You are on page 1of 16

2009

09

ISBN 978-0-8269-4360-6

AMERICAN TECHNICAL PUBLISHERS, INC.


HOMEWOOD, ILLINOIS 60430-4600
BOILER 23. A BOILER
24. A
OPERATION 25. D FITTINGS
PRINCIPLES
Boiler Systems_____________5 True-False _________________9
True-False _________________1 1. A 1. T
2. C 2. F
1. T
3. B 3. F
2. F
4. E 4. F
3. T
5. D 5. F
4. T
6. T
5. T 7. F
6. T
7. F
Scotch Marine Boiler ________6 8. T
9. T
8. T 1. B 10. T
9. F 2. A 11. F
10. T 3. D 12. T
11. T 4. C 13. T
12. T 14. T
13. F 15. F
14. T Steam Heating System ______6 16. F
15. T 17. T
16. F 1. D 18. F
17. T 2. G 19. T
18. F 3. E 20. F
19. T 4. I 21. F
20. F 5. C 22. F
6. H 23. T
7. A 24. F
Multiple Choice ____________2 8. B 25. T
9. F 26. F
1. D 27. T
2. B 28. F
3. A HRT Boiler ________________7 29. T
4. B 30. T
5. C 1. C 31. T
6. D 2. E 32. T
7. B 3. A 33. T
8. C 4. B 34. F
9. A 5. D 35. T
10. B 6. G 36. T
11. C 7. F 37. T
12. B 38. F
13. C 39. F
14. A Straight-Tube Watertube 40. T
15. C Boiler ____________________7
16. D
17. A 1. E Multiple Choice ___________11
18. D 2. F
19. D 3. B 1. B
20. D 4. A 2. B
21. D 5. C 3. C
22. D 6. D 4. D

1
2 LOW PRESSURE BOILERS WORKBOOK ANSWER KEY

5. D 5. F 9. D
6. D 6. A 10. C
7. B 7. B 11. B
8. C 12. B
9. C 13. B
10. B Water Column and 14. B
11. D 15. C
12. A
Gauge Glass _____________17
16. A
13. C 1. C 17. C
14. B 2. D 18. D
15. D 19. A
3. A
16. A 20. B
4. I
17. A
5. G
18. D
6. F
19. B
20. D
7. H Testing Low Water
8. B Fuel Cutoff _______________22
21. C
9. E
22. C
23. C 1. D
24. D 2. B
25. B Bottom Blowdown Valve ____18 3. A
26. C 4. E
27. B 1. D 5. C
28. D 2. A
29. C 3. B
4. C
30. D Feedwater System _________23
31. D
32. A 1. C
33. B 2. E
34. C 3. J
35. A FEEDWATER 4. I
36. A SYSTEM 5. F
37. C 6. G
38. A 7. L
39. B 8. N
True-False ________________19
40. A 9. A
1. T 10. B
2. T 11. M
Safety Valve ______________16 3. F 12. D
4. T 13. H
1. F 5. T 14. K
2. E 6. T
3. A 7. T
4. B 8. T
5. H Makeup Water System ______23
9. T
6. C 10. F 1. H
7. D 11. F 2. A
8. G 12. T 3. F
13. T 4. G
14. F 5. J
Safety Valve 15. T 6. E
Huddling Chamber ________17 16. T 7. B
17. F 8. C
1. D 18. T 9. I
2. E 19. T 10. D
3. A 20. T
4. F
5. C Feedwater Control _________24
6. B
Multiple Choice ___________20
1. A
1. C 2. B
Steam Pressure Gauge 2. B 3. F
Operation ________________17 3. D 4. E
4. D 5. C
1. C 5. B 6. I
2. E 6. B 7. D
3. D 7. D 8. H
4. G 8. C 9. G
Answers 3

Feedwater Line ___________24 8. F Steam Trap Location _______32


9. T
1. B 10. F 1. F
2. D 2. E
3. E 3. H
4. A Multiple Choice ___________27 4. A
5. C 5. K
1. B 6. G
2. C 7. J
Vacuum Pump ____________24 3. D 8. D
4. A 9. I
1. E 5. C 10. B
2. F 6. D 11. C
3. B 7. A
4. G 8. D
5. A 9. B Steam Trap
6. D 10. A
11. D Testing Devices ___________33
7. C
12. B
1. C
13. A
2. D
14. D
Centrifugal Water Pump ____25 15. C
3. B
4. A
1. B 16. B
5. E
2. F 17. A
3. C 18. B
19. C
4. E Testing Steam Traps _______34
20. B
5. A
6. D 1. B
2. C
Main Steam Stop Valve _____30 3. A
Low Water Fuel 1. D
Cutoff Parts ______________25 2. B
3. E
1. B 4. A
2. E 5. G FUEL SYSTEM
3. A 6. I
4. F 7. F
5. C 8. H True-False ________________37
6. D 9. C
1. T
2. T
Low Water Fuel Cutoff Steam Trap Operation ______31 3. T
4. T
Operation ________________25 1. A 5. T
2. B 6. F
1. B
3. D 7. T
2. F
4. C 8. T
3. C
5. C 9. F
4. D
6. A 10. T
5. A
7. D 11. T
6. E
8. B 12. T
9. D 13. F
10. B 14. T
11. C 15. T
STEAM SYSTEM 12. A 16. T
13. C 17. T
14. A 18. F
15. B 19. T
True-False ________________27 16. D 20. F
21. F
1. T 22. T
2. F Steam Trap _______________31 23. T
3. T 24. T
4. T 1. C 25. F
5. T 2. A 26. T
6. F 3. D 27. T
7. T 4. B 28. T
4 LOW PRESSURE BOILERS WORKBOOK ANSWER KEY

29. F 45. A 7. D
30. T 46. B 8. G
31. T 47. D 9. B
32. F 48. B 10. F
33. T 49. C 11. K
34. T 50. C 12. C
35. T 51. B 13. H
36. T 52. B 14. N
37. F 53. C
38. F 54. A
39. F 55. B Ram-Feed Stoker __________49
40. F 56. D
41. T 57. D 1. G
42. T 58. B 2. E
43. T 59. D 3. A
44. T 60. C 4. I
45. T 5. D
46. T 6. B
47. F Fuel Oil Pump ____________47 7. H
48. T 8. F
1. B 9. C
2. E
3. A
Multiple Choice ___________39 4. F Fuel Oil Burner____________49
1. D 5. C
2. B 6. D 1. D
3. B 2. A
4. C 3. C
5. C Low Pressure Gas System __47 4. B
6. B
1. I
7. D 2. E
8. B Modulating Control ________50
3. L
9. A 4. A 1. C
10. C 5. N 2. D
11. C 6. G 3. B
12. B 7. K 4. A
13. B 8. D
14. C 9. H
15. B 10. B
16. A
Fuel Oil System ___________50
11. M
17. D 12. C 1. G
18. D 13. J 2. L
19. B 14. F 3. A
20. C 4. E
21. C 5. J
22. C Screw-Feed Stoker ________48 6. C
23. B 7. N
24. A 1. F 8. H
25. D 2. I 9. F
26. C 3. B 10. K
27. D 4. D 11. B
28. D 5. H 12. M
29. D 6. J 13. I
30. C 7. C 14. D
31. B 8. G
32. C 9. A
33. B 10. E Flame Sensor _____________51
34. D
35. D 1. C
36. A High Pressure 2. A
37. B Gas System ______________48 3. D
38. B 4. B
39. A 1. L
40. D 2. E
41. A 3. I Fuel Oil Strainer ___________51
42. C 4. A
43. D 5. M 1. A
44. C 6. J 2. E
Answers 5

3. B 3. A 16. F
4. D 4. F 17. T
5. C 5. B 18. F
6. F 6. D 19. T
20. F
21. T
Forced Draft ______________57 22. T
23. F
DRAFT SYSTEM 1. F 24. T
2. J 25. T
3. A
4. G
True-False ________________53 5. I Multiple Choice ___________60
1. T 6. B
7. H 1. B
2. F
3. F 8. D 2. C
4. T 9. E 3. B
5. T 10. C 4. B
6. T 5. A
7. F 6. A
8. T Draft Control _____________57 7. D
9. T 8. D
10. F 1. E 9. D
11. T 2. B 10. D
12. T 3. H 11. D
13. F 4. G 12. A
14. T 5. C 13. A
15. F 6. F 14. D
16. T 7. D 15. D
17. T 8. A 16. C
18. T 17. A
19. T
20. T Stack ____________________58
Sludge Removal ___________62
1. B
2. G 1. D
Multiple Choice ___________54 3. D 2. A
1. B 4. C 3. C
2. D 5. F 4. E
3. D 6. E 5. B
4. D 7. A
5. B 8. H
6. B 9. I Priming and Carryover _____62
7. A
8. B 1. D
9. D 2. A
10. A 3. B
11. D
BOILER WATER 4. E
12. B TREATMENT 5. C
13. C
14. B
15. A True-False ________________59 Foaming _________________63
16. B
17. A 1. T 1. B
18. C 2. F 2. E
3. T 3. D
4. T 4. A
Manometer _______________56 5. F 5. C
6. F
1. C 7. T
2. A 8. T Water Treatment
3. B 9. F Log Readings _____________63
10. T
11. F 1. 10.9
Natural Draft ______________56 12. F 2. 45
13. T 3. 16
1. E 14. F 4. 0
2. C 15. T 5. 2700
6 LOW PRESSURE BOILERS WORKBOOK ANSWER KEY

Bypass Feeder ____________64 3. B 20. T


4. C 21. T
1. E 5. B 22. F
2. B 6. B 23. F
3. D 7. D 24. T
4. A 8. D 25. F
5. C 9. A 26. T
6. F 10. C 27. T
11. D 28. F
12. C 29. T
13. A 30. T
BOILER 14. B
15. D
OPERATION 16. C Multiple Choice ___________74
PROCEDURES 17. C
18. A 1. A
19. C 2. B
True-False ________________65 20. B 3. D
21. A 4. C
1. T
2. T 22. A 5. C
3. T 23. D 6. B
4. T 24. B 7. C
5. F 25. D 8. D
6. T 26. D
9. D
7. F 27. A
10. D
8. F 28. A
11. B
9. F 29. C
12. A
10. T 30. A
13. C
11. F 31. A
14. C
12. T 32. A
15. B
13. T 33. A
34. D 16. C
14. T
15. F 35. D 17. C
16. F 36. C 18. D
17. T 37. B 19. B
18. F 38. B 20. D
19. T 39. B 21. D
20. F 40. A 22. D
21. F 23. C
22. T 24. B
23. T 25. C
24. F
25. T HOT WATER
26. T Natural Circulation Hot Water
27. F HEATING SYSTEMS
28. F Heating System ___________78
29. T
1. G
30. T True-False ________________73 2. A
31. F
32. T 3. H
1. T
33. F 4. C
2. F
34. T 5. F
3. F
35. F 6. E
4. T
36. T 7. B
5. F
37. T 8. D
6. F
38. F
7. F
39. F
8. T
40. T
41. F 9. F Aquastat _________________78
42. T 10. T
43. F 11. T 1. B
44. F 12. F 2. G
45. F 13. F 3. I
14. T 4. D
15. T 5. F
Multiple Choice ___________67 16. T 6. H
17. F 7. C
1. D 18. T 8. E
2. C 19. F 9. A
Answers 7

Forced Circulation Hot Water 22. T Cooling System Application


Heating System ___________79 23. F Pasteurization Process ___86
24. T
1. K 25. F 1. D
2. A 26. T 2. B
3. Q 27. F 3. C
4. H 28. F 4. G
5. T 29. T 5. F
6. E 30. T 6. A
7. O 7. E
8. S
9. B Multiple Choice ___________82
10. P Chilled Water System ______87
11. F 1. B
12. L 2. C 1. B
13. D 3. D 2. D
14. I 4. C 3. F
15. M 5. D 4. A
16. G 6. D 5. E
17. C 7. C 6. G
18. N 8. D 7. C
19. J 9. A
20. R 10. C
11. B
12. B
Relief Valve ______________80 13. A BOILER
1. D
14. D OPERATION
15. A
2. F 16. B SAFETY
3. B 17. D
4. E 18. B
5. A 19. C
True-False ________________89
6. G 20. C 1. T
7. C
2. T
3. F
Compression Refrigeration 4. T
Cycle ____________________85 5. F
6. T
7. F
COOLING 1. D
8. T
2. B
SYSTEMS 3. F 9. T
4. E 10. T
5. C 11. T
True-False ________________81 6. A 12. F
13. T
1. T 14. F
2. T 15. F
3. T Centrifugal Compressor ____85 16. T
4. F 17. T
1. A
5. T 18. T
2. E
6. F
3. C
7. F
4. D
8. T
5. B Multiple Choice ___________90
9. F
10. T 1. D
11. T 2. B
12. F Ammonia-Water Absorption 3. D
13. T Refrigeration System ______86 4. A
14. T 5. C
15. F 1. G 6. B
16. F 2. B 7. C
17. T 3. C 8. D
18. F 4. F 9. B
19. T 5. D 10. D
20. F 6. A 11. A
21. T 7. E 12. C
8 LOW PRESSURE BOILERS WORKBOOK ANSWER KEY

13. D 25. A 29. B


14. A 26. D 30. D
15. D 27. B 31. A
16. B 28. B 32. B
29. A 33. B
30. C 34. D
Hazardous Material Container 31. D 35. B
32. D 36. C
Labeling RTK Labeling____92 33. B 37. D
34. B 38. A
1. D
35. B 39. D
2. F
36. C 40. B
3. A
37. C 41. B
4. E
38. B 42. C
5. B
39. A 43. A
6. C 40. D 44. C
41. D 45. C
42. A
43. B
44. B
Sample Licensing Exam 3
45. D
BOILER OPERATOR True-False _______________109
LICENSING Sample Licensing Exam 2 1. F
2. T
True-False _______________101 3. T
Sample Licensing Exam 1 1. T
4. T
True-False ________________93 5. F
2. F
6. T
3. F
1. T 7. T
4. T
2. F 8. F
5. T
3. T 9. T
6. F
4. F 10. T
7. T
5. F 11. T
8. T
6. T 9. F
7. T 10. T
8. F Multiple Choice __________109
9. T
10. T Multiple Choice __________101 1. D
11. T 2. A
1. C 3. D
2. D 4. B
Multiple Choice ___________94 3. B 5. D
4. C 6. C
1. A 5. C 7. A
2. B 6. A 8. A
3. B 7. B 9. B
4. B 8. B 10. B
5. D 9. A 11. B
6. C 10. A 12. C
7. C 11. A 13. B
8. A 12. C 14. C
9. A 13. D 15. A
10. C 14. D 16. D
11. D 15. C 17. C
12. C 16. B 18. A
13. A 17. D 19. A
14. B 18. B 20. A
15. B 19. A 21. D
16. A 20. A 22. B
17. C 21. A 23. B
18. D 22. B 24. D
19. C 23. A 25. A
20. C 24. C 26. A
21. A 25. C 27. A
22. B 26. D 28. B
23. D 27. A 29. B
24. C 28. D 30. B
Answers 9

31. D 37. C 40. A


32. B 38. A 41. A
33. D 39. C
34. A 40. B
35. D 41. A Sample Licensing Exam 6
36. A True-False _______________127
37. A
38. A Sample Licensing Exam 5 1. T
39. A 2. T
40. A
True-False _______________121
3. F
41. C 1. T 4. F
2. F 5. T
3. T 6. T
Sample Licensing Exam 4 4. F 7. T
True-False _______________115 5. T 8. F
6. T 9. T
1. T 7. T 10. F
2. F 8. T 11. F
3. F 9. T 12. T
4. T 10. F 13. F
5. T 11. T 14. F
6. F 12. F 15. T
7. T 13. F
8. F
9. F Multiple Choice __________127
10. T
11. F
Multiple Choice __________121 1. B
1. D 2. C
3. C
2. A
Multiple Choice __________115 4. C
3. B
5. C
4. C
1. B 6. B
5. B
2. A 7. B
6. C
3. C 8. D
7. B
4. C 9. B
8. C
5. A 10. C
9. C
6. B 11. D
10. A
7. C 12. D
11. D
8. D 13. A
12. C 14. B
9. A
13. C 15. D
10. C
14. A 16. A
11. D
15. B 17. D
12. C
16. A 18. C
13. B
14. D 17. C 19. D
15. A 18. B 20. C
16. D 19. B 21. A
17. C 20. C 22. D
18. B 21. C 23. C
19. C 22. C 24. A
20. D 23. C 25. C
21. B 24. C 26. B
22. D 25. C 27. C
23. D 26. C 28. D
24. C 27. C 29. A
25. D 28. C 30. D
26. C 29. D 31. A
27. C 30. B 32. C
28. B 31. A 33. B
29. A 32. C 34. A
30. B 33. C 35. B
31. D 34. C 36. C
32. B 35. B 37. B
33. D 36. D 38. C
34. C 37. A 39. D
35. C 38. D 40. A
36. B 39. D 41. B
10 LOW PRESSURE BOILERS WORKBOOK ANSWER KEY

Sample Licensing Exam 7 testing of safety valves under pressure cover it with your hand, which should
Essay __________________133 once a year, preferably before the start shut off the burner. The second method
of the heating season. In addition to the is to secure the fuel going to the burner
ASME code, safety valves should be to simulate a fuel failure, which should
1. Report to work 10 to 15 minutes early. tested according to recommendations cause the scanner to shut the burner off
Check the water level on all the boilers on of the local boiler inspector. on safety lockout.
the line by blowing down the gauge glass,
water column, and low water fuel cutoff. 8. The function of the low water fuel cutoff is 16. There are two methods of determining the
NOTE: (1) The burners should be ring to shut the burner off to protect the boiler water level in the boiler. One method is to
when the low water fuel cutoff is blown heating surface from becoming over- blow down the gauge glass and watch the
down. This not only removes any sludge heated due to low water in the boiler. action of the water leaving and returning
and sediment from the lines, but also shuts to the glass. The second method is to
9. The two methods of testing the low water use the three try cocks and observe what
off the burner to ensure its proper opera- fuel cutoff are by hand or by an evapo-
tion. (2) When blowing down the gauge comes out of the top try cock, middle try
ration test. When testing the burner by cock, and bottom try cock when they are
glass, the water should leave the gauge hand, the blowdown valve on the low wa-
glass quickly and return quickly when the opened. With an NOWL the top try cock
ter fuel cutoff is opened and steam and should discharge steam, the middle try
gauge glass blowdown valve is closed. water rushing out cause the oat in the
This indicates that the lines are clean. cock should discharge a mixture of wa-
low water fuel cutoff to drop, resulting in ter and steam, and the bottom try cock
2. Steam coming out of the bottom try cock the burner shutting off. When performing should discharge water.
is an indication of low water condition in an evaporation test, the vacuum pump,
the boiler. The burner must be secured, feedwater pump (if the boiler has one), 17. Smoke is the result of incomplete com-
the boiler taken off-line and cooled slowly, and the automatic city water makeup bustion. For example, in fuel oil-burning
and the chief engineer and/or boiler in- feeder must be secured. The water level plants, smoke could be caused by cold
spector must be notied so the boiler can will drop in the boiler and the oat in fuel oil, poor atomization, insufcient pri-
be inspected for any overheating of the the low water fuel cutoff will fall slowly, mary and secondary air, a dirty burner,
heating surface. NOTE: Never add water shutting the burner off. NOTE: When the or fuel oil impinging on the brickwork.
to a boiler that has overheated before burner shuts off, there must always be
water still visible in the gauge glass. 18. The two types of draft used in boilers
checking for possible damage.
are natural draft and mechanical draft.
10. The maximum allowable working pres- Mechanical draft can be further clas-
3. Water coming out of the top try cock is an
sure (MAWP) for a low pressure steam sied as forced draft, induced draft, or
indication of a high water level condition.
boiler is 15 psi. A safety valve must pop combination forced and induced draft.
The boiler must be given a bottom blow-
(open) whenever pressure exceeds the
down to prevent carryover and possible
safety valve setting to prevent the boiler 19. The check valve on the feedwater line pre-
water hammer. The operator should then
from exceeding its MAWP. Anytime a vents water from leaving the boiler when
determine the cause of the high water
safety valve pops, the boiler operator the vacuum pump or boiler feedwater
level condition.
must determine the cause and take cor- pump stops. A check valve controls the
4. The different ways of getting water to the rective action. ow of feedwater in one direction only.
boiler are the vacuum pump, feedwater
11. The safety valves on low pressure steam 20. The stop valve is located on the feedwa-
pump, automatic city water makeup
boilers are set to pop open at 15 psi. ter line as close to the shell of the boiler
feeder, and hand-operated city water
as practical between the boiler and the
makeup valve. 12. Purging a furnace is the part of the check valve. The stop valve is required
ring cycle when the burner motor fan in the event the check valve malfunctions
5. The pressure control is sensitive to pres-
blows air into the furnace to remove any (sticks open or closed). The stop valve
sure and controls the boiler operating
mixture of gases or fumes of a combus- could then be secured (closed) and the
range. It starts and stops the burner on
tible nature that might cause a furnace check valve repaired without having to
steam pressure demand.
explosion. The furnace is always purged dump the boiler.
6. Safety valves are tested by hand or by before the burner lights off (prepurge)
pressure. The ASME code recommends and starts again after the burner shuts 21. The safety valve popping and steam
that safety valves be tested at least once off (postpurge). pressure of 30 psi would indicate mal-
a month by raising the boiler pressure and function of the safety valve(s). The pro-
13. The most important valve on the boiler cedure to follow would be to: (1) Secure
causing the safety valve(s) to pop open.
is the safety valve. The safety valve the burner. (2) Allow steam pressure to
When testing a safety valve by hand there
prevents the boiler from exceeding its drop to approximately 15 psi. (3) Use the
should be at least 5 psi of pressure before
MAWP. If the safety valve exceeds its safety valve test lever to test the safety
lifting the test lever. The hand test lever is
MAWP, a boiler explosion could result. valve(s) by hand. (4) If the safety valve(s)
lifted to fully open the safety valve and is
released to allow the safety valve to snap pop open and reset at the proper blow-
14. The boiler should be given a bottom
shut. NOTE: Check with local inspectors or back, raise the steam pressure to see if
blowdown whenever tests of the boiler
the mechanical inspection bureau regard- the safety valve(s) popped by pressure.
water indicate high chemical concentra-
ing the proper testing of safety valves. (5) If the safety valve(s) popped by pres-
tion or high total dissolved solids. The
sure, determine why the pressure control
boiler should also be blown down when
7. According to Section VI of the ASME did not function properly. NOTE: The
a high water level develops.
code, safety valves on low pressure boiler in question should not be left unat-
boilers should be tested by hand once 15. The flame scanner can be tested in tended. A new boiler should be warmed
every 30 days the boiler is in operation. two ways. One method is to remove up and cut in on the line if there is one
The ASME code also recommends the the scanner from its sighting tube and available. If this is the only boiler in the
Answers 11

plant, it must be attended 24 hours a day installed, or the safety valves must be the highest heating surface. The top line
until it can be taken off-line and given a gagged. (A gag is a clamp that prevents to the water column is connected to the
complete safety check. the valve from popping open without highest part of the steam side of the boiler.
damaging the valve.) (4) The boiler vent The bottom line to the water column is
22. Perfect combustion is the burning of all must remain open until water comes connected approximately 6 below the
the fuel using the theoretical amount out and then is closed. (5) Pressure on center line of a retube boiler.
of air. Perfect combustion can only be the boiler is brought up to 1 times the
achieved in a laboratory setting. Com- MAWP. (The pressure must be under 38. The best time to give a boiler a bottom
plete combustion is the burning of all control so that it does not exceed this blowdown is when the boiler is at its
the fuel using the minimum amount of pressure by more than 10 pounds.) lightest load. This allows sludge and
excess air. Incomplete combustion is sediment to fall to the bottom.
when all the fuel is not burned, resulting 28. NOWL stands for the normal operating
in soot and smoke. water level. In a steam boiler the NOWL 39. The function of a boiler vent is to: (1) vent
is approximately one-third to one-half a air from the boiler when lling it with water,
23. Furnace explosions are caused by a gauge glass. (2) vent air from the boiler when warming
buildup of highly combustible gases or up prior to cutting in on the line, and (3)
fumes that ignite when exposed to a 29. MAWP stands for the maximum allow- prevent a vacuum from forming in the
spark, pilot ame, or radiant brickwork. able working pressure of a boiler. The boiler when taking the boiler off-line.
In addition, furnace explosions can result MAWP of a given boiler is determined 40. The high and low re of the burner are
from improper purging of the furnace by the ASME code. controlled by the modulating pressure
after a ame failure, a leaking fuel valve
control through the modulating motor.
allowing fuel to enter the furnace, or the 30. Carryover can be caused by (1) carrying
operator bypassing safety interlocks in too high a water level, (2) high boiler wa- 41. An os&y valve is open when its stem is
order to light the burner quicker after a ter surface tension, and (3) opening the visible in the up position.
fuel interruption. boiler main steam stop valve too quickly.
42. The purpose of the vacuum pump is to
24. Before a boiler can be inspected, it must 31. Natural draft is created by the height of help return the condensate back to the
be taken off-line. Once a boiler is off-line, the chimney and the difference in tem- vacuum tank. At the vacuum tank, air is
the following safety checks must be perature of the gases of combustion in the vented to the atmosphere, and water is
made: (1) The main steam stop valve(s) chimney and the air outside the chimney. pumped directly back to the boiler or a
(some boilers have two) must be closed Mechanical draft is caused by a fan. condensate return tank.
and tagged out. To tag out a valve means
to mark it so it will not be opened by 32. A feedwater pump becomes steam- 43. The automatic city water makeup feeder
mistake. Some plants attach a sign to the bound when the temperature of the water is a safety device that ensures that the
valve wheel that reads Danger! Person- in the open feedwater heater gets too hot boiler will have water if the vacuum pump
nel in boilerdo not open. (2) The boiler and water in the suction line going to the fails or condensate is lost in the system.
vent or top try cock should be checked to feedwater pump ashes into steam. For maximum protection and safety, the
see that it is open. This ensures there is automatic city water makeup feeder
no vacuum inside. (3) The feedwater line 33. A fast gauge is a pressure gauge that reads should be blown down daily to ensure
to the boiler must be closed and tagged more steam pressure than is actually pres- its proper operation in an emergency.
out. If there is an automatic city water ent in the boiler. A slow gauge is a pressure
44. The steam traps most commonly used
makeup valve, it must be secured also. gauge that reads less steam pressure than
are the nonreturn type. This type in-
is actually present in the boiler.
25. A gauge glass should be blown down cludes thermostatic, inverted bucket,
once a shift or whenever the operator and oat thermostatic.
34. Foaming is caused by impurities in the
questions the level of water in the boiler. boiler water. A surface blowdown is used 45. The two methods most commonly used
to remove impurities in the boiler water to test the proper function of steam
26. In a forced circulation system, the system
that cause foaming. traps are strap-on thermometers and
is closed to the atmosphere and water
is forced (circulated) through the heat- temperature-indicating crayons.
35. An open gate valve offers no restriction to
ing system using circulating pumps. In the ow of the material passing through 46. Fuel oil strainers should be cleaned daily
a natural circulation system, the system it. A gate valve must always be fully open and whenever unusually high suction
is open to the atmosphere. It works on or fully closed. A globe valve has mate- readings occur when fuel oil is at its
the principle that water when heated rial owing under a valve seat and has proper temperature.
increases in volume (expands) and some resistance to ow. A globe valve
becomes less dense. The warmer water is used for throttling (varying the rate of 47. Two types of fuel oil burners commonly
rises and cold, denser water ows back ow) service by partly opening or closing used in low pressure plants are rotary
into the bottom of the boiler. the valve. cup burners and air atomizing burners.
27. In order to do a hydrostatic test on a 36. In a watertube boiler, water passes 48. The advantage of using a combination
boiler, the boiler must be completely through tubes that are surrounded by burner is plant flexibility. The opera-
lled with water. To perform a hydrostatic gases of combustion. In a retube boiler, tor can burn the fuel that is cheapest,
test, the following operations must be gases of combustion pass through tubes change from one fuel to another if prob-
carried out: (1) If the water column has that are surrounded by water. lems occur, and keep the plant operating
a whistle valve, it must be removed and if there is a shortage of a fuel.
plugged. (2) The main steam stop valve 37. The water column must be located at the
must be closed. (3) The safety valve(s) NOWL so that the lowest visible part of 49. Air used in the combustion process is
must be removed and blank flanges the gauge glass is a minumum of 1 above broadly classied as primary, secondary,
12 LOW PRESSURE BOILERS WORKBOOK ANSWER KEY

and excess air. Primary air controls 56. A boiler room log is a record of informa- in the eld prior to taking a licensing
the combustion rate, which determines tion pertaining to the operation of a boiler examination. For specic requirements,
the amount of fuel burned. Secondary during a given period of time. Maintain- the licensing jurisdiction should be con-
air controls combustion efciency by ing a boiler room log allows evaluation tacted directly.
controlling how completely the fuel is of boiler performance history such as
burned. Excess air is supplied to the steam pressure generated, water treat- 61. Wear the proper hand and eye protec-
burner above the theoretical amount ment, water levels, fuel consumption, tion. Close the gauge glass steam and
required to burn the fuel. and condensate returns. Boiler room log water valves and open the gauge glass
information can be used to determine the drain valve. Tighten the leaking gauge
50. A flame safeguard system is burner cause of a malfunction or help prevent a glass nut one at of the nut and test for
control equipment that monitors the future problem. leaks. Repeat procedure until the leak
burner star t-up sequence and the stops or the nut cannot be turned any
main flame during normal operation. 57. An aquastat is a hot water boiler tting more. If the leak can not be xed in this
The ame safeguard programmer se- that measures the water temperature in manner, the gauge glass needs to be
quences burner function in a set order the boiler and controls the temperature isolated so the gauge glass washers can
including prepurge, ignition trials, pilot by starting and stopping the burner. An be replaced with new ones. If the gauge
ame-establishing period, main burner aquastat functions like a switch using a glass shows any wear, the gauge glass
ame-establishing period, run period, boiler water temperature setpoint to turn will also need to be replaced.
and postpurge. the burner ON or OFF.
62. The main steam stop valve should be
51. Hydrostatic pressure is pressure caused 58. A compression refrigeration system opened slowly when the boiler pressure
by the weight of water (approximately uses a compressor, refrigerant, and is a few pounds per square inch less than
0.433 psi per vertical foot). Hydrostatic pressure control devices. A compression the header pressure. The valve should
pressure can affect a steam pressure refrigeration system is commonly divided be opened fully and then closed a half
gauge reading depending on the dis- into the high-pressure side and the turn to prevent the valve from seizing up
tance from the steam boiler connec- low-pressure side. In the high-pressure from the expansion of the valve body as
tion. Hydrostatic pressure must also side, refrigerant is changed from a gas it is heated.
be considered when sizing circulating to a liquid. A compressor compresses
pumps for hot water heating systems in refrigerant vapor, and heat is released 63. This is a dangerous low water condition.
multiple-story buildings. in the condenser. In the low-pressure Secure the fuel to the boiler and secure
52. Three types of heat transfer that occur in side, the refrigerant is changed from the pump. Allow the boiler to cool and
a boiler are conduction, convection, and a liquid to a gas. An expansion valve open the boiler for internal inspection
radiation. Conduction is heat transfer that allows a drop in pressure, and the liquid by a qualied inspector. Determine the
occurs when molecules in a material are refrigerant passes to the evaporator reason the feedwater pump did not have
heated and the heat is passed from mol- where it changes to a low-pressure gas water supplied to it and remedy the
ecule to molecule through the material. and absorbs heat. problem. Inspect the feedwater pump to
Convection is heat transfer that occurs determine if there was any damage to
59. A confined space is a space large the pump and repair as needed.
when currents circulate between warm enough and so congured that a worker
and cool regions of a uid. Radiation can physically enter and perform as- 64. A boiler that has been off-line for several
is heat transfer that occurs as radiant signed work, has limited or restricted days should have been completely lled
energy (electromagnetic waves) without means for entry or exit, and is not with treated water to prevent corrosion.
a material carrier. designed for continuous occupancy. To Open the boiler bottom blow down valve(s)
53. A backow preventer is a boiler acces- ensure worker safety, each facility must to decrease the boilers water level to
sory that prevents the ow of boiler water have specic conned space procedures slightly below the normal operating water
back to the city water supply. A backow to comply with OSHA standards in the level (NOWL). The water will expand as
preventer is located on the makeup water Code of Federal Regulations. Depend- the water in the boiler heats up, raising
supply line and functions like a check valve ing on the conned space and task, a the level of the water to the NOWL.
to allow water ow in one direction only. conned space permit may be required.
A conned space permit is a document
54. Expansion bends are sometimes required that details requirements such as lock
on steam lines to allow for the expan- out, personal protective equipment, and
sion and contraction which occurs from ventilation requirements. An entry per-
temperature variation. Without proper mit must be posted at conned space
expansion bends, damage to piping may entrances before entering a permit-
occur from movement in steam lines. required conned space.
55. An evaporation test is a test performed 60. A boiler operator license is obtained by
to ensure proper operation of a low water meeting the requirements established
fuel cutoff. During an evaporation test, a by the specific jurisdiction in which
low water condition is simulated by secur- the boiler is operated. These require-
ing all water fed to the boiler. The boiler ments include passing a boiler operator
water level is then gradually lowered and licensing examination. The licensing
the low water fuel cutoff should shut off jurisdiction can be a state, county, city, or
the burner. Because a low water con- other authority that has specic grades
dition is created, an evaporation test of licensing examinations for different
must only be performed under the close sizes of boilers and related equipment.
supervision of authorized personnel. Some jurisdictions require experience
ISBN 978-0-8269-4360-6
9 0 0 0 0

9 780826 943606

You might also like