Techniques and
Considerations for
Systems Design
James Lagree
Chief Engineer
Eaton
Arc Flash
An Arc Flash - An electrical arc due to either a
phase to ground or phase to phase fault.
80 percent of all electrical injuries are burns
that result from the electric arc flash
Arc flashes cause electrical equipment to
explode, resulting in an arc-plasma fireball
Solid copper vaporizes, expands to 67,000
times its original volume
Temperatures exceed 35,000 degrees F
Detected sound levels of 141.5 decibels
Pressure levels of 2,160 pounds per square
foot
Peak RMS
Let-Through IRMS Let-Through
Current (Ip) Current
(Calculated)
t tarc
t
Total
Clearing Time
2016 Eaton. All Rights Reserved.. 8
Good Design
Remote Racking and Robots
VS.
Racking
Window Dead-front
Handles
Dead-front
Cover
Series arc
Parallel arc
L
fault
AFCI o
a
d
120V ac Z
Cable impedance
2016 Eaton. All Rights Reserved.. 25
Arc Detection - AFCI
Standard overcurrent protection does not detect if:
Parallel Arc Faults are sputtering will not trip on overload because
there is not enough RMS heating current.
Parallel Arc Faults that are limited due to wiring impedances Below the
breakers instantaneous value.
Algorithms for Parallel arc fault protection looking at the slope of the rise
of the fault current.
Series Arc Faults that look like load current Ok arcs (light switch, bi-
metal on a skillet or coffee pot)
Complex Algorithms for series arc faults to detect the signature of good
vs. bad arcs.
EAFR-101D
EAFR-110 EAFR-101/102
EAFR-
110P
EAFR-
EAFR-
101
101
2016 Eaton. All Rights Reserved.. 33
Sensor Locations
Point Arrows
Sensors Point to the
Fiber Loop
Fault Current /
Arcing Event
Starts
2 to
7ms 35ms 13ms
Light Sensor Tripping a Circuit Breaker ~52ms
Light Detected and Breaker Fault
initiate a Shunt Trip coil contacts Clears
part
2016 Eaton. All Rights Reserved.. 37
Arc Flash Mitigation
Pre Arcing Arcing
Arc Prevention Arc Containment
Training -Safe Arc Resistant / Explosion Proof Enclosures: Panelboards,
Work Practices Switchboards, Motor Control Centers and Switchgear
Maintenance Personal Protective Equipment (PPE)
Good Design
Remote Racking Passive
Arc Prediction - Arc Detection Arc Elimination Active
Shorting Bar Arc Mitigator
Monitoring Current / Create a Parallel Arc
Partial Discharge Voltage signal
Smoke analysis Arc Flash Reduction
Temperature Ground Fault Differential Protection
Zone Selective Interlocking
Acoustic Light sensing
Maintenance Switch
Light
Dangerous arc fault is cleared in Quenching
Current
less than 7ms Device
M
2016 Eaton. All Rights Reserved.. 39
Quench the Arc with another Arc
Create an Arc In Parallel
Higher impedance fault then the Shorting Bar (quenching device).
Less stress on the upstream circuit breaker and transformer
Arc
Fault
L3
L2
L1 M
Fault Current /
Arcing Event
Starts
4 to
7ms 32ms
Quenching Device Enabled ~5ms
Short Circuit eliminated Created Fault Clears
2 to
7ms 35ms 13ms
Light Sensor Tripping a Circuit Breaker ~52ms
Light Detected and Breaker Fault
initiate a Shunt Trip coil contacts Clears
part
2016 Eaton. All Rights Reserved.. 41
Arc Flash Mitigation
Pre Arcing Arcing
Arc Prevention Arc Containment
Training -Safe Arc Resistant / Explosion Proof Enclosures: Panelboards,
Work Practices Switchboards, Motor Control Centers and Switchgear
Maintenance Personal Protective Equipment (PPE)
Good Design
Remote Racking Passive
Arc Prediction - Arc Detection Arc Elimination Active
Shorting Bar Arc Mitigator
Monitoring Current / Create a Parallel Arc
Partial Discharge Voltage signal
Smoke analysis Arc Flash Reduction
Temperature Ground Fault Differential Protection
Zone Selective Interlocking
Acoustic Light sensing
Maintenance Switch
3.1
ZSI
tsd = 300ms
Zone 1
2.2 2.1
ZSI ZSI
tsd = 200ms
Zone 2 M
1.2 1.1
ZSI ZSI
tsd = 100ms tsd =100ms
Zone 3
2016 Eaton. All Rights Reserved.. M 46
Zone Selective Interlocking
1.1 2.1 3.1
Trip
Time 10
3.1
ZSI
tsd = 300ms
0.1
Zone 1
0.01
2.2 2.1
Fault Current
ZSI ZSI 3
tsd = 200ms
M Zone 2
1.2 1.1
ZSI ZSI
tsd = 100ms tsd =100ms
3 Zone 3
M
2016 Eaton. All Rights Reserved.. 47
Zone Selective Interlocking
1.1 2.1 3.1
Trip
Time 10
3.1
ZSI
tsd = 300ms
0.1
Zone 1
0.01
2.2 2.1
Fault Current
ZSI ZSI 3
tsd = 200ms
M Zone 2
1.2 1.1
tsd = 100ms
ZSI
tsd =100ms
ZSI Zone Trip
3 Zone 3
M
2016 Eaton. All Rights Reserved.. 48
Zone Selective Interlocking
1.1 2.1 3.1
Trip
Time 10
3.1
ZSI
tsd = 300ms
0.1
Zone 1
0.01
2.2 2.1
Fault Current
ZSI ZSI 2
tsd = 200ms
2
M Zone 2
1.2 1.1
ZSI ZSI
tsd = 100ms tsd =100ms
Zone 3
M
2016 Eaton. All Rights Reserved.. 49
Zone Selective Interlocking
1.1 2.1 3.1
Trip
Time 10
3.1
ZSI
tsd = 300ms
0.1
Zone 1
0.01
2.2 2.1
Fault Current
ZSI
tsd = 200ms
ZSI Zone Trip 2
2
M Zone 2
1.2 1.1
ZSI ZSI
tsd = 100ms tsd =100ms
Zone 3
M
2016 Eaton. All Rights Reserved.. 50
Zone Selective Interlocking
1.1 2.1 3.1
Trip
Time 10
3.1
ZSI
tsd = 300ms
0.1
1
Zone 1
0.01
2.2 2.1
Fault Current
ZSI ZSI 1
tsd = 200ms
M Zone 2
1.2 1.1
ZSI ZSI
tsd = 100ms tsd =100ms
Zone 3
M
2016 Eaton. All Rights Reserved.. 51
Zone Selective Interlocking
1.1 2.1 3.1
Trip
Time 10
3.1
tsd = 300ms
ZSI
Zone Trip
0.1
1
Zone 1
0.01
2.2 2.1
Fault Current
ZSI ZSI 1
tsd = 200ms
M Zone 2
1.2 1.1
ZSI ZSI
tsd = 100ms tsd =100ms
Zone 3
M
2016 Eaton. All Rights Reserved.. 52
ZSI Design Considerations
Number of devices
Auxiliary Power requirement
Length of each run
Compatibility with other protective devices
MV
Definition of Instantaneous: 10
delay.
Actually it is a second short 0.1
Fault Current /
Arcing Event
Starts 4 to
6ms 37ms 16ms 13ms Zone Interlock Trip ~70ms
21ms
ETU Zone Out Trip Coil Breaker Fault
powers up Signal Engaged contacts Clears
4 to part
7ms 32ms
Quenching Device Enabled ~5ms
Short Circuit eliminated Created Fault Clears
2 to
7ms 35ms 13ms
Light Sensor Tripping a Circuit Breaker ~52ms
Light Detected and Breaker Fault
initiate a Shunt Trip coil contacts Clears
part
2016 Eaton. All Rights Reserved.. 55
(2) Differential Relaying
Differential Relay
Similar To Zone Selective
Interlocking
Current
Transformers
Recognizes Faults Within
The Zone Of Protection
Zone of Protection
Acts To Reduce Arc Flash
4 to
6ms 25ms 16ms 13ms
Software Instantaneous Trip ~58ms
Breaker
Fault Current / ETU Trip Coil
contacts Fault
Arcing Event powers up Engaged
part Clears
Starts 4 to
6ms 37ms 16ms 13ms Zone Interlock Trip ~70ms
21ms
ETU Zone Out Trip Coil Breaker Fault
powers up Signal Engaged contacts Clears
4 to part
7ms 32ms
Quenching Device Enabled ~5ms
Short Circuit eliminated Created Fault Clears
2 to
7ms 35ms 13ms
Light Sensor Tripping a Circuit Breaker ~52ms
Light Detected and Breaker Fault
initiate a Shunt Trip coil contacts Clears
part
2016 Eaton. All Rights Reserved.. 58
(3) Energy-reducing maintenance
switching with local status indicator
Indicating
Light
Lockout
Tag out
Switch
Remote Indication:
Power Relay Module Maintenance Mode Contact
Lock-out/Tag-out
Power Breaker
2016 Eaton. All Rights Reserved.. 61
Arc Flash Testing
IEEE 1584 Test Setup for Power Circuit Breakers
Lab Output Cable Connection to
Terminals Downstream Test Enclosure
Circuit
Breaker 3/4 Diameter
Copper Electrodes 7
Calorimeter
Array
Simulates
Body Torso
Arc Flash
Hazard Area
18 AWG Shorting
Wire between 3
Phase Electrodes
Creates Arcing Output =
Fault Arc Flash Energy
20 x 20 x 20 Open Side of
Downstream Test Enclosure Enclosure
With Open Front
2016 Eaton. All Rights Reserved.. 62
Magnum DS Arc Flash Test Program
Eaton High Power Test
Laboratory Test
configured per IEEE 1584
Circuit breaker
with ARMS enabled
Enclosure
with internal 3 phase fault
Calorimeter Array
1000
100
10
Time (s)
1
6X
0.1 120ms
2.5X
0.01
1 10 100
Current (pu)