You are on page 1of 176

FIELDBUS

COMPONENTS
FOR
FOUNDATION
FIELDBUS

F1024/02
FIELDBUS COMPONENTS FOR
FOUNDATION FIELDBUS
Fieldbus systems in process auto- Junction modules in IP67 Junction modules in IP20
mation (1, 4 and 6 ports) (4, 6, 8 and 12 ports)
Fieldbus systems have become prevalent Device versions for use in: Device versions for use in:
in the field of process automation in zone 1 zone 1
addition to decentral peripheral systems. zone 2 zone 2
FOUNDATION fieldbus and PROFIBUS- Non-Ex area Non-Ex area
PA fieldbus systems are now the esta- Adjustable current limitation Adjustable current limitation
blished fieldbuses in this field (for further Switch-in terminating resistors Switch-in terminating resistors
information about the TURCK-product Housing material: powder-coated Housing material: aluminium
portfolio and in particular PROFIBUS-PA aluminium die-cast (4- and 6-port Connection technology: cage clamp
products, please see catalog D301026). types) or encapsulated Polyurethane terminals or removeable connectors
The advantages of both of these systems (PUR) for the single channel versions.
are the process adapted specification and Connection technology: cable glands-
the real interoperability of field devices or flange connections
from various manufacturers and their in 7/8 or M12 1, stainless steel
compatibility with external host systems.

Both the FOUNDATION fieldbus and


PROFIBUS-PA fieldbus fulfil the demands
of the chemical, pharmaceutical and
petrochemical industries. The most
important features are :
standardised user profile
suited for use in explosion
hazardous areas
bus supply and fieldbus Stainless steel housing for IP20
communication via shielded and junction boxes
twisted pair cables Plastic or stainless steel cable glands
online device exchange without Degree of protection IP67
affecting system processes Pressure compensation element
diagnostics for Asset Management Isolated shielding bus
Multibarriers in IP66 (4 ports)
Comprehensive tests performed by the
Installation in explosion hazardous
industry, interest groups and committees
areas (zone 1)
confirm the unlimited suitability of both bus
Galvanic isolation between the EEx i
systems for use in process engineering.
outputs and the EEx e main cable
as well as between the individual
TURCK fieldbus components
EEx i outputs
With TURCK products you are not tied
Fieldbus power supply accord-
down to company-specific fieldbus
ing to enhanced safety EEx e
technologies, but can choose the most
Four intrinsically safe EEx ia
suitable bus product for your application
outputs, 4 40 mA, short-circuit
from a comprehensive product spectrum.
protected and non-interacting
FISCO and Entity conform outputs
TURCK offers the complete range for all
(IEC TS 60079-27)
conventional industrial fieldbus systems in
Short-circuit indication via LEDs
factory and process automation, no matter
(inside housing)
whether you require junction modules,
Integrated terminating resistors
connection products or even complete
(switch-in)
systems.

TURCK fieldbus components are spe-


cially designed for the harsh industrial
environment. The extensive product line
for diverse applications fulfils all demands
and provides Plug & Play connectivity to
ensure fast and easy connection of the
field device to the control system.

Fieldbus cables and cordsets in various


fieldbus standards and materials and with
different connector types are available for
data transfer and voltage supply of the
stations.

2 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Diagnostic Power Conditioner System FISCO and FNICO power supply Terminating resistors
Segment and system diagnostics Integrated repeater function Versions for intrinsically-safe and
Commissioning support
Longterm diagnostics via FF-HSE
Certified to FISCO and FNICO
Switch-in terminating resistor
non-intrinsically safe circuits
M12 1 or 7/8
1
FF functions blocks for diagnostic Switch-in power supply for the host Plug-and-Play technology
alarms Output current: Connector pin assignment conform to
Diagnostics via DTM and/or DD 120 mA or 265 mA for FISCO CENELEC standard EN 50044
Redundant power supply 180 mA or 320 mA for FNICO
High output power for extended
fieldbus segments (800 mA, 30 VDC)
Complete galvanic isolation

Special accessories
Stripping tool, stripping of round
(shielded) data conductors from
2.5...8 mm (also for
FastConnect/Fast Assembly),
Connectors Special tool for cable glands on
Connector size: M12 1 or 7/8, multibarrier and junction modules
type: straight or angled Closure caps and feed-throughs
(angled M12 1 only) in 7/8 and M12 1
Plug-and-Play technology
Load capacity: 7/8 with 9 A,
M12 1 with 4 A
Connector pin assignment conform to
Fieldbus cable available as bulk cable CENELEC standard EN 50044
or premoulded
For indoor and outdoor use
For connection to field-wireable
M12 1 or 7/8 connectors, PG9
or M16/M20 cable glands
Simple installation via Fast-Assembly
technology
Just-In-Time delivery by the TURCK-
JIT-5D-programme: Delivery of all
available premoulded cable lenghts
within 5 days.

Flange connections
Field-wireable or prefabricated
Connector size: M12 1 or 7/8
Solderable and screw-type versions
Standard installation thread
Stainless steel housings

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 3 /0309
Service & Support
A fast delivery service and a comprehen-
sive e-support system perfectly comple-
ment the extensive TURCK program.

With the product database, available on Around 13000 products, clearly structured
www.turck.com, TURCK offers a fast and completely documented, are ready
way to problem solving around the clock, for you to download together with all the
seven days a week, at any place in this necessary information you need.
world and in six different languages. Please have a look on: www.turck.com

4 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FIELDBUS COMPONENTS FOR
FOUNDATION FIELDBUS
Fieldbus systems Basics Page
FOUNDATION fieldbus Bus physics 6
FOUNDATION fieldbus Topology 7 1
Overview Application areas of TURCKs fieldbus components in the explosion
hazardous and non-explosion hazardous area 9

Power conditioners/Power supplies


Diagnostic power conditioner system DPC-49... 10
Power conditioner RPC-49-205 24 2
Power supply PSU-3214 26
FISCO power supplies RPC-49... 28

Active components
Multibarrier MBD49-T415/Ex Basics and application benefits 33
Multibarrier MBD49-T415/Ex 34 3
Fieldbus display FD-49-T317/Ex 36

Junctions
Junctions by TURCK 39
T-pieces 40 4
Junction boxes in IP67 with short-circuit protection 42
Junction boxes in IP67 without short-circuit protection 66
Junction boxes in IP20 with short-circuit protection 90
Junction boxes in IP20 without short-circuit protection 106

Fieldbus cables
Cable technology Basics 122
Cable FBY-.../SD... 124 5
Cable FBY-BK/LD... 125
Cable FBH-YE... 126
Cable FBA-YE... 127
Cable 492A.../Cable 492BA... 128
Cable FB4910-BK... 129

Premoulded cables
The TURCK JIT-5D-Programme 130
M12 1 with cable FBY49... 131 6
7/8 with cable FBY49... 131
7/8 with armoured cables 492A... or 492BA... 132

Flange connectors
7/8 connector 134
M12 1 connector 140 7
Field wireable connectors
7/8 connector 146
M12 1 connector 154 8
Bus termination resistors
7/8 connector 159
M12 1 connector 160 9
7/8 connector for Ex applications 161
Accessories
Stainless steel housings 162
Stripping tool, special tool for cable glands, 10
closure caps, feed-through receptacles 166
Type index 172

11

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 5 /0309
FOUNDATION fieldbus
Basics

FOUNDATION fieldbus Bus physics


With the publication of the international
standard IEC 61158-2 in October 1994,
a suitable transmission technology was bus voltage fieldbus data signal
determined and internationally specified
for the application areas of FOUNDA- 0,75...1,0 VSS
TION fieldbus and PROFIBUS-PA. This
was later integrated into the European
standards as EN 61158-2. 9...32 V

Both systems comply with IEC 61158-2


and operate on the voltage mode with a
transmission speed of 31.25 kBit/s. In this t
way the data packages are modulated
onto the supply voltage for the fieldbus
station and transmitted via a shielded two- Fig. 1 Transmission of data packages to IEC 61158-2
wire cable (see Fig. 1).

These bus physics offer a decisive


advantage: fieldbus communication and
power supply of the bus station can be
implemented using a single cable. These
bus physics lead to enhanced operational
safety and lower costs compared with the
conventional fieldbus solution used up to
this point with its additional wiring effort.

Characteristic features of the IEC 61158-2 transmission physics

Data transmission digital, bit synchronous, Manchester coding

Transmission speed 31.25 kBit/s, voltage mode

Data security preamble, fault protected start and end delimiter

Cable shielded and twisted 2-wire cable

Remote supply of the stations optionally via signal cables

Protection classes intrinsically safe (Ex ia/ib or Ex nL), increased safe (Ex e or Ex nA) and
explosion protected (EEx d/m/p/q)

Topology spur and tree topologies; also in combination

Number of stations up to 32 stations per cable segment

Repeater can be extended with a maximum of 4 repeaters

6 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus Topology
The FOUNDATION fieldbus network is
PC Host-System
1
either
opened directly via a FOUNDATION
fieldbus segment card from the pro-
cess host system and supplied via H1
the TURCK DPC system (diagnostic
power conditioner system) Segment in

(Fig. 2 and 3)
or
enabled via a linking device by high DPC
speed Ethernet (HSE).
PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X

We recommend the use of TURCK multi-


barriers for a FOUNDATION fieldbus Segment out
Junction box
application in the explosion hazardous JBBS-49..-..../-Ex

area (Fig. 3) which can supply up to 32


stations (in the explosion hazardous area)
when cascaded. The benefits compared
to a simple intrinsically safe power supply
device are primarily the enhanced number
of stations within a bus segment. Further-
more, a higher level of security is given by
the enhanced level of availability provided
by the galvanic isolation to all sides in the
barrier (refer to page 33 for more details).

The number of multibarriers, which can be Fig. 2 Topology FOUNDATION fieldbus in the non-explosion hazardous area
switched in, and the usable cable lengths
depend on the output power of the power
conditioner and also on the cable type.
TURCK recommends the long-distance
cable type FBY.../LD (see page 125) for PC Host-System
the main cable (trunk line); for the outputs
the standard cable type FBY.../SD (see
page 124) is recommended.
H1
Both system configurations in Fig. 2 and 3
Segment in
are operated with the TURCK DPC sys-
tem (diagnostic power conditioner sys-
tem, see from page 10 on). Due to the
high output power of the DPC system, DPC
PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X

segments can be extended up to 1900 m.

Segment out

Multibarrier
MBD49-T415/Ex


Trunk in
Zone 1
EEx e EEx e Trunk out
max. 120 m


Zone 0

Fig. 3 Topology FOUNDATION fieldbus in the explosion hazardous area

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 7 /0309
FOUNDATION fieldbus
Basics

In zone 2 a simple but safe energy limita-


tion is necessary. Fig. 4 shows a FOUN- PC Host-System

DATION fieldbus network topology for


zone 2. The power limitation can of cause
be implemented in the power supply, e.g.
with the TURCK-FNICO-Power-Supply.
The advantage is, that working within
zone 2 is possible while the system is
under power. The disadvantages are, the Zone 2
low number of field devices per
FNICO-Power-Supply and a limited seg- FNICO Power Supplies
ment extension of 1000 m maximum.

Due to these disadvantages TURCK rec-


ommends the combination of the power Junction box
JBBS-49..-..../-Ex
conditioner and the TURCK junction
boxes with short circuit protection, also
applicable in zone 2. The trunk line is fed
with explosion protection Ex nA, as the
output of the power conditioner is voltage
limited. The limitation of power in the junc-
tion boxes is implemented such that the
circuits of the drop line are limited accord-
ing to Ex nL. Therefore working at the field
devices during operation is possible and
the segment can be extended up to
1900 m max. (Fig. 5).
Fig. 4 Topology FOUNDATION fieldbus with FNICO power supply in zone 2
A FOUNDATION fieldbus network in
non-Ex and Ex areas can also be estab-
lished via a HSE-H1 link.
HSE stands for High Speed Ethernet
and supports Ethernet fieldbus solutions. PC Host-System
In addition to the Ethernet protocol family,
the HSE also supports the FOUNDATION
fieldbus H1 protocol. As a result, it is
possible to access every Ethernet based H1
network with a transmission speed of
10...1000 MBit/s in H1 fieldbus segments. Segment in

HSE and H1 have been fundamentally


developed as supplementary networks. Power Conditioner
Whereas H1 has been optimized for appli- with voltage limitation

cations in traditional process automation,


HSE is more suited for high performance
process control applications. Attractively- Segment out
priced, commercial standard Ethernet
Junction box
devices can be operated in HSE applica- JBBS-49..-..../-Ex
tions. Trunk Ex nA
Zone 2

The combined H1 and HSE fieldbus solu-


tion enables complete integration of fun- Spurs Ex nL
damental and complex industrial process
instrumentation and measurement into
the higher level control system. This kind
of integrated architecture not only helps
to reduce system downtimes but also
provides improved diagnostic functions
and better user information.

Fig. 5 Topology FOUNDATION fieldbus with power conditioner in zone 2

8 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Overview Application areas of TURCKs fieldbus components in the explosion hazardous and non-explosion hazardous
area 1
Application in Application in Application in Installation Installation
EEx i circuits EEx i circuits Ex nL in in the
conform to FISCO conform to EN 60079-11 circuits Non-Ex
conform to area
EEx ia EEx ia
EEx ib EEx ib
Zone 0 Zone 1 Zone 2 Zone 0 Zone 1 Zone 2 FNICO Entity Zone 0 Zone 1 Zone 2

Junction boxes without


short-circuit protection
JBBS...M.../3G
JBBS...E.../3G
JBBS...T.../3G
Junction boxes with
short-circuit protection
JBBS...SC...M.../3G
JBBS...SC...E.../3G
JBBS...SC...T.../3G
Ex junction boxes without
short-circuit protection
JBBS...M.../Ex
JBBS...E.../Ex
JBBS...T.../Ex
Ex junction boxes with
short-circuit protection
JBBS...SC...M.../Ex
JBBS...SC...E.../Ex
JBBS...SC...T.../Ex
Ex junction boxes for
DIN rail mounting
JRBS...1)
Multibarriers
MBD...2)
Power conditioner system
FISCO power supply
FNICO power supply
Terminating resistors
RS...-TR
Ex terminating resistors
RS...-TR/Ex
Passive equipment
without electronics (cable,
connectors, flanges ...3)

Application:
= allowed
= not allowed

CAUTION
1) Use only permitted when installed in an additional housing (minimum IP54 degree of protection) If previously operated in non-
2) Equipment with differing protection classes only the EEx i outputs have intrinsically safe applications,
intrinsically safe circuits subsequent installation in
3) Taking consideration of the EN 60079-0, EN 60079-11 and EN 60079-14 standards
intrinsically safe applications is
not allowed.

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 9 /0309
FOUNDATION fieldbus
Backplane for the DPC system
DPC-49-4RMB

FOUNDATION fieldbus
Backplane for the DPC system
DPC-49-4RMB
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Host
1 2 3 4
+ S + S + S + S

Segment 1B

Segment 2B

Segment 3B

Segment 4B
Segment 1A

Segment 2A

Segment 3A

Segment 4A
Diagnostic

Err

Pwr A +

+
Pwr B

+ S + S + S + S
1 2 3 4
Case Field Shield
ground

The DPC system (Diagnostic Power Condi- The single components of the system are Module rack for up to 8 power sup-
tioner) is a power supply system for the in- electrically linked via the connection termi- ply modules and 1 diagnostics mo-
stallation of FOUNDATION fieldbus H1 nals of the backplane. From electrical per- dule for the mounting of up to 4 H1
segments.
segments. It provides extensive diagnostic spective, the backplane is to be considered
options for monitoring FOUNDATION passive. Redundant power supply
fieldbus segments and thus supports plant- Removable terminal blocks with
wide asset management. The power can be supplied via two 2-pole screw connections
screw connectors. The connection of the RJ45 connector for HSE fieldbus
A DPC system consists of one or more mo- host system is established per segment via diagnostics
dule racks, each with up to eight DPC-49- removable 3-pole screw terminals.
IPS1 power supply modules and one DPC-
49-ADU resp. DPC-49-DU diagnostics mo- For the connection of the H1 segments to
dule. Up to four H1 segments for each mo- the fieldbus side, each segment is indivi-
dule rack can be operated and monitored dually connected with a removable 3-pole
redundantly in the FOUNDATION fieldbus screw terminal.
network. The diagnostic data of the H1
segment can be transmitted via the HSE The shielding is achieved via insulated
interface module DPC-49-HSEFD/24VDC shield bus or via the 3-pole screw terminal,
to the higher level asset management sys- which is internally connected with the M5
tem (only in conjunction with the diagnos- threaded bolt for equipotential bonding. A
tics module DPC-49-ADU). further M5 threaded bolt for equipontential
bonding is simply connected to the hou-
The module rack consist of a backplane sing.
and the actual rack system for the power
supply modules and the diagnostics mo- For simple diagnostics processing, a con-
dule. nection is provided to the relay alarm con-
tact of the diagnostics module.

10 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Backplane for the DPC system
DPC-49-4RMB

Type DPC-49-4RMB
Ident-No. 6882024
Dimensions

Operational voltage range: 18 32 VDC 113


Overvoltage protection > 250 VDC 220 107

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
RJ45 socket 210
2
Degree of protection IP20
Ambient temperature -20 + 60 C
Housing material aluminium
Housing color black/yellow
Dimensions 220 x 210 x 113 mm
Connection mode snap-on DIN rail (EN 60715)

Accessories
Type code Ident- Short text Dimension drawing
No.
BM-DPC 6882015 blind module for unused slots

118

103

18

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 11 /0309
FOUNDATION fieldbus
Backplane for the DPC system
DPC-49-4RMB/SY

FOUNDATION fieldbus
Backplane for the DPC system
DPC-49-4RMB/SY
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Host A Host B
1 2 3 4 1 2 3 4
+ S + S + S + S + S + S + S + S

Segment 1B

Segment 2B

Segment 3B

Segment 4B
Segment 1A

Segment 2A

Segment 3A

Segment 4A
Diagnostic

Err

Pwr A +

+
Pwr B

+ S + S + S + S
1 2 3 4
Case Field Shield
ground

The DPC system (Diagnostic Power Condi- The single components of the system are Module rack for up to 8 power sup-
tioner) is a power supply system for the in- electrically linked via the connection termi- ply modules and 1 diagnostics mo-
stallation of FOUNDATION fieldbus H1 nals of the backplane. From electrical per- dule for the mounting of up to 4 H1
segments.
segments. It provides extensive diagnostic spective, the backplane is to be considered
options for monitoring FOUNDATION passive. Redundant power supply
fieldbus segments and thus supports plant- Redundant HOST connection
wide asset management. The power can be supplied via two 2-pole
Removable terminal blocks with
screw connectors. The connection to the screw connections
A DPC system consists of one or more mo- host system is provided via two system ca-
dule racks, each with up to eight DPC-49- bles. Premoulded system cables are optio- RJ45 connector for HSE fieldbus
diagnostics
IPS1 power supply modules and one DPC- nally available at TURCK.
49-ADU resp. DPC-49-DU diagnostics mo-
dule. Up to four H1 segments for each mo- For the connection of the H1 segments to
dule rack can be operated and monitored the fieldbus side, each segment is indivi-
redundantly in the FOUNDATION fieldbus dually connected with a removable 3-pole
network. The diagnostic data of the H1 screw terminal.
segment can be transmitted via the HSE
interface module DPC-49-HSEFD/24VDC The shielding is achieved via insulated
to the higher level asset management sy- shield bus or via the 3-pole screw terminal,
stem (only in conjunction with the diagno- which is internally connected with the M5
stics module DPC-49-ADU). threaded bolt for equipotential bonding. A
further M5 threaded bolt for equipontential
The module rack consist of a backplane bonding is simply connected to the hou-
and the actual rack system for the power sing.
supply modules and the diagnostics mo-
dule. For simple diagnostics processing, a con-
nection is provided to the relay alarm con-
tact of the diagnostics module.

12 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Backplane for the DPC system
DPC-49-4RMB/SY

Type DPC-49-4RMB/SY
Ident-No. 6882025
Dimensions

Operational voltage range: 18 32 VDC 113


Overvoltage protection > 250 VDC 220 107

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
RJ45 socket 210
2
Degree of protection IP20
Ambient temperature -20 + 60 C
Housing material aluminium
Housing color black/yellow
Dimensions 220 x 210 x 113 mm
Connection mode snap-on DIN rail (EN 60715)

Accessories
Type code Ident- Short text Dimension drawing
No.
BM-DPC 6882015 blind module for unused slots

118

103

18

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 13 /0309
FOUNDATION fieldbus
Backplane for the DPC system
DPC-49-1RMB

FOUNDATION fieldbus
Backplane for the DPC system
DPC-49-1RMB
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

+
Host
S
+
Field
S

Segment 1A Segment 1B

Err

+
Pwr A

+
Pwr B

Case Shield
ground

The DPC system (Diagnostic Power Condi- The H1 segment is connected separately Module rack for two power supply
tioner) is a power supply system for the in- on the fieldbus side via a removable 3-pole modules to built a H1 segment
stallation of FOUNDATION fieldbus H1 screw terminal. Redundant power supply
segments.
Removable terminal blocks with
The shielding is achieved via insulated screw connections
The module rack consist of a backplane shield bus or via the 3-pole screw terminal,
and the actual rack system for the power which is internally connected with the M5
supply modules. threaded bolt for equipotential bonding. A
further M5 threaded bolt for equipontential
The single components of the system are bonding is simply connected to the hou-
electrically linked via the connection termi- sing.
nals of the backplane.
A connection to the relay alarm contact is
Redundant power supply via two 2-pole provided for redundancy monitoring of the
screw connectors. The connection to the external power supply and the H1 power
host system is established via a removable supply modules.
3-pole screw terminal.

14 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Backplane for the DPC system
DPC-49-1RMB

Type DPC-49-1RMB
Ident-No. 6882026
Dimensions

113
Operational voltage range: 18 32 VDC
42 107
Overvoltage protection > 250 VDC

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
2
Degree of protection IP20
210
Ambient temperature -20 + 60 C
Housing material aluminium
Housing color black/yellow
Dimensions 220 x 210 x 113 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 15 /0309
FOUNDATION fieldbus
Power supply module
DPC-49-IPS1

FOUNDATION fieldbus
Power supply module
DPC-49-IPS1
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

ON Load Com Fault


Segment out Host
YE YE YE RD

Diagnostics

Pwr
Power
GN

The DPC system (Diagnostic Power Condi- performance. Supply of one FOUNDATION field-
tioner) is a power supply system for the in- If two power supply modules are con- bus H1 segment
stallation of FOUNDATION fieldbus H1 nected, the segment can be operated red- Output current: 800 mA
segments. It provides extensive diagnostic undantly. Thereby the modules can be
Output voltage: 2830 VDC
options for monitoring FOUNDATION plugged and unplugged during operation
fieldbus segments and thus supports plant- (Hot swap-able in run). Local diagnostics via LEDs
wide asset management. Complete galvanic isolation
Due to complete galvanic isolation,
A DPC system consists of one or more mo- H1 to H1,
dule racks, each with up to eight DPC-49- H1 to internal supply,
IPS1 power supply modules and one DPC- H1 to the diagnostic module ,
49-ADU resp. DPC-49-DU diagnostics mo- H1 to HSE diagnostic bus,
dules . Up to four H1 segments for each formation of parasitic voltages is avoided
module rack can be operated and moni- and error-free communication is guaran-
tored redundantly in the FOUNDATION teed.
fieldbus network. The diagnostic data of the
H1 segment can be transmitted via the Local comissioning and diagnostics are
HSE interface module DPC-49-HSEFD/ supported by the following LED indications:
24VDC to the higher level asset manage-
ment system (only in conjunction with the Pwr: green: Operational readiness
diagnostics module DPC-49-ADU). ON/OFF: yellow: Output ON:
Load: yellow: Consumer (field device) detec-
The power supply module provides up to ted at segment:
30 VDC and 800 mA for the installation of a Com: yellow: Communication display
H1 segment. The network topology can be Fault: red: Short-circuit message
extended to 1900 m, due to the high output

16 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Power supply module
DPC-49-IPS1

Type DPC-49-IPS1
Ident-No. 6882023
Dimensions

Supply voltage via the backplane


Current consumption 0.8 1.7 A
Test voltage complete galvanic isolation, test voltage 500
VAC

Output circuits Field


2
Output current 800 mA 118

Output voltage > 28 VDC


Short-circuit protection 850 mA
Efficiency 80 %
Output circuits HOST 103
Output current < 30 mA
Output voltage 27 VDC 18

Indication
Operational readiness 1 x green
Output active 1 x yellow
Output current 1 x yellow
Short-circuit message 1 x red
Bus communication 1 x yellow

Degree of protection IP20


Ambient temperature -20 + 60 C
Relative humidity 95% at 55 C acc. to EN 60069-2
Housing material plastic
flammability class V-0 to UL 96
Housing color yellow
Dimensions 18 x 118 x 103 mm

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 17 /0309
FOUNDATION fieldbus
Diagnostic module
DPC-49-DU

FOUNDATION fieldbus
Diagnostic module
DPC-49-DU
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

The DPC system (Diagnostic Power Condi- interface module DPC-49-HSEFD/24VDC


tioner) is a power supply system for the in- to the higher level Asset Management sys- Redundancy monitoring of 4 H1
stallation of FOUNDATION fieldbus H1 tem (only in conjunction with the diagnos- segments.
segments. It provides extensive diagnostic tics module DPC-49-ADU). Local diagnostics via LEDs
options for monitoring FOUNDATION
Alarm signal via relay contact
fieldbus segments and thus supports plant-The DPC-49-DU monitors the external
wide asset management. power supply at the module rack, the Complete galvanic isolation
FOUNDATION fieldbus-H1 power mo-
A DPC system consists of one or more mo- dules and their redundant operation mode.
dule racks, each with up to eight DPC-49- The diagnostic function can be switched off
IPS1 power supply modules and one DPC- separately for each segment.
49-ADU or DPC-49-DU diagnostic modules
. Up to four H1 segments per module rack The device features three LEDs indicating
can be operated and monitored redun- the operating status. Alarm messages are
dantly in the FOUNDATION fieldbus net- indicated by a red LED. Alarm signals are
work. The diagnostic data of the H1 also output via a relay contact.
segment can be transmitted via the HSE

18 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Diagnostic module
DPC-49-DU

Type DPC-49-DU
Ident-No. 6882021
Dimensions

Supply voltage via the backplane


Current consumption < 100 mA
Test voltage complete galvanic isolation, test voltage 500
VAC

Diagnostics 1 x relay
2
Switching current 1000 mA 118

Switching voltage 30 VDC


galvanically isolated from other electronic de-
vices
103
Operational readiness 2 x green
Alarm 1 x red 18

Degree of protection IP20


Ambient temperature -20 + 60 C
Housing material plastic
flammability class V-0 to UL 96
Housing color yellow
Dimensions 18 x 118 x 103 mm

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 19 /0309
FOUNDATION fieldbus
Diagnostic module
DPC-49-ADU

FOUNDATION fieldbus
Diagnostic module
DPC-49-ADU
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

HSE
Host

H1

DPC-49-HSEFD/24VDC

DPC

Segment 1...4

The DPC system (Diagnostic Power Condi- The diagnostics module DPC-49-ADU is Long-term diagnostics for 4 H1 seg-
tioner) is a power supply system for the in- used as a diagnostic interface between H1 ments
stallation of FOUNDATION fieldbus H1 segments and the HSE interface module. Local diagnostics via LEDs
segments. It provides extensive diagnostic The diagnostics module monitors the elec-
Alarm signal via relay contact
options for monitoring FOUNDATION trical and the communication parameters of
fieldbus segments and thus supports plant- the H1 segments. Operation without dia- Complete galvanic isolation
wide asset management. gnostics module is possible.

A DPC system consists of one or more mo- The diagnostic information is collected in
dule racks, each with up to eight DPC-49- the device and transmitted via the HSE in-
IPS1 power supply modules and one DPC- terface module to the higher fieldbus level
49-ADU resp. DPC-49-DU diagnostics mo- (e.g. the host) as diagnostic and alarm data.
dules . Up to four H1 segments for each Thereby the modules can be plugged and
module rack can be operated and moni- unplugged during operation (Hot swap-able
tored redundantly in the FOUNDATION in run).
fieldbus network. The diagnostic data of the
H1 segment can be transmitted via the The device features LEDs indicating the
HSE interface module DPC-49-HSEFD/ operating status of the H1 segments. A pre-
24VDC to the higher level asset manage- alarm is indicated by a yellow LED, the main
ment system (only in conjunction with the alarm by a red LED. Additionally, alarm si-
diagnostics module DPC-49-ADU). gnals can be analysed via a relay contact.

20 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Diagnostic module
DPC-49-ADU

Type DPC-49-ADU
Ident-No. 6882012
Dimensions

Supply voltage via the backplane


Current consumption < 100 mA
Test voltage complete galvanic isolation, test voltage 500
VAC

Diagnostics 1 x relay
2
Switching current 1000 mA 118

Switching voltage 30 VDC


galvanically isolated against other electronic
parts .
103
Operational readiness 1 x green / red
Alarm 4 x yellow / red 18

Degree of protection IP20


Ambient temperature -20 + 60 C
Housing material plastic
flammability class V-0 to UL 96
Housing color yellow
Dimensions 18 x 118 x 103 mm

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 21 /0309
FOUNDATION fieldbus
HSE field device
DPC-49-HSEFD/24VDC

FOUNDATION fieldbus
HSE field device
DPC-49-HSEFD/24VDC
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

HSE
Host

H1

DPC-49-HSEFD/24VDC

DPC

Segment 1...4

The DPC system (Diagnostic Power Condi- nostics data of the DPC-49-ADU are trans- HSE interface device for transmissi-
tioner) is a power supply system for the in- mitted via the HSE interface module but not on of diagnostics data
stallation of FOUNDATION fieldbus H1 the process data of the H1 segments. Each FOUNDATION fieldbus function
segments. It provides extensive diagnostic diagnostics module monitors up to four H1 blocks for remote diagnostics
options for monitoring FOUNDATION segments. Local diagnostics via LEDs
fieldbus segments and thus supports plant-
wide asset management. As a FOUNDATION fieldbus device the Long-term diagnostics for 16 H1
segments
HSE interface module features a resource
A DPC system consists of one or more mo- and transducer block as well as several Complete galvanic isolation
dule racks, each with up to eight DPC-49- standard function blocks. On the basis of
IPS1 power supply modules and one DPC- these standard function blocks, suitable ap-
49-ADU resp. DPC-49-DU diagnostics mo- plications can be programmed in the con-
dules . Up to four H1 segments for each trol system for the analysis of diagnostic
module rack can be operated and moni- data.
tored redundantly in the FOUNDATION
fieldbus network. The diagnostic data of the Features
H1 segment can be transmitted via the HSE interface device for transmission of
HSE interface module DPC-49-HSEFD/ diagnostic data
24VDC to the higher level asset manage- FOUNDATION fieldbus function blocks
ment system (only in conjunction with the for remote diagnostics
diagnostics module DPC-49-ADU). Local diagnostics via LEDs

Long-term diagnostics for 4 H1 seg-


The diagnostic data of up to 16 H1 seg-
ments
ments are transmitted by the HSE interface
complete galvanic isolation
module DPC-49-HSEFD/24VDC via the
FOUNDATION fieldbus-HSE to the higher
level asset management system. Only diag-

22 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
HSE field device
DPC-49-HSEFD/24VDC

Type DPC-49-HSEFD/24VDC
Ident-No. 6882014
Dimensions
47
21
Supply voltage via the backplane

DIAG/ACT
LNK/ACT
Current consumption < 100 mA

Pwr 1
Pwr 2
GW
+ +
Pwr 1 Pwr 2
52,5
Test voltage complete galvanic isolation, test voltage 500
DPC-49-HSEFD/24VDC
VAC FOUNDATION fieldbusTM
45466 Mlheim an der Ruhr
105

2
Germany

Diagnostic Ethernet

Indication
Operational readiness 2 x green 32 31
State/ Fault 1 x yellow / red 107
176

Bus communication 1 x green / yellow


Int. communication (CAN) 1 x yellow / red

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
RJ45 connector

Degree of protection IP20


Ambient temperature -20 + 60 C
Housing material aluminium
Housing color black/yellow
Dimensions 176 x 105 x 31 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 23 /0309
FOUNDATION fieldbus
Power conditioner, dual channel
RPC49-205

FOUNDATION fieldbus
Power conditioner, dual channel
RPC49-205
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

+
Monitor 1 Power A
GN

+
Monitor 2 Power B
GN

Term. 1 Reset 1
+
+
I > 0,5A
GN RD
Segment 1 Out Segment 1 In
S1 S1
Term. 2 Reset 2 Shield
+
+
I > 0,5A
GN RD
Segment 2 Out Segment 2 In
S2 S2
Shield

The RPC49-205 provides two segments for The two green LEDs indicate power ON. Supply of 2 H1-segments, connec-
the installation of a FOUNDATION The green active LEDs also indicate power tion via removable screw terminals
fieldbus network. In combination with the ON. The two short-circuit protected outputs Aluminium rail housing
PSU-3214, each segment provides up to of the power conditioner switch off the
Degree of protection IP20
500 mA with an output voltage of at least output in case of overload (I > 500 mA). The
27.5 V. The output voltage depends on the switch-off state is indicated by a red LED for Connection of the housing potential
output current. each segment. The overload protection for via an M5 x 1 bolt
the correspondent segment can be reset Monitor function
The conditioner can be supplied redun- with two reset buttons.
LEDs for indication of the operating
dantly by two supply devices, whereby status
"POWER A" is the primary input. As long as Hardware diagnostics is provided via the
no redundant voltage supply is available , monitor terminals. The power conditioner is 2 x 500 mA output current
the voltage supply should be connected to equipped with an optional terminating resi- Redundant power supply
"POWER B". Should the voltage at stor for the bus. Short-circuit protected outputs
"POWER A" drop below 20 V, input
"POWER B" is energized.

24 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Power conditioner, dual channel
RPC49-205

Type RPC49-205
Ident-No. 6603801
Dimensions

Operational voltage range: 21 32 VDC

er
A ow
P
ve
cti

05
A

-2
49
C
r
P
uh
Overvoltage protection > 36 VDC

R
rR
A

de
r

an
ito

er
eim
on

w
M

ve B
lh

Po
M
66
54

cti
-4

A
D
A
P

K
er

C
R
ow
+

TU
Current consumption 535 mA (1 x 500 mA Iout)

et
es

1
R
en
In
t1
gm +
Se 1

.
rm
S

off
Te

on
en
1043 mA (2 x 500 mA Iout)

In

1
t2

2
gm +
Se 2

et
S

es

2
R
30

ld
ie
2

Sh
Voltage drop 4.4 V

S1

ld
ie
S1

Sh
182
Output circuits
75
Output current 500 mA
Output voltage Uout = Pwr - [2 V + (Iout x 4.4 Ohm)]
Short-circuit protection 500 mA

Diagnostics 2 x solid state relay Segment (in/out):


Switching current 700 mA
Switching voltage 400 VDC
galvanically isolated against other electronic S2 + S1 + + S2 + S1
Segment 2 In Segment 1 In Segment 2 Out Segment 1 Out
parts .

Indication
Operational readiness 2 x green
Output active 2 x green
power/monitor
Short-circuit message 2 x red

Electrical connection 8 x 3-pole removable terminal blocks, screw + +


Power A Monitor A Power B Monitor B
connection
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20 Voltage dip/ load current


Ambient temperature -20 + 70 C
UV [V]
Relative humidity 95 %, non condensing 5
Housing material aluminium
Housing color black/yellow 4

Dimensions 182 x 75 x 30 mm 3
Connection mode snap-on DIN rail (EN 60715)
2

0
0 0,1 0,2 0,3 0,4 0,5 IL [A]

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 25 /0309
Power supply
single-channel
PSU-3214

Power supply
single-channel
PSU-3214
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

+
94...265 VAC 32 VDC

GN

The power supply unit PSU-3214 supplies Depending on the output current, the Output voltage 32 VDC
a power conditioner. fieldbus segment is supplied with an output Output current 1.4 A
voltage of approx. 29 V which is provided in
The device provides safety extra-low combination with the TURCK power condi- Safety extra low voltage SELV ac-
cording to IEC/EN 60950
voltage (SELV) according to IEC/EN 60950. tioner RPC49-205.
It features protection class II and corre- Universal operating voltage
sponds to EMC class B. Cable lengths of upto 1900 m in the Ex area (94264 VAC)
can be achieved with the TURCK multibar-
The output volgate is 32 VDC with a ma- rier MBD49-T415/Ex in combination with
ximum output current of 1.4 A. The over- the power conditioner.
load protection is activated if the current
exceeds 1.6 A. The green LED indicates operational readi-
ness.

26 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Power supply
single-channel
PSU-3214

Type PSU-3214
Ident-No. 7545024
Dimensions

Operational voltage range: 94 265 VAC


Frequency 47 63 Hz
Current consumption 0.6 A at 230 V AC / 1.1 A at 120 V AC
Starting current inrush I2t < 2.8 A2s
Test voltage Input circuit to output circuit and supply
voltage for 250 Veff; test voltage 3 kVeff 72
2
L1
N
NETZ
LINE

Output circuits
Output current 1400 mA PSU
-32
14

Output voltage 32 VDC ( 3 %) 32V


er A
Pow / 1,4
SGAN
AUTPUT
G

OU

Residual ripple 50 mVss +

Short-circuit protection 1600 mA 105


Efficiency 89 % 45
Derating 2.5 %/K ( starting form +60C)

Indication
Operational readiness 1 x green
Output curve
Electrical connection flat terminals with self-lifting pressure plates
Terminal cross-section 1 x 2.5 mm2 / 2 x 2.5 mm2 V

Degree of protection IP20 35


Ambient temperature -10 + 70 C 30
Housing material plastic 25
Housing color blue 20
Dimensions 45 x 72 x 105 mm 15
Connection mode snap-on DIN rail (EN 60715)
10
5
0
0 0,4 0,8 1,2 1,6 2,0 A

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 27 /0309
FOUNDATION fieldbus
FISCO Power Supply
RPC49-10120EX

FOUNDATION fieldbus
FISCO Power Supply
RPC49-10120EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

+7 4
S1
IS fieldbus S 8 5 S Host fieldbus

9 6+

S2

1+

2 Power

3+

The intrinsically safe power supply RPC49- designed to exploit the very latest develop- FISCO compliant according to IEC
10120EX transmitts the fieldbus signal from ments of the FISCO specification (Fieldbus TS 60079-27
a host to an intrinsically safe fieldbus device Intrinsically Safe Concept) concerning the Protection type: [EEx ib] IIC
in the Ex area, zone 2. application in explosion hazardous areas.
Mounting possible in zone 2
To reap the full potential of digital fieldbus
The RPC49-10120EX enables integrated communication without system inherent FISCO power supply for FOUNDATI-
transmission between the host and fieldbus constrains is thus possible. ONfieldbus
connections and thus allows parallel con- Output current: 120 mA
nection of several devices in the fieldbus The excellent performance and flexibility of
Fieldbus - Repeater
and accordingly a higher number of field the RPC49-10120EX makes it easy to plan,
devices in the segment. install and mount fieldbus networks in com- Temperature range: -40 +70C
pliance with the 31.25 kbits/s physical layer
Designed to operate in harsh environments specification. Moreover, compatibility with
and suitable for installation in zone 2, the the TURCK wiring components and acces-
TURCK power supply RPC49-10120EX ex- sories ensures high reliability, low installation
pands the boundaries for fieldbus topolo- costs and high operational safety.
gies.
Power supply to the host is procured via a
The RPC49-10120EX provides upto 120 switch making additional power sources
mA, powering field devices in Gas Group redundant.
IIC. The device is mounted on DIN rail. It is

28 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
FISCO Power Supply
RPC49-10120EX

Type RPC49-10120EX
Ident-No. 6604157
Dimensions
42 137,5
Operational voltage range: 19.2 30 VDC
Current consumption 235 mA (typ.) 330 mA (max.) at 20 V
190 mA (typ.) 265 mA (max.) at 24 V
155 mA (typ.) 215 mA (max.) at 30 V
Test voltage Input circuit to output circuit and supply
voltage for 250 Veff
166 152,6 117 146

2
Output circuits
Output current 120 mA
Output voltage 12.4 VDC
Short-circuit protection 140 mA

Indication
Operational readiness 1 x green
Short-circuit message 1 x red
Bus communication 2 x yellow

Ex approval acc. to conformity certificate BASEEFA 05 ATEX 0127


FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 14 V
Max. output current Io 180 mA
Max. output power Po 2520 mW
External inductance/capacitance Lo/Co 300 H / 0.2 F
Device designation II (2) GD [EEx ib] IIC
II 3 G EEx nA II T4 X
FISCO Power Supply

Electrical connection 3 x 3-pole removable terminal blocks, reverse


polarity protected, screw connection or tension
spring
Terminal cross-section 2.5 mm2

Degree of protection IP20


Ambient temperature -40 + 70 C
Housing material plastic
Housing color black/yellow
Dimensions 42 x 166 x 137.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 29 /0309
FOUNDATION fieldbus
FISCO Power Supply
RPC49-10265EX

FOUNDATION fieldbus
FISCO Power Supply
RPC49-10265EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

+7 4
S1
IS fieldbus S 8 5 S Host fieldbus

9 6+

S2

1+

2 Power

3+

The RPC49-10265EX transmitts the latest developments of the FISCO specifica- FISCO compliant according to IEC
fieldbus signal from a host to an intrinsically tion (Fieldbus Intrinsically Safe Concept) TS 60079-27
safe fieldbus device in the Ex area, zone 2. concerning the application in explosion ha- Protection type: [EEx ib] IIB
zardous areas. To reap the full potential of
Mounting possible in zone 2
The RPC49-10265EX enables integrated digital fieldbus communication without sy-
transmission between the host and fieldbus stem inherent constrains is thus possible. FISCO power supply for FOUNDATI-
connections and thus allows parallel con- ON fieldbus
nection of several devices in the fieldbus The excellent performance and flexibility of Output current: 265 mA
and accordingly a higher number of field the RPC49-10265EX makes it easy to plan,
Fieldbus - Repeater
devices in the segment. install and mount fieldbus networks in com-
pliance with the 31.25 kbits/s physical layer Temperature range: -40 +70C
Designed to operate in harsh environments specification. Moreover, compatibility with
and suitable for installation in zone 2, the the TURCK wiring components and acces-
TURCK power supply RPC49-10265EX ex- sories ensures high reliability, low installation
pands the boundaries for fieldbus topolo- costs and high operational safety.
gies.
Power supply to the host is procured via a
The RPC49-10265EX provides up to 265 switch making additional power sources
mA, powering field devices in the Ex area of redundant.
the Gas Group IIB. The device is mounted
on DIN rail. It is designed to exploit the very

30 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
FISCO Power Supply
RPC49-10265EX

Type RPC49-10265EX
Ident-No. 6604158
Dimensions
42 137,5
Operational voltage range: 19.2 30 VDC
Current consumption 380 mA (typ.) 495 mA (max.) at 20 V
315 mA (typ.) 410 mA (max.) at 24 V
255 mA (typ.) 330 mA (max.) at 30 V
Test voltage Input circuit to output circuit and supply
voltage for 250 Veff
166 152,6 117 146

2
Output circuits
Output current 265 mA
Output voltage 13.1 VDC
Short-circuit protection 285 mA

Indication
Operational readiness 1 x green
Short-circuit message 1 x red
Bus communication 2 x yellow

Ex approval acc. to conformity certificate BASEEFA 05 ATEX 0127


FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 14.8 V


Max. output current Io 359 mA
Max. output power Po 5310 mW
External inductance/capacitance Lo/Co 550 H / 0.5 F
Device designation II (2) GD [EEx ib] IIB
II 3 G EEx nA II T4 X
FISCO Power Supply

Electrical connection 3 x 3-pole removable terminal blocks, reverse


polarity protected, screw connection or tension
spring
Terminal cross-section 2.5 mm2

Degree of protection IP20


Ambient temperature -40 + 70 C
Housing material plastic
Housing color black/yellow
Dimensions 42 x 166 x 137.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 31 /0309
FOUNDATION fieldbus

32 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Multibarrier MBD49-T415/Ex
Basics and application benefits

The operating principle of the MBD49- Intrinsic safety and galvanic isolation Functions which supplement the
T415/Ex multibarrier is physically based between all outputs standard
on IEC 61158-2. The use of multibarriers For safety reasons, galvanic isolation of FISCO conformity
increases the number of fieldbus stations signals plays a decisive role in the Ex area. The FISCO model has been developed
in the FOUNDATION fieldbus network to The multibarrier provides four intrinsically for the supply of power to fieldbus
a maximum of 32 field devices. safe and galvanically isolated outputs. The stations in the Ex area by the PTB in
complete galvanic isolation exists between cooperation with renowned
This high number of stations is achieved the main bus cable (trunk line) and the out- manufacturers. FISCO stands for
by enhanced safety of the fieldbus supply put circuits as well as between all of the Fieldbus Intrinsically Safe Concept.
which can be looped through from multi- four individual output circuits. It is intended to simplify the verification
barrier to multibarrier. The fieldbus stations of intrinsic safety of fieldbus systems.
in zone 0 are supplied with power via Galvanic isolation of intrinsically safe cir- Intrinsically safe networks can be
the four intrinsically safe outputs of each
multibarrier device.
cuits, as demanded by the industry,
in particular for zone 0, is thus provided.
configured without highly complex
calculations, and also expanded and
3
operated without system certification.
User benefits Potential transfers and potential equaliza- The outputs of the multibarrier are
The user can expect substantial cost ad- tion currents are thus reduced and safe conform to the demands of an Ex
vantages due to the possibility of cascad- data transmission is guaranteed. current supply and also conform to
ing the multibarriers in a single segment FISCO.
in the explosion hazardous area, thus fully Operational safety
exploiting the entire function range of the Operational safety of the bus system must Switch-in terminating resistors
bus systems. be guaranteed should a bus station fail Data transmission on bus cables is
or malfunction. The four outputs of the frequently influenced by signal reflection,
All fieldbus devices can be operated in multibarrier each supply an output current which can occur when the bus ends are
a single fieldbus segment in the explo- of max. 40 mA. not terminated. The fieldbus must be
sion hazard area. Thus, the costs for an provided with a terminating resistor at
additional bus coupler or a segment card If a short-circuit occurs on a fieldbus sta- both ends in order to avoid signal
as well as their integration and parameter tion, the integrated short-circuit protection reflection. The multibarrier is provided
definition are eliminated. An additional comes into play. Only the affected output with an integrated terminating resistor,
trunk line and the wiring material is also will be shut down, the main line and the which should be activated, when the
spared. other outputs of the fieldbus segment multibarrier is connected as the last
remain operational. The short-circuit is device on the main bus line (trunk line).
The supply of power to the multibarriers indicated for each channel by a red LED
is implemented via the bus which means inside the housing. Climatic compensation
that an additional power cable is not In regions subject to large temperature
required. Industrially suitable housing and air-humidity variations, it is possible
Industrial environmental conditions are fre- that formation of condensation or a
Installation in the explosion hazar- quently harsh and aggressive. Therefore, build-up of water within the housing is
dous area a housing suitable for these conditions is possible during operation. In order to
The area of application to ATEX is necessary. The enhanced IP66 degree of avoid this, the multibarrier is fitted on
II 2 (1 GD) G EEx m e [ia] IIC T4. protection and the special housing mate- the cable connection end with a
rial (die-cast aluminium) in conjunction pressure equalization element to avoid
Due to its EEx e protection rating, the with the encapsulated module electronics the build-up of condensation.
MBD49-T415/Ex multibarrier can be meet these demands and provide a high The pressure equalisation element
installed in zone 1 (II 2 G) according to level of operational safety. Direct installa- features IP67 degree of protection and
94/9/EC (ATEX 95a). tion of a multibarrier in the system is thus guarantees continuous and reliable
unproblematic. ventilation and venting of the
Use in explosion hazardous areas with multibarriers. The ePTFE diaphragm in
explosion protection group IIC in con- The EEx e cable glands guarantee safe the centre of the gland features a very
junction with temperature class T4 is the and quick connection technology in high water ingress pressure and repels
standard in the process industry. conjunction with the high-quality cage oil. Even 100 % of salt crystals are kept
clamps. out.
Within zone 1, the MBD49-T415/Ex is
connected via a cable and connections Shield terminals are capacitively connec-
with enhanced safety (EEx e) to the main ted to the housing potential in order to
line (trunk line) of a fieldbus conform to divert possible interference voltages on
IEC 61158-2. This offers the advantage the cable shield. The riveted ground bolt
that the connection to the bus can be connects the housing to the main poten-
implemented using a loop isolator without tial equalization.
EX approval, but with a sufficiently high
capacity.

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 33 /0309
FOUNDATION fieldbus
Multibarrier, 4-port
MBD49-T415/EX

FOUNDATION fieldbus
multibarrier, 4-channel
MBD49-T415/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

+
1
S RD
3,3 nF
+ +
2 Trunk In
S RD
S
3,3 nF
+ S1
3 +
S RD Trunk Out
3,3 nF S
1,5 nF
+
4
S RD
3,3 nF

The 4-port multibarrier MBD49-T415/EX The multibarrier is equipped with an selec- Entity and FISCO compliant accor-
enables the connection of a large number of table bus terminating resistor. This switch is ding to IEC TS 60079-27
field devices to one fieldbus in the Ex-area, integrated in the housing on the board. Galvanic isolation between the EEx i
according to IEC 61158-2. outputs and the EEx e bus line, as
The multibarrier is equipped with four LEDs well as between the EEx i outputs
The number of field devices to be con- located on the printed circuit board inside Powder-coated die-cast aluminium
nected to the multibarrier depends on the the housing to provide short-circuit indica- housing
current consumption of the individual de- tions separately for each channel. Pressure compensation element for
vices. Up to 32 EEx i field devices can be protection against condensation
connected to the bus. The number of Because of complete galvanic isolation of water
slaves can be extended by the EEx e the Connection of the housing potential
fieldbus supply which can be looped trunk line to EEx i outputs and between via an M5 x 1 bolt
through from multibarrier to multibarrier. the
Temperature range: -20+70 C
EEx i outputs, (-4+158 F)
Inputs and outputs of the trunk line feature safe operation is guaranteed.
increased safety protection (EEx e) and the Integrated terminating resistor
(switch-in)
outputs to the field devices are intrinsically
safe (EEx i). Cable shielding: capacitive connec-
tion to housing potential
Output data: 10 V/40 mA (short-cir-
cuit proof)

34 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Multibarrier, 4-port
MBD49-T415/EX

Type MBD49-T415/EX
Ident-No. 6611247
Dimensions
260 90
Fieldbus standard IEC 61158-2

Operational voltage range: 16 32 VDC


Current self-consumption 40 mA 160

Test voltage input circuits (EEx e) to output circuits (EEx i)


for 253 Veff; output circuits (EEx i) to each other
for 60 Veff

Output circuits
Output current 40 mA
Output voltage
Short-circuit protection
10 VDC
45 mA
Trunk line 3
Indication
Short-circuit message 4 x red SS ++
EEx e
Ex approval acc. to conformity certificate PTB 04 ATEX 2021
Max.output voltage Uo 14.3 V
Max. output current Io 268 mA
Max. output power Po 958 mW Outputs
Internal resistance Ri 53.3
S1 S2 S3 S4
External inductance/capacitance Li/Ci negligible
Characteristic Linear
Device designation II 2(1 G/D)G EEx m e [ia] IIC T4 +S +S +S +S
FISCO / Entity multibarrier EEx i

Electrical connection cable glands


Segment IN 1 x M20 x 1.5 ( 1014 mm); plastic; black
Current consumption
Segment OUT 1 x M20 x 1.5 ( 1014 mm); plastic; black
Drop line 4 x M20 x 1.5 ( 59 mm); plastic; blue
mA
Terminal cross-section 2.5 mm2
300
Earthing bolt M5 x 1
250
Imax
Degree of protection IP66 200
Ambient temperature -20 + 70 C 150
Relative humidity 95 %, non condensing 100
Housing material powder-coated die-cast aluminium
50 Imin
Housing color black/yellow
0
Dimensions 260 x 160 x 90 mm 16 18 20 22 24 26 28 30 32 V
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 35 /0309
FOUNDATION fieldbus
Fieldbus display, 3-port
FD-49-T317/EX

FOUNDATION fieldbus
Fieldbus display, 3-channel
FD-49-T317/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

The 3-port digital indicator FD-49-T317/EX Apart from a measuring value indicator, the
displays the process information of the display contains a 41-segment bargraph for Entity and FISCO compliant accor-
fieldbus nodes of a FOUNDATION trend monitoring, which can be scaled ding to IEC TS 60079-27
fieldbus network. separately from the display value. Digital fieldbus display for the indi-
cation of process values
The device (listener) receives and displays The FD-49-T317/EX performs as a "li- Powder-coated die-cast aluminium
the values of the adjusted fieldbus stener", i.e. initialization by the host is not housing
addresses. Parameterization is code word required (integration via software redundant)
Connection of the housing potential
protected and implemented via a keypad and does not appear in the network as a via external earthing
on the front side. Adjustements can be node with an own address.
done for each port separately. The process
value of the actuator/sensor is displayed as The device is supplied with energy by the
a 5-digit number and the process value fieldbus (10 mA) and can be applied in Ex
status is displayed via limit value markers. areas up to temperatures of the class T6.

36 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Fieldbus display, 3-port
FD-49-T317/EX

Type FD-49-T317/EX
Ident-No. 6901312
Dimensions

Fieldbus standard IEC 61158-2

Operational voltage range: 9 30 VDC 125 140

Current self-consumption 10 mA

Indication
Display LCD, 5-digit, 7-segment 103
140
71

Ex approval acc. to conformity certificate TV 07 ATEX 553588


Max. input voltage Ui 30 V
Max. input current Ii
Max. input power Pi
660 mA
1600 mW
3
External inductance/capacitance Li/Ci negligible
Device designation II 2(1) G EEx ia IIC T6 bzw. T5
II 2 D IP65 T70C
FISCO / Entity field device

Electrical connection cable glands


Terminal cross-section 2.5 mm2

Degree of protection IP66


Ambient temperature -10 + 60 C
Housing material powder-coated die-cast aluminium
Housing color black
Dimensions 140 x 140 x 71 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 37 /0309
FOUNDATION fieldbus

38 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
Junctions by TURCK

TURCK offers junctions in various designs IP67 T-pieces and junction boxes with IP20 junction boxes with or without
for the distribution of energy and data. or without short-circuit protection short-circuit protection
(1, 4 and 6 ports) (4 , 6, 8 and 12 ports)
The junctions differ in the number of ports, Explosion-protected junctions (for use Suitable for the explosion hazardous
the housing style and special features in zone 1 or 2, distribution of EEx ia and the safe area
such as integrated short-circuit protection, signals in zone 0) For use in zone 1 or 2, distribution of
switch-in terminating resistor and selec- Standard junctions (non-Ex) EEx ia signals in zone 0
table shielding concept. IP67 degree of protection IP20 degree of protection
Switch-in terminating resistor Switch-in terminating resistor
The following junctions are available as Selectable shielding concept Selectable shielding concept
standard versions. (hard-wired or capacitive grounding) (hard-wired or capacitive grounding)
Special solutions are available on request. Active and passive types Active and passive types
Pressure compensation element to Housing material: aluminium
prevent water condensation Connection technology:
Housing material: powder-coated cage-clamp terminals or removable
die-cast aluminium screw terminals
(4 and 6-port type) Temperature range: -40C ...+70C
Connection technology: stainless steel
flange connectors 7/8, M12 or cage-
clamp terminals
4
Cable glands: plastic, stainless steel,
nickel-plated brass, EMC
Temperature range: -25C ... +70C

CAUTION
Explosion Danger!
The EC type test examina-
tion certificate and the
manufacturers declaration
of conformity must be
observed.
It is essential that the
special conditions in
the EU type test certificate
are observed.

Junction boxes, which have


been used in non intrinsically
safe applications, may not
be used in intrinsically safe
applications subsequently.

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 39 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


T-piece
RSV-2RKV49

Version: 7/8 connector


4-pole, T-piece, stainless steel cou-
pling nut
For use in FOUNDATION Fieldbus
73,0 7/8-16UN applications
37,4 28,0

17,5
FOUNDATION fieldbus connection
34,8
26,0
7/8-16UN
7/8-16UN
1=
26,0 1 3 2=+
2 4 3 = shield
4 = n.c.

Type RSV-2RKV49
Ident-No. 6602319

Junction box T adapter, 7/8'' v


Polarity 4-pole 1=
Grip plastic, PUR, yellow 3 1 2=+
4 2 3 = shield
4 = n.c.
Connector female connector, 2x, 7/8", straight
Grip plastic, PUR, yellow
Contact carriers plastic, PUR, black
Contacts metal, CuZn, gold-plated
Coupling nut/screw stainless steel, 1.4404 Wiring diagram
Seal plastic
Degree of protection IP67, only with screws tightened
1 1
Mechanical lifespan min. 100 Contact durability
Pollution degree 3/2 2
2
Connector Connector, 1x, 7/8", straight 3 3
Grip plastic, PUR, yellow
Contact carriers plastic, PUR, black 4 4
Contacts metal, CuZn, gold-plated
Coupling nut/screw stainless steel, 1.4404
Degree of protection IP67, only when plugged in
Mechanical lifespan min. 100 Contact durability
Pollution degree 3/2 1 2 3 4

Rated voltage max. 250 V


Ampacity 4A
Forward resistance 5 m
Insulation resistance 109
Ambient temperature junction -40 + 80 C

40 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


T-piece
RSCV-2RKCV49

Version: M12 connector


4-pole, T-piece, stainless steel cou-
pling nut
For use in FOUNDATION fieldbus
54,9 applications
23,5

FOUNDATION fieldbus connection


M12 x 1 M12 x 1

M12 x 1
2 1=
2=+
3 1 3 = shield
4 4 = n.c.

Type RSCV-2RKCV49
Ident-No. 6603431
4
Junction box T adapter, M12 x 1 v
Polarity 4-pole 2 1=
Grip plastic, PUR, yellow 2=+
1 3 3 = shield
4 4 = n.c.
Connector female connector, 2x, M12 x 1, straight
Grip plastic, PUR, yellow
Contact carriers plastic, PA 6, black
Contacts metal, CuZn, gold-plated
Coupling nut/screw stainless steel, 1.4404 Wiring diagram
Seal plastic
Degree of protection IP67, only with screws tightened
1 1
Mechanical lifespan min. 100 Contact durability
Pollution degree 3/2 2 2

Connector Connector, 1x, M12 x 1, straight 3 3


Grip plastic, PUR, yellow
Contact carriers plastic, PA, black 4 4
Contacts metal, CuZn, gold-plated
Coupling nut/screw stainless steel, 1.4404
Degree of protection IP67, only when plugged in
Mechanical lifespan min. 100 Contact durability
Pollution degree 3/2 1 2 3 4

Rated voltage max. 250 V


Ampacity 4A
Forward resistance 5 m
Insulation resistance 109
Ambient temperature junction -40 + 80 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 41 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-T415/3G

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-T415/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
n.c. 1 1 n.c.
S 2 2 S
P1 S0
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S1 S2
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S3 S4
+ 3 3 +
4 4

Case ground

The 4-port Ex-junction module JBBS- the board. Entity and FNICO compliant accor-
49SC-T415/3G is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Mounting possible in zone 2
sing, the devices are equipped with a con-
Junction box for wall mounting with
The junction box features an adjustable densate drain. PVC cable glands M20 x 1.5
short-circuit limit. The max. current limita-
tion is selected for all ports via a rotary The shield is capacitively coupled to the Powder-coated die-cast aluminium
housing
switch. The following values can be sel- housing potential. A switch for direct cou-
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- Pressure compensation element for
mented. protection against condensation
water
The housing is made of robust die-cast alu-
minium and features protection degree Attention: Sufficient equipotential bonding Connection of the housing potential
IP67. of the installation must be ensured. The de- via an M5 x 1 bolt
vice is connected via the bolt of the hou- Short-circuit protection per drop
The junction box is equipped with a selec- sing to the systems potentializer. line/spur
table bus terminating resistor. The accor- For Ex applications: -25+70 C
ding switch is integrated in the housing on (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

42 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-T415/3G

Type JBBS-49SC-T415/3G
Ident-No. 6611440
Dimensions

122
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V
138
Short-circuit protection 30 , 35 , 45 , 60 mA
150
Indication
172
Operational readiness 1 x green
Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cable glands


Terminal Configuration 4
Segment IN 1 x M20 x 1.5 ( 612 mm)
Segment OUT 1 x M20 x 1.5 ( 612 mm)
1 = n.c.
Drop line 4 x M20 x 1.5 ( 612 mm) 2 = shield
Terminal cross-section 2.5 mm2 3=+
1234 4=
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 150 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 43 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-T615/3G

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-T615/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out
n.c. 1 1 n.c.
S 2 2 S
P1 S0
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S1 S2
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S3 S4
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S5 S6
+ 3 3 +
4 4

case ground

The 6-port Ex-junction module JBBS- the board. Entity and FNICO compliant accor-
49SC-T615/3G is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Mounting possible in zone 2
sing, the devices are equipped with a con-
Junction box for wall mounting with
The junction box features an adjustable densate drain. PVC cable glands M20 x 1.5
short-circuit limit. The max. current limita-
tion is selected for all ports via a rotary The shield is capacitively coupled to the Powder-coated die-cast aluminium
housing
switch. The following values can be sel- housing potential. A switch for direct cou-
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- Pressure compensation element for
mented. protection against condensation
water
The housing is made of robust die-cast alu-
minium and features protection degree Attention: Sufficient equipotential bonding Connection of the housing potential
IP67. of the installation must be ensured. The de- via an M5 x 1 bolt
vice is connected via the bolt of the hou- Short-circuit protection per drop
The junction box is equipped with a selec- sing to the systems potentializer. line/spur
table bus terminating resistor. The accor- For Ex applications: -25+70 C
ding switch is integrated in the housing on (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

44 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-T615/3G

Type JBBS-49SC-T615/3G
Ident-No. 6611442
Dimensions

122
Fieldbus standard IEC 61158-2 64,0
36,0 45,0

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V
173,5
Short-circuit protection 30 , 35 , 45 , 60 mA

Indication 185,5

Operational readiness 1 x green 207

Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cable glands 4


Segment IN 1 x M20 x 1.5 ( 612 mm)
Segment OUT 1 x M20 x 1.5 ( 612 mm) Terminal Configuration
Drop line 6 x M20 x 1.5 ( 612 mm)
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1 1 = n.c.
2 = shield
3=+
Degree of protection IP67 1234 4=
Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 45 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-E413/3G

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-E413/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS- the board. Entity and FNICO compliant accor-
49SC-E413/3G is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Mounting possible in zone 2
sing, the devices are equipped with a con-
Junction box for wall mounting with
The junction box features an adjustable densate drain. stainless steel M12 flange connec-
short-circuit limit. The max. current limita- tions
tion is selected for all ports via a rotary The shield is capacitively coupled to the
Powder-coated die-cast aluminium
switch. The following values can be sel- housing potential. A switch for direct cou- housing
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple-
mented. Pressure compensation element for
protection against condensation
The housing is made of robust die-cast alu- water
minium and features protection degree Attention: Sufficient equipotential bonding
IP67. of the installation must be ensured. The de- Connection of the housing potential
via an M5 x 1 bolt
vice is connected via the bolt of the hou-
The junction box is equipped with a selec- sing to the systems potentializer. Short-circuit protection per drop
table bus terminating resistor. The accor- line/spur
ding switch is integrated in the housing on For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

46 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-E413/3G

Type JBBS-49SC-E413/3G
Ident-No. 6611432
Dimensions

83
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA 138

150
Indication
172
Operational readiness 1 x green
Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection M12 flange connection


Terminal Configuration
4
Segment IN 1 x M12 - connector
Segment OUT 1 x M12 - female connector
M12 x 1 M12 x 1
Drop line 4 x M12 - female connector
Segment in Segment out, Spur
Earthing bolt M5 x 1
2 2
1=V
Degree of protection IP67 2=V+
3 1 1 3
Ambient temperature -25 + 70 C 3 = shield
Housing material powder-coated die-cast aluminium 4 4 = n.c. 4
Housing color black/yellow
nominal values: 4 A, 300 V
Dimensions 64 x 150 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 47 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-E613/3G

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-E613/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 + S6
S5
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS- the board. Entity and FNICO compliant accor-
49SC-E613/3G is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Mounting possible in zone 2
sing, the devices are equipped with a con-
Junction box for wall mounting with
The junction box features an adjustable densate drain. stainless steel M12 flange connec-
short-circuit limit. The max. current limita- tions
tion is selected for all ports via a rotary The shield is capacitively coupled to the
Powder-coated die-cast aluminium
switch. The following values can be sel- housing potential. A switch for direct cou- housing
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple-
mented. Pressure compensation element for
protection against condensation
The housing is made of robust die-cast alu- water
minium and features protection degree Attention: Sufficient equipotential bonding
IP67. of the installation must be ensured. The de- Connection of the housing potential
via an M5 x 1 bolt
vice is connected via the bolt of the hou-
The junction box is equipped with a selec- sing to the systems potentializer. Short-circuit protection per drop
table bus terminating resistor. The accor- line/spur
ding switch is integrated in the housing on For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

48 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-E613/3G

Type JBBS-49SC-E613/3G
Ident-No. 6611434
Dimensions

83
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V

173,5
Short-circuit protection 30 , 35 , 45 , 60 mA

Indication
185,5
Operational readiness 1 x green
207
Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection M12 flange connection 4


Segment IN 1 x M12 - connector
Segment OUT 1 x M12 - female connector
Drop line 6 x M12 - female connector Terminal Configuration
Earthing bolt M5 x 1
M12 x 1 M12 x 1
Degree of protection IP67 Segment in Segment out, Spur
Ambient temperature -25 + 70 C
2 2
Housing material powder-coated die-cast aluminium 1=V
Housing color black/yellow 2=V+
3 1 1 3
Dimensions 64 x 185.5 x 45 mm 3 = shield
Connection mode Wall mounting 4 4 = n.c. 4
nominal values: 4 A, 300 V

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 49 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-M413/3G

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-M413/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS- the board. Entity and FNICO compliant accor-
49SC-M413/3G is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Mounting possible in zone 2
sing, the devices are equipped with a con-
Junction box for wall mounting with
The junction box features an adjustable densate drain. stainless steel 7/8" flange connec-
short-circuit limit. The max. current limita- tions
tion is selected for all ports via a rotary The shield is capacitively coupled to the
Powder-coated die-cast aluminium
switch. The following values can be sel- housing potential. A switch for direct cou- housing
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple-
mented. Pressure compensation element for
protection against condensation
The housing is made of robust die-cast alu- water
minium and features protection degree Attention: Sufficient equipotential bonding
IP67. of the installation must be ensured. The de- Connection of the housing potential
via an M5 x 1 bolt
vice is connected via the bolt of the hou-
The junction box is equipped with a selec- sing to the systems potentializer. Short-circuit protection per drop
table bus terminating resistor. The accor- line/spur
ding switch is integrated in the housing on For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

50 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-M413/3G

Type JBBS-49SC-M413/3G
Ident-No. 6611436
Dimensions

96
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA 138

150
Indication
172
Operational readiness 1 x green
Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection 7/8" flange connection Terminal Configuration 4


Segment IN 1 x 7/8 "- plug
Segment OUT 1 x 7/8 "- plug 7/8 7/8"
Drop line 4 x 7/8 "- plug Segment in Segment out, Spur
Earthing bolt M5 x 1
1=V
1 3 3 1
2=V+
Degree of protection IP67
2 4 3 = shield 4 2
Ambient temperature -25 + 70 C
4 = n.c.
Housing material powder-coated die-cast aluminium
Housing color black/yellow nominal values: 9 A, 300 V
Dimensions 64 x 150 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 51 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-M613/3G

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-M613/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 + S6
S5
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS- the board. Entity and FNICO compliant accor-
49SC-M613/3G is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Mounting possible in zone 2
sing, the devices are equipped with a con-
Junction box for wall mounting with
The junction box features an adjustable densate drain. stainless steel 7/8" flange connec-
short-circuit limit. The max. current limita- tions
tion is selected for all ports via a rotary The shield is capacitively coupled to the
Powder-coated die-cast aluminium
switch. The following values can be sel- housing potential. A switch for direct cou- housing
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple-
mented. Pressure compensation element for
protection against condensation
The housing is made of robust die-cast alu- water
minium and features protection degree Attention: Sufficient equipotential bonding
IP67. of the installation must be ensured. The de- Connection of the housing potential
via an M5 x 1 bolt
vice is connected via the bolt of the hou-
The junction box is equipped with a selec- sing to the systems potentializer. Short-circuit protection per drop
table bus terminating resistor. The accor- line/spur
ding switch is integrated in the housing on For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

52 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-M613/3G

Type JBBS-49SC-M613/3G
Ident-No. 6611438
Dimensions

96
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA
173,5
Indication 185,5
Operational readiness 1 x green 207
Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection 7/8" flange connection 4


Segment IN 1 x 7/8 "- plug
Segment OUT 1 x 7/8 "- plug
Terminal Configuration
Drop line 6 x 7/8 "- plug
Earthing bolt M5 x 1 7/8 7/8"
Segment in Segment out, Spur
Degree of protection IP67
Ambient temperature -25 + 70 C 1=V
1 3 3 1
Housing material powder-coated die-cast aluminium 2=V+
Housing color black/yellow 2 4 3 = shield 4 2
Dimensions 64 x 185.5 x 45 mm 4 = n.c.
Connection mode Wall mounting nominal values: 9 A, 300 V

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 53 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-T415B/EX

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-T415B/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
n.c. 1 1 n.c.
S 2 2 S
P1 S0
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S1 S2
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S3 S4
+ 3 3 +
4 4

Case ground

The 4-port Ex-junction module JBBS- the board. Entity and FISCO compliant accor-
49SC-T415B/EX is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Junction box for wall mounting with
sing, the devices are equipped with a con- PVC cable glands M20 x 1.5
The junction box features an adjustable densate drain. Powder-coated die-cast aluminium
short-circuit limit. The max. current limita- housing
tion is selected for all ports via a rotary The shield is capacitively coupled to the
Pressure compensation element for
switch. The following values can be sel- housing potential. A switch for direct cou- protection against condensation
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- water
mented.
Connection of the housing potential
The housing is made of robust die-cast alu- via an M5 x 1 bolt
minium and features protection degree Attention: Sufficient equipotential bonding
IP67. of the installation must be ensured. The de- Short-circuit protection per drop
line/spur
vice is connected via the bolt of the hou-
The junction box is equipped with a selec- sing to the systems potentializer. For Ex applications: -25+70 C
table bus terminating resistor. The accor- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
ding switch is integrated in the housing on
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

54 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-T415B/EX

Type JBBS-49SC-T415B/EX
Ident-No. 6611441
Dimensions

122
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V
138
Short-circuit protection 30 , 35 , 45 , 60 mA
150
Indication
172
Operational readiness 1 x green
Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
Terminal Configuration 4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
1 = n.c.
FISCO parameter according to IEC TS 60079-27 2 = shield
3=+
1234 4=
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci trunk (in/out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection cable glands


Segment IN 1 x M20 x 1.5 ( 612 mm)
Segment OUT 1 x M20 x 1.5 ( 612 mm)
Drop line 4 x M20 x 1.5 ( 612 mm)
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 150 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 55 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-T615B/EX

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-T615B/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out
n.c. 1 1 n.c.
S 2 2 S
P1 S0
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S1 S2
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S3 S4
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S5 S6
+ 3 3 +
4 4

case ground

The 6-port Ex-junction module JBBS- the board. Entity and FISCO compliant accor-
49SC-T615B/EX is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Junction box for wall mounting with
sing, the devices are equipped with a con- PVC cable glands M20 x 1.5
The junction box features an adjustable densate drain. Powder-coated die-cast aluminium
short-circuit limit. The max. current limita- housing
tion is selected for all ports via a rotary The shield is capacitively coupled to the
Pressure compensation element for
switch. The following values can be sel- housing potential. A switch for direct cou- protection against condensation
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- water
mented.
Connection of the housing potential
The housing is made of robust die-cast alu- via an M5 x 1 bolt
minium and features protection degree Attention: Sufficient equipotential bonding
IP67. of the installation must be ensured. The de- Short-circuit protection per drop
line/spur
vice is connected via the bolt of the hou-
The junction box is equipped with a selec- sing to the systems potentializer. For Ex applications: -25+70 C
table bus terminating resistor. The accor- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
ding switch is integrated in the housing on
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

56 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-T615B/EX

Type JBBS-49SC-T615B/EX
Ident-No. 6611443
Dimensions

122
Fieldbus standard IEC 61158-2 64,0
36,0 45,0

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V
173,5
Short-circuit protection 30 , 35 , 45 , 60 mA

Indication 185,5

Operational readiness 1 x green 207

Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
4
Max. input current Ii 250 mA
Terminal Configuration
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V 1 = n.c.


2 = shield
Max. output current Io 380 mA 3=+
1234 4=
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci trunk (in/out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection cable glands


Segment IN 1 x M20 x 1.5 ( 612 mm)
Segment OUT 1 x M20 x 1.5 ( 612 mm)
Drop line 6 x M20 x 1.5 ( 612 mm)
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 57 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-E413/EX

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-E413/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS- the board. Entity and FISCO compliant accor-
49SC-E413/EX is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Junction box for wall mounting with
sing, the devices are equipped with a con- stainless steel M12 flange connec-
The junction box features an adjustable densate drain. tions
short-circuit limit. The max. current limita- Powder-coated die-cast aluminium
tion is selected for all ports via a rotary The shield is capacitively coupled to the housing
switch. The following values can be sel- housing potential. A switch for direct cou- Pressure compensation element for
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- protection against condensation
mented. water
The housing is made of robust die-cast alu- Connection of the housing potential
minium and features protection degree Attention: Sufficient equipotential bonding via an M5 x 1 bolt
IP67. of the installation must be ensured. The de-
Short-circuit protection per drop
vice is connected via the bolt of the hou- line/spur
The junction box is equipped with a selec- sing to the systems potentializer.
table bus terminating resistor. The accor- For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ding switch is integrated in the housing on ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

58 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-E413/EX

Type JBBS-49SC-E413/EX
Ident-No. 6611433
Dimensions

83
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA 138

150
Indication
172
Operational readiness 1 x green
Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po
Max. input voltage Ui


2560 mW
24 V Terminal Configuration
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW M12 x 1 M12 x 1
FISCO parameter according to IEC TS 60079-27 Segment in Segment out, Spur
2 2
Max.output voltage Uo 17.5 V 1=V
Max. output current Io 380 mA 2=V+
3 1 1 3
Max. output power Po 5320 mW 3 = shield
Max. input voltage Ui 17.5 V 4 4 = n.c. 4
Max. input current Ii 380 mA nominal values: 4 A, 300 V
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci trunk (in/out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection M12 flange connection


Segment IN 1 x M12 - connector
Segment OUT 1 x M12 - female connector
Drop line 4 x M12 - female connector
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 150 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 59 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-E613/EX

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-E613/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 + S6
S5
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS- the board. Entity and FISCO compliant accor-
49SC-E613/EX is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Junction box for wall mounting with
sing, the devices are equipped with a con- stainless steel M12 flange connec-
The junction box features an adjustable densate drain. tions
short-circuit limit. The max. current limita- Powder-coated die-cast aluminium
tion is selected for all ports via a rotary The shield is capacitively coupled to the housing
switch. The following values can be sel- housing potential. A switch for direct cou- Pressure compensation element for
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- protection against condensation
mented. water
The housing is made of robust die-cast alu- Connection of the housing potential
minium and features protection degree Attention: Sufficient equipotential bonding via an M5 x 1 bolt
IP67. of the installation must be ensured. The de-
Short-circuit protection per drop
vice is connected via the bolt of the hou- line/spur
The junction box is equipped with a selec- sing to the systems potentializer.
table bus terminating resistor. The accor- For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ding switch is integrated in the housing on ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

60 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-E613/EX

Type JBBS-49SC-E613/EX
Ident-No. 6611435
Dimensions

83
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V

173,5
Short-circuit protection 30 , 35 , 45 , 60 mA

Indication
185,5
Operational readiness 1 x green
207
Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27 Terminal Configuration

Max.output voltage Uo 17.5 V M12 x 1 M12 x 1


Max. output current Io 380 mA Segment in Segment out, Spur
Max. output power Po 5320 mW 2 2
1=V
Max. input voltage Ui 17.5 V
2=V+
Max. input current Ii 380 mA 3 1 1 3
3 = shield
Max. input power Pi 5320 mW
4 4 = n.c. 4
External inductance/capacitance Li/Ci trunk (in/out):
negligible / 5.00 nF nominal values: 4 A, 300 V
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection M12 flange connection


Segment IN 1 x M12 - connector
Segment OUT 1 x M12 - female connector
Drop line 6 x M12 - female connector
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 61 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-M413/EX

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-M413/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS- the board. Entity and FISCO compliant accor-
49SC-M413/EX is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Junction box for wall mounting with
sing, the devices are equipped with a con- stainless steel 7/8" flange connec-
The junction box features an adjustable densate drain. tions
short-circuit limit. The max. current limita- Powder-coated die-cast aluminium
tion is selected for all ports via a rotary The shield is capacitively coupled to the housing
switch. The following values can be sel- housing potential. A switch for direct cou- Pressure compensation element for
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- protection against condensation
mented. water
The housing is made of robust die-cast alu- Connection of the housing potential
minium and features protection degree Attention: Sufficient equipotential bonding via an M5 x 1 bolt
IP67. of the installation must be ensured. The de-
Short-circuit protection per drop
vice is connected via the bolt of the hou- line/spur
The junction box is equipped with a selec- sing to the systems potentializer.
table bus terminating resistor. The accor- For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ding switch is integrated in the housing on ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

62 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49SC-M413/EX

Type JBBS-49SC-M413/EX
Ident-No. 6611437
Dimensions

96
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA 138

150
Indication
172
Operational readiness 1 x green
Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po
Max. input voltage Ui


2560 mW
24 V Terminal Configuration 4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW 7/8 7/8"
FISCO parameter according to IEC TS 60079-27 Segment in Segment out, Spur

1=V
Max.output voltage Uo 17.5 V 1 3 3 1
2=V+
Max. output current Io 380 mA 3 = shield
2 4 4 2
Max. output power Po 5320 mW 4 = n.c.
Max. input voltage Ui 17.5 V
nominal values: 9 A, 300 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci trunk (in/out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection 7/8" flange connection


Segment IN 1 x 7/8 "- plug
Segment OUT 1 x 7/8 "- plug
Drop line 4 x 7/8 "- plug
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 150 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 63 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-M613/EX

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-M613/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 + S6
S5
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS- the board. Entity and FISCO compliant accor-
49SC-M613/EX is designed for FOUNDA- ding to IEC TS 60079-27
TION fieldbus systems. To avoid condensation build-up in the hou- Junction box for wall mounting with
sing, the devices are equipped with a con- stainless steel 7/8" flange connec-
The junction box features an adjustable densate drain. tions
short-circuit limit. The max. current limita- Powder-coated die-cast aluminium
tion is selected for all ports via a rotary The shield is capacitively coupled to the housing
switch. The following values can be sel- housing potential. A switch for direct cou- Pressure compensation element for
ected: 30, 35, 45 and 60 mA. pling of the shield and housing is imple- protection against condensation
mented. water
The housing is made of robust die-cast alu- Connection of the housing potential
minium and features protection degree Attention: Sufficient equipotential bonding via an M5 x 1 bolt
IP67. of the installation must be ensured. The de-
Short-circuit protection per drop
vice is connected via the bolt of the hou- line/spur
The junction box is equipped with a selec- sing to the systems potentializer.
table bus terminating resistor. The accor- For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ding switch is integrated in the housing on ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

64 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49SC-M613/EX

Type JBBS-49SC-M613/EX
Ident-No. 6611439
Dimensions

96
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA
173,5
Indication 185,5
Operational readiness 1 x green 207
Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW Terminal Configuration
FISCO parameter according to IEC TS 60079-27
7/8 7/8"
Max.output voltage Uo 17.5 V Segment in Segment out, Spur
Max. output current Io 380 mA
Max. output power Po 5320 mW 1=V
1 3 3 1
Max. input voltage Ui 17.5 V 2=V+
Max. input current Ii 380 mA 2 4 3 = shield 4 2
Max. input power Pi 5320 mW 4 = n.c.
External inductance/capacitance Li/Ci trunk (in/out): nominal values: 9 A, 300 V
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection 7/8" flange connection


Segment IN 1 x 7/8 "- plug
Segment OUT 1 x 7/8 "- plug
Drop line 6 x 7/8 "- plug
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 65 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-T415/3G

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-T415/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
n.c. 1 1 n.c.
S 2 2 S
P1 S0
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S1 S2
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S3 S4
+ 3 3 +
4 4

case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FNICO compliant accor-
T415/3G is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 60079-27
fieldbus systems. densate drain. Mounting possible in zone 2
Junction box for wall mounting with
The housing is made of robust die-cast alu- The shield is capacitively coupled to the PVC cable glands M20 x 1.5
minium and features protection degree housing potential. A switch for direct cou-
IP67. pling of the shield and housing is imple- Powder-coated die-cast aluminium
housing
mented.
The junction box is equipped with a selec- Pressure compensation element for
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding protection against condensation
water
ding switch is integrated in the housing on of the installation must be ensured. The de-
the board. vice is connected via the bolt of the hou- Connection of the housing potential
sing to the systems potentializer. via an M5 x 1 bolt
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

66 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-T415/3G

Type JBBS-49-T415/3G
Ident-No. 6611444
Dimensions

122
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
138
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device 150

172
Electrical connection cable glands
Segment IN 1 x M20 x 1.5 ( 612 mm)
Segment OUT 1 x M20 x 1.5 ( 612 mm)
Drop line 4 x M20 x 1.5 ( 612 mm)
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection
Ambient temperature
IP67
-25 + 70 C
Terminal Configuration 4
Housing material powder-coated die-cast aluminium
Housing color black/yellow
1 = n.c.
Dimensions 64 x 150 x 45 mm 2 = shield
3=+
Connection mode Wall mounting 1234 4=

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 67 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-T615/3G

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-T615/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out
n.c. 1 1 n.c.
S 2 2 S
P1 S0
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S1 S2
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S3 S4
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S5 S6
+ 3 3 +
4 4

case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FNICO compliant accor-
T615/3G is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 6007927
fieldbus systems. densate drain. Mounting possible in zone 2
Junction module for wall mounting
The housing is made of robust die-cast alu- The shield is capacitively coupled to the with PVC cable glands M20 x 1.5
minium and features protection degree housing potential. A switch for direct cou-
IP67. pling of the shield and housing is imple- Powder-coated die-cast aluminium
housing
mented.
The junction box is equipped with a selec- Pressure compensation element for
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding protection against condensation
water
ding switch is integrated in the housing on of the installation must be ensured. The de-
the board. vice is connected via the bolt of the hou- Connection of the housing potential
sing to the systems potentializer. via an M5 x 1 bolt
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

68 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-T615/3G

Type JBBS-49-T615/3G
Ident-No. 6611446
Dimensions

122
Fieldbus standard IEC 61158-2 64,0
36,0 45,0

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4 173,5
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device
185,5

Electrical connection cable glands 207

Segment IN 1 x M20 x 1.5 ( 612 mm)


Segment OUT 1 x M20 x 1.5 ( 612 mm)
Drop line 6 x M20 x 1.5 ( 612 mm)
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection
Ambient temperature
IP67
-25 + 70 C
4
Housing material powder-coated die-cast aluminium
Terminal Configuration
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm
Connection mode Wall mounting
1 = n.c.
2 = shield
3=+
1234 4=

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 69 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-E413/3G

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-E413/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FNICO compliant accor-
E413/3G is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 60079-27
fieldbus systems. densate drain. Mounting possible in zone 2
Junction box for wall mounting with
The housing is made of robust die-cast alu- The shield is capacitively coupled to the stainless steel M12 flange connec-
minium and features protection degree housing potential. A switch for direct cou- tions
IP67. pling of the shield and housing is imple-
Powder-coated die-cast aluminium
mented. housing
The junction box is equipped with a selec-
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding Pressure compensation element for
protection against condensation
ding switch is integrated in the housing on of the installation must be ensured. The de- water
the board. vice is connected via the bolt of the hou-
sing to the systems potentializer. Connection of the housing potential
via an M5 x 1 bolt
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

70 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-E413/3G

Type JBBS-49-E413/3G
Ident-No. 6611424
Dimensions

83
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4 138

FNICO / Entity field device


150
172
Electrical connection M12 flange connection
Segment IN 1 x M12 - connector
Segment OUT 1 x M12 - female connector
Drop line 4 x M12 - female connector
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature
Housing material
-25 + 70 C
powder-coated die-cast aluminium Terminal Configuration
4
Housing color black/yellow
Dimensions 64 x 150 x 45 mm M12 x 1 M12 x 1
Connection mode Wall mounting Segment in Segment out, Spur
2 2
1=V
2=V+
3 1 1 3
3 = shield
4 4 = n.c. 4
nominal values: 4 A, 300 V

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 71 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-E613/3G

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-E613/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 + S6
S5
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FNICO compliant accor-
E613/3G is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 6007927
fieldbus systems. densate drain. Mounting possible in zone 2
Junction box for wall mounting with
The housing is made of robust die-cast alu- The shield is capacitively coupled to the stainless steel M12 flange connec-
minium and features protection degree housing potential. A switch for direct cou- tions
IP67. pling of the shield and housing is imple-
Powder-coated die-cast aluminium
mented. housing
The junction box is equipped with a selec-
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding Pressure compensation element for
protection against condensation
ding switch is integrated in the housing on of the installation must be ensured. The de- water
the board. vice is connected via the bolt of the hou-
sing to the systems potentializer. Connection of the housing potential
via an M5 x 1 bolt
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

72 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-E613/3G

Type JBBS-49-E613/3G
Ident-No. 6611426
Dimensions

83
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
173,5
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

185,5
Electrical connection M12 flange connection
207
Segment IN 1 x M12 - connector
Segment OUT 1 x M12 - female connector
Drop line 6 x M12 - female connector
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature
Housing material
-25 + 70 C
powder-coated die-cast aluminium
4
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm
Connection mode Wall mounting Terminal Configuration

M12 x 1 M12 x 1
Segment in Segment out, Spur
2 2
1=V
2=V+
3 1 1 3
3 = shield
4 4 = n.c. 4
nominal values: 4 A, 300 V

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 73 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-M413/3G

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-M413/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FNICO compliant accor-
M413/3G is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 6007927
fieldbus systems. densate drain. Mounting possible in zone 2
Junction box for wall mounting with
The housing is made of robust die-cast alu- The shield is capacitively coupled to the stainless steel 7/8" flange connec-
minium and features protection degree housing potential. A switch for direct cou- tions
IP67. pling of the shield and housing is imple-
Powder-coated die-cast aluminium
mented. housing
The junction box is equipped with a selec-
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding Pressure compensation element for
protection against condensation
ding switch is integrated in the housing on of the installation must be ensured. The de- water
the board. vice is connected via the bolt of the hou-
sing to the systems potentializer. Connection of the housing potential
via an M5 x 1 bolt
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

74 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-M413/3G

Type JBBS-49-M413/3G
Ident-No. 6611428
Dimensions

96
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4 138

FNICO / Entity field device 150

172
Electrical connection 7/8" flange connection
Segment IN 1 x 7/8 "- plug
Segment OUT 1 x 7/8 "- plug
Drop line 4 x 7/8 "- plug
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature
Housing material
-25 + 70 C
powder-coated die-cast aluminium Terminal Configuration 4
Housing color black/yellow
Dimensions 64 x 150 x 45 mm 7/8 7/8"
Connection mode Wall mounting Segment in Segment out, Spur

1=V
1 3 3 1
2=V+
2 4 3 = shield 4 2
4 = n.c.
nominal values: 9 A, 300 V

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 75 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-M613/3G

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-M613/3G
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 + S6
S5
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FNICO compliant accor-
M613/3G is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 60079-27
fieldbus systems. densate drain. Mounting possible in zone 2
Junction box for wall mounting with
The housing is made of robust die-cast alu- The shield is capacitively coupled to the stainless steel 7/8" flange connec-
minium and features protection degree housing potential. A switch for direct cou- tions
IP67. pling of the shield and housing is imple-
Powder-coated die-cast aluminium
mented. housing
The junction box is equipped with a selec-
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding Pressure compensation element for
protection against condensation
ding switch is integrated in the housing on of the installation must be ensured. The de- water
the board. vice is connected via the bolt of the hou-
sing to the systems potentializer. Connection of the housing potential
via an M5 x 1 bolt
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

76 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-M613/3G

Type JBBS-49-M613/3G
Ident-No. 6611430
Dimensions

96
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 07 ATEX 2017 X


Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device 173,5

185,5
Electrical connection 7/8" flange connection 207
Segment IN 1 x 7/8 "- plug
Segment OUT 1 x 7/8 "- plug
Drop line 6 x 7/8 "- plug
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature
Housing material
-25 + 70 C
powder-coated die-cast aluminium
4
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm Terminal Configuration
Connection mode Wall mounting
7/8 7/8"
Segment in Segment out, Spur

1=V
1 3 3 1
2=V+
2 4 3 = shield 4 2
4 = n.c.
nominal values: 9 A, 300 V

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 77 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-T415B/EX

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-T415B/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
n.c. 1 1 n.c.
S 2 2 S
P1 S0
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S1 S2
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S3 S4
+ 3 3 +
4 4

case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FISCO compliant accor-
E413/EX is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 60079-27
fieldbus systems. densate drain. Junction box for wall mounting with
PVC cable glands M20 x 1.5
The housing is made of robust die-cast alu- The shield is capacitively coupled to the Powder-coated die-cast aluminium
minium and features protection degree housing potential. A switch for direct cou- housing
IP67. pling of the shield and housing is imple-
Pressure compensation element for
mented. protection against condensation
The junction box is equipped with a selec- water
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding
Connection of the housing potential
ding switch is integrated in the housing on of the installation must be ensured. The de- via an M5 x 1 bolt
the board. vice is connected via the bolt of the hou-
sing to the systems potentializer. For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

78 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-T415B/EX

Type JBBS-49-T415B/EX
Ident-No. 6611445
Dimensions

122
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
138
Max.output voltage Uo 24 V
Max. output current Io 250 mA 150

Max. output power Po 2560 mW


172
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V
Terminal Configuration 4
Max. input current Ii 380 mA
Max. input power Pi 5320 mW 1 = n.c.
External inductance/capacitance Li/Ci trunk (in/out): 2 = shield
3=+
negligible / 5.00 nF 1234 4=
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection cable glands


Segment IN 1 x M20 x 1.5 ( 612 mm)
Segment OUT 1 x M20 x 1.5 ( 612 mm)
Drop line 4 x M20 x 1.5 ( 612 mm)
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 150 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 79 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-T615B/EX

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-T615B/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out
n.c. 1 1 n.c.
S 2 2 S
P1 S0
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S1 S2
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S3 S4
+ 3 3 +
4 4

n.c. 1 1 n.c.
S 2 2 S
S5 S6
+ 3 3 +
4 4

case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FISCO compliant accor-
T615B/EX is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 60079-27
fieldbus systems. densate drain. Junction box for wall mounting with
PVC cable glands M20 x 1.5
The housing is made of robust die-cast alu- The shield is capacitively coupled to the Powder-coated die-cast aluminium
minium and features protection degree housing potential. A switch for direct cou- housing
IP67. pling of the shield and housing is imple-
Pressure compensation element for
mented. protection against condensation
The junction box is equipped with a selec- water
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding
Connection of the housing potential
ding switch is integrated in the housing on of the installation must be ensured. The de- via an M5 x 1 bolt
the board. vice is connected via the bolt of the hou-
sing to the systems potentializer. For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

80 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-T615B/EX

Type JBBS-49-T615B/EX
Ident-No. 6611447
Dimensions

122
Fieldbus standard IEC 61158-2 64,0
36,0 45,0

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter 173,5
Max.output voltage Uo 24 V
Max. output current Io 250 mA
185,5
Max. output power Po 2560 mW
207
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V
4
Max. input current Ii 380 mA Terminal Configuration
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci trunk (in/out):
negligible / 5.00 nF
1 = n.c.
per field current circuit: 2 = shield
negligible / 0.47 nF 3=+
1234 4=
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection cable glands


Segment IN 1 x M20 x 1.5 ( 612 mm)
Segment OUT 1 x M20 x 1.5 ( 612 mm)
Drop line 6 x M20 x 1.5 ( 612 mm)
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 81 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-E413/EX

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-E413/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FISCO compliant accor-
E413/EX is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 60079-27
fieldbus systems. densate drain. Junction box for wall mounting with
stainless steel M12 flange connec-
The housing is made of robust die-cast alu- The shield is capacitively coupled to the tions
minium and features protection degree housing potential. A switch for direct cou- Powder-coated die-cast aluminium
IP67. pling of the shield and housing is imple- housing
mented. Pressure compensation element for
The junction box is equipped with a selec- protection against condensation
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding water
ding switch is integrated in the housing on of the installation must be ensured. The de- Connection of the housing potential
the board. vice is connected via the bolt of the hou- via an M5 x 1 bolt
sing to the systems potentializer.
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

82 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-E413/EX

Type JBBS-49-E413/EX
Ident-No. 6611425
Dimensions

83
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
Max.output voltage Uo 24 V 138

Max. output current Io 250 mA


150
Max. output power Po 2560 mW
172
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V Terminal Configuration
4
Max. input current Ii 380 mA
Max. input power Pi 5320 mW M12 x 1 M12 x 1
External inductance/capacitance Li/Ci trunk (in/out): Segment in Segment out, Spur
negligible / 5.00 nF 2 2
1=V
per field current circuit:
negligible / 0.47 nF 2=V+
3 1 1 3
field current circuits: 3 = shield
negligible / 5.00 nF 4 4 = n.c. 4
Device designation II 2 G EEx ib IIC/IIB T4 nominal values: 4 A, 300 V
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection M12 flange connection


Segment IN 1 x M12 - connector
Segment OUT 1 x M12 - female connector
Drop line 4 x M12 - female connector
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 150 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 83 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-E613/EX

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-E613/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 + S6
S5
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FISCO compliant accor-
E613/EX is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 60079-27
fieldbus systems. densate drain. Junction box for wall mounting with
stainless steel M12 flange connec-
The housing is made of robust die-cast alu- The shield is capacitively coupled to the tions
minium and features protection degree housing potential. A switch for direct cou- Powder-coated die-cast aluminium
IP67. pling of the shield and housing is imple- housing
mented. Pressure compensation element for
The junction box is equipped with a selec- protection against condensation
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding water
ding switch is integrated in the housing on of the installation must be ensured. The de- Connection of the housing potential
the board. vice is connected via the bolt of the hou- via an M5 x 1 bolt
sing to the systems potentializer.
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

84 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-E613/EX

Type JBBS-49-E613/EX
Ident-No. 6611427
Dimensions

83
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
173,5
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po 2560 mW
185,5
Max. input voltage Ui 24 V
207
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V
4
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci trunk (in/out): Terminal Configuration
negligible / 5.00 nF
per field current circuit: M12 x 1 M12 x 1
negligible / 0.47 nF Segment in Segment out, Spur
field current circuits: 2 2
1=V
negligible / 5.00 nF
2=V+
Device designation II 2 G EEx ib IIC/IIB T4 3 1 1 3
3 = shield
II 2(1) G EEx ia IIC/IIB T4
4 4 = n.c. 4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4 nominal values: 4 A, 300 V
FISCO / Entity field device

Electrical connection M12 flange connection


Segment IN 1 x M12 - connector
Segment OUT 1 x M12 - female connector
Drop line 6 x M12 - female connector
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 85 /0309
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-M413/EX

FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-M413/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 4-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FISCO compliant accor-
M413/EX is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 60079-27
fieldbus systems. densate drain. Junction box for wall mounting with
stainless steel 7/8" flange connec-
The housing is made of robust die-cast alu- The shield is capacitively coupled to the tions
minium and features protection degree housing potential. A switch for direct cou- Powder-coated die-cast aluminium
IP67. pling of the shield and housing is imple- housing
mented. Pressure compensation element for
The junction box is equipped with a selec- protection against condensation
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding water
ding switch is integrated in the housing on of the installation must be ensured. The de- Connection of the housing potential
the board. vice is connected via the bolt of the hou- via an M5 x 1 bolt
sing to the systems potentializer.
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

86 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 4-port
JBBS-49-M413/EX

Type JBBS-49-M413/EX
Ident-No. 6611429
Dimensions

96
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
Max.output voltage Uo 24 V 138

Max. output current Io 250 mA 150


Max. output power Po 2560 mW
172
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V
Terminal Configuration 4
Max. input current Ii 380 mA
7/8 7/8"
Max. input power Pi 5320 mW
Segment in Segment out, Spur
External inductance/capacitance Li/Ci trunk (in/out):
negligible / 5.00 nF 1=V
1 3 3 1
per field current circuit: 2=V+
negligible / 0.47 nF 2 4 3 = shield 4 2
field current circuits: 4 = n.c.
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4 nominal values: 9 A, 300 V
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) [Ex ibD] EEx ib IIB T4
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection 7/8" flange connection


Segment IN 1 x 7/8 "- plug
Segment OUT 1 x 7/8 "- plug
Drop line 4 x 7/8 "- plug
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 150 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 87 /0309
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-M613/EX

FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-M613/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Segment IN 1F Segment OUT
1 1
+ 2 2 +
P1 S0
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S1 S2
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 +
S3 S4
S 3 3 S
n.c. 4 4 n.c.

1 1
+ 2 2 + S6
S5
S 3 3 S
n.c. 4 4 n.c.

Case ground

The 6-port Ex-junction module JBBS-49- To avoid condensation build-up in the hou- Entity and FISCO compliant accor-
M613/EX is designed for FOUNDATION sing, the devices are equipped with a con- ding to IEC TS 60079-27
fieldbus systems. densate drain. Junction box for wall mounting with
stainless steel 7/8" flange connec-
The housing is made of robust die-cast alu- The shield is capacitively coupled to the tions
minium and features protection degree housing potential. A switch for direct cou- Powder-coated die-cast aluminium
IP67. pling of the shield and housing is imple- housing
mented. Pressure compensation element for
The junction box is equipped with a selec- protection against condensation
table bus terminating resistor. The accor- Attention: Sufficient equipotential bonding water
ding switch is integrated in the housing on of the installation must be ensured. The de- Connection of the housing potential
the board. vice is connected via the bolt of the hou- via an M5 x 1 bolt
sing to the systems potentializer.
For Ex applications: -25+70 C
(-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
Integrated terminating resistor
(switch-in)
Cable shielding: capacitive or direct
connection to housing potential sel-
ectable via switch
Isolated support terminal for optio-
nal protective conductor incorpora-
ted in cable

88 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus
IP67 junction box, 6-port
JBBS-49-M613/EX

Type JBBS-49-M613/EX
Ident-No. 6611431
Dimensions

96
Fieldbus standard IEC 61158-2 64
36 45

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 03 ATEX 2236


Entity Parameter
Max.output voltage Uo 24 V
Max. output current Io 250 mA 173,5

Max. output power Po 2560 mW 185,5


Max. input voltage Ui 24 V 207
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V
4
Max. input current Ii 380 mA
Max. input power Pi 5320 mW Terminal Configuration
External inductance/capacitance Li/Ci trunk (in/out):
negligible / 5.00 nF 7/8 7/8"
per field current circuit: Segment in Segment out, Spur
negligible / 0.47 nF
field current circuits: 1=V
1 3 3 1
negligible / 5.00 nF 2=V+
Device designation II 2 G EEx ib IIC/IIB T4 2 4 3 = shield 4 2
II 2(1) G EEx ia IIC/IIB T4 4 = n.c.
II 2 G (2D) [Ex ibD] EEx ib IIB T4 nominal values: 9 A, 300 V
II 2 (1) G (1D) [Ex iaD] EEx ia IIB T4
FISCO / Entity field device

Electrical connection 7/8" flange connection


Segment IN 1 x 7/8 "- plug
Segment OUT 1 x 7/8 "- plug
Drop line 6 x 7/8 "- plug
Earthing bolt M5 x 1

Degree of protection IP67


Ambient temperature -25 + 70 C
Housing material powder-coated die-cast aluminium
Housing color black/yellow
Dimensions 64 x 185.5 x 45 mm
Connection mode Wall mounting

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 89 /0309
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 4-port
JRBS-40SC-4C/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 4-port
JRBS-40SC-4C/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 4
S S


+ +
2 3
S S

case ground

The 4-port Ex junction box JRBS-40SC- the board. Entity and FISCO compliant accor-
4C/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27
cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the Junction box for DIN rail mounting
both PROFIBUS PA and FOUNDATION housing potential. A switch for direct cou-
Aluminium housing
fieldbus. pling of the shield and housing is imple-
mented. Short-circuit protection per drop
The junction box features an adjustable line/spur
short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40+70 C (-40+158 F)
ected: 30, 35, 45 and 60 mA. sing to the systems potentializer. Switch-in terminating resistor
Cable shielding: Capacitive or direct
The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential
tures protection degree IP20. protection, there are various aluminium and selectable via switch
stainless steel housings with IP6x rating and
The junction box is equipped with a selec- various cable glands available on request.
table bus terminating resistor. The accor-
ding switch is integrated in the housing on

90 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 4-port
JRBS-40SC-4C/EX

Type JRBS-40SC-4C/EX
Ident-No. 6611451
Dimensions

Fieldbus standard IEC 61158-2


31
Operational voltage range: 12 32 VDC
Current self-consumption 7 mA
Voltage drop 0.3 V 119
75,5

Short-circuit protection 30 , 35 , 45 , 60 mA

Indication
Operational readiness 1 x green Terminal Configuration
Short-circuit message 4 x red

1=
Ex approval acc. to conformity certificate PTB 05 ATEX 2002 2=+
Entity Parameter 3=S
1 23
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.82 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cage clamp terminals


Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 119 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 91 /0309
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 6-port
JRBS-40SC-6C/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 6-port
JRBS-40SC-6C/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 6
S S


+ +
2 5
S S


+ +
3 4
S S

case ground

The 6-port Ex junction box JRBS-40SC- the board. Entity and FISCO compliant accor-
6C/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27
cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the Junction box for DIN rail mounting
both PROFIBUS PA and FOUNDATION housing potential. A switch for direct cou-
Aluminium housing
fieldbus. pling of the shield and housing is imple-
mented. Short-circuit protection per drop
The junction box features an adjustable line/spur
short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40+70 C (-40+158 F)
ected: 30, 35, 45 and 60 mA. sing to the systems potentializer. Switch-in terminating resistor
Cable shielding: Capacitive or direct
The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential
tures protection degree IP20. protection, there are various aluminium and selectable via switch
stainless steel housings with IP6x rating and
The junction box is equipped with a selec- various cable glands available on request.
table bus terminating resistor. The accor-
ding switch is integrated in the housing on

92 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 6-port
JRBS-40SC-6C/EX

Type JRBS-40SC-6C/EX
Ident-No. 6611452
Dimensions

Fieldbus standard IEC 61158-2


31
Operational voltage range: 12 32 VDC
Current self-consumption 7 mA
Voltage drop 0.3 V
142

75,5
Short-circuit protection 30 , 35 , 45 , 60 mA

Indication
Operational readiness 1 x green
Short-circuit message 6 x red Terminal Configuration

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 1=


Entity Parameter 2=+
3=S
Max.output voltage Uo 24 V 1 23
Max. output current Io 250 mA
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.82 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cage clamp terminals


Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 142 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 93 /0309
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 8-port
JRBS-40SC-8C/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 8-port
JRBS-40SC-8C/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 8
S S


+ +
2 7
S S


+ +
3 6
S S


+ +
4 5
S S

case ground

The 8-port Ex junction box JRBS-40SC- the board. Entity and FISCO compliant accor-
8C/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27
cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the Junction box for DIN rail mounting
both PROFIBUS PA and FOUNDATION housing potential. A switch for direct cou-
Aluminium housing
fieldbus. pling of the shield and housing is imple-
mented. Short-circuit protection per drop
The junction box features an adjustable line/spur
short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40+70 C (-40+158 F)
ected: 30, 35, 45 and 60 mA. sing to the systems potentializer. Switch-in terminating resistor
Cable shielding: Capacitive or direct
The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential
tures protection degree IP20. protection, there are various aluminium and selectable via switch
stainless steel housings with IP6x rating and
The junction box is equipped with a selec- various cable glands available on request.
table bus terminating resistor. The accor-
ding switch is integrated in the housing on

94 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 8-port
JRBS-40SC-8C/EX

Type JRBS-40SC-8C/EX
Ident-No. 6611453
Dimensions

Fieldbus standard IEC 61158-2


31

Operational voltage range: 12 32 VDC


Current self-consumption 7 mA
Voltage drop 0.3 V 177

Short-circuit protection 30 , 35 , 45 , 60 mA 75,5

Indication
Operational readiness 1 x green
Short-circuit message 8 x red Terminal Configuration

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 1=


Entity Parameter 2=+
3=S
Max.output voltage Uo 24 V 1 23
Max. output current Io 250 mA
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cage clamp terminals


Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 177 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 95 /0309
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 12-port
JRBS-40SC-12C/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 12-port
JRBS-40SC-12C/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 12
S S

. .
. .
. .


+ +
6 7
S S

case ground

The 12-port Ex junction box JRBS-40SC- the board. Entity and FISCO compliant accor-
12C/EX is designed for fieldbus systems ding to IEC TS 60079-27
according to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the Junction box for DIN rail mounting
both PROFIBUS PA and FOUNDATION housing potential. A switch for direct cou-
Aluminium housing
fieldbus. pling of the shield and housing is imple-
mented. Short-circuit protection per drop
The junction box features an adjustable line/spur
short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40+70 C (-40+158 F)
ected: 30, 35, 45 and 60 mA. sing to the systems potentializer. Switch-in terminating resistor
Cable shielding: Capacitive or direct
The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential
tures protection degree IP20. protection, there are various aluminium and selectable via switch
stainless steel housings with IP6x rating and
The junction box is equipped with a selec- various cable glands available on request.
table bus terminating resistor. The accor-
ding switch is integrated in the housing on

96 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 12-port
JRBS-40SC-12C/EX

Type JRBS-40SC-12C/EX
Ident-No. 6611455
Dimensions

Fieldbus standard IEC 61158-2


31
Operational voltage range: 12 32 VDC
Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA 276

Indication
75,5
Operational readiness 1 x green
Short-circuit message 12 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Terminal Configuration


Entity Parameter
Max.output voltage Uo 24 V
Max. output current Io 250 mA 1=
2=+
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
1 23
3=S
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27

Max.output voltage Uo 17.5 V


Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.33 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cage clamp terminals


Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 276 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 97 /0309
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 4-port
JRBS-40SC-4R/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 4-port
JRBS-40SC-4R/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 4
S S


+ +
2 3
S S

case ground

The 4-port Ex junction box JRBS-40SC- the board. Entity and FISCO compliant accor-
4R/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27
cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the Junction box for DIN rail mounting
both PROFIBUS PA and FOUNDATION housing potential. A switch for direct cou-
Aluminium housing
fieldbus. pling of the shield and housing is imple-
mented. Short-circuit protection per drop
The junction box features an adjustable line/spur
short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40+70 C (-40+158 F)
ected: 30, 35, 45 and 60 mA. sing to the systems potentializer. Switch-in terminating resistor
Cable shielding: Capacitive or direct
The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential
tures protection degree IP20. protection, there are various aluminium and selectable via switch
stainless steel housings with IP6x rating and
The junction box is equipped with a selec- various cable glands available on request.
table bus terminating resistor. The accor-
ding switch is integrated in the housing on

98 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 4-port
JRBS-40SC-4R/EX

Type JRBS-40SC-4R/EX
Ident-No. 6611459
Dimensions

Fieldbus standard IEC 61158-2

Operational voltage range: 12 32 VDC 60

Current self-consumption 7 mA 31
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA 107


75,5

Indication
Operational readiness 1 x green
Short-circuit message 4 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Terminal Configuration


Entity Parameter
Max.output voltage Uo 24 V 1=
2=+
Max. output current Io 250 mA 3=S
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
1 23
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter acc. to IEC TS 60079-27
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.82 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 119 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 99 /0309
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 6-port
JRBS-40SC-6R/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 6-port
JRBS-40SC-6R/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 6
S S


+ +
2 5
S S


+ +
3 4
S S

case ground

The 6-port Ex junction box JRBS-40SC- the board. Entity and FISCO compliant accor-
6R/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27
cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the Junction box for DIN rail mounting
both PROFIBUS PA and FOUNDATION housing potential. A switch for direct cou-
Aluminium housing
fieldbus. pling of the shield and housing is imple-
mented. Short-circuit protection per drop
The junction box features an adjustable line/spur
short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40+70 C (-40+158 F)
ected: 30, 35, 45 and 60 mA. sing to the systems potentializer. Switch-in terminating resistor
Cable shielding: Capacitive or direct
The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential
tures protection degree IP20. protection, there are various aluminium and selectable via switch
stainless steel housings with IP6x rating and
The junction box is equipped with a selec- various cable glands available on request.
table bus terminating resistor. The accor-
ding switch is integrated in the housing on

100 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 6-port
JRBS-40SC-6R/EX

Type JRBS-40SC-6R/EX
Ident-No. 6611460
Dimensions

Fieldbus standard IEC 61158-2


60
Operational voltage range: 12 32 VDC
31
Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA 142


75,5
Indication
Operational readiness 1 x green
Short-circuit message 6 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Terminal Configuration


Entity Parameter
Max.output voltage Uo 24 V 1=
2=+
Max. output current Io 250 mA 3=S
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
1 23
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter acc. to IEC TS 60079-27
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.82 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 142 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 101 /0309
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 8-port
JRBS-40SC-8R/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 8-port
JRBS-40SC-8R/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 8
S S


+ +
2 7
S S


+ +
3 6
S S


+ +
4 5
S S

case ground

The 8-port Ex junction box JRBS-40SC- the board. Entity and FISCO compliant accor-
8R/EX is designed for fieldbus systems ac- ding to IEC TS 60079-27
cording to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the Junction box for DIN rail mounting
both PROFIBUS PA and FOUNDATION housing potential. A switch for direct cou-
Aluminium housing
fieldbus. pling of the shield and housing is imple-
mented. Short-circuit protection per drop
The junction box features an adjustable line/spur
short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40+70 C (-40+158 F)
ected: 30, 35, 45 and 60 mA. sing to the systems potentializer. Switch-in terminating resistor
Cable shielding: Capacitive or direct
The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential
tures protection degree IP20. protection, there are various aluminium and selectable via switch
stainless steel housings with IP6x rating and
The junction box is equipped with a selec- various cable glands available on request.
table bus terminating resistor. The accor-
ding switch is integrated in the housing on

102 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 8-port
JRBS-40SC-8R/EX

Type JRBS-40SC-8R/EX
Ident-No. 6611461
Dimensions

Fieldbus standard IEC 61158-2


60
Operational voltage range: 12 32 VDC 31
Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA
212

Indication 75,5
Operational readiness 1 x green
Short-circuit message 8 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 Terminal Configuration


Entity Parameter
Max.output voltage Uo 24 V
1=
Max. output current Io 250 mA 2=+
3=S
Max. output power Po
Max. input voltage Ui


2560 mW
24 V
1 23
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter acc. to IEC TS 60079-27
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 177 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 103 /0309
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 12-port
JRBS-40SC-12R/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 12-port
JRBS-40SC-12R/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 12
S S

. .
. .
. .


+ +
6 7
S S

case ground

The 12-port Ex junction box JRBS-40SC- the board. Entity and FISCO compliant accor-
12R/EX is designed for fieldbus systems ding to IEC TS 60079-27
according to IEC 61158-2, i.e. it is suited for The shield is capacitively coupled to the Junction box for DIN rail mounting
both PROFIBUS PA and FOUNDATION housing potential. A switch for direct cou-
Aluminium housing
fieldbus. pling of the shield and housing is imple-
mented. Short-circuit protection per drop
The junction box features an adjustable line/spur
short-circuit limit. The max. current limita- Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
tion is selected for all ports via a rotary of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
switch. The following values can be sel- vice is connected via the bolt of the hou- ons: -40+70 C (-40+158 F)
ected: 30, 35, 45 and 60 mA. sing to the systems potentializer. Switch-in terminating resistor
Cable shielding: Capacitive or direct
The housing is made of aluminium and fea- Accessories: To increase the degree of connection with housing potential
tures protection degree IP20. protection, there are various aluminium and selectable via switch
stainless steel housings with IP6x rating and
The junction box is equipped with a selec- various cable glands available on request.
table bus terminating resistor. The accor-
ding switch is integrated in the housing on

104 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 12-port
JRBS-40SC-12R/EX

Type JRBS-40SC-12R/EX
Ident-No. 6611463
Dimensions

Fieldbus standard IEC 61158-2


60

Operational voltage range: 12 32 VDC 31


Current self-consumption 7 mA
Voltage drop 0.3 V

Short-circuit protection 30 , 35 , 45 , 60 mA
276

Indication
Operational readiness 1 x green 75,5

Short-circuit message 12 x red

Ex approval acc. to conformity certificate PTB 05 ATEX 2002


Entity Parameter Terminal Configuration
Max.output voltage Uo 24 V
Max. output current Io 250 mA 1=
2=+
Max. output power Po
Max. input voltage Ui


2560 mW
24 V 1 23
3=S
4
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter acc. to IEC TS 60079-27
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po 5320 mW
Max. input voltage Ui 17.5 V
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.33 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 276 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 105 /0309
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 4-port
JRBS-40-4C/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 4-port
JRBS-40-4C/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 4
S S


+ +
2 3
S S

case ground

The 4-port Ex junction box JRBS-40-4C/EX The shield is capacitively coupled to the Entity and FISCO compliant accor-
is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27
to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- Junction box for DIN rail mounting
PROFIBUS PA and FOUNDATION mented.
Aluminium housing
fieldbus.
Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
tures protection degree IP20. vice is connected via the bolt of the hou-
sing to the systems potentializer. Switch-in terminating resistor
The junction box is equipped with a selec- Cable shielding: Capacitive or direct
table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential
ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch
the board. stainless steel housings with IP6x rating and
various cable glands available on request.

106 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 4-port
JRBS-40-4C/EX

Type JRBS-40-4C/EX
Ident-No. 6611448
Dimensions

Fieldbus standard IEC 61158-2


31
Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 119


75,5
Entity Parameter
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po 2560 mW
Max. input voltage Ui 24 V Terminal Configuration
Max. input current Ii 250 mA
Max. input power Pi 2560 mW 1=
FISCO parameter according to IEC TS 60079-27 2=+
3=S
1 23
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V
4
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.82 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cage clamp terminals


Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 119 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 107 /0309
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 6-port
JRBS-40-6C/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 6-port
JRBS-40-6C/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 6
S S


+ +
2 5
S S


+ +
3 4
S S

case ground

The 6-port Ex junction box JRBS-40-6C/EX The shield is capacitively coupled to the Entity and FISCO compliant accor-
is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27
to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- Junction box for DIN rail mounting
PROFIBUS PA and FOUNDATION mented.
aluminium housing
fieldbus.
Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
tures protection degree IP20. vice is connected via the bolt of the hou-
sing to the systems potentializer. Switch-in terminating resistor
The junction box is equipped with a selec- Cable shielding: Capacitive or direct
table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential
ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch
the board. stainless steel housings with IP6x rating and
various cable glands available on request.

108 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 6-port
JRBS-40-6C/EX

Type JRBS-40-6C/EX
Ident-No. 6611449
Dimensions

Fieldbus standard IEC 61158-2


31
Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 05 ATEX 2002


142
Entity Parameter
75,5
Max.output voltage Uo 24 V
Max. output current Io 250 mA
Max. output power Po 2560 mW
Max. input voltage Ui 24 V
Terminal Configuration
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27 1=
2=+
3=S
1 23
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V
4
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.82 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cage clamp terminals


Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 142 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 109 /0309
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 8-port
JRBS-40-8C/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 8-port
JRBS-40-8C/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 8
S S


+ +
2 7
S S


+ +
3 6
S S


+ +
4 5
S S

case ground

The 8-port Ex junction box JRBS-40-8C/EX The shield is capacitively coupled to the Entity and FISCO compliant accor-
is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27
to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- Junction box for DIN rail mounting
PROFIBUS PA and FOUNDATION mented.
Aluminium housing
fieldbus.
Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
tures protection degree IP20. vice is connected via the bolt of the hou-
sing to the systems potentializer. Switch-in terminating resistor
The junction box is equipped with a selec- Cable shielding: Capacitive or direct
table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential
ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch
the board. stainless steel housings with IP6x rating and
various cable glands available on request.

110 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 8-port
JRBS-40-8C/EX

Type JRBS-40-8C/EX
Ident-No. 6611450
Dimensions

Fieldbus standard IEC 61158-2


31

Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 05 ATEX 2002 177

Entity Parameter
Max.output voltage Uo 24 V 75,5

Max. output current Io 250 mA


Max. output power Po 2560 mW
Max. input voltage Ui 24 V
Terminal Configuration
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27 1=
2=+
3=S
1 23
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V
4
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cage clamp terminals


Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 177 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 111 /0309
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 12-port
JRBS-40-12C/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 12-port
JRBS-40-12C/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 12
S S

. .
. .
. .


+ +
6 7
S S

case ground

The 12-port Ex junction box JRBS-40-12C/ The shield is capacitively coupled to the Entity and FISCO compliant accor-
EX is designed for fieldbus systems accor- housing potential. A switch for direct cou- ding to IEC TS 60079-27
ding to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- Junction box for DIN rail mounting
PROFIBUS PA and FOUNDATION mented.
Aluminium housing
fieldbus.
Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
tures protection degree IP20. vice is connected via the bolt of the hou-
sing to the systems potentializer. Switch-in terminating resistor
The junction box is equipped with a selec- Cable shielding: Capacitive or direct
table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential
ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch
the board. stainless steel housings with IP6x rating and
various cable glands available on request.

112 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus and PROFIBUS-PA
IP20 junction box, 12-port
JRBS-40-12C/EX

Type JRBS-40-12C/EX
Ident-No. 6611454
Dimensions

Fieldbus standard IEC 61158-2


31
Operational voltage range: 9 32 VDC

Ex approval acc. to conformity certificate PTB 05 ATEX 2002


Entity Parameter
Max.output voltage Uo 24 V 276

Max. output current Io 250 mA


Max. output power Po 2560 mW 75,5
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter according to IEC TS 60079-27 Terminal Configuration

Max.output voltage Uo 17.5 V


1=
Max. output current Io 380 mA 2=+
Max. output power Po
Max. input voltage Ui
5320 mW
17.5 V
1 23
3=S
4
Max. input current Ii 380 mA
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.33 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection cage clamp terminals


Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 276 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 113 /0309
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 4-port
JRBS-40-4R/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 4-port
JRBS-40-4R/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 4
S S


+ +
2 3
S S

case ground

The 4-port Ex junction box JRBS-40-4R/EX The shield is capacitively coupled to the Entity and FISCO compliant accor-
is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27
to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- Junction box for DIN rail mounting
PROFIBUS PA and FOUNDATION mented.
Aluminium housing
fieldbus.
Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
tures protection degree IP20. vice is connected via the bolt of the hou-
sing to the systems potentializer. Switch-in terminating resistor
The junction box is equipped with a selec- Cable shielding: Capacitive or direct
table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential
ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch
the board. stainless steel housings with IP6x rating and
various cable glands available on request.

114 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 4-port
JRBS-40-4R/EX

Type JRBS-40-4R/EX
Ident-No. 6611456
Dimensions

Fieldbus standard IEC 61158-2

Operational voltage range: 9 32 VDC 60

31
Ex approval acc. to conformity certificate PTB 05 ATEX 2002
Entity Parameter
Max.output voltage Uo 24 V 107
75,5
Max. output current Io 250 mA
Max. output power Po 2560 mW
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW Terminal Configuration
FISCO parameter acc. to IEC TS 60079-27
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA 1=
2=+
Max. output power Po 5320 mW 3=S

Max. input voltage Ui


Max. input current Ii
17.5 V
380 mA
1 23
4
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.82 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 119 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 115 /0309
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 6-port
JRBS-40-6R/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 6-port
JRBS-40-6R/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 6
S S


+ +
2 5
S S


+ +
3 4
S S

case ground

The 6-port Ex junction box JRBS-40-6R/EX The shield is capacitively coupled to the Entity and FISCO compliant accor-
is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27
to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- Junction box for DIN rail mounting
PROFIBUS PA and FOUNDATION mented.
Aluminium housing
fieldbus.
Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
tures protection degree IP20. vice is connected via the bolt of the hou-
sing to the systems potentializer. Switch-in terminating resistor
The junction box is equipped with a selec- Cable shielding: Capacitive or direct
table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential
ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch
the board. stainless steel housings with IP6x rating and
various cable glands available on request.

116 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 6-port
JRBS-40-6R/EX

Type JRBS-40-6R/EX
Ident-No. 6611457
Dimensions

Fieldbus standard IEC 61158-2


60
Operational voltage range: 9 32 VDC
31

Ex approval acc. to conformity certificate PTB 05 ATEX 2002


Entity Parameter
Max.output voltage Uo 24 V 142
Max. output current Io 250 mA 75,5
Max. output power Po 2560 mW
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW Terminal Configuration
FISCO parameter acc. to IEC TS 60079-27
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA 1=
2=+
Max. output power Po 5320 mW 3=S

Max. input voltage Ui


Max. input current Ii
17.5 V
380 mA
1 23
4
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.82 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 142 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 117 /0309
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 8-port
JRBS-40-8R/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 8-port
JRBS-40-8R/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 8
S S


+ +
2 7
S S


+ +
3 6
S S


+ +
4 5
S S

case ground

The 8-port Ex junction box RBS-40-8R/EX The shield is capacitively coupled to the Entity and FISCO compliant accor-
is designed for fieldbus systems according housing potential. A switch for direct cou- ding to IEC TS 60079-27
to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- Junction box for DIN rail mounting
PROFIBUS PA and FOUNDATION mented.
Aluminium housing
fieldbus.
Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
tures protection degree IP20. vice is connected via the bolt of the hou-
sing to the systems potentializer. Switch-in terminating resistor
The junction box is equipped with a selec- Cable shielding: Capacitive or direct
table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential
ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch
the board. stainless steel housings with IP6x rating and
various cable glands available on request.

118 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 8-port
JRBS-40-8R/EX

Type JRBS-40-8R/EX
Ident-No. 6611458
Dimensions

Fieldbus standard IEC 61158-2


60
Operational voltage range: 9 32 VDC 31

Ex approval acc. to conformity certificate PTB 05 ATEX 2002


Entity Parameter
Max.output voltage Uo 24 V
212
Max. output current Io 250 mA
Max. output power Po 2560 mW 75,5
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter acc. to IEC TS 60079-27 Terminal Configuration
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA 1=
Max. output power Po 5320 mW 2=+
3=S
Max. input voltage Ui
Max. input current Ii
17.5 V
380 mA
1 23
4
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.47 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 177 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 119 /0309
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 12-port
JRBS-40-12R/EX

FOUNDATION fieldbus und PROFIBUS-PA


IP20 junction box, 12-port
JRBS-40-12R/EX
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

100 W
Trunk In 1F Trunk Out

+ +
P1 S0
S S


+ +
1 12
S S

. .
. .
. .


+ +
6 7
S S

case ground

The 12-port Ex junction box JRBS-40-12R/ The shield is capacitively coupled to the Entity and FISCO compliant accor-
EX is designed for fieldbus systems accor- housing potential. A switch for direct cou- ding to IEC TS 60079-27
ding to IEC 61158-2, i.e. it is suited for both pling of the shield and housing is imple- Junction box for DIN rail mounting
PROFIBUS PA and FOUNDATION mented.
Aluminium housing
fieldbus.
Attention: Sufficient equipotential bonding For Ex applications: -25+70 C
The housing is made of aluminium and fea- of the installation must be ensured. The de- (-13+158 F); for non-Ex applicati-
ons: -40+70 C (-40+158 F)
tures protection degree IP20. vice is connected via the bolt of the hou-
sing to the systems potentializer. Switch-in terminating resistor
The junction box is equipped with a selec- Cable shielding: Capacitive or direct
table bus terminating resistor. The accor- Accessories: To increase the degree of connection with housing potential
ding switch is integrated in the housing on protection, there are various aluminium and selectable via switch
the board. stainless steel housings with IP6x rating and
various cable glands available on request.

120 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
FOUNDATION fieldbus und PROFIBUS-PA
IP20 junction box, 12-port
JRBS-40-12R/EX

Type JRBS-40-12R/EX
Ident-No. 6611462
Dimensions

Fieldbus standard IEC 61158-2


60

Operational voltage range: 9 32 VDC 31

Ex approval acc. to conformity certificate PTB 05 ATEX 2002


Entity Parameter
Max.output voltage Uo 24 V
276
Max. output current Io 250 mA
Max. output power Po 2560 mW
75,5
Max. input voltage Ui 24 V
Max. input current Ii 250 mA
Max. input power Pi 2560 mW
FISCO parameter acc. to IEC TS 60079-27 Terminal Configuration
Max.output voltage Uo 17.5 V
Max. output current Io 380 mA
Max. output power Po 5320 mW 1=
2=+
Max. input voltage Ui
Max. input current Ii
17.5 V
380 mA
1 23
3=S
4
Max. input power Pi 5320 mW
External inductance/capacitance Li/Ci Trunk (In/Out):
negligible / 5.00 nF
per field current circuit:
negligible / 0.33 nF
field current circuits:
negligible / 5.00 nF
Device designation II 2 G EEx ib IIC/IIB T4
II 2(1) G EEx ia IIC/IIB T4
II 2 G (2D) EEx ib [ibD] IIB T4
II 2 (1) G (1D) EEx ia [iaD] IIB T4
FISCO / Entity field device
Ex approval acc. to conformity certificate PTB 07 ATEX 2035 X
Device designation II 3 G Ex nA II T4
II 3 G Ex nA [nL] IIC/IIB T4
FNICO / Entity field device

Electrical connection removable terminal block, reverse polarity pro-


tected, screw connection
Terminal cross-section 2.5 mm2
Earthing bolt M5 x 1

Degree of protection IP20


Ambient temperature -25 + 70 C
Housing material aluminium
Housing color black
Dimensions 276 x 31 x 75.5 mm
Connection mode snap-on DIN rail (EN 60715)

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 121 /0309
FOUNDATION fieldbus
Cable technology Basics

A two or three wire cable is prescribed by Cable parameters In the following table (Tab. 1) we compare
IEC 61158-2 as the transmission medium Electrical data and permissible cable types the four standard cable types (at 25 C):
for transmission energy and data. are not prescribed. Cable parameters
determine the achievable fieldbus proper-
ties such as the distances to be covered,
number of connectable stations and
electromagnetic compatibility.

Type A Type B Type C Type D


(Reference)

Cable design Twisted One or Multiple twisted Multiple non-


conductor pair multiple twisted pairs, not shielded twisted pairs
conductor pairs, not shielded
overall shield

Conductor cross-section (nominal) 0.8 mm2 0.32 mm2 0.13 mm2 1.25 mm2
(AWG 18) (AWG 22) (AWG 26) (AWG 16)

Loop impedance (DC current) 44 /km 112 /km 264 /km 40 /km

Wave resistance at 31.25 kHz 100 20 % 100 30 % not specified not specified

Wave attenuation at 39 kHz 3 dB/km 5 dB/km 8 dB/km 8 dB/km

Capacitive asymmetry 2 nF/km 2 nF/km not specified not specified

Group delay distortion (7,9...39 kHz) 1.7 s/km not specified not specified not specified

Degree of shield coverage 90 % not specified not specified not specified

Recommended network expansion 1900 m 1200 m 400 m 200 m


(incl. spur lines)

Tab. 1 Cable types to IEC 61158-2

Use of the individual cable types the types and limit values listed in Tab. 1, Maximum cable lengths, spur lines
Cables conforming to the minimum but its particularly suitable for FOUN- Each fieldbus installation must follow a
requirements of type A, should be used DATION fieldbus and PROFIBUS-PA defined set of rules, the Network confi-
for new installations. Cable types C fieldbus systems. All of TURCKs cables guration rules (see IEC 61158-2, Chap.
and D should only be used in so-called for fieldbuses compliant with IEC 61158-2 11.2.2). The following limit values for
Retrofit Applications (usage of cable feature optimum quality even exceeding permissible attenuation, reflection and
already installed) involving only very limited type A requirements. distortion (rule 8), as well as the maximum
network extensions. It is necessary to signal delay (rule 4) are listed (see Tab. 2).
consider that in these cases the immunity
to interference during data transmission
may not meet the demands described in
the standard.

Installations conform to the FISCO


Attenuation between any two bus interfaces (at 31.25 kHz) 10.5 dB
model
Installations conform to the FISCO model
Attenuation distortion a (f = 39 kHz) a (f = 7.8 kHz), 6 dB
are not subject to any technical safety limi-
monotonic increasing with frequency
tations, if the limit values defined in Tab. 1
are observed. Operation outside of these
limit values is not generally excluded, but Reflection factor at any point (7.8...39 kHz) 0.2
requires that each case is considered
individually. Signal delay between any two bus interfaces 640 s
For example, the TURCK long distance
Cable FBY../LD is not comparable with Tab. 2 Limit values for attenuation, distortion, reflection and propagation delay

122 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Topology An individual calculation of the four The basis for a network should be a tree
If the limit values listed on the previous variables listed in Tab. 2 for all possible or linear topology or a combination of
page are taken into consideration, various connections between two bus interfaces both.
topologies such as star, tree or linear is associated with a very high effort. It is A network of this type consists of a main
structures, as well as every cable is per- advisable to define rules which set down cable (trunk line), a number of spur lines
missible. an optimum basic topology. These rules (spur), connection elements (connectors
should ensure that the limit values stated or junction boxes) and a terminating resis-
cannot be exceeded. tor (see Fig. 1).

process device PC

control room

DPC
PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X

trunk terminating
resistor
field

spur spur

5
Fig. 1 Network topology

Maximum cable lengths


The sum of main cable lengths and all Cable Max. cable lengths (incl. spur lines)
spur line lengths results in the overall
cable length, as already defined in Tab. 1 Type A 1900 m
as the network expansion (see Tab. 3).
Type B 1200 m

Type C 400 m

Type D 200 m

Tab. 3 Maximum cable lengths (main cable and spur lines)

Maximum spur cable lengths


The maximum spur cable length depends Number of 1 device 2 devices 3 devices 4 devices
on the number of field devices per spur devices per spur line per spur line per spur line per spur line
line and is listed in Tab. 4.
25...32 1m 1m 1m 1m

19...24 30 m 1m 1m 1m

15...18 60 m 30 m 1m 1m
Instrumentation to FISCO
13...14 90 m 60 m 30 m 1m
With FISCO conform EEx i instrumenta-
tion, the maximum expansion of the trunk
1...12 120 m 90 m 60 m 30 m
line in the explosion hazardous area is
1000 m. A maximum spur line length of
60 m may not be exceeded. Tab. 4 Maximum spur line lengths

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 123 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 turckmh@turck.com www.turck.com

Fieldbus cables for fieldbus systems


According to IEC61158-2
CABLE FBY-.../SD-...M

G Fieldbus cables, type A, IEC 61158-2


G PVC cable jacket, colour blue,
black, yellow or orange
Jacket Braid G Oil, gas and sunlight resistant
Shield
G Temperature range -40... +75 C
G Cable conductor cross section: 18/7
BU AWG (0.8 mm2)
Foil Shield Data
BN

Conductor cross-section
Drain Wire BN

BU

BK
Type CABLE FBY-.../SD-...M
Ident-No. depending on length and colour, Ident-No. on
request

Cable 18/7 AWG (0.8 mm2), stranded plain copper


Cable jacket PVC (blue, black, yellow or orange)
Shield aluminium foil, tinned copper braid and stran-
8
ded filler litz wire
Max. tensile strength 90 N
Bending radius minimum 5 x cable diameter
Core insulation material PE-foam with PE-casing
Core insulation colours BN, BU
Core cross-section 2 x 0.8 mm2
DC resistance (loop) 43.6 /km
Shield resistance nom. 9 /km
Nom. Impedance 100 20 (31.25 kBit/s)
Working capacitance nom. 60 nF/km
Capacitive earthing max. 2 nF/km
Dampening max. 3.0 dB/km (with f = 39 kHz]
Skew max. 1.7 s/km (7.9 kHz -39 kHz)
Inductivity nom. 0.7 mH/km

Rated voltage max. 300 V


Ambient temperature
At rest -40... + 75 C
In moving state -5... + 50 C
Approvals UL
UV resistance according to UL 1581, section 1200
Resistance to oil according to ICEA S82-552
Flame retardant according to IEC 60332

124 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 turckmh@turck.com www.turck.com

Fieldbus cables for fieldbus systems


According to IEC61158-2
CABLE FBY-BK/LD-...M

G Long-distance fieldbus cables, type


A, acc.IEC 61158-2
G PVC cable jacket, colour black
Jacket Braid G Oil, gas and sunlight resistant
Shield
G Temperature range -40... +75 C
G Cable conductor cross section: 14/
BU 7AWG (2.1 mm2)
Foil Shield Data
BN

Conductor cross-section
Drain Wire BN

BU

BK
Type CABLE FBY-BK/LD-...M
Ident-No. depending on the length, Ident-No. on request

Cable 14/7 AWG (2.1 mm2), stranded plain copper


Cable jacket PVC, black
Shield aluminium foil, tinned copper braid and stran-
ded filler litz wire 11,5
Max. tensile strength 90 N
Bending radius minimum 5 x cable diameter
Core insulation material
Core insulation colours
PE-foam with PE-casing
BN, BU
5
Core cross-section 2 x 2.1 mm2
DC resistance (loop) 17.2 /km
Shield resistance nom. 6 /km
Nom. Impedance 100 20 (31.25 kBit/s)
Working capacitance nom. 60 nF/km
Capacitive earthing max. 2 nF/km
Dampening max. 3.0 dB/km (with f = 39 kHz]
Skew max. 1.7 s/km (7.9 kHz -39 kHz)
Inductivity nom. 0.7 mH/km

Rated voltage max. 300 V


Ambient temperature
At rest -40... + 75 C
In moving state -5... + 50 C
Approvals UL
UV resistance according to UL 1581, section 1200
Resistance to oil according to ICEA S82-552
Flame retardant according to IEC 60332

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 125 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 turckmh@turck.com www.turck.com

Fieldbus cables for fieldbus systems


According to IEC61158-2
CABLE FBH-YE/SD-...M

G Fieldbus cables, type A, acc. to IEC


61158-2
G LSZH (low smoke zero halogen) mix
Jacket Braid G PVC cable jacket, colour yellow
Shield
G Oil, gas and sunlight resistant
G Temperature range -40 ... +75 C
BU
Foil Shield Data G Cable cross section: 18/7 AWG (0.8
BN mm2)

Drain Wire Conductor cross-section


BN

BU

Type CABLE FBH-YE/SD-...M YE


Ident-No. depending on the length, Ident-No. on request

Cable 18/7 AWG (0.8 mm2), stranded plain copper


Cable jacket LSZH (low smoke zero halogen) mix, yellow
Shield aluminium foil, tinned copper braid and stran-
ded filler litz wire
Max. tensile strength 90 N
Bending radius minimum 5 x cable diameter 8
Core insulation material PE-foam with PE-casing
Core insulation colours BN, BU
Core cross-section 2 x 0.8 mm2
DC resistance (loop) 43.6 /km
Shield resistance nom. 9 /km
Nom. Impedance 100 20 (31.25 kBit/s)
Working capacitance nom. 60 nF/km
Capacitive earthing max. 2 nF/km
Dampening max. 3.0 dB/km (with f = 39 kHz]
Skew max. 1.7 s/km (7.9 kHz - 39 kHz)
Inductivity nom. 0.7 mH/km

Rated voltage max. 300 V


Ambient temperature
At rest -40... + 75 C
In moving state -5... + 50 C
Approvals UL
UV resistance according to UL 1581, section 1200
Resistance to oil according to ICEA S82-552
Flame retardant yes
Halogen-free yes

126 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 turckmh@turck.com www.turck.com

Fieldbus cables for fieldbus systems


According to IEC61158-2
CABLE FBA-YE/SD...M

G Fieldbus cables, type A, acc. to IEC


61158-2
G PVC cable jacket, colour yellow
Jacket Armor Braid G Armouring Steel round wire
Shield
G Oil, gas and sunlight resistant
G Temperature range -40 ... +75 C
BU
Foil Shield Data G Cable conductor cross section: 18/7
BN AWG (0.8 mm2)

Drain Wire Conductor cross-section


BN

BU

Type CABLE FBA-YE/SD...M


Ident-No. depending on the length, Ident-No. on request

Cable 18/7 AWG (0.8 mm2), stranded plain copper


Cable jacket PVC, yellow
Shield aluminium foil, tinned copper braid and stran-
ded filler litz wire
Max. tensile strength 90 N
11,8
Core insulation material PE-foam with PE-casing
Core insulation colours
Core cross-section
BN, BU
2 x 0.8 mm2
5
DC resistance (loop) 43.6 /km
Armouring zinc-plated steel round wire
Diameter 0.9 mm
Shield resistance nom. 9 /km
Nom. Impedance 100 20 (31.25 kBit/s)
Working capacitance nom. 60 nF/km
Capacitive earthing max. 2 nF/km
Dampening max. 3.0 dB/km (with f = 39 kHz]
Skew max. 1.7 s/km (7.9 kHz - 39 kHz)
Inductivity nom. 0.7 mH/km

Rated voltage max. 300 V


Ambient temperature
At rest -40... + 75 C
In moving state -5... + 50 C
Approvals UL
UV resistance according to UL 1581, section 1200
Resistance to oil according to ICEA S82-552
Flame retardant according to IEC 60332

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 127 /0309
Fieldbus cables for fieldbus systems
According to IEC 61158-2
Cable 492A-...M, 492BA-...M

Fieldbus cables, type A, IEC 61158-2


Suitable for harsh environmental
conditions
Aluminium armouring
Aluminium Inner Suitable for 7/8 male connector
Jacket Armor Jacket
UV resistant
Device Temperature range -40...+75 C
GNYE Ground
Cable conductor cross section 18/7
BU
Foil Shield Data AWG (0.8 mm2)
BN
Cable 492A with yellow cable jacket
Drain Wire Cable 492BA with blue cable jacket

Conductor cross-section

GNYE
BU
Type designation and Ident-No. BN
Type Cable 492A-...M depending on the length, Ident-No. on request
YE
Type Cable 492BA-...M depending on the length, Ident-No. on request

Cable 18/7 AWG (0.8 mm), stranded bare copper


Insulation XLPE foam
Color code A-conductor: brown; B-conductor: blue;
ground: green/yellow
Shield aluminium foil, metallic external surface
with contact to the tinned copper braid and
12,7
stranded drain wire
Jacket Polyvinyl chloride (PVC)
Armoured Aluminium
Overall diameter approx. 12.7 mm

Physical properties/
fire resistance
Minimum bending radius once: 40 mm/repeated: 60 mm
Ambient temperature
At rest -40 ... +75 C
In moving state -5 ... +50 C
UV resistance conform to UL 1581, section 1200
Flame retardant PLTC cable, flame resistant conform to CSA-
FT4

Electrical properties at 20 C
Inductance max. 0.44 mH/km
Total capacitance max. 52.43 nF/km
Impedance (at 31.25 kBit/s) 100 / 20
DC resistance 2 x 21.3 /Km
High voltage test (conductor/conductor
and conductor/shield) 1500 V
Operational voltage max. 300 V

128 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Fieldbus cables for fieldbus systems
According to IEC 61158-2
Cable FB4910-BK...M

Fieldbus cables, type A, IEC 61158-2


Special cable for FOUNDATION
fieldbus
Area of application:
Jacket offshore
extremely cold regions
Device
GN Ground tropical regions
BU Resistant to oil, gases and
Foil Shield Data
BN sunlight
Excellent tensile strength and
Drain Wire
abrasion resistance
Highly flame resistant conform to
IEEE 1202/FT4 and IEC 332-3,
category A
Temperature range -50..+90 C
Cable conductor cross section 18/7
AWG (0.8 mm2)
Type Cable FB4910-BK-...M Approvals
Ident-No. depending on the length, Ident-No. on request UL 1309 (Marine Shipboard) and
CSA 222 No. 245
Cable 18/7 AWG (0.8 mm), stranded bare copper
Insulation XLPE foam
Color code A-conductor: brown; B-conductor: blue; Conductor cross-section
ground: green
Shield aluminium foil, metallic external surface GN
with contact to the tinned copper braid and BU
stranded drain wire BN 5
Jacket TPE BK
Overall diameter approx. 8.9 mm

Physical properties/fire resistance


Minimum bending radius once: 40 mm/repeated: 60 mm
Ambient temperature
At rest -40 ... +90 C
In moving state -50 ... +50 C
UV resistance conform to UL 1581, section 1200 8,9
Resistance to oils conform to ICEA S61-402
Flame resistance conform to IEC 60332

Electrical properties at 20 C
Inductance max. 0.44 mH/km
Total capacitance max. 52.43 nF/km
Impedance (at 31.25 kBit/s) 100 / 20
DC resistance 2 x 21.3 /Km
High voltage test (conductor/conductor
and conductor/shield) 1500 V
Operational voltage max. 300 V

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 129 /0309
JUST
IN
TIME! 1. Workday

Ideally the length of the cord set is adjusted according to the requirements of the
plant. For this reason TURCK now offers a Just-in-Time-delivery service (JIT) for
premoulded cables.

The new JIT-5D-Programme


for perfect connections: Ordering until
Just-in-Time delivery
within 5 days only
12 p.m.
Free choice of cable length
Premoulded fieldbus and power
cables
High flexibility with respect to
planning and mounting Production
of your application
High cost savings

Delivery
3 workdays after
ordering

Arrival
at the
customer

* valid for deliveries 5. Workday*


within the European Union (EU)

130 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
M12 x 1 Type designation
cable type FBY49x, x = colour (BU, BK, OG, YE), *M = variable length in m
m RSCV w WSCV w RKCV v WKCV v
one-sided 7,6 M12 x 1 33,5 7,6 M12 x 1 33,5

premoulded 15 15
32,0
38,5
55,2 48,5
M12 x 1
15
M12 x 1
15

RSCV RSCV-FBY49x- RSCV-RSCV- RSCV-RKCV-


w *M/5D FBY49x-*M/5D FBY49x-*M/5D
WSCV WSCV-FBY49x- WSCV-WSCV- WSCV-WKCV-
w *M/5D FBY49x-*M/5D FBY49x-*M/5D
RKCV RKCV-FBY49x- RKCV-RKCV-
v *M/5D FBY49x-*M/5D
WKCV WKCV-FBY49x- WKCV-WKCV-
v *M/5D FBY49x-*M/5D

w v
Pin configuration: 2
2
Malew 1 = (BU) 1 = (BU)
3 1 2 = + (BN) 1 3 2 = + (BN)
Female v 3 = S (Shield) 3 = S (Shield)
4 4 = n.c. 4 4 = n.c.

7/8 Type designation


cable type FBY49x, x = colour (BU, BK, OG, YE), *M = variable length in m
m RSV w WSV w RKV v WKV v
7/8-16UN 51,25 7/8-16UN 51,25
one-sided 15,5 7,3 41,0 15,5 7,3 41,0
8,5 8,5
premoulded 26,0
17,5
26,0 17,5
43,5 40,0
34,0 30,55

36,0 18,0 29,0 7/8-16UN


7/8-16UN 50,5
54,0 26,0
26,0

RSV RSV-FBY49x- RSV-RSV-FBY49x- RSV-RKV-FBY49x-


6
w *M/5D *M/5D *M/5D
WSV WSV-FBY49x- WSV-WSV-FBY49x- WSV-WKV-FBY49x-
w *M/5D *M/5D *M/5D
RKV RKV-FBY49x- RKV-RKV-FBY49x-
v *M/5D *M/5D
WKV WKV-FBY49x- WKV-WKV-FBY49x-
v *M/5D *M/5D

w v
Pin configuration:
Malew 1 3 1 = (BU) 3 1 1 = (BU)
2 = + (BN) 2 = + (BN)
Female v 3 = S (Shield) 4 2 3 = S (Shield)
2 4
4 = n.c. 4 = n.c.

Connectors Cable layout


Coupling nut: Stainless steel Outer jacket: Polyvinyl chloride (PVC)
Contacts: Gold-plated Core isolation: PE-foam with PR-jacket
Grip: PA Colour code: BN, BU
Protection degree: IP67 Insolation: Extruded special compound
Shield: One side plastic coated with aluminium strip, metal
exterior with contact to tin-plated copper braid and stranded
drain wire
Diameter: 8 mm
Conductor: 18/7 AWG (0.8 mm2), stranded blank copper

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 131 /0309
7/8 Type designation
armoured cable type 492A, 492 BA, *M = variable length in m
m RSV w RKV v
one-sided 20,5 20,5
7/8-16UN 7/8-16UN
premoulded 7,3 7,3

17,5 27,0 17,5 27,0

36,0 29,0
68,5 65,0

RSV RSV492A-*M RSV-RKV492A-*M


w RSV492BA-*M RSV-RKV492BA-*M
RKV RKV492A-*M
v RKV492BA-*M

w v
Pin configuration:
Malew 1 3 1 = (BU) 3 1 1 = (BU)
2 = + (BN) 2 = + (BN)
Female v 3 = S (Shield) 4 2 3 = S (Shield)
2 4
4 = Ground (GNYE) 4 = Ground (GNYE)

Note: This field-wireable fieldbus cable is not included in the JIT-5D-Programme.

132 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
6

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 133 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
RSFV49

Version: male 7/8" connector


1/2-14 NPT screw-in thread
Stainless steel flange housing

26,5
4-pole, solderable
10 7,5 For FOUNDATION fieldbus appli-
cations
25,4

FOUNDATION fieldbus connection


1/2-14 NPT 26 7/8-16UN

1=
1 3 2=+
2 4 3 = shield
4 = n.c.

Type RSFV49
Ident-No. 6602199

Connector Male flange connector, 7/8''


Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, PUR, black
Screw-in thread seal NBR
Flange housing stainless steel, 1.4401 (316)
Degree of protection IP67, only with screws tightened
Screw-in thread 1/2-14 NPT
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Rated voltage max. 600 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 105 C

134 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
RKFV49

Version: female 7/8" connector


1/2-14 NPT screw-in thread
Stainless steel flange housing
4-pole, solderable
19,5
10 For FOUNDATION fieldbus appli-
cations
25,4

FOUNDATION fieldbus connection


7/8-16UN
1/2-14 NPT 26 v

1=
3 1 2=+
4 2 3 = shield
4 = n.c.

Type RKFV49
Ident-No. 6602198

Connector female flange connector, 7/8''


Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, PUR, black
Screw-in thread seal NBR
Flange housing stainless steel, 1.4401 (316)
Degree of protection IP67, only with screws tightened
Screw-in thread 1/2-14 NPT
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Rated voltage max. 600 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 135 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
RSFV49-0,3M/14,5/C1117

Version: male 7/8" connector


1/2-14 NPT screw-in thread
Stainless steel flange housing
4-pole, litz wire length 0.3 m
33
16 7,5 For FOUNDATION fieldbus appli-
cations
25,4

Pin configuration
26
1/2-14 NPT 7/8" UNC

1 = BU
1 3 2 = BN
2 4 3 = GY
4 = GNYE

Type RSFV49-0,3M/14,5/C1117
Ident-No. 6603396

Connector Male flange connector, 7/8'', with litz wire


FOUNDATION fieldbus connection
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, PUR, black 1=
1 3 2=+
Screw-in thread seal NBR
2 4 3 = shield
Flange housing stainless steel, 1.4401 (316) 4 = n.c.
Degree of protection IP67, only with screws tightened
Screw-in thread 1/2-14 NPT
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Litz wire length 0.3 m


Core insulation material PVC
Core insulation colours BU, BN, GY, GNYE
Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 105 C

136 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
RKFV49-0,3M/14,5

Version: female 7/8" connector


1/2-14 NPT screw-in thread
Stainless steel flange housing

25,5 4-pole, litz wire length 0.3 m


16 For FOUNDATION fieldbus appli-
cations
25,4

Pin configuration
7/8" UNC
1/2-14 NPT 26
v

1 = BU
3 1 2 = BN
4 2 3 = GY
4 = GNYE

Type RKFV49-0,3M/14,5
Ident-No. 6602475

Connector female flange connector, 7/8'', with litz wire FOUNDATION fieldbus connection
Polarity 4-pole
Contacts metal, CuZn, gold-plated v
Contact carriers plastic, PUR, black 1=
Screw-in thread seal NBR 3 1 2=+
4 2 3 = shield
Flange housing stainless steel, 1.4401 (316) 4 = n.c.
Degree of protection IP67, only with screws tightened
Screw-in thread 1/2-14 NPT
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Litz wire length 0.3 m


Core insulation material PVC
Core insulation colours BU, BN, GY, GNYE
Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 105 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 137 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
RSFV49-0,3M/M20/C1117

Version: male 7/8" connector


M20 x 1.5 screw-in thread
Stainless steel flange housing

30
4-pole, litz wire length 0.3 m
10 8 For FOUNDATION fieldbus appli-
cations
25,4

M20 x 1,5 Pin configuration


26 7/8" UNC

1 = BU
1 3 2 = BN
2 4 3 = GY
4 = GNYE

Type RSFV49-0,3M/M20/C1117
Ident-No. 6603583

Connector Male flange connector, 7/8'', with litz wire


FOUNDATION fieldbus connection
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, PUR, black 1=
1 3 2=+
Screw-in thread seal NBR
2 4 3 = shield
Flange housing stainless steel, 1.4401 (316) 4 = n.c.
Degree of protection IP67, only with screws tightened
Screw-in thread M20 x 1,5
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Litz wire length 0.3 m


Core insulation material PVC
Core insulation colours BU, BN, GY, GNYE
Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 105 C

138 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
RKFV49-0,3M/M20

Version: female 7/8" connector


M20 x 1.5 screw-in thread
Stainless steel flange housing
4-pole, litz wire length 0.3 m
19,5
10 For FOUNDATION fieldbus appli-
cations
25,4

Pin configuration
M20 x 1,5 7/8" UNC
26
v

1 = BU
3 1 2 = BN
4 2 3 = GY
4 = GNYE

Type RKFV49-0,3M/M20
Ident-No. 6603584

Connector female flange connector, 7/8'', with litz wire FOUNDATION fieldbus connection
Polarity 4-pole
Contacts metal, CuZn, gold-plated v
Contact carriers plastic, PUR, black 1=
Screw-in thread seal NBR 3 1 2=+
4 2 3 = shield
Flange housing stainless steel, 1.4401 (316) 4 = n.c.
Degree of protection IP67, only with screws tightened
Screw-in thread M20 x 1,5
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Litz wire length 0.3 m


Core insulation material PVC
Core insulation colours BU, BN, GY, GNYE
Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 105 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 139 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
FSV49

Version: M12 connector


PG 9 screw-in thread
Stainless steel flange housing
4-pole, solderable
For use in Foundation fieldbus
PG 9 18 M12 x 1 and PROFIBUS-PA applications

6 FOUNDATION fieldbus connection


19

2 1=
2=+
3 1 3 = shield
4 4 = n.c.

Type FSV49
Ident-No. 6604378

Connector Male flange connector, M12 x 1


PROFIBUS-PA connection
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, PA, black 2 1=+
Screw-in thread seal plastic 3 1 2 = ground
3=
Flange housing stainless steel, 1.4401 (316) 4 4 = shield
Degree of protection IP67, only with screws tightened
Screw-in thread PG 9
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Rated voltage max. 250 V


Insulation resistance 109
Ampacity 4A
Forward resistance 5 m
Ambient temperature Connector -40 + 90 C

140 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
FKV49

Version: female M12 connector


PG 9 screw-in thread
Stainless steel flange housing
4-pole, solderable
For use in Foundation fieldbus
PG 9 18 M12 x 1 and PROFIBUS-PA applications
13,5

7 FOUNDATION fieldbus connection


21
v
2 1=
2=+
1 3 3 = shield
4 4 = ground

Type FKV49
Ident-No. 6603426

Connector female flange connector, M12 x 1


PROFIBUS-PA connection
Polarity 4-pole
v
Contacts metal, CuZn, gold-plated
Contact carriers plastic, PA, black 2 1=+
Screw-in thread seal plastic 2 = ground
1 3 3=
Flange housing stainless steel, 1.4401 (316) 4 4 = shield
Degree of protection IP67, only with screws tightened
Screw-in thread PG 9
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Rated voltage max. 250 V


Insulation resistance 109
Ampacity 4A
Forward resistance 5 m
Ambient temperature Connector -40 + 90 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 141 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
FSV49-0,3M/14,5/C1117

Version: M12 connector


1/2-14 NPT screw-in thread
Stainless steel flange housing

31
4-pole, litz wire length 0.3 m
15 For FOUNDATION fieldbus appli-
cations

Pin configuration
1/2-14 NPT 26 M12 x 1

2 1 = BU
3 1 2 = BN
3 = GY
4 4 = GNYE

Type FSV49-0,3M/14,5/C1117
Ident-No. 6602107

Connector Male flange connector, M12 x 1, with litz


FOUNDATION fieldbus connection
wire
Polarity 4-pole
Contacts metal, CuZn, gold-plated 2 1=
2=+
Contact carriers plastic, PA, black 3 1 3 = shield
Screw-in thread seal plastic 4 4 = n.c.
Flange housing stainless steel, 1.4401 (316)
Degree of protection IP67, only with screws tightened
Screw-in thread 1/2-14 NPT
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Litz wire length 0.3 m


Core insulation material PVC
Core insulation colours BU, BN, GY, GNYE
Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 105 C

142 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
FKV49-0,3M/14,5/C1117

Version: female M12 connector


1/2-14 NPT screw-in thread
Stainless steel flange housing
4-pole, litz wire length 0.3 m
30
14 For FOUNDATION fieldbus appli-
cations

M12 x 1 Pin configuration


1/2-14 NPT 26
v
2 1 = BU
1 3 2 = BN
3 = GY
4 4 = GNYE

Type FKV49-0,3M/14,5/C1117
Ident-No. 6603298

Connector female flange connector, M12 x 1, with litz


FOUNDATION fieldbus connection
wire
v
Polarity 4-pole
Contacts metal, CuZn, gold-plated 2 1=
2=+
Contact carriers plastic, PA, black 1 3 3 = shield
Screw-in thread seal plastic 4 4 = n.c.
Flange housing stainless steel, 1.4401 (316)
Degree of protection IP67, only with screws tightened
Screw-in thread 1/2-14 NPT
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Litz wire length 0.3 m


Core insulation material PVC
Core insulation colours BU, BN, GY, GNYE
Core cross-section 4 x 0.8 mm2

Rated voltage max. 300 V


Insulation resistance 109
Ampacity 4A
Forward resistance 5 m
Ambient temperature Connector -40 + 105 C
7

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 143 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
FSV49-0,3M/M20/C1117

Version: M12 connector


M20 x 1.5 screw-in thread
Stainless steel flange housing
25 4-pole, litz wire length 0.3 m
15 For FOUNDATION fieldbus appli-
cations

Pin configuration
M20 x 1,5 26 M12 x 1

2 1 = BU
3 1 2 = BN
3 = GY
4 4 = GNYE

Type FSV49-0,3M/M20/C1117
Ident-No. 6603682

Connector Male flange connector, M12 x 1, with litz


FOUNDATION fieldbus connection
wire
Polarity 4-pole
Contacts metal, CuZn, gold-plated 2 1=
2=+
Contact carriers plastic, PA, black 3 1 3 = shield
Screw-in thread seal plastic 4 4 = n.c.
Flange housing stainless steel, 1.4401 (316)
Degree of protection IP67, only with screws tightened
Screw-in thread M20 x 1,5
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Litz wire length 0.3 m


Core insulation material PVC
Core insulation colours BU, BN, GY, GNYE
Core cross-section 4 x 0.8 mm2

Rated voltage max. 600 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 105 C

144 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Flange connector
FKV49-0,3M/M20/C1117

Version: female M12 connector


M20 x 1.5 screw-in thread
Stainless steel flange housing
24 4-pole, litz wire length 0.3 m
14 For FOUNDATION fieldbus appli-
cations

M12 x 1 Pin configuration


M20 x 1,5 26
v
2 1 = BU
1 3 2 = BN
3 = GY
4 4 = GNYE

Type FKV49-0,3M/M20/C1117
Ident-No. 6603683

Connector female flange connector, M12 x 1, with litz


FOUNDATION fieldbus connection
wire
v
Polarity 4-pole
Contacts metal, CuZn, gold-plated 2 1=
2=+
Contact carriers plastic, PA, black 1 3 3 = shield
Screw-in thread seal plastic 4 4 = n.c.
Flange housing stainless steel, 1.4401 (316)
Degree of protection IP67, only with screws tightened
Screw-in thread M20 x 1,5
Mechanical lifespan min. 100 Contact durability
Pollution degree 3

Litz wire length 0.3 m


Core insulation material PVC
Core insulation colours BU, BN, GY, GNYE
Core cross-section 4 x 0.8 mm2

Rated voltage max. 300 V


Insulation resistance 109
Ampacity 4A
Forward resistance 5 m
Ambient temperature Connector -40 + 105 C
7

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 145 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BS4140-0/9

Version: Connector
Round connector 7/8"
Field-wireable
Screw/terminal connection
6...8
84
4-pole, straight anodised aluminium
coupling nut
28 Cable exit 6 8 mm
For use in PROFIBUS-PA and
7/8-16UN FOUNDATION fieldbus applicati-
ons and and as auxiliary supply for
DeviceNet slaves

PROFIBUS-PA connection

Type BS4140-0/9
Ident-No. 6914550 1=+
1 3 2 = n.c.
2 4 3=
Connector field-wireable male connector, 7/8'', straight 4 = shield
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, TPU, black
Grip plastic, PA, black
Coupling nut/screw metal, Al, anodized FOUNDATION fieldbus connection
Seal plastic, NBR
Screw-in thread seal plastic, NBR
Degree of protection IP67, only with screws tightened 1=
External diameter of the cable 6 8 mm 1 3 2=+
2 4 3 = shield
Core cross-section/Clamping ability max. 1 mm2 4 = n.c.
Screw-in thread PG 9
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 250 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 90 C

146 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BK4140-0/9

Version: female connector


Round connector 7/8"
Field-wireable
Screw/terminal connection
6...8 4-pole, straight anodised aluminium
85 coupling nut
Cable exit 6 8 mm
27
For use in PROFIBUS-PA and
FOUNDATION fieldbus applicati-
7/8-16UN onsand and as auxiliary supply for
DeviceNet slaves

PROFIBUS-PA connection

v
Type BK4140-0/9
Ident-No. 6914551 1=+
3 1 2 = n.c.
4 2 3=
Connector field-wireable female connector, 7/8'', 4 = shield
straight
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, TPU, black
Grip plastic, PA, black FOUNDATION fieldbus connection
Coupling nut/screw metal, Al, anodized
Seal plastic, NBR v
Screw-in thread seal plastic, NBR 1=
Degree of protection IP67, only with screws tightened 3 1 2=+
4 2 3 = shield
External diameter of the cable 6 8 mm 4 = n.c.
Core cross-section/Clamping ability max. 1 mm2
Screw-in thread PG 9
Connection mode Screw terminals
Pollution degree 3
Voltage supply
Rated voltage max. 250 V
Insulation resistance 109 v
Ampacity 9A
1 = RD (Aux +)
Forward resistance 5 m 3 1 2 = GN (E +)
Ambient temperature Connector -40 + 90 C 4 2 3 = WH (E )
4 = BK (Aux )

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 147 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BSV4140-0/9

Version: Connector
Round connector 7/8"
Field-wireable
Screw/terminal connection
6...8
84
4-pole, straight, stainless steel cou-
pling nut
28 Cable exit 6 8 mm
For use in PROFIBUS-PA and
7/8-16UN FOUNDATION fieldbus applicati-
ons

PROFIBUS-PA connection

Type BSV4140-0/9 1=+


1 3 2 = n.c.
Ident-No. 6914542
2 4 3=
4 = shield
Connector field-wireable male connector, 7/8'', straight
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, TPU, black
Grip plastic, PA, black FOUNDATION fieldbus connection
Coupling nut/screw stainless steel, 1.4404
Seal plastic, NBR
Screw-in thread seal plastic, NBR
1=
Degree of protection IP67, only with screws tightened 1 3 2=+
External diameter of the cable 6 8 mm 2 4 3 = shield
4 = n.c.
Core cross-section/Clamping ability max. 1 mm2
Screw-in thread PG 9
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 250 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 90 C

148 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BKV4140-0/9

Version: female connector


Round connector 7/8"
Field-wireable
Screw/terminal connection
6...8 4-pole, straight, stainless steel cou-
80 pling nut
28 Cable exit 6 8 mm
For use in PROFIBUS-PA and
7/8-16UN FOUNDATION fieldbus applicati-
ons

PROFIBUS-PA connection

v
Type BKV4140-0/9 1=+
3 1 2 = n.c.
Ident-No. 6914543
4 2 3=
4 = shield
Connector field-wireable female connector, 7/8'',
straight
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, TPU, black FOUNDATION fieldbus connection
Grip plastic, PA, black
Coupling nut/screw stainless steel, 1.4404 v
Seal plastic, NBR
1=
Screw-in thread seal plastic, NBR 3 1 2=+
Degree of protection IP67, only with screws tightened 4 2 3 = shield
4 = n.c.
External diameter of the cable 6 8 mm
Core cross-section/Clamping ability max. 1 mm2
Screw-in thread PG 9
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 240 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 90 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 149 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BSV4140-0/13.5

Version: Connector
Round connector 7/8"
Field-wireable
Screw/terminal connection
10...12
84 4-pole, straight, stainless steel cou-
pling nut
28 Cable exit 10 12 mm

7/8-16UN
For use in PROFIBUS-PA and
FOUNDATION fieldbus applicati-
ons

PROFIBUS-PA connection

Type BSV4140-0/13.5 1=+


1 3 2 = n.c.
Ident-No. 6914562
2 4 3=
4 = shield
Connection mode Screw terminals
Junction box field-wireable male connector, 7/8'', straight
Polarity 4-pole
Grip plastic, PA, black
Contact carriers plastic, TPU, black FOUNDATION fieldbus connection
Contacts metal, CuZn, gold-plated
Coupling nut/screw stainless steel, 1.4404
Seal plastic, NBR
1=
1 3 2=+
Degree of protection IP67, only with screws tightened 2 4 3 = shield
4 = n.c.
Pollution degree 3

External diameter of cable max. 12 mm

Rated voltage max. 250 V


Ampacity 9A
Forward resistance 5 m
Insulation resistance 109
Ambient temperature junction -40 + 90 C

150 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BKV4140-0/13.5

Version: female connector


Round connector 7/8"
Field-wireable
10...12 Screw/terminal connection
80
4-pole, straight, stainless steel cou-
pling nut
28
Cable exit 10 12 mm
7/8-16UN For use in PROFIBUS-PA and
FOUNDATION fieldbus applicati-
ons

PROFIBUS-PA connection

v
Type BKV4140-0/13.5 1=+
3 1 2 = n.c.
Ident-No. 6914563
4 2 3=
4 = shield
Connector field-wireable female connector, 7/8'',
straight
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, TPU, black FOUNDATION fieldbus connection
Grip plastic, PA, black
Coupling nut/screw stainless steel, 1.4404 v
Seal plastic, NBR
1=
Screw-in thread seal plastic, NBR 3 1 2=+
Degree of protection IP67, only with screws tightened 4 2 3 = shield
4 = n.c.
External diameter of the cable 10 12 mm
Core cross-section/Clamping ability max. 1 mm2
Screw-in thread PG 13,5
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 240 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 90 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 151 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BSV4140-0/16

Version: Connector
Round connector 7/8"
Field-wireable
Screw/terminal connection
12...14
88 4-pole, straight, stainless steel cou-
pling nut
28 Cable exit 12 14 mm

7/8-16UN
For use in PROFIBUS-PA and
FOUNDATION fieldbus applicati-
ons

PROFIBUS-PA connection

Type BSV4140-0/16 1=+


1 3 2 = n.c.
Ident-No. 6914541
2 4 3=
4 = shield
Connector field-wireable male connector, 7/8'', straight
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, TPU, black
Grip plastic, PA, black FOUNDATION fieldbus connection
Coupling nut/screw stainless steel, 1.4404
Seal plastic, NBR
Screw-in thread seal plastic, NBR
1=
Degree of protection IP67, only with screws tightened 1 3 2=+
External diameter of the cable 12 14 mm 2 4 3 = shield
4 = n.c.
Core cross-section/Clamping ability max. 1 mm2
Screw-in thread PG 16
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 250 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 90 C

152 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BKV4140-0/16

Version: female connector


Round connector 7/8"
Field-wireable
Screw/terminal connection
12...14
85 4-pole, straight, stainless steel cou-
pling nut
28 Cable exit 12 14 mm
For use in PROFIBUS-PA and
7/8-16UN
FOUNDATION fieldbus applicati-
ons

PROFIBUS-PA connection

v
Type BKV4140-0/16 1=+
3 1 2 = n.c.
Ident-No. 6914544
4 2 3=
4 = shield
Connector field-wireable female connector, 7/8'',
straight
Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, TPU, black FOUNDATION fieldbus connection
Grip plastic, PA, black
Coupling nut/screw stainless steel, 1.4404 v
Seal plastic, NBR
1=
Screw-in thread seal plastic, NBR 3 1 2=+
Degree of protection IP67, only with screws tightened 4 2 3 = shield
4 = n.c.
External diameter of the cable 12 14 mm
Core cross-section/Clamping ability max. 1 mm2
Screw-in thread PG 16
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 240 V


Insulation resistance 109
Ampacity 9A
Forward resistance 5 m
Ambient temperature Connector -40 + 90 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 153 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BSV8140-0/9

Version: M12 connector


Field-wireable
4-pole, straight, stainless steel cou-
pling nut
4...8 Cable exit 4.0 8.0 mm
60
For use in PROFIBUS-PA and
21
FOUNDATION fieldbus applicati-
ons

M12 x 1 19
PROFIBUS-PA connection

2 1=+
3 1 2 = n.c.
3=
4 4 = shield
Type BSV8140-0/9
Ident-No. 6914537

Connector field-wireable male connector, M12 x 1,


straight FOUNDATION fieldbus connection
Polarity 4-pole
Contacts metal, CuZn,CuSnZn, Optalloy coated
Contact carriers plastic, PA, black
2 1=
Grip plastic, PA, black
2=+
Coupling nut/screw stainless steel, 1.4404 3 1 3 = shield
4 4 = n.c.
Seal plastic, FKM/FPM
Screw-in thread seal plastic, NBR
Degree of protection IP67, only with screws tightened
External diameter of the cable 4 8 mm
Core cross-section/Clamping ability 0.14 0.75 mm2
Screw-in thread PG 9
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 250 V


Insulation resistance 109
Ampacity 4A
Forward resistance 5 m
Ambient temperature Connector -25 + 90 C

154 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BKV8140-0/9

Version: female M12 connector


Field-wireable
4-pole, straight, stainless steel cou-
pling nut
4...8 Cable exit 4.0 8.0 mm
55
For use in PROFIBUS-PA and
FOUNDATION fieldbus applicati-
21 ons

M12 x 1 19
PROFIBUS-PA connection

v
2 1=+
2 = n.c.
1 3 3=
4 4 = shield
Type BKV8140-0/9
Ident-No. 6914538

Connector field-wireable female connector, M12 x 1,


straight FOUNDATION fieldbus connection
Polarity 4-pole
Contacts metal, CuZn,CuSnZn, Optalloy coated v
Contact carriers plastic, PA, black
2 1=
Grip plastic, PA, black
2=+
Coupling nut/screw stainless steel, 1.4404 1 3 3 = shield
4 4 = n.c.
Seal plastic, FKM/FPM
Screw-in thread seal plastic, NBR
Degree of protection IP67, only with screws tightened
External diameter of the cable 4 8 mm
Core cross-section/Clamping ability 0.14 0.75 mm2
Screw-in thread PG 9
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 250 V


Insulation resistance 109
Ampacity 4A
Forward resistance 5 m
Ambient temperature Connector -25 + 90 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 155 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BSV8240-0/9

Version: M12 connector


Field-wireable
4-pole, angled, stainless steel cou-
pling nut
40
Cable exit 48 mm
19
For use in PROFIBUS-PA and
21 FOUNDATION fieldbus applicati-
40
ons
M12 x 1

PROFIBUS-PA connection
4...8

2 1=+
3 1 2 = n.c.
3=
4 4 = shield
Type BSV8240-0/9
Ident-No. 6914539

Connector field-wireable male connector, M12 x 1,


angled FOUNDATION fieldbus connection
Polarity 4-pole
Contacts metal, CuZn,CuSnZn, Optalloy coated
Contact carriers plastic, PA, black
2 1=
Grip plastic, PA, black
2=+
Coupling nut/screw stainless steel, 1.4404 3 1 3 = shield
4 4 = n.c.
Seal plastic, FKM/FPM
Screw-in thread seal plastic, NBR
Degree of protection IP67, only with screws tightened
External diameter of the cable 4 8 mm
Core cross-section/Clamping ability 0.14 0.75 mm2
Screw-in thread PG 9
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 250 V


Insulation resistance 109
Ampacity 4A
Forward resistance 5 m
Ambient temperature Connector -25 + 90 C

156 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Field wireable connectors
BKV8240-0/9

Version: female M12 connector


Field-wireable
4-pole, angled, stainless steel cou-
pling nut
35
19
Cable exit 4.0 8.0 mm
For use in PROFIBUS-PA and
21 FOUNDATION fieldbus applicati-
40 ons
M12 x 1

PROFIBUS-PA connection
4...8
v
2 1=+
2 = n.c.
1 3 3=
4 4 = shield
Type BKV8240-0/9
Ident-No. 6914540

Connector field-wireable female connector, M12 x 1,


angled FOUNDATION fieldbus connection
Polarity 4-pole
Contacts metal, CuZn,CuSnZn, Optalloy coated v
Contact carriers plastic, PA, black
2 1=
Grip plastic, PA, black
2=+
Coupling nut/screw stainless steel, 1.4404 1 3 3 = shield
4 4 = n.c.
Seal plastic, FKM/FPM
Screw-in thread seal plastic, NBR
Degree of protection IP67, only with screws tightened
External diameter of the cable 4 8 mm
Core cross-section/Clamping ability 0.14 0.75 mm2
Screw-in thread PG 9
Connection mode Screw terminals
Pollution degree 3

Rated voltage max. 250 V


Insulation resistance 109
Ampacity 4A
Forward resistance 5 m
Ambient temperature Connector -25 + 90 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 157 /0309
FOUNDATION fieldbus
Bus termination resistors

Data transmission on bus cables is TURCK offers plug-in termination


frequently influenced by signal reflection, resistors, type M12 1 and 7/8, for
which can occur when the bus ends are intrinsically safe and non-intrinsically safe
not terminated. circuits.
The fieldbus must be provided with a
termination resistor at both ends in order
to avoid signal reflection.

Specification

Connector PUR housing material and contact carriers, oil resistant, 300 V rating
Coupling nut stainless steel
Protection degree (IEC 60529/EN 60529) IP67 and NEMA 1, 3, 4, 6P
Max. ratings
RSV49-TR, RSEV49-TR Umax = 50 VDC
Ta = -40...+80 C
RSV-49-TR-Ex Ui = 25 VDC, Ii = 250 mA, Pi =1.2 W
Ta = -40...70 C (EEx ia IIC T4)
-40...40 C (EEx ia IIC T6)

Use of the intrinsically-safe version In zone 0 the power supply circuit must
The intrinsically-safe fieldbus termination conform to protection class ia.
resistors feature protection class intrinsic
safety and may be used in the explosion The RS-49-TR-Ex termination resistor can
hazardous area category 1 G (zone 0), be used in networks, which are designed
2 G (zone 1) or 3 G (zone 2). conform to the FISCO model.

CAUTION NOTE
The EC type test The TURCK JBBS...
examination junctions to IP67
certificate and the (4 and 6 ports) and
manufacturers declaration JRBS... to IP20 are already
of conformity must be provided with integrated
observed. switch-in bus termination
It is essential that the resistors.
special conditions in the Special versions excepted.
EU type test examination
certificate are observed.

158 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Bus termination resistor
RSV49-TR

Version: male 7/8" connector


4-pole, straight, stainless steel cou-
pling nut
For use in FOUNDATION fieldbus
applications
48,5 7/8-16UN

26,0 Wiring diagram


1 3
1 F
36,0 2 4
100 W

Type RSV49-TR
Ident-No. 6602094

Connector Connector, 7/8''


Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, PUR, black
Grip plastic, PUR, yellow
Coupling nut/screw stainless steel, 1.4404
Degree of protection IP67, only with screws tightened
Ambient temperature -40+ 70 C

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 159 /0309
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Bus termination resistor
RSEV49-TR

Version: M12 connector


4-pole, straight, stainless steel cou-
pling nut
For use in FOUNDATION fieldbus
applications
12,5
M12 x 1

14,2 Wiring diagram


4
4,0 18,0
48,5 1
3
1 F
100 W 2

Type RSEV49-TR
Ident-No. 6602096

Connector Connector, M12 x 1


Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, PUR, black
Grip plastic, PUR, black
Coupling nut/screw stainless steel, 1.4404
Degree of protection IP67, only with screws tightened
Ambient temperature -40+ 70 C

160 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Edition:
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

Accessories for fieldbus systems


Bus termination resistor
RSV-49TR-EX

FISCO compliant according to IEC


TS 60079-27
Version: male 7/8" connector
4-pole, straight, stainless steel cou-
pling nut
48,5 7/8-16UN
For use in FOUNDATION fieldbus
applications
26,0

Wiring diagram
36,0
1 3
1 F
2 4
100 W

Type RSV-49TR-EX
Ident-No. 6602709

Connector Connector, M12 x 1


Polarity 4-pole
Contacts metal, CuZn, gold-plated
Contact carriers plastic, PUR, black
Grip plastic, PUR, blue
Coupling nut/screw stainless steel, 1.4404
Degree of protection IP67, only with screws tightened
Ambient temperature -40+ 70 C

Ex approval acc. to conformity certificate TV 03 ATEX 2379 X


Max. input voltage Ui 25 V
Max. input current Ii 250 mA
Max. input power Pi 1200 mW
External inductance/capacitance Li/Ci negligible

Device designation II 1 G EEx ia IIC T6


FISCO / Entity field device

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 161 /0309
Accessories for fieldbus systems
IP67 stainless steel housing
EG-VA2020/BV67-T105

accessories for fieldbus systems


IP67 stainless steel housing
EG-VA2020/BV67-T105
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

The stainless steel housing EG-VA2020/ with ten M20 1.5-cable glands.
BV67-T105 is suited for the integration of Stainless steel housing to accom-
TURCK junction boxes JRBS- With a pressure compensation element modate the TURCK IP20 junction
(Protection degree IP67) a continuous and modules
The robust model is especially suited for reliable ventilation is ensured. This way con- Protection degree IP67
rough and aggressive environmental condi- densation and accumulation of water is (IEC/EN 60529)
tions. avoided. 10 plastic cable glands M20 x 1.5
for cable guides
Inside the housing a hat rail is located used Note: Ensure sufficient equipotential bon- Insulated shield terminals
for retaining a 4, 6 or 8 port JRBS junction ding of the installation. The housing is con-
box with a maximum width of 180 mm. nected to the equipotential bond via an M5 Wall mounting
x 1 connector. Pressure compensation element
Connection of the housing potential
The connection of the cables is attained via an M5 x 1 bolt

162 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Accessories for fieldbus systems
IP67 stainless steel housing
EG-VA2020/BV67-T105

Type EG-VA2020/BV67-T105
Ident-No. 6884135
Dimensions

Electrical connection cable glands


10 x M20 x 1.5 ( 613mm); plastic, black
Earthing bolt M5 x 1

Degree of protection IP67 M5 x 12


Ambient temperature -30 + 80 C
Relative humidity 95 %, non condensing
80,5
Housing material Stainless steel 1.430/AISI304
90
Wall thickness 1.5 mm
200
Housing surface grinded and polished (240 grain size distribu- 160
tion) 220,1
Housing color silver
Sealing material PUR
Dimensions 200 x 200 x 80.5 mm
Connection mode Wall mounting

10

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 163 /0309
Accessories for fieldbus systems
IP67 stainless steel housing
EG-VA2020/BV67-T103

accessories for fieldbus systems


IP67 stainless steel housing
EG-VA2020/BV67-T103
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com

The stainless steel housing EG-VA2020/ with ten M20 1.5-cable glands.
BV67-T103 is suited for the integration of Stainless steel housing to accom-
TURCK junction boxes JRBS- With a pressure compensation element modate the TURCK IP20 junction
(Protection degree IP67) a continuous and modules
The robust model is especially suited for reliable ventilation is ensured. This way con- Protection degree IP67
rough and aggressive environmental condi- densation and accumulation of water is (IEC/EN 60529)
tions. avoided. 10 stainless steel cable glands
M20 x 1.5 for cable guides
Inside the housing a hat rail is located used Note: Ensure sufficient equipotential bon- Insulated shield terminals
for retaining a 4, 6 or 8 port JRBS junction ding of the installation. The housing is con-
box with a maximum width of 180 mm. nected to the equipotential bond via an M5 Wall mounting
x 1 connector. Pressure compensation element
Connection of the housing potential
The connection of the cables is attained via an M5 x 1 bolt

164 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Accessories for fieldbus systems
IP67 stainless steel housing
EG-VA2020/BV67-T103

Type EG-VA2020/BV67-T103
Ident-No. 6884136
Dimensions

Electrical connection cable glands


10 x M20 x 1.5 ( 613mm); stainless steel
Earthing bolt M5 x 1

Degree of protection IP67 M5 x 12


Ambient temperature -30 + 80 C
Relative humidity 95 %, non condensing
80,5
Housing material Stainless steel 1.430/AISI304
90
Wall thickness 1.5 mm
200
Housing surface grinded and polished (240 grain size distribu- 160
tion) 220,1
Housing color silver
Sealing material PUR
Dimensions 200 x 200 x 80.5 mm
Connection mode Wall mounting

10

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 165 /0309
FOUNDATION fieldbus
Accessories for fieldbus systems

Dimensions Application Type designation Ident-No.

Stripping the insulation from round (shielded) data cables TCS wire stripping tool 6900454
from 2.5...8 mm (also for FastConnect/
Fast Assembly),
1, 2 and 3-stage cable stripping in a single operation;
Adjustment block provided for fast preadjustment of the
depth, cutting edges can be used on both sides

Special tool for cable glands on multibarriers, excom- VSTS22 (AF 22) 6884043
1
housings ) and junctions. VSTS24 (AF 24) 6900462
Open and close cable glands from various positions. Also VSTS27 (AF 27) 6884073
work in difficult positions using the swivelling handle. Use is sim-
plified by the slot provided in the tube (the cables fed through
the cable gland are pushed through the slot on the tube). Tool
sizes 22, 24 and 27, special sizes are
22, 24, 27 available on request

1
) excom is the TURCK Ex remote I/O system for use in zones 1 and 2. More detailed information can be found in the product catalog.

166 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Dimensions Application Material and Type designation Ident-No.
colour

7/8 end cap, male, stainless steel RSMV-BC 6603783


7/8-16UN
25 oil resistant, IP67 to IEC 60529/
EN 60529 and NEMA 1, 3, 4, 6P

7
19,5

7/8 end cap, female, stainless steel RKMV-BC 6603784


25
7/8-16UN
oil resistant, IP67 to IEC 60529/
EN 60529 and NEMA 1, 3, 4, 6P

16,5

7/8-16UN
7/8 end cap, male, stainless steel RSMV-CC 6604030
25
oil resistant, IP67 to IEC 60529/
EN 60529 and NEMA 1, 3, 4, 6P,
7
24
with wire rope

25 7/8 end cap, female, stainless steel RKMV-CC 6604038


7/8-16UN

oil resistant, IP67 to IEC 60529/


EN 60529 and NEMA 1, 3, 4, 6P,

21,3
with wire rope

7/8-16UN 7/8 end cap, male, stainless steel RSMV-CCC 6604490


25
oil resistant, IP67 to IEC 60529/
EN 60529 and NEMA 1, 3, 4, 6P,
7 with chain, approx. 210 mm,
24
closure closed

7/8 end cap, male, stainless steel RKMV-CCC 6604488


25
7/8-16UN
oil resistant, IP67 to IEC 60529/
EN 60529 and NEMA 1, 3, 4, 6P,

21,3
with chain, approx. 210 mm,
closure closed
10

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 167 /0309
FOUNDATION fieldbus
Accessories for fieldbus systems

Dimensions Application Material and Type designation Ident-No.


colour

7/8-16UN
7/8 end cap, male, stainless steel RSMV-CCO 6604489
25
oil resistant, IP67 to IEC 60529/
EN 60529 and NEMA 1, 3, 4, 6P,
7
24 with chain, approx. 210 mm,
closure open

25 7/8 end cap, female, stainless steel RKMV-CCO 6604485


7/8-16UN
oil resistant, IP67 to IEC 60529/
EN 60529 and NEMA 1, 3, 4, 6P,

21,3
with chain, approx. 210 mm,
closure open

M12 1 end cap, male, stainless steel RSEV-BC 6902305


M12 x 1
oil resistant, IP67 to IEC 60529/
16,3
EN 60529 and NEMA 1, 3, 4, 6P

9,5
16

M12 1 end cap, female, stainless steel RKEV-BC 6902304


15
M12 x 1 oil resistant, IP67 to IEC 60529/
16,3
EN 60529 and NEMA 1, 3, 4, 6P

16

M12 x 1
M12 1 end cap, male, stainless steel RSEV-CC 6604174
16,3
oil resistant, IP67 to IEC 60529/
9,5 EN 60529 and NEMA 1, 3, 4, 6P,
20,2
with chain

15 M12 1 end cap, female, stainless steel RKEV-CC 6604176


M12 x 1
16,3
oil resistant, IP67 to IEC 60529/
EN 60529 and NEMA 1, 3, 4, 6P,
20 with chain

168 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
Dimensions Application Material and Type designation Ident-No.
colour

7/8-16UN 28 Screw-on cap for 7/8 female connectors, polyamide VZ8 8018816
no internal wiring black
24

12
18

24 7/8-16UN 28
Screw-on cap for 7/8 male connectors, polyamide VK-7/8 6999027
no internal wiring black
24

12
18

Dust cap for 7/8 flange fitting, polyamide RSM-DUST-CAP 6914862


for male flanges, no internal wiring black
21,8

1,5

12,7

Dust cap for 7/8 flange fitting, polyamide RKM-DUST-CAP 6914863


for female flanges, no internal wiring black
24,8

1,5

12,7

16 M12 x 1 M12 1 end cap, male, PUR VS-M12 6999003


oil resistant, IP54 to IEC 60529/ yellow
EN 60529 and NEMA 1, 3, 4, 6P

9
14

16
M12 1 end cap, female, PUR VK-M12 6999025
oil resistant, IP54 to IEC 60529/ yellow

M12 x 1
EN 60529 and NEMA 1, 3, 4, 6P 10
14

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 169 /0309
FOUNDATION fieldbus
Accessories for fieldbus systems

Dimensions Application Material and Type designation Ident-No.


colour/
Connection
technology
Fig. ( Fxxx )

12,5
M12 x 1
M12 1 end cap, male stainless steel/PUR RSEV49-CC 6603489
oil resistant, IP67 to IEC 60529/ grey
14,2
EN 60529 and NEMA 1, 3, 4, 6P
4,0 18,0
48,5

7/8 feed-through receptacles, male/fe- 1 7/8 ( F015 ) RSFV-RKFV49/22 6602357


49.2
32.7 male, IP67 to IEC 60529/EN 60529 and 1 7/8 ( F016 )
NEMA 1, 3, 4, 6, stainless steel
7/8-16UN

7/8-16UN
locknut sealing gasket
lockwasher thrust washer

47.4 M12 1 feed-through receptacles, male/ 1 M12 ( F040 ) FKV-FSV49/M12 6603678


29.4
O-ring
female, IP67 to IEC 60529/EN 60529 and 1 M12 ( F041 )
NEMA 1, 3, 4, 6, stainless steel
M12 x 1

M12 x 1
locknut lockwasher
LN-M12 LW-M12

Pin assignment ( F015 ) ( F016 ) ( F040 ) ( F041 )

w v w v
2 2
1 3 3 1
3 1 1 3
2 4 4 2
4 4
1 = 1 = 1 = 1 =
2 =+ 2 =+ 2 =+ 2 =+
3 = shield 3 = shield 3 = shield 3 = shield
4 = earth 4 = earth 4 = earth 4 = earth

170 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
10

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 171 /0309
Type index

Type designation Page Type designation Page Type designation Page

BK4140-0/9 147 JBBS-49-T615/3G 68 RSV49-TR 159


BKV4140-0/13.5 151 JBBS-49-T615B/Ex 80 RSV-49TR-Ex 161
BKV4140-0/16 153 JRBS-40-12C/Ex 112 RSV-FBY49x-*M/5D 131
BKV4140-0/9 149 JRBS-40-4C/Ex 106 RSV-RKV492A-*M 132
BKV8140-0/9 155 JRBS-40-6C/Ex 108 RSV-RKV492BA-*M 132
BKV8240-0/9 157 JRBS-40-8C/Ex 110 RSV-RKV-FBY49x-*M/5D 131
BS4140-0/9 146 JRBS-40-12R/Ex 120 RSV-RSV-FBY49x-*M/5D 131
BS8149-0/9 144 JRBS-40-4R/Ex 114 TCS wire stripping tool 166
BSV4140-0/13.5 150 JRBS-40-6R/Ex 116 VK-7/8 169
BSV4140-0/16 152 JRBS-40-8R/Ex 118 VK-M12 169
BSV4140-0/9 148 JRBS-40SC-12C/Ex 96 VS-M12 169
BSV8140-0/9 154 JRBS-40SC-4C/Ex 90 VSTS22 166
BSV8240-0/9 156 JRBS-40SC-6C/Ex 92 VSTS24 166
Cable 492AM 128 JRBS-40SC-8C/Ex 94 VSTS27 166
Cable 492BAM 128 JRBS-40SC-12R/Ex 104 VZ8 169
Cable FB4910-BK...M 129 JRBS-40SC-4R/Ex 98 WKCV-FBY49x-*M/5D 131
Cable FBA-YE/SDM 127 JRBS-40SC-6R/Ex 100 WKCV-WKCV-FBY49x-*M/5D 131
Cable FBH-YE/SDM 126 JRBS-40SC-8R/Ex 102 WKV-FBY49x-*M/5D 131
Cable FBY-.../SDM 124 MBD49-T415/Ex 34 WKV-WKV-FBY49x-*M/5D 131
Cable FBY-BK/LDM 125 PSU-3214 26 WSCV-FBY49x-*M/5D 131
DPC-49-1-RMB 14 RKCV-FBY49x-*M/5D 131 WSCV-WKCV-FBY49x-*M/5D 131
DPC-49-4-RMB 10 RKCV-RKCV-FBY49x-*M/5D 131 WSCV-WSCV-FBY49x-*M/5D 131
DPC-49-4-RMB/SY 12 RKEV-BC 168 WSV-FBY49x-*M/5D 131
DPC-49-ADU 20 RKEV-CC 168 WSV-WKV-FBY49x-*M/5D 131
DPC-49-DU 18 RKFV49 135 WSV-WSV-FBY49x-*M/5D 131
DPC-49-HSEFD/24VDC 22 RKFV49-0,3M/14,5 137
DPC49-IPS1 16 RKFV49-0,3M/M20 139
EG-VA2020/BV67-T103 164 RKM-DUST-CAP 169
EG-VA2020/BV67-T105 162 RKMV-BC 167
FD-49-T317/Ex 36 RKMV-CC 167
FKV49 141 RKMV-CCC 167
FKV49-0,3M/14,5/C1117 143 RKMV-CCO 168
FKV49-0,3M/M20/C1117 145 RKV492A-*M 132
FKV-FSV49/M12 170 RKV492BA-*M 132
FSV49 140 RKV-FBY49x-*M/5D 131
FSV49-0,3M/14,5/C1117 142 RKV-RKV-FBY49x-*M/5D 131
FSV49-0,3M/M20/C1117 144 RPC49-10120Ex 28
JBBS-49-E413/3G 70 RPC49-10265Ex 30
JBBS-49-E413/Ex 82 RPC49-205 24
JBBS-49-E613/3G 72 RSCV-2RKCV49 41
JBBS-49-E613/Ex 84 RSCV-FBY49x-*M/5D 131
JBBS-49-M413/3G 74 RSCV-RKCV-FBY49x-*M/5D 131
JBBS-49-M413/Ex 86 RSCV-RSCV-FBY49x-*M/5D 131
JBBS-49-M613/3G 76 RSEV49-CC 170
JBBS-49-M613/Ex 88 RSEV49-TR 160
JBBS-49SC-E413/3G 46 RSEV-BC 168
JBBS-49SC-E413/Ex 58 RSEV-CC 168
JBBS-49SC-E613/3G 48 RSFV49 134
JBBS-49SC-E613/Ex 60 RSFV49-0,3M/14,5/C1117 136
JBBS-49SC-M413/3G 50 RSFV49-0,3M/M20/C1117 138
JBBS-49SC-M413/Ex 62 RSFV-RKFV49/22 170
JBBS-49SC-M613/3G 52 RSM-DUST-CAP 169
JBBS-49SC-M613/Ex 64 RSMV-BC 167
JBBS-49SC-T415/3G 42 RSMV-CC 167
JBBS-49SC-T415B/Ex 54 RSMV-CCC 167
JBBS-49SC-T615/3G 44 RSMV-CCO 168
JBBS-49SC-T615B/Ex 56 RSV-2RKV49 40
JBBS-49-T415/3G 66 RSV492A-*M 132
JBBS-49-T415B/Ex 78 RSV492BA-*M 132

172 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
10

11

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 173 /0309
174 /0309 Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com
10

11

Hans Turck GmbH & Co.KG Witzlebenstrae 7 45472 Mlheim/Ruhr Germany Tel. +49 (0)208 4952-0 Fax +49 (0)208 4952-264 more@turck.com www.turck.com 175 /0309
TURCK WORLD-WIDE HEADQUARTERS

GERMANY
Hans Turck GmbH & Co. KG
Witzlebenstrae 7
45472 Mlheim an der Ruhr
P. O. Box 45466 Mlheim an der Ruhr
Tel. +49 208 4952-0
Fax +49 208 4952-264
E-Mail more@turck.com

AUSTRALIA HUNGARY THE NETHERLANDS


TURCK Australia Pty. Ltd. TURCK Hungary kft. TURCK B. V.
unit 5, 6-7 Gilda Court Mulgrave Knyves Kalman Krt.76 Postbus 297
Victoria 3170 1087 Budapest 8000 AG Zwolle
Tel. +61 (0) 3 95609066 Tel. +36 1 4770-740 Tel. +31 38 4227-750
Fax +61 (0) 3 95601620 Fax +36 1 4770-741 Fax +31 38 4227-451
E-Mail E-Mail hungary@turck.com E-Mail info@turck.nl
cameron.dwyer@turck.com

BAHRAIN INDIA POLAND


TURCK Middle East S.P. TURCK India Automation Pvt Ltd. TURCK sp.z o.o
P.O. Box 18370 603/604, 6th Floor, A-wing Ul. Zeromskiego 1
Manama - Kingdom of Bahrain ICC Trade Towers, 45-053 Opole
Tel. +973 17 814920 Senapati Bapat Road, Tel. +48 77 443 48 00
Fax +973 17 814925 Pune - 411016, Fax +48 77 443 48 01
E-Mail Maharashtra - India E-Mail poland@turck.com
turckmiddleeast@turck.com Tel. + 91 20 25630039
25630040
Fax + 91 20 25630040
E-Mail sales.india@turck.com

BELGIUM ITALY ROMANIA


Multiprox N. V. TURCK Process Automation TURCK Automation Romania SRL
P. B. 71 Via ATorta 30/A Str. luliu Tetrat nr. 18 Sector 1
Lion dOrweg 12 24047 Treviglio (BG) 011914 Bukarest
9300 Aalst Tel. +39 03 6346128 Tel. +40 21 2300279
Tel. +32 53 766566 Fax +39 03 63598268 2300594
Fax +32 53 783977 E-Mail pa-italy@turck.com Fax +40 21 2314087
E-Mail mail@multiprox.be E-Mail: romania@turck.com

CZECH REPUBLIC JAPAN RUSSIA


TURCK s.r.o. TURCK Japan Corporation TURCK Rus O.O.O.
Hradeck 1151 #202 MBD Bldg. 2F, 3-3-23, Altufyevskoe shosse, 1/7
500 03 Hradec Krlov 3 Minami-Aoyama, 127106 Moskau
Tel. +420 495 518 766 Minato-ku, 107-0062, Tokyo, Tel. +7 495 2342661
Fax +420 495 518 767 Japan Fax +7 495 2342665
E-Mail turck-cz@turck.com Tel. + 81 3 57722820 E-Mail russia@turck.com
Fax + 81 3 34082571
E-Mail info@turck.jp

PR OF CHINA KOREA SINGAPORE


TURCK (Tianjin) Sensor Co. Ltd. TURCK Korea Co. Ltd. TURCK Singapore Pte. Ltd.
18,4th Xinghuazhi Road, RIT center Room No 412, 25 International Business Park
Xiqing Economic Gyeonggi Technopark #03-22/23 German Centre
Development Area, Phone +82 (31) 5004555 609916 Singapore
300381 Tianjin Fax +82 (31) 5004558 Tel. +65 65628716
Tel. +86 22 83988-188 E-Mail sensor@sensor.co.kr Fax +65 65628719
83988-199 E-Mail singapore@turck.com
Fax +86 22 83988-111
E-Mail turcktj@public1.tpt.tj.cn

FRANCE
TURCK BANNER S.A.S
MEXICO
TURCK Mexico S. DE R.L. DE C.V.
USA
TURCK Inc.
www.turck.com
3, Rue de Courtalin Carr. Saltillo-Zacatecas km 4.5 s/n 3000 Campus Drive
Magny-Le-Hongre Parque Industrial La Angostura Minneapolis, MN 55441-2656
77703 Marne-La-Vallee Cedex 4 Saltillo, COAH. 25070 Tel. +1 763 553-9224
Tel. +33 1 6043-6070 Tel. +52 844 4826-924 553-7300
Fax +33 1 6043-1018 Fax +52 844 4826-926 Fax +1 763 553-0708
E-Mail info@turckbanner.fr E-Mail ventasmexico@turck.com E-Mail mailbag@turck.com

GREAT BRITAIN
TURCK BANNER LIMITED
Blenheim House
Hurricane Way
Wickford, Essex SS11 8YT
Tel. +44 1268 578888
Fax +44 1268 763648 D301024 0309
E-Mail info@turckbanner.co.uk

*D3010240309*
... and more than 60 representatives and agencies world-wide. Subject to change without notice