Professional Documents
Culture Documents
HRV
(Heat Reclaim Ventilation)
VAM GJ Series
ED71-613
Table of Contents i
ED71-613
Nomenclature
V A M 500 GJ VE
Ventilation
Air
Mounted type
Air flow rate (m3 / h)
Major design category
(Design category for EC application)
Power supply
VE: Single phase 50 Hz 220 240 V,
60 Hz 220 V
(HC0001)
Note:
HRV means; Heat Reclaim Ventilation = Total Heat Exchanger (Old name)
ii Table of Contents
ED71-613
HRV
(Heat Reclaim Ventilation)
Model name
VAM 150GJVE
VAM 250GJVE
VAM 350GJVE
VAM 500GJVE
VAM 650GJVE
VAM 800GJVE
VAM1000GJVE
VAM1500GJVE
VAM2000GJVE
VAMGJ Series 1
Product introduction ED71-613
1. Product introduction
1.1 HRV (Heat Reclaim Ventilation)
Background
To maintain the comfortable environment in a building, the fresh air intake is essential the same as an appropriate room
temperature control.
The heating / cooling efficiency of conventional standard ventilating systems drops during cooling / heating operation and it is
waste of energy.
The Heat Reclaim Ventilation was developed to solve those problems.
What is HRV (Heat Reclaim Ventilation) ?
HRV is a system which recovers the thermal energy of exhaust air and reuses it for heating or cooling of supply air.
It exchanges heat between the exhaust and the supply air.
Daikins HRV
Daikins HRV greatly reduces the total power consumption by operation interlocked with air conditioner such as VRV or SkyAir.
The total heat exchange mode and the ventilation mode can be automatically selected by setting to the automatic ventilation mode.
Main Features
1. The operation is available when the outdoor air temperature is down to 15C.
2. Interlocked operation with VRV (SkyAir)
3. Automatic ventilation mode changeover
4. Energy Saving
5. FRESH-UP operation
6. Quiet operation
7. Easy installation
8. Easy maintenance
9. Wide variety of optional accessories
ON / OFF signal
Cooling / Heating mode signal HRV
Setting temperature signal
Ventilation mode signal
Needs no dedicated
remote controller
Operation mode signal
Filter cleaning signal
Alarm signal
VRV or SkyAir
indoor unit
Remote Controller
(HC0002)
2 VAMGJ Series
ED71-613 Product introduction
1.2 Structure
OA
(Outdoor air)
[Fresh air from outdoor]
EA
(Exhaust air)
[Exhaust air to outdoor]
SA
(Supply air)
[Feed air to room]
RA
(Return air)
[Exhaust air from room]
3P034927-5J
VAM1500GJVE, VAM2000GJVE
OA
(Outdoor air) (1) Hanger bracket
(3) Exhaust fan [Fresh air from outdoor] (7) Maintenance cover
EA
(Exhaust air)
[Exhaust air to outdoor]
SA
(Supply air)
[Feed air to room]
(5) Damper
VAMGJ Series 3
Product introduction ED71-613
1.3 Features
1.3.1 Interlocked operation with VRV (SkyAir)
1. Simultaneous ON / OFF with the indoor unit by the indoor unit remote controller.
2. HRV independent operation during air conditioning off season by the indoor unit remote controller.
3. Automatic ventilation mode changeover: Auto / Heat Recovery / Bypass
4. Fan speed changeover by the indoor unit remote controller : High / Low (Ultra-High / High, Ultra-High / Low)
5. Precooling / heating control function setting to delay the start of ventilation during air conditioner start-up to realize the high
energy saving efficiency.
6. FRESH-UP operation setting
7. Filter sign display notifies the time for cleaning the filter.
8. No need to purchase or install the HRV exclusive remote controller
9. Advantage to IAQ (Internal Air Quality)
Note:
5,6 can be set at the initial setting only.
Indoor
unit
Structure HRV HRV
Remote Remote
Controller Controller
(HC0228) (HC0229)
Dust does not fall off from the air filter because the air supply fan If conventional HRV, with exclusive remote controller, is directly
of the interlocked indoor unit remains activated even when the connected to indoor unit of air conditioner, dust may fall off from
HRV is operated independently. air filter when air conditioner is OFF.
Installation Examples
(HC0007) (HC0008)
4 VAMGJ Series
ED71-613 Product introduction
Exhaust Return
Approx. 20% reduction Air
Air
of heating / cooling load
Outdoor Supply
Air Air
Heat Exchanger Element
(Heat Recovery) (HC0230)
Proper use of Heat recovery ventilation and normal ventilation saves energy.
When the cooling operation is required in winter, use of heat recovery ventilation is not
By setting to automatic
efficient because the outdoor air temperature is normally lower than that of the indoor.
ventilation mode Thus, the proper use of ventilation mode enhances the heating / cooling efficiency.
Outdoor Supply
Air Air
Heat Exchanger Element
(Heat Recovery) (HC0231) Automatic
Changeover
Normal (Bypass) mode
Exhaust Return
Air Air
Outdoor Supply
Air Air
Heat Exchanger Element
(Heat Recovery) (HC0232)
The load is reduced at startup of the air conditioner by the following control.
By Precooling / heating operation Before the working hour, the room air is clean.
Therefore, the startup of HRV can be delayed.
Working hour starts Working hour ends
Approx. 2% reduction
of heating / cooling load 8:15 9:00 18:00
Air
conditioner ON OFF
HRV ON OFF
Cooling / Heating
load is reduced
Total Reduction of
30% reduction
heating / cooling 30%
load (%)
of heating / cooling 20%
load 0%
Normal HRV independent Interlocked
operation operation operation (HC0233)
Note:
The total heating / cooling load may vary depending on the climate or the other environmental conditions.
VAMGJ Series 5
Product introduction ED71-613
Supply air volume can be set at a higher level than the Exhaust air volume can be set at a higher level than the
Detail
exhaust air by the remote controller. supply air by the remote controller.
Prevents inflow of toilet odor Prevents outflow of airborne bacteria from rooms in a
Major
effects
Prevents inflow of outdoor air in winter hospital
Prevents outflow of odors from rooms in a nursing home
Application Offices, etc. Hospitals, Nursing homes, etc.
Normal Portion of
Air supply HRV
HRV ventilation fan exhaust operation
Air exhaust
Air supply
Portion of
fresh up
operation
ex. <Hospital>
ex. <Office> (HC0010)
(HC0009)
40
(a) NOTE
The nighttime free cooling operation works when the HRV
30 unit is off. Therefore, it is not possible to stop the nighttime
free cooling operation, though the forced off is input from
(c) the optional controllers for centralized control.
20 (b)
OFF ON OFF
Nighttime free cooling operation
(e)
OFF
(d)
6 VAMGJ Series
ED71-613 Product introduction
(HC0013)
Features
High air shielding
Even in the conventional less humidity conditions, maintaining the features of the material that can get excellent moisture
permeability, we have achieved high air shielding, by special processing in the step of milling paper.
New ultra-thin film element
New
Conventional element New ultra-thin film element
develo ly
Moisture absorption is less effective due Due to the thinner film ped!
to the thickness of the partition sheets. It Decreases the moisture resistance of the partition
also limits the effective area that supply sheets drastically.
Realizes more space for extra layers in the element, Thickness of
and exhaust air can be exposed to. resulting in increased effective area that supply and the partition sheet
Thickness of
the partition sheet
exhaust air can be exposed to.
Moisture absorption increased by approx. 10%! 40 m
60 m Sheet structure Molecule of water
Miscellaneous gas
CO2 molecule, etc.
Indoor Outdoor
Indoor Outdoor
Exhaust air
High-humidity air
Exhaust air
SA Exhaust air
SA
Precise, thin-film
Outdoor air material
RA
(fresh air) Outdoor air
(unclean RA
indoor air) (fresh air)
(unclean Supply air Low-humidity air
indoor air)
Moisture exchange efficiency is greatly improved by using optimized
thinner films and moisture-absorption materials in the element.
Furthermore, miscellaneous gas barrier properties are maintained by
decreasing the porosity in the moisture-absorption materials.
VAMGJ Series 7
Product introduction ED71-613
SA EA SA EA
RA OA RA OA
(HC0234) (HC0235)
Service Maintenance
Vertical installation is available.
The unit must be installed with the side of RA, SA down.
It is necessary to make a trap.
Because the trap of wiring can protect against ingress of water.
EA OA Maintenance cover
Wiring
Trap
Control box
Maintenance cover
Celling hock
In the case of upside-down
Maintenance cover Inspection hole installation, take a turn 180
the celling hocks.
8 VAMGJ Series
ED71-613 Product introduction
1.3.7 The operation is available when the outdoor air temperature is down to -15C
(Operation when the outdoor air temperature becomes lower than -10C)
When the outdoor air suction temperature becomes lower than -10C, the unit is changed to intermittent operation to prevent
freezing of the heat exchanger element and dew condensation within the unit.
Intermittent operation
The outdoor air thermistor (standard equipment) within the unit detects the temperature. According to the detected temperature,
the following operation determines.
<Step 1>
The air supply fan is changed to intermittent operation, when the temperature is lower than -10C.
The intermittent operation of the air supply fan is changed to an operation of each cycle for 45 minutes operation after stopping
operation for 15 minutes.
The exhaust fan operates continuously according to setup.
<Step 2>
When the temperature becomes lower than -15C, the unit stops operation to prevent any defect, such as dew condensation and
freezing. The unit does not ventilate.
But, to detect the elevation of the outdoor air temperature, the unit operates for 5 minutes per hour.
The control by the external damper (local purchase) is available.
When the unit is not operating, the unit prevents the cool outdoor air from invading.
The power is applied from the connector X15A to the external damper. Therefore, the operation of the unit is controlled in
conjunction with the external damper.
Note:
Local setting is required.
1.3.8 The high efficiency filter (that has 65% of average dust collecting efficiency) is suitable
High efficiency filter Maintenance cover
Name plate
Control box Install the high efficiency AIR
FLOW High efficiency
filter to meet the direction The side of heat filter
exchanger element
of the arrow of the name plate.
Rail
VAMGJ Series 9
Product introduction ED71-510
= 20 A
Required ventilating Required ventilating
air flow rate (m3 / h) = CDE
B air flow rate (m3 / h)
A : Living room floor space (m2) C : Number of ventilation required per hour (ventilation / h)
B : Area occupied per person (m2) D : Area of room (m2) (See table 3 of the following page)
E : Height of Ceiling (m) (See table 2)
The above equation conforms to article 20, 2
No.2 of the Building Standards Act in Japan. Calculation is based on the experiences of hygienic laboratory,
Note: etc. to find out the number of hourly ventilation of the room air.
1. 20 (in the above equation) means 20 (m3 / h / person),
which is the required ventilating air flow rate based on the (Selection example)
CO2 exhausted by an adult sitting still in a room. If Place: Living room of common household
smoking is allowed, other calculation method should be Required ventilation: 6 times / h (See table 2)
used. Area of room: Approx. 9.9 (m2)
2. Use 10 (m2) if the area occupied per person exceeds Height of ceiling: 2.4 m
10 (m2). Required ventilating air flow rate =
<Table 1> 6 9.9 2.4 .=. 143 (m3 / h)
Area occupied Required ventilating air flow rate and the unit size
Type of building Remarks
per person (N) such as 150, 250, 350 ...... 2000 are almost equal.
Eating houses, So select the close size of the unit.
Floor space of a part used
restaurants, 3 m2 In this case, select VAM150GJVE.
for business purposes.
coffee-shops
<Table 2>
Cabarets, beer Floor space of a part used
2 m2
halls for business purposes. Groups Type of room Ventilation Groups Type of room
Ventilation
required required
Japanese-style
Floor space of a part used Living room, 6 Audience room, 6
restaurants, hall 3 m2
for hire
for business purposes. Common bathroom, 6 Playhouses corridor, 6
household drawing room, 6 and movie smoking room, 12
toilet, 10 theaters toilet, 12
Floor space of a part used
Store market 3 m2 kitchen 15 projector room 20
for business purposes.
Restaurant, 6 Office room, 6
Pool rooms, sushi restaurant, 6 general work room, 6
Ping-pong Eating banquet hall, 10 telephone room, 6
Floor space of a part used places tempura spinning plant, 10
rooms, dance 2 m2 restaurant, 20 printing plant, 10
for business purposes.
halls, bowling cooking room 20 battery room, 10
alleys machinery plant, 10
Guest room, 5 Plants generator room, 15
Pin-ball parlors, corridor, 5 substation room, 15
Floor space of a part used dance hall, 8
Go club houses, 2 m2 large dining hall, 8
painting shop, 15
for business purposes. Inns and welding plant, 15
mahjong parlors hotels
washroom, toilet, 10 chemical plant, 15
cooking room, 15 food plant, 20
Inns, hotels, and Floor space of a part used
10 m2 laundry room, 15 wood working plant, 20
motels for business purposes. engine room, 20 casting plant 50
boiler room 20
Floor space of a part used
Massage parlors 5 m2 Consultation office, 6
Office room, 6
for business purposes. General waiting room, 10
sick room, 6 buildings show room, toilet, 10
Persons accommodated office room, 6 conference room 12
Meeting places, simultaneously with the corridor, 10
0.5 1 m2 waiting room, 10 Comfort
20
public halls number of persons bathroom, 10 stations
calculated per unit. dining room, toilet,
Hospitals respiratory disease room,
10
10 Dark Dark rooms for
16
Offices 5 m2 Floor space of an office. laundry room, 15 rooms photo
cooking room, 15 Guest
* : Values set by the Metropolitan Maintenance Bureau in surgery room, 15 rooms of 6
Japan. sterilizing room, 15 ship
engine room, 20
Note: boiler room 20 Room of potential noxious 20 or
gas or combustible gas more
1. Table indicates the required ventilating air flow rate Class room, 6
calculated as 20 m3 / h. library, auditorium, 6
experimental
2. The area occupied per person by type of business is Schools chemistry room, 6
calculated in reference to Application Standards for gymnasium, 8
building administration in compliance with Building toilet, 12
cooking room 15
Standards Act in Japan.
Note:
Refer to the following pages for the tables.
10 VAMGJ Series
ED71-613 Product introduction
VAMGJ Series 11
Product introduction ED71-613
12 VAMGJ Series
ED71-613 Control System
2. Control System
2.1 Introduction of control system
The control systems introduced here is for the HRV unit adopting the high speed and high performance transmission system (DIII-
NET), the same as the VRV systems and SkyAir series.
Description of system
Control system
Controller Function
changeover
Unified ON / OFF controller
Malfunction display
Description of system
applications
Operation / Stop
Schedule timer
Automatic
Manual
Basic method to
operate HRV unit HRV unit
Independent
(Operation by
exclusive remote
controller for HRV
unit)
groups can be
(Only when remote controller for HRV unit is used)
controlled of
ON / OFF by one
unified ON / OFF
Indoor unit Indoor unit
controller.
(Note)
Up to 4 unified
Initial setting required
Centralized control
ON / OFF controllers
Central remote controller
can be installed in Schedule timer
one system. Multi-function centralized controller
(HC0018)
VAMGJ Series 13
Control System ED71-613
controller
HRV unit is installed on By
each HRV unit for its Ve
operation. Fr
HRV unit
Remote
controller
for HRV unit
Remote
controller
for indoor unit
Remote
controller
for indoor unit
14 VAMGJ Series
ED71-613 Control System
uired Function Nos. of the unit controlled and length of wiring Cautions page
BRC301B61 One remote controller operates each HRV The wire for remote controller is not
ON / OFF unit. included as standard accessories and
Ventilation mode (Auto / Heat Exchange / Remote control wiring can be extended up should be arranged locally.
Bypass) to 500 m maximum. By connecting the adapter PCB, the
Ventilating rate (High / Low) operation signal can be taken out remotely.
Fresh up mode (ON / OFF) Fresh-up operation is possible by
external input. 18
The group control is not possible by the
remote controller for HRV unit.
BRC301B61 Control of one HRV with two remote Same as operation from local place.
ON / OFF controllers It is necessary to set the Master / Slave
Ventilation mode (Auto / Heat Exchange / The maximum allowable total length of changeover switch in the remote controller.
Bypass) remote controller wiring is 500 m. Two remote controller operation is not
Ventilating rate (High / Low) available with simple remote controllers.
Fresh up mode (ON / OFF)
Timer setting (ON / OFF) 18
Indication of filter cleaning signal
Digital indication of malfunction
Up to 16 HRV units can be controlled with Same as operation from local place.
one liquid crystal remote controller. Group control is not available with a simple
The maximum total length of remote remote controller.
controller wiring is 500 m. * All the settings of HRVs in the same group
Control with two remote controllers is are the same (However, it is possible to fix
available. the individual setting by each unit.)
19
The HRV unit operates whenever the A maiximum of 16 units of indoor unit and
indoor unit is in operation. HRV unit can be controlled by the remote
Precool / preheat operation is also controller for indoor unit. (If they are in the
possible. same group)
Various settings are available by adding Remote control wiring can be extended up
the HRV remote controllers. to 500 m maximum.
19
A maximum of 16 units of indoor unit and Make sure to set ON for direct ducting
HRV unit can be controlled the operation setting.
by the remote controller for indoor unit. The HRV cannot be operated
Remote control wiring can be extended up independently to prevent the dust, when
to 500 m maximum. the indoor unit is not in operation.
However, if the fan of indoor unit is in
operation, the HRV unit can be operated 19
independently.
(HC0019)
VAMGJ Series 15
Control System ED71-613
Control
system Purposes and applications Description of system Optional accessories required
When the HRV unit is Th
Interlocked operation system with VRV
remote control
HRV unit operates if one of (One adapter PCB Th
indoor unit in the groups is should be installed in HR
in operation. The HRV unit Indoor unit Indoor unit HRV unit con
either the HRV unit or
can also be operated the indoor unit.)
Remote controller for indoor unit Remote controller for indoor unit
independently by remote
Adapter PCB for remote conrol
controller for indoor unit,
even if the indoor unit is not
in operation.
remote tim
controller
Remote controller for indoor unit Remote controller for HRV unit
Zone 2
16 VAMGJ Series
ED71-613 Control System
uired Function Nos. of the unit controlled and length of wiring Cautions page
The HRV unit operates of one of the A maximum of 64 groups of the units can No direct duct connection is possible.
indoor units connected to the central be controlled. Set ON for collective zone interlock
control transmission line is in operation. The central control transmission line can setting.
The various setting for the operation of be extended up to 1000 m maximum.
d in HRV unit should be set by the remote
t or controller for the indoor unit.
20
Collective / Individual operation A maximum of 64 groups connected by the When you use the central controller, no
[Unified ON / OFF controller] central transmission line can be controlled. direct duct connection is possible.
Each group can be controlled of ON / The central transmission line can be [Unified ON / OFF controller]
s) OFF individually. extended up to 1000 m maximum. Each group should be set the group
Each 16 groups can be controlled number. (It cannot be set by the remote
ON / OFF collectively. controller for HRV unit.)
The power supply terminal for the The power must be supplied.
schedule timer is provided. [Schedule timer]
[Schedule timer] When you use the schedule timer alone, it
The schedule timer can control collectively is necessary to supply the power of
the operation ON / OFF twice a day by DC16V, which can be supplied from the
e weekly. printed circuit board of the unit. (from
r Back-up power supply for 48 hours is CX11A in case of HRV unit)
provided, when the power failure is [Adapter PCB for remote control]
20
occurred. The adapter PCB for remote control cannot
e [Adapter PCB for remote control] be used with other central controller. (It can
The HRV units can be controlled be installed in the either indoor unit or HRV
ON / OFF collectively by external input. unit.)
Only KRP2A61 can be installed in the HRV
o be unit. (KRP2A2A3 cannot be installed in the
nit.) HRV unit because of their size.)
The interlocked operation A maximum of 64 groups connected by the The initial setting by remote controller for
[Multi function centralized controller] centralized transmission line can be indoor unit is needed. (The collective zone
It can control the operation ON / OFF controlled. interlock setting should be ON.)
individually or collectively. The central transmission line can be However, if there is no indoor unit in the
The several group of the units can be extended up to 1000 m maximum. same zone (only HRV units), the initial
controlled collectively by zone. setting is not required.
It can control the interlocked operation of When you use the central transmission
the indoor units and the HRV units in the line, no direct duct connection is possible.
same zone. [Multi function central controller]
The electrical terminal for the schedule Each group should be set the group
timer is provided. number for central control. (It cannot be set
by the remote controller for HRV unit.)
The power supply is needed.
21
(HC0020)
VAMGJ Series 17
Control System ED71-613
J1 J2 JC F1 F2
X9A SS1 X11A
X10A
P1 P2
HRV unit
Up to 500 m maximum
P1 P2
18 VAMGJ Series
ED71-613 Control System
Group control
Purpose and functions Example of wiring for control
Simultaneous control of multiple HRV units (max. 16 units)
J1 J2 JC F1 F2 J1 J2 JC F1 F2 J1 J2 JC F1 F2
is available. (for application to such as a spacious room)
X11A X11A X11A
All operation and individual setting can be carried out from X9A SS1 X9A SS1 X9A SS1
X10A X10A X10A
one remote controller.
In case the liquid crystal indicates malfunction, the P1 P2 P1 P2 P1 P2
indication of HRV unit No. shows in the display.
HRV unit HRV unit HRV unit
(If another remote controller is additionally installed,
control with two remote controllers is possible.)
Point P1 P2
No address setting is required because address is
Remote controller
automatically set.
for HRV unit
(The address is optionally allocated. The address No. can (HC0024)
VAMGJ Series 19
Control System ED71-613
Cautions F1 F2 F1 F2 J1 J2 JC F1 F2
1. It is not necessary to set the group number for central X9A SS1
X11A
control. X10A
P1 P2 P1 P2
2. One adapter PCB for remote control should be installed in P1 P2
the one of the unit connected to the central transmission Indoor unit Indoor unit HRV unit
line. P1 P2 P1 P2
(When you install an adapter PCB for remote control in the Remote controller for indoor unit
indoor unit, select the applicable model number of Adapter
PCB to be installed.)
F1 F2
P1 P2
Indoor unit
P1 P2 Remote controller for indoor unit
(HC0027)
Note:
The central transmission line can be extended up to 1000 m
maximum.
Switch setting for HRV unit
The initial setting by the remote controller for indoor unit or
HRV unit.
Optional accessories required
Wiring adapter for electrical appendices : KRP2A61
Installation box for adapter PCB : KRP50-2A90
F1 F2 J1 J2 JC F1 F2
SS1 X11A
X9A
X10A
P1 P2 P1 P2
P1 P2
20 VAMGJ Series
ED71-613 Control System
Zone 1
connected to the central transmission line is in operation, SS1 X11A
X9A
refer to the applied system. X10A
Cautions
P1 P2
1. It is necessary to assign a central control group number. P1 P2
2. If you operate the HRV unit interlocked to the operation of Indoor unit HRV unit
indoor unit, please set the same zone number. At that
time, it is necessary to set the zone operation on the HRV P1 P2 P1 P2 Remote controller
unit. for HRV unit
3. It is not possible to operate ON / OFF from the remote Remote controller
for indoor unit
controller for the HRV unit in zone 1.
4. It is not necessary to set the zone operation mode in zone
2, which is already set at the factory.
Switch setting for HRV unit
The initial setting is required by the remote controller for J1 J2 JC F1 F2 J1 J2 JC F1 F2
indoor unit or HRV unit. X9A
SS1 X11A
X9A
SS1 X11A
For zone 1.......... ON [17(27) 8 02]
Zone 2
X10A X10A
For zone 2.......... Factory set (No change is required)
P1 P2 P1 P2
Optional accessories required
Remote controller (Only when you use) BRC301B61 HRV unit HRV unit
P1 P2 Remote controller
for HRV unit
(HC0029)
VAMGJ Series 21
Control System ED71-613
Install the remote controller for indoor unit for the initial
setting. After completion of the initial setting, remove the
remote controller.
Optional accessories required
None
Monitor of operation (KRP50-2) [HRV unit operating pilot lamp (local supply)]
Purposes and functions
To monitor the operation of one HRV unit.
Example of control wiring
P1 P2
22 VAMGJ Series
ED71-613 Control System
P1 P2
Local wiring
Operation of Terminal for local Capacity of connecting
HRV unit connection terminal
Fresh-up Short-circuit No-voltage normally open
contact for micro-current
Normal Open circuit
16 V, 10 mA
Note:
The connecting wiring between HRV unit and the terminal for
local connection can be extended up to 50 m maximum.
Switch setting of HRV unit
No change is required. (factory setting)
Optional accessories required
None
Wiring procedure
Connect external damper interlocking harness (accessory) to terminals (X15A) on the printed circuit board with connectors,
and wire the other end to the harness toward the damper with insulation-coated closed end connection binder.
Insulation-coated closed end connection binder
(field supplied) External damper interlocking harness
(accessory)
To external
damper
* Select insulation-coated closed end connection binder with
specification suitable for the wire diameter. And, connect
External damper interlocking electric wire
X15A the closed end connection binder in the control box.
(field supplied)
Power supply turns ON when total heat exchanger starts operating. Note) VAM is different from VAC in presence or absence of
Power supply turns OFF when total heat exchanger is switched OFF. voltage supply (as described previously), therefore,
HRV unit
Supply voltage Connected load capacity pay much attention.
220V
230V 0.5A or less
240V
Required setting changes for switchover to X15A output
VAMGJ Series 23
Control System ED71-613
24 VAMGJ Series
ED71-613 Control System
1. In case of Zone control, the operation / stop and the timer X10A
P1 P2 P1 P2
setting cannot be done by the remote controller for the
Indoor unit HRV unit
HRV unit. (The operation lamp blinks twice to indicate that
P1 P2 P1 P2
the operation is not possible.)
2. The remote controller for the HRV unit cannot set the Remote controller Remote controller
for indoor unit for HRV unit
group no. for centralized control. In this case, the remote (HC0035)
controller for the indoor unit has to be connected once for Switch setting of the HRV unit
this setting. Group no. setting for central control is required.
3. It is not possible to have precool / preheat time setting It is necessary to set the group number for each unit connected
function. to the central transmission line (terminal no. (F1) and (F2)).
Initial setting is required by the remote controller for indoor unit.
In case of collective / individual control
Collective zone interlock setting
................................. OFF (as per factory set)
In case of zone control
Collective zone interlock setting
................................. ON [17(27) 8 02]
Optional accessories required
Remote controller : BRC301B61
Cautions
1. It is required the local setting of the group number for
central control. F1 F2 J1 J2 JC F1 F2
2. The HRV unit judges the ventilation mode individually. X9A SS1 X11A
X10A
P1 P2
P1 P2
F1 F2 J1 J2 JC F1 F2
SS1 X11A
X9A
X10A
P1 P2
P1 P2
Indoor unit HRV unit
P1 P2 P1 P2
(HC0036)
VAMGJ Series 25
Control System ED71-613
required.
2. The HRV unit judges the ventilation mode individually.
3. The power supply for the schedule timer can be supplied F1 F2 J1 J2 JC F1 F2
from the PCB of the unit. (X18A for the indoor unit and X18A
X9A SS1 X11A
P1 P2
Indoor unit HRV unit
P1 P2 P1 P2
F1 F2 J1 J2 JC F1 F2
SS1 X11A
X9A
X10A
P1 P2
P1 P2
Indoor unit HRV unit
P1 P2 P1 P2
(HC0037)
F1 F2 J1 J2 JC F1 F2
SS1 X11A
X9A
X18A
X10A
P1 P2
P1 P2
F1 F2 J1 J2 JC F1 F2
SS1 X11A
X9A
X10A
P1 P2
P1 P2
26 VAMGJ Series
ED71-613 Control System
A 1 2 3
[1-00] [1-01] [1-02]
RSA R1
Zone setting
5 4
[1-04] [1-03]
R2
(Individual operation of each group)
B 6 7 8
[1-05] [1-06] [1-07]
RSB R3
Zone setting
10 9
[1-09] [1-08]
R4
Ventilation air
by remote
controller
controller
ventilation
Remote
setting for
(Independent Malfunction code
ventilation Fresh-up centralized control
operation mode) *2 *3 HRV unit side
RSA or B
RSA or B
RSA or B
RSA or B
RSA or B
Collective
Individual
Zone Interlock
R1~4
R1~4
R1~4
R1~4
R1~4
RC1
RC2
RC1
RC2
RC1
RC2
RC1
RC2
RC1
RC2
interlock Total
ON OFF evaluation
ON OFF Energy saving
Linked Linked Not required (Setting
Collective by zone
Once connected
*1
Once connected
Linked Linked Not required (Setting
to B to B required only for B )
Not available HRV unit setting error (Set zone
interlock to "OFF", in case of no air
Not available conditioner in the same zone.)
Once connected
*1. Setting to the independent ventilation operation mode is available, if zone interlock setting is "ON" with the air conditioner in the
same zone.
*2. RC1 is available in case of VAM-GJ series.
*3. Fresh-up of RCA or RCB is available at initial setting.
VAMGJ Series 27
Control System ED71-613
To central controller
Centralized transmission line
F1 F2 J1 J2 JC F1 F2 F1 F2 J1 J2 JC F1 F2
SS1 X11A SS1 X11A
X9A X14A X9A
X10A X15A X10A
X17A
P1 P2 P1 P2 P1 P2 P1 P2
P1 P2
No remote controller
Remote controller
(HC0041) for indoor unit (HC0042)
Reason Reason
Because the signal through the transmission line is originated The information from the indoor unit cannot be transmitted to
from the remote controller, there is no transmission signal to the central controller through the HRV unit. And also the
operate the units, if the remote controller is not installed. information from the central controller cannot be transmitted
to the indoor unit through the HRV unit.
28 VAMGJ Series
ED71-613 Control System
VAMGJ Series 29
Control System ED71-613
1. Tranformer 6. Connector for damper 11. Connector for indoor air 15. Terminal port for
2. Secondary 7. Power supply thermistor centralized control
3. Primary 8. Terminals 12. Connector for outdoor air 16. Terminal port for no-
4. Connector for supply air 9. Connector for KPR50-2 thermistor voltage external input
fan 10. Connector for damper 13. Selector switch 17. Factory setting
5. Connector for exhaust air 14. Terminal port for remote
fan controller
3P034928-5J
F1 F2
Input from outside
(HC0043)
30 VAMGJ Series
ED71-613 Control System
Fresh-up Fresh-up
Ventilation air flow Supply air setting Exhaust air setting
Fan speed Fresh-up operation
Interlocked operation system
setting
Supply side Exhaust side Supply side Exhaust side
Off Low Low Low Low
Low
On High Low Low High
Normal
Off High High High High
High
On Ultra-high High High Ultra-high
Off Low Low Low Low
Low
On High Low Low High
Ultra-high
Off Ultra-high Ultra-high Ultra-high Ultra-high
High
On Ultra-high High High Ultra-high
Terminal between Fan operation
Ventilation air flow
Independent system
J1 and JC
With remote controller for HRV unit
Low
Centralized
J1 and JC
Switch on the PCB (H / M / L) (Fresh-up by external Supply Exhaust Supply Exhaust
With remote controller
H
Short-circuit Ultra-high High High Ultra-high
(HC0044)
time counting
More than N
2 hours elapsed
Interlocked after the unit Stand-by for operation
control Only for stopped.
Interlocked interlocked cooling and N
{ Y Setting time
operation to single- heating elapsed
group and mode
two-groups Y
Operation starts
(HC0045)
VAMGJ Series 31
Control System ED71-613
Room temp.(R.T.)
O.T=R.T.
O.T<R.T.
Set temp.
of A / C
(HC0046)
O.T=R.T.
O.T<R.T.
Set temp.
of A / C
(HC0047)
Bypass Bypass
O.T.>R.T. Heat
exchange
Room temp.(R.T.)
O.T=R.T.
O.T<R.T.
approx.22 C
(HC0048)
32 VAMGJ Series
ED71-613 Product specification
3. Product specification
3.1 Specification
(50 / 60Hz)
Model name VAM150GJVE VAM250GJVE VAM350GJVE
Power supply Single phase 220 240 V / 220 V, 50 / 60 Hz
Ultra-High % 79 / 79 75 / 75 79 / 79
Temperature exchange efficiency High % 79 / 79 75 / 75 79 / 79
Low % 84 / 85 79 / 79 82 / 82
Ultra-High % 66 / 66 63 / 63 66 / 66
Cooling High % 66 / 66 63 / 63 66 / 66
Enthalpy Low % 70 / 70.5 66 / 66 70 / 70
exchange
efficiency Ultra-High % 72 / 72 71 / 71 70 / 70
Heating High % 72 / 72 71 / 71 70 / 70
Low % 76 / 76.5 74 / 74 77 / 77
Casing Galvanized steel plate
Insulation material Self-extinguishable urethane foam
Dimensions HWD mm 278 810 551 278 810 551 306 879 800
Heat exchange system Air to air cross flow total heat (sensible heat + latent heat) exchange
Heat exchange element Specially processed nonflammable paper
Air filter Multidirectional fibrous fleeces
Type Sirroco fan
Heat Ultra-High m3 / h 150 / 150 250 / 250 350 / 350
Air flow rate exchange High m3 / h 150 / 150 250 / 250 350 / 350
Fan mode Low m3 /h 100 / 95 155 / 155 230 / 230
Ultra-High Pa 120 / 154 70 / 96 169 / 222
External static pressure High Pa 106 / 131 54 / 65 141 / 145
Low Pa 56 / 60 24 / 20 67 / 30
Fan motor Type Open type capacitor permanent split-phase induction motor, 4 poles 2
Motor output kW 0.030 2 0.030 2 0.090 2
Ultra-High dBA 27 28.5 / 28.5 27 29 / 29 31.5 33 / 33
Heat exchange mode High dBA 26 27.5 / 27.5 26 27.5 / 28 30 31.5 / 30
Low dBA 20.5 21.5 / 21 21 22 / 21 23 25 / 23
Operating sound
Ultra-High dBA 28.5 29.5 / 29.5 28.5 30.5 / 30.5 33 34.5 / 34.5
Bypass mode High dBA 27.5 28.5 / 28.5 27.5 29 / 29.5 31.5 33 / 31.5
Low dBA 22.5 23.5 / 22 22.5 23 / 22.5 24.5 26.5 / 24.5
Operation range (Ambient) 15C to 50CDB (80% RH or less)
Connection duct diameter mm 100 150 150
Weight kg 24 24 32
Drawing number C : 4D051116 C : 4D051117 C : 4D051118
Indoor Outdoor
Condition
CDB R H (%) CDB R H (%)
Cooling condition 27 50 35 60
Heating condition 20 40 7 70
Note:
1. Operation sound is measured at 1.5 m below the center of the body.
2. Air flow rate can be changed over to Low mode or High mode.
3. Nomal AMP., input, efficiency depend on the other above conditions.
4. Operating sound is measured in an anechoic chamber.
Operating sound level generally may become greater than this value depending on the operating conditions, reflected sound,
and peripheral noise.
5. The sound level at the air discharge port is about 8 dB higher than the units operating sound.
6. The specifications, designs and information here are subject to change without notice.
7. Temperature Exchange Efficiency is the mean value in cooling and heating.
8. Efficiency is measured under the following conditions.
Ratio of rated external static pressure has been kept as follows. Outdoor side to indoor side = 7 to 1
VAMGJ Series 33
Product specification ED71-613
(50 / 60Hz)
Model name VAM500GJVE VAM650GJVE VAM800GJVE
Power supply Single phase 220 240 V / 220 V, 50 / 60 Hz
Ultra-High % 74 / 74 75 / 75 72 / 72
Temperature exchange efficiency High % 74 / 74 75 / 75 72 / 72
Low % 80 / 80.5 77 / 77.5 74 / 74.5
Ultra-High % 55 / 55 61 / 61 61 / 61
Cooling High % 55 / 55 61 / 61 61 / 61
Enthalpy Low % 59 / 59.5 64 / 64.5 64 / 64.5
exchange
efficiency Ultra-High % 67 / 67 67.5 / 67.5 65 / 65
Heating High % 67 / 67 67.5 / 67.5 65 / 65
Low % 74 / 74.5 71.5 / 72 67.5 / 68
Casing Galvanized steel plate
Insulation material Self-extinguishable urethane foam
Dimensions HWD mm 306 879 800 338 973 832 387 1,111 832
Heat exchange system Air to air cross flow total heat (sensible heat + latent heat) exchange
Heat exchange element Specially processed nonflammable paper
Air filter Multidirectional fibrous fleeces
Type Sirroco fan
Heat Ultra-High m3 / h 500 / 500 650 / 650 800 / 800
Air flow rate exchange High m3 / h 500 / 500 650 / 650 800 / 800
Fan mode Low m3 /h 320 / 295 500 / 470 700 / 670
Ultra-High Pa 105 / 150 85 / 125 133 / 170
External static pressure High Pa 66 / 52 53 / 67 92 / 85
Low Pa 32 / 18 35 / 38 72 / 61
Fan motor Type Open type capacitor permanent split-phase induction motor, 4 poles 2
Motor output kW 0.090 2 0.140 2 0.280 2
Ultra-High dBA 33 35.5 / 34 34 36 / 36 39 40.5 / 39.5
Heat exchange mode High dBA 31.5 34 / 32 33 34.5 / 34 37 39.5 / 37.5
Low dBA 25 28.5 / 24 27.5 29.5 / 28 35 37.5 / 34
Operating sound
Ultra-High dBA 34.5 36 / 35.5 35 37.5 / 37.5 40.5 42 / 41
Bypass mode High dBA 33 34.5 / 33.5 33 35.5 / 35.5 38.5 40 / 39
Low dBA 25.5 28.5 / 25.5 27.5 30.5 / 29.5 36 38.5 / 35.5
Operation range (Ambient) 15C to 50CDB (80% RH or less)
Connection duct diameter mm 200 200 250
Weight kg 32 45 55
Drawing number C : 4D051120 C : 4D051121 C : 4D051122
Indoor Outdoor
Condition
CDB R H (%) CDB R H (%)
Cooling condition 27 50 35 60
Heating condition 20 40 7 70
Note:
1. Operation sound is measured at 1.5 m below the center of the body.
2. Air flow rate can be changed over to Low mode or High mode.
3. Nomal AMP., input, efficiency depend on the other above conditions.
4. Operating sound is measured in an anechoic chamber.
Operating sound level generally may become greater than this value depending on the operating conditions, reflected sound,
and peripheral noise.
5. The sound level at the air discharge port is about 8 dB higher than the units operating sound.
6. The specifications, designs and information here are subject to change without notice.
7. Temperature Exchange Efficiency is the mean value in cooling and heating.
8. Efficiency is measured under the following conditions.
Ratio of rated external static pressure has been kept as follows. Outdoor side to indoor side = 7 to 1
34 VAMGJ Series
ED71-613 Product specification
(50 / 60Hz)
Model name VAM1000GJVE VAM1500GJVE VAM2000GJVE
Power supply Single phase 220 240 V / 220 V, 50 / 60 Hz
Ultra-High % 78 / 78 72 / 72 77 / 77
Temperature exchange efficiency High % 78 / 78 72 / 72 77 / 77
Low % 80.5 / 81 75.5 / 76 79 / 81
Ultra-High % 64 / 64 61 / 61 62 / 62
Cooling High % 64 / 64 61 / 61 62 / 62
Enthalpy Low % 68.5 / 69 64 / 64.5 66 / 67
exchange
efficiency Ultra-High % 70 / 70 65 / 65 72 / 72
Heating High % 70 / 70 65 / 65 72 / 72
Low % 72.5 / 73 67 / 67.5 75 / 76
Casing Galvanized steel plate
Insulation material Self-extinguishable urethane foam
Dimensions HWD mm 387 1,111 1,214 785 1,619 832 785 1,619 1,214
Heat exchange system Air to air cross flow total heat (sensible heat + latent heat) exchange
Heat exchange element Specially processed nonflammable paper
Air filter Multidirectional fibrous fleeces
Type Sirroco fan
Heat Ultra-High m3 / h 1,000 / 1,000 1,500 / 1,500 2,000 / 2,000
Air flow rate exchange High m3 / h 1,000 / 1,000 1,500 / 1,500 2,000 / 2,000
Fan mode Low m3 /h 860 / 840 1,320 / 1,260 1,720 / 1,580
Ultra-High Pa 168 / 192 112 / 150 116 / 140
External static pressure High Pa 110 / 86 73 / 72 58 / 32
Low Pa 85 / 60 56 / 50 45 / 45
Fan motor Type Open type capacitor permanent split-phase induction motor, 4 poles 2
Motor output kW 0.280 2 0.280 4 0.280 4
Ultra-High dBA 39.5 41.5 / 39.5 39.5 41.5 / 41.5 41.5 43.5 / 42
Heat exchange mode High dBA 37.5 39.5 / 37.5 37.5 39.5 / 39.5 39 43 / 40
Low dBA 35 37.5 / 34.5 35 37.5 / 36 36 39 / 39
Operating sound
Ultra-High dBA 40.5 42.5 / 40.5 41 43 / 42.5 43 45.5 / 44
Bypass mode High dBA 38.5 40.5 / 38.5 39.5 41 / 41.5 40.5 45 / 42
Low dBA 36 38.5 / 35.5 36.5 38 / 37.5 37.5 39.5 / 41
Operation range (Ambient) 15C to 50CDB (80% RH or less)
Connection duct diameter mm 250 350 350
Weight kg 67 129 157
Drawing number C : 4D051123 C : 4D051119 C : 4D051124
VAMGJ Series 35
Product specification ED71-613
3.2 Dimensions
VAM150GJVE
Unit (mm)
3D051174
VAM250GJVE
Unit (mm)
3D051175
36 VAMGJ Series
ED71-613 Product specification
VAM350GJVE
Unit (mm)
3D051176
VAM500GJVE
Unit (mm)
3D051177
VAMGJ Series 37
Product specification ED71-613
VAM650GJVE
Unit (mm)
3D051178
VAM800GJVE
Unit (mm)
3D051179
38 VAMGJ Series
ED71-613 Product specification
VAM1000GJVE
Unit (mm)
3D051180
VAM1500GJVE
Unit (mm)
3D051181
VAMGJ Series 39
Product specification ED71-613
VAM2000GJVE
Unit (mm)
3D051182
3D013155A
40 VAMGJ Series
ED71-613 Product specification
VAMGJ Series 41
Product specification ED71-613
VAM1500GJVE
VAM2000GJVE
42 VAMGJ Series
ED71-613 Product specification
VAM150GJVE
4D042374
VAM250GJVE
4D042375
VAMGJ Series 43
Product specification ED71-613
VAM350GJVE
4D042376
VAM500GJVE
4D042377
44 VAMGJ Series
ED71-613 Product specification
VAM650GJVE
4D042378
VAM800GJVE
4D042379
VAMGJ Series 45
Product specification ED71-613
VAM1000GJVE
4D042380
VAM1500GJVE
4D042381
46 VAMGJ Series
ED71-613 Product specification
VAM2000GJVE
4D042382
VAMGJ Series 47
Product specification ED71-613
C : 4D023764
<Example of correction>
48 VAMGJ Series
ED71-613 Product specification
VAMGJ Series 49
Product specification ED71-613
VAM2000GJVE dB(A)
Model Power Supply Notch Hz 63 125 250 500 1000 2000 4000 8000
U-H 52.3 48.2 49.2 41.3 36.0 29.8 23.0 15.1
220V H 50.4 45.9 46.8 38.8 33.6 27.5 19.7 11.3
L 49.5 42.8 42.6 36.7 30.7 25.0 16.0 8.2
U-H 52.1 48.8 50.3 42.2 36.9 30.8 23.8 16.1
50Hz 230V H 52.8 47.5 49.8 41.2 35.7 29.6 22.3 14.6
VAM L 50.4 44.4 45.2 38.5 32.3 26.4 18.1 10.8
2000
GJVE U-H 54.1 50.0 51.2 43.3 38.0 31.8 24.9 17.5
240V H 54.3 49.8 50.7 42.7 37.5 31.4 23.9 17.3
L 52.4 45.7 45.5 39.6 33.6 27.9 19.5 13.5
U-H 52.9 48.5 49.7 41.4 36.9 30.6 23.5 16.0
60Hz 220V H 52.3 46.3 47.2 39.9 34.8 28.4 21.1 13.8
L 52.5 45.3 45.7 39.4 34.0 28.4 20.2 14.6
Measuring place
Note:
1. Operation sound is measured in an anechoic chamber.
2. The sound is measured at 1.5 m below the center of the body. Location of microphone
3. The operating sound level may become greater than this value depending on
the operating conditions, reflected sound, and peripheral noise.
4. Operation sound differs with operation and ambient conditions.
5. The power levels have been calculated on the assumption that the measuring
point were right under the source of operating sound.
6. U-H: Ultra high 1.5 m
H: High
L: Low Measuring point
4D042394
50 VAMGJ Series
ED71-613 Product specification
VAMGJ Series 51
Product specification ED71-613
52 VAMGJ Series
ED71-613 Product specification
VAMGJ Series 53
Product specification ED71-613
4D051624
54 VAMGJ Series
ED71-613 Installation
4. Installation
4.1 Reducing operating sound
HRV unit Air supply
The operation noise level is determined by operating an and exhaust
OA RA grille
equipment unit according to the JIS standard (JIS B 8628),
and converting the measurement into a value as measured in
EA SA
an anechoic room. Also, noise from the discharge grill is not Flexible duct
taken into account, for only the main body is considered as Apply sound-insulating
material here for effective
sound source. In actual operation, therefore, the operation operating sound reduction.
noise level tends to be higher than the indicated value. (Flexible duct (approx. 2m) is effective.) (HC0055)
VAMGJ Series 55
Installation ED71-613
3. To reduce the air flow sound heard from the air discharge
Fig.3 1 2 3 outlet (suction inlet) of a ceiling mounted duct connection
type model, use a small diameter flexible duct, which excels
in sound absorptivity, for greater sound reduction effect.
Fig.5 1 2
(HC0058)
Silencer Silencer
Flexible duct 2 m
(Effect of a remedy for noise does not change even for over 2 m long duct)
Silencer +5
Spiral duct 4 m
Spiral duct 6 m
Suction /
discharge grill 5
(HC0061)
Note:
Measure the noise at 1.5 m below the air supply grille. Operating noise conforms to JIS standard and the value is converted in
terms of the anechoic chamber.
56 VAMGJ Series
ED71-613 Installation
4.3 Centralized pipings Fig.2: Install a duct for each HRV units.
: Direction of
air flow
Wherever possible, avoid centralized OA and EA
pipings for two or more HRV units, and install ducts (Indoor side)
for each body of the unit. (Fig. 2)
OA
Because the air flow shown in Fig.1 is generated when Discharge grille
EA
centralized OA and EA pipings for two or more HRV units
HRV units (No. 1 unit)
normal air flow cannot be maintained. If a back flow
(Outdoor side)
prevention damper is installed in the duct on OA and EA side Air suction grille
of each HRV units (Fig.3), costs will increase as compared
with the case a duct is installed for each body. It is therefore
recommended that a duct be installed for each body. Discharge grille
(Before installing the back flow prevention damper, contact
our engineering section.) HRV units (No. 2 unit)
(HC0062)
In the above duct system diagram, the air of No.1 unit will
flow into normal direction regardless of the operation of
No.2 unit when one duct is provided for each unit.
Fig.1: Centralized piping cannot be installed. Fig.3: Install a back flow prevention damper on each duct
on OA and EA sides. (Field supply)
Discharge grille
Discharge grille HRV units (No. 2 unit)
HRV units (No. 2 unit)
: Direction of air flow
Air suction
grille : Damper opened
Air suction grille : Damper closed
(HC0063) (HC0064)
In the above duct system diagram, if a damper is not provided In the above duct system diagram, if a back flow prevention
and No.1 unit is operated with No.2 unit being stopped, the damper (field supply) is installed on each duct on OA and EA
air flows in the direction indicated by a broken line, the sides and the damper interlocked to the operation signals of
amount of the air supplied from outside to OA side is HRV units, faults such as those shown in Fig.1 can be
decreased, and the air is discharged from the discharge grille eliminated and the normal air flow maintained.
of EA side. (Note, however, that the above does not apply to the
Therefore, the air will not flow into the normal direction. standard duct system.)
VAMGJ Series 57
Installation ED71-613
4.4 Cautions
When a smoke back flow prevention damper is installed
1. Install the unit on a rigid and stable place. Refer to Smoke back flow
the specification and weight of the unit. prevention damper
Rigid mounting
2 m or more
58 VAMGJ Series
ED71-613 Installation
rve
place where damage from sea wind and hot
cu
spring prevail or where air containing odor is
ati
RH
y
tur
nc
%
ie
Sa
95
f i c
=<
ef %
l py g B OA
a 9. Do not operate HRV units in [Bypass] ventilation
th olin
En co mode when the indoor is heated during winter.
in SA
RA
Such operation may cause frost to form in the body and dirty
ceiling may result.
Temperature efficiency A%
Dry bulb temperature (CDB) 10. When a unit is installed on the ceiling using
(HC0067) short suspension bolts, abnormal noise may be
Fig.1 shows the limit under normal indoor conditions. generated due to resonance with the ceiling.
Fig.1 Conditions :
Temperature efficiency A = 72% Provide resonance preventive measures for the body
Enthalpy efficiency B = 56% (In cooling) suspension bolts.
This conditions are at the minimum efficiency that Example
are the severest to dew formation.
Ceiling
100
Not
Outdoor air relative humidity (% RH)
available
90
80
Indoor conditions HRV units Vibration
body isolating rubber
25C DB, 60% RH
70 22C DB, 50% RH
22C DB, 60% RH (HC0070)
Available
60 If abnormal noise is suspected generating from a spiral duct
connection, change the duct to flexible duct. The above
50 preventive measure is considered to eliminate the problem
(resonance) but contact our service group and provide means
40 to prevent vibration or necessary changes of the motor of the
unit body.
20 30 40
Outdoor air temperature (CDB)
(HC0068)
Motor Motor
2) Operation in cold areas (in the heating mode)
To prevent dew formation and freezing, use the unit under
the conditions that the outdoor discharge air is 95% RH or
less on the psychrometiric chart. Vibration isolating rubber
Motor mount
(HC0071)
Absolute humidity (kg / kg)
ve
Caution
ur
When the outdoor air infiltrates into the ceiling and the
c
on
ati
e
lpy C% RH
tha ing 5%
En heat <= 9
in
RA
OA EA
(In heating)
Temperature efficiency A%
Dry bulb temperature (CDB)
(HC0069)
Note:
If the outdoor discharge air exceeds 95% RH, please
preheat the outdoor suction air before it goes through the
heat exchanger.
VAMGJ Series 59
Installation ED71-613
VAM150GJVE
Unit (mm)
3D051148
VAM250GJVE
Unit (mm)
3D051150
60 VAMGJ Series
ED71-613 Installation
VAM350GJVE
Unit (mm)
3D051152
VAM500GJVE
Unit (mm)
3D051154
VAMGJ Series 61
Installation ED71-613
VAM650GJVE
Unit (mm)
3D051155
VAM800GJVE
Unit (mm)
3D051156
62 VAMGJ Series
ED71-613 Installation
VAM1000GJVE
Unit (mm)
3D051160
VAM1500GJVE
Unit (mm)
3D051163
VAMGJ Series 63
Installation ED71-613
VAM2000GJVE
Unit (mm)
3D051164
64 VAMGJ Series
ED71-613 Installation
VAMGJ Series 65
Installation ED71-613
4.7 Installation
(4) a bend right next to the outlet
4.7.1 Installation of HRV units
Pass hanger bracket over the bolts and secure with
commercially available washers and nuts.
(When installing the main unit, make sure there are no foreign
objects (plastic, paper, etc.) inside the fan housing by looking 1. To prevent air leakage, wind aluminum tape round the section
inside through the duct hole before connecting the duct.) after the duct connecting flange and the duct are connected.
When reversing the hanger brackets in order to install the 2. Install the opening of the indoor air intake as far as from
unit upside down, be sure to secure them with the removed the opening of the exhaust suction.
screws. 3. Use the duct applicable to the model of unit used (Refer to
Attach the indoor (SA, RA) and outdoor (EA, OA) ducts by the outline drawing.)
referring to the duct diagram on the name plate. 4. Install the two outdoor ducts with down slope (slope of 1 /
30 or more) to prevent entry of rain water. Also, provide
<VAM150GJVE, VAM250GJVE, VAM350GJVE, VAM500GJVE,
insulation for both ducts to prevent dew formation.
VAM650GJVE, VAM800GJVE, VAM1000GJVE>
(Material : Glass wool of 25 mm thick)
1
Insulator
(Field supply)
2
Body
3
Slope: Over 1 / 30
4 Aluminum tape
Duct connecting flange
(Field supply)
(HC0079)
<VAM1500GJVE, VAM2000GJVE>
1 5. If the level of temperature and humidity inside the ceiling is
always install a ventilation equipment inside the ceiling.
2
6. Insulate the duct and the wall electrically when a metal
3 duct is to be penetrated through the metal lattice and wire
lattice or metal lining of a wooden structure wall.
(HC0080)
66 VAMGJ Series
ED71-613 Installation
Image picture
Fig. 1
Mortar
1 / 100 1 / 50
150
100
Hood
Caulking material
Insulation material
(Sealing material)
Spiral duct
VAMGJ Series 67
Installation ED71-613
Main
switch Switch
Fuse
VRV
Indoor unit
HRV
VRV
Indoor unit
HRV
Remote controller
(HC0082)
68 VAMGJ Series
ED71-613 Installation
PRECAUTIONS
1. Do not connect wires of different gauge to the same power
View seen from VRV supply terminal. Looseness in the connection may cause
Terminal board for
Terminal board for transmission power supply overheating. When connecting more than one wire to the
Wiring power supply wiring, use a 2 mm2 ( 1.6) gauge wire.
Grounding
IN OUT
P1 P2 F1 F2 T1 T2 L N Same gauge wires Different gauge wires
1 2 1 2 terminal
Unit wiring 2. Keep total current of crossover wiring between indoor units
less than 12 A. When using two power wiring of gauge
Remote controller
Clamp material Power supply greater than 2 mm2 ( 1.6), branch the line outside the
(attached)
wiring wiring terminal board of the unit in accordance with electrical
Field supplied wire
equipment standards. The branch must be sheathed so as
Earth terminal (attached) to provide an equal or greater degree of insulation as the
Ground the shield part power supply wiring itself.
of shielded wire. 3. Do not connect wires of different gauge to the same
grounding terminal. Looseness in the connection may
Earth screw deteriorate protection.
(attached)
4. Keep the power supply wiring distant from other wires to
prevent noise.
C-cup washer 5. For remote controller wiring, refer to the INSTALLATION
Shield part (attached) MANUAL OF REMOTE CONTROLLER.
(HC0084)
Wiring Example
Outdoor unit / BS unit
Power supply Power supply
1 ~ 50Hz Switch box
Following items are figured as shown below
1 ~ 50Hz
220 - 240V Out
1 2 220 - 240V : transmission wiring
L N L N
P1
P2 P1 P2
Indoor unit
VRV HRV
LN 121 2 P1 P2 F1 F1 T1 T1 P2 P1 F1 F2 J1 J2 JC L N
VRV
HRV
Indoor unit
P1 P2
transmission
wiring
Remote controller (HRV)
(HC0085)
All transmission wiring except for the remote controller wires is polarized and must match the terminal symbol.
Use screened wire in transmission wiring. Ground the shield of the shield wire to , at the grounding screw, with the C-cup
washer.
Sheathed wire materials may be used for transmission wiring, but they are not suitable for EMC (Electromagnetic Compatibility)
(European Directive).
When using sheathed wire, electromagnetic compatibility must conform to Japanese standards stipulated in the Electric
Appliance Regulatory Act.
Transmission wiring need not be grounded when using sheathed wire.
VAMGJ Series 69
Installation ED71-613
Transmission wiring
terminal board
Transmission wiring Terminal board
terminal board
(HC0089)
Before opening the cover, be sure to turn off the power switches of the main units and other devices connected with the main units.
Remove the screw securing the cover and open the control box.
Secure the power cord control wires with the clamp, as shown above.
4.9.2 How to install the optional adapter circuit board
1. Open the electrical compartment cover by following the procedure described in the Opening the control box section.
2. Remove the securing screw, and install the adapter circuit board.
3. After the wires are connected, fasten the electrical compartment cover. (For detail, refer to 6. Optional accessories.)
4.9.3 Wiring system of centralized transmission control wiring
Total length of wiring should not exceed 1000 m.
In this technical manual, all the schematic drawings is shown by the series wiring, which do not require relay terminals.
70 VAMGJ Series
ED71-613 Installation
Remote controller
for indoor unit
Note:
When you make the plural setting to one (or one group) indoor unit, the item 2 to 6 of the above setting procedure should be repeated
and it should be returned to the normal mode by the procedure of item 7 at last.
(HC0093)
VAMGJ Series 71
Installation ED71-613
<Example>
No necessary
[1-03]
Remote controller
for indoor unit
4 5 GROUP
CODE SETTING A
FRESH UP
RATE to select the mode no. 00.
hr
3 Use the top or lower section of the TIMER
button to set the group no. for the centralized
3 controller.
6 (When you use the unified ON / OFF
1 7 controller, it displays only the group no.
BRC301B61
selected by the setting switch for zone
control.)
4 Press the PROGRAM / CANCEL button to
enter the setting group no. shown on the
4 5 2
display.
5 Press INSPECTION button to return to normal
mode.
Note:
Do not duplicate the group number.
Be sure to supply the power to the remote controller side.
(It cannot be set without the power supply.)
(HC0094)
72 VAMGJ Series
ED71-613 Installation
Cautions
When you make an initial setting ON, the interlocked operation has a priority, and it is impossible to operate / stop HRV unit
independently by the central remote controller or the unified ON / OFF controller. If there is no indoor unit for interlocked
operation in the same zone, make an initial setting OFF.
When you make an initial setting OFF, the independent operation of HRV unit has a priority, and the interlocked operation is
not possible.
When the HRV unit is operated independently by the central controller, the HRV unit will not operate until the preset time elapses
if the precool / preheat time setting is set. Therefore, please do not set the precool / preheat time setting in normal operation.
Example of system
Zone 1
Central
Unified ON / OFF
remote
controller Controller
1 2
Collective zone Collective zone
The unit 1 interlock setting OFF interlock setting ON
The operation and display by the central
Remote controller for indoor unit
controller will be basically the same as those on
the remote controller for indoor unit. However,
the HRV unit cannot be operated independently Zone 2 Zone 3
by the central controller.
The unit 2
The operation of HRV unit is interlocked with
indoor units in the same zone, and the HRV unit 5 4 3
can also be operated independently by the Collective zone Collective zone Collective zone
central remote controller. However, it can not be interlock setting OFF interlock setting OFF interlock setting OFF
operated independently by the unified ON / OFF
controller. (HC0095)
The unit 5
When the central remote controller is used, each
unit will be one zone, unless you set the zone for
plural units.
VAMGJ Series 73
Operation ED71-613
5. Operation
5.1 Method of operation
5.1.1 Operation with the remote control exclusively for Air conditioning operation HRV units.
(BRC301B61)
For non-independent systems, starting / stopping operation and timer operation may not be possible.
Use the air conditioner remote control or the Centralized controller in such cases.
1 Operation lamp 5 Indication of operation control method :
This pilot lamp (red) light up while the unit is in Operation. When the operation of HRVs are interlocked with the air
2 Operation / Stop button conditioners, this indication may be shown. While the
indication is shown, the ON / OFF of HRVs cannot be
When pushed once, the unit starts operating.
operated by the HRV remote controller.
When pushed twice, the unit stops.
6 Indication of operation standby :
It indicates the precooling / preheating operation. This unit
is at stop and will start operation after the precooling /
preheating operation is over. Precooling / preheating
5 7 1 2 operation means the operation of HRVs is delayed during
the startup operation of interlocked air conditioners such
FRESH UP a before the office hours. During this period the cooling or
HRV heating load is reduced to bring the room temperature to
6
A the set temperature in a short time.
hr
FRESH UP
hr FRESH UP
8 7 Indication of centralized control :
When a remote controller for air conditioners or devices
11 4
12 A
for centralized control are connected to the HRVs, this
13 3
indication may show.
10 TEST 9 During this indication appears on the display, the ON /
BRC301B61
74 VAMGJ Series
ED71-613 Operation
5.1.2 Operating the HRV unit using the remote controller of the VRV- system air conditioner
The HRV unit cannot be operated independently when the air conditioner
Operation mode display
is connected to the HRV unit via a duct. When using the HRV unit, set the
air conditioner to fan mode on weak fan strength. Ventilation is displayed.
Operation mode
hr
selector button
hr NOT
TEST AVAILABLE
TEST
Each time you press the operation selection button, the operation mode
display will change as shown in the figure below.
Remote controller for indoor unit
When air conditioner and HRV When air conditioner and HRV
unit are not connected via duct unit are connected via duct
VRV: VRV:
Cooling mode Cooling mode
HRV: HRV:
Heat exchange mode Heat exchange mode
VRV: VRV:
Fan mode Fan mode
HRV: HRV:
Heat exchange mode Heat exchange mode
VRV:
Stopping NOTE) Current Ventilation mode can be visible and
HRV:
Heat exchange mode selected on the remote controller.
3P034927-5J
5.1.3 Independent operation of the HRV unit using the Centralized controller (DCS302C(A)61)
After selecting the zone where the only the HRV unit operation is desired, press the operation mode selector and select
VENTILATION. The HRV unit can then be operated independently from the air conditioner.
When the FILTER indication appears on the display, clean the filter of the HRV unit. (Refer to the section 3.)
VAMGJ Series 75
Operation ED71-613
Essential Wiring
1. Connect one end of the harness to the X15A on the print board and the other end to the harness leading to the damper via a
connector such as a closed connector.
With regard to closed connector, select one that suits wire diameter.
Essential Setting Changes
The X15A output is at the default setting and is not in operation, so the output setting should be changed at the LCD of the remote
controller.
Setting changes should be made in the following way.
Mode No. : 18 (group tie up) or 28 (per each unit)
Setting switch No. : 3
Setting position No. : 03
76 VAMGJ Series
ED71-613 Operation
WARNING WARNING
Before obtaining access to terminal devices( ), all power BEFORE OBTAINING ACCESS TO TERMINAL
supply circuit must be interrupted. DEVICES, ALL POWER SUPPLY CIRCUITS MUST BE
INTERRUPTED.
To clean the HRV, or maintenance be sure to stop operation,
and turn the power switch off. It may cause electrical shock
and it is very dangerous to touch the rotating part.
Do not wash the HRV with water.
Doing so may result in an electric shock.
! CAUTION
Use gloves when cleaning.
Cleaning without gloves may cause injury.
OFF Watch your step.
(HC0227) Use caution, as this requires working in high places.
Electric shock may result. Before servicing the unit, always Do not use benzene or thinner to clean the outside
shut off power. surfaces of the air conditioner.
This may cause cracks, discoloration, or machine trouble.
5.3.1 How to clean the air filter
WARNING Clean the air filter when the display shows
Always use the air filter. (TIME TO CLEAN AIR FILTER).
If the air filter is not used, heat exchanger elements will be It will display that it will operate for a set amount of time.
clogged, possibly causing poor performance and
CLEANING FREQUENCY
subsequent failure.
AT LEAST ONCE EVERY YEARS
(FOR GENERAL OFFICE USE)
(CLEAN THE MORE FREQUENTLY IF NECESSARY.)
Increase the frequency of cleaning if the unit is installed in
a room where the air is etermely contaminated.
If the dirt becomes impossible to clean, change the air filter
(Air filter for exchange is optional).
1. Detach the maintenance cover.
Go into ceiling through the inspection hatch, remove
(HC0101) binding metal of maintenance cover and take it off.
Do not operate
in the Bypass
ventilation
mode in winter!!
HR
HRV
A
UNIT No. hr
CODE SETTING A
GROUP hr FRESH UP
BRC301B61
(HC0103)
3P034927-5J
VAMGJ Series 77
Operation ED71-613
3P034927-5J
78 VAMGJ Series
ED71-613 Operation
4. Use a vacuum cleaner to remove dust and foreign CAUTION (During Operation)
objects on the surface of the heat exchange element. Do not clean touching strongly with a vacuum cleaner. This
may crush the mesh of the heat exchange elements.
Never wash the heat exchange element with water.
Have your dealer professionally clean the filter if it is very
dirty.
5. Put the heat exchange element on the rail and insert it
securely in place.
6. Install the air filter securely in place.
(Refer to the section (5.3.1, 4))
7. Install the maintenance cover securely in place.
(Refer to the section (5.3.1, 5))
CAUTION
Always use the air filter.
Use the vacuum cleaner equipped with a brush on the If the air filter is not used, heat exchange elements will be
tip of the suction nozzle. clogged, possibly causing poor performance and
Lightly contact the brush on the surface of the heat subsequent failure.
3P034927-5J
exchange element when cleaning.
(Do not crush the heat exchange element while
cleaning.)
5.4.2 If the following occurs, consult the dealer where the unit was purchased.
List of malfunction codes of Remote controller of the HRV-system
Operation Inspection Malfunction
Unit No. Description
lamp indicator code
On Off Blinking 64 Indoor air thermistor malfunction
On Off Blinking 65 Outdoor air thermistor malfunction
On Off Blinking 6A Dumper-related malfunction
Blinking Blinking Blinking 6A Dumper-related malfunction + thermistor malfunction
Blinking Blinking Blinking U5 Transmission error between the unit and remote controller
Off Blinking Off U5 Setting error of remote controller
Off Blinking Off U8 Transmission error between main remote controller and sub remote controller
Off Blinking Blinking UA Incorrect combination with indoor unit and remote controller.
On Blinking On UC Central control address over lapping
Blinking Blinking Blinking UE Transmission error between the unit and centralized controller
On Off Blinking 60 External protection device abnormal
Blinking Blinking Blinking 60 External protection device abnormal
In case of the malfunction with the code in white letters on the black background in the unit still operates.
However, be sure to have it inspected and repaired and as soon as possible.
If other than the above error codes are displayed, there is a possibility that the problem in question has occurred with a combined
air conditioner or outdoor unit. See the operation manuals included with the air conditioners or outdoor units for details.
VAMGJ Series 79
Optional accessories ED71-613
6. Optional accessories
Optional Accessories
VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE
Remote Controller BRC301B61
Wiring adapter for Humidifier KRP502
Installation box for adapter PCB KRP502A90 (Mounted electric component assembly of HRV)
Wiring adapter for electrical appendices KRP2A61 (For general) KRP2A51 (For EC Market)
Central Remote Controller DCS302C(A)61 (For general) DCS302C(A)51 (For EC Market)
Schedule Timer DST301B(A)61 (For general) DST301B(A)51 (For EC Market)
Unified ON / OFF controller DCS301B(A)61 (For general) DCS301B(A)51 (For EC Market)
Model name KDDM24B50 KDDM24B100
Silencer
Nominal pipe diameter (mm) 200
Air Filter for replacement KAF241G25M KAF241G25M KAF241G50M KAF241G50M KAF241G65M
High efficiency filter KAF242G25M KAF242G25M KAF242G50M KAF242G50M KAF242G65M
Model name (1m) KFDS101C KFDS151C KFDS201C
Flexible duct Nominal pipe diameter (mm) 100 150 200
*** Model name (2m) KFDS102C KFDS152C KFDS202C
Nominal pipe diameter (mm) 100 150 200
Heater control kit BRP4A50
Note:
1. Installation box ** is necessary for each adapter marked *.
2. Up to 2 adapters can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box ** is necessary for second adapter.
6. Installation box ** is necessary for each adapter.
7. Flexible duct size *** is for the duct from HRV unit to branch duct (or air outlet).
C : 3D051623
80 VAMGJ Series
ED71-613 Optional accessories
Lower Part of
Remote Controller
Minus screwdriver
Insert the minus
screwdriver and
twist lightly to remove.
Switch Box
(Field supplied parts)
Machine Screws
(M4 16)
For the field supplied switch box, use optional accessories KJB111A or KJB211A.
NOTE
Choose the flattest place possible for the mounting surface. Be careful not to distort the shape of the lower
part of remote controller by over-tightening the mounting screws.
(HC0111)
2P034150
VAMGJ Series 81
Optional accessories ED71-613
" " is displayed for about one minute when the power supply is turned on, and the remote controller
cannot be operated in some cases.
(HC0112)
2P034150
82 VAMGJ Series
ED71-613 Optional accessories
(16) (5)
2. Installation guide
1. The KRP50-2 can be connected to HRV units as follows to
send the operation signal (pilot lamp, etc.) to remote
locations.
Electric wiring is as follows.
Power supply
Pilot lamp (1 220 240 V)
(Operation display) J1J2JC F1F2
3P connector 4P055444
L 1 X9A SS1 X11A
2P connector X10A
2
3 P1P2
KRP50-2 HRV unit
P1P2
Remote controller
for HRV unit
(HC0253-1)
For Humidifier
Power supply
1 100 V or 200 V
J1J2JC F1F2
YC 3P connector X9A SS1 X11A
SV 1
2P connector X10A
A 2
B
Float 3
switch Y2 P1P2
KRP50-2 HRV unit
Humidifier
Humidity Controller P1P2
(Field supplied)
Remote controller
for HRV unit
(HC0115-1)
VAMGJ Series 83
Optional accessories ED71-613
(HC0116)
C : 1PA63641G
84 VAMGJ Series
ED71-613 Optional accessories
Max. 16 units
Remote controller
Max. 64 groups
Max. 16 units
To outdoor unit
NOTES
Individual indoor units connected to the centralized line cannot be displayed
individually.
1PA63641G
VAMGJ Series 85
Optional accessories ED71-613
3 Installation
Ceiling Mounted Cassette Corner Type Ceiling Mounted Cassette Type (Double-Flow)
FXK(Q) FXC(Q)
FXYKP FXYCP
Ceiling Mounted Cassette Type (Multi-Flow) Ceiling Mounted Cassette Type (Multi-Flow) 600600
FXF(Q) FXZQ
(KRP2A62)
C : 1PA63641G
86 VAMGJ Series
ED71-613 Optional accessories
Note :
Installation box is necessary for second adaptor (FXS (Q)) .
KRP2A61
C : 1PA63641G
VAMGJ Series 87
Optional accessories ED71-613
4 Electrical wiring
1 First, wire between the indoor and outdoor units, then to the separate power sources, and between
the indoor units and the remote controllers. Then, check wiring is correct. (If wanting group control
by remote controller check transmission wiring.) For details, see the installation manual of the indoor
and outdoor units.
2 Next, wire between the wiring adaptor for electrical appendices (1) and the indoor units.
For details, see Wiring to indoor units .
3 Finally, wire between external units such as the host computer monitor panel, and make the
necessary settings. For details, see Wiring to external units (host computer monitor panel) .
Note) It is not necessary to set address No. for centralized control. (Setting is automatic.) (HC0122)
SS
Z 3
X18A
PC board assy
I
DISPLAY OUTPUT
Adaptor
PCB
Max. 16 units
Max. 16 units
(Wiring specifications)
Wiring .... Sheathed wire (2-wire)
Gauge .... 0.75 ~ 1.25 mm2
Length .... Max. 1000 m
IMPORTANT
P1,P2 F1,F2
Keep transmission wiring at least 50 mm away from power
supply wiring to avoid malfunctions.
Max. 64
groups R/C Remote controller
(HC0123)
1PA63642B
88 VAMGJ Series
ED71-613 Optional accessories
NON
Set input changeover switch
For non-voltage input VOLT
(Wiring specifications)
Wiring .... Sheathed wire
Gauge .... 0.18 ~ 1.25 mm2
Length .... Max. 150 m
( IMPORTANT )
Keep transmission wiring at least 50 mm away from power
supply wiring to avoid malfunctions.
(HC0124)
1PA63642B
VAMGJ Series 89
Optional accessories ED71-613
CONTROL MODE
Using control mode selector switch (RS1), select the
control mode as described below.
Factory set:
0 position
Note
Input B is for forced-OFF. When ON, stop + remote controller is rejected, and input
A is ignored. When OFF, even if A is ON, the contents of when input A is ON are
not achieved. Input A must therefore be re-input.
3 When operating with momentary input from A
(Use a momentary input of ON time 200 mili-sec or longer.)
90 VAMGJ Series
ED71-613 Optional accessories
Notes
In zone control, operation is displayed as long as one indoor unit is running. When
in the last command priority mode, some units are not operation while ON.
In such case, even if input A is ON, the unit and all other units in the same zone
will stop.
Contents when
Position Function Contents when input A is ON
input A is OFF
Note
Doing constant input A with position 7 to A, it will be forced OFF function
(input A is ignored.)
Constant input cannot use for input B with position B.
(HC0126)
1PA63642B
VAMGJ Series 91
Optional accessories ED71-613
Wiring adaptor
KRP2A61 62 51 52
Resistance ()
3.4 11.6 20.0 28.4 36.4 44.8 52.8 61.2 69.4
Temperature
25 26 27 28 29 30 31 32
setting (C)
73.8 82.4 91.0 99.4 108.6 117.2 125.8 134.2
Resistance ()
77.8 85.8 94.0 102.2 110.4 119.2 127.4 140.0
92 VAMGJ Series
ED71-613 Optional accessories
Adaptor
X1 PC board support 4
Clamp 3
Installation manual 1
(HC0129)
1. Names of parts
X2A
VAMGJ Series 93
Optional accessories ED71-613
2. Electric Wiring
Refer to the WIRING DIAGRAM attached to the indoor unit before attempting to wire.
[Make sure wires to units do not pass over the PC board when wiring.]
Wire the adaptor to the indoor unit as shown below,
X2A
X16A
X1A
Blue
N
Red L
(HC0131)
Output is generated at the contact while the Output is generated at the contact while the fan is
compressor is running. running.
(HC0132) (HC0133)
94 VAMGJ Series
ED71-613 Optional accessories
3. Installation
Installation differs according to models as shown below.
Do not bundle low and high voltage wires together.
Bundle any access wires with the attached clamps so as to keep loose wirings off the indoor unit PC board.
Indoor PC board
Adaptor
(KRP1B61)
PCB support
PCB support
Installation screw
Adaptor
(KRP1B61)
Indoor PC board
Electric parts box
(HC0136)
NOTE) A separate plate is needed to install the adaptor PCB.
C : 2PA61563C
VAMGJ Series 95
Optional accessories ED71-613
FXM40~125L FXM200250L
Adaptor
(KRP1B61)
Indoor PC board
PCB support
Floor-standing type
PCB support
Adaptor
(KRP1B61)
(HC0139)
FXYDKA
Indoor PC board
PCB support
Electric parts box
Adaptor
(KRP1B61)
C : 2PA61563C
96 VAMGJ Series
ED71-613 Optional accessories
VAMGJ Series 97
Optional accessories ED71-613
Adaptor PCB
Plastic strap 3 pieces
1 set Installation manual 1 piece
PCB support * 4 pieces
* For ceiling suspended type
CN1
(HC0217)
1. Name of parts
CN1
(HC0225)
2. Electrical wiring
Refer to the wiring diagram of the indoor unit for its wiring connection.
(Make sure all the wiring to the unit should not go over the PC board.)
Connect the wiring to the indoor unit as shown below.
X2A
X16A
CN1
(HC0211)
J : 2PA58148A
98 VAMGJ Series
ED71-613 Optional accessories
Output signal to detect the operation of the Output signal to detect the operation of the fan.
compressor.
(HC0132-1) (HC0133-1)
FXYAK FXHL
(V2443)
JC : 2PA58148A
VAMGJ Series 99
Optional accessories ED71-613
The group means the indoor units connected by the same control wiring for remote controller (connected to terminal P1 and P2)
and all the unit in group have the same setting and the same operation.
The indoor units in the group are controlled by the remote controller for indoor unit.
The number of indoor units in one group is up to 16 units.
Zone control
The zone means the indoor units connected by the same control wiring for central remote controller (connected to terminal F1 and
F2) and all the unit in zone have the same setting.
The zone control of the indoor unit is operated by the central remote controller.
From 1 up to 64 zones can be controlled by the central remote controller.
The number of groups you can set in one zone is from 1 up to 64 groups.
Up to 16 units can be set in one group, and up to 64 groups (up to 128 units) can be connected.
Note:
The following setting cannot be made by the sub side. Be sure to set by the main side.
Operation code setting
Combined operation between indoor unit and HRV unit.
Caution for wiring of BEV unit system with Central Remote Controller
When the BEV unit system, such as FXAQ / FXLQ-MHV1, FXUQ-MV1, and FUYP-BV1 are connected to the Central Remote
Controller, the wiring becomes more complicated than that of general VRV system.
Please take care as follows when wiring.
[Indoor unit] [Indoor unit] [Indoor unit] [Indoor unit] [Indoor unit] [Indoor unit]
(NOTES)
1. When 3 or more wirings are branched from the [Wiring Example (2)]
same terminal block, use a relaying terminal
block of field supply.
2. In the Wiring Example (1) and (2), 3 wires are
not connected on the same terminal block.
3. FXAQ-MH : Interface adapter for SkyAir [Central
R/C]
series is not necessary.
Interface adapter for SkyAir is required when
connecting with optional controller for F1, F2 F1, F2 F1, F2
centralized control. [BEV] [BEV] [BEV]
Specifications
DCS302C(A)61
Power supply voltage / frequency AC100~240V 10% 50 / 60Hz
Power consumption Max. 8W
Setting data backup Non-volatile memory (Data preserved semi-permanently)
Effects of instantaneous power failure No effect for 20 mili-sec. or less
Forced OFF input No-voltage normal open contact
Operation on the local side cannot be carried out Micro-current contact capable of handling 16VDC and approx. 10mA.
during forced OFF input. Max. 150 m cable length
Power supply for schedule timer Power can be supplied to schedule timer. (Max. 1 unit)
Operating ambient temperature /humidity condition -5~40 C, 95% RH or less (no condensation)
Size (width height depth) 18012064.5 mm exposed portion of front panel : 16 mm
Weight (Mass) Approx. 420 g
Dimensions
DCS302C(A)61
Unit (mm)
3D050340
DISPLAY (REFRIGERANT
It lights up when any individual unit
(group) has reached the time for the
SYSTEM DISPLAY)
filter or element to be cleaned.
This indication in the square is lit
while the refrigerant system is DISPLAY
being displayed. (COOLING/HEATING SELECTION
PRIVILEGE NOT SHOWN)
ALL OPTION
DISPLAY (ZONE SETTING) INDIVIDUALLY For zones or individual units (groups)
TEST for which this is displayed, cooling and
The lamp is lit while setting zones.
F 12 heating cannot be selected.
SET C No..
DISPLAY (OPERATION CODE
NOT
T UNIT No. DISPLAY (UNDER HOST
MONITOR) L H HH
AVAILABLE FRESH UP COMPUTER INTEGRATED
The lamp is lit while operation is CONTROL)
being monitored. While this display is lit up, no settings
can be made. It lights up when the upper
ALL INDIVIDUALLY DISPLAY central machines are present on the
The status displays indicates either same air conditioning network.
batch functions or which zone or
individual unit (or group) are being used. No. DISPLAY (TIME NO.)
TEST DISPLAY
(INSPECTION/TEST)
Pressing the maintenance/test run
button(for service) displays this. This
button should not normally be used.
Control Section
3P124623-8D
Basic functions
Descriptions of outline
Up to 64 groups (Max. 128 units and max. 16 units per group) of indoor units and HRV
Individual / Zone control
units can be controlled by individually or by zone.
ON / OFF can be set for each zone, and can be controlled simultaneously for entire
Unified ON / OFF
system by push button or by contact signal from outside.
The status of each group is always displayed, such as ON / OFF, error, etc. If the error occurs,
Malfunction code display
it displays the contents of error by malfunction code through the self-diagnosis function.
By connecting the unification adaptor for computerized control (option), it can be linked
Connection of unification adaptor for
with the central monitoring panel and etc. by contact signal, which enables you to
computerized control
operate ON / OFF simultaneously or monitor the operating status.
It is possible to restrict the function of local remote controller.
Remote control acceptance/rejection
(Only ON operation rejection, or ON / OFF operation rejection)
By connecting two central remote controllers, the same air-conditioner can be controlled
2 central controllers
from 2 locations (By tenant or administration office.)
Cool / heat Selection Eligibility Setting by Remote Controller for Indoor Unit
The outdoor unit of VRVII, VRV inverter "K" series, Heat Recovery series and VRV Plus series can freely be selected the operation
mode (fan, dry, auto[Heat Recovery only], cooling or heating) by the remote controller for indoor unit. However, as shown below as
example, for VRV inverter "K" series, you have to set the selection eligibility for fan, dry, cooling and heating operation on the one of
the remote controller out of the indoor units connected to the outdoor unit. For Heat Recovery series and the function unit (for heat
recovery), if 2 or more indoor units are connected to one BS unit, you have set the selection eligibility for fan, dry, auto, cooling and
heating operation on the one of the remote controller out of the indoor units connected to the BS unit.
(Only remote controller having the selection eligibility can change the operation mode.)
It is also possible to set the selection eligibility on the wireless remote controller.
It does not possile to set the "Dry" by the Central Remote Controller.
Note:
Be sure that if timer No. is registered by the sub central remote controller, [Timer mode acceptance for local remote controller (mode
no. 8,9,18, and 19)] for the same units set by the Main remote controller becomes meaningless (operates when time comes.).
<Cautions>
Operation code cannot be set by the sub central remote controller.
Combined zone operation can only be set by zone registration of the main central remote controller.
Both main and sub central remote controller are operated by a Last priority command for the functions other than the above.
However, the display on the central remote controller cannot be changed by each other. (On the display for the group, you can
monitor the present operation status.)
Sequential Start
<Operation command from central control equipment>
Each unit operates in sequence. For example, if you set the simultaneous operation by the central remote controller, which controls
1-00 ~ 4-15 and 5-00 ~ 8-15 groups, two outdoor units start simultaneously.
Registering Zone
It is possible to set multiple groups as one zone and control each zone
separately.
No zones are registered when the unit is shipped from the factory. 2
9
Zone registration can be done in the individual screen, all screen, or zone
screen.
5
1 6 3
4
7 8
Registration
1. 1 Pressing the ALL/INDIVIDUAL button for four seconds. 2 Displays ZONE SET.
Zone Number 1 will be displayed, and if there are any groups already registered in the displayed zone, a will light up on
the operation monitor.
2. 3 Select the Zone Number to be registered using the ZONE NUMBER button.
Keeping the button pressed down will move it rapidly.
3. 5 to the group you wish to 4 register using the arrow keys.
Keeping the button pressed down will move it rapidly.
4. 6 Press the SELECT button to register that group to the zone.
The display lights up on all the selected units.
7 Pressing the RESET button removes the group from that zone, and goes OFF.
Repeat steps 3 and 4 until all the units you wish to register to the zone have been added.
In this example, a screen is shown with units 1-00, 1-02, 1-03, and 2-00 registered to Zone Number 1.
5. Repeat steps 2 to 4 to register to the next zone.
6. Once zone registration is complete, 1 press the ALL/INDIVIDUAL button to turn OFF ZONE SET display and
return to the individual screen.
The display returns to the normal screen if nothing is done for one minute when in zone registration mode.
(NOTE)
It is impossible to register one group to several different zones.
If this is done, the last zone registered to will be valid.
3P124623-8D
Zone setting
Set the screen of [Zone 0] on the display, and if you set the following mode, you can set to the all zone registered on the central
remote controller by one operation.
Operation mode
Control mode
Room temperature setting
Time NO.
When an indoor without FAN DIRECTION, FAN STRENGTH is chosen, NOT AVAILABLE will be displayed if FAN DIRECTION",
FAN STRENGTH button is pushed.
When a HRV without VENTILATION MODE, VENTILATION STRENGTH is chosen, NOT AVAILABLE will be displayed if
VENTILATION MODE , VENTILATION STRENGTH button is pushed.
On the Zone screen and All screen, the FAN DIRECTION ADJUSTMENT, FAN STRENGTH ADJUSTMENT, VENTILATION MODE,
and VENTILATION STRENGTH buttons are disabled.
Pressing any of these buttons will display the NOT AVAILABLE message on the screen.
With the Schedule Timer not connected, even if the Timer No. button is pressed, the NOT AVAILABLE message will not be displayed.
While in double central control function, even if the OPERATION CODE button is pressed, the NOT AVAILABLE message will not be
displayed.
For monitoring the zone settings: The following screens are displayed.
Outdoor Unit
Zone 1 Zone 2 Zone 3
Central Remote
Controller Indoor Unit HRV
1-00 1-01 1-02 1-03 1-04 1-05 1-06 1-07 1-08
Zone 4
Operation Code
Main Indoor Unit Temp. Display Operation Mode Ventilation Mode
Timer No.
Zone 1 1-00 1-00 1-00 1-00 N/A
Zone 2 1-03 1-03 1-03 1-03 1-05
Zone 3 1-06 1-06 1-07 1-07 1-06
Zone 4 2-00 2-00 N/A N/A 2-00
If the system is operated on the Zone screen, one and the same setting will be made on all indoor units registered with the zone.
On the Zone screen, ventilation mode is only monitored. In order to change ventilation mode, be sure to use the Individual screen.
On the Batch screen, operating and monitoring is also enabled, thus monitoring an indoor unit with a lower address within the scope
of control.
4 2
INDIVIDUALLY
1 3
6
[Registration]
1. 1 Press the ALL/INDIVIDUAL button to enter the 2 individual screen.
The unit will enter the individual screen automatically if nothing is done for one minute.
2. 3 Using the arrow keys, 4 move the to select the units to fan direction adjustment or fan strength adjustment.
Keeping the button pressed down will move it rapidly.
3. 5 Press the FAN DIRECTION ADJUSTMENT button.
This sets fixed or swing for the fan direction.
6 Press the FAN STRENGTH ADJUSTMENT button.
Pressing this button scrolls through L
, H
and HH
.
H
FRESH UP
5
1
3
[Registration]
1. 1 Press the ALL/INDIVIDUAL button to enter the 2 individual screen.
The unit will enter the individual screen automatically if nothing is done for one minute.
2. 3 Using the arrow keys, 4 move the to select the units to ventilation mode or ventilation strength adjustment.
Keeping the button pressed down will move it rapidly.
3. 5 Press the VENTILATION MODE button.
It will scroll through .
6 Press the "VENTILATION STRENGTH ADJUSTMENT" button.
The fresh up function may not be available depending on the connected unit model.
The functions included in the indoor units may vary.Pressing a button for a function which is not available will cause NOT
AVAILABLE to be displayed.
1 2
C No.
[Registration]
1. 1 Pressing the TIMER NO. button causes the number set for timer number 1 to blink.
If no timer setting has been made will be displayed.Select the desired timer number by pressing the 1 1 2
TIMER NO. button. No.
2. 2 Once the desired timer number is displayed, press the SET button.
Press the 2 SET button within 10 seconds after the timer number is displayed. 1 2
The display will return to how it was after 10 seconds. No.
The display for timer number 1 will stop blinking and then timer number 2 will start blinking.
3. 1 Select the desired timer number by pressing the TIMER NO. button.
Once the desired timer number is displayed, 2 press the SET button. 1 2
The display for timer number 2 will stop blinking. No.
Since the timer number will be set to after-press priority, the timer number in the last screen set will be valid for the
connected units.
Example 1
Setting timer number 1 for unit 1-00 to 1 and timer number 2 to 2 in the individual screen and then setting timer number 1 to 3
and timer number 2 to 4 in the batch screen causes the timer numbers for all units to be set, so timer number 1 for unit 1-00 will
be 3 and timer number 2 will be 4.
Example 2
To prevent leaving units on, timer number 1 is set to 5 in the batch screen.
Setting timer number 1 in zone number 1 to in the zone screen after that will change the timer number for zone number 1, so
the setting to prevent leaving the units on will be lost for zone number 1 only.
If a timer number is set incorrectly by accident, redo the setting in the desired screen.
What happens when the timer number on time and off time are set to the same time
When the on time and off time are set to the same time for the same timer number, operation does not change.
When the on time and off time are set to the same time for different timer numbers, the off time is given priority.
When using timer operation, make sure the times do not overlap when setting the program of the schedule timer.
3P124623-8D
Wiring instructions
For control wiring of DIII-NET, you can select from the following 3 types of wiring methods.
1. Series method :
Wiring is connected by a single line from the central controller.
2. Bus method :
Up to 16 branches is possible. Never diverge the sub-branches from the branch line.
3. Star method :
Up to 16 branches is possible. Never diverge the sub-branches from the branch line.
4 4
5 4 3 3.7 6 5 5
2.6
3P124623-8D
<Cautions>
Even in the system without remote control, connect the remote controller once to set group No. for central control equipment and
remove the remote controller after setting.
When you set the group No., be sure to supply the power to the central remote controller, the unified ON / OFF controller and the
indoor unit.
Cautions
When the power is supplied, all the display appears once on the remote controller and then the display changes to [88] for about one
minute and during that time the remote controller does not function. However, this is not a malfunction of remote controller.
3P124623-8D
Schedule Timer
Operation by Central
Remote Controller Acceptance
ON OFF ON ON OFF ON OFF ON ON Rejection
DCS302C(A)61
Command
ON OFF ON OFF OFF ON OFF
Remote Controller
Command
Indoor Units Status ON
OFF
Operation by remote controller is the same as central priority.
2P162816
2P162816
2P162816
SET C
1.5 2 4
Setting Procedure
1. Press and hold the INSPECTION/TEST RUN button for a period of four seconds or more to set the system to FIELD SETTING
mode.
2. Use the TEMPERATURE ADJUSTMENT button to select a desired Mode No.
: Press to increase the Mode No. : Press to decrease the Mode No.
3. Press the CONTROL MODE (CODE No.) button to select a Switch Setting No..
4. Press the SET button to determine the content of the setting changed.
Upon determination, the blinking the Switch Setting No. will turn ON.
5. Press the INSPECTION/TEST RUN button to return the system to NORMAL mode.
In this case, power supply is not needed to turn ON again.
Example : In case of no restriction items from the sub central remote controller while in double central control, make setting of the
Mode No. to 02 and the Switch Setting No. to 0.
Setting Contents and Setting No.
No. of setting switch
Mode No. Setting contents
0 1 2
00 Setting of sequential operation function NO YES
01 Setting of refresh function NO YES
Setting of restriction items from sub central remote
02 Disabled Enabled
controller while in double central control function
Setting of area designation for forced OFF Forced OFF all within Forced OFF only within Forced thermostat OFF
03
(Operation with T1 and T2 entered) the scope of control the scope of control with the scope of control
Items indicated by boldface represent the factory set for the No. of Switch Setting.
Do not make setting of any items not listed in the table above.
Refresh function
This function is used to automatically send OPERATION MODE and TEMPERATURE SETTING from the central control system
while in operation. In order to disable the refresh function, set the No. of Switch Setting to 0.
Restriction items from sub central remote controller while in double central control function
While in double central control function, no settings of zone interlock and operation code can be made from the sub central remote
controller. In order to disable the refresh function from the sub central remote controller, set the No. of Switch Setting to 0.
Setting of area designation for forced OFF
In order to stop all indoor units within the scope of control as a single unit using the entry of T1 and T2, set the No. of Switch
Setting to 1.
In order to stop all indoor units within the scope of control with forced thermostat OFF using the entry of T1 and T2, set the No.
of Switch Setting to 2. With this parameter set to 2, no forced stop can be made on any indoor unit.
6.7.13 Refreshed operation
Refreshed operation is the function to transmit setting of Temperature control, Temperature setting automatically from DCS302C(A)61.
Refreshed operation is ON when shipped from the factory.
Factory Setting
Outdoor Units Systems Indoor Units Mode
Cooling Mode Cooling 28 C
Heating Mode Heating 22 C
Fan Mode Fan Operation
It depends on the setting of outdoor systems that an indoor unit setting is Temperature control or Temperature setting
In case of Refreshed operation is ON
When setting is changed by DCS302C(A)61, it operates by this setting from the next operation.
If it sets up with 26 C in cooling by DCS302C(A)61, in the case of the equipment which has not carried out zone setting by a
central remote controller, it operates from next with the mode of operation and preset temperature which were set up on the
individual screen.
In the case of the equipment which carried out zone setting, it operates from next with the mode of operation and preset
temperature which were set up on the zone screen.
(Priority is given over the mode of operation and preset temperature which were set up on the zone setting screen).
When it sets up all at once, it operates from next with the mode of operation and preset temperature which were set up last
time on the individual screen (Equipment which has not carried out zone registration), or the zone screen.
If a setting change is made with 26 C of cooling by a central remote controller on an individual screen (Equipment which has
not carried out zone setting) next operation will also be operated at 26 C in cooling. (Even if it has changed into heating
operation, fan only operation with wired or wireless remote control, it operates at 26 C in cooling.)
When zone registration is carried out by Central Remote Controller.
It operates from next time with the value set up in the zone.
When a zone 1 is set up with 20 C of heating. (Refer to the system of the following figure.)
When controlled by Central Remote Controller, 3 indoor units registered into the zone 1 are operated by 20 C of heating.
Because priority is given to zone setting, even if it sets up 2-02 with 25 C of heating on an individual screen from Central
Remote Controller, 2-02 is operated at 20 C.
When there are two or more indoor units in a zone.
Because an operating mode depends on the outdoor unit, the operating mode of each indoor unit does not become the same
setting.
When the outdoor unit system 1 is cooling, the outdoor unit system 2 is heating and it operates by the system of the following
figure. Setting of a zone 2 is operated in heating mode, because 2-03, 2-04, and 2-05 do not have a cooling/heating selection
right as for 26 C of cooling, but temperature setting becomes 26 C.
When you unify the operating mode of an indoor unit in the same zone, please set up a zone in the indoor unit of the same
outdoor unit system.
Zone 2
Outdoor Unit
System 2
2-00 2-01 2-02 2-03 2-04 2-05
Installation
2P162816
L UNIT No.
3P124623-8D
3P124623-8D
Transmission error between indoor unit/BEV unit and outdoor unit within a
single system
U9
Transmission error between BS unit and indoor unit/BEV unit and outdoor
unit within a single system
error codes (in outline font) do not display maintenance and the system will run, but please check the content
of the display and contact your dealer.
3P124623-8D
1P162827
1P162827
6.8.3 Dimension
Unit (mm)
3D050339
6.8.4 Installation
1P162827
1P162827
1P162827
1P162827
System Configuration
If using the schedule timer alone, you dont have to set the centralized control group No. for group control.
Transmission Wiring
<Indoor Unit Wiring>
1. If using the schedule timer alone :
For the schedule timers power supply, connect the schedule timer (D1, D2) with the connector (X18A) on the indoor unit PC board
by crimped style terminal with the attached electric wire.
Transmission wiring for control : 0.75~1.25 mm2 sheathed vinyl cord or cable (2 wire) ..... Max. 1,000 m (Total Max. 2,000 m)
<Transmission Wiring Connection Example>
1 series wiring, 2 bus wiring, and 3 star wiring are the same as with the central remote controller.
4 6 5 3 1 2
7
8
DST301BA61
9 10 11
Fig. 1
12 15 14 16 17
DST301BA61
13 18 19 20
Fig. 2
3P124623-5C
DISPLAY (Note)
1. Please note that all the displays in the figure appear for
10 (PROGRAMMED TIME OF SYSTEM START) explanation purpose or when the cover is open.
Displays the time programmed to start.
DISPLAY (PROGRAMMED TIME OF SYSTEM OFF)
11
Displays the time programmed to stop. 3P124623-5C
6.9.4 Dimension
Schedule Timer
DST301B(A)61
Unit (mm)
3D049544
3P162015A
3P162015A
3P162015A
This schedule timer is provided with the malfunction diagnosing function. The malfunction code flashes if there occurs any malfunction
in communication, etc. between and among the optional controllers for centralized control. In addition, the operation lamp also flashes
if there occurs any malfunction in communication with the indoor unit. Check the contents of the display and contact your DAIKIN
dealer because the signals give you the idea of the trouble area.
3P124623-5C
210 210
KDDM24B100
380 19 480
J : D3K03771A
JC : 3P107619
JC : D3K03725
Filter element Filter frame
Specification
Filters material Non woven cloth
Ambient temperature (0 50C)
Available conditions
Relative humidity (40 95%)
Initial pressure loss 24.5 Pa (2.5 mmH2O) or less.
Final pressure loss 78.4 Pa (8 mmH2O) or less.
Average dust collecting efficiency 65% (Colorimetric method)
Life time Over 2500 hours (Outdoor dust density : 0.1 mg / m3)
VAM1500 2000 need 2 sets per one unit.
(HC0222)
6- 5.5Hole
ON
HRV OFF
heat
cool
on
FAN OFF
on
EH OFF
Installation example
Adapter
BRP4A50
Wiring
Electric heater (EH)
Bimetal Temperature
switch fuse (120C)
(85C)
52H
Power supply
for HRV units
Preheater
X9A L N
X10A HRV
BRP4A50 (printed circuit board)
TH3 TH4 (Option)
3P055038
Switch box
3D024303
7. Psychrometric chart
7.1 Psychrometric chart