reconsidered in the risk assessment required for Class
3 buildings. However, it should still be listed in the risk register.

6.5 Risk Reduction Measures


6.5.1 Preventing hazards

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Totally preventing hazards from occurring is not possible for all types of
hazard. However, significantly reducing the consequences (see 6.5.3) or their
probability (see 6.5.2) is often achievable.

The overall building concept can have significant influence on the type and
magnitude of hazards that need to be addressed. This includes the building
location and proximity to specific hazards. For example, should a hospital be
located near a railway or chemical works? The building structural form must
also be considered. Large parts of the building should not be reliant on one or
two critical members, where possible loads should be distributed between many
members and alternative load paths should be present which could be utilised in
the event of an incident.

Some hazards can be avoided. Deliberate or accidental vehicular impact on the


building may be prevented by the installation of suitable external barriers.
Excluding explosive materials from a building will avoid the hazard of their
explosion.

6.5.2 Reducing the probability of hazards


The likelihood of hazards such as design or construction errors can be reduced
by improving procedures and applying additional precautions for critical
elements.

A simple but effective method of reducing the likelihood of terrorist attack is to


have security checks on people entering the building.

6.5.3 Reducing the consequences of hazards


There are many measures that can be adopted to reduce the consequences of
hazards. Providing increased levels robustness (e.g. providing reserves of
strength, alternative load paths, and resistance to degradation) is the most
obvious. Sub-dividing larger buildings with movement joints can be used to
restrict the spread of collapse. Sprinklers can be installed to control the spread

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 29 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

of fire and venting panels can be installed to reduce the blast loading from
explosions. Traffic calming measures can be used to reduce the speed of
accidental vehicular impact.

Failure of beams supporting one or more columns and structure providing


lateral stability is likely to have particularly severe consequences and standard
tie forces may prove inadequate in this particular situation. It is recommended
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

that either element removal or key element design is used.

6.6 Sources of further guidance

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
The following references offer further guidance when a risk assessment for
Class 3 Buildings is necessary.

pr EN 1991-1-7[5]
This document contains a great deal of helpful information and guidance that
can be applied to Class 3 Buildings. Annex B provides guidance on risk
assessment methods, acceptance criteria and mitigation measures. Section 3
includes guidance on identifying accidental actions. Sections 4 (Impact) and 5
(Internal Explosions) provide guidance on the size of loads that accidental
actions might cause. This is likely to be a key source of guidance for engineers

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


designing Class 3 buildings.
[18]
SCI publication P244
This publication provides guidance on the protection of commercial buildings
and personnel from the effects of explosions caused by the detonation of high
explosives. It is aimed at engineers and architects who are involved in building
designs where this type of protection is required. Particularly useful topics that
are covered are; calculation of blast loads, structural design approach and non-
structural enhancements.
[19]
BS 7974: 2001
This code of practice provides a framework for developing a rational method for
designing buildings using fire safety engineering. However, there are several
aspects that could be applied more generally to Class 3 Buildings, particularly
the Qualitative Design Review (QDR).
[20]
ISO 2394:1998
This International Standard specifies general principles for the verification of the
reliability of structures subjected to known or foreseeable types of action.
Section 8 provides guidance on the principles of probability-based design and
Annex B provides examples of permanent, variable and accidental actions. The
information contained within this standard is similar to that contained in
EN1990 Eurocode: Basis of Structural Design[21].
[22]
A theory of structural vulnerability
This paper presents a theory of structural vulnerability based on structural form
and connectivity. The theory enables identification of weak links within a
structure and therefore determines elements or groups of elements that may
require special attention when considering structural robustness.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 30 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

[23]
Engineering Safety
This publication provides information on many issues relating to safety and risk.
Subjects of particular interest for dealing with Class 3 buildings are risk
assessments and acceptability of risk. Descriptions of how the theory may be
applied to different civil engineering projects are included.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

6.7 Unclassified Buildings


Approved Document A suggests alternative approaches for buildings which
either,

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
(a) do not fall into any of the classifications of Table 11 (Table 2.1 of this
publication), or
(b) are buildings for which the consequences of collapse may warrant
particular examination of the risks involved.

For (a), the alternative approach suggested consists of following the guidance
given in two reports referenced in Approved Document A. The report titles are
given incorrectly in Approved Document A; they should be:
Guidance on Robustness and Provision against Accidental Actions, July

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


1999 [24]
Proposed Revised Guidance on meeting Compliance with the requirements
of Building Regulation A3: Revision of Allott and Lomax proposals.
Project report number 205966 [25]

Both of these reports (available from the ODPM website) provide methods for
determining the risk category of buildings. They may be used to classify
buildings which do not fall into the descriptions listed in Table 11 (Table 2.1 of
this publication). However, no risk assessment guidance or recommendations
for design are provided, which means their usefulness is limited.

For (b), it is recommended that buildings should be considered as Class 3


buildings and the guidance given in Section 6 of this publication should be
followed.

26

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 31 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

7 REFERENCES

1. Building Regulations 2000 (SI 2000/2531)


As amended by:
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

The Building (Amendment) Regulations 2001 (SI 2001/3335),


The Building (Amendment) Regulations 2002 (SI 2002/440)
The Building (Amendment)(No. 2) Regulations 2002 (SI 2002/2871)
The Building (Amendment) Regulations 2003 (SI 2003/2692)

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
The Building (Amendment) Regulations 2004 (SI 2004/1465))
The Stationery Office

2. Building Regulations 2000 Approved Document A (2004 Edition)


Structure
Approved Document A Amendments 2004
The Stationery Office

3. BRITISH STANDARDS INSTITUTION


BS 5950 Structural use of steelwork in building

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


BS 5950-1:2000 Code of practice for design Rolled and welded
sections

4. Advisory Desk Note 280


Structural integrity of light gauge steel structures, Building Regulations
Approved Document A (2004)
New Steel Construction, vol. 13 (1), Jan 2005

5. prEN 1991-1-7 (July 2004)


Eurocode 1: Actions on structures
Part 1-7: General actions - Accidental Actions
CEN Document (Not a public document)

6. Safety in tall buildings and other buildings of large occupancy


The Institution of Structural Engineers, 2002

7. SHANKAR NAIR, R.qq


Progressive Collapse Basics
AISC, Modern Steel Construction, March 2004

8. Technical Guidance Note: The Building Regulations 2004 Edition


England and Wales
Requirement A3 Disproportionate Collapse
NHBC, 2004

9. Advisory Desk Note 267


Notional horizontal forces and industrial platforms
New Steel Construction, vol. 11 (5), Sept/Oct 2003

10. Joints in Steel Construction: Simple connections (P212)


The Steel Construction Institute and The British Constructional
Steelwork Association, 2002

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 32 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

11. COUCHMAN, G. H., MULLET, D. L. and RACKHAM, J. W.


Composite slabs and beams using steel decking: Best practice for design
and construction (P300)
The Steel Construction Institute, 2000

12. HICKS, S. J. and LAWSON, R. M.


Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Design of composite beams using precast concrete slabs (P287)


The Steel Construction Institute, 2003

13. BS 8110 Structural use of concrete

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
BS 8110-1:1997 Code of practice for design and construction
British Standards Institution, 1997

14. BS 6399-1:1996 Loading for buildings. Code of practice for dead and
imposed loads
British Standards Institution, 1996

15. Joints in steel construction: Composite connections (P213)


The Steel Construction Institute, 1998

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


16. ALEXANDER, S.qq
The New Approach to Disproportionate Collapse
The Structural Engineer, vol. 82, Issue 23, December 2004

17. ENV 1998-1-1:1996


Eurocode 8: Design provisions for earthquake resistance of structures.
General rules. Seismic actions and general requirements for structures
British Standards Institution, 1996

18. YANDZIO, E. and GOUGH, M.


Protection of buildings against explosions (P244)
The Steel Construction Institute,1999

19. BS 7974: 2001 Application of fire safety engineering principles to the


design of buildings
British Standards Institution, 2001

20. ISO 2394: 1998 Second Edition


General principles on reliability for structures
British Standards Institution, 1998

21. BS EN 1990:2002
Eurocode 0: Basis of structural design
British Standards Institution, 2002

22. LU, YU, WOODMAN and BLOCKLEY


A theory of structural vulnerability
The Structural Engineer, vol. 77, Issue 18, September 1999

23. BLOCKLEY, D.
Engineering Safety
McGraw-Hill, 1992

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 33 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

24. Guidance on robustness and provision against accidental actions


(www.odpm.gov.uk)
ODPM, 1999

25. Proposed revised guidance on meeting compliance with the requirements


of Building Regulation A3: Revision of Allot and Lomax proposal.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Project report number: 205966


(www.odpm.gov.uk)
ODPM, 2001

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
26 Steelwork design guide to BS 5950-1:2000. Volume 1: Section
properties and member capacities (Sixth Edition) (P202)
The Steel Construction Institute and The British Constructional
Steelwork Association,, 2001

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 34 Printed 01/07/05


Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc


APPENDIX A

35
WORKED EXAMPLE
P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Printed 01/07/05
To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/
This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Job No. BCB987 Sheet 1 of 13 Rev. A


Job Title Worked Example

Silwood Park, Ascot, Berks SL5 7QN Tying and the avoidance of disproportionate
Subject
Telephone: (01344) 623345 collapse of a Class 2B building
Fax: (01344) 622944
Made by MDH Date Jun 2003
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Client SCI
CALCULATION SHEET Checked by ASM Date Oct 2003

Tying and the avoidance of disproportionate BS 5950-

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
collapse of a Class 2B building 1:2000

A.1 Introduction
The ten-storey building shown in Figure A.1 has been designed on the basis of
Simple Design in accordance with the recommendations of BS 5950-1:2000.
All storeys are 4.0 m high, apart from the ground to first floor, which has a
height of 5.0 m. The columns are laid out on a 6 m 9 m grid with the
primary beams spanning 6 m and the secondary beams spanning 9 m as shown
in Figure A.2. The spacing of the secondary beams is 3.0 m. A composite

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


flooring system is used with steel decking spanning between the secondary
beams. All the secondary and primary beams are assumed to act compositely
with the floor slab. The steel frame is of simple construction, with two braced
bays on each of the four sides providing lateral stability.

Check that the building meets the requirements of Approved Document A and
BS 5950-1:2000 in terms of structural integrity and the avoidance of
disproportionate collapse.

4.0

4.0

4.0

4.0

4.0

4.0

4.0 6.0
6.0
4.0
6.0
4.0 6.0
6.0
5.0
6.0
A B C
9.0 9.0 9.0 9.0

Figure A.1

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 36 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 2 of 13 Rev. A
building
In the first instance, check that integrity is achieved by ensuring that the five
conditions listed in sub-Clause 2.4.5.3 of BS 5950-1:2000 are satisfied. Where
this is not possible, the designer must check that the removal of any individual
member does not lead to disproportionate collapse as defined in BS 5950-1:2000
and Approved Document A. Finally, if the removal of a member would cause
disproportionate collapse, this member must be designed as a key element. All
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

three stages of this process are demonstrated in this example.

In practice, these checks must be carried out on all members to ensure adequate
robustness throughout the structure. However, in this example, the checks are

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
only performed on a typical secondary beam, an edge column and an internal
column. These columns are denoted B and E respectively in Figure A.2.

6.0

6.0

3.0 (typ.)
6.0

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Secondary beams
6.0 (also acting as tie beams)
G H I

6.0 Primary beams


(also acting as tie beams)
D E F

6.0
A B C
9.0 9.0 9.0 9.0

Figure A.2

The composite floor system comprises steel decking spanning between the
secondary beams, as shown in Figure A.3, with a 125 mm thick slab in grade
C30 concrete.

Composite decking
panel

Secondary beams

6.0
Primary beam

9.0

Figure A.3

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 37 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 3 of 13 Rev. A
building
A.1.2 Unfactored roof and floor loads
Dead load (assume the same for roof and floor)
S/w concrete = 2.67 kN/m2
S/w decking = 0.17 kN/m2
S/w beams = 0.15 kN/m2
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Total s/w = 2.99 kN/m2

Allow 0.5 kN/m2 for ceilings and services.

Total unfactored dead load = 3.49 kN/m2

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Imposed load
Roof: 1.0 kN/m2
Floor: 5.0 kN/m2 + 1.0 kN/m2 (partitions) = 6.0 kN/m2

A.1.3 Unfactored cladding loads


The external beams carry a brick and block cavity wall plastered on one side.
From BS 648:1964, the weight of the wall is 3.76 kN/m2. Since the storey
height is 4.0 m, the distributed load on each external beam is
= 4.0 3.76 = 15.04 kN/m

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


wclad

A.1.4 Factored roof loads


Edge column B
Edge columns support an area of 27 m2
WNroof,B = ((3.49 1.4) + (1.0 1.6)) 27 = 175 kN

Internal column E
Internal columns support an area of 54 m2
WNroof,E = ((3.49 1.4) + (1.0 1.6)) 54 = 350 kN

A.1.5 Factored floor loads on secondary beams


Edge beams
w = (15.04 1.4) + (1.5 3.49 1.4) + (1.5 6.0 1.6) = 42.8 kN/m
Total load per beam = 42.8 9.0 = 385.2 kN

Internal beams
w = (3.0 3.49 1.4) + (3.0 6.0 1.6) = 43.5 kN/m
Total load per beam = 43.5 9.0 = 391.5 kN

A.1.6 Factored floor loads on primary beams


It is assumed that the entire slab loading is carried by the secondary beams and
then transferred to the primary beams as point loads. Therefore, the only loads
applied to the primary beams are the internal secondary beam reactions. Each
internal primary beam supports two secondary beams.

Total load per beam = 2 0.5 391.5 = 391.5 kN

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 38 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 4 of 13 Rev. A
building
A.1.7 Factored floor loads on columns
Edge column B
Column B supports 2 edge beams and 1 primary beam and carries half the load
from each beam.
WNfloor,B = (2 0.5 385.2) + (0.5 391.5) = 581 kN
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Internal column E
Column E supports 2 internal secondary beams and 2 internal primary beams
and carries half the load from each beam.

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
WNfloor,E = (2 0.5 391.5) + (2 0.5 391.5) = 783 kN

A.2 Member sizes


The composite beams were designed using the BDES* software and the column
sizes were estimated using the member capacity tables in SCI publication
P202[26]. In sizing the beams, the final composite condition and the construction
stage non-composite condition were both checked. Since the internal and
external beams experience similar loading, only the internal beams were

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


considered. For simplicity, the columns were sized for compression only. In
practice, they would have to be designed as columns in simple construction,
following the procedure outlined in Example 14.
*Available from www.corusconstruction.com/page_679.htm

A.2.1 Beam sizes


Secondary beams
406 140 46 UB in grade S355.

Primary beams
457 152 52 UB in grade S355.

A.2.2 Column sizes


The factored loading, effective lengths and selected column sizes for columns B
and E are given in Tables A.1 and A.2 respectively.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 39 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 5 of 13 Rev. A
building
Table A.1 Edge column B
Column Leff Factored load Selected section Factored load Resistance
location (m) ex. column (all S355) inc. column (kN)
s/w (kN) s/w (kN)
Roof-9 4.0 175 30530597UC 175 3310
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

9-8 4.0 756 30530597UC 761 3310


P202
8-7 4.0 1337 30530597UC 1348 3310
Page D-6
7-6 4.0 1918 30530597UC 1934 3310

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
6-5 4.0 2499 30530597UC 2520 3310
5-4 4.0 3080 30530597UC 3107 3310
4-3 4.0 3661 305305137UC 3693 4620
3-2 4.0 4242 305305137UC 4282 4620
2-1 4.0 4823 305305198UC 4870 6780
1-0 5.0 5404 305305198UC 5462 5920

Table A.2 Internal column E

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Column Leff Factored Selected section Factored Resistance
location (m) load ex. (all S355) load inc. (kN)
column s/w column s/w
(kN) (kN)
Roof-9 4.0 350 30530597UC 350 3310
9-8 4.0 1133 30530597UC 1138 3310 P202
8-7 4.0 1916 30530597UC 1927 3310 Page D-6
7-6 4.0 2699 30530597UC 2716 3310
6-5 4.0 3482 305305137UC 3504 4620
5-4 4.0 4265 305305137UC 4295 4620
4-3 4.0 5048 305305198UC 5085 6780
3-2 4.0 5831 305305198UC 5879 6780
2-1 4.0 6614 305305283UC 6674 9200
1-0 5.0 7397 305305283UC 7473 8030

It is assumed that the columns are spliced every two storeys and that lateral
restraint is provided at every floor. It is further assumed that the columns may
be treated as pin-ended between the floor levels.

A.3 Disproportionate collapse checks using fin


plate beam-to-column connections
Designing Class 2B buildings to satisfy the five conditions listed in 2.4.5.3 of
BS 5950-1:2000 will meet the requirements of Approved Document A. These
five conditions are considered in the Sections below. It is assumed that fin
plates are used for all beam-to-column connections.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 40 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 6 of 13 Rev. A
building
A.3.1 General tying
Horizontal ties should be arranged in continuous lines throughout each floor and
roof level in two approximately perpendicular directions. All members acting as 2.4.5.3 a)
ties and their end connections should be designed to resist a tensile force equal
to the end reaction of the member under factored loads or 75 kN, whichever is
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

greater.

Typical secondary beam (406 140 46 UB in grade S355)


The connection should be designed to resist the beam-to-column reaction in

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
shear and then checked to ensure that it has an adequate tying capacity. The
values of shear capacity and tying capacity used in this example have been
obtained from P212 Joints in steel construction: Simple connections[10] and are
based on the steel connection alone. No allowance has been made for the
capacity of the reinforcement in the concrete to carry some of the load.

Try 290 x 150 x 10 mm fin plate in S275 with two lines of 4 bolts.
Basic requirement 1: Reaction Shear capacity
Reaction under factored loads = 196 kN P212
Shear capacity = 289 kN Table H.30
196 kN < 289 kN

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Therefore the shear capacity is adequate.

Basic requirement 2: Tying force Tying capacity


Required tying force = 196 kN
Tying capacity = 488 kN P212
196 kN < 488 kN Table H.30
Therefore the tying capacity is adequate.

Typical primary beam (457 x 152 x 52 UB in grade S355)


Try 290 x 100 x 10 mm fin plate in S275 with a single line of 4 bolts.
Basic requirement 1: Reaction Shear capacity
Reaction under factored loads = 196 kN P212
Shear capacity = 212 kN Table H.29
196 kN <212 kN
Therefore the shear capacity is adequate.

Basic requirement 2: Tying force Tying capacity


Required tying force = 196 kN
Tying capacity = 334 kN P212
196 kN < 334 kN Table H.29
Therefore the tying capacity is adequate.

A.3.2 Tying of edge columns


Horizontal ties should be provided to hold the vertical perimeter columns in
position. These ties should be capable of resisting a tying force, acting 2.4.5.3 b)
perpendicular to the edge, equal to the greater of 1% of the maximum factored
vertical load in the column adjacent to that level or the load specified in the
general tying requirement.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 41 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 7 of 13 Rev. A
building
Consider the lowest level, where the load in the column is greatest.
From Table 23.1, the load in the column = 5462 kN
1% of 5462 kN = 54.62 kN
The tying force specified in A.3.1 = 196 kN.
Therefore, the general tying requirement is critical in this case.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

A.3.3 Continuity of columns


The column splices should be capable of resisting a tensile force equal to the
largest factored vertical reaction applied to the column at a single floor level 2.4.5.3 c)
located between the column splice under consideration and the next column

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
splice down.

Basic requirement: Applied vertical floor load Column splice capacity


For the purpose of this example, consider column E as a typical internal
column. The factored vertical load applied to the column from each floor is
WNfloor,E = 783 kN.

Consider the weakest splice in that column (that between 305 305 97UC and
305 305 97UC). From Table H.32 of P212[10], the capacity of one external Table H.32
flange cover plate is 794 kN. P212

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Splice capacity = 2 794 kN = 1588 kN
783 kN < 1588 kN Therefore the column splice capacity is adequate.

A.3.4 Resistance to horizontal forces


Condition d) of Clause 2.4.5.3 states that there must be more than one system of
bracing stabilizing the structure in two approximately orthogonal directions. In 2.4.5.3 d)
this Example, this is satisfied by the braced bays shown in Figure A.1

A.3.5 Heavy floor units


Heavy precast floor units are not used in this Example, so condition e) of
Clause 2.4.5.3 does not apply. If heavy precast floor units are used, the 2.4.5.3 e)
designer must ensure that they are sufficiently secure against dislodgement.

A.3.6 Conclusion
Having satisfied the five conditions in Clause 2.4.5.3 of BS 5950-1:2000, it may
be assumed that this building meets the requirements of the regulations for the
avoidance of disproportionate collapse.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 42 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 8 of 13 Rev. A
building
A.4 Disproportionate collapse checks using flexible
end plate beam-to-column connections
As an alternative to fin plate connections, this Section considers the use of
flexible end plates.
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

A.4.1 General tying


Typical secondary beam (406 x 140 x 46 UB in grade S355)
Try 290 x 150 x 8 mm flexible end plate in S275 with 4 rows of bolts.

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Basic requirement 1: Reaction Shear capacity P212
Reaction under factored loads = 196 kN Table H.21
Shear capacity = 378 kN
196 kN < 378 kN
Therefore the shear capacity is adequate.

Basic requirement 2: Tying force Tying capacity


Required tying force = 196 kN P212
Tying capacity = 226 kN Table H.21
196 kN < 226 kN

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Therefore the tying capacity is adequate.

Now consider the situation in which the designer is unable to use such a deep
secondary beam and opts instead for the slightly heavier 305 165 54 UB in
S355.

Try 290 x 150 x 8 mm flexible end plate in S275 with 3 rows of bolts.
Basic requirement 1: Reaction Shear capacity P212
Reaction under factored loads = 196 kN Table H.21
Shear capacity = 333 kN
196 kN < 333 kN
Therefore the shear capacity is adequate.

Basic requirement 2: Tying force Tying capacity


Required tying force = 196 kN Table H.21
Tying capacity = 175 kN P212
196 kN > 175 kN
Therefore the tying capacity is NOT adequate and it is necessary to check for
disproportionate collapse. (In practice it may be more convenient to change the
connection detail and increase the tying capacity.)

A.4.2 Check for disproportionate collapse


If any of the first three conditions listed in Clause 2.4.5.3 of BS 5950-1:2000 2.4.5.3
are not satisfied, the building should be checked to ensure that the removal of
any one column would not lead to disproportionate collapse. Collapse is said to
be disproportionate if at any given level it exceeds 15% of the floor or roof area
or 70 m2. For the purpose of this example, this check has been restricted to
column E. In practice, each column should be checked in turn.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 43 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 9 of 13 Rev. A
building
The checks performed in Section 23.4.1 have already established that the tying
capacity of the flexible end plate connections is inadequate, so the current check
becomes one of measuring the area supported by the column. In this case, the
removal of column E would lead to the collapse of a section of floor measuring
12 m 18 m, i.e. 216 m2 (and possibly more as the floor areas directly above
could also collapse). Therefore, there is a risk of disproportionate collapse
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

and the member should be designed as a key element using the accidental
loading specified in BS 6399-1, i.e. 34 kN/m2.

A.4.3 Key element design

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
The area to which the accidental loading is applied is dependent on the type of 2.4.5.4
cladding or floor decking and, in particular, its integrity under blast loading. In
this example, it is assumed that there is partitioning running between columns
D, E and F, but none in the perpendicular direction. As the partitioning is not
load-bearing, it is reasonable to assume that it is mostly blown out by the blast,
leaving only a small section as shown in Figure 23.4. In this case, the breadth
of partitioning remaining after the blast is estimated to be B + 200 mm.

B + 200

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


D

Figure A.4

In the design of key elements, the accidental loading should be applied in all
directions, but only in one direction at a time. This means checking column E
in bending about both the major and minor axes. The ordinary dead and
imposed loads must also be taken into account (there is no wind loading on
column E) and should be applied simultaneously with the accidental loading. 2.4.5.3
However, the imposed load can be reduced to one third of its normal value for
this check, with a f factor of 1.05. The same f should also be applied to the
dead load, but the accidental load should be factored by 1.0.

All of the calculations below relate to the column length between ground and
first floor levels. In practice, all levels should be checked.

Section properties
The size of the internal column between ground and first floor levels is
305 x 305 x 283 UC, grade S355.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 44 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 10 of 13 Rev. A
building
From section property tables:
Depth D = 365.3 mm
Width B = 322.2 mm
Web thickness t = 26.8 mm P202
Flange thickness T = 44.1 mm Page B 8
Depth between fillets d = 246.7 mm
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Area of cross-section Ag = 360 cm2


Plastic modulus Sx = 5110 cm3
Plastic modulus Sy = 2340 cm3 P202
Elastic modulus Zx = 4320 cm3 Page B 9

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Elastic modulus Zy = 1530 cm3
Radius of gyration rx = 14.8 cm
Radius of gyration ry = 8.27 cm

Grade of steel = S355 3.1.1


40 mm < T < 63 mm Table 9
Therefore py = 335 N/mm2

Axial load
For the purpose of key element design, the factored axial loads applied to the

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


column by the roof and each floor level are as follows:

Roof
WN = 1.05(3.49 + (1.0/3)) 54 = 216.8 kN

Floor
WN = 1.05(3.49 + (6.0/3)) 54 = 311.3 kN

Column self-weight
Unfactored column s/w
= ((44.097)+(24.0137)+(24.0198)+(4.0283)) 9.81/1000
= 52.6 kN

Factored column s/w = 1.05 52.6 = 55.2 kN

Total factored axial load including self-weight


Fc = 216.8 +(9 311.3) +55.2 = 3074 kN

Section classification
According to P202[26], the compact F/Pz limit for a 305 305 283UC in grade P202
S355 is 1.0. Therefore, the section is at least compact. Page D 126

Major axis bending


Loading
The accidental loading about the major axis is applied to the section of
partitioning shown in Figure 23.4.

B = 322.2 mm. Therefore, the total loaded width = 522.2 mm

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 45 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 11 of 13 Rev. A
building
Accidental loading = 0.5222 34 = 17.8 kN/m.

The accidental load is applied uniformly along the column between ground and
first floor levels, with the section of column between floors 1 and 2 unloaded.
Although the column is continuous across the support at floor level 1, it is a safe
approximation to take the maximum moment as wL2/8, where L = 5.0 m. The
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

actual moment will not be greater than this value.


Mx = 17.8 52 /8 = 55.6 kNm.

Bending

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
Basic requirement: Mx Mcx 4.2.5
From P202[26] 1, Mcx = 1710 kNm P202
Page D 126
From above, Mx = 55.6 kNm
55.6 kNm < 1710 kNm
Therefore, the moment capacity is adequate.

Basic requirement: Mx Mb / mLT 4.3.6


From P202[26], for LE = 5.0 m, Mb = 1640 kNm P202
Page D 127
mLT is obtained from Table 18 of BS 5950-1:2000 [3] according to the shape of

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


the bending moment diagram.
mLT = 0.925 Table 18
Mb / mLT = 1640/0.925 = 1773 kNm
From above, Mx = 55.6 kNm
55.6 kNm < 1773 kNm
Therefore, the buckling resistance moment is adequate.

Interaction checks section capacity

Fc Mx My 4.8.3.2. a)
Basic requirement: + + 1
Ag p y M cx M cy

From P202, Ag py = 12100 kN P202


From above, Fc = 3074 kN Page D 127
There is no minor axis loading in this case so the third term in the equation can
be ignored.

3074 55.6
+ + 0 = 0.254 + 0.033 = 0.29 <1
12100 1710

Interaction checks member buckling


Fc mx Mx my My
Basic requirement: + + 1 4.8.3.3.1
Pc py Z x py Z y

For LE = 5.0 m, Pc = 8030 kN P202


Page D 126
mx is obtained from Table 26 of BS 5950-1:2000 4.8.3.3.4
Table 26
mx = 0.95

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 46 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 12 of 13 Rev. A
building
pyZx = 1450 kNm
P202
3074 0.95 55.6 Page D 127
+ + 0 = 0 .383 + 0.036 = 0.42 <1
8030 1450

my My
Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

Fc m LT M LT
Basic requirement: + + 1 4.8.3.3.1
Pcy Mb py Z y

MLT is the maximum major axis moment in the segment = 55.6 kNm.

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
For LE = 5.0 m, Pcy = 8030 kN
P202
Mb = 1640 kNm
Page D 127
mLT = 0.925
Table 18
3074 0.925 55.6
+ + 0 = 0.383 + 0.031 = 0.41 <1
8030 1640

Therefore, the column is adequate when subjected to the accidental load


causing bending about the major axis.

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


Minor axis bending
Loading
The accidental loading about the minor axis is applied to the column and an
assumed thickness of partitioning, say 50 mm.

D = 365.3 mm. Therefore, the total loaded width = 415.3 mm,


say 415 mm.

Accidental loading = 0.415 34 = 14.1 kN/m.

Once again, assume the maximum moment is given by wL2/8.


My = 14.1 52 /8 = 44.1 kNm.

Bending
4.2.5
Basic requirement: My Mcy
Page D-126
From P202, Mcy = 615 kNm

From above, My = 44.1 kNm


44.1 kNm < 615 kNm

Therefore, the moment capacity is adequate.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 47 Printed 01/07/05


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Tying and the avoidance of disproportionate collapse of a Class 2B


Sheet 13 of 13 Rev. A
building
Interaction checks section capacity
Fc Mx My
Basic requirement: + + 1 4.8.3.2. a)
Ag p y M cx M cy

As before, Ag py = 12100 kN and Fc = 3074 kN


Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

There is no major axis loading in this case so the second term in the equation
can be ignored.

This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005
3074 44.1
+0+ = 0.254 + 0.072 = 0.33 <1
12100 615

Interaction checks member buckling

Fc mx Mx my My
Basic requirement: + + 1
Pc py Z x py Z y

From above, the column resistance Pc = 8030 kN

To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/


The shape of the bending moment diagram is identical to that for major axis
bending (even though the values are different). Therefore, my = 0.95.
py Zy = 512 kNm

3074 0.95 44.1


+ 0+ = 0.383 + 0.082 = 0.47 <1
8030 512

Fc m LT M LT my My
Basic requirement: + + 1
P cy Mb py Z y

3074 0.95 44.1


+ 0+ = 0.383 + 0.082 = 0.47 <1
8030 512

Therefore, the column is also adequate when subjected to the accidental load
causing bending about the minor axis.

Note: The calculations given above demonstrate the procedure for designing a
key element. However, in the vast majority of circumstances, the recommended
approach is to satisfy the tying requirements in Clause 2.4.5.3 of BS 5950-1:
2000. The key element route should only be followed as a last resort.

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc 48 Printed 01/07/05


Licensed copy:dewhurst, Dewhurst MacFarlane & Partners, 27/10/2006, Uncontrolled Copy, SCI

P:\Pub\Pub800\Sign_off\P341 (ED003)\Draft V08.doc


P341: Guidance on meeting the Robustness Requirements in Approved Document A (2005 Edition)

Printed 01/07/05
To buy a hardcopy version of this document call 01344 872775 or go to http://shop.steelbiz.org/
This material is copyright - all rights reserved. Reproduced under licence from The Steel Construction Institute on 31/10/2005

You might also like