www.hilti.lu PROFIS Anchor 2.4.

6
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: -|- Date: 1/30/2017
E-Mail:

Specifier's comments:

1. Input data
Anchor type and diameter: HIT-RE 500 + Rebar, 16mm
Dynamic set or any suitable annular gap filling solution
Effective embedment depth: h ef,opti = 203 mm (hef,limit = 320 mm)
Material: BSt 500 S
Evaluation Service Report: ETA 04/0027
Issued I Valid: 6/26/2013 | 5/16/2018
Proof: design method SOFA design method + fib (07/2011) - after ETAG BOND testing
Stand-off installation: e b = 0 mm (no stand-off); t = 13 mm
Anchor plate: lx x l y x t = 300 x 300 x 13 mm (Recommended plate thickness: not calculated)
Profile no profile
Base material: uncracked concrete , C25/30, fc = 25.00 N/mm; h = 500 mm, Temp. short/long: 40/24C
Installation: hammer drilled hole, installation condition: dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm)
no longitudinal edge reinforcement

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.lu PROFIS Anchor 2.4.6
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: -|- Date: 1/30/2017
E-Mail:

2. Load case/Resulting anchor forces


Load case (Design loads):
Anchor reactions [kN]
Tension force: (+Tension, -Compression)

Anchor Tension force Shear force Shear force x Shear force y


1 0.000 5.374 -5.164 -1.486 y
Tension
3 4
2 11.995 7.739 -5.164 -5.764
3 33.887 1.730 -0.886 -1.486
4 58.779 5.832 -0.886 -5.764
x
max. concrete compressive strain []: 0.91
max. concrete compressive stress [N/mm]: 27.44
resulting tension force in (x/y)=(32/69) [kN]: 104.700
resulting compression force in (x/y)=(-83/-115) [kN]: 172.200 Compression
1 2

3. Tension load SOFA (fib (07/2011), section 16.2.1)


Proof Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 58.779 79.286 74 OK
Combined pullout-concrete cone 104.661 109.704 95 OK
failure**
Concrete Breakout Strength** 104.661 106.130 99 OK
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

Steel Strength
NRk,s [kN] g M,s NRd,s [kN] NSd [kN]
111.000 1.400 79.286 58.779

Combined pullout-concrete cone failure


2 0 2 2
Ap,N [mm ] Ap,N [mm ] y A,Np t Rk,ucr,25 [N/mm ] s cr,Np [mm] c cr,Np [mm] c [mm]
348540 191147 1.823 14.00 437 219 10000
2 2 0
yc t Rk,ucr [N/mm ] maxt Rk,ucr [N/mm ] y g,Np y g,Np
1.018 14.26 15.59 1.092 1.033

e c1,N [mm] y ec1,Np e c2,N [mm] y ec2,Np y s,Np y re,Np


2 0.992 39 0.847 1.000 1.000
0
NRk,p [kN] NRk,p [kN] g M,p NRd,p [kN] NSd [kN]
145.487 230.377 2.100 109.704 104.661

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.lu PROFIS Anchor 2.4.6
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: -|- Date: 1/30/2017
E-Mail:

Concrete Breakout Strength


2 0 2
Ac,N [mm ] Ac,N [mm ] y A,N c cr,N [mm] s cr,N [mm]
590121 370881 1.591 305 609

e c1,N [mm] y ec1,N e c2,N [mm] y ec2,N y s,N y re,N k1


2 0.994 39 0.886 1.000 1.000 11.000
0
NRk,c [kN] g M,c NRd,c [kN] NSd [kN]
159.077 2.100 106.130 104.661

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.lu PROFIS Anchor 2.4.6
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: -|- Date: 1/30/2017
E-Mail:

4. Shear load SOFA (fib (07/2011), section 16.2.2)


Proof Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 7.739 36.667 21 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 18.885 252.050 7 OK
Concrete edge failure in N/A N/A N/A N/A
direction**
* anchor having the highest loading **anchor group (relevant anchors)

Steel Strength (without lever arm)


VRk,s [kN] g M,s V Rd,s [kN] VSd [kN]
55.000 1.500 36.667 7.739

Pryout Strength (Concrete Breakout Strength controls)


2 0 2
Ac,N [mm ] Ac,N [mm ] y A,N c cr,N [mm] s cr,N [mm] k4
622521 370881 1.678 305 609 2.000

e c1,V [mm] y ec1,N e c2,V [mm] y ec2,N y s,N y re,N k1


63 0.829 52 0.854 1.000 1.000 11.000
0
NRk,c [kN] g M,c,p VRd,c1 [kN] VSd [kN]
159.077 1.500 252.050 18.885

5. Combined tension and shear loads SOFA (fib (07/2011), section 16.2.3)
bN bV a Utilization bN,V [%] Status
steel 0.741 0.159 2.0 57 OK
concrete 0.986 0.075 1.5 100 OK
a a
bN + bV <= 1
6. Displacements
The displacement of the highest loaded anchor should be calculated according to the relevant approval under the effect of the following
characteristic loads.
NSk = 43.540 [kN]
VSk = 5.730 [kN]

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7. Warnings
The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient sompressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means.
The compliance with current standards (e.g. EC3) is the responsibility of the user
Characteristic bond resistances depend on short- and long-term temperatures.
Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
To avoid failure of the anchor plate the required thickness can be calculated in PROFIS Anchor. Load re-distributions on the anchors due to
elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be sufficiently stiff, in order not to be deformed
when subjected to the loading!
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.lu PROFIS Anchor 2.4.6
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: -|- Date: 1/30/2017
E-Mail:

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.lu PROFIS Anchor 2.4.6
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: -|- Date: 1/30/2017
E-Mail:

8. Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500 + Rebar, 16mm
Profile: no profile Installation torque: 0.000 kNm
Hole diameter in the fixture: df = 16 mm Hole diameter in the base material: 20 mm
Plate thickness (input): 13 mm Hole depth in the base material: 203 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 243 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
Annular gap must be removed by e.g. filling the holes with mortar of sufficient compressive strength.

8.1. Required accessories

Drilling Cleaning Setting


Suitable Rotary Hammer Manual blow-out pump Dispenser including cassette and mixer
Properly sized drill bit Proper diameter wire brush For deep installations, a piston plug is
necessary
Dynamic set
Torque wrench
y

60.0
150.0

3 4

x
150.0

1 2
60.0

60.0 60.0
150.0 150.0

Coordinates Anchor [mm]


Anchor x y c -x c +x c -y c +y
1 -90 -90 - - - -
2 90 -90 - - - -
3 -90 90 - - - -
4 90 90 - - - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.lu PROFIS Anchor 2.4.6
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: -|- Date: 1/30/2017
E-Mail:

9. Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard
to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret
norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a
specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not
use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in
each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

You might also like