Professional Documents
Culture Documents
Alongside the above algorithm, the localization algorithm is HYSTERESIS subroutine, its respective Hysteresis curve is
performed and it will indicate whether the fault was internal or obtained, representing its residual flow.
external to the differential protection zone, where the tripping
signal is released when saturation is detected and the internal The three-phase circuit shown in Fig. 2 models a 345 kV /
fault is identified. 1,54 km transmission line of USIMINAS Steel Plant (Cubato-
SP-Brazil) and the CTs of the three phases on both line
II METHODOLY terminals. The hysteresis curve was inserted in the transformer
model itself. This circuit is used in the second stage to
simulate faults and test the detection and localization
C. Description of the Electric Power System (Modeling)
algorithms.
The circuit shown in Fig. 1 is used in the first stage to D. Data Generation
generate data of normal faults and with saturation for the ANN
training. 1) Sampling and Digital Treatment of Signals:
2) Data Organization
1
Uses nexT
2 frame
Transformada
Janela Wavelet Identificao
Deslizante Discreta 3 da saturao
e
(Corrente) Discrete Comparison
Normalizao
Wavelet of same-phase
Transform values
41 A and B ends
Absolut value
and
Fig. 5 Saturation Identification Process Normalization
Same
Artificial Neural polarity in more No External
G. Final Treatment
Network than 70% of the Fault
This stage aims at interpreting the Neural Network output, frame
so as to avoid identification errors. The Neural Network output Yes
Fig. 7 Single-phase Internal Fault Saturation identification and operation Fig. 10 Three-phase External Fault Shifting between A Phases on both
ends
III - CONCLUSIONS
IV BIBLIOGRAPHIC REFERENCES