Derating Factors
a) Variation of ground temperature 0.91 ----------> a
(of cond. Temp 90 deg C for XLPE)
b) Variation of soil thermal resistivity 1.11 ----------> b
(3 cables in trefoil)
c) Group rating factor for 3 group of 0.88 ----------> c
cables in trefoil formation and touching
each other
d) Rating factor for depth of laying 0.91 ----------> d
Derating Factors
a) Variation of ambient temperature 1 ----------> a
to 50 deg C
b) Group rating factor for 2 ckt. of cables in 0.98 ----------> b
trefoil formation to top tire with
horizontal formation.
347284048.xls Page 1 of 8
POWER CABLE SIZING CALCULATION
Derating Factors
a) Variation of ambient temperature 1 ----------> a
to 50 deg C
b) Group rating factor for 2 ckt. of cables in 0.98 ----------> b
trefoil formation to top tire with
horizontal formation.
Derating Factors
a) Variation of ambient temperature 1 ----------> a
to 50 deg C
b) Group rating factor for 2 ckt. of cables in 0.98 ----------> b
trefoil formation to top tire with
horizontal formation.
Hence number of run required for 3.5C x 300 sq.mm. AL, XLPE
For the Phase 1 nos.
347284048.xls Page 2 of 8
POWER CABLE SIZING CALCULATION
Derating Factors
a) Variation of ambient temperature 1 ----------> a
to 50 deg C
b) Group rating factor for multi core cables 0.93 ----------> b
with 6 cables in rack, laid in
horizontal formation.
Hence number of run required for 3.5C x 300 sq.mm. AL, XLPE
1 nos.
Check for voltage drop
AC Resistance of the cable 0.1 ohms/km
Equivalent Star reactance 0.0877 ohms/km
Equivalent Impedance 0.1330 ohms/km
Route length 0.07 km
Cable Impedance 0.0093 ohms Note: Starting is not critical becasuse
Voltage drop during normal load 4.2066 Volts of Delta / Star start
Percentage Drop 1.01% < 3% (permissible limit)
6. Cable sizing for 15kW Jockey Pump Motor for Fire Fighting System
347284048.xls Page 3 of 8
POWER CABLE SIZING CALCULATION
1 nos.
Check for voltage drop
AC Resistance of the cable 1.1 ohms/km
Equivalent Star reactance 0.0827 ohms/km
Equivalent Impedance 1.1031 ohms/km
Route length 0.07 km
Cable Impedance 0.0772 ohms
Voltage drop during normal load 6.9775 Volts
Percentage Drop 1.68% < 3% (permissible limit)
347284048.xls Page 4 of 8
A
POWER CABLE SIZING CALCULATION
with 6 cables in rack, laid in
horizontal formation.
Composite derating factor (a*b) 0.93 A
Continuous current rating after applying 39.06 A
the derating factor
9. Cable sizing for Air Handling Unit (A.H.U.) for Air Conditioning
347284048.xls Page 5 of 8
POWER CABLE SIZING CALCULATION
10. Cable sizing for Winter Heating Unit for Air Conditioning
11. Cable sizing for Ventilation Fan (Axail Flow type) for Exhaust Ventilation
347284048.xls Page 6 of 8
POWER CABLE SIZING CALCULATION
Voltage drop during normal load 2.2738 Volts
Percentage Drop 0.55% < 3% (permissible limit)
12. Cable sizing for Ventilation Fan (Propeller) for Exhaust Ventilation
Voltage 415 V
Rating of the equipment 100.00 A
347284048.xls Page 7 of 8
POWER CABLE SIZING CALCULATION
to 50 deg C
b) Group rating factor for multi core cables 0.93 ----------> b
with 6 cables in rack, laid in
horizontal formation.
Composite derating factor (a*b) 0.93
Continuous current rating after applying 428.73 A
the derating factor
Hence number of run required for 3.5C x 300 sq.mm. AL, XLPE
1 nos.
Check for voltage drop
AC Resistance of the cable 0.533 ohms/km
Equivalent Star reactance 0.0771 ohms/km
Equivalent Impedance 0.5385 ohms/km
Route length 0.045 km
Cable Impedance 0.0242 ohms
Voltage drop during normal load 4.1974 Volts
Percentage Drop 1.01% < 3% (permissible limit)
347284048.xls Page 8 of 8