Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/69/2492
Project Rembang Page 36
Application note 1 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 1
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 37
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 5,35
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 9,7 % 0,0 %
Concrete edge failure: 3,9 %
Concrete failure on the
opposing side of the 8,8 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/6a/2492
Project Rembang Page 41
Application note 2 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 2
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 42
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 5,31
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 9,6 % 0,0 %
Concrete edge failure: 3,2 %
Concrete failure on the
opposing side of the 8,8 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/6c/2492
Project Rembang Page 46
Application note 3 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 3
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 47
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 5,12
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 9,3 % 0,0 %
Concrete edge failure: 1,3 %
Concrete failure on the
opposing side of the 8,4 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/6d/2492
Project Rembang Page 51
Application note 4 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 4
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 52
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 5,11
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 9,3 % 0,0 %
Concrete edge failure: 1,0 %
Concrete failure on the
opposing side of the 8,4 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/6e/2492
Project Rembang Page 56
Application note 5 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 5
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 57
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 5,11
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 9,3 % 0,0 %
Concrete edge failure: 0,9 %
Concrete failure on the
opposing side of the 8,4 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/6f/2492
Project Rembang Page 61
Application note 6 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 6
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 62
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 5,10
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 9,3 % 0,0 %
Concrete edge failure: 0,5 %
Concrete failure on the
opposing side of the 8,4 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/70/2492
Project Rembang Page 66
Application note 7 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 7
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 67
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 3,84
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 7,0 % 0,0 %
Concrete edge failure: 1,1 %
Concrete failure on the
opposing side of the 6,3 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/71/2492
Project Rembang Page 71
Application note 8 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 8
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 72
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 3,83
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 6,9 % 0,0 %
Concrete edge failure: 1,0 %
Concrete failure on the
opposing side of the 6,3 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/72/2492
Project Rembang Page 76
Application note 9 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 9
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 77
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 4,12
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 7,5 % 0,0 %
Concrete edge failure: 1,3 %
Concrete failure on the
opposing side of the 6,8 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/73/2492
Project Rembang Page 81
Application note 10 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 10
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 82
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 4,11
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 7,5 % 0,0 %
Concrete edge failure: 1,1 %
Concrete failure on the
opposing side of the 6,8 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/74/2492
Project Rembang Page 86
Application note 11 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 11
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 87
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 4,30
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 7,8 % 0,0 %
Concrete edge failure: 2,0 %
Concrete failure on the
opposing side of the 7,1 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/75/2492
Project Rembang Page 91
Application note 12 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 12
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 92
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 4,30
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 7,8 % 0,0 %
Concrete edge failure: 1,9 %
Concrete failure on the
opposing side of the 7,1 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/76/2492
Project Rembang Page 96
Application note 13 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 13
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 97
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 4,54
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 8,2 % 0,0 %
Concrete edge failure: 1,8 %
Concrete failure on the
opposing side of the 7,5 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/77/2492
Project Rembang Page 101
Application note 14 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 14
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 102
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 4,54
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 8,2 % 0,0 %
Concrete edge failure: 1,6 %
Concrete failure on the
opposing side of the 7,5 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/78/2492
Project Rembang Page 106
Application note 15 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 15
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 107
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 4,70
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 8,5 % 0,0 %
Concrete edge failure: 1,4 %
Concrete failure on the
opposing side of the 7,8 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/79/2492
Project Rembang Page 111
Application note 16 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 16
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 112
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 4,70
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 8,5 % 0,0 %
Concrete edge failure: 1,3 %
Concrete failure on the
opposing side of the 7,8 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/7c/2492
Project Rembang Page 116
Application note 17 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 17
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 117
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 5,56
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 10,1 % 0,0 %
Concrete edge failure: 1,3 %
Concrete failure on the
opposing side of the 9,2 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/7d/2492
Project Rembang Page 121
Application note 18 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 18
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 122
Important:
The anchors are not subjected to a tensile force.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 0,00 5,56
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 10,1 % 0,0 %
Concrete edge failure: 1,2 %
Concrete failure on the
opposing side of the 9,2 %
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/7e/2492
Project Rembang Page 126
Application note 19 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 19
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 127
Important:
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 10,08 23,39
Tension load, Concrete cone failure: Shear load, Concrete failure on the opposing side of the load:
Unit Sd Unit Sd
N0Rk,c kN 79,80 N0Rk,c kN 79,80
A c,N cm 2 1810,50 A c,N cm 2 1810,50
0
Ac,N cm 2 2601,00 0
Ac,N cm 2 2601,00
Ac,N / A0c,N - 0,70 Ac,N / A0c,N - 0,70
y s,N - 0,82 y s,N - 0,82
y ec1,N - 1,00 y ec1,N - 1,00
y ec2,N - 1,00 y ec2,N - 1,00
y re,N - 1,00 y re,N - 1,00
NRk,c kN 45,42 y g,N - -
gM,c - 1,50 k - 2,00
NRd,c kN 30,28 VRk,cp kN 90,83
NgSd kN 10,08 gM,cp - 1,50
b N,c - 0,33 VRd,cp kN 60,55
VgSd kN 23,39
b V,cp - 0,39
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 19
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 128
Tension load, Combined pull-out and concrete cone failure: Shear load, Concrete edge failure:
Unit Sd Unit Sd
N0Rk,p kN 80,11 V0Rk,c kN 18,23
A p,N cm 2 1810,50 Ac,V cm 2 450,00
0
Ap,N cm 2 2601,00 0
Ac,V cm 2 450,00
Ap,N / A0p,Np - 0,70 Ac,V / A0c,V - 1,00
y s,Np - 0,82 y s,V - 1,00
y g,Np - 1,00 y h,V - 1,00
y ec1,Np - 1,00 y a ,V - 2,50
y ec2,Np - 1,00 y ec,V - 1,00
y re,Np - 1,00 y re,V - 1,00
NRk,p kN 45,59 VRk,c kN 45,57
gM,p - 1,50 gM,c - 1,50
NRd,p kN 30,40 VRd,c kN 30,38
NgSd kN 10,08 VgSd kN 4,17
b N,p - 0,33 b V,c - 0,14
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 11,0 % Steel failure: 42,4 % 46,9 %
Concrete cone failure: 33,3 % Concrete edge failure: 13,7 %
Concrete failure on the
Combined pull-out and
33,2 % opposing side of the 38,6 %
concrete cone failure:
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/7f/2492
Project Rembang Page 131
Application note 20 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 20
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 132
Important:
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 10,05 20,85
Tension load, Concrete cone failure: Shear load, Concrete failure on the opposing side of the load:
Unit Sd Unit Sd
N0Rk,c kN 79,80 N0Rk,c kN 79,80
A c,N cm 2 1810,50 A c,N cm 2 1810,50
0
Ac,N cm 2 2601,00 0
Ac,N cm 2 2601,00
Ac,N / A0c,N - 0,70 Ac,N / A0c,N - 0,70
y s,N - 0,82 y s,N - 0,82
y ec1,N - 1,00 y ec1,N - 1,00
y ec2,N - 1,00 y ec2,N - 1,00
y re,N - 1,00 y re,N - 1,00
NRk,c kN 45,42 y g,N - -
gM,c - 1,50 k - 2,00
NRd,c kN 30,28 VRk,cp kN 90,83
NgSd kN 10,05 gM,cp - 1,50
b N,c - 0,33 VRd,cp kN 60,55
VgSd kN 20,85
b V,cp - 0,34
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 20
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=170mm) Page 133
Tension load, Combined pull-out and concrete cone failure: Shear load, Concrete edge failure:
Unit Sd Unit Sd
N0Rk,p kN 80,11 V0Rk,c kN 18,23
A p,N cm 2 1810,50 Ac,V cm 2 450,00
0
Ap,N cm 2 2601,00 0
Ac,V cm 2 450,00
Ap,N / A0p,Np - 0,70 Ac,V / A0c,V - 1,00
y s,Np - 0,82 y s,V - 1,00
y g,Np - 1,00 y h,V - 1,00
y ec1,Np - 1,00 y a ,V - 2,50
y ec2,Np - 1,00 y ec,V - 1,00
y re,Np - 1,00 y re,V - 1,00
NRk,p kN 45,59 VRk,c kN 45,57
gM,p - 1,50 gM,c - 1,50
NRd,p kN 30,40 VRd,c kN 30,38
NgSd kN 10,05 VgSd kN 2,98
b N,p - 0,33 b V,c - 0,10
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 10,9 % Steel failure: 37,8 % 42,4 %
Concrete cone failure: 33,2 % Concrete edge failure: 9,8 %
Concrete failure on the
Combined pull-out and
33,1 % opposing side of the 34,4 %
concrete cone failure:
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/80/2492
Project Rembang Page 136
Application note 21 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 21
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 137
Important:
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 4,44 5,57
2 kN 4,44 5,57
3 kN 4,44 5,57
4 kN 4,44 5,57
Tension load, Concrete cone failure: Shear load, Concrete failure on the opposing side of the load:
Unit Sd Unit Sd
N0Rk,c kN 109,55 N0Rk,c kN 109,55
A c,N cm 2 3773,00 A c,N cm 2 3773,00
0
Ac,N cm 2 3969,00 0
Ac,N cm 2 3969,00
Ac,N / A0c,N - 0,95 Ac,N / A0c,N - 0,95
y s,N - 0,78 y s,N - 0,78
y ec1,N - 1,00 y ec1,N - 1,00
y ec2,N - 1,00 y ec2,N - 1,00
y re,N - 1,00 y re,N - 1,00
NRk,c kN 81,33 y g,N - -
gM,c - 1,50 k - 2,00
NRd,c kN 54,22 VRk,cp kN 162,66
NgSd kN 17,77 gM,cp - 1,50
b N,c - 0,33 VRd,cp kN 108,44
VgSd kN 22,27
b V,cp - 0,21
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 21
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 138
Tension load, Combined pull-out and concrete cone failure: Shear load, Concrete edge failure:
Unit Sd Unit Sd
N0Rk,p kN 98,96 V0Rk,c kN 15,92
A p,N cm 2 3266,46 Ac,V cm 2 503,63
0
Ap,N cm 2 2773,33 0
Ac,V cm 2 325,13
Ap,N / A0p,Np - 1,18 Ac,V / A0c,V - 1,55
y s,Np - 0,80 y s,V - 1,00
y g,Np - 1,05 y h,V - 1,00
y ec1,Np - 1,00 y a ,V - 2,46
y ec2,Np - 1,00 y ec,V - 1,00
y re,Np - 1,00 y re,V - 1,00
NRk,p kN 97,48 VRk,c kN 60,55
gM,p - 1,50 gM,c - 1,50
NRd,p kN 64,99 VRd,c kN 40,37
NgSd kN 17,77 VgSd kN 11,16
b N,p - 0,27 b V,c - 0,28
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 4,8 % Steel failure: 10,1 % 33,3 %
Concrete cone failure: 32,8 % Concrete edge failure: 27,7 %
Concrete failure on the
Combined pull-out and
27,3 % opposing side of the 20,5 %
concrete cone failure:
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/81/2492
Project Rembang Page 141
Application note 22 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 22
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 142
Important:
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 4,45 4,45
2 kN 4,45 4,45
3 kN 4,45 4,45
4 kN 4,45 4,45
Tension load, Concrete cone failure: Shear load, Concrete failure on the opposing side of the load:
Unit Sd Unit Sd
N0Rk,c kN 109,55 N0Rk,c kN 109,55
A c,N cm 2 3773,00 A c,N cm 2 3773,00
0
Ac,N cm 2 3969,00 0
Ac,N cm 2 3969,00
Ac,N / A0c,N - 0,95 Ac,N / A0c,N - 0,95
y s,N - 0,78 y s,N - 0,78
y ec1,N - 1,00 y ec1,N - 1,00
y ec2,N - 1,00 y ec2,N - 1,00
y re,N - 1,00 y re,N - 1,00
NRk,c kN 81,33 y g,N - -
gM,c - 1,50 k - 2,00
NRd,c kN 54,22 VRk,cp kN 162,66
NgSd kN 17,78 gM,cp - 1,50
b N,c - 0,33 VRd,cp kN 108,44
VgSd kN 17,79
b V,cp - 0,16
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 22
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 143
Tension load, Combined pull-out and concrete cone failure: Shear load, Concrete edge failure:
Unit Sd Unit Sd
N0Rk,p kN 98,96 V0Rk,c kN 15,92
A p,N cm 2 3266,46 Ac,V cm 2 503,63
0
Ap,N cm 2 2773,33 0
Ac,V cm 2 325,13
Ap,N / A0p,Np - 1,18 Ac,V / A0c,V - 1,55
y s,Np - 0,80 y s,V - 1,00
y g,Np - 1,05 y h,V - 1,00
y ec1,Np - 1,00 y a ,V - 2,43
y ec2,Np - 1,00 y ec,V - 1,00
y re,Np - 1,00 y re,V - 1,00
NRk,p kN 97,48 VRk,c kN 59,96
gM,p - 1,50 gM,c - 1,50
NRd,p kN 64,99 VRd,c kN 39,98
NgSd kN 17,78 VgSd kN 8,93
b N,p - 0,27 b V,c - 0,22
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 4,8 % Steel failure: 8,1 % 29,3 %
Concrete cone failure: 32,8 % Concrete edge failure: 22,3 %
Concrete failure on the
Combined pull-out and
27,4 % opposing side of the 16,4 %
concrete cone failure:
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/82/2492
Project Rembang Page 146
Application note 23 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 23
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 147
Important:
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 8,77 8,52
2 kN 8,77 8,52
3 kN 8,77 8,52
4 kN 8,77 8,52
Tension load, Concrete cone failure: Shear load, Concrete failure on the opposing side of the load:
Unit Sd Unit Sd
N0Rk,c kN 109,55 N0Rk,c kN 109,55
A c,N cm 2 3773,00 A c,N cm 2 3773,00
0
Ac,N cm 2 3969,00 0
Ac,N cm 2 3969,00
Ac,N / A0c,N - 0,95 Ac,N / A0c,N - 0,95
y s,N - 0,78 y s,N - 0,78
y ec1,N - 1,00 y ec1,N - 1,00
y ec2,N - 1,00 y ec2,N - 1,00
y re,N - 1,00 y re,N - 1,00
NRk,c kN 81,33 y g,N - -
gM,c - 1,50 k - 2,00
NRd,c kN 54,22 VRk,cp kN 162,66
NgSd kN 35,09 gM,cp - 1,50
b N,c - 0,65 VRd,cp kN 108,44
VgSd kN 34,08
b V,cp - 0,31
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 23
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 148
Tension load, Combined pull-out and concrete cone failure: Shear load, Concrete edge failure:
Unit Sd Unit Sd
N0Rk,p kN 98,96 V0Rk,c kN 15,92
A p,N cm 2 3266,46 Ac,V cm 2 503,63
0
Ap,N cm 2 2773,33 0
Ac,V cm 2 325,13
Ap,N / A0p,Np - 1,18 Ac,V / A0c,V - 1,55
y s,Np - 0,80 y s,V - 1,00
y g,Np - 1,05 y h,V - 1,00
y ec1,Np - 1,00 y a ,V - 2,34
y ec2,Np - 1,00 y ec,V - 1,00
y re,Np - 1,00 y re,V - 1,00
NRk,p kN 97,48 VRk,c kN 57,69
gM,p - 1,50 gM,c - 1,50
NRd,p kN 64,99 VRd,c kN 38,46
NgSd kN 35,09 VgSd kN 17,21
b N,p - 0,54 b V,c - 0,45
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 9,5 % Steel failure: 15,5 % 82,0 %
Concrete cone failure: 64,7 % Concrete edge failure: 44,8 %
Concrete failure on the
Combined pull-out and
54,0 % opposing side of the 31,4 %
concrete cone failure:
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/83/2492
Project Rembang Page 151
Application note 24 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 24
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 152
Important:
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 8,77 7,57
2 kN 8,77 7,57
3 kN 8,77 7,57
4 kN 8,77 7,57
Tension load, Concrete cone failure: Shear load, Concrete failure on the opposing side of the load:
Unit Sd Unit Sd
N0Rk,c kN 109,55 N0Rk,c kN 109,55
A c,N cm 2 3773,00 A c,N cm 2 3773,00
0
Ac,N cm 2 3969,00 0
Ac,N cm 2 3969,00
Ac,N / A0c,N - 0,95 Ac,N / A0c,N - 0,95
y s,N - 0,78 y s,N - 0,78
y ec1,N - 1,00 y ec1,N - 1,00
y ec2,N - 1,00 y ec2,N - 1,00
y re,N - 1,00 y re,N - 1,00
NRk,c kN 81,33 y g,N - -
gM,c - 1,50 k - 2,00
NRd,c kN 54,22 VRk,cp kN 162,66
NgSd kN 35,09 gM,cp - 1,50
b N,c - 0,65 VRd,cp kN 108,44
VgSd kN 30,30
b V,cp - 0,28
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 24
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 153
Tension load, Combined pull-out and concrete cone failure: Shear load, Concrete edge failure:
Unit Sd Unit Sd
N0Rk,p kN 98,96 V0Rk,c kN 15,92
A p,N cm 2 3266,46 Ac,V cm 2 503,63
0
Ap,N cm 2 2773,33 0
Ac,V cm 2 325,13
Ap,N / A0p,Np - 1,18 Ac,V / A0c,V - 1,55
y s,Np - 0,80 y s,V - 1,00
y g,Np - 1,05 y h,V - 1,00
y ec1,Np - 1,00 y a ,V - 2,30
y ec2,Np - 1,00 y ec,V - 1,00
y re,Np - 1,00 y re,V - 1,00
NRk,p kN 97,48 VRk,c kN 56,70
gM,p - 1,50 gM,c - 1,50
NRd,p kN 64,99 VRd,c kN 37,80
NgSd kN 35,09 VgSd kN 15,35
b N,p - 0,54 b V,c - 0,41
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 9,5 % Steel failure: 13,7 % 77,9 %
Concrete cone failure: 64,7 % Concrete edge failure: 40,6 %
Concrete failure on the
Combined pull-out and
54,0 % opposing side of the 27,9 %
concrete cone failure:
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/84/2492
Project Rembang Page 156
Application note 25 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 25
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 157
Important:
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 3,64 4,44
2 kN 3,64 4,44
3 kN 3,64 4,44
4 kN 3,64 4,44
Tension load, Concrete cone failure: Shear load, Concrete failure on the opposing side of the load:
Unit Sd Unit Sd
N0Rk,c kN 109,55 N0Rk,c kN 109,55
A c,N cm 2 3773,00 A c,N cm 2 3773,00
0
Ac,N cm 2 3969,00 0
Ac,N cm 2 3969,00
Ac,N / A0c,N - 0,95 Ac,N / A0c,N - 0,95
y s,N - 0,78 y s,N - 0,78
y ec1,N - 1,00 y ec1,N - 1,00
y ec2,N - 1,00 y ec2,N - 1,00
y re,N - 1,00 y re,N - 1,00
NRk,c kN 81,33 y g,N - -
gM,c - 1,50 k - 2,00
NRd,c kN 54,22 VRk,cp kN 162,66
NgSd kN 14,55 gM,cp - 1,50
b N,c - 0,27 VRd,cp kN 108,44
VgSd kN 17,76
b V,cp - 0,16
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 25
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 158
Tension load, Combined pull-out and concrete cone failure: Shear load, Concrete edge failure:
Unit Sd Unit Sd
N0Rk,p kN 98,96 V0Rk,c kN 15,92
A p,N cm 2 3266,46 Ac,V cm 2 503,63
0
Ap,N cm 2 2773,33 0
Ac,V cm 2 325,13
Ap,N / A0p,Np - 1,18 Ac,V / A0c,V - 1,55
y s,Np - 0,80 y s,V - 1,00
y g,Np - 1,05 y h,V - 1,00
y ec1,Np - 1,00 y a ,V - 2,38
y ec2,Np - 1,00 y ec,V - 1,00
y re,Np - 1,00 y re,V - 1,00
NRk,p kN 97,48 VRk,c kN 58,80
gM,p - 1,50 gM,c - 1,50
NRd,p kN 64,99 VRd,c kN 39,20
NgSd kN 14,55 VgSd kN 8,94
b N,p - 0,22 b V,c - 0,23
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 4,0 % Steel failure: 8,1 % 24,8 %
Concrete cone failure: 26,8 % Concrete edge failure: 22,8 %
Concrete failure on the
Combined pull-out and
22,4 % opposing side of the 16,4 %
concrete cone failure:
load:
Installation details
Street Dornierstrae
Postcode / City 48477 Hrstel COMPUFIX 8.4
Phone Fax 8.4.4840.25953/85/2492
Project Rembang Page 161
Application note 26 Date: 27.10.2014
Remarks
Brokweg 75
48249 Dlmen
Dimensions/loads:
Design actions
(*) Not true to scale
[mm], [kN], [kNm]
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 26
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 162
Important:
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The COMPUFIX anchor plate design is based on a proof of stresses and does not allow a statement
about the stiffness of the plate. The proof of the necessary stiffness is not carried out by COMPUFIX.
The design utilises specific values for each anchor. When alterations will be made, even for similar products, a new design
calculation is required.
With slotted holes the design is carried out under the assumption that the anchor is located in the centre of the hole.
Please check that the fixing thickness of the fixing is adequate.
Maximum hole diameter in the attachment: 22 mm / 26 mm (First value without filled gap, second value with filled gap).
To ensure the structural component's capacity, the proofs in accordance with Section 7 of ETAG Annex C must be observed.
All additional conditions of the Approvals are to be observed.
Due to the following reasons splitting failure will not occur:
- Cracked concrete is assumed.
- Reinforcement is present which limits the crack width to wk = 0.3 mm, taking into account the splitting forces according to
ETAG 001, Annex C, chapter 7.3.
Anchor-No. Unit Sd
N V
1 kN 3,64 3,68
2 kN 3,64 3,68
3 kN 3,64 3,68
4 kN 3,64 3,68
Tension load, Concrete cone failure: Shear load, Concrete failure on the opposing side of the load:
Unit Sd Unit Sd
N0Rk,c kN 109,55 N0Rk,c kN 109,55
A c,N cm 2 3773,00 A c,N cm 2 3773,00
0
Ac,N cm 2 3969,00 0
Ac,N cm 2 3969,00
Ac,N / A0c,N - 0,95 Ac,N / A0c,N - 0,95
y s,N - 0,78 y s,N - 0,78
y ec1,N - 1,00 y ec1,N - 1,00
y ec2,N - 1,00 y ec2,N - 1,00
y re,N - 1,00 y re,N - 1,00
NRk,c kN 81,33 y g,N - -
gM,c - 1,50 k - 2,00
NRd,c kN 54,22 VRk,cp kN 162,66
NgSd kN 14,55 gM,cp - 1,50
b N,c - 0,27 VRd,cp kN 108,44
VgSd kN 14,72
b V,cp - 0,14
Print sender VHV Anlagenbau GmbH
Project Rembang
Application note 26
Anchor Resin bonded anchor hammer drilling RG M20x260 A4 (hef=210mm) Page 163
Tension load, Combined pull-out and concrete cone failure: Shear load, Concrete edge failure:
Unit Sd Unit Sd
N0Rk,p kN 98,96 V0Rk,c kN 15,92
A p,N cm 2 3266,46 Ac,V cm 2 503,63
0
Ap,N cm 2 2773,33 0
Ac,V cm 2 325,13
Ap,N / A0p,Np - 1,18 Ac,V / A0c,V - 1,55
y s,Np - 0,80 y s,V - 1,00
y g,Np - 1,05 y h,V - 1,00
y ec1,Np - 1,00 y a ,V - 2,34
y ec2,Np - 1,00 y ec,V - 1,00
y re,Np - 1,00 y re,V - 1,00
NRk,p kN 97,48 VRk,c kN 57,65
gM,p - 1,50 gM,c - 1,50
NRd,p kN 64,99 VRd,c kN 38,43
NgSd kN 14,55 VgSd kN 7,44
b N,p - 0,22 b V,c - 0,19
Combined tensile
Tension load Used capacity Shear load Used capacity Used capacity
and shear load
Steel failure: 4,0 % Steel failure: 6,7 % 22,4 %
Concrete cone failure: 26,8 % Concrete edge failure: 19,4 %
Concrete failure on the
Combined pull-out and
22,4 % opposing side of the 13,6 %
concrete cone failure:
load:
Installation details