FD100 SERIES

General Description Display / Function Panel


The Cutler Hammer FD100 microprocessor based
Diesel Engine Fire Pump Controller is designed to Behind the breakable panel on the front of
control and monitor 12 or 24 volt, listed diesel fire the FD100 is the Display/Function Panel -
pump engines. These controllers are listed by UL the information and programming center for
and ULC, and approved by Factory Mutual and CSA, the controller. This panel includes (from
as well as meeting or exceeding the requirements top to bottom), alarm and condition
of NFPA 20 and NFPA 70. LED indicators, main switch membrane
pushbuttons, LCD battery and system
The FD100 Diesel Controller includes dual 10Amp, pressure readout, programming keys and
current limiting, solid state battery chargers which function keys.
maintain the proper charge on both sets of batteries
at all times. The TRI-colour LED annunciator lights are
color keyed to the urgency of the indication.
All FD100 Controllers come with the features
Green:
required for starting and stopping the diesel engine,
Normal running
monitoring the engine operating conditions, and
conditions.
alarming (audible and visible) for the engine,
controller, and system conditions. Yellow:
Supervisory alarms.
Operation
These controllers automatically start the fire pump Red:
diesel engine to provide adequate water pressure Critical alarms.
to the fire protection system. The FD100 monitors The LCD readout includes all programming
the fire sprinkler system pressure using a pressure parameters in addition to battery and
transducer. Upon detecting a drop in system pressure information.
pressure, the microprocessor sends a start signal to
the engine, initiating its crank cycle. The starting The F1, F2, F3, and Menu keys are
process can be initiated by other causes such as used to program the FD100 - set points,
deluge valve opening or remote start pushbutton. timers, etc.. The Function keys are self
explanatory.
The crank cycle consists of six periods of 15
second duration, separated by five rest periods of
15 second duration alternating on each set of Relay Board
batteries. If the engine does not start within this
cycle, audible and visible Fail to Start alarm is Clearly labeled pull-apart terminal blocks for
activated. Should voltage of either battery fall ease of wiring and connections.
below 67% of normal during the crank cycle, a
Battery Failure alarm will be activated and the All relays labeled with full
FD100 will alter the sequence by continuing the description as well as
process utilizing the remaining good battery. corresponding three letter
designation as indicated on the
The crank cycle terminates when the engine starts wiring diagram.
and the FD100 continues to monitor the batteries
and engine conditions, such as: water temperature, Visual LED indication to show
oil pressure, and speed (rpm). energized state of relay.

The FD100 comes factory set in the "Automatic All plug-in relays are identical
Stop" mode. It can be easily programmed for 3PDT, allowing complete
Manual Stop. In this configuration, the engine must interchangeability.
be shutdown by either placing the main switch in All terminal numbers are indicated
the "OFF" position or, if all starting conditions are on both the stationary and moveable
satisfied, by pressing the "Stop" pushbutton on the portion of the terminal blocks.
outside of the enclosure.
Pump Room Trouble and Engine
The FD100 can be programmed for Auto Stop, Trouble common alarm relays are
which incorporates the RPT timer, without the standard.
addition of any auxiliary equipment.

The FD100, Diesel Fire Pump Controller is designed and


built to the latest requirements of NFPA 20.
Standard Features Alarm Messages
NEMA Type-2 Drip Proof Auto Mode
Enclosure Fail to Start
Dual 10 Amp Battery Low Oil Pressure
Chargers Engine Overspeed
Pressure Transducer Engine Run
(0-600 psi)
Battery Failure
Printer / Recorder
Charger Failure
Relay Energized
Low Fuel Level
Indicator
High Fuel Level
Weekly Test Timer
Fuel Spill
Run Period Timer
High Engine Temperature
AC Power Failure Start
Low Pump Room Temperature
Sequential Start Timer
High Reservoir Level
Manual Stop
Low Reservoir Level
Remote Start
Deluge Valve Start
Options
Lamp Test Circuit
Alarm Silence Button Enclosures
Time Display Button NEMA 12, 3R, 4, 4X
Printer Command Button (2) sets Form C Relays rated Anti-Condensation Space
10A, 220VAC for: Heaters
(3) sets Form C Relays rated Fuel Solenoid Valve Heater Only
10A, 220VAC for: Drain Solenoid Valve Heater with Humidistat
Manual Mode (1) set Form C Relays rated Heater with Thermostat
OFF Mode 10A, 220VAC for: 12 Floor Mounted Legs
Engine Trouble Common Alarm Pressure switch: 0 - 600psi,
Pump Room Trouble Cranking Battery #1 Sea water service
Engine Run Cranking Battery #2 Energize to stop circuit

Printer / Recorder

Details all alarm and events including:


Cause of alarm/event
Date and Time
Operating mode of controller
at time of alarm
"Status Print Out" detailing controller parameter configuration
Excellent troubleshooting tool
Capable of operating between 8-32VAC/DC
Electric Fire Pump Controller Family

FD20 FDC
Limited Service Compact
Controller

FD60
Auto transformer
Reduced Voltage

FD30 FDF
Across-the-Line Foam Pump
Controller

FD70
Wye-Delta
Open Transition
Reduced Voltage

FD40 FDR
Part Winding Residential
Reduced Voltage

FD80
Wye-Delta
Closed Transition
Reduced Voltage

FD50 FT Series
Primary Resistor Automatic
Reduced Voltage Transfer Switch

FD90
Soft Start
Reduced Voltage

FPMP
Fire Pump
Multi-Pack

Cutler-Hammer also offers a complete line of Jockey Pumps and Remote Alarm Panels.
Phone: 403-948-7955
Cutler-Hammer
403 East Lake Blvd., Airdrie, Alberta CAN T4B 2B9
Fax: 403-948-6967
www.chfire.com
Publication No TD.42.01B.T.K
July 2002
Printed in Canada / IM