STRUCTURAL
CALCULATIONS
PREPARED BY:
NOEL M. DONATO
PRC NO : 79498
PTR NO : 3288281
ISSUED ON : JANUARY 15 2010
ISSUED AT : QUEZON CITY
STRUCTURAL DESIGN CRITERIA:
DESIGN LOADS:
ROOF
DEAD LOAD
roofing 16 psf
purlins 2
rafter 2
ceiling 6
26 psf 1.4 36.40 psf
LIVE LOAD 16 psf 1.7 27.20 psf
DEAD LOAD
slab 110 mm 55 psf
topping and finish 25
partition 25
ceiling 6
111 psf 1.4 155.40 psf
LIVE LOAD 40 psf 1.7 68.00 psf
REFERENCES:
Loadings
Design of Slab
Design Moment
M (disc.) = 0.1250 25.78 3.2223 k - ft
BEAM
ku 465.43
As 1.51 in2
BEAM
ku 349.59
As 1.22 in2
BEAM
ku 349.59
As 1.22 in2
BEAM
ku 524.39
As 2.01 in2
SHORT SPAN
MOMENT COEFFICIENTS
1.00 0.98 0.96 0.94 0.92 0.90
Negative Moment at
Negative Moment at
Negative Moment at
Negative Moment at
Negative Moment at
Continous Edge
Discontinous Edge 0.0330 0.0340 0.0350 0.0360 0.0370 0.0380
Positive Mom. Mid Span 0.0500 0.0514 0.0528 0.0542 0.0556 0.0570
SLAB COEFFICIENT
SHORT SPAN
MOMENT COEFFICIENTS
0.74 0.72 0.70 0.68 0.66 0.64
Negative Moment at
Negative Moment at
Negative Moment at
Negative Moment at
Negative Moment at
Continous Edge
Discontinous Edge 0.0454 0.0462 0.0470 0.0482 0.0494 0.0506
Positive Mom. Mid Span 0.0688 0.0704 0.0720 0.0736 0.0752 0.0768
SHORT SPAN LONG SPAN
0.88 0.86 0.84 0.82 0.8 0.78 0.76 ALL VALUES OF M