NATIONAL UNIVERSITY OF SCIENCES AND TECHNOLOGY

Assignment 3(5 marks)


MS-EEE-812 ADVANCED POWER SYSTEM PROTECTION-Fall 2016
Due Date: Tue 10 Jan 2017
U.S.- PAKISTAN CENTER FOR ADVANCED STUDIES IN ENERGY AT
NUST (USPCAS-E)

Establish appropriate value of the resistor R connected to the secondary


winding of an earthing transformer using the following data:
Generator: Sn=90MVA, Vn=15kV,
Earthing Transformer: ratio 20/0.5 kV/kV, R1=500, R2=0.1
Total capacitance of the system (generator, transformer and connecting
cables) is C=0.45F per phase. Assume that it is desired that the earth fault
current should not exceed the total residual capacitive current IC.