You are on page 1of 184

MiCOM

P342, P343,
P344, P345 & P391
Generator Protection Relay

Software Version 33
Hardware Suffix J (P342/3/4)
Hardware Suffix K (P345)
Hardware Suffix A (391)

Relay Menu Database

P34x/EN MD/J76
Note: The technical manual for this device gives instructions for its installation, commissioning, and
operation. However, the manual cannot cover all conceivable circumstances or include detailed
information on all topics. In the event of questions or specific problems, do not take any action
without proper authorization. Contact the appropriate AREVA technical sales office and request
the necessary information.

Any agreements, commitments, and legal relationships and any obligations on the part of AREVA
including settlements of warranties, result solely from the applicable purchase contract, which is
not affected by the contents of the technical manual.

This device MUST NOT be modified. If any modification is made without the express permission of
AREVA, it will invalidate the warranty, and may render the product unsafe.

The AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.

MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered
or not, are the property of their owners.

This manual is provided for informational use only and is subject to change without notice.

2008, AREVA. All rights reserved.


Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391

RELAY MENU DATABASE

Date: 20th August 2008


J (P342/3/4) K (P345)
Hardware Suffix:
A (P391)
Software Version: 33
Connection Diagrams: 10P342xx (xx = 01 to 17)
10P343xx (xx = 01 to 19)
10P344xx (xx = 01 to 12)
10P345xx (xx = 01 to 07)
10P391xx (xx = 01 to 02)
P34x/EN MD/J76 Relay Menu Database

MiCOM P342, P343, P344, P345 & P391


Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391

MiCOM P342, P343, P344, P345 & P391

Generator Protection Relay

Relay Menu Database

This version of the Relay Menu Database is specific to the following models:

Model Number Software Number


P342------0330J P342------0330 - A/B/C
P343------0330J P343------0330 - A/B/C
P344------0330J P344------0330 - A/B/C
P345------0330K P345------0330 - A/B/C
P391------0330A P391------0330 - A/B/C

For other models/software versions, please contact AREVA T&D for the relevant
information.
The following software versions are not supported by this menu database, see
TG8614A (0010), TG8614B (0200 - 0400), P34x/EN T/C11 (0500), P34x/EN T/D22
(0600), P34x/EN T/F33 (0700), P34x/EN GC/G44 (0300 - 0310) for information on
the menu database for these software versions).

P342 P343 P344


P342------0010* P343------0010*
P342------0020* P343------0020*
P342------0030* P343------0030*
P342------0040* P343------0040*
P342------0050* P343------0050*
P342------0060* P343------0060*
P342------0070* P343------0070*
P342------0300* P343------0300*
P342------0310* P343------0310* P344------0310*
P34x/EN MD/J76 Relay Menu Database

MiCOM P342, P343, P344, P345 & P391


Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -1

RELAY MENU DATABASE


This Relay Menu Database is split into several sections, these are as follows:

Menu Database for Courier, User Interface and MODBUS

Menu Datatype Definition

Event Data for Courier, User Interface and MODBUS

IEC60870-5-103 Interoperability Guide

Internal Digital Signals

DNP3.0 Device Profile Document

Default Programmable Logic

Menu database
This database defines the structure of the relay menu for the courier interface, the front
panel user interface and the MODBUS interface. This includes all of the relay settings and
measurements. Datatypes for MODBUS and indexed strings for Courier and the user
interface are cross-referenced to the Menu Datatype Definition section (using a G Number).
For all settable cells the setting limits and default value are also defined within this database.

Note: The following labels are used within the database.

Label Description Value


V1 Main VT Rating 1 (100/120V) 4 (380/480V)
V2 Checksynch VT Rating 1 (100/120V) 4 (380/480V)
V3 NVD VT Rating 1 (100/120V) 4 (380/480V)
1 Phase CT Rating 1 or 5 (Setting 0A33)
2 Earth Fault CT Rating 1 or 5 (Setting 0A53)
3 Sensitive CT Rating 1 or 5 (Setting 0A63)

Menu datatype definition


This table defines the datatypes used for MODBUS (the datatypes for the Courier and user
interface are defined within the Menu Database itself using the standard Courier Datatypes).
This section also defines the indexed string setting options for all interfaces. The datatypes
defined within this section are cross-referenced to from the menu database using a G
number.

Event data
This section specifies all the event information that can be produced by the relay. It details
exactly how each event will be presented via the Courier, User and MODBUS interfaces.

IEC60870-5-103 interoperability guide


This table fully defines the operation of the IEC60870-5-103 (VDEW) interface for the relay it
should be read in conjunction with the relevant section of the Communications chapter of this
manual (P34x/EN CM).
P34x/EN MD/J76 Relay Menu Database

(MD) -2 MiCOM P342, P343, P344, P345 & P391

Internal digital signals


This table defines all of the relay internal digital signals (opto inputs, output contacts and
protection inputs and outputs). A relay may have up to 1408 internal signals each
referenced by a numeric index as shown in this table. This numeric index is used to select a
signal for the commissioning monitor port. It is also used to explicitly define protection
events produced by the relay (see the Event Data section).

DNP3.0 device profile document


This table defines all of the objects, functions and/or qualifiers supported.

References
Introduction (P34x/EN IT): User Interface operation and connections to the relay
Communications (P34x/EN CM):Overview of communication interfaces
Courier User Guide R6512
Modicon MODBUS Protocol Reference Guide PI-MBUS-300 Rev E
IEC60870-5-103 Telecontrol Equipment and Systems - Transmission Protocols - Companion
Standard for the informative interface of Protection Equipment.
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 3

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
SYSTEM DATA 00 00 * * * * *
Language 00 01 Indexed String G19 G19 English Setting 0 3 1 2 * * * * *
Password 00 02 ASCII Password(4 chars) G20 4x40001 4x40002 G20 AAAA Setting 65 90 1 0 * * * * *
Binary Flag (8 bits)
Sys Fn Links 00 03 G95 4x40003 G95 Setting 1 1 1 2 * * * * *
Indexed Strings

* = 1 for Model 1, 2 for Model 2, 3 for Model 3, 4 for Model


Description 00 04 ASCII Text(16 chars) G3 4x40004 4x40011 G3 MiCOM P34* Setting 32 163 1 2 * * * * *
4, 5 for Model 5

Plant Reference 00 05 ASCII Text(16 chars) G3 4x40012 4x40019 G3 MiCOM Setting 32 163 1 2 * * * * *
Model Number 00 06 ASCII Text(32 chars) G3 3x30020 3x30035 G3 Model Number Data * * * * *
Serial Number 00 08 ASCII Text(7 chars) G3 3x30044 3x30051 G3 Serial Number Data * * * * *
Frequency 00 09 Unsigned Integer(8 bits) 4x40020 G1 50 Setting 50 60 10 2 * * * * *
Comms Level 00 0A Unsigned Integer(16 bits) 2 Data * * * * *

Relay Address 00 0B Unsigned Integer(16 bits) 255 Setting 0 255 1 1 * * * * *

Relay status (repeat of Courier Status byte without the busy


Binary Flag(16 bits) 3x30001 G26 Data * * * * *
flag)

Plant Status 00 0C Binary Flag(16 bits) G4 3x30002 G4 Data * * * * *


Control Status 00 0D Binary Flag(16 bits) G5 3x30004 G5 Data * * * * *
Active Group 00 0E Unsigned Integer(16 bits) 3x30006 G1 Data * * * * *
UNUSED 00 0F
CB Trip/Close 00 10 Indexed String(2) G55 No Operation Command 0 2 1 1 * Visible to LCD+Front Port
CB Trip/Close N/A 00 10 Indexed String(2) G55 4x40021 G55 No Operation Command 0 2 1 1 * Visible to Rear Port
Software Ref. 1 00 11 ASCII Text(16 chars) 3x30052 3x30059 G3 Data * * * * *
Software Ref. 2 00 12 ASCII Text(16 chars) Data * * * * * Ethernet card software reference, if fitted
Binary Flag The original register 30007 is available for opto inputs #1 to
Opto I/P Status 00 20 G8 3x11025 3x11026 G8 Data * * * * *
Indexed String #16

Binary Flag
Relay O/P Status 00 21 G9 3x30008 3x30009 G9 Data * * * * *
Indexed String
Binary Flag
Alarm Status 1 00 22 G96 3x30011 3x30012 G96 Data * * * * *
Indexed String
UNUSED 00 23
Binary Flag
Opto I/P Status 00 30 G8 3x11025 3x11026 G8 Data * * * * * The original register 30007 is available
Indexed String
Binary Flag
Relay O/P Status 00 40 G9 3x30008 3x30009 G9 Data * * * * *
Indexed String
Binary Flag
Alarm Status 1 00 50 G96 3x30011 3x30012 G96 Data * * * * *
Indexed String
Binary Flag
Alarm Status 2 00 51 G128 3x30013 3x30014 G128 Data * * * * *
Indexed String
Binary Flag(32 bits)
Alarm Status 3 00 52 G228 3x30015 3x30016 G228 Data * * * * *
Indexed String
Access Level 00 D0 Unsigned Integer(16 bits) 3x30010 G1 Data * * * * *
Password Control 00 D1 Unsigned Integer(16 bits) G22 4x40022 G22 2 Setting 0 2 1 2 * * * * *
Password Level 1 00 D2 ASCII Password(4 chars) G20 4x40023 4x40024 G20 AAAA Setting 65 90 1 1 * * * * *
Password Level 2 00 D3 ASCII Password(4 chars) G20 4x40025 4x40026 G20 AAAA Setting 65 90 1 2 * * * * *
Previous Modbus addresses in the event and fault records
VIEW RECORDS 01 00 * * * * *
are retained
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 4

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Number of event records stored. Previous MODBUS
3x10000 G1
address - 3x00100
Number of fault records stored. Previous MODBUS address
3x10001 G1
- 3x00101
Number of maintenance records stored. Previous address -
3x10002 G1
3x00102
Select Event 01 01 Unsigned Integer(16 bits) 4x00100 0 Setting 0 249 1 0 Max value is oldest record

Indicates type of event. Previous MODBUS address -


Menu Cell Ref N/A 01 02 Cell Reference 3x10007 G13 (From Record) Data * * * * *
3x00107. See Event sheet.

Time & Date 01 03 IEC870 Time & Date 3x10003 3x10006 G12 (From Record) Data * * * * * Previous MODBUS address - 3x00103 to 3x00106
Event Text 01 04 Ascii String (32 chars) Data * * * * * See Event sheet
Previous addresses 3x00108 to 3x00109. Binary flag for
Event Value 01 05 Unsigned Int / Binary Flag (32 bits) 3x10008 3x10009 G27 Data * * * * * contact, opto, alarm & protection events. Unsigned integers
for maintenance records. Details see Event sheet.
Select Fault 01 06 Unsigned Integer (16 bits) 4x00101 Setting 0 4 1 2 * * * * * Allows Fault Record to be selected
MODBUS address where change occurred. Previous
3x10010 G1 Data * * * * * address 3x00110. For fault records and maintenance
events the default is 0.
Previous address 3x00111. Contains the DDB ordinal for
3x10011 G1 Data * * * * *
protection events or bit number for alarms.
Previous address 3x00112. 0 = no additional data, 1 = fault
3x10012 G1 Data * * * * *
record data, 2 = maintenance data.
Previous MODBUS address 3x00113. For fault record use
Faulted Phase N/A 01 40 Binary Flag (8 Bits) G16 3x10020 G16 Data * * * * *
only.
Previous MODBUS address 3x00114 to 3x00115. for fault
Start Elements1 N/A 01 42 Binary Flag (32 Bits) G84 3x10022 3x10023 G84 Data * * * * *
record use only.
Previous MODBUS address 3x00116 to 3x00117. For fault
Start Elements2 N/A 01 43 Binary Flag (32 Bits) G107 3x10024 3x10025 G107 Data * * * * *
record use only.
Start Elements3 N/A 01 44 Binary Flag (32 Bits) G129 3x10026 3x10027 G129 Data * * * * * For fault record use only.
Previous MODBUS address 3x00118 to 3x00119. For fault
Trip Elements1 N/A 01 49 Binary Flag (32 Bits) G85 3x10030 3x10031 G85 Data * * * * *
record use only.
Previous MODBUS address 3x00120 to 3x00121. For fault
Trip Elements2 N/A 01 4A Binary Flag (32 Bits) G86 3x10032 3x10033 G86 Data * * * * *
record use only.
Trip Elements3 N/A 01 4B Binary Flag (32 Bits) G130 3x10034 3x10035 G130 Data * * * * * For fault record use only.
Previous MODBUS address 3x00122 to 3x00123. For fault
Fault Alarms N/A 01 50 Binary Flag (32 Bits) G87 3x10038 3x10039 G87 Data * * * * *
record use only.
Previous MODBUS address 3x00124 to 3x00127. For fault
Fault Time 01 55 IEC870 Time & Date 3x10042 3x10045 G12 (From Record) Data * * * * *
record use only.
Previous MODBUS address 3x00128. For fault record use
Active Group 01 57 Unsigned Integer 3x10046 G1 Data * * * * *
only.
Previous MODBUS address 3x00129. For fault record use
System Frequency 01 59 Courier Number (frequency) 3x10047 G30 Data * * * * *
only.
Previous MODBUS addresses 3x00130 to 3x00131. For
Fault Duration 01 5B Courier Number (time) 3x10048 3x10049 G24 Data * * * * *
fault record use only.
Previous MODBUS address 3x00132. For fault record use
CB Operate Time 01 5E Courier Number (time) 3x10050 G25 Data * * * * *
only.
Previous MODBUS addresses 3x00133 to 3x00134. For
Relay Trip Time 01 60 Courier Number (time) 3x10051 3x10052 G24 Data * * * * *
fault record use only.
IA * * Previous MODBUS addresses 3x00135 to 3x00136.
01 62 Courier Number (current) 3x10053 3x10054 G24 Data
IA-1 * * * For fault record use only.
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 5

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
IB * * Previous MODBUS addresses 3x00137 to 3x00138.
01 63 Courier Number (current) 3x10055 3x10056 G24 Data
IB-1 * * * For fault record use only.
IC * * Previous MODBUS addresses 3x00139 to 3x00140.
01 64 Courier Number (current) 3x10057 3x10058 G24 Data
IC-1 * * * For fault record use only.
Previous MODBUS Addresses 3x00141 to 3x00142. For
VAB 01 65 Courier Number (voltage) 3x10059 3x10060 G24 Data * * * * *
fault record use only.
Previous MODBUS addresses 3x00143 to 3x00144. For
VBC 01 66 Courier Number (voltage) 3x10061 3x10062 G24 Data * * * * *
fault record use only.
Previous MODBUS addresses 3x00145 to 3x00146. For
VCA 01 67 Courier Number (voltage) 3x10063 3x10064 G24 Data * * * * *
fault record use only.
Previous MODBUS addresses 3x00147 to 3x00148. For
VAN 01 68 Courier Number (voltage) 3x10065 3x10066 G24 Data * * * * *
fault record use only.
Previous MODBUS addresses 3x00149 to 3x00150. For
VBN 01 69 Courier Number (voltage) 3x10067 3x10068 G24 Data * * * * *
fault record use only.
Previous MODBUS addresses 3x00151 to 3x00152. For
VCN 01 6A Courier Number (voltage) 3x10069 3x10070 G24 Data * * * * *
fault record use only.
Previous MODBUS addresses 3x00153 to 3x00154. For
IA-2 01 70 Courier Number (current) 3x10071 3x10072 G24 Data * * *
fault record use only.
Previous MODBUS addresses 3x00155 to 3x00156. For
IB-2 01 71 Courier Number (current) 3x10073 3x10074 G24 Data * * *
fault record use only.
Previous MODBUS addresses 3x00157 to 3x00158. For
IC-2 01 72 Courier Number (current) 3x10075 3x10076 G24 Data * * *
fault record use only.
Previous MODBUS addresses 3x00159 to 3x00160. For
IA Differential 01 80 Courier Number (current) 3x10077 3x10078 G24 Data * * *
fault record use only.
Previous MODBUS addresses 3x00161 to 3x00162. For
IB Differential 01 81 Courier Number (current) 3x10079 3x10080 G24 Data * * *
fault record use only.
Previous MODBUS addresses 3x00163 to 3x00164. For
IC Differential 01 82 Courier Number (current) 3x10081 3x10082 G24 Data * * *
fault record use only.
VN Measured * * * Previous MODBUS addresses 3x00165 to 3x00166.
01 90 Courier Number (voltage) 3x10083 3x10084 G24 Data
VN1 Measured * * For fault record use only.
VN2 Measured 01 92 Courier Number (voltage) 3x10085 3x10086 G24 Data * * For fault record use only.
Previous MODBUS addresses 3x00167 to 3x00168. For
VN Derived 01 94 Courier Number (voltage) 3x10087 3x10088 G24 Data * * * * *
fault record use only.
IN Measured * * * * Previous MODBUS addresses 3x00169 to 3x00170.
01 96 Courier Number (current) 3x10089 3x10090 G24 Data
IN Derived * For fault record use only.
Previous MODBUS addresses 3x00171 to 3x00172. For
I Sensitive 01 99 Courier Number (current) 3x10091 3x10092 G24 Data * * * * *
fault record use only.
Previous MODBUS addresses 3x00173 to 3x00174. For
IREF Diff 01 9C Courier Number (current) 3x10093 3x10094 G24 Data * * * *
fault record use only.
Previous MODBUS addresses 3x00175 to 3x00176. For
IREF Bias 01 9D Courier Number (current) 3x10095 3x10096 G24 Data * * * *
fault record use only.
Previous MODBUS addresses 3x00177 to 3x00178. For
I2 01 A0 Courier Number (current) 3x10097 3x10098 G24 Data * * * * *
fault record use only.
V2 01 A2 Courier Number (voltage) 3x10099 3x10100 G24 Data * * * * * For fault record use only.
Previous MODBUS addresses 3x00179 to 3x00180. For
3 Phase Watts 01 A6 Courier Number (Power) 3x10101 3x10102 G125 Data * * * * *
fault record use only.
Previous MODBUS addresses 3x00181 to 3x00182. For
3 Phase VArs 01 A8 Courier Number (VAr) 3x10103 3x10104 G125 Data * * * * *
fault record use only.
Previous MODBUS address 3x00183. For fault record use
3Ph Power Factor 01 AA Courier Number (Decimal) 3x10105 G30 Data * * * * *
only.
Previous MODBUS address 3x00184. For fault record use
RTD 1 01 B0 Courier Number (Temperature) 3x10106 G10 Data * * * *
only. Courier text = RTD Label setting.
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 6

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Previous MODBUS address 3x00185. For fault record use
RTD 2 01 B1 Courier Number (Temperature) 3x10107 G10 Data * * * *
only. Courier text = RTD Label setting.
Previous MODBUS address 3x00186. For fault record use
RTD 3 01 B2 Courier Number (Temperature) 3x10108 G10 Data * * * *
only. Courier text = RTD Label setting.
Previous MODBUS address 3x00187. For fault record use
RTD 4 01 B3 Courier Number (Temperature) 3x10109 G10 Data * * * *
only. Courier text = RTD Label setting.
Previous MODBUS address 3x00188. For fault record use
RTD 5 01 B4 Courier Number (Temperature) 3x10110 G10 Data * * * *
only. Courier text = RTD Label setting.
Previous MODBUS address 3x00189. For fault record use
RTD 6 01 B5 Courier Number (Temperature) 3x10111 G10 Data * * * *
only. Courier text = RTD Label setting.
Previous MODBUS address 3x00190. For fault record use
RTD 7 01 B6 Courier Number (Temperature) 3x10112 G10 Data * * * *
only. Courier text = RTD Label setting.
Previous MODBUS address 3x00191. For fault record use
RTD 8 01 B7 Courier Number (Temperature) 3x10113 G10 Data * * * *
only. Courier text = RTD Label setting.
Previous MODBUS address 3x00192. For fault record use
RTD 9 01 B8 Courier Number (Temperature) 3x10114 G10 Data * * * *
only. Courier text = RTD Label setting.
Previous MODBUS address 3x00193. For fault record use
RTD 10 01 B9 Courier Number (Temperature) 3x10115 G10 Data * * * *
only. Courier text = RTD Label setting.
Previous MODBUS address 3x00194. For fault record use
df/dt 01 C2 Courier Number (Hz/s) 3x10116 G25 Data *
only.
Previous MODBUS address 3x00195. For fault record use
V Vector Shift 01 C4 Courier Number (Angle) 3x10117 G30 Data *
only.
Previous MODBUS address 3x00490. For fault record use
CLIO Input 1 01 C6 Courier Number (Decimal) 3x10118 3x10119 G125 Data * * * * *
only. Courier text = CLIO Input label setting.
Previous MODBUS address 3x00492. For fault record use
CLIO Input 2 01 C7 Courier Number (Decimal) 3x10120 3x10121 G125 Data * * * * *
only. Courier text = CLIO Input label setting.
Previous MODBUS address 3x00494. For fault record use
CLIO Input 3 01 C8 Courier Number (Decimal) 3x10122 3x10123 G125 Data * * * * *
only. Courier text = CLIO Input label setting.
Previous MODBUS address 3x00496. For fault record use
CLIO Input 4 01 C9 Courier Number (Decimal) 3x10124 3x10125 G125 Data * * * * *
only. Courier text = CLIO Input label setting.
64S V Magnitude 01 CA Courier Number (Voltage) 3x10126 3x10127 G24 Data * For fault record use only.
64S I Magnitude 01 CB Courier Number (Current) 3x10128 3x10129 G24 Data * For fault record use only.
64S R Primary 01 CC Courier Number (Resistance) 3x10130 3x10131 G125 Data * For fault record use only.
64R CL Input 01 CD Courier Number (current) 3x10132 3x10133 G125 Data * * * * For fault record use only.
64R R Fault 01 CE Courier Number (resistance) 3x10134 3x10135 G125 Data * * * * For fault record use only.
Manual override to
Select Maint 01 F0 Unsigned Integer (16 bits) 4x00102 G1 Setting 0 9 1 0 * * * * * Allows Self Test Report to be selected.
select a fault record.
Maint Text 01 F1 Ascii Text (32 chars) Data * * * * *
Maint Type 01 F2 Unsigned integer (32 bits) 3x00036 3x00037 G27 Data * * * * *
Maint Data 01 F3 Unsigned integer (32 bits) 3x00038 3x00039 G27 Data * * * * *
Reset Indication 01 FF Indexed String G11 No Command 0 1 1 1 * * * * *
MEASUREMENTS 1 02 00 * * * * *
IA Magnitude * *
02 01 Courier Number (current) 3x00200 3x00201 G24 Data
IA-1 Magnitude * * *
IA Phase Angle * *
02 02 Courier Number (angle) 3x00202 G30 Data
IA-1 Phase Angle * * *
IB Magnitude * *
02 03 Courier Number (current) 3x00203 3x00204 G24 Data
IB-1 Magnitude * * *
IB Phase Angle * *
02 04 Courier Number (angle) 3x00205 G30 Data
IB-1 Phase Angle * * *
IC Magnitude * *
02 05 Courier Number (current) 3x00206 3x00207 G24 Data
IC-1 Magnitude * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 7

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
IC Phase Angle * *
02 06 Courier Number (angle) 3x00208 G30 Data
IC-1 Phase Angle * * *
IN Measured Mag 02 07 Courier Number (current) 3x00209 3x00210 G24 Data * * * *
IN Measured Ang 02 08 Courier Number (angle) 3x00211 G30 Data * * * *
IN Derived Mag * *
02 09 Courier Number (current) 3x00212 3x00213 G24 Data
IN-1 Derived Mag * * *
IN Derived Angle 02 0A Courier Number (angle) 3x00214 G30 Data *
Isen Magnitude 02 0B Courier Number (current) 3x00215 3x00216 G24 Data * * * * *-
Isen Angle 02 0C Courier Number (degrees) 3x00217 G30 Data * * * * *
I1 Magnitude 02 0D Courier Number (current) 3x00218 3x00219 G24 Data * * * * *
I2 Magnitude 02 0E Courier Number (current) 3x00220 3x00221 G24 Data * * * * *
I0 Magnitude 02 0F Courier Number (current) 3x00222 3x00223 G24 Data * * * * *
IA RMS 02 10 Courier Number (current) 3x00224 3x00225 G24 Data * * * * *
IB RMS 02 11 Courier Number (current) 3x00226 3x00227 G24 Data * * * * *
IC RMS 02 12 Courier Number (current) 3x00228 3x00229 G24 Data * * * * *
IN-2 Derived Mag 02 13 Courier Number (current) 3x00273 3x00274 G24 Data * * *
VAB Magnitude 02 14 Courier Number (voltage) 3x00230 3x00231 G24 Data * * * * *
VAB Phase Angle 02 15 Courier Number (angle) 3x00232 G30 Data * * * * *
VBC Magnitude 02 16 Courier Number (voltage) 3x00233 3x00234 G24 Data * * * * *
VBC Phase Angle 02 17 Courier Number (angle) 3x00235 G30 Data * * * * *
VCA Magnitude 02 18 Courier Number (voltage) 3x00236 3x00237 G24 Data * * * * *
VCA Phase Angle 02 19 Courier Number (angle) 3x00238 G30 Data * * * * *
VAN Magnitude 02 1A Courier Number (voltage) 3x00239 3x00240 G24 Data * * * * *
VAN Phase Angle 02 1B Courier Number (angle) 3x00241 G30 Data * * * * *
VBN Magnitude 02 1C Courier Number (voltage) 3x00242 3x00243 G24 Data * * * * *
VBN Phase Angle 02 1D Courier Number (angle) 3x00244 G30 Data * * * * *
VCN Magnitude 02 1E Courier Number (voltage) 3x00245 3x00246 G24 Data * * * * *
VCN Phase Angle 02 1F Courier Number (angle) 3x00247 G30 Data * * * * *
VN Measured Mag * * *
02 20 Courier Number (voltage) 3x00248 3x00249 G24 Data
VN1 Measured Mag * *
VN Measured Ang * * *
02 21 Courier Number (angle) 3x00250 G30 Data
VN1 Measured Ang * *
VN Derived Mag 02 22 Courier Number (voltage) 3x00251 3x00252 G24 Data * * * * *
VN Derived Ang 02 23 Courier Number (angle) 3x00272 G30 Data * * * * *
V1 Magnitude 02 24 Courier Number (voltage) 3x00253 3x00254 G24 Data * * * * *
V2 Magnitude 02 25 Courier Number (voltage) 3x00255 3x00256 G24 Data * * * * *
V0 Magnitude 02 26 Courier Number (voltage) 3x00257 3x00258 G24 Data * * * * *
VAN RMS 02 27 Courier Number (voltage) 3x00259 3x00260 G24 Data * * * * *
VBN RMS 02 28 Courier Number (voltage) 3x00261 3x00262 G24 Data * * * * *
VCN RMS 02 29 Courier Number (voltage) 3x00263 3x00264 G24 Data * * * * *
Frequency 02 2D Courier Number (frequency) 3x00265 G30 Data * * * * *
I1 Magnitude 02 40 Courier Number (current) 3x00218 3x00219 G24 Data * * * * *
I1 Phase Angle 02 41 Courier Number (angle) 3x00266 G30 Data * * * * *
I2 Magnitude 02 42 Courier Number (current) 3x00220 3x00221 G24 Data * * * * *
I2 Phase Angle 02 43 Courier Number (angle) 3x00267 G30 Data * * * * *
I0 Magnitude 02 44 Courier Number (current) 3x00222 3x00223 G24 Data * * * * *
I0 Phase Angle 02 45 Courier Number (angle) 3x00268 G30 Data * * * * *
V1 Magnitude 02 46 Courier Number (voltage) 3x00253 3x00254 G24 Data * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 8

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
V1 Phase Angle 02 47 Courier Number (angle) 3x00269 G30 Data * * * * *
V2 Magnitude 02 48 Courier Number (voltage) 3x00255 3x00256 G24 Data * * * * *
V2 Phase Angle 02 49 Courier Number (angle) 3x00270 G30 Data * * * * *
V0 Magnitude 02 4A Courier Number (voltage) 3x00257 3x00258 G24 Data * * * * *
V0 Phase Angle 02 4B Courier Number (angle) 3x00271 G30 Data * * * * *
VN2 Measured Mag 02 50 Courier Number (voltage) 3x00275 3x00276 G24 Data * *
VN2 Measured Ang 02 51 Courier Number (angle) 3x00277 G30 Data * *
MEASUREMENTS 2 03 00 * * * *
Alternative MODBUS register pairs 30391 and 30392
A Phase Watts 03 01 Courier Number (Power) 3x00300 3x00302 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30393 and 30394
B Phase Watts 03 02 Courier Number (Power) 3x00303 3x00305 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30395 and 30396
C Phase Watts 03 03 Courier Number (Power) 3x00306 3x00308 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30397 and 30398
A Phase VArs 03 04 Courier Number (VAr) 3x00309 3x00311 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30399 and 30400
B Phase VArs 03 05 Courier Number (VAr) 3x00312 3x00314 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30401 and 30402
C Phase VArs 03 06 Courier Number (VAr) 3x00315 3x00317 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30403 and 30404
A Phase VA 03 07 Courier Number (VA) 3x00318 3x00320 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30405 and 30406
B Phase VA 03 08 Courier Number (VA) 3x00321 3x00323 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30407 and 30408
C Phase VA 03 09 Courier Number (VA) 3x00324 3x00326 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30409 and 30410
3 Phase Watts 03 0A Courier Number (Power) 3x00327 3x00329 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30411 and 30412
3 Phase VArs 03 0B Courier Number (VAr) 3x00330 3x00332 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30413 and 30414
3 Phase VA 03 0C Courier Number (VA) 3x00333 3x00335 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30500 and 30501
NPS Power S2 03 0D Courier Number (VA) 3x00336 3x00338 G29 Data * * * *
available with improved G125 floating point data type.
3Ph Power Factor 03 0E Courier Number (decimal) 3x00339 G30 Data * * * * *
APh Power Factor 03 0F Courier Number (decimal) 3x00340 G30 Data * * * * *
BPh Power Factor 03 10 Courier Number (decimal) 3x00341 G30 Data * * * * *
CPh Power Factor 03 11 Courier Number (decimal) 3x00342 G30 Data * * * * *
Alternative MODBUS register pairs 30415 and 30416
3Ph WHours Fwd 03 12 Courier Number (Wh) 3x00343 3x00345 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30417 and 30418
3Ph WHours Rev 03 13 Courier Number (Wh) 3x00346 3x00348 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30419 and 30420
3Ph VArHours Fwd 03 14 Courier Number (VArh) 3x00349 3x00351 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30421 and 30422
3Ph VArHours Rev 03 15 Courier Number (VArh) 3x00352 3x00354 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30423 and 30424
3Ph W Fix Demand 03 16 Courier Number (Power) 3x00355 3x00357 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30425 and 30426
3Ph VArs Fix Dem 03 17 Courier Number (Vars) 3x00358 3x00360 G29 Data * * * * *
available with improved G125 floating point data type.
IA Fixed Demand 03 18 Courier Number (Current) 3x00361 3x00362 G24 Data * * * * *
IB Fixed Demand 03 19 Courier Number (Current) 3x00363 3x00364 G24 Data * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 9

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
IC Fixed Demand 03 1A Courier Number (Current) 3x00365 3x00366 G24 Data * * * * *
Alternative MODBUS register pairs 30427 and 30428
3 Ph W Roll Dem 03 1B Courier Number (Power) 3x00367 3x00369 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30429 and 30430
3Ph VArs RollDem 03 1C Courier Number (VAr) 3x00370 3x00372 G29 Data * * * * *
available with improved G125 floating point data type.
IA Roll Demand 03 1D Courier Number (Current) 3x00373 3x00374 G24 Data * * * * *
IB Roll Demand 03 1E Courier Number (Current) 3x00375 3x00376 G24 Data * * * * *
IC Roll Demand 03 1F Courier Number (Current) 3x00377 3x00378 G24 Data * * * * *
Alternative MODBUS register pairs 30431 and 30432
3Ph W Peak Dem 03 20 Courier Number (Power) 3x00379 3x00381 G29 Data * * * * *
available with improved G125 floating point data type.
Alternative MODBUS register pairs 30433 and 30434
3Ph VAr Peak Dem 03 21 Courier Number (VAr) 3x00382 3x00384 G29 Data * * * * *
available with improved G125 floating point data type.
IA Peak Demand 03 22 Courier Number (Current) 3x00385 3x00386 G24 Data * * * * *
IB Peak Demand 03 23 Courier Number (Current) 3x00387 3x00388 G24 Data * * * * *
IC Peak Demand 03 24 Courier Number (Current) 3x00389 3x00390 G24 Data * * * * *
Reset Demand 03 25 Indexed String G11 4x00103 G11 No Command 0 1 1 1 * * * * *
Recommended MODBUS register pairs for power and energy measurements using G125 floating point data type. See SCADA Communications section of the Technical Manual.
N/A 3x00391 3x00392 G125 Data * * * * * A Phase Watts (see [0301])
N/A 3x00393 3x00394 G125 Data * * * * * B Phase Watts (see [0302])
N/A 3x00395 3x00396 G125 Data * * * * * C Phase Watts (see [0303])
N/A 3x00397 3x00398 G125 Data * * * * * A Phase VArs (see [0304])
N/A 3x00399 3x00400 G125 Data * * * * * B Phase VArs (see [0305])
N/A 3x00401 3x00402 G125 Data * * * * * C Phase VArs (see [0306])
N/A 3x00403 3x00404 G125 Data * * * * * A Phase VA (see [0307])
N/A 3x00405 3x00406 G125 Data * * * * * B Phase VA (see [0308])
N/A 3x00407 3x00408 G125 Data * * * * * C Phase VA (see [0309])
N/A 3x00409 3x00410 G125 Data * * * * * 3 Phase Watts (see [030A])
N/A 3x00411 3x00412 G125 Data * * * * * 3 Phase VArs (see [030B])
N/A 3x00413 3x00414 G125 Data * * * * * 3 Phase VA (see [030C])
N/A 3x00415 3x00416 G125 Data * * * * * 3 Phase WHours Fwd (see [0312])
N/A 3x00417 3x00418 G125 Data * * * * * 3 Phase WHours Rev (see [0313])
N/A 3x00419 3x00420 G125 Data * * * * * 3 Phase VArHours Fwd (see [0314])
N/A 3x00421 3x00422 G125 Data * * * * * 3 Phase VArHours Rev (see [0315])
N/A 3x00423 3x00424 G125 Data * * * * * 3 Phase W Fix Demand (see [0316])
N/A 3x00425 3x00426 G125 Data * * * * * 3 Phase VArs Fix Demand (see [0317])
N/A 3x00427 3x00428 G125 Data * * * * * 3 Phase W Roll Demand (see [031B])
N/A 3x00429 3x00430 G125 Data * * * * * 3 Phase VArs Roll Demand (see [031C])
N/A 3x00431 3x00432 G125 Data * * * * * 3 Phase W Peak Demand (see [0320])
N/A 3x00433 3x00434 G125 Data * * * * * 3 Phase VArs Peak Demand (see [0321])
N/A 3x00500 3x00501 G125 Data * * * * NPS Power S2 (see [030D])
MEASUREMENTS 3 04 00 * * *
MEASUREMENTS 3 04 00 *
MEASUREMENTS 3 04 00 *
IA-2 Magnitude 04 01 Courier Number (Current) 3x00435 3x00436 G24 Data * * *
IA-2 Phase Angle 04 02 Courier Number (Angle) 3x00437 G30 Data * * *
IB-2 Magnitude 04 03 Courier Number (Current) 3x00438 3x00439 G24 Data * * *
IB-2 Phase Angle 04 04 Courier Number (Angle) 3x00440 G30 Data * * *
IC-2 Magnitude 04 05 Courier Number (Current) 3x00441 3x00442 G24 Data * * *
IC-2 Phase Angle 04 06 Courier Number (Angle) 3x00443 G30 Data * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 10

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
IA Differential 04 07 Courier Number (Current) 3x00444 3x00445 G24 Data * * *
IB Differential 04 08 Courier Number (Current) 3x00446 3x00447 G24 Data * * *
IC Differential 04 09 Courier Number (Current) 3x00448 3x00449 G24 Data * * *
IA Bias 04 0A Courier Number (Current) 3x00450 3x00451 G24 Data * * *
IB Bias 04 0B Courier Number (Current) 3x00452 3x00453 G24 Data * * *
IC Bias 04 0C Courier Number (Current) 3x00454 3x00455 G24 Data * * *
IREF Diff 04 0D Courier Number (Current) 3x00456 3x00457 G24 Data * * * *
IREF Bias 04 0E Courier Number (Current) 3x00458 3x00459 G24 Data * * * *
VN 3rd Harmonic 04 0F Courier Number (Voltage) 3x00460 3x00461 G24 Data * * *
NPS Thermal 04 10 Courier Number (Percentage) 3x00462 G1 Data * * * *
Reset NPSThermal 04 11 Indexed String G11 4x00104 G11 No Command 0 1 1 1 * * * *
RTD 1 04 12 Courier Number (Temperature) 3x00463 G10 Data * * * * Courier text = RTD label setting
RTD 2 04 13 Courier Number (Temperature) 3x00464 G10 Data * * * * Courier text = RTD label setting
RTD 3 04 14 Courier Number (Temperature) 3x00465 G10 Data * * * * Courier text = RTD label setting
RTD 4 04 15 Courier Number (Temperature) 3x00466 G10 Data * * * * Courier text = RTD label setting
RTD 5 04 16 Courier Number (Temperature) 3x00467 G10 Data * * * * Courier text = RTD label setting
RTD 6 04 17 Courier Number (Temperature) 3x00468 G10 Data * * * * Courier text = RTD label setting
RTD 7 04 18 Courier Number (Temperature) 3x00469 G10 Data * * * * Courier text = RTD label setting
RTD 8 04 19 Courier Number (Temperature) 3x00470 G10 Data * * * * Courier text = RTD label setting
RTD 9 04 1A Courier Number (Temperature) 3x00471 G10 Data * * * * Courier text = RTD label setting
RTD 10 04 1B Courier Number (Temperature) 3x00472 G10 Data * * * * Courier text = RTD label setting
Binary Flag (10 bits)
RTD Open Cct 04 1C G108 3x00473 G108 Data * * * *
Indexed String
Binary Flag (10 bits)
RTD Short Cct 04 1D G109 3x00474 G109 Data * * * *
Indexed String
Binary Flag (10 bits)
RTD Data Error 04 1E G110 3x00475 G110 Data * * * *
Indexed String
Reset RTD Flags 04 1F Indexed string G11 4x00105 G11 No Command 0 1 1 1 * * * *
APh Sen Watts 04 20 Courier Number (Power) 3x00476 3x00477 G125 Data * * * * *
APh Sen Vars 04 21 Courier Number (Var) 3x00478 3x00479 G125 Data * * * * *
APh Power Angle 04 22 Courier Number (angle) 3x00480 G30 Data * * * * *
Thermal Overload 04 23 Courier Number (Percentage) 3x00481 G1 Data * * * * *
Reset ThermalO/L 04 24 Indexed String G11 4x00106 G11 No Command 0 1 1 1 * * * * *
CLIO Input 1 04 25 Courier Number (Decimal) 3x00482 3x00483 G125 Data * * * * * Courier Text = CLIO label setting
CLIO Input 2 04 26 Courier Number (Decimal) 3x00484 3x00485 G125 Data * * * * * Courier Text = CLIO label setting
CLIO Input 3 04 27 Courier Number (Decimal) 3x00486 3x00487 G125 Data * * * * * Courier Text = CLIO label setting
CLIO Input 4 04 28 Courier Number (Decimal) 3x00488 3x00489 G125 Data * * * * * Courier Text = CLIO label setting
Turbine Abnormal Frequency (TAF) Band 1
F Band1 Time (s) 04 30 Unsigned Integer (32 bits) 3x00502 3x00503 G27 Data * * * *
Accumulated Time
Reset Freq Band1 04 32 Indexed String G11 4x00107 G11 No Command 0 1 1 1 * * * * Reset TAF Band 1 Time
Turbine Abnormal Frequency (TAF)
F Band2 Time (s) 04 34 Unsigned Integer (32 bits) 3x00504 3x00505 G27 Data * * * *
Band 2 Accumulated Time
Reset Freq Band2 04 36 Indexed String G11 4x00108 G11 No Command 0 1 1 1 * * * * Reset TAF Band 2 Time
Turbine Abnormal Frequency (TAF)
F Band3 Time (s) 04 38 Unsigned Integer (32 bits) 3x00506 3x00507 G27 Data * * * *
Band 3 Accumulated Time
Reset Freq Band3 04 3A Indexed String G11 4x00109 G11 No Command 0 1 1 1 * * * * Reset TAF Band 3 Time
Turbine Abnormal Frequency (TAF)
F Band4 Time (s) 04 3C Unsigned Integer (32 bits) 3x00508 3x00509 G27 Data * * * *
Band 4 Accumulated Time
Reset Freq Band4 04 3E Indexed String G11 4x00110 G11 No Command 0 1 1 1 * * * * Reset TAF Band 4 Time
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 11

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Turbine Abnormal Frequency (TAF)
F Band5 Time (s) 04 40 Unsigned Integer (32 bits) 3x00510 3x00511 G27 Data * * * *
Band 5 Accumulated Time
Reset Freq Band5 04 42 Indexed String G11 4x00111 G11 No Command 0 1 1 1 * * * * Reset TAF Band 5 Time
Turbine Abnormal Frequency (TAF)
F Band6 Time (s) 04 44 Unsigned Integer (32 bits) 3x00512 3x00513 G27 Data * * * *
Band 6 Accumulated Time
Reset Freq Band6 04 46 Indexed String G11 4x00112 G11 No Command 0 1 1 1 * * * * Reset TAF Band 6 Time
Volts/Hz 04 50 Courier Number (Volts/Hz) 3x00514 3x00515 G24 Data * * * * Vab/Frequency
Low frequency injection St EF Voltage magnitude
64S V Magnitude 04 52 Courier Number (Voltage) 3x00516 3x00517 G24 Data *
measured at the relay terminal
Low frequency injection St EF Current magnitude
64S I Magnitude 04 54 Courier Number (Current) 3x00518 3x00519 G24 Data *
measured at the relay terminal
St EF current angle measurement, affected by Comp Angle
64S I Angle 04 55 Courier Number (Angle) 3x00520 G30 Data * setting when St EF is enabled. I64S phase angle relative to
V64S vector.
St EF secondary resistance measurement at the relay
64S R secondary 04 57 Courier Number (Resistance) 3x00521 3x00522 G125 Data Data *
terminal, affected by Series R and Parallel G settings
St EF primary resistance, converted from secondary
64S R primary 04 58 Courier Number (Resistance) 3x00523 3x00524 G125 Data *
resistance using the R Factor setting
64R CL Input 04 71 Courier Number (current) 3x00539 3x00540 G125 Data * * * *
64R R Fault 04 72 Courier Number (resistance) 3x00541 3x00542 G125 Data * * * *
CB CONDITION 06 00 * * * * *
CB Operations 06 01 Unsigned Integer 3x00600 G1 Data * * * * * Number of Circuit Breaker Operations
Total IA Broken 06 02 Courier Number (current) 3x00601 3x00602 G24 Data * * * * * Broken Current A Phase
Total IB Broken 06 03 Courier Number (current) 3x00603 3x00604 G24 Data * * * * * Broken Current B Phase
Total IC Broken 06 04 Courier Number (current) 3x00605 3x00606 G24 Data * * * * * Broken Current C Phase
CB Operate Time 06 05 Courier Number (time) 3x00607 G25 Data * * * * * Circuit Breaker operating time
Reset CB Data 06 06 Indexed String G11 4x00150 G11 No Command 0 1 1 1 * * * * * Reset All Values
CB CONTROL 07 00 * * * * *
CB Control by 07 01 Indexed String G99 4x00200 G99 Disabled Setting 0 7 1 2 *
Close Pulse Time 07 02 Courier Number (Time) 4x00201 G2 0.5 Setting 0.1 10 0.01 2 *
Trip Pulse Time 07 03 Courier Number (Time) 4x00202 G2 0.5 Setting 0.1 5 0.01 2 *
Man Close Delay 07 05 Courier Number (Time) 4x00203 G2 10 Setting 0.01 600 0.01 2 * Manual Close Delay
CB Healthy Time 07 06 Courier Number (Time) 4x00204 4x00205 G35 5 Setting 0.01 9999 0.01 2 *
Lockout Reset 07 08 Indexed String G11 4x00206 G11 No Command 0 1 1 2 * * * * *
Reset Lockout by 07 09 Indexed String G81 4x00207 G81 CB Close Setting 0 1 1 2 * * * * *
Man Close RstDly 07 0A Courier Number (Time) 4x00208 G2 5 Setting 0.01 600 0.01 2 * * * * * Manual Close Reset Delay
CB Status Input 07 11 Indexed String G118 4x00209 G118 None Setting 0 3 1 2 * * * * *
DATE AND TIME 08 00 * * * * *
Date/Time N/A 08 01 IEC870 Time & Date 4x00300 4x00303 G12 Setting 0 * * * * *
Date *
N/A * * * * Front Panel Menu Only
12-Jan-98
Time *
N/A * * * * Front Panel Menu Only
12:00
IRIG-B Sync 08 04 Indexed String G37 4x00304 G37 Disabled Setting 0 1 1 2 * * * * *
IRIG-B Status 08 05 Indexed String G17 3x00090 G17 Data * * * * *
Battery Status 08 06 Indexed String G59 3x00091 G59 Data * * * * *
Battery Alarm 08 07 Indexed String G37 4x00305 G37 Enabled Setting 0 1 1 2 * * * * *
SNTP Status 08 13 Indexed String G247 Data * * * * *
LocalTime Enable 08 20 Indexed String G254 Fixed Setting 0 2 1 2 * * * * *
LocalTime Offset 08 21 Courier Number (Time Minutes) 0 Setting -720 720 15 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 12

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
DST Enable 08 22 Indexed String G37 Enabled Setting 0 1 1 2 * * * * *
DST Offset 08 23 Courier Number (Time Minutes) 60 Setting 30 60 30 2 * * * * *
DST Start 08 24 Indexed String G252 Last Setting 0 4 1 2 * * * * *
DST Start Day 08 25 Indexed String G250 Sunday Setting 0 6 1 2 * * * * *
DST Start Month 08 26 Indexed String G251 March Setting 0 11 1 2 * * * * *
DST Start Mins 08 27 Courier Number (Time Minutes) 60 Setting 0 1425 15 2 * * * * *
DST End 08 28 Indexed String G252 Last Setting 0 4 1 2 * * * * *
DST End Day 08 29 Indexed String G250 Sunday Setting 0 6 1 2 * * * * *
DST End Month 08 2A Indexed String G251 October Setting 0 11 1 2 * * * * *
DST End Mins 08 2B Courier Number (Time Minutes) 60 Setting 0 1425 15 2 * * * * *
RP1 Time Zone 08 30 Indexed String G253 Local Setting 0 1 1 2 * * * * *
RP2 Time Zone 08 31 Indexed String G253 Local Setting 0 1 1 2 * * * * *
Tunnel Time Zone 08 33 Indexed String G253 Local Setting 0 1 1 2 * * * * *
CONFIGURATION 09 00 * * * * *
Restore Defaults 09 01 Indexed String G53 4x00402 G53 No Operation Command 0 5 1 2 * * * * *
Setting Group 09 02 Indexed String G61 4x00403 G61 Menu Setting 0 1 1 2 * * * * *
Active Settings 09 03 Indexed String G90 4x00404 G90 1 Setting 0 3 1 1 * * * * *
Save Changes 09 04 Indexed String G62 4x00405 G62 No Operation Command 0 2 1 2 * * * * *
Copy From 09 05 Indexed String G90 4x00406 G90 Group 1 Setting 0 3 1 2 * * * * *
Copy To 09 06 Indexed String G98 4x00407 G98 No Operation Command 0 3 1 2 * * * * *
Setting Group 1 09 07 Indexed String G37 4x00408 G37 Enabled Setting 0 1 1 2 * * * * *
Setting Group 2 09 08 Indexed String G37 4x00409 G37 Disabled Setting 0 1 1 2 * * * * *
Setting Group 3 09 09 Indexed String G37 4x00410 G37 Disabled Setting 0 1 1 2 * * * * *
Setting Group 4 09 0A Indexed String G37 4x00411 G37 Disabled Setting 0 1 1 2 * * * * *
System Config 09 0B Indexed String G80 4x00437 Visible Setting 0 1 1 2 * * * * *
Power 09 0C Indexed String G37 4x00413 G37 Enabled Setting 0 1 1 2 * * * * *
Field Failure 09 0D Indexed String G37 4x00414 G37 Enabled Setting 0 1 1 2 * * * *
NPS Thermal 09 0E Indexed String G37 4x00415 G37 Enabled Setting 0 1 1 2 * * * *
System Backup 09 0F Indexed String G37 4x00416 G37 Enabled Setting 0 1 1 2 * * * *
Overcurrent 09 10 Indexed String G37 4x00417 G37 Enabled Setting 0 1 1 2 * * * * *
Thermal Overload 09 11 Indexed String G37 4x00433 G37 Disabled Setting 0 1 1 2 * * * * *
Gen Differential 09 12 Indexed String G37 4x00412 G37 Enabled Setting 0 1 1 2 * * *
Earth Fault 09 13 Indexed String G37 4x00418 G37 Enabled Setting 0 1 1 2 * * * * *
Rotor EF 09 14 Indexed String G37 4x00438 G37 Enabled Setting 0 1 1 2 * * * *
Disabled *
SEF/REF/SPower 09 15 Indexed String G114 4x00419 G114 Setting 0 2 1 2
SEF/REF * * * *
Residual O/V NVD 09 16 Indexed String G37 4x00420 G37 Enabled Setting 0 1 1 2 * * * * * Residual Overvoltage
100% Stator EF 09 17 Indexed String G37 4x00421 G37 Disabled Setting 0 1 1 2 * *
Enabled *
V/Hz 09 18 Indexed String G37 4x00422 G37 Disabled Setting 0 1 1 2 * * * *
df/dt 09 19 Indexed String G37 4x00423 G37 Enabled Setting 0 1 1 2 *
V Vector Shift 09 1A Indexed String G37 4x00424 G37 Disabled Setting 0 1 1 2 *
Dead Machine 09 1B Indexed String G37 4x00425 G37 Disabled Setting 0 1 1 2 * * *
Reconnect Delay 09 1C Indexed String G37 4x00426 G37 Disabled Setting 0 1 1 2 *
Volt Protection 09 1D Indexed String G37 4x00427 G37 Enabled Setting 0 1 1 2 * * * * *
Freq Protection 09 1E Indexed String G37 4x00428 G37 Enabled Setting 0 1 1 2 * * * * *
RTD Inputs 09 1F Indexed String G37 4x00429 G37 Enabled Setting 0 1 1 2 * * * *
CB Fail 09 20 Indexed String G37 4x00430 G37 Disabled Setting 0 1 1 2 * * * * *
Supervision 09 21 Indexed String G37 4x00431 G37 Disabled Setting 0 1 1 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 13

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
NOT USED 09 22
NOT USED 09 23
Pole Slipping 09 24 Indexed String G37 4x00436 G37 Enabled Setting 0 1 1 2 * * *
Input Labels 09 25 Indexed String G80 Visible Setting 0 1 1 1 * * * * *
Output Labels 09 26 Indexed String G80 Visible Setting 0 1 1 1 * * * * *
RTD Labels 09 27 Indexed String G80 Visible Setting 0 1 1 1 * * * *
CT & VT Ratios 09 28 Indexed String G80 Visible Setting 0 1 1 1 * * * * *
Record Control 09 29 Indexed String G80 Visible Setting 0 1 1 1 * * * * *
Disturb Recorder 09 2A Indexed String G80 Visible Setting 0 1 1 1 * * * * * Disturbance Recorder
Measure't Setup 09 2B Indexed String G80 Visible Setting 0 1 1 1 * * * * *
Comms Settings 09 2C Indexed String G80 Visible Setting 0 1 1 1 * * * * *
Commission Tests 09 2D Indexed String G80 Visible Setting 0 1 1 1 * * * * *
Setting Values 09 2E Indexed String G54 Primary Setting 0 1 1 1 * * * * *
Control Inputs 09 2F Indexed String G80 Visible Setting 0 1 1 2 * * * * *
CLIO Inputs 09 30 Indexed String G37 4x00434 G37 Enabled Setting 0 1 1 2 * * * * *
CLIO Outputs 09 31 Indexed String G37 4x00435 G37 Enabled Setting 0 1 1 2 * * * * *
CLIO status (Hidden)
09 32
(Note: No Courier Text)
Ctrl I/P Config 09 35 Indexed String G80 Visible Setting 0 1 1 1 * * * *
Ctrl I/P Labels 09 36 Indexed String G80 Visible Setting 0 1 1 1 * * * * *
0 3 1 1 *
Direct Access 09 39 Indexed String G231 Enabled Setting
0 1 1 1 * * * *
Function Keys 09 50 Indexed String G80 4x00432 Visible Setting 0 1 1 1 *

LCD Contrast 09 FF Unsigned Integer (16 bits) 11 Setting 0 31 1 1 * * * * *

4x00400 G18 * * * * * Record Selection Command Register


4x00401 G6 * * * * * Record Control Command Register
CT AND VT RATIOS 0A 00 * * * * * Values for Multipliers Used Elsewhere
Main VT Primary 0A 12 Courier Number (Voltage) 4x00500 4x00501 G35 110 Setting 100 1000000 1 2 * * * * * Label V1=Main VT Rating/110
Main VT Sec'y 0A 13 Courier Number (Voltage) 4x00502 G2 110 Setting 80*V1 140*V1 1*V1 2 * * * * * Label M1=Main [0A12]/[0A13]
Neutral Displacement VT Primary
VN1 VT Primary 0A 22 Courier Number (Voltage) 4x00503 4x00504 G35 110 Setting 100 1000000 1 2 * * * * *
Label V3=Neutral Disp VT Rating/110
Neutral Displacement VT Secondary
VN1 VT Secondary 0A 23 Courier Number (Voltage) 4x00505 G2 110 Setting 80*V3 140*V3 1*V3 2 * * * * *
Label M3=[0A22]/[0A23]
Second NVD VT
VN2 VT Primary 0A 27 Courier Number (Voltage) 4x00506 4x00507 G35 110 Setting 100 1000000 1 2 * *
Label V2=VN2 VT Rating/110
Second NVD VT
VN2 VT Secondary 0A 28 Courier Number (Voltage) 4x00508 G2 110 Setting 80*V2 140*V2 1*V2 2 * *
Label M2=[0A27]/[0A28]
Phase CT Primary 0A 32 Courier Number (Current) 4x00509 G2 1 Setting 1 30000 1 2 * * * * * I1=Phase CT Secondary Rating
Phase CT Sec'y 0A 33 Courier Number (Current) 4x00510 G2 1 Setting 1 5 4 2 * * * * * Label M4=[0A32]/[0A33]
E/F CT Primary 0A 52 Courier Number (Current) 4x00511 G2 1 Setting 1 30000 1 2 * * * * Label I2=E/F CT Secondary Rating
E/F CT Secondary 0A 53 Courier Number (Current) 4x00512 G2 1 Setting 1 5 4 2 * * * * Label M5=[0A52]/[0A53]
Isen CT Primary 0A 62 Courier Number (Current) 4x00513 G2 1 Setting 1 30000 1 2 * * * * * Label I3=SEF CT Secondary Rating
Isen CT Sec'y 0A 63 Courier Number (Current) 4x00514 G2 1 Setting 1 5 4 2 * * * * * Label M6=[0A62]/[0A63]
RECORD CONTROL 0B 00 * * * * *
Clear Events 0B 01 Indexed String G11 No Command 0 1 1 1 * * * * *
Clear Faults 0B 02 Indexed String G11 No Command 0 1 1 1 * * * * *
Clear Maint 0B 03 Indexed String G11 No Command 0 1 1 1 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 14

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Alarm Event 0B 04 Indexed String G37 4x10400 G37 Enabled Setting 0 1 1 2 * * * * *
Relay O/P Event 0B 05 Indexed String G37 4x10401 G37 Enabled Setting 0 1 1 2 * * * * *
Opto Input Event 0B 06 Indexed String G37 4x10402 G37 Enabled Setting 0 1 1 2 * * * * *
General Event 0B 07 Indexed String G37 4x10403 G37 Enabled Setting 0 1 1 2 * * * * *
Fault Rec Event 0B 08 Indexed String G37 4x10404 G37 Enabled Setting 0 1 1 2 * * * * *
Maint Rec Event 0B 09 Indexed String G37 4x10405 G37 Enabled Setting 0 1 1 2 * * * * *
Protection Event 0B 0A Indexed String G37 4x10406 G37 Enabled Setting 0 1 1 2 * * * * *
DDB 31 - 0 0B 40 Binary Flag (32 bits) 4x10407 4x10408 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 63 - 32 0B 41 Binary Flag (32 bits) 4x10409 4x10410 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 95 - 64 0B 42 Binary Flag (32 bits) 4x10411 4x10412 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 127 - 96 0B 43 Binary Flag (32 bits) 4x10413 4x10414 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 159 - 128 0B 44 Binary Flag (32 bits) 4x10415 4x10416 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 191 - 160 0B 45 Binary Flag (32 bits) 4x10417 4x10418 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 223 - 192 0B 46 Binary Flag (32 bits) 4x10419 4x10420 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 255 - 224 0B 47 Binary Flag (32 bits) 4x10421 4x10422 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 287 - 256 0B 48 Binary Flag (32 bits) 4x10423 4x10424 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 319 - 288 0B 49 Binary Flag (32 bits) 4x10425 4x10426 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 351 - 320 0B 4A Binary Flag (32 bits) 4x10427 4x10428 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 383 - 352 0B 4B Binary Flag (32 bits) 4x10429 4x10430 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 415 - 384 0B 4C Binary Flag (32 bits) 4x10431 4x10432 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 447 - 416 0B 4D Binary Flag (32 bits) 4x10433 4x10434 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 479 - 448 0B 4E Binary Flag (32 bits) 4x10435 4x10436 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 511 - 480 0B 4F Binary Flag (32 bits) 4x10437 4x10438 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 543 - 512 0B 50 Binary Flag (32 bits) 4x10439 4x10440 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 575 - 544 0B 51 Binary Flag (32 bits) 4x10441 4x10442 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 607 - 576 0B 52 Binary Flag (32 bits) 4x10443 4x10444 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 639 - 608 0B 53 Binary Flag (32 bits) 4x10445 4x10446 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 671 - 640 0B 54 Binary Flag (32 bits) 4x10447 4x10448 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 703 - 672 0B 55 Binary Flag (32 bits) 4x10449 4x10450 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 735 - 704 0B 56 Binary Flag (32 bits) 4x10451 4x10452 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 767 - 736 0B 57 Binary Flag (32 bits) 4x10453 4x10454 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 799 - 768 0B 58 Binary Flag (32 bits) 4x10455 4x10456 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 831 - 800 0B 59 Binary Flag (32 bits) 4x10457 4x10458 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 863 - 832 0B 5A Binary Flag (32 bits) 4x10459 4x10460 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 895 - 864 0B 5B Binary Flag (32 bits) 4x10461 4x10462 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 927 - 896 0B 5C Binary Flag (32 bits) 4x10463 4x10464 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 959 - 928 0B 5D Binary Flag (32 bits) 4x10465 4x10466 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 991 - 960 0B 5E Binary Flag (32 bits) 4x10467 4x10468 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1023 - 992 0B 5F Binary Flag (32 bits) 4x10469 4x10470 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1055 - 1024 0B 60 Binary Flag (32 bits) 4x10471 4x10472 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1087 - 1056 0B 61 Binary Flag (32 bits) 4x10473 4x10474 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1119 - 1088 0B 62 Binary Flag (32 bits) 4x10475 4x10476 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1151 - 1120 0B 63 Binary Flag (32 bits) 4x10477 4x10478 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1183 - 1152 0B 64 Binary Flag (32 bits) 4x10479 4x10480 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1215 - 1184 0B 65 Binary Flag (32 bits) 4x10481 4x10482 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1247 - 1216 0B 66 Binary Flag (32 bits) 4x10483 4x10484 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1279 - 1248 0B 67 Binary Flag (32 bits) 4x10485 4x10486 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1311 - 1280 0B 68 Binary Flag (32 bits) 4x10487 4x10488 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 15

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
DDB 1343 - 1312 0B 69 Binary Flag (32 bits) 4x10489 4x10490 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1375 - 1344 0B 6A Binary Flag (32 bits) 4x10491 4x10492 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DDB 1407 - 1376 0B 6B Binary Flag (32 bits) 4x10493 4x10494 G27 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * *
DISTURB RECORDER 0C 00 * * * * * DISTURBANCE RECORDER
Duration 0C 52 Courier Number (Time) 4x00600 G2 1.5 Setting 0.1 10.5 0.01 2 * * * * *
Trigger Position 0C 54 Courier Number (%) 4x00601 G2 33.3 Setting 0 100 0.1 2 * * * * *
Trigger Mode 0C 56 Indexed String G34 4x00602 G34 Single 0 1 1 2 * * * * *
** Max = 7 for P341, 8 for P342, 11 for P343, 12 for P344,
Analog Channel 1 0C 58 Indexed String G31 4x00603 G31 VAN Setting 0 ** 1 2 * * * * *
14 for P345
Analog Channel 2 0C 59 Indexed String G31 4x00604 G31 VBN Setting 0 ** 1 2 * * * * *
Analog Channel 3 0C 5A Indexed String G31 4x00605 G31 VCN Setting 0 ** 1 2 * * * * *
Analog Channel 4 0C 5B Indexed String G31 4x00606 G31 VN1 Setting 0 ** 1 2 * * * * *
Analog Channel 5 0C 5C Indexed String G31 4x00607 G31 IA (IA-1) Setting 0 ** 1 2 * * * * *
Analog Channel 6 0C 5D Indexed String G31 4x00608 G31 IB (IB-1) Setting 0 ** 1 2 * * * * *
Analog Channel 7 0C 5E Indexed String G31 4x00609 G31 IC (IC-1) Setting 0 ** 1 2 * * * * *
Analog Channel 8 0C 5F Indexed String G31 4x00610 G31 I Sensitive Setting 0 ** 1 2 * * * * *
Analog Channel 9 0C 60 Indexed String G31 4x00675 G31 IN Setting 0 ** 1 2 * * * *
AnalogChannel 10 0C 61 Indexed String G31 4x00676 G31 IA-2 Setting 0 ** 1 2 * * *
AnalogChannel 11 0C 62 Indexed String G31 4x00677 G31 IB-2 Setting 0 ** 1 2 * * *
AnalogChannel 12 0C 63 Indexed String G31 4x00678 G31 IC-2 Setting 0 ** 1 2 * * *
AnalogChannel 13 0C 64 Indexed String G31 4x00679 G31 VN2 Setting 0 ** 1 2 * *
AnalogChannel 14 0C 65 Indexed String G31 4x00680 G31 V64S Setting 0 ** 1 2 *
AnalogChannel 15 0C 66 Indexed String G31 4x00681 G31 I64S Setting 0 ** 1 2 *
Digital Input 1 0C 80 Indexed String G32 4x00611 G32 Output R1 Setting 0 DDB Size 1 2 * * * * *
Input 1 Trigger 0C 81 Indexed String G66 4x00612 G66 No Trigger Setting 0 2 1 2 * * * * *
Digital Input 2 0C 82 Indexed String G32 4x00613 G32 Output R2 Setting 0 DDB Size 1 2 * * * * *
Input 2 Trigger 0C 83 Indexed String G66 4x00614 G66 No Trigger Setting 0 2 1 2 * * * * *
Digital Input 3 0C 84 Indexed String G32 4x00615 G32 Output R3 Setting 0 DDB Size 1 2 * * * * *
Input 3 Trigger 0C 85 Indexed String G66 4x00616 G66 Trigger L/H Setting 0 2 1 2 * * * * *
Digital Input 4 0C 86 Indexed String G32 4x00617 G32 Output R4 Setting 0 DDB Size 1 2 * * * * *
Input 4 Trigger 0C 87 Indexed String G66 4x00618 G66 No Trigger Setting 0 2 1 2 * * * * *
Digital Input 5 0C 88 Indexed String G32 4x00619 G32 Output R5 Setting 0 DDB Size 1 2 * * * * *
Input 5 Trigger 0C 89 Indexed String G66 4x00620 G66 No Trigger Setting 0 2 1 2 * * * * *
Digital Input 6 0C 8A Indexed String G32 4x00621 G32 Output R6 Setting 0 DDB Size 1 2 * * * * *
Input 6 Trigger 0C 8B Indexed String G66 4x00622 G66 No Trigger Setting 0 2 1 2 * * * * *
Digital Input 7 0C 8C Indexed String G32 4x00623 G32 Output R7 Setting 0 DDB Size 1 2 * * * * *
Input 7 Trigger 0C 8D Indexed String G66 4x00624 G66 No Trigger Setting 0 2 1 2 * * * * *
Input L1 * *
Digital Input 8 0C 8E Indexed String G32 4x00625 G32 Setting 0 DDB Size 1 2
Output R8 * * *
Input 8 Trigger 0C 8F Indexed String G66 4x00626 G66 No Trigger Setting 0 2 1 2 * * * * *
Input L2 * *
Digital Input 9 0C 90 Indexed String G32 4x00627 G32 Setting 0 DDB Size 1 2
Output R9 * * *
Input 9 Trigger 0C 91 Indexed String G66 4x00628 G66 No Trigger Setting 0 2 1 2 * * * * *
Input L3 * *
Digital Input 10 0C 92 Indexed String G32 4x00629 G32 Setting 0 DDB Size 1 2
Output R10 * * *
Input 10 Trigger 0C 93 Indexed String G66 4x00630 G66 No Trigger Setting 0 2 1 2 * * * * *
Input L4 * *
Digital Input 11 0C 94 Indexed String G32 4x00631 G32 Setting 0 DDB Size 1 2
Output R11 * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 16

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Input 11 Trigger 0C 95 Indexed String G66 4x00632 G66 No Trigger Setting 0 2 1 2 * * * * *
Input L5 * *
Digital Input 12 0C 96 Indexed String G32 4x00633 G32 Setting 0 DDB Size 1 2
Output R12 * * *
Input 12 Trigger 0C 97 Indexed String G66 4x00634 G66 No Trigger Setting 0 2 1 2 * * * * *
Input L6 * *
Digital Input 13 0C 98 Indexed String G32 4x00635 G32 Setting 0 DDB Size 1 2
Output R13 * * *
Input 13 Trigger 0C 99 Indexed String G66 4x00636 G66 No Trigger Setting 0 2 1 2 * * * * *
Input L7 * *
Digital Input 14 0C 9A Indexed String G32 4x00637 G32 Setting 0 DDB Size 1 2
Output R14 * * *
Input 14 Trigger 0C 9B Indexed String G66 4x00638 G66 No Trigger Setting 0 2 1 2 * * * * *
Input L8 * *
Digital Input 15 0C 9C Indexed String G32 4x00639 G32 Setting 0 DDB Size 1 2
Input L1 * * *
Input 15 Trigger 0C 9D Indexed String G66 4x00640 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 16 0C 9E Indexed String G32 4x00641 G32 Setting 0 DDB Size 1 2
Input L2 * * *
Input 16 Trigger 0C 9F Indexed String G66 4x00642 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 17 0C A0 Indexed String G32 4x00643 G32 Setting 0 DDB Size 1 2
Input L3 * * *
Input 17 Trigger 0C A1 Indexed String G66 4x00644 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 18 0C A2 Indexed String G32 4x00645 G32 Setting 0 DDB Size 1 2
Input L4 * * *
Input 18 Trigger 0C A3 Indexed String G66 4x00646 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 19 0C A4 Indexed String G32 4x00647 G32 Setting 0 DDB Size 1 2
Input L5 * * *
Input 19 Trigger 0C A5 Indexed String G66 4x00648 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 20 0C A6 Indexed String G32 4x00649 G32 Setting 0 DDB Size 1 2
Input L6 * * *
Input 20 Trigger 0C A7 Indexed String G66 4x00650 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 21 0C A8 Indexed String G32 4x00651 G32 Setting 0 DDB Size 1 2
Input L7 * * *
Input 21 Trigger 0C A9 Indexed String G66 4x00652 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 22 0C AA Indexed String G32 4x00653 G32 Setting 0 DDB Size 1 2
Input L8 * * *
Input 22 Trigger 0C AB Indexed String G66 4x00654 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 23 0C AC Indexed String G32 4x00655 G32 Setting 0 DDB Size 1 2
Input L9 * * *
Input 23 Trigger 0C AD Indexed String G66 4x00656 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 24 0C AE Indexed String G32 4x00657 G32 Setting 0 DDB Size 1 2
Input L10 * * *
Input 24 Trigger 0C AF Indexed String G66 4x00658 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 25 0C B0 Indexed String G32 4x00659 G32 Setting 0 DDB Size 1 2
Input L11 * * *
Input 25 Trigger 0C B1 Indexed String G66 4x00660 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 26 0C B2 Indexed String G32 4x00661 G32 Setting 0 DDB Size 1 2
Input L12 * * *
Input 26 Trigger 0C B3 Indexed String G66 4x00662 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 27 0C B4 Indexed String G32 4x00663 G32 Setting 0 DDB Size 1 2
Input L13 * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 17

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Input 27 Trigger 0C B5 Indexed String G66 4x00664 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 28 0C B6 Indexed String G32 4x00665 G32 Setting 0 DDB Size 1 2
Input L14 * * *
Input 28 Trigger 0C B7 Indexed String G66 4x00666 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 29 0C B8 Indexed String G32 4x00667 G32 Setting 0 DDB Size 1 2
Input L15 * * *
Input 29 Trigger 0C B9 Indexed String G66 4x00668 G66 No Trigger Setting 0 2 1 2 * * * * *
Unused * *
Digital Input 30 0C BA Indexed String G32 4x00669 G32 Setting 0 DDB Size 1 2
Input L16 * * *
Input 30 Trigger 0C BB Indexed String G66 4x00670 G66 No Trigger Setting 0 2 1 2 * * * * *
Digital Input 31 0C BC Indexed String G32 4x00671 G32 Unused Setting 0 DDB Size 1 2 * * * *
Function Key 10 *
Input 31 Trigger 0C BD Indexed String G66 4x00672 G66 No Trigger Setting 0 2 1 2 * * * *
Trigger L/H *
Digital Input 32 0C BE Indexed String G32 4x00673 G32 Unused Setting 0 DDB Size 1 2 * * * * *
Input 32 Trigger 0C BF Indexed String G66 4x00674 G66 No Trigger Setting 0 2 1 2 * * * * *
MEASURE'T SETUP 0D 00 * * * * * MEASUREMENT SETTINGS
Default Display 0D 01 Indexed String G52 4x00700 G52 Description Setting 0 7 1 2 * * * * *
Local Values 0D 02 Indexed String G54 4x00701 G54 Primary Setting 0 1 1 1 * * * * * Local Measurement Values
Remote Values 0D 03 Indexed String G54 4x00702 G54 Primary Setting 0 1 1 1 * * * * * Remote Measurement Values
Measurement Ref 0D 04 Indexed String G56 4x00703 G56 VA Setting 0 5 1 1 * * * * * Measurement Phase Reference
Measurement Mode 0D 05 Unsigned Integer 4x00705 G1 0 Setting 0 3 1 1 * * * * *
Fix Dem Period 0D 06 Courier Number (time-minutes) 4x00706 G2 15 Setting 1 99 1 2 * * * * * Fixed Demand Interval
Roll Sub Period 0D 07 Courier Number (time-minutes) 4x00707 G2 1 Setting 1 99 1 2 * * * * * Rolling Demand Sub Period
Num Sub Periods 0D 08 Unsigned Integer 4x00708 G1 15 Setting 1 15 1 2 * * * * * Number of Rolling Sub Periods
Remote 2 Measurement Values Visible when Model No.
Remote 2 Values 0D 0B Indexed String G54 Primary Setting 0 1 1 2 * * * * *
Hardware Option (Field 7) = 7 or 8
COMMUNICATIONS 0E 00 * * * * *
RP1 Protocol 0E 01 Indexed String G71 Data * * * * *
RP1 Address 0E 02 Unsigned integer (16 bits) 255 Setting 0 255 1 1 * * * * * Rear Port 1 Courier Protocol device address
RP1 Address 0E 02 Unsigned integer (16 bits) 1 Setting 1 247 1 1 * * * * * Rear Port 1 MODBUS Protocol device address
RP1 Address 0E 02 Unsigned integer (16 bits) 1 Setting 0 254 1 1 * * * * * Rear Port 1 IEC60870-5-103 Protocol Device Address
RP1 Address 0E 02 Unsigned integer (16 bits) 1 Setting 0 65534 1 1 * * * * * Rear Port 1 DNP 3.0 Protocol Device Address
RP1 InactivTimer 0E 03 Courier Number (Time-minutes) 15 Setting 1 30 1 2 * * * * * Rear Port 1 Courier Protocol Inactivity Timer
RP1 InactivTimer 0E 03 Courier Number (Time-minutes) 15 Setting 1 30 1 2 * * * * * Rear Port 1 MODBUS Protocol Inactivity Timer
RP1 InactivTimer 0E 03 Courier Number (Time-minutes) 15 Setting 1 30 1 2 * * * * * Rear Port 1 IEC60870-5-103 Protocol Inactivity Timer
RP1 Baud Rate 0E 04 Indexed String G38m 19200 bits/s Setting 0 2 1 2 * * * * * Rear Port 1 MODBUS Protocol Serial Bit/Baud Rate
RP1 Baud Rate 0E 04 Indexed String G38v 19200 bits/s Setting 0 1 1 2 * * * * * Rear Port 1 IEC60870-5-103 Protocol Serial Bit/Baud Rate
RP1 Baud Rate 0E 04 Indexed String G38d 19200 bits/s Setting 0 5 1 2 * * * * * Rear Port 1 DNP 3.0 Protocol Serial Bit/Baud Rate
RP1 Parity 0E 05 Indexed String G39 None Setting 0 2 1 2 * * * * * Rear Port 1 MODBUS Protocol Parity
RP1 Parity 0E 05 Indexed String G39 None Setting 0 2 1 2 * * * * * Rear Port 1 DNP 3.0 Protocol Parity
RP1 Meas Period 0E 06 Courier Number (Time) 15 Setting 1 60 1 2 * * * * * Rear Port 1 IEC60870-5-103 Protocol Measurement Period
Rear Port 1 Physical Link Selector Available when Fiber Optic
RP1 PhysicalLink 0E 07 Indexed String G21 Copper Setting 0 1 1 1 * * * * *
Comms Card is Specified by Model Number
Rear Port 1 DNP 3.0 Protocol Time Sync. Configuration. N.B.
RP1 Time Sync 0E 08 Indexed String G37 Disabled Setting 0 1 1 2 * * * * *
Not Available When IRIG-B Option Fitted and Enabled.
Controls the Format of the Time-Date G12 Data Type.
Modbus IEC Time 0E 09 Indexed String G238 4x00306 G238 Standard Setting 0 1 1 2 * * * * *
MODBUS Only.

RP1 CS103Blcking 0E 0A Indexed String G210 Disabled Setting 0 2 1 2 * * * * * Rear Port 1 IEC60870-5-103 Protocol Blocking Configuration
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 18

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
RP1 Card Status 0E 0B Indexed String G208 Data * * * * * Rear Port 1 Courier Protocol Status
Rear Port 1 Courier Protocol Copper Port Configuration; K-
RP1 Port Config 0E 0C Indexed String G207 K-Bus Setting 0 1 1 2 * * * * *
Bus or EIA(RS)485
RP1 Comms Mode 0E 0D Indexed String G206 IEC60870 FT1.2 Setting 0 1 1 2 * * * * * Rear Port 1 Courier Protocol EIA485 Mode
RP1 Baud Rate 0E 0E Indexed String G38c 19200 bits/s Setting 0 2 1 2 * * * * * Rear Port 1 Courier Protocol EIA(RS)485 Bit/Baud Rate
DNP Need Time 0E 11 Courier Number (Time) 10 Setting 1 30 1 2 * * * * *
DNP App Fragment 0E 12 Unsigned Integer 2048 Setting 100 2048 1 2 * * * * *
DNP App Timeout 0E 13 Courier Number (Time) 2 Setting 1 120 1 2 * * * * *
DNP SBO Timeout 0E 14 Courier Number (Time) 10 Setting 1 10 1 2 * * * * *
DNP Link Timeout 0E 15 Courier Number (Time) 0 Setting 0 120 1 2 * * * * *
NIC Protocol 0E 1F Indexed String G235 IEC 61850 Data * * * * *
NIC MAC Address 0E 22 ASCII Text (17 chars) Ethernet MAC Addr Data * * * * *
NIC Tunl Timeout 0E 64 Courier Number (time-minutes) 5.00 min Setting 1 30 1 2 * * * * *
NIC Link Report 0E 6A Indexed String G226 Alarm Setting 0 2 1 2 * * * * *
NIC Link Timeout 0E 6B Courier Number (time) 60.00s Setting 0.1 60 0.1 2 * * * * *
REAR PORT2 (RP2) 0E 80 (Sub Heading) * * * * * Visible when Rear Port 2 Fitted
RP2 Protocol 0E 81 ASCII Text(16 chars) Courier Data * * * * * Rear Port 2 Protocol - "Courier"
RP2 Card Status 0E 84 Indexed String G204 Data * * * * * Rear Port 2 Courier Protocol Status
Rear Port 2 Courier Protocol Port Configuration;
RP2 Port Config 0E 88 Indexed String G205 EIA232 (RS232) Setting 0 2 1 2 * * * * *
K-Bus or EIA(RS)485
RP2 Comms Mode 0E 8A Indexed String G206 IEC60870 FT1.2 Setting 0 1 1 2 * * * * * Rear Port 2 Courier Protocol EIA(RS)485 Mode
RP2 Address 0E 90 Unsigned Integer (16 bits) 255 Setting 0 255 1 1 * * * * * Rear Port 2 Courier Protocol Device Address
RP2 InactivTimer 0E 92 Courier Number (time-minutes) 15 Setting 1 30 1 2 * * * * * Rear Port 2 Courier Protocol Inactivity Timer
RP2 Baud Rate 0E 94 Indexed String G38c 19200 bits/s Setting 0 2 1 2 * * * * * Rear Port 2 Courier Protocol EIA(RS)485 Bit/Baud Rate
COMMISSION TESTS 0F 00 * * * * *
Binary Flag (32 bits) The Original Register 30007 is Available for Opto Inputs #1
Opto I/P Status 0F 01 G8 3x11025 3x11026 G8 Data * * * * *
Indexed String to #16

Binary Flag (32 bits)


Relay O/P Status 0F 02 G9 3x00008 3x00009 G9 Data * * * * *
Indexed String
Binary Flag(8 bits)
Test Port Status 0F 03 3x00722 G1 Data * * * * *
Indexed String
LED Status 0F 04 Binary Flag(8 bits) Data * * * *
Monitor Bit 1 0F 05 Unsigned Integer 4x00850 G1 64 Setting 0 1022 1 1 * * * * *
Monitor Bit 2 0F 06 Unsigned Integer 4x00851 G1 65 Setting 0 1022 1 1 * * * * *
Monitor Bit 3 0F 07 Unsigned Integer 4x00852 G1 66 Setting 0 1022 1 1 * * * * *
Monitor Bit 4 0F 08 Unsigned Integer 4x00853 G1 67 Setting 0 1022 1 1 * * * * *
Monitor Bit 5 0F 09 Unsigned Integer 4x00854 G1 68 Setting 0 1022 1 1 * * * * *
Monitor Bit 6 0F 0A Unsigned Integer 4x00855 G1 69 Setting 0 1022 1 1 * * * * *
Monitor Bit 7 0F 0B Unsigned Integer 4x00856 G1 70 Setting 0 1022 1 1 * * * * *
Monitor Bit 8 0F 0C Unsigned Integer 4x00857 G1 71 Setting 0 1022 1 1 * * * * *
Test Mode 0F 0D Indexed String G119 4x00858 G119 Disabled Setting 0 2 1 2 * * * * * IEC60870 Test Mode Change
Test Pattern 0F 0E Binary Flag (32bits) G9 4x00859 4x00860 G9 0 Setting 0 20 1 2 * * * * * IEC60870 Test Mode Change
Contact Test 0F 0F Indexed String G93 4x00861 G93 No Operation Command 0 2 1 2 * * * * * IEC60870 Test Mode Change
Test LEDs 0F 10 Indexed String G94 4x00862 G94 No Operation Command 0 1 1 2 * * * * *
Binary Flag (32 bits)
Red LED Status 0F 15 Data *
Indexed String
Binary Flag (32 bits)
Green LED Status 0F 16 Data *
Indexed String
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 19

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
The following cells (0F20 to 0F3F) and MODBUS addresses (311023 to 311110) are available to access real-time DDB status, including starts, trips and alarms.
DDB 31 - 0 N/A 0F 20 Binary Flag(32) 3x11023 3x11024 G27 Data * * * * * See DDB Definition Table
DDB 63 - 32 N/A 0F 21 Binary Flag(32) 3x11025 3x11026 G27 Data * * * * *
DDB 95 - 64 N/A 0F 22 Binary Flag(32) 3x11027 3x11028 G27 Data * * * * *
DDB 127 - 96 N/A 0F 23 Binary Flag(32) 3x11029 3x11030 G27 Data * * * * *
DDB 159 - 128 N/A 0F 24 Binary Flag(32) 3x11031 3x11032 G27 Data * * * * *
DDB 191 - 160 N/A 0F 25 Binary Flag(32) 3x11033 3x11034 G27 Data * * * * *
DDB 223 - 192 N/A 0F 26 Binary Flag(32) 3x11035 3x11036 G27 Data * * * * *
DDB 255 - 224 N/A 0F 27 Binary Flag(32) 3x11037 3x11038 G27 Data * * * * *
DDB 287 - 256 N/A 0F 28 Binary Flag(32) 3x11039 3x11040 G27 Data * * * * *
DDB 319 - 288 N/A 0F 29 Binary Flag(32) 3x11041 3x11042 G27 Data * * * * *
DDB 351 - 320 N/A 0F 2A Binary Flag(32) 3x11043 3x11044 G27 Data * * * * *
DDB 383 - 352 N/A 0F 2B Binary Flag(32) 3x11045 3x11046 G27 Data * * * * *
DDB 415 - 384 N/A 0F 2C Binary Flag(32) 3x11047 3x11048 G27 Data * * * * *
DDB 447 - 416 N/A 0F 2D Binary Flag(32) 3x11049 3x11050 G27 Data * * * * *
DDB 479 - 448 N/A 0F 2E Binary Flag(32) 3x11051 3x11052 G27 Data * * * * *
DDB 511 - 480 N/A 0F 2F Binary Flag(32) 3x11053 3x11054 G27 Data * * * * *
DDB 543 - 512 N/A 0F 30 Binary Flag(32) 3x11055 3x11056 G27 Data * * * * *
DDB 575 - 544 N/A 0F 31 Binary Flag(32) 3x11057 3x11058 G27 Data * * * * *
DDB 607 - 576 N/A 0F 32 Binary Flag(32) 3x11059 3x11060 G27 Data * * * * *
DDB 639 - 608 N/A 0F 33 Binary Flag(32) 3x11061 3x11062 G27 Data * * * * *
DDB 671 - 640 N/A 0F 34 Binary Flag(32) 3x11063 3x11064 G27 Data * * * * *
DDB 703 - 672 N/A 0F 35 Binary Flag(32) 3x11065 3x11066 G27 Data * * * * *
DDB 735 - 704 N/A 0F 36 Binary Flag(32) 3x11067 3x11068 G27 Data * * * * *
DDB 767 - 736 N/A 0F 37 Binary Flag(32) 3x11069 3x11070 G27 Data * * * * *
DDB 799 - 768 N/A 0F 38 Binary Flag(32) 3x11071 3x11072 G27 Data * * * * *
DDB 831 - 800 N/A 0F 39 Binary Flag(32) 3x11073 3x11074 G27 Data * * * * *
DDB 863 - 832 N/A 0F 3A Binary Flag(32) 3x11075 3x11076 G27 Data * * * * *
DDB 895 - 864 N/A 0F 3B Binary Flag(32) 3x11077 3x11078 G27 Data * * * * *
DDB 927 - 896 N/A 0F 3C Binary Flag(32) 3x11079 3x11080 G27 Data * * * * *
DDB 959 - 928 N/A 0F 3D Binary Flag(32) 3x11081 3x11082 G27 Data * * * * *
DDB 991 - 960 N/A 0F 3E Binary Flag(32) 3x11083 3x11084 G27 Data * * * * *
DDB 1023 - 992 N/A 0F 3F Binary Flag(32) 3x11085 3x11086 G27 Data * * * * *
DDB 1055 - 1024 N/A 0F 40 Binary Flag(32) 3x11087 3x11088 G27 Data * * * * *
DDB 1087 - 1056 N/A 0F 41 Binary Flag(32) 3x11089 3x11090 G27 Data * * * * *
DDB 1119 - 1088 N/A 0F 42 Binary Flag(32) 3x11091 3x11092 G27 Data * * * * *
DDB 1151 - 1120 N/A 0F 43 Binary Flag(32) 3x11093 3x11094 G27 Data * * * * *
DDB 1183 - 1152 N/A 0F 44 Binary Flag(32) 3x11095 3x11096 G27 Data * * * * *
DDB 1215 - 1184 N/A 0F 45 Binary Flag(32) 3x11097 3x11098 G27 Data * * * * *
DDB 1247 - 1216 N/A 0F 46 Binary Flag(32) 3x11099 3x11100 G27 Data * * * * *
DDB 1279 - 1248 N/A 0F 47 Binary Flag(32) 3x11101 3x11102 G27 Data * * * * *
DDB 1311 - 1280 N/A 0F 48 Binary Flag(32) 3x11103 3x11104 G27 Data * * * * *
DDB 1343 - 1312 N/A 0F 49 Binary Flag(32) 3x11105 3x11106 G27 Data * * * * *
DDB 1375 - 1344 N/A 0F 4A Binary Flag(32) 3x11107 3x11108 G27 Data * * * * *
DDB 1407 - 1376 N/A 0F 4B Binary Flag(32) 3x11109 3x11110 G27 Data * * * * *
Following Registers are in a Logical Block for Ease of
Access
N/A Binary Flag(16) 3x11001 G26 Data * * * * * Relay Status (Repeat of Courier Status)
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 20

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
N/A Courier Number (current) 3x11002 3x11003 G24 Data * * * * * IA Magnitude
N/A Courier Number (current) 3x11004 3x11705 G24 Data * * * * * IB Magnitude
N/A Courier Number (current) 3x11006 3x11007 G24 Data * * * * * IC Magnitude
N/A Courier Number (voltage) 3x11008 3x11009 G24 Data * * * * * VAB Magnitude
N/A Courier Number (voltage) 3x11010 3x11011 G24 Data * * * * * VBC Magnitude
N/A Courier Number (voltage) 3x11012 3x11013 G24 Data * * * * * VCA Magnitude
N/A Courier Number (power) 3x11014 3x11016 G29 Data * * * * * 3 Phase Watts
N/A Courier Number (power) 3x11017 3x11019 G29 Data * * * * * 3 Phase VArs
N/A Courier Number (decimal) 3x11020 G30 Data * * * * * 3 Phase Power Factor
N/A Courier Number (frequency) 3x11021 G30 Data * * * * * Frequency

Relay Test Port Status Note: Maximum block read is 128


registers, with 1408 DDBs & measurements requires a block
N/A Binary Flag(8) 3x11022 G1 Data * * * *
read of 10 registers. Max DDB size supported for 1 read
would be 1696 DDBs

CB MONITOR SETUP 10 00 * * * * *
Broken I^ 10 01 Courier Number (Decimal) 4x00151 G2 2 Setting 1 2 0.1 2 * * * * * Broken Current Index
I^ Maintenance 10 02 Indexed String G88 4x00152 G88 Alarm Disabled Setting 0 1 1 2 * * * * * Broken Current to Cause Maintenance Alarm
I^ Maintenance 10 03 Courier Number (Current) 4x00153 4x00154 G35 1000 Setting 1 25000 1 2 * * * * * IX Maintenance Alarm
I^ Lockout 10 04 Indexed String G88 4x00155 G88 Alarm Disabled Setting 0 1 1 2 * * * * * Broken Current to Cause Lockout Alarm
I^ Lockout 10 05 Courier Number (Current) 4x00156 4x00157 G35 2000 Setting 1 25000 1 2 * * * * * IX Maintenance Lockout
No. CB Ops Maint 10 06 Indexed String G88 4x00158 G88 Alarm Disabled Setting 0 1 1 2 * * * * * Circuit Breaker Trips to Cause Maintenance Alarm
No. CB Ops Maint 10 07 Unsigned Integer 4x00159 G1 10 Setting 1 10000 1 2 * * * * * Number of Circuit Breaker Trips for Maintenance Alarm
No. CB Ops Lock 10 08 Indexed String G88 4x00160 G88 Alarm Disabled Setting 0 1 1 2 * * * * * Circuit Breaker Trips to Cause Lockout Alarm
No. CB Ops Lock 10 09 Unsigned Integer 4x00161 G1 20 Setting 1 10000 1 2 * * * * * Number of Circuit Breaker Trips for Lockout Alarm

CB Time Maint 10 0A Indexed String G88 4x00162 G88 Alarm Disabled Setting 0 1 1 2 * * * * * Circuit Breaker Operating Time to Cause Maintenance Alarm

CB Time Maint 10 0B Courier Number (Time) 4x00163 4x00164 G35 0.1 Setting 0.005 0.5 0.001 2 * * * * * Circuit Breaker Operating Time for Maintenance Alarm
CB Time Lockout 10 0C Indexed String G88 4x00165 G88 Alarm Disabled Setting 0 1 1 2 * * * * * Circuit Breaker Operating Time to Cause Lockout Alarm
CB Time Lockout 10 0D Courier Number (Time) 4x00166 4x00167 G35 0.2 Setting 0.005 0.5 0.001 2 * * * * * Circuit Breaker Operating Time for Lockout Alarm
Fault Freq Lock 10 0E Indexed String G88 4x00168 G88 Alarm Disabled Setting 0 1 1 2 * * * * * Excessive Fault Frequency
Fault Freq Count 10 0F Unsigned Integer 4x00169 G1 10 Setting 1 9999 1 2 * * * * * Excessive Fault Frequency Counter
Fault Freq Time 10 10 Courier Number (Time) 4x00170 4x00171 G35 3600 Setting 0 9999 1 2 * * * * * Excessive Fault Frequency Time
OPTO CONFIG 11 00 * * * * * Visible for Model Number Design Suffix 'B' and Beyond
Global Nominal V 11 01 Indexed String G200 4x00900 G200 48-54V Setting 0 5 1 2 * * * * * Select Custom to Select Individual Opto Threshold Voltages
Opto Input 1 11 02 Indexed String G201 4x00901 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 2 11 03 Indexed String G201 4x00902 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 3 11 04 Indexed String G201 4x00903 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 4 11 05 Indexed String G201 4x00904 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 5 11 06 Indexed String G201 4x00905 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 6 11 07 Indexed String G201 4x00906 G201 48-54V Setting 0 4 1 2 * * * * *
*
Opto Input 7 11 08 Indexed String G201 4x00907 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 8 11 09 Indexed String G201 4x00908 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 9 11 0A Indexed String G201 4x00909 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 10 11 0B Indexed String G201 4x00910 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 11 11 0C Indexed String G201 4x00911 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 12 11 0D Indexed String G201 4x00912 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 13 11 0E Indexed String G201 4x00913 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 14 11 0F Indexed String G201 4x00914 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 15 11 10 Indexed String G201 4x00915 G201 48-54V Setting 0 4 1 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 21

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Opto Input 16 11 11 Indexed String G201 4x00916 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 17 11 12 Indexed String G201 4x00917 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 18 11 13 Indexed String G201 4x00918 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 19 11 14 Indexed String G201 4x00919 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 20 11 15 Indexed String G201 4x00920 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 21 11 16 Indexed String G201 4x00921 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 22 11 17 Indexed String G201 4x00922 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 23 11 18 Indexed String G201 4x00923 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 24 11 19 Indexed String G201 4x00924 G201 48-54V Setting 0 4 1 2 * * * * *
Opto Input 25 11 1A Indexed String G201 4x00925 G201 48-54V Setting 0 4 1 2 * * *
Opto Input 26 11 1B Indexed String G201 4x00926 G201 48-54V Setting 0 4 1 2 * * *
Opto Input 27 11 1C Indexed String G201 4x00927 G201 48-54V Setting 0 4 1 2 * * *
Opto Input 28 11 1D Indexed String G201 4x00928 G201 48-54V Setting 0 4 1 2 * * *
Opto Input 29 11 1E Indexed String G201 4x00929 G201 48-54V Setting 0 4 1 2 * * *
Opto Input 30 11 1F Indexed String G201 4x00930 G201 48-54V Setting 0 4 1 2 * * *
Opto Input 31 11 20 Indexed String G201 4x00931 G201 48-54V Setting 0 4 1 2 * * *
Opto Input 32 11 21 Indexed String G201 4x00932 G201 48-54V Setting 0 4 1 2 * * *
Opto Filter Ctrl 11 50 Binary Flag (32 bits) G8 4x00933 4x00934 G8 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * * Opto Filter Configuration
Opto Input Pick-up & Drop-off Threshold Applicable to
Characteristic 11 80 Indexed String G237 4x00935 G237 Standard 60%-80% Setting 0 1 1 2 * * * * *
Design Suffix "J" or Better
CONTROL INPUTS 12 00 * * * * *
Binary Flag (32 bits)
Ctrl I/P Status 12 01 G202 4x00950 4x00951 G202 Setting 2 * * * * *
Indexed String
Control Input 1 12 02 Indexed String G203 4x00952 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 2 12 03 Indexed String G203 4x00953 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 3 12 04 Indexed String G203 4x00954 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 4 12 05 Indexed String G203 4x00955 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 5 12 06 Indexed String G203 4x00956 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 6 12 07 Indexed String G203 4x00957 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 7 12 08 Indexed String G203 4x00958 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 8 12 09 Indexed String G203 4x00959 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 9 12 0A Indexed String G203 4x00960 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 10 12 0B Indexed String G203 4x00961 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 11 12 0C Indexed String G203 4x00962 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 12 12 0D Indexed String G203 4x00963 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 13 12 0E Indexed String G203 4x00964 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 14 12 0F Indexed String G203 4x00965 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 15 12 10 Indexed String G203 4x00966 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 16 12 11 Indexed String G203 4x00967 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 17 12 12 Indexed String G203 4x00968 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 18 12 13 Indexed String G203 4x00969 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 19 12 14 Indexed String G203 4x00970 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 20 12 15 Indexed String G203 4x00971 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 21 12 16 Indexed String G203 4x00972 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 22 12 17 Indexed String G203 4x00973 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 23 12 18 Indexed String G203 4x00974 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 24 12 19 Indexed String G203 4x00975 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 25 12 1A Indexed String G203 4x00976 G203 No Operation Command 0 2 1 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 22

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Control Input 26 12 1B Indexed String G203 4x00977 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 27 12 1C Indexed String G203 4x00978 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 28 12 1D Indexed String G203 4x00979 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 29 12 1E Indexed String G203 4x00980 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 30 12 1F Indexed String G203 4x00981 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 31 12 20 Indexed String G203 4x00982 G203 No Operation Command 0 2 1 2 * * * * *
Control Input 32 12 21 Indexed String G203 4x00983 G203 No Operation Command 0 2 1 2 * * * * *
CTRL I/P CONFIG 13 00 * * * * *
Binary Flag (32 bits)
Hotkey Enabled 13 01 G233 0xFFFFFFFF Setting 0xFFFFFFFF 32 1 2 * * * * * Hotkey Menu - Control Input Availability
Indexed String
Control Input 1 13 10 Indexed String G234 4x10002 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 1 13 11 Indexed String G232 4x10003 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 2 13 14 Indexed String G234 4x10004 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 2 13 15 Indexed String G232 4x10005 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 3 13 18 Indexed String G234 4x10006 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 3 13 19 Indexed String G232 4x10007 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 4 13 1C Indexed String G234 4x10008 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 4 13 1D Indexed String G232 4x10009 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 5 13 20 Indexed String G234 4x10010 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 5 13 21 Indexed String G232 4x10011 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 6 13 24 Indexed String G234 4x10012 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 6 13 25 Indexed String G232 4x10013 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 7 13 28 Indexed String G234 4x10014 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 7 13 29 Indexed String G232 4x10015 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 8 13 2C Indexed String G234 4x10016 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 8 13 2D Indexed String G232 4x10017 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 9 13 30 Indexed String G234 4x10018 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 9 13 31 Indexed String G232 4x10019 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 10 13 34 Indexed String G234 4x10020 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 10 13 35 Indexed String G232 4x10021 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 11 13 38 Indexed String G234 4x10022 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 11 13 39 Indexed String G232 4x10023 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 12 13 3C Indexed String G234 4x10024 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 12 13 3D Indexed String G232 4x10025 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 13 13 40 Indexed String G234 4x10026 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 13 13 41 Indexed String G232 4x10027 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 14 13 44 Indexed String G234 4x10028 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 14 13 45 Indexed String G232 4x10029 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 15 13 48 Indexed String G234 4x10030 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 15 13 49 Indexed String G232 4x10031 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 16 13 4C Indexed String G234 4x10032 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 16 13 4D Indexed String G232 4x10033 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 17 13 50 Indexed String G234 4x10034 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 17 13 51 Indexed String G232 4x10035 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 18 13 54 Indexed String G234 4x10036 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 18 13 55 Indexed String G232 4x10037 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 19 13 58 Indexed String G234 4x10038 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 19 13 59 Indexed String G232 4x10039 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 23

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Control Input 20 13 5C Indexed String G234 4x10040 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 20 13 5D Indexed String G232 4x10041 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 21 13 60 Indexed String G234 4x10042 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 21 13 61 Indexed String G232 4x10043 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 22 13 64 Indexed String G234 4x10044 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 22 13 65 Indexed String G232 4x10045 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 23 13 68 Indexed String G234 4x10046 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 23 13 69 Indexed String G232 4x10047 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 24 13 6C Indexed String G234 4x10048 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 24 13 6D Indexed String G232 4x10049 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 25 13 70 Indexed String G234 4x10050 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 25 13 71 Indexed String G232 4x10051 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 26 13 74 Indexed String G234 4x10052 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 26 13 75 Indexed String G232 4x10053 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 27 13 78 Indexed String G234 4x10054 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 27 13 79 Indexed String G232 4x10055 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 28 13 7C Indexed String G234 4x10056 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 28 13 7D Indexed String G232 4x10057 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 29 13 80 Indexed String G234 4x10058 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 29 13 81 Indexed String G232 4x10059 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 30 13 84 Indexed String G234 4x10060 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 30 13 85 Indexed String G232 4x10061 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 31 13 88 Indexed String G234 4x10062 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 31 13 89 Indexed String G232 4x10063 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
Control Input 32 13 8C Indexed String G234 4x10064 G234 Latched Setting 0 1 1 2 * * * * * Individual Control Input Type
Ctrl Command 32 13 8D Indexed String G232 4x10065 G232 SET/RESET Setting 0 3 1 2 * * * * * Individual Control Input Command Text
FUNCTION KEYS 17 00 *

Fn Key Status 17 01 Binary Flag (10 bits) 0 Data


*
Indexed String
Fn Key 1 17 02 Indexed String G242 4x10575 G242 Unlocked Setting 0 2 1 2 *
Key 1 Mode 17 03 Indexed String G243 4x10576 G243 Toggled Setting 0 1 1 2 *
Fn Key 1 Label 17 04 ASCII Text (16 chars) 4x10577 4x10584 G3 Function Key 1 Setting 32 163 1 2 *
Fn Key 2 17 05 Indexed String G242 4x10585 G242 Unlocked Setting 0 2 1 2 *
Fn Key 2 Mode 17 06 Indexed String G243 4x10586 G243 Normal Setting 0 1 1 2 *
Fn Key 2 Label 17 07 ASCII Text (16 chars) 4x10587 4x10594 G3 Function Key 2 Setting 32 163 1 2 *
Fn Key 3 17 08 Indexed String G242 4x10595 G242 Unlocked Setting 0 2 1 2 *
Fn Key 3 Mode 17 09 Indexed String G243 4x10596 G243 Normal Setting 0 1 1 2 *
Fn Key 3 Label 17 0A ASCII Text (16 chars) 4x10597 4x10604 G3 Function Key 3 Setting 32 163 1 2 *
Fn Key 4 17 0B Indexed String G242 4x10605 G242 Unlocked Setting 0 2 1 2 *
Fn Key 4 Mode 17 0C Indexed String G243 4x10606 G243 Toggled Setting 0 1 1 2 *
Fn Key 4 Label 17 0D ASCII Text (16 chars) 4x10607 4x10614 G3 Function Key 4 Setting 32 163 1 2 *
Fn Key 5 17 0E Indexed String G242 4x10615 G242 Unlocked Setting 0 2 1 2 *
Fn Key 5 Mode 17 0F Indexed String G243 4x10616 G243 Toggled Setting 0 1 1 2 *
Fn Key 5 Label 17 10 ASCII Text (16 chars) 4x10617 4x10624 G3 Function Key 5 Setting 32 163 1 2 *
Fn Key 6 17 11 Indexed String G242 4x10625 G242 Unlocked Setting 0 2 1 2 *
Fn Key 6 Mode 17 12 Indexed String G243 4x10626 G243 Toggled Setting 0 1 1 2 *
Fn Key 6 Label 17 13 ASCII Text (16 chars) 4x10627 4x10634 G3 Function Key 6 Setting 32 163 1 2 *
Fn Key 7 17 14 Indexed String G242 4x10635 G242 Unlocked Setting 0 2 1 2 *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 24

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Fn Key 7 Mode 17 15 Indexed String G243 4x10636 G243 Normal Setting 0 1 1 2 *
Fn Key 7 Label 17 16 ASCII Text (16 chars) 4x10637 4x10644 G3 Function Key 7 Setting 32 163 1 2 *
Fn Key 8 17 17 Indexed String G242 4x10645 G242 Unlocked Setting 0 2 1 2 *
Fn Key 8 Mode 17 18 Indexed String G243 4x10646 G243 Normal Setting 0 1 1 2 *
Fn Key 8 Label 17 19 ASCII Text (16 chars) 4x10647 4x10654 G3 Function Key 8 Setting 32 163 1 2 *
Fn Key 9 17 1A Indexed String G242 4x10655 G242 Unlocked Setting 0 2 1 2 *
Fn Key 9 Mode 17 1B Indexed String G243 4x10656 G243 Normal Setting 0 1 1 2 *
Fn Key 9 Label 17 1C ASCII Text (16 chars) 4x10657 4x10664 G3 Function Key 9 Setting 32 163 1 2 *
Fn Key 10 17 1D Indexed String G242 4x10665 G242 Unlocked Setting 0 2 1 2 *
Fn Key 10 Mode 17 1E Indexed String G243 4x10666 G243 Normal Setting 0 1 1 2 *
Fn Key 10 Label 17 1F ASCII Text (16 chars) 4x10667 4x10674 G3 Function Key 10 Setting 32 163 1 2 *
IED CONFIGURATOR 19 00 * * * * *
Switch Conf.Bank 19 05 Indexed String G248 No Action Control 0 1 1 2 * * * * *
Active Conf.Name 19 10 ASCII Text Not Available Data * * * * *
Active Conf.Rev 19 11 ASCII Text Not Available Data * * * * *
Inact.Conf.Name 19 20 ASCII Text Not Available Data * * * * *
Inact.Conf.Rev 19 21 ASCII Text Not Available Data * * * * *
IP PARAMETERS 19 30 Sub Heading * * * * *
IP Address 19 31 ASCII Text 0.0.0.0 Data * * * * *
Subnet Address 19 32 ASCII Text 0.0.0.0 Data * * * * *
Gateway 19 33 ASCII Text 0.0.0.0 Data * * * * *
SNTP PARAMETERS 19 40 Sub Heading * * * * *
SNTP Server 1 19 41 ASCII Text 0.0.0.0 Data * * * * *
SNTP Server 2 19 42 ASCII Text 0.0.0.0 Data * * * * *
IEC 61850 SCL 19 50 Sub Heading * * * * *
IED Name 19 51 ASCII Text Not Available Data * * * * *
IEC 61850 GOOSE 19 60 Sub Heading * * * * *
GoID 19 61 ASCII Text Not Available Data * * * * *
GoEna 19 70 ASCII Text G37 Disabled Setting 0 1 1 2 * * * * *
Test Mode 19 71 ASCII Text G246 Disabled Setting 0 2 1 2 * * * * *
VOP Test Pattern 19 72 ASCII Text 0x00000000 Setting 0xFFFFFFFF 32 1 2 * * * * *
Ignore Test Flag 19 73 ASCII Text G11 No Setting 0 1 1 2 * * * * *
CTRL I/P LABELS 29 00 * * * * *
Control Input 1 29 01 ASCII Text (16 chars) 4x10100 4x10107 G3 Control Input 1 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 2 29 02 ASCII Text (16 chars) 4x10108 4x10115 G3 Control Input 2 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 3 29 03 ASCII Text (16 chars) 4x10116 4x10123 G3 Control Input 3 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 4 29 04 ASCII Text (16 chars) 4x10124 4x10131 G3 Control Input 4 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 5 29 05 ASCII Text (16 chars) 4x10132 4x10139 G3 Control Input 5 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 6 29 06 ASCII Text (16 chars) 4x10140 4x10147 G3 Control Input 6 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 7 29 07 ASCII Text (16 chars) 4x10148 4x10155 G3 Control Input 7 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 8 29 08 ASCII Text (16 chars) 4x10156 4x10163 G3 Control Input 8 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 9 29 09 ASCII Text (16 chars) 4x10164 4x10171 G3 Control Input 9 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 10 29 0A ASCII Text (16 chars) 4x10172 4x10179 G3 Control Input 10 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 11 29 0B ASCII Text (16 chars) 4x10180 4x10187 G3 Control Input 11 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 12 29 0C ASCII Text (16 chars) 4x10188 4x10195 G3 Control Input 12 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 13 29 0D ASCII Text (16 chars) 4x10196 4x10203 G3 Control Input 13 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 14 29 0E ASCII Text (16 chars) 4x10204 4x10211 G3 Control Input 14 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 15 29 0F ASCII Text (16 chars) 4x10212 4x10219 G3 Control Input 15 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 25

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Control Input 16 29 10 ASCII Text (16 chars) 4x10220 4x10227 G3 Control Input 16 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 17 29 11 ASCII Text (16 chars) 4x10228 4x10235 G3 Control Input 17 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 18 29 12 ASCII Text (16 chars) 4x10236 4x10243 G3 Control Input 18 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 19 29 13 ASCII Text (16 chars) 4x10244 4x10251 G3 Control Input 19 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 20 29 14 ASCII Text (16 chars) 4x10252 4x10259 G3 Control Input 20 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 21 29 15 ASCII Text (16 chars) 4x10260 4x10267 G3 Control Input 21 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 22 29 16 ASCII Text (16 chars) 4x10268 4x10275 G3 Control Input 22 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 23 29 17 ASCII Text (16 chars) 4x10276 4x10283 G3 Control Input 23 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 24 29 18 ASCII Text (16 chars) 4x10284 4x10291 G3 Control Input 24 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 25 29 19 ASCII Text (16 chars) 4x10292 4x10299 G3 Control Input 25 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 26 29 1A ASCII Text (16 chars) 4x10300 4x10307 G3 Control Input 26 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 27 29 1B ASCII Text (16 chars) 4x10308 4x10315 G3 Control Input 27 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 28 29 1C ASCII Text (16 chars) 4x10316 4x10323 G3 Control Input 28 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 29 29 1D ASCII Text (16 chars) 4x10324 4x10331 G3 Control Input 29 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 30 29 1E ASCII Text (16 chars) 4x10332 4x10339 G3 Control Input 30 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 31 29 1F ASCII Text (16 chars) 4x10340 4x10347 G3 Control Input 31 Setting 32 163 1 2 * * * * * Text Description for the Control Input
Control Input 32 29 20 ASCII Text (16 chars) 4x10348 4x10355 G3 Control Input 32 Setting 32 163 1 2 * * * * * Text Description for the Control Input
GROUP 1
30 00 * * * * *
SYSTEM CONFIG
Phase Sequence 30 04 Indexed String G163 4x11000 G163 Standard ABC Setting 0 1 1 2 * * * * *
VT Reversal 30 08 Indexed String G164 4x11001 G164 No Swap Setting 0 3 1 2 * * * * *
CT1 Reversal 30 0A Indexed String G164 4x11002 G164 No Swap Setting 0 3 1 2 * * * * *
CT2 reversal 30 0C Indexed String G164 4x11003 G164 No Swap Setting 0 3 1 2 * *
GROUP 1
31 00 * * * * *
POWER
Operating Mode 31 20 Indexed String G115 4x01064 G115 Generating Setting 0 1 1 2 * * * * *
Over *
Power1 Function 31 24 Indexed String G102 4x01050 G102 Setting 0 3 1 2 *
Reverse * * *
20 4*V1*I1 300*V1*I1 1*V1*I1 2 *
-P>1 Setting 31 28 Courier Number (Power) 4x01051 G2 Setting *
5 1*V1*I1 300*V1*I1 0.2*V1*I1 2 * * *
20 4*V1*I1 300*V1*I1 1*V1*I1 2 *
P<1 Setting 31 2C Courier Number (Power) 4x01052 G2 Setting *
10 1*V1*I1 300*V1*I1 0.2*V1*I1 2 * * *
120 4*V1*I1 300*V1*I1 1*V1*I1 2 *
P>1 Setting 31 30 Courier Number (Power) 4x01053 G2 Setting *
120 1*V1*I1 300*V1*I1 0.2*V1*I1 2 * * *
Power1 TimeDelay 31 34 Courier Number (Time) 4x01054 G2 5 Setting 0 100 0.01 2 * * * * *
Power1 DO Timer 31 38 Courier Number (Time) 4x01055 G2 0 Setting 0 100 0.01 2 * * * * *
P1 Poledead Inh 31 3C Indexed String G37 4x01056 G37 Enabled Setting 0 1 1 2 * * * * *
Disabled *
Power2 Function 31 40 Indexed String G102 4x01057 G102 Setting 0 3 1 2 *
Low Forward * * *
20 4*V1*I1 300*V1*I1 1*V1*I1 2 *
-P>2 Setting 31 44 Courier Number (Power) 4x01058 G2 Setting *
5 1*V1*I1 300*V1*I1 0.2*V1*I1 2 * * *
20 4*V1*I1 300*V1*I1 1*V1*I1 2 *
P<2 Setting 31 48 Courier Number (Power) 4x01059 G2 Setting *
10 1*V1*I1 300*V1*I1 0.2*V1*I1 2 * * *
120 4*V1*I1 300*V1*I1 1*V1*I1 2 *
P>2 Setting 31 4C Courier Number (Power) 4x01060 G2 Setting *
120 1*V1*I1 300*V1*I1 0.2*V1*I1 2 * * *
Power2 TimeDelay 31 50 Courier Number (Time) 4x01061 G2 2 Setting 0 100 0.01 2 * * * * *
Power2 DO Timer 31 54 Courier Number (Time) 4x01062 G2 0 Setting 0 100 0.01 2 * * * * *
P2 Poledead Inh 31 58 Indexed String G37 4x01063 G37 Enabled Setting 0 1 1 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 26

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
NPS OVERPOWER 31 60 (Sub Heading) * * * *
S2>1 Status 31 62 Indexed String G37 4x01065 G37 Disabled Setting 0 1 1 2 * * * *
S2>1 Setting 31 64 Courier Number (VA) 4x01066 G2 0.5 Setting 0.1*V1*I1 30*V1*I1 0.01*V1*I1 2 * * * *
S2>1 Time Delay 31 68 Courier Number (Time) 4x01067 G2 0.1 Setting 0 100 0.01 2 * * * *
GROUP 1
32 00 * * * *
FIELD FAILURE
FFail Alm Status 32 01 Indexed String G37 4x01100 G37 Disabled Setting 0 1 1 2 * * * *
FFail Alm Angle 32 02 Courier Number (Angle) 4x01101 G2 15 Setting 15 75 1 2 * * * *
FFail Alm Delay 32 03 Courier Number (Time) 4x01102 G2 5 Setting 0 100 0.01 2 * * * *
FFail1 Status 32 04 Indexed String G37 4x01103 G37 Enabled Setting 0 1 1 2 * * * *
FFail1 -Xa1 32 05 Courier Number (Impedance) 4x01104 G2 20 Setting 0 40*V1/I1 0.5*V1/I1 2 * * * *
FFail1 Xb1 32 06 Courier Number (Impedance) 4x01105 G2 220 Setting 25*V1/I1 325*V1/I1 1*V1/I1 2 * * * *
FFail1 TimeDelay 32 07 Courier Number (Time) 4x01106 G2 5 Setting 0 100 0.01 2 * * * *
FFail1 DO Timer 32 08 Courier Number (Time) 4x01107 G2 0 Setting 0 100 0.01 2 * * * *
FFail2 Status 32 09 Indexed String G37 4x01108 G37 Disabled Setting 0 1 1 2 * * * *
FFail2 -Xa2 32 0A Courier Number (Impedance) 4x01109 G2 20 Setting 0 40*V1/I1 0.5*V1/I1 2 * * * *
FFail2 Xb2 32 0B Courier Number (Impedance) 4x01110 G2 110 Setting 25*V1/I1 325*V1/I1 1*V1/I1 2 * * * *
FFail2 TimeDelay 32 0C Courier Number (Time) 4x01111 G2 0 Setting 0 100 0.01 2 * * * *
FFail2 DO Timer 32 0D Courier Number (Time) 4x01112 G2 0 Setting 0 100 0.01 2 * * * *
GROUP 1 33 00 * * * *
NPS THERMAL
I2therm>1 Alarm 33 01 Indexed String G37 4x01150 G37 Enabled Setting 0 1 1 2 * * * *
I2therm>1 Set 33 02 Courier Number (Current) 4x01151 G2 0.05 Setting 0.03*I1 0.5*I1 0.01*I1 2 * * * *
I2therm>1 Delay 33 03 Courier Number (Time) 4x01152 G2 20s Setting 0 100 0.01 2 * * * *
I2therm>2 Trip 33 04 Indexed String G37 4x01153 G37 Enabled Setting 0 1 1 2 * * * *
I2therm>2 Set 33 05 Courier Number (Current) 4x01154 G2 0.1 Setting 0.05*I1 0.5*I1 0.01*I1 2 * * * *
I2therm>2 k 33 06 Courier Number (Time) 4x01155 G2 15 Setting 2 40 0.1 2 * * * *
I2therm>2 kRESET 33 07 Courier Number (Time) 4x01156 G2 15 Setting 2 40 0.1 2 * * * *
I2therm>2 tMAX 33 08 Courier Number (Time) 4x01157 G2 1000 Setting 500 2000 1 2 * * * *
I2therm>2 tMIN 33 09 Courier Number (Time) 4x01158 G2 0.25 Setting 0 100 0.01 2 * * * *
GROUP 1
34 00 * * * *
SYSTEM BACKUP
Backup Function 34 01 Indexed String G103 4x01200 G103 Voltage controlled Setting 0 3 1 2 * * * *
Vector Rotation 34 02 Indexed String G104 4x01201 G104 None Setting 0 1 1 2 * * * *
V Dep OC Char 34 20 Indexed String G111 4x01202 G111 IEC S Inverse Setting 0 11 1 2 * * * *
V Dep OC I> Set 34 23 Courier Number (Current) 4x01203 G2 1 Setting 0.8*I1 4*I1 0.01*I1 2 * * * *
V Dep OC T Dial 34 25 Courier Number (Decimal) 4x01204 G2 1 Setting 0.01 100 0.01 2 * * * *
V Dep OC Reset 34 26 Indexed String G60 4x01205 G60 DT Setting 0 1 1 2 * * * *
V Dep OC Delay 34 27 Courier Number (Time) 4x01206 G2 1 Setting 0 100 0.01 2 * * * *
V Dep OC TMS 34 28 Courier Number (Decimal) 4x01207 G2 1 Setting 0.025 1.2 0.025 2 * * * *
V Dep OC K (RI) 34 29 Courier Number (Decimal) 4x01219 G2 1 Setting 0.1 10 0.05 2 * * * *
V Dep OC tRESET 34 2A Courier Number (Time) 4x01208 G2 0 Setting 0 100 0.01 2 * * * *
V Dep OC V<1 Set 34 2D Courier Number (Voltage) 4x01209 G2 80 Setting 5*V1 120*V1 1*V1 2 * * * *
V Dep OC V<2 Set 34 2E Courier Number (Voltage) 4x01210 G2 60 Setting 5*V1 120*V1 1*V1 2 * * * *
V Dep OC k Set 34 2F Courier Number (Decimal) 4x01211 G2 0.25 Setting 0.1 1 0.05 2 * * * *
Z<1 Setting 34 30 Courier Number (Impedance) 4x01212 G2 70 Setting 2*V1/I1 120*V1/I1 0.5*V1/I1 2 * * * *
Z<1 Time Delay 34 31 Courier Number (Time) 4x01213 G2 5 Setting 0 100 0.01 2 * * * *
Z<1 tRESET 34 32 Courier Number (Time) 4x01214 G2 0 Setting 0 100 0.01 2 * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 27

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Z< Stage 2 34 33 Indexed String G37 4x01215 G37 Disabled Setting 0 1 1 2 * * * *
Z<2 Setting 34 34 Courier Number (Impedance) 4x01216 G2 70 Setting 2*V1/I1 120*V1/I1 0.5*V1/I1 2 * * * *
Z<2 Time Delay 34 35 Courier Number (Time) 4x01217 G2 5 Setting 0 100 0.01 2 * * * *
Z<2 tRESET 34 36 Courier Number (Time) 4x01218 G2 0 Setting 0 100 0.01 2 * * * *
GROUP 1
35 00 * * * * *
OVERCURRENT
PHASE O/C 35 20 (Sub Heading) * * * * *
I>1 Function 35 23 Indexed String G150 4x01250 G150 IEC S Inverse Setting 0 12 1 2 * * * * *
I>1 Direction 35 24 Indexed String G44 4x01251 G44 Non-Directional Setting 0 2 1 2 * * * * *
I>1 Current Set 35 27 Courier Number (Current) 4x01252 G2 1 Setting 0.08*I1 4.0*I1 0.01*I1 2 * * * * *
I>1 Time Delay 35 29 Courier Number (Time) 4x01253 G2 1 Setting 0 100 0.01 2 * * * * *
I>1 TMS 35 2A Courier Number (Decimal) 4x01254 G2 1 Setting 0.025 1.2 0.025 2 * * * * *
I>1 Time Dial 35 2B Courier Number (Decimal) 4x01255 G2 1 Setting 0.01 100 0.01 2 * * * * *
I>1 K (RI) 35 2C Courier Number (Decimal) 4x01276 G2 1 Setting 0.1 10 0.05 2 * * * * *
I>1 Reset Char 35 2E Indexed String G60 4x01256 G60 DT Setting 0 1 1 2 * * * * *
I>1 tRESET 35 2F Courier Number (Time) 4x01257 G2 0 Setting 0 100 0.01 2 * * * * *
G150 G150 * * * *
I>2 Function 35 32 Indexed String 4x01258 Disabled Setting 0 12 1 2 *
G105 G105
I>2 Direction 35 33 Indexed String G44 4x01259 G44 Non-Directional Setting 0 2 1 2 * * * * *
I>2 Current Set 35 36 Courier Number (Current) 4x01260 G2 1 Setting 0.08*I1 4.0*I1 0.01*I1 2 * * * * *
I>2 Time Delay 35 38 Courier Number (Time) 4x01261 G2 1 Setting 0 100 0.01 2 * * * * *
I>2 TMS 35 39 Courier Number (Decimal) 4x01262 G2 1 Setting 0.025 1.2 0.025 2 * * * * *
I>2 Time Dial 35 3A Courier Number (Decimal) 4x01263 G2 1 Setting 0.01 100 0.01 2 * * * * *
I>2 K (RI) 35 3B Courier Number (Decimal) 4x01277 G2 1 Setting 0.1 10 0.05 2 * * * * *
I>2 Reset Char 35 3D Indexed String G60 4x01264 G60 DT Setting 0 1 1 2 * * * * *
I>2 tRESET 35 3E Courier Number (Time) 4x01265 G2 0 Setting 0 100 0.01 2 * * * * *
I>3 Status 35 40 Indexed String G37 4x01266 G37 Disabled Setting 0 1 1 2 * * * * *
I>3 Direction 35 41 Indexed String G44 4x01267 G44 Non-Directional Setting 0 2 1 2 * * * * *
32*I1 *
I>3 Current Set 35 44 Courier Number (Current) 4x01268 G2 10 Setting 0.08*I1 0.01*I1 2
10*I1 * * * *
I>3 Time Delay 35 45 Courier Number (Time) 4x01269 G2 0 Setting 0 100 0.01 2 * * * * *
I>4 Status 35 47 Indexed String G37 4x01270 G37 Disabled Setting 0 1 1 2 * * * * *
I>4 Direction 35 48 Indexed String G44 4x01271 G44 Non-Directional Setting 0 2 1 2 * * * * *
32*I1 *
I>4 Current Set 35 4B Courier Number (Current) 4x01272 G2 10 Setting 0.08*I1 0.01*I1 2
10*I1 * * * *
I>4 Time Delay 35 4C Courier Number (Time) 4x01273 G2 0 Setting 0 100 0.01 2 * * * * *
I> Char Angle 35 4E Courier Number (Angle) 4x01274 G2 30 Setting -95 95 1 2 * * * * *
I> Function Link 35 4F Binary Flag G14 4x01275 G14 15 Setting 15 4 1 2 * * * * *
NPS OVERCURRENT 35 50 (Sub Heading) * * * * *
I2>1 Status 35 52 Indexed String G37 4x01278 G37 Disabled Setting 0 1 1 2 * * * * *
I2>1 Direction 35 54 Indexed String G44 4x01279 G44 Non-Directional Setting 0 2 1 2 * * * * *
I2>1 Current Set 35 56 Courier Number (Current) 4x01280 G2 0.2 Setting 0.08*I1 4*I1 0.01*I1 2 * * * * *
I2>1 Time Delay 35 58 Courier Number (Time) 4x01281 G2 10 Setting 0 100 0.01 2 * * * * *
I2>2 Status 35 62 Indexed String G37 4x01282 G37 Disabled Setting 0 1 1 2 * * * * *
I2>2 Direction 35 64 Indexed String G44 4x01283 G44 Non-Directional Setting 0 2 1 2 * * * * *
I2>2 Current Set 35 66 Courier Number (Current) 4x01284 G2 0.2 Setting 0.08*I1 4*I1 0.01*I1 2 * * * * *
I2>2 Time Delay 35 68 Courier Number (Time) 4x01285 G2 10 Setting 0 100 0.01 2 * * * * *
I2>3 Status 35 72 Indexed String G37 4x01286 G37 Disabled Setting 0 1 1 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 28

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
I2>3 Direction 35 74 Indexed String G44 4x01287 G44 Non-Directional Setting 0 2 1 2 * * * * *
I2>3 Current Set 35 76 Courier Number (Current) 4x01288 G2 0.2 Setting 0.08*I1 4*I1 0.01*I1 2 * * * * *
I2>3 Time Delay 35 78 Courier Number (Time) 4x01289 G2 10 Setting 0 100 0.01 2 * * * * *
I2>4 Status 35 82 Indexed String G37 4x01290 G37 Disabled Setting 0 1 1 2 * * * * *
I2>4 Direction 35 84 Indexed String G44 4x01291 G44 Non-Directional Setting 0 2 1 2 * * * * *
I2>4 Current Set 35 86 Courier Number (Current) 4x01292 G2 0.2 Setting 0.08*I1 4*I1 0.01*I1 2 * * * * *
I2>4 Time Delay 35 88 Courier Number (Time) 4x01293 G2 10 Setting 0 100 0.01 2 * * * * *
I2> VTS Block 35 90 Binary Flag G158 4x01294 G158 15 Setting 15 4 1 2 * * * * *
I2> V2pol Set 35 94 Courier Number (Voltage) 4x01295 G2 5 Setting 0.5*V1 25*V1 0.5*V1 2 * * * * *
I2> Char Angle 35 98 Courier Number (Angle) 4x01296 G2 -60 Setting -95 95 1 2 * * * * *
GROUP 1
36 00 * * * * *
THERMAL OVERLOAD
Thermal 36 50 Indexed String G37 4x01308 G37 Enabled Setting 0 1 1 2 * * * * *
Thermal I> 36 55 Courier Number (Current) 4x01309 G2 1.2 Setting 0.5*I1 2.5*I1 0.01*I1 2 * * * * *
Thermal Alarm 36 5A Courier Number (Percentage) 4x01310 G2 90 Setting 20 100 1 2 * * * * *
T-Heating 36 5F Courier Number (Time, minutes) 4x01311 G2 60 Setting 1 200 1 2 * * * * *
T-Cooling 36 64 Courier Number (Time, minutes) 4x01312 G2 60 Setting 1 200 1 2 * * * * *
M Factor 36 69 Courier Number (Decimal) 4x01313 G2 0 Setting 0 10 1 2 * * * * *
GROUP 1
37 00 * * * Was in database column 30, moved in version 32 s/w
GEN DIFF
GenDiff Function 37 01 Indexed String G101 4x01000 G101 Percentage Bias Setting 0 3 1 2 * * *
Gen Diff Is1 37 02 Courier Number (Current) 4x01001 G2 0.1 Setting 0.05*I1 0.5*I1 0.01*I1 2 * * *
Gen Diff k1 37 03 Courier Number (Percentage) 4x01002 G2 0 Setting 0 20 5 2 * * *
Gen Diff Is2 37 04 Courier Number (Current) 4x01003 G2 1.2 Setting 1*I1 5*I1 0.1*I1 2 * * *
Gen Diff k2 37 05 Courier Number (Percentage) 4x01004 G2 150 Setting 20 150 10 2 * * *
Interturn Is_A 37 10 Courier Number (Current) 4x01005 G2 0.1 Setting 0.05*I1 2*I1 0.01*I1 2 * * *
Interturn Is_B 37 14 Courier Number (Current) 4x01006 G2 0.1 Setting 0.05*I1 2*I1 0.01*I1 2 * * *
Interturn Is_C 37 18 Courier Number (Current) 4x01007 G2 0.1 Setting 0.05*I1 2*I1 0.01*I1 2 * * *
Interturn Delay 37 1C Courier Number (Time) 4x01008 G2 0.1 Setting 0 100 0.01 2 * * *
GROUP 1
38 00 * * * * *
EARTH FAULT
Derived *
IN Input 38 01 Indexed String G49 G49 Data
Measured * * * *
IN>1 Function 38 25 Indexed String G151 4x01400 G151 IEC S Inverse Setting 0 12 1 2 * * * * *
IN>1 Direction 38 26 Indexed String G44 4x01401 G44 Non-Directional Setting 0 2 1 2 *
0.2 0.08*I1 4.0*I1 0.01*I1 2 *
IN>1 Current 38 29 Courier Number (Current) 4x01402 G2 Setting
0.1 0.02*I2 4.0*I2 0.01*I2 * * * *
IN>1 IDG Is 38 2A Courier Number (Decimal) 4x01431 G2 1.5 Setting 1 4 0.1 2 * * * * *
IN>1 Time Delay 38 2C Courier Number (Time) 4x01403 G2 1 Setting 0 200 0.01 2 * * * * *
IN>1 TMS 38 2D Courier Number (Decimal) 4x01404 G2 1 Setting 0.025 1.2 0.025 2 * * * * *
IN>1 Time Dial 38 2E Courier Number (Decimal) 4x01405 G2 1 Setting 0.01 100 0.01 2 * * * * *
IN>1 K (RI) 38 2F Courier Number (Decimal) 4x01432 G2 1 Setting 0.1 10 0.05 2 * * * * *
IN>1 IDG Time 38 30 Courier Number (Decimal) 4x01433 G2 1.2 Setting 1 2 0.01 2 * * * * *
IN>1 Reset Char 38 32 Indexed String G60 4x01406 G60 DT Setting 0 1 1 2 * * * * *
IN>1 tRESET 38 33 Courier Number (Time) 4x01407 G2 0 Setting 0 100 0.01 2 * * * * *
G151 G151 Disabled 0 12 1 2 *
IN>2 Function 38 36 Indexed String 4x01408 Setting
G105 G105 Disabled 0 1 1 2 * * * *
IN>2 Direction 38 37 Indexed String G44 4x01409 G44 Non-Directional Setting 0 2 1 2 *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 29

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
0.2 0.08*I1 4.0*I1 0.01*I1 2 *
IN>2 Current 38 3A Courier Number (Current) 4x01410 G2 Setting
0.45 0.02*I2 10.0*I2 0.01*I2 * * * *
IN>2 IDG Is 38 3B Courier Number (Decimal) 4x01434 G2 1.5 Setting 1 4 0.1 2 *
1 *
IN>2 Time Delay 38 3D Courier Number (Time) 4x01411 G2 Setting 0 200 0.01 2
0 * * * *
IN>2 TMS 38 3E Courier Number (Decimal) 4x01412 G2 1 Setting 0.025 1.2 0.025 2 *
IN>2 Time Dial 38 3F Courier Number (Decimal) 4x01413 G2 1 Setting 0.01 100 0.01 2 *
IN>2 K (RI) 38 40 Courier Number (Decimal) 4x01435 G2 1 Setting 0.1 10 0.05 2 *
IN>2 IDG Time 38 41 Courier Number (Time) 4x01436 G2 1.2 Setting 1 2 0.01 2 *
IN>2 Reset Char 38 43 Indexed String G60 4x01414 G60 DT Setting 0 1 1 2 *
IN>2 tRESET 38 44 Courier Number (Time) 4x01415 G2 0 Setting 0 100 0.01 2 *
IN>3 Status 38 46 Indexed String G37 4x01416 G37 Disabled Setting 0 1 1 2 *
IN>3 Direction 38 47 Indexed String G44 4x01417 G44 Non-Directional Setting 0 2 1 2 *
IN>3 Current 38 4A Courier Number (Current) 4x01418 G2 0.5 Setting 0.08*I1 32*I1 0.01*I1 2 *
IN>3 Time Delay 38 4B Courier Number (Time) 4x01419 G2 0 Setting 0 200 0.01 2 *
IN>4 Status 38 4D Indexed String G37 4x01420 G37 Disabled Setting 0 1 1 2 *
IN>4 Direction 38 4E Indexed String G44 4x01421 G44 Non-Directional Setting 0 2 1 2 *
IN>4 Current 38 51 Courier Number (Current) 4x01422 G2 0.5 Setting 0.08*I1 32*I1 0.01*I1 2 *
IN>4 Time Delay 38 52 Courier Number (Time) 4x01423 G2 0 Setting 0 200 0.01 2 *
IN> Func Link 38 54 Binary Flags G63 4x01424 G63 15 Setting 15 4 1 2 *
IN> DIRECTIONAL 38 55 (Sub Heading) 2 *
IN> Char Angle 38 56 Courier Number(Angle) 4x01425 G2 -60 Setting -95 95 1 2 *
IN> Pol 38 57 Indexed String G46 4x01426 G46 Zero Sequence Setting 0 1 1 2 *
IN> VNpol Input 38 58 Indexed String G49 4x01427 G49 Measured Setting 0 1 1 2 *
0.5*V1 80*V1 0.5*V1 2 *
IN> VNpol Set 38 59 Courier Number (Voltage) 4x01428 G2 5 Setting
0.5*V3 80*V3 0.5*V3
IN> V2pol Set 38 5A Courier Number (Voltage) 4x01429 G2 5 Setting 0.5*V1 25*V1 0.5*V1 2 *
IN> I2pol Set 38 5B Courier Number (Current) 4x01430 G2 0.08 Setting 0.08*I1 1*I1 0.01*I1 2 *
GROUP 1 * * * *
39 00
ROTOR EF
Injection Freq 39 02 Indexed String G168 4x01450 G168 0.25 Hz Setting 0 2 1 2 * * * *
CL I/P Select 39 04 Indexed String G166 4x01451 G166 Current Loop CL1 Setting 0 3 1 2 * * * *
64R R<1 Alarm 39 08 Indexed String G37 4x01452 G37 Enabled Setting 0 1 1 2 * * * *
64R R<1 Alm Set 39 0C Courier Number (Resistance) 4x01453 4x01454 G35 40000 Setting 1000 80000 1 2 * * * *
64R R<1 Alm Dly 39 10 Courier Number (Time) 4x01455 G2 10 Setting 0 600 0.1 2 * * * *
64R R<2 Trip 39 14 Indexed String G37 4x01456 G37 Enabled Setting 0 1 1 2 * * * *
64R R<2 Trip Set 39 18 Courier Number (Resistance) 4x01457 4x01458 G35 5000 Setting 1000 80000 1 2 * * * *
64R R<2 Trip Dly 39 1C Courier Number (Time) 4x01459 G2 1 Setting 0 600 0.1 2 * * * *
R Compensation 39 20 Courier Number (Resistance) 4x01460 G2 0 Setting -1000 1000 1 2 * * * *
GROUP 1
3A 00 * * * * *
SEF/REF PROT'N
SEF/REF Options 3A 01 Indexed String G58 4x01500 G58 SEF Setting 0 4 1 2 *
0 7 1 2 * * * *
G152 G152 0 11 1 2 *
ISEF>1 Function 3A 2A Indexed String 4x01501 DT Setting
G105 G105 0 1 1 * * * *
ISEF>1 Direction 3A 2B Indexed String G44 4x01502 G44 Non-Directional Setting 0 2 1 2 * * * * *
ISEF>1 Current 3A 2E Courier Number (Current) 4x01503 G2 0.05 Setting 0.005*I3 0.1*I3 0.00025*I3 2 * * * * *
ISEF>1 IDG Is 3A 2F Courier Number (Decimal) 4x01535 G2 1.5 Setting 1 4 0.1 2 *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 30

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
ISEF>1 Delay 3A 31 Courier Number (Time) 4x01504 G2 1 Setting 0 200 0.01 2 * * * * *
ISEF>1 TMS 3A 32 Courier Number (Decimal) 4x01505 G2 1 Setting 0.025 1.2 0.025 2 *
ISEF>1 Time Dial 3A 33 Courier Number (Decimal) 4x01506 G2 1 Setting 0.01 100 0.01 2 *
ISEF>1 IDG Time 3A 34 Courier Number (Time) 4x01536 G2 1.2 Setting 1 2 0.01 2 *
ISEF>1 Reset Chr 3A 36 Indexed String G60 4x01507 G60 DT Setting 0 1 1 2 *
ISEF>1 tRESET 3A 37 Courier Number (Time) 4x01508 G2 0 Setting 0 100 0.01 2 *
ISEF>2 Function 3A 3A Indexed String G152 4x01509 G152 Disabled Setting 0 11 1 2 *
ISEF>2 Direction 3A 3B Indexed String G44 4x01510 G44 Non-Directional Setting 0 2 1 2 *
ISEF>2 Current 3A 3E Courier Number (Current) 4x01511 G2 0.05 Setting 0.005*I3 0.1*I3 0.00025*I3 2 *
ISEF>2 IDG Is 3A 3F Courier Number (Decimal) 4x01537 G2 1.5 Setting 1 4 0.1 2 *
ISEF>2 Delay 3A 41 Courier Number (Time) 4x01512 G2 1 Setting 0 200 0.01 2 *
ISEF>2 TMS 3A 42 Courier Number (Decimal) 4x01513 G2 1 Setting 0.025 1.2 0.025 2 *
ISEF>2 Time Dial 3A 43 Courier Number (Decimal) 4x01514 G2 1 Setting 0.01 100 0.01 2 *
ISEF>2 IDG Time 3A 44 Courier Number (Time) 4x01538 G2 1.2 Setting 1 2 0.01 2 *
ISEF>2 Reset Chr 3A 46 Indexed String G60 4x01515 G60 DT Setting 0 1 1 2 *
ISEF>2 tRESET 3A 47 Courier Number (Time) 4x01516 G2 0 Setting 0 100 0.01 2 *
ISEF>3 Status 3A 49 Indexed String G37 4x01517 G37 Disabled Setting 0 1 1 2 *
ISEF>3 Direction 3A 4A Indexed String G44 4x01518 G44 Non-Directional Setting 0 2 1 2 *
ISEF>3 Current 3A 4D Courier Number (Current) 4x01519 G2 0.4 Setting 0.005*I3 0.80*I3 0.001*I3 2 *
ISEF>3 Delay 3A 4E Courier Number (Time) 4x01520 G2 0.5 Setting 0 200 0.01 2 *
ISEF>4 Status 3A 50 Indexed String G37 4x01521 G37 Disabled Setting 0 1 1 2 *
ISEF>4 Direction 3A 51 Indexed String G44 4x01522 G44 Non-Directional Setting 0 2 1 2 *
ISEF>4 Current 3A 54 Courier Number (Current) 4x01523 G2 0.6 Setting 0.005*I3 0.80*I3 0.001*I3 2 *
ISEF>4 Delay 3A 55 Courier Number (Time) 4x01524 G2 0.25 Setting 0 200 0.01 2 *
ISEF> Func Link 3A 57 Binary Flags G64 4x01525 G64 15 Setting 15 4 1 2 *
1 1 1 2 * * * *
ISEF DIRECTIONAL 3A 58 (Sub Heading) 2 * * * * *
ISEF> Char Angle 3A 59 Courier Number(Angle) 4x01526 G2 90 Setting -95 95 1 2 * * * * *
ISEF>VNpol Input 3A 5A Indexed String G49 4x01527 G49 Measured Setting 0 1 1 2 * * * * *
0.5*V1 80*V1 0.5*V1 2 * * * * *
ISEF> VNpol Set 3A 5B Courier Number (Voltage) 4x01528 G2 5 Setting
0.5*V3 80*V3 0.5*V3 * * * * *
WATTMETRIC SEF 3A 5D (Sub Heading) * * * * *
0.0*V1*I3 20*V1*I3 0.05*V1*I3 2 * * * * *
PN> Setting 3A 5E Courier Number (Power) 4x01529 G2 9 Setting
0.0*V3*I3 20*V3*I3 0.05*V3*I3 * * * * *
RESTRICTED E/F 3A 60 (Sub Heading) * * * * *
IREF> k1 3A 61 Courier Number (Percentage) 4x01530 G2 20 Setting 0 20 1 2 * * * *
IREF> k2 3A 62 Courier Number (Percentage) 4x01531 G2 150 Setting 0 150 1 2 * * * *
IREF> Is1 3A 63 Courier Number (Current) 4x01532 G2 0.2 Setting 0.05*I1 1.0*I1 0.01*I1 2 * * * *
IREF> Is2 3A 64 Courier Number (Current) 4x01533 G2 1 Setting 0.1*I1 1.5*I1 0.01*I1 2 * * * *
IREF> Is 3A 65 Courier Number (Current) 4x01534 G2 0.2 Setting 0.05*I3 1.0*I3 0.01*I3 2 * * * * *
GROUP 1
3B 00 * * *
RESIDUAL O/V NVD
VN>1 Status 3B 10 Indexed String G37 4x11550 G37 Enabled Setting 0 1 1 2 * * * * *
VN>1 Input 3B 12 Indexed String G159 G159 Derived Data * * * * * VN>1 Input is Always the Derived VN
VN>1 Function 3B 14 Indexed String G161 4x11551 G161 DT Setting 0 1 1 2 * * * * *
1*V1 80*V1 1*V1 2 * * * * *
VN>1 Voltage Set 3B 16 Courier Number (Voltage) 4x11552 G2 5 Setting 1*V3 80*V3 1*V3 * * * * *
1*V2 80*V2 1*V2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 31

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
VN>1 Time Delay 3B 18 Courier Number (Time) 4x11553 G2 5 Setting 0 100 0.01 2 * * * * *
VN>1 TMS 3B 1A Courier Number (Decimal) 4x11554 G2 1 Setting 0.5 100 0.5 2 * * * * *
VN>1 tReset 3B 1C Courier Number (Time) 4x11555 G2 0 Setting 0 100 0.01 2 * * * * *
VN>2 Status 3B 20 Indexed String G37 4x11556 G37 Disabled Setting 0 1 1 2 * * * * *
VN>2 Input 3B 22 Indexed String G159 G159 Derived Data * * * * * VN>2 Input is Always the Derived VN
VN>2 Function 3B 24 Indexed String G161 4x11557 G161 DT Setting 0 1 1 2 * * * * *
1*V1 80*V1 1*V1 2 * * * * *
VN>2 Voltage Set 3B 26 Courier Number (Voltage) 4x11558 G2 10 Setting 1*V3 80*V3 1*V3 * * * * *
1*V2 80*V2 1*V2 * * * * *
VN>2 Time Delay 3B 28 Courier Number (Time) 4x11559 G2 10 Setting 0 100 0.01 2 * * * * *
VN>2 TMS 3B 2A Courier Number (Decimal) 4x11560 G2 1 Setting 0.5 100 0.5 2 * * * * *
VN>2 tReset 3B 2C Courier Number (Time) 4x11561 G2 0 Setting 0 100 0.01 2 * * * * *
VN>3 Status 3B 30 Indexed String G37 4x11562 G37 Enabled Setting 0 1 1 2 * * * * *
VN>3 Input 3B 32 Indexed String G159 G159 VN1 Data * * * * * VN>3 Input is Always the Measured VN1
VN>3 Function 3B 34 Indexed String G161 4x11563 G161 DT Setting 0 1 1 2 * * * * *
1*V1 80*V1 1*V1 2 * * * * *
VN>3 Voltage Set 3B 36 Courier Number (Voltage) 4x11564 G2 5 Setting 1*V3 80*V3 1*V3 * * * * *
1*V2 80*V2 1*V2 * * * * *
VN>3 Time Delay 3B 38 Courier Number (Time) 4x11565 G2 5 Setting 0 100 0.01 2 * * * * *
VN>3 TMS 3B 3A Courier Number (Decimal) 4x11566 G2 1 Setting 0.5 100 0.5 2 * * * * *
VN>3 tReset 3B 3C Courier Number (Time) 4x11567 G2 0 Setting 0 100 0.01 2 * * * * *
VN>4 Status 3B 40 Indexed String G37 4x11568 G37 Disabled Setting 0 1 1 2 * * * * *
VN>4 Input 3B 42 Indexed String G159 G159 VN1 Data * * * * * VN>4 Input is Always the Measured VN1
VN>4 Function 3B 44 Indexed String G161 4x11569 G161 DT Setting 0 1 1 2 * * * * *
1*V1 80*V1 1*V1 2 * * * * *
VN>4 Voltage Set 3B 46 Courier Number (Voltage) 4x11570 G2 10 Setting 1*V3 80*V3 1*V3 * * * * *
1*V2 80*V2 1*V2 * * * * *
VN>4 Time Delay 3B 48 Courier Number (Time) 4x11571 G2 10 Setting 0 100 0.01 2 * * * * *
VN>4 TMS 3B 4A Courier Number (Decimal) 4x11572 G2 1 Setting 0.5 100 0.5 2 * * * * *
VN>4 tReset 3B 4C Courier Number (Time) 4x11573 G2 0 Setting 0 100 0.01 2 * * * * *
VN>5 Status 3B 50 Indexed String G37 4x11574 G37 Enabled Setting 0 1 1 2 * *
VN>5 Input 3B 52 Indexed String G159 G159 VN2 Data * * VN>5 Input is Always the Measured VN2
VN>5 Function 3B 54 Indexed String G161 4x11575 G161 DT Setting 0 1 1 2 * *
1*V1 80*V1 1*V1 2 * *
VN>5 Voltage Set 3B 56 Courier Number (Voltage) 4x11576 G2 5 Setting 1*V3 80*V3 1*V3 * *
1*V2 80*V2 1*V2 * *
VN>5 Time Delay 3B 58 Courier Number (Time) 4x11577 G2 5 Setting 0 100 0.01 2 * *
VN>5 TMS 3B 5A Courier Number (Decimal) 4x11578 G2 1 Setting 0.5 100 0.5 2 * *
VN>5 tReset 3B 5C Courier Number (Time) 4x11579 G2 0 Setting 0 100 0.01 2 * *
VN>6 Status 3B 60 Indexed String G37 4x11580 G37 Disabled Setting 0 1 1 2 * *
VN>6 Input 3B 62 Indexed String G159 G159 VN2 Data * * VN>6 Input is Always the Measured VN2
VN>6 Function 3B 64 Indexed String G161 4x11581 G161 DT Setting 0 1 1 2 * *
1*V1 80*V1 1*V1 2 * *
VN>6 Voltage Set 3B 66 Courier Number (Voltage) 4x11582 G2 10 Setting 1*V3 80*V3 1*V3 * *
1*V2 80*V2 1*V2 * *
VN>6 Time Delay 3B 68 Courier Number (Time) 4x11583 G2 10 Setting 0 100 0.01 2 * *
VN>6 TMS 3B 6A Courier Number (Decimal) 4x11584 G2 1 Setting 0.5 100 0.5 2 * *
VN>6 tReset 3B 6C Courier Number (Time) 4x11585 G2 0 Setting 0 100 0.01 2 * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 32

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
GROUP 1
3C 00 * * *
100% STATOR EF
VN 3rd Harmonic 3C 01 Indexed String G112 4x01600 G112 1 (Undervoltage) Setting 0 2 1 2 * * *
100% St EF VN3H< 3C 02 Courier Number (Voltage) 4x01601 G2 1 Setting 0.3*V3 20*V3 0.1*V3 2 * * *
VN3H< Delay 3C 03 Courier Number (Time) 4x01602 G2 5 Setting 0 100 0.01 2 * * *
V<Inhibit set 3C 04 Courier Number (Voltage) 4x01603 G2 80 Setting 30*V1 120*V1 1*V1 2 * * *
P< Inhibit 3C 05 Indexed String G37 4x01604 G37 Disabled Setting 0 1 1 2 * * *
P<Inhibit set 3C 06 Courier Number (Power) 4x01605 G2 4 Setting 4*V1*I1 200*V1*I1 0.5*V1*I1 2 * * *
Q< Inhibit 3C 07 Indexed String G37 4x01606 G37 Disabled Setting 0 1 1 2 * * *
Q<Inhibit set 3C 08 Courier Number (VAr) 4x01607 G2 4 Setting 4*V1*I1 200*V1*I1 0.5*V1*I1 2 * * *
S< Inhibit 3C 09 Indexed String G37 4x01608 G37 Disabled Setting 0 1 1 2 * * *
S<Inhibit set 3C 0A Courier Number (VA) 4x01609 G2 4 Setting 4*V1*I1 200*V1*I1 0.5*V1*I1 2 * * *
100% St EF VN3H> 3C 0B Courier Number (Voltage) 4x01610 G2 1 Setting 0.3*V3 20*V3 0.1*V3 2 * * *
VN3H> Delay 3C 0C Courier Number (Time) 4x01611 G2 5 Setting 0 100 0.01 2 * * *
64S LF Injection 3C 10 Indexed String G37 4x01612 G37 Enabled Setting 0 1 1 2 * Available to P345 only
64S R Factor 3C 14 Courier Number (Decimal) 4x01613 G2 10 Setting 0.01 200 0.01 2 * Scaling factor for primary resistance across earthing
transformer. Affects the stator resistance settings and
measurements only.
(Not used)
64S R<1 Alarm 3C 1C Indexed String G37 4x01614 G37 Enabled Setting 0 1 1 2 *
64S R<1 Alm Set 3C 20 Courier Number (Resistance) 4x01615 G2 100 Setting 10 700 0.1 2 *
64S R<1 Alm Dly 3C 24 Courier Number (Time) 4x01616 G2 1 Setting 0 100 0.01 2 *
64S R<2 Trip 3C 28 Indexed String G37 4x01617 G37 Enabled Setting 0 1 1 2 *
64S R<2 Trip Set 3C 2C Courier Number (Resistance) 4x01618 G2 20 Setting 10 700 0.1 2 *
64S R<2 Trip Dly 3C 30 Courier Number (Time) 4x01619 G2 1 Setting 0 100 0.01 2 *
64S Angle Comp 3C 34 Courier Number (Angle) 4x01620 G2 0 Setting -60 60 0.1 2 *
64S Series R 3C 38 Courier Number (Resistance) 4x01621 G2 0 Setting 0 700 0.1 2 *
64S Parallel G 3C 3C Courier Number (Conductance) 4x01623 G35 0 Setting 0 0.1 0.0000001 2 *
64S Overcurrent 3C 40 Indexed String G37 4x01625 G37 Enabled Setting 0 1 1 2 *
64S I>1 Trip Set 3C 44 Courier Number (Current) 4x01626 G2 0.5 Setting 0.02 1.5 0.01 2 *
64S I>1 Trip Dly 3C 48 Courier Number (Time) 4x01627 G2 1 Setting 0 100 0.01 2 *
64S Supervision 3C 4C Indexed String G37 4x01628 G37 Disabled Setting 0 1 1 2 *
64S V<1 Set 3C 50 Courier Number (Voltage) 4x01629 G2 1 Setting 0.3 25 0.1 2 *
64S I<1 Set 3C 54 Courier Number (Current) 4x01630 G2 0.01 Setting 0.005 0.04 0.001 2 *
64S Superv'n Dly 3C 58 Courier Number (Time) 4x01631 G2 1 Setting 0 100 0.01 2 *
GROUP 1
3D 00 * * * *
VOLTS/HZ
V/Hz Alm Status 3D 01 Indexed String G37 4x01650 G37 Enabled Setting 0 1 1 2 * * * *
V/Hz Alarm Set 3D 02 Courier Number (Volts/Hz) 4x01651 G2 2.31 Setting 1.5*V1 3.5*V1 0.01*V1 2 * * * *
V/Hz Alarm Delay 3D 03 Courier Number (Time) 4x01652 G2 10 Setting 0 100 0.01 2 * * * *
V/Hz>1 Status 3D 10 Indexed String G37 4x01657 G37 Enabled Setting 0 1 1 2 * * * *
V/Hz>1 Trip Func 3D 13 Indexed String G160 4x01658 G160 DT Setting 0 1 1 2 * * * *
V/Hz>1 Trip Set 3D 16 Courier Number (Volts/Hz) 4x01659 G2 2.42 Setting 1.5*V1 3.5*V1 0.01*V1 2 * * * *
V/Hz>1 Trip TMS 3D 19 Courier Number (Decimal) 4x01660 G2 1 Setting 0.01 12 0.01 2 * * * *
V/Hz>1 Delay 3D 1A Courier Number (Time) 4x01661 G2 60 Setting 0 600 0.01 2 * * * *
V/Hz>2 Status 3D 20 Indexed String G37 4x01663 G37 Enabled Setting 0 1 1 2 * * * *
V/Hz>2 Trip Set 3D 25 Courier Number (Volts/Hz) 4x01664 G2 2.64 Setting 1.5*V1 3.5*V1 0.01*V1 2 * * * *
V/Hz>2 Delay 3D 2A Courier Number (Time) 4x01665 G2 3 Setting 0 600 0.01 2 * * * *
V/Hz>3 Status 3D 30 Indexed String G37 4x01667 G37 Enabled Setting 0 1 1 2 * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 33

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
V/Hz>3 Trip Set 3D 35 Courier Number (Volts/Hz) 4x01668 G2 2.86 Setting 1.5*V1 3.5*V1 0.01*V1 2 * * * *
V/Hz>3 Delay 3D 3A Courier Number (Time) 4x01669 G2 2 Setting 0 600 0.01 2 * * * *
V/Hz>4 Status 3D 40 Indexed String G37 4x01671 G37 Enabled Setting 0 1 1 2 * * * *
V/Hz>4 Trip Set 3D 45 Courier Number (Volts/Hz) 4x01672 G2 3.08 Setting 1.5*V1 3.5*V1 0.01*V1 2 * * * *
V/Hz>4 Delay 3D 4A Courier Number (Time) 4x01673 G2 1 Setting 0 600 0.01 2 * * * *
GROUP 1
3E 00 *
DF/DT
df/dt Status 3E 01 Indexed String G37 4x01700 G37 Enabled Setting 0 1 1 2 *
df/dt Setting 3E 02 Courier Number (Hz/s) 4x01701 G2 0.2 Setting 0.1 10 0.01 2 *
df/dt Time Delay 3E 03 Courier Number (Time) 4x01702 G2 0.5 Setting 0 100 0.01 2 *
df/dt f Low 3E 04 Courier Number (Frequency) 4x01703 G2 49.5 Setting 45 65 0.01 2 *
df/dt f High 3E 05 Courier Number (Frequency) 4x01704 G2 50.5 Setting 45 65 0.01 2 *
GROUP 1
3F 00 *
V VECTOR SHIFT
V Shift Status 3F 01 Indexed String G37 4x01750 G37 Enabled Setting 0 1 1 2 *
V Shift Angle 3F 02 Courier Number (Angle) 4x01751 G2 10 Setting 2 30 1 2 *
GROUP 1
40 00 * * *
DEAD MACHINE
Dead Mach Status 40 01 Indexed String G37 4x01800 G37 Disabled Setting 0 1 1 2 * * *
Dead Mach I> 40 02 Courier Number (Current) 4x01801 G2 0.1 Setting 0.08*I1 4*I1 0.01*I1 2 * * *
Dead Mach V< 40 03 Courier Number (Voltage) 4x01802 G2 80 Setting 10*V1 120*V1 1*V1 2 * * *
Dead Mach tPU 40 04 Courier Number (Time) 4x01803 G2 5 Setting 0 10 0.1 2 * * *
Dead Mach tDO 40 05 Courier Number (Time) 4x01804 G2 0.5 Setting 0 10 0.1 2 * * *
GROUP 1
41 00 *
RECONNECT DELAY
Reconnect Status 41 01 Indexed String G37 4x01850 G37 Enabled Setting 0 1 1 2 *
Reconnect Delay 41 02 Courier Number (Time) 4x01852 G2 60 Setting 0 300 0.01 2 *
Reconnect tPULSE 41 03 Courier Number (Time) 4x01853 G2 1 Setting 0.01 30 0.01 2 *
GROUP 1
42 00 * * * * *
VOLT PROTECTION
UNDER VOLTAGE 42 01 (Sub Heading) * * * * *
V< Measur't Mode 42 02 Indexed String G47 4x01950 G47 Phase-Neutral Setting 0 1 1 2 * * * * *
V< Operate Mode 42 03 Indexed String G48 4x01951 G48 Any Phase Setting 0 1 1 2 * * * * *
V<1 Function 42 04 Indexed String G23 4x01952 G23 DT Setting 0 2 1 2 * * * * *
V<1 Voltage Set 42 05 Courier Number (Voltage) 4x01953 G2 50 Setting 10*V1 120*V1 1*V1 2 * * * * *
V<1 Time Delay 42 06 Courier Number (Time) 4x01954 G2 10 Setting 0 100 0.01 2 * * * * *
V<1 TMS 42 07 Courier Number (Decimal) 4x01955 G2 1 Setting 0.05 100 0.05 2 * * * * *
V<1 Poledead Inh 42 08 Indexed String G37 4x01956 G37 Enabled Setting 0 1 1 2 * * * * *
V<2 Status 42 09 Indexed String G37 4x01957 G37 Disabled Setting 0 1 1 2 * * * * *
V<2 Voltage Set 42 0A Courier Number (Voltage) 4x01958 G2 38 Setting 10*V1 120*V1 1*V1 2 * * * * *
V<2 Time Delay 42 0B Courier Number (Time) 4x01959 G2 5 Setting 0 100 0.01 2 * * * * *
V<2 Poledead Inh 42 0C Indexed String G37 4x01960 G37 Enabled Setting 0 1 1 2 * * * * *
OVERVOLTAGE 42 0D (Sub Heading) * * * * *
V> Measur't Mode 42 0E Indexed String G47 4x01961 G47 Phase-Phase Setting 0 1 1 2 * * * * *
V> Operate Mode 42 0F Indexed String G48 4x01962 G48 Any Phase Setting 0 1 1 2 * * * * *
V>1 Function 42 10 Indexed String G23 4x01963 G23 DT Setting 0 2 1 2 * * * * *
V>1 Voltage Set 42 11 Courier Number (Voltage) 4x01964 G2 130 Setting 60*V1 185*V1 1*V1 2 * * * * *
V>1 Time Delay 42 12 Courier Number (Time) 4x01965 G2 10 Setting 0 100 0.01 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 34

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
V>1 TMS 42 13 Courier Number (Decimal) 4x01966 G2 1 Setting 0.05 100 0.05 2 * * * * *
V>2 Status 42 14 Indexed String G37 4x01967 G37 Disabled Setting 0 1 1 2 * * * * *
V>2 Voltage Set 42 15 Courier Number (Voltage) 4x01968 G2 150 Setting 60*V1 185*V1 1*V1 2 * * * * *
V>2 Time Delay 42 16 Courier Number (Time) 4x01969 G2 0.5 Setting 0 100 0.01 2 * * * * *
NPS OVERVOLTAGE 42 20 (Sub Heading) * * * * *
V2>1 Status 42 22 Indexed String G37 4x01970 G37 Disabled Setting 0 1 1 2 * * * * *
V2>1 Voltage Set 42 26 Courier Number (Voltage) 4x01971 G2 15 Setting 1*V1 150*V1 1*V1 2 * * * * *
V2>1 Time Delay 42 28 Courier Number (Time) 4x01972 G2 1 Setting 0 100 0.01 2 * * * * *
GROUP 1
43 00 * * * * *
FREQ PROTECTION
UNDER FREQUENCY 43 01 (Sub Heading) * * * * *
F<1 Status 43 02 Indexed String G37 4x02000 G37 Enabled Setting 0 1 1 2 * * * * *
F<1 Setting 43 03 Courier Number (Frequency) 4x02001 G2 49.5 Setting 45 65 0.01 2 * * * * *
F<1 Time Delay 43 04 Courier Number (Time) 4x02002 G2 4 Setting 0 100 0.01 2 * * * * *
F<2 Status 43 05 Indexed String G37 4x02003 G37 Disabled Setting 0 1 1 2 * * * * *
F<2 Setting 43 06 Courier Number (Frequency) 4x02004 G2 49 Setting 45 65 0.01 2 * * * * *
F<2 Time Delay 43 07 Courier Number (Time) 4x02005 G2 3 Setting 0 100 0.01 2 * * * * *
F<3 Status 43 08 Indexed String G37 4x02006 G37 Disabled Setting 0 1 1 2 * * * * *
F<3 Setting 43 09 Courier Number (Frequency) 4x02007 G2 48.5 Setting 45 65 0.01 2 * * * * *
F<3 Time Delay 43 0A Courier Number (Time) 4x02008 G2 2 Setting 0 100 0.01 2 * * * * *
F<4 Status 43 0B Indexed String G37 4x02009 G37 Disabled Setting 0 1 1 2 * * * * *
F<4 Setting 43 0C Courier Number (Frequency) 4x02010 G2 48 Setting 45 65 0.01 2 * * * * *
F<4 Time Delay 43 0D Courier Number (Time) 4x02011 G2 1 Setting 0 100 0.01 2 * * * * *
F< Function Link 43 0E Binary Flag (4 bits) G65 4x02012 G65 16 Setting 15 4 1 2 * * * * *
OVER FREQUENCY 43 0F (Sub Heading) * * * * *
F>1 Status 43 10 Indexed String G37 4x02013 G37 Enabled Setting 0 1 1 2 * * * * *
F>1 Setting 43 11 Courier Number (Frequency) 4x02014 G2 50.5 Setting 45 68 0.01 2 * * * * *
F>1 Time Delay 43 12 Courier Number (Time) 4x02015 G2 2 Setting 0 100 0.01 2 * * * * *
F>2 Status 43 13 Indexed String G37 4x02016 G37 Disabled Setting 0 1 1 2 * * * * *
F>2 Setting 43 14 Courier Number (Frequency) 4x02017 G2 51 Setting 45 68 0.01 2 * * * * *
F>2 Time Delay 43 15 Courier Number (Time) 4x02018 G2 1 Setting 0 100 0.01 2 * * * * *
TURBINE F PROT 43 20 (Sub Heading) * * * * Turbine Abnormal Frequency Protection
Turbine F Status 43 22 Indexed String G37 4x12000 G37 Disabled Setting 0 1 1 2 * * * *
Band 1 Status 43 24 Indexed String G37 4x12001 G37 Enabled Setting 0 1 1 2 * * * *
Band 1 Freq Low 43 26 Courier Number (Frequency) 4x12002 G2 46.5 Setting 20 70 0.01 2 * * * *
Band 1 Freq High 43 28 Courier Number (Frequency) 4x12003 G2 47 Setting 20 70 0.01 2 * * * *
Band 1 Duration 43 2A Courier Number (Time) 4x12004 4x12025 G35 1 Setting 0 3600000 0.01 2 * * * * Band 1 Accumulated Time Threshold
Band 1 Dead Time 43 2C Courier Number (Time) 4x12026 G2 0.2 Setting 0 200 0.01 2 * * * *
Band 2 Status 43 34 Indexed String G37 4x12027 G37 Enabled Setting 0 1 1 2 * * * *
Band 2 Freq Low 43 36 Courier Number (Frequency) 4x12028 G2 47 Setting 20 70 0.01 2 * * * *
Band 2 Freq High 43 38 Courier Number (Frequency) 4x12029 G2 47.5 Setting 20 70 0.01 2 * * * *
Band 2 Duration 43 3A Courier Number (Time) 4x12030 4x12031 G35 2.5 Setting 0 3600000 0.01 2 * * * * Band 2 Accumulated Time Threshold
Band 2 Dead Time 43 3C Courier Number (Time) 4x12032 G2 0.2 Setting 0 200 0.01 2 * * * *
Band 3 Status 43 44 Indexed String G37 4x12033 G37 Enabled Setting 0 1 1 2 * * * *
Band 3 Freq Low 43 46 Courier Number (Frequency) 4x12034 G2 47.5 Setting 20 70 0.01 2 * * * *
Band 3 Freq High 43 48 Courier Number (Frequency) 4x12035 G2 48 Setting 20 70 0.01 2 * * * *
Band 3 Duration 43 4A Courier Number (Time) 4x12036 4x12037 G35 14 Setting 0 3600000 0.01 2 * * * * Band 3 Accumulated Time Threshold
Band 3 Dead Time 43 4C Courier Number (Time) 4x12038 G2 0.2 Setting 0 200 0.01 2 * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 35

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Band 4 Status 43 54 Indexed String G37 4x12039 G37 Enabled Setting 0 1 1 2 * * * *
Band 4 Freq Low 43 56 Courier Number (Frequency) 4x12040 G2 48 Setting 20 70 0.01 2 * * * *
Band 4 Freq High 43 58 Courier Number (Frequency) 4x12041 G2 48.5 Setting 20 70 0.01 2 * * * *
Band 4 Duration 43 5A Courier Number (Time) 4x12042 4x12043 G35 100 Setting 0 3600000 0.01 2 * * * * Band 4 Accumulated Time Threshold
Band 4 Dead Time 43 5C Courier Number (Time) 4x12044 G2 0.2 Setting 0 200 0.01 2 * * * *
Band 5 Status 43 64 Indexed String G37 4x12045 G37 Enabled Setting 0 1 1 2 * * * *
Band 5 Freq Low 43 66 Courier Number (Frequency) 4x12046 G2 48.5 Setting 20 70 0.01 2 * * * *
Band 5 Freq High 43 68 Courier Number (Frequency) 4x12047 G2 49 Setting 20 70 0.01 2 * * * *
Band 5 Duration 43 6A Courier Number (Time) 4x12048 4x12049 G35 540 Setting 0 3600000 0.01 2 * * * * Band 5 Accumulated Time Threshold
Band 5 Dead Time 43 6C Courier Number (Time) 4x12050 G2 0.2 Setting 0 200 0.01 2 * * * *
Band 6 Status 43 74 Indexed String G37 4x12051 G37 Enabled Setting 0 1 1 2 * * * *
Band 6 Freq Low 43 76 Courier Number (Frequency) 4x12052 G2 49 Setting 20 70 0.01 2 * * * *
Band 6 Freq High 43 78 Courier Number (Frequency) 4x12053 G2 49.5 Setting 20 70 0.01 2 * * * *
Band 6 Duration 43 7A Courier Number (Time) 4x12054 4x12055 G35 3000 Setting 0 3600000 0.01 2 * * * * Band 6 Accumulated Time Threshold
Band 6 Dead Time 43 7C Courier Number (Time) 4x12056 G2 0.2 Setting 0 200 0.01 2 * * * *
GROUP 1
44 00 * * * *
RTD PROTECTION
Select RTD 44 01 Binary Flags(10 bits)Indexed String G50 4x02053 G50 0 Setting 1023 10 1 2 * * * *
RTD 1 Alarm Set 44 02 Courier Number (Temperature) 4x02054 G1 80 Setting 0 200 1 2 * * * *
RTD 1 Alarm Dly 44 03 Courier Number (Time) 4x02055 G1 10 Setting 0 100 1 2 * * * *
RTD 1 Trip Set 44 04 Courier Number (Temperature) 4x02056 G1 85 Setting 0 200 1 2 * * * *
RTD 1 Trip Dly 44 05 Courier Number (Time) 4x02057 G1 1 Setting 0 100 1 2 * * * *
RTD 2 Alarm Set 44 06 Courier Number (Temperature) 4x02058 G1 80 Setting 0 200 1 2 * * * *
RTD 2 Alarm Dly 44 07 Courier Number (Time) 4x02059 G1 10 Setting 0 100 1 2 * * * *
RTD 2 Trip Set 44 08 Courier Number (Temperature) 4x02060 G1 85 Setting 0 200 1 2 * * * *
RTD 2 Trip Dly 44 09 Courier Number (Time) 4x02061 G1 1 Setting 0 100 1 2 * * * *
RTD 3 Alarm Set 44 0A Courier Number (Temperature) 4x02062 G1 80 Setting 0 200 1 2 * * * *
RTD 3 Alarm Dly 44 0B Courier Number (Time) 4x02063 G1 10 Setting 0 100 1 2 * * * *
RTD 3 Trip Set 44 0C Courier Number (Temperature) 4x02064 G1 85 Setting 0 200 1 2 * * * *
RTD 3 Trip Dly 44 0D Courier Number (Time) 4x02065 G1 1 Setting 0 100 1 2 * * * *
RTD 4 Alarm Set 44 0E Courier Number (Temperature) 4x02066 G1 80 Setting 0 200 1 2 * * * *
RTD 4 Alarm Dly 44 0F Courier Number (Time) 4x02067 G1 10 Setting 0 100 1 2 * * * *
RTD 4 Trip Set 44 10 Courier Number (Temperature) 4x02068 G1 85 Setting 0 200 1 2 * * * *
RTD 4 Trip Dly 44 11 Courier Number (Time) 4x02069 G1 1 Setting 0 100 1 2 * * * *
RTD 5 Alarm Set 44 12 Courier Number (Temperature) 4x02070 G1 80 Setting 0 200 1 2 * * * *
RTD 5 Alarm Dly 44 13 Courier Number (Time) 4x02071 G1 10 Setting 0 100 1 2 * * * *
RTD 5 Trip Set 44 14 Courier Number (Temperature) 4x02072 G1 85 Setting 0 200 1 2 * * * *
RTD 5 Trip Dly 44 15 Courier Number (Time) 4x02073 G1 1 Setting 0 100 1 2 * * * *
RTD 6 Alarm Set 44 16 Courier Number (Temperature) 4x02074 G1 80 Setting 0 200 1 2 * * * *
RTD 6 Alarm Dly 44 17 Courier Number (Time) 4x02075 G1 10 Setting 0 100 1 2 * * * *
RTD 6 Trip Set 44 18 Courier Number (Temperature) 4x02076 G1 85 Setting 0 200 1 2 * * * *
RTD 6 Trip Dly 44 19 Courier Number (Time) 4x02077 G1 1 Setting 0 100 1 2 * * * *
RTD 7 Alarm Set 44 1A Courier Number (Temperature) 4x02078 G1 80 Setting 0 200 1 2 * * * *
RTD 7 Alarm Dly 44 1B Courier Number (Time) 4x02079 G1 10 Setting 0 100 1 2 * * * *
RTD 7 Trip Set 44 1C Courier Number (Temperature) 4x02080 G1 85 Setting 0 200 1 2 * * * *
RTD 7 Trip Dly 44 1D Courier Number (Time) 4x02081 G1 1 Setting 0 100 1 2 * * * *
RTD 8 Alarm Set 44 1E Courier Number (Temperature) 4x02082 G1 80 Setting 0 200 1 2 * * * *
RTD 8 Alarm Dly 44 1F Courier Number (Time) 4x02083 G1 10 Setting 0 100 1 2 * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 36

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
RTD 8 Trip Set 44 20 Courier Number (Temperature) 4x02084 G1 85 Setting 0 200 1 2 * * * *
RTD 8 Trip Dly 44 21 Courier Number (Time) 4x02085 G1 1 Setting 0 100 1 2 * * * *
RTD 9 Alarm Set 44 22 Courier Number (Temperature) 4x02086 G1 80 Setting 0 200 1 2 * * * *
RTD 9 Alarm Dly 44 23 Courier Number (Time) 4x02087 G1 10 Setting 0 100 1 2 * * * *
RTD 9 Trip Set 44 24 Courier Number (Temperature) 4x02088 G1 85 Setting 0 200 1 2 * * * *
RTD 9 Trip Dly 44 25 Courier Number (Time) 4x02089 G1 1 Setting 0 100 1 2 * * * *
RTD 10 Alarm Set 44 26 Courier Number (Temperature) 4x02090 G1 80 Setting 0 200 1 2 * * * *
RTD 10 Alarm Dly 44 27 Courier Number (Time) 4x02091 G1 10 Setting 0 100 1 2 * * * *
RTD 10 Trip Set 44 28 Courier Number (Temperature) 4x02092 G1 85 Setting 0 200 1 2 * * * *
RTD 10 Trip Dly 44 29 Courier Number (Time) 4x02093 G1 1 Setting 0 100 1 2 * * * *
GROUP 1
45 00 * * * * *
CB FAIL & I<
BREAKER FAIL 45 01 (Sub Heading) * * * * *
CB Fail 1 Status 45 02 Indexed String G37 4x02100 G37 Enabled Setting 0 1 1 2 * * * * *
CB Fail 1 Timer 45 03 Courier Number (Time) 4x02101 G2 0.2 Setting 0 10 0.01 2 * * * * *
CB Fail 2 Status 45 04 Indexed String G37 4x02102 G37 Disabled Setting 0 1 1 2 * * * * *
CB Fail 2 Timer 45 05 Courier Number (Time) 4x02103 G2 0.4 Setting 0 10 0.01 2 * * * * *
CBF Non I Reset 45 06 Indexed String G68 4x02104 G68 CB Open & I< Setting 0 2 1 2 * * * * *
CBF Ext Reset 45 07 Indexed String G68 4x02105 G68 CB Open & I< Setting 0 2 1 2 * * * * *
UNDER CURRENT 45 08 (Sub Heading) * * * * *
I< Current Set 45 09 Courier Number (Current) 4x02106 G2 0.1 Setting 0.02*I1 3.2*I1 0.01*I1 2 * * * * *
IN< Current Set 45 0A Courier Number (Current) 4x02107 G2 0.1 Setting 0.02*I2 3.2*I2 0.01*I2 2 * * * *
ISEF< Current 45 0B Courier Number (Current) 4x02108 G2 0.02 Setting 0.001*I3 0.8*I3 0.0005*I3 2 * * * * *
BLOCKED O/C 45 0C (Sub Heading) *
Remove I> Start 45 0D Indexed String G37 4x02109 G37 Disabled Setting 0 1 1 2 *
Remove IN> Start 45 0E Indexed String G37 4x02110 G37 Disabled Setting 0 1 1 2 *
I< CT Source 45 15 Indexed String G116 4x02111 G116 IA-1, IB-1, IC-1 Setting 0 1 1 2 * * *
GROUP 1
46 00 * * * * *
SUPERVISION
VT SUPERVISION 46 01 (Sub Heading) * * * * *
VTS Status 46 02 Indexed String G7 4x02150 G7 Blocking Setting 0 1 1 2 * * * * *
VTS Reset Mode 46 03 Indexed String G69 4x02151 G69 Manual Setting 0 1 1 2 * * * * *
VTS Time Delay 46 04 Courier Number (Time) 4x02152 G2 5 Setting 1 10 0.1 2 * * * * *
VTS I> Inhibit 46 05 Courier Number (Current) 4x02153 G2 10 Setting 0.08*I1 32*I1 0.01*I1 2 * * * * *
VTS I2> Inhibit 46 06 Courier Number (Current) 4x02154 G2 0.05 Setting 0.05*I1 0.5*I1 0.01*I1 2 * * * * *
CT SUPERVISION 46 07 (Sub Heading) * * * * *
CTS1 Status 46 08 Indexed String G37 4x02155 G37 Disabled Setting 0 1 1 2 * * * * *
CTS1 VN Input 46 09 Indexed String G49 4x02156 G49 Derived Setting 0 1 1 2 * * * * *
0.5*V1 22*V1 0.5*V1 2 * * * * *
CTS1 VN< Inhibit 46 0A Courier Number (Voltage) 4x02157 G2 5 Setting
0.5*V3 22*V3 0.5*V3
CTS1 IN> Set 46 0B Courier Number (Current) 4x02158 G2 0.2 Setting 0.08*I1 4*I1 0.01*I1 2 * * * * *
CTS1 Time Delay 46 0C Courier Number (Time) 4x02159 G2 5 Setting 0 10 1 2 * * * * *
CTS2 Status 46 20 Indexed String G37 4x02160 G37 Disabled Setting 0 1 1 2 * * *
CTS2 VN Input 46 24 Indexed String G49 4x02161 G49 Derived Setting 0 1 1 2 * * *
0.5*V1 22*V1 0.5*V1 2 * * *
CTS2 VN< Inhibit 46 28 Courier Number (Voltage) 4x02162 G2 5 Setting
0.5*V3 22*V3 0.5*V3
CTS2 IN> Set 46 2C Courier Number (Current) 4x02163 G2 0.2 Setting 0.08*I1 4*I1 0.01*I1 2 * * *
CTS2 Time Delay 46 30 Courier Number (Time) 4x02164 G2 5 Setting 0 10 1 2 * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 37

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
GROUP 1
47 00 * * * * *
SENSITIVE POWER
Comp Angle 47 20 Courier Number (Angle) 4x02175 G2 0 Setting -5 5 0.1 2 * * * * *
Operating Mode 47 24 Indexed String G115 4x02190 G115 Generating Setting 0 1 1 2 * * * * *
Sen Power1 Func 47 28 Indexed String G102 4x02176 G102 Reverse Setting 0 3 1 2 * * * * *
Sen -P>1 Setting 47 2C Courier Number (Power) 4x02177 G2 0.5*V1*I3 Setting 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * *
Sen P<1 Setting 47 30 Courier Number (Power) 4x02178 G2 0.5*V1*I3 Setting 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * *
Sen P>1 Setting 47 34 Courier Number (Power) 4x02179 G2 50*V1*I3 Setting 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * *
Sen Power1 Delay 47 38 Courier Number (Time) 4x02180 G2 5 Setting 0 100 0.01 2 * * * * *
Power1 DO Timer 47 3C Courier Number (Time) 4x02181 G2 0 Setting 0 100 0.01 2 * * * * *
P1 PoleDead Inh 47 40 Indexed String G37 4x02182 G37 Enabled Setting 0 1 1 2 * * * * *
Sen Power2 Func 47 44 Indexed String G102 4x02183 G102 Low Forward Setting 0 3 1 2 * * * * *
Sen -P>2 Setting 47 48 Courier Number (Power) 4x02184 G2 0.5*V1*I3 Setting 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * *
Sen P<2 Setting 47 4C Courier Number (Power) 4x02185 G2 0.5*V1*I3 Setting 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * *
Sen P>2 Setting 47 50 Courier Number (Power) 4x02186 G2 50*V1*I3 Setting 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * *
Sen Power2 Delay 47 54 Courier Number (Time) 4x02187 G2 2 Setting 0 100 0.01 2 * * * * *
Power2 DO Timer 47 58 Courier Number (Time) 4x02188 G2 0 Setting 0 100 0.01 2 * * * * *
P2 PoleDead Inh 47 5C Indexed String G37 4x02189 G37 Enabled Setting 0 1 1 2 * * * * *
GROUP 1
48 00
NOT USED
GROUP 1
49 00 * * *
POLE SLIPPING
PSlip Function 49 01 Indexed String G37 4x02250 G37 Enabled Setting 0 1 1 2 * * *
Z Based PoleSlip 49 02 (Sub Heading) * * *
Pole Slip Mode 49 03 Indexed String G113 4x02251 G113 Generating Setting 0 2 1 2 * * *
PSlip Za Forward 49 04 Courier Number (Impedance) 4x02252 G2 100*V1/I1 Setting 0.5*V1/I1 350*V1/I1 0.5*V1/I1 2 * * *
PSlip Zb Reverse 49 05 Courier Number (Impedance) 4x02253 G2 150*V1/I1 Setting 0.5*V1/I1 350*V1/I1 0.5*V1/I1 2 * * *
Lens Angle 49 06 Courier Number (Angle) 4x02254 G2 120 Setting 90 150 1 2 * * *
PSlip Timer T1 49 07 Courier Number (Time) 4x02255 G2 0.015 Setting 0 1 0.005 2 * * *
PSlip Timer T2 49 08 Courier Number (Time) 4x02256 G2 0.015 Setting 0 1 0.005 2 * * *
Blinder Angle 49 09 Courier Number (Angle) 4x02257 G2 75 Setting 20 90 1 2 * * *
PSlip Zc 49 0A Courier Number (Impedance) 4x02258 G2 50*V1/I1 Setting 0.5*V1/I1 350*V1/I1 0.5*V1/I1 2 * * *
Zone1 Slip Count 49 0B Unsigned Integer 4x02259 G1 1 Setting 1 20 1 2 * * *
Zone2 Slip Count 49 0C Unsigned Integer 4x02260 G1 2 Setting 1 20 1 2 * * *
PSlip Reset Time 49 0D Courier Number (Time) 4x02261 G2 30 Setting 0 100 0.01 2 * * *
GROUP 1
4A 00 * * * * *
INPUT LABELS
Opto Input 1 4A 01 ASCII Text (16 chars) 4x02300 4x02307 G3 L1 Setting Group Setting 32 163 1 2 * * * * *
Opto Input 2 4A 02 ASCII Text (16 chars) 4x02308 4x02315 G3 L2 Setting Group Setting 32 163 1 2 * * * * *
L3 Block IN>3&4 *
Opto Input 3 4A 03 ASCII Text (16 chars) 4x02316 4x02323 G3 Setting 32 163 1 2
L3 Block IN>2 * * * *
L4 Block I>3&4 *
Opto Input 4 4A 04 ASCII Text (16 chars) 4x02324 4x02331 G3 Setting 32 163 1 2
L4 Block I>2 * * * *
Opto Input 5 4A 05 ASCII Text (16 chars) 4x02332 4x02339 G3 L5 Reset Setting 32 163 1 2 * * * * *
Opto Input 6 4A 06 ASCII Text (16 chars) 4x02340 4x02347 G3 L6 Ext Prot Trip Setting 32 163 1 2 * * * * *
Opto Input 7 4A 07 ASCII Text (16 chars) 4x02348 4x02355 G3 L7 52a Setting 32 163 1 2 * * * * *
Opto Input 8 4A 08 ASCII Text (16 chars) 4x02356 4x02363 G3 L8 52b Setting 32 163 1 2 * * * * *
Opto Input 9 4A 09 ASCII Text (16 chars) 4x02364 4x02371 G3 L9 Not Used Setting 32 163 1 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 38

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Opto Input 10 4A 0A ASCII Text (16 chars) 4x02372 4x02379 G3 L10 Not Used Setting 32 163 1 2 * * * * *
Opto Input 11 4A 0B ASCII Text (16 chars) 4x02380 4x02387 G3 L11 Not Used Setting 32 163 1 2 * * * * *
Opto Input 12 4A 0C ASCII Text (16 chars) 4x02388 4x02395 G3 L12 Not Used Setting 32 163 1 2 * * * * *
Opto Input 13 4A 0D ASCII Text (16 chars) 4x02396 4x02403 G3 L13 Not Used Setting 32 163 1 2 * * * * *
Opto Input 14 4A 0E ASCII Text (16 chars) 4x02404 4x02411 G3 L14 Not Used Setting 32 163 1 2 * * * * *
Opto Input 15 4A 0F ASCII Text (16 chars) 4x02412 4x02419 G3 L15 Not Used Setting 32 163 1 2 * * * * *
Opto Input 16 4A 10 ASCII Text (16 chars) 4x02420 4x02427 G3 L16 Not Used Setting 32 163 1 2 * * * * *
Opto Input 17 4A 11 ASCII Text (16 chars) 4x02428 4x02435 G3 L17 Not Used Setting 32 163 1 2 * * * * *
Opto Input 18 4A 12 ASCII Text (16 chars) 4x02436 4x02443 G3 L18 Not Used Setting 32 163 1 2 * * * * *
Opto Input 19 4A 13 ASCII Text (16 chars) 4x02444 4x02451 G3 L19 Not Used Setting 32 163 1 2 * * * * *
Opto Input 20 4A 14 ASCII Text (16 chars) 4x02452 4x02459 G3 L20 Not Used Setting 32 163 1 2 * * * * *
Opto Input 21 4A 15 ASCII Text (16 chars) 4x02460 4x02467 G3 L21 Not Used Setting 32 163 1 2 * * * * *
Opto Input 22 4A 16 ASCII Text (16 chars) 4x02468 4x02475 G3 L22 Not Used Setting 32 163 1 2 * * * * *
Opto Input 23 4A 17 ASCII Text (16 chars) 4x02476 4x02483 G3 L23 Not Used Setting 32 163 1 2 * * * * *
Opto Input 24 4A 18 ASCII Text (16 chars) 4x02484 4x02491 G3 L24 Not Used Setting 32 163 1 2 * * * * *
Opto Input 25 4A 19 ASCII Text (16 chars) 4x02492 4x02499 G3 L25 Not Used Setting 32 163 1 2 * * *
Opto Input 26 4A 1A ASCII Text (16 chars) 4x02500 4x02507 G3 L26 Not Used Setting 32 163 1 2 * * *
Opto Input 27 4A 1B ASCII Text (16 chars) 4x02508 4x02515 G3 L27 Not Used Setting 32 163 1 2 * * *
Opto Input 28 4A 1C ASCII Text (16 chars) 4x02516 4x02523 G3 L28 Not Used Setting 32 163 1 2 * * *
Opto Input 29 4A 1D ASCII Text (16 chars) 4x02524 4x02531 G3 L29 Not Used Setting 32 163 1 2 * * *
Opto Input 30 4A 1E ASCII Text (16 chars) 4x02532 4x02539 G3 L30 Not Used Setting 32 163 1 2 * * *
Opto Input 31 4A 1F ASCII Text (16 chars) 4x02540 4x02547 G3 L31 Not Used Setting 32 163 1 2 * * *
Opto Input 32 4A 20 ASCII Text (16 chars) 4x02548 4x02555 G3 L32 Not Used Setting 32 163 1 2 * * *
GROUP 1
4B 00 * * * * *
OUTPUT LABELS
R1 IN>1 Start * * * * *
Relay 1 4B 01 ASCII Text (16 chars) 4x02556 4x02563 G3 Setting 32 163 1 2
R1 Trip CB
R2 I>1 Start * * * * *
Relay 2 4B 02 ASCII Text (16 chars) 4x02564 4x02571 G3 Setting 32 163 1 2
R2 Trip PrimeMov
Relay 3 4B 03 ASCII Text (16 chars) 4x02572 4x02579 G3 R3 Any Trip Setting 32 163 1 2 * * * * *
Relay 4 4B 04 ASCII Text (16 chars) 4x02580 4x02587 G3 R4 General Alarm Setting 32 163 1 2 * * * * *
Relay 5 4B 05 ASCII Text (16 chars) 4x02588 4x02595 G3 R5 CB Fail Setting 32 163 1 2 * * * * *
R6 Control Close *
Relay 6 4B 06 ASCII Text (16 chars) 4x02596 4x02603 G3 Setting 32 163 1 2
R6 E/F Trip * * * *
R7 Control Trip *
Relay 7 4B 07 ASCII Text (16 chars) 4x02604 4x02611 G3 R7 V or F Trip Setting 32 163 1 2 *
R7 Volt Trip * * *
R8 Not Used * *
Relay 8 4B 08 ASCII Text (16 chars) 4x02612 4x02619 G3 Setting 32 163 1 2
R8 Freq Trip * * *
R9 Not Used * *
Relay 9 4B 09 ASCII Text (16 chars) 4x02620 4x02627 G3 Setting 32 163 1 2
R9 Diff Trip * * *
R10 Not Used * *
Relay 10 4B 0A ASCII Text (16 chars) 4x02628 4x02635 G3 Setting 32 163 1 2
R10 SysBack Trip * * *
R11 Not Used * *
Relay 11 4B 0B ASCII Text (16 chars) 4x02636 4x02643 G3 Setting 32 163 1 2
R11 NPS Trip * * *
R12 Not Used * *
Relay 12 4B 0C ASCII Text (16 chars) 4x02644 4x02651 G3 Setting 32 163 1 2
R12 Ffail Trip * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 39

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
R13 Not Used * *
Relay 13 4B 0D ASCII Text (16 chars) 4x02652 4x02659 G3 Setting 32 163 1 2
R13 Power Trip * * *
R14 Not Used * *
Relay 14 4B 0E ASCII Text (16 chars) 4x02660 4x02667 G3 Setting 32 163 1 2
R14 V/Hz Trip * * *
Relay 15 4B 0F ASCII Text (16 chars) 4x02668 4x02675 G3 R15 Not Used Setting 32 163 1 2 * * * * *
Relay 16 4B 10 ASCII Text (16 chars) 4x02676 4x02683 G3 R16 Not Used Setting 32 163 1 2 * * * * *
Relay 17 4B 11 ASCII Text (16 chars) 4x02684 4x02691 G3 R17 Not Used Setting 32 163 1 2 * * * * *
Relay 18 4B 12 ASCII Text (16 chars) 4x02692 4x02699 G3 R18 Not Used Setting 32 163 1 2 * * * * *
Relay 19 4B 13 ASCII Text (16 chars) 4x02700 4x02707 G3 R19 Not Used Setting 32 163 1 2 * * * * *
Relay 20 4B 14 ASCII Text (16 chars) 4x02708 4x02715 G3 R20 Not Used Setting 32 163 1 2 * * * * *
Relay 21 4B 15 ASCII Text (16 chars) 4x02716 4x02723 G3 R21 Not Used Setting 32 163 1 2 * * * * *
Relay 22 4B 16 ASCII Text (16 chars) 4x02724 4x02731 G3 R22 Not Used Setting 32 163 1 2 * * * * *
Relay 23 4B 17 ASCII Text (16 chars) 4x02732 4x02739 G3 R23 Not Used Setting 32 163 1 2 * * * * *
Relay 24 4B 18 ASCII Text (16 chars) 4x02740 4x02747 G3 R24 Not Used Setting 32 163 1 2 * * * * *
Relay 25 4B 19 ASCII Text (16 chars) 4x02748 4x02755 G3 R25 Not Used Setting 32 163 1 2 * * *
Relay 26 4B 1A ASCII Text (16 chars) 4x02756 4x02763 G3 R26 Not Used Setting 32 163 1 2 * * *
Relay 27 4B 1B ASCII Text (16 chars) 4x02764 4x02771 G3 R27 Not Used Setting 32 163 1 2 * * *
Relay 28 4B 1C ASCII Text (16 chars) 4x02772 4x02779 G3 R28 Not Used Setting 32 163 1 2 * * *
Relay 29 4B 1D ASCII Text (16 chars) 4x02780 4x02787 G3 R29 Not Used Setting 32 163 1 2 * * *
Relay 30 4B 1E ASCII Text (16 chars) 4x02788 4x02795 G3 R30 Not Used Setting 32 163 1 2 * * *
Relay 31 4B 1F ASCII Text (16 chars) 4x02796 4x02803 G3 R31 Not Used Setting 32 163 1 2 * * *
Relay 32 4B 20 ASCII Text (16 chars) 4x02804 4x02811 G3 R32 Not Used Setting 32 163 1 2 * * *
GROUP 1
4C 00 * * * *
RTD LABELS
RTD 1 4C 01 ASCII Text (16 chars) 4x02812 4x02819 G3 RTD 1 Setting 32 163 1 2 * * * *
RTD 2 4C 02 ASCII Text (16 chars) 4x02820 4x02827 G3 RTD 2 Setting 32 163 1 2 * * * *
RTD 3 4C 03 ASCII Text (16 chars) 4x02828 4x02835 G3 RTD 3 Setting 32 163 1 2 * * * *
RTD 4 4C 04 ASCII Text (16 chars) 4x02836 4x02843 G3 RTD 4 Setting 32 163 1 2 * * * *
RTD 5 4C 05 ASCII Text (16 chars) 4x02844 4x02851 G3 RTD 5 Setting 32 163 1 2 * * * *
RTD 6 4C 06 ASCII Text (16 chars) 4x02852 4x02859 G3 RTD 6 Setting 32 163 1 2 * * * *
RTD 7 4C 07 ASCII Text (16 chars) 4x02860 4x02867 G3 RTD 7 Setting 32 163 1 2 * * * *
RTD 8 4C 08 ASCII Text (16 chars) 4x02868 4x02875 G3 RTD 8 Setting 32 163 1 2 * * * *
RTD 9 4C 09 ASCII Text (16 chars) 4x02876 4x02883 G3 RTD 9 Setting 32 163 1 2 * * * *
RTD 10 4C 0A ASCII Text (16 chars) 4x02884 4x02891 G3 RTD 10 Setting 32 163 1 2 * * * *
GROUP 1
4D 00 * * * * *
CLIO PROTECTION
CLIO Input 1 4D 02 Indexed String G37 4x02895 G37 Enabled Setting 0 1 1 2 * * * * *
CLI1 Input Type 4D 04 Indexed String G153 4x02896 G153 4-20mA Setting 0 3 1 2 * * * * *
CLI1 Input Label 4D 06 ASCII Text (16 chars) 4x01900 4x01907 G3 CLIO Input 1 Setting 32 163 1 2 * * * * *
CLI1 Minimum 4D 08 Courier Number (Decimal) 4x02897 4x02898 G35 0 Setting -9999 9999 0.1 2 * * * * *
CLI1 Maximum 4D 0A Courier Number (Decimal) 4x02899 4x02900 G35 100 Setting -9999 9999 0.1 2 * * * * *
CLI1 Alarm 4D 0C Indexed String G37 4x02901 G37 Disabled Setting 0 1 1 2 * * * * *
CLI1 Alarm Fn 4D 0E Indexed String G154 4x02902 G154 Over Setting 0 1 1 2 * * * * *
MIN(CLI1 MAX(CLI1 * * * * *
CLI1 Alarm Set 4D 10 Courier Number (Decimal) 4x02903 4x02904 G35 50 Setting 0.1 2
Min, Max) Min, Max)
CLI1 Alarm Delay 4D 12 Courier Number (Time) 4x02905 G2 1 Setting 0 100 0.1 2 * * * * *
CLI1 Trip 4D 14 Indexed String G37 4x02906 G37 Disabled Setting 0 1 1 2 * * * * *
CLI1 Trip Fn 4D 16 Indexed String G154 4x02907 G154 Over Setting 0 1 1 2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 40

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
MIN(CLI1 MAX(CLI1 * * * * *
CLI1 Trip Set 4D 18 Courier Number (Decimal) 4x02908 4x02909 G35 60 Setting 0.1 2
Min, Max) Min, Max)
CLI1 Trip Delay 4D 1A Courier Number (Time) 4x02910 G2 0 Setting 0 100 0.1 2 * * * * *
CLI1 I< Alarm 4D 1C Indexed String G37 4x02911 G37 Disabled Setting 0 1 1 2 * * * * *
CLI1 I< Alm Set 4D 1E Courier Number (Current) 4x02912 G2 0.0035 Setting 0 0.004 0.0001 2 * * * * *
CLIO Input 2 4D 22 Indexed String G37 4x02913 G37 Enabled Setting 0 1 1 2 * * * * *
CLI2 Input Type 4D 24 Indexed String G153 4x02914 G153 4-20mA Setting 0 3 1 2 * * * * *
CLI2 Input Label 4D 26 ASCII Text (16 chars) 4x01908 4x01915 G3 CLIO Input 2 Setting 32 163 1 2 * * * * *
CLI2 Minimum 4D 28 Courier Number (Decimal) 4x02915 4x02916 G35 0 Setting -9999 9999 0.1 2 * * * * *
CLI2 Maximum 4D 2A Courier Number (Decimal) 4x02917 4x02918 G35 100 Setting -9999 9999 0.1 2 * * * * *
CLI2 Alarm 4D 2C Indexed String G37 4x02919 G37 Disabled Setting 0 1 1 2 * * * * *
CLI2 Alarm Fn 4D 2E Indexed String G154 4x02920 G154 Over Setting 0 1 1 2 * * * * *
MIN(CLI2 MAX(CLI2 * * * * *
CLI2 Alarm Set 4D 30 Courier Number (Decimal) 4x02921 4x02922 G35 50 Setting 0.1 2
Min, Max) Min, Max)
CLI2 Alarm Delay 4D 32 Courier Number (Time) 4x02923 G2 1s Setting 0 100 0.1 2 * * * * *
CLI2 Trip 4D 34 Indexed String G37 4x02924 G37 Disabled Setting 0 1 1 2 * * * * *
CLI2 Trip Fn 4D 36 Indexed String G154 4x02925 G154 Over Setting 0 1 1 2 * * * * *
MIN(CLI2 MAX(CLI2 * * * * *
CLI2 Trip Set 4D 38 Courier Number (Decimal) 4x02926 4x02927 G35 60 Setting 0.1 2
Min, Max) Min, Max)
CLI2 Trip Delay 4D 3A Courier Number (Time) 4x02928 G2 0s Setting 0 100 0.1 2 * * * * *
CLI2 I< Alarm 4D 3C Indexed String G37 4x02929 G37 Disabled Setting 0 1 1 2 * * * * *
CLI2 I< Alm Set 4D 3E Courier Number (Current) 4x02930 G2 0.0035 Setting 0 0.004 0.0001 2 * * * * *
CLIO Input 3 4D 42 Indexed String G37 4x02931 G37 Enabled Setting 0 1 1 2 * * * * *
CLI3 Input Type 4D 44 Indexed String G153 4x02932 G153 4-20mA Setting 0 3 1 2 * * * * *
CLI3 Input Label 4D 46 ASCII Text (16 chars) 4x01916 4x01923 G3 CLIO Input 3 Setting 32 163 1 2 * * * * *
CLI3 Minimum 4D 48 Courier Number (Decimal) 4x02933 4x02934 G35 0 Setting -9999 9999 0.1 2 * * * * *
CLI3 Maximum 4D 4A Courier Number (Decimal) 4x02935 4x02936 G35 100 Setting -9999 9999 0.1 2 * * * * *
CLI3 Alarm 4D 4C Indexed String G37 4x02937 G37 Disabled Setting 0 1 1 2 * * * * *
CLI3 Alarm Fn 4D 4E Indexed String G154 4x02938 G154 Over Setting 0 1 1 2 * * * * *
MIN(CLI3 MAX(CLI3 * * * * *
CLI3 Alarm Set 4D 50 Courier Number (Decimal) 4x02939 4x02940 G35 50 Setting 0.1 2
Min, Max) Min, Max)
CLI3 Alarm Delay 4D 52 Courier Number (Time) 4x02941 G2 1s Setting 0 100 0.1 2 * * * * *
CLI3 Trip 4D 54 Indexed String G37 4x02942 G37 Disabled Setting 0 1 1 2 * * * * *
CLI3 Trip Fn 4D 56 Indexed String G154 4x02943 G154 Over Setting 0 1 1 2 * * * * *
MIN(CLI3 MAX(CLI3 * * * * *
CLI3 Trip Set 4D 58 Courier Number (Decimal) 4x02944 4x02945 G35 60 Setting 0.1 2
Min, Max) Min, Max)
CLI3 Trip Delay 4D 5A Courier Number (Time) 4x02946 G2 0s Setting 0 100 0.1 2 * * * * *
CLI3 I< Alarm 4D 5C Indexed String G37 4x02947 G37 Disabled Setting 0 1 1 2 * * * * *
CLI3 I< Alm Set 4D 5E Courier Number (Current) 4x02948 G2 0.0035 Setting 0 0.004 0.0001 2 * * * * *
CLIO Input 4 4D 62 Indexed String G37 4x02949 G37 Enabled Setting 0 1 1 2 * * * * *
CLI4 Input Type 4D 64 Indexed String G153 4x02950 G153 4-20mA Setting 0 3 1 2 * * * * *
CLI4 Input Label 4D 66 ASCII Text (16 chars) 4x01924 4x01931 G3 CLIO Input 4 Setting 32 163 1 2 * * * * *
CLI4 Minimum 4D 68 Courier Number (Decimal) 4x02951 4x02952 G35 0 Setting -9999 9999 0.1 2 * * * * *
CLI4 Maximum 4D 6A Courier Number (Decimal) 4x02953 4x02954 G35 100 Setting -9999 9999 0.1 2 * * * * *
CLI4 Alarm 4D 6C Indexed String G37 4x02955 G37 Disabled Setting 0 1 1 2 * * * * *
CLI4 Alarm Fn 4D 6E Indexed String G154 4x02956 G154 Over Setting 0 1 1 2 * * * * *
MIN(CLI4 MAX(CLI4 * * * * *
CLI4 Alarm Set 4D 70 Courier Number (Decimal) 4x02957 4x02958 G35 50 Setting 0.1 2
Min, Max) Min, Max)
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 41

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
CLI4 Alarm Delay 4D 72 Courier Number (Time) 4x02959 G2 1s Setting 0 100 0.1 2 * * * * *
CLI4 Trip 4D 74 Indexed String G37 4x02960 G37 Disabled Setting 0 1 1 2 * * * * *
CLI4 Trip Fn 4D 76 Indexed String G154 4x02961 G154 Over Setting 0 1 1 2 * * * * *
MIN(CLI4 MAX(CLI4 * * * * *
CLI4 Trip Set 4D 78 Courier Number (Decimal) 4x02962 4x02963 G35 60 Setting 0.1 2
Min, Max) Min, Max)
CLI4 Trip Delay 4D 7A Courier Number (Time) 4x02964 G2 0s Setting 0 100 0.1 2 * * * * *
CLI4 I< Alarm 4D 7C Indexed String G37 4x02965 G37 Disabled Setting 0 1 1 2 * * * * *
CLI4 I< Alm Set 4D 7E Courier Number (Current) 4x02966 G2 0.0035 Setting 0 0.004 0.0004 2 * * * * *
CLIO Output 1 4D A0 Indexed String G37 4x02967 G37 Disabled Setting 0 1 1 2 * * * * *
CLO1 Output Type 4D A2 Indexed String G153 4x02968 G153 4-20mA Setting 0 2 1 2 * * * * *
CLO1 Set Values 4D A4 Indexed String G54 4x02969 G54 Primary Setting 0 1 1 2 * * * * *
CLO1 Parameter 4D A6 Indexed String G155 4x02970 G155 IA Magnitude Setting 0 See 1 2 * * * * *
CLO1 Minimum 4D A8 Courier Number 4x02971 4x02972 G35 See G155 table Setting See G155 Meas. Range Table 2 * * * * *
CLO1 Maximum 4D AA Courier Number 4x02973 4x02974 G35 See G155 table Setting See G155 Meas. Range Table 2 * * * * *
CLIO Output 2 4D B0 Indexed String G37 4x02975 G37 Disabled Setting 0 1 1 2 * * * * *
CLO2 Output Type 4D B2 Indexed String G153 4x02976 G153 4-20mA Setting 0 2 1 2 * * * * *
CLO2 Set Values 4D B4 Indexed String G54 4x02977 G54 Primary Setting 0 1 1 2 * * * * *
CLO2 Parameter 4D B6 Indexed String G155 4x02978 G155 IB Magnitude Setting 0 See 1 2 * * * * *
CLO2 Minimum 4D B8 Courier Number 4x02979 4x02980 G35 See G155 table Setting See G155 Meas. Range Table 2 * * * * *
CLO2 Maximum 4D BA Courier Number 4x02981 4x02982 G35 See G155 table Setting See G155 Meas. Range Table 2 * * * * *
CLIO Output 3 4D C0 Indexed String G37 4x02983 G37 Disabled Setting 0 1 1 2 * * * * *
CLO3 Output Type 4D C2 Indexed String G153 4x02984 G153 4-20mA Setting 0 2 1 2 * * * * *
CLO3 Set Values 4D C4 Indexed String G54 4x02985 G54 Primary Setting 0 1 1 2 * * * * *
CLO3 Parameter 4D C6 Indexed String G155 4x02986 G155 IC Magnitude Setting 0 See 1 2 * * * * *
CLO3 Minimum 4D C8 Courier Number 4x02987 4x02988 G35 See G155 Table Setting See G155 Meas. Range Table 2 * * * * *
CLO3 Maximum 4D CA Courier Number 4x02989 4x02990 G35 See G155 Table Setting See G155 Meas. Range Table 2 * * * * *
CLIO Output 4 4D D0 Indexed String G37 4x02991 G37 Disabled Setting 0 1 1 2 * * * * *
CLO4 Output Type 4D D2 Indexed String G153 4x02992 G153 4-20mA Setting 0 2 1 2 * * * * *
CLO4 Set Values 4D D4 Indexed String G54 4x02993 G54 Primary Setting 0 1 1 2 * * * * *
IN Measured Mag 0 See 1 2 * * * *
CLO4 Parameter 4D D6 Indexed String G155 4x02994 G155 Setting
IN Derived Mag G155 *
CLO4 Minimum 4D D8 Courier Number 4x02995 4x02996 G35 See G155 Table Setting See G155 Meas. Range Table 2 * * * * *
CLO4 Maximum 4D DA Courier Number 4x02997 4x02998 G35 See G155 Table Setting See G155 Meas. Range Table 2 * * * * *
GROUP 2 PROTECTION SETTINGS * * * * *
Repeat of Group 1 columns/rows 50 00 4x03000 4x04999 * * * * *
4x13000 4x14999
GROUP 3 PROTECTION SETTINGS * * * * *
Repeat of Group 1 columns/rows 70 00 4x05000 4x06999 * * * * *
4x15000 4x16999
GROUP 4 PROTECTION SETTINGS * * * * *
Repeat of Group 1 columns/rows 90 00 4x07000 4x08999 * * * * *
4x17000 4x18999
(No Header) N/A B0 00 Auto extraction Event Record Column * * * * *
Select Record B0 01 Unsigned Integer(2) Setting 0 65535 1 * * * * *
Faulted Phase 40 Binary Flag (8 Bits) G16 Data * * * * *
Start Elements1 42 Binary Flag (32 Bits) Indexed String G84 Data * * * * *
Start Elements2 43 Binary Flag (32 Bits) Indexed String G107 Data * * * * *
Start Elements3 44 Binary Flag (32 Bits) Indexed String G129 Data * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 42

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Trip Elements1 49 Binary Flag (32 Bits) Indexed String G85 Data * * * * *
Trip Elements2 4A Binary Flag (32 Bits) Indexed String G86 Data * * * * *
Trip Elements3 4B Binary Flag (32 Bits) Indexed String G130 Data * * * * *
Fault Alarms 50 Binary Flag (32 Bits) Indexed String G87 Data * * * * *
Fault Time 55 IEC870 Time & Date Data * * * * *
Active Group 57 Unsigned Integer Data * * * * *
System Frequency 59 Courier Number (frequency) Data * * * * *
Fault Duration 5B Courier Number (time) Data * * * * *
CB Operate Time 5E Courier Number (time) Data * * * * *
Relay Trip Time 60 Courier Number (time) Data * * * * *
IA 62 Courier Number (current) Data * *
IA-1 62 Courier Number (current) Data * * *
IB 63 Courier Number (current) Data * *
IB-1 63 Courier Number (current) Data * * *
IC 64 Courier Number (current) Data * *
IC-1 64 Courier Number (current) Data * * *
VAB 65 Courier Number (voltage) Data * * * * *
VBC 66 Courier Number (voltage) Data * * * * *
VCA 67 Courier Number (voltage) Data * * * * *
VAN 68 Courier Number (voltage) Data * * * * *
VBN 69 Courier Number (voltage) Data * * * * *
VCN 6A Courier Number (voltage) Data * * * * *
IA-2 70 Courier Number (current) Data * * *
IB-2 71 Courier Number (current) Data * * *
IC-2 72 Courier Number (current) Data * * *
IA Differential 80 Courier Number (current) Data * * *
IB Differential 81 Courier Number (current) Data * * *
IC Differential 82 Courier Number (current) Data * * *
VN Measured 90 Courier Number (voltage) Data * * *
VN1 Measured 90 Courier Number (voltage) Data * *
VN2 Measured 92 Courier Number (voltage) Data * *
VN Derived 94 Courier Number (voltage) Data * * * * *
IN Measured 96 Courier Number (current) Data * * * *
IN Derived 96 Courier Number (current) Data *
I Sensitive 99 Courier Number (current) Data * * * * *
IREF Diff 9C Courier Number (current) Data * * * *
IREF Bias 9D Courier Number (current) Data * * * *
I2 A0 Courier Number (current) Data * * * * *
V2 A2 Courier Number (voltage) Data * * * * *
3 Phase Watts A6 Courier Number (Power) Data * * * * *
3 Phase VArs A8 Courier Number (VAr) Data * * * * *
3Ph Power Factor AA Courier Number (Decimal) Data * * * * *
RTD 1 B0 Courier Number (Temperature) Data * * * *
RTD 2 B1 Courier Number (Temperature) Data * * * *
RTD 3 B2 Courier Number (Temperature) Data * * * *
RTD 4 B3 Courier Number (Temperature) Data * * * *
RTD 5 B4 Courier Number (Temperature) Data * * * *
RTD 6 B5 Courier Number (Temperature) Data * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 43

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
RTD 7 B6 Courier Number (Temperature) Data * * * *
RTD 8 B7 Courier Number (Temperature) Data * * * *
RTD 9 B8 Courier Number (Temperature) Data * * * *
RTD 10 B9 Courier Number (Temperature) Data * * * *
df/dt C2 Courier Number (Hz/s) Data *
V Vector Shift C4 Courier Number (Angle) Data *
CLIO Input 1 C6 Courier Number (Decimal) Data * * * * *
CLIO Input 2 C7 Courier Number (Decimal) Data * * * * *
CLIO Input 3 C8 Courier Number (Decimal) Data * * * * *
CLIO Input 4 C9 Courier Number (Decimal) Data * * * * *
64S V Magnitude B0 CA Courier Number (voltage) Data *
64S I Magnitude B0 CB Courier Number (current) Data *
64S R primary B0 CC Courier Number (resistance) Data *
64R CL Input B0 CD Courier Number (current) Data * * * *
64R R Fault B0 CE Courier Number (resistance) Data * * * *
(No Header) N/A B1 00 * * * * *
Select Record B1 01 UINT16 Setting 0 65535 1 * * * * *
Time and Date B1 02 IEC Date and Time Data * * * * *
Maint Text B1 03 ASCII Text Data * * * * *
Maint Type B1 04 UINT32 Data * * * * *
Maint Data B1 05 UINT32 Data * * * * *

DATA TRANSFER
N/A B2 00
(No Header)

Domain B2 04 Indexed String G57 PSL Settings Setting 0 1 1 2 * * * * *


Sub-Domain B2 08 Indexed String G90 Group 1 Setting 0 3 1 2 * * * * *
Version B2 0C Unsigned Integer (2 Bytes) 256 Setting 0 65535 1 2 * * * * *
Start B2 10 Not Used * * * * *
Length B2 14 Not Used * * * * *
Data Transfer Reference B2 18 * * * * *
Transfer Mode B2 1C Unsigned Integer Indexed Strings G76 6 Setting 0 7 1 2 * * * * *
Data Transfer B2 20 Repeated groups of Unsigned Integers Setting * * * * *

RECORDER CONTROL
N/A B3 00 * * * * *
(No Header)

UNUSED B3 01 * * * * *
Recorder Source B3 02 Indexed String Samples Data * * * * *
Reserved for future use B3 03-1F * * * * *

RECORDER EXTRACTION
N/A B4 00 * * * * *
COLUMN (No Header)

Select Record B4 01 Unsigned Integer 0 Setting -199 199 1 0 * * * * *


Trigger Time B4 02 IEC870 Time & Date Data * * * * *
Active Channels B4 03 Binary Flag Data * * * * *
Channel Types B4 04 Binary Flag Data * * * * *
Channel Offsets B4 05 Courier Number (decimal) Data * * * * *
Channel Scaling B4 06 Courier Number (decimal) Data * * * * *
Channel SkewVal B4 07 Integer Data * * * * *
Channel MinVal B4 08 Integer Data * * * * *
Channel MaxVal B4 09 Integer Data * * * * *
Format B4 0A Unsigned Integer Data * * * * * Record format: 0 = uncompressed, 1 = compressed
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 44

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Upload B4 0B Unsigned Integer Data * * * * *
UNUSED B4 0C-0F
No. Of Samples B4 10 Unsigned Integer Data * * * * *
Trig Position B4 11 Unsigned Integer Data * * * * *
Time Base B4 12 Courier Number (time) Data * * * * *
UNUSED B4 13
Sample Timer B4 14 Unsigned Integer Data * * * * *
UNUSED B4 15-1F
Dist. Channel 1 B4 20 Integer Data * * * * *
Dist. Channel 2 B4 21 Integer Data * * * * *
Dist. Channel 3 B4 22 Integer Data * * * * *
Dist. Channel 4 B4 23 Integer Data * * * * *
Dist. Channel 5 B4 24 Integer Data * * * * *
Dist. Channel 6 B4 25 Integer Data * * * * *
Dist. Channel 7 B4 26 Integer Data * * * * *
Dist. Channel 8 B4 27 Integer Data * * * * *
Dist. Channel 9 B4 28 Integer Data * * * * *
Dist. Channel 10 B4 29 Integer Data * * * * *
Dist. Channel 11 B4 2A Integer Data * * * * *
Dist. Channel 12 B4 2B Integer Data * * * * *
Dist. Channel 13 B4 2C Integer Data * * * * *
UNUSED B4 2D-3D
Dist. Channel 31 B4 3E Binary Flag Data * * * * *
Dist. Channel 32 B4 3F Binary Flag Data * * * * *
3x00800 G1 Data Number of Disturbance Records (0 to 200)
3x00801 G1 Data Oldest Stored Disturbance Record (1 to 65535)
3x00802 G1 Data Number of Registers in Current Page
3x00803 3x00929 G1 Data Disturbance Record Page (0 to 65535)
4x00250 G1 Setting 1 65535 1 2 Select Disturbance Record
Select Disturbance Record File Format (Presently BINARY
4x00251 G1 Setting 0 0 1 2
Format Only)
3x00930 3x00933 G12 Data Timestamp of Selected Record
3x00934 G1 Data Disturbance Recorder Status
Calibration Coefficients N/A B5 * * * * *
Cal Soft Version B5 01 ASCII text 16 chars * * * * *
Cal Date and Time B5 02 IEC Date and time * * * * *
Channel Types B5 03 Repeated Group 16 * Binary Flag 8 bits * * * * *
Cal Coeffs B5 04 Block transfer Repeated Group of UINT32 (4 coeffs voltage channel, 8 coeffs current channel) * * * * *
Comms Diagnostics (Hidden) N/A B6 00 Note: No text in column text * * * * *
Bus Comms Err Count Front B6 01 UINT32 * * * * *
Bus Message Count Front B6 02 UINT32 * * * * *
Protocol Err Count Front B6 03 UINT32 * * * * *
Slave Message Count Front B6 04 UNIT32
Reset front count B6 05 (Reset Menu Cell cmd only) * * * * *
Bus Comms Err Count Rear B6 06 UINT32 * * * * *
Protocol Err Count Rear B6 07 UINT32 * * * * *
Slave Message Count Rear B6 08 UINT32
Busy Count Rear B6 09 UINT32 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 45

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
Reset Rear Count B6 0A (Reset Menu Cell cmd only) * * * * *
PSL DATA B7 00
Grp 1 PSL Ref B7 01 ASCII Text (32 Chars) 3x01000 3x01015 G3 Data * * * * *
Date/Time B7 02 IEC 870 Date & Time 3x01016 3x01019 G12 Data * * * * *
Grp 1 PSL ID B7 03 Unsigned Integer (32 bits) 3x01020 3x01021 G27 Data * * * * *
Grp 2 PSL Ref B7 11 ASCII Text (32 Chars) 3x01022 3x01037 G3 Data * * * * *
Date/Time B7 12 IEC 870 Date & Time 3x01038 3x01041 G12 Data * * * * *
Grp 2 PSL ID B7 13 Unsigned Integer (32 bits) 3x01042 3x01043 G27 Data * * * * *
Grp 3 PSL Ref B7 21 ASCII Text (32 Chars) 3x01044 3x01059 G3 Data * * * * *
Date/Time B7 22 IEC 870 Date & Time 3x01060 3x01063 G12 Data * * * * *
Grp 3 PSL ID B7 23 Unsigned Integer (32 bits) 3x01064 3x01065 G27 Data * * * * *
Grp 4 PSL Ref B7 31 ASCII Text (32 Chars) 3x01066 3x01079 G3 Data * * * * *
Date/Time B7 32 IEC 870 Date & Time 3x01082 3x01085 G12 Data * * * * *
Grp 4 PSL ID B7 33 Unsigned Integer (32 bits) 3x01086 3x01087 G27 Data * * * * *
COMMS SYS DATA N/A BF 00 * * * * *
Dist Record Cntrl Ref BF 01 Menu Cell(2) B300 Data * * * * *
Dist Record Extract Ref BF 02 Menu Cell(2) B400 Data * * * * *
Setting Transfer BF 03 Unsigned Integer Setting * * * * *
Reset Demand BF 04 None (Reset Menu Cell) Data(but supports Reset Menu cell) * * * * *
UNUSED BF 05 * * * * *
Block Xfer Ref BF 06 Menu Cell(2) B200 Data * * * * *
DIAGNOSTICS (hidden) E0 00 * * * * *
Enable Column E0 01 Indexed String G11 0 (No) Setting 0 1 1 2 * * * * *
CPU Load-Instant E0 11 Unsigned Integer (32 bits) Data * * * * *
CPU Load-Average E0 12 Unsigned Integer (32 bits) Data * * * * *
CPU Load-Min E0 13 Unsigned Integer (32 bits) Data * * * * *
CPU Load-Max E0 14 Unsigned Integer (32 bits) Data * * * * *
CPU Load Reset E0 1F Indexed String G11 0 (No) Setting 0 1 1 2 * * * * *
DDB to set: E0 21 Unsigned Integer (32 bits) Setting 0 1022 1 2 * * * * *
DDB to reset: E0 22 Unsigned Integer (32 bits) Setting 0 1022 1 2 * * * * *
DDB to pulse: E0 23 Unsigned Integer (32 bits) Setting 0 1022 1 2 * * * * *
Name Unfitted IO E0 26 Indexed String G11 0 (No) Setting 0 1 1 2 * * * * *
UINT32 - 1 E0 31 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * *
UINT32 - 2 E0 32 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * *
UINT32 - 3 E0 33 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * *
UINT32 - 4 E0 34 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * *
UINT32 - 5 E0 35 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * *
INT32 - 1 E0 41 Signed Integer (32 bits) Data * * * * *
INT32 - 2 E0 42 Signed Integer (32 bits) Data * * * * *
INT32 - 3 E0 43 Signed Integer (32 bits) Data * * * * *
INT32 - 4 E0 44 Signed Integer (32 bits) Data * * * * *
INT32 - 5 E0 45 Signed Integer (32 bits) Data * * * * *
BIN32 - 1 E0 51 Binary Flag (32 bits) Data * * * * *
BIN32 - 2 E0 52 Binary Flag (32 bits) Data * * * * *
BIN32 - 3 E0 53 Binary Flag (32 bits) Data * * * * *
BIN32 - 4 E0 54 Binary Flag (32 bits) Data * * * * *
BIN32 - 5 E0 55 Binary Flag (32 bits) Data * * * * *
FLT32 - 1 E0 61 Courier Number (meters) Data * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 46

Courier Modbus address Modbus Password Model


Menu text UI Data type Strings Default setting Cell type Min Max Step Comment
Col Row Start End datagroup level P341 P342 P343 P344 P345
FLT32 - 2 E0 62 Courier Number (meters) Data * * * * *
FLT32 - 3 E0 63 Courier Number (meters) Data * * * * *
FLT32 - 4 E0 64 Courier Number (meters) Data * * * * *
FLT32 - 5 E0 65 Courier Number (meters) Data * * * * *
ETHERNET STATUS N/A F0 00 Heading * * * * *
Ethernet Status Selector F0 01 Unsigned Integer Setting 0 239 1 1 * * * * *
F0 02
Ethernet Status Number F0 03 Unsigned Integer Data * * * * *
Ethernet Fatal Error F0 04 Unsigned Integer Data * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 47

Data Types

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

G1 1 Register UNSIGNED INTEGER (16 bits) * * * * *


G2 1 Register NUMERIC SETTING (unsigned 16 bit) * * * * *

Used for floating point settings. The setting value is represented as the number of
step increments from the minimum value (see also G35).

Data formatted as per data type G1.


i.e. Setting value = (setting minimum) + ((register value) x (setting step size))
G3 1 Register ASCII TEXT CHARACTERS (2 characters per register) * * * * *
Bit Mask (hex)
0xFF00 First character in high order 8 bits
0x00FF Second character in low order 8 bits
G4 2 Registers PLANT STATUS (32 bits)
Bit Mask (hex) Data formatted as per data type G27
0x00000001 CB1 Open (0 = Off, 1 = On) * * * * *
0x00000002 CB1 Closed (0 = Off, 1 = On) * * * * *
0x00000004 Not Used (0 = Off, 1 = On)
0x00000008 Not Used (0 = Off, 1 = On)
0x00000010 Not Used (0 = Off, 1 = On)
0x00000020 Not Used (0 = Off, 1 = On)
0x00000040 Not Used (0 = Off, 1 = On)
0x00000080 Not Used (0 = Off, 1 = On)
0x00000100 Not Used (0 = Off, 1 = On)
0x00000200 Not Used (0 = Off, 1 = On)
0x00000400 Not Used (0 = Off, 1 = On)
0x00000800 Not Used (0 = Off, 1 = On)
0x00001000 Not Used (0 = Off, 1 = On)
0x00002000 Not Used (0 = Off, 1 = On)
0x00004000 Not Used (0 = Off, 1 = On)
0x00008000 Not Used (0 = Off, 1 = On)
0x00010000 Not Used (0 = Off, 1 = On)
0x00020000
0x00040000 Not Used (0 = Off, 1 = On)
0x00080000 Not Used (0 = Off, 1 = On)
0x00100000 Not Used (0 = Off, 1 = On)
0x00200000 Not Used (0 = Off, 1 = On)
0x00400000 Not Used (0 = Off, 1 = On)
0x00800000 Not Used (0 = Off, 1 = On)
0x01000000 Not Used (0 = Off, 1 = On)
0x02000000 Not Used (0 = Off, 1 = On)
0x04000000 Not Used (0 = Off, 1 = On)
0x08000000 Not Used (0 = Off, 1 = On)
0x10000000 Not Used (0 = Off, 1 = On)
0x20000000 Not Used (0 = Off, 1 = On)
0x40000000 Not Used (0 = Off, 1 = On)
0x80000000 Not Used (0 = Off, 1 = On)
G5 2 Registers CONTROL STATUS (32 bits)
Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Not Used (0 = Off, 1 = On)
0x00000002 Not Used (0 = Off, 1 = On)
0x00000004 Not Used (0 = Off, 1 = On)
0x00000008 Not Used (0 = Off, 1 = On)
0x00000010 Not Used (0 = Off, 1 = On)
0x00000020 Not Used (0 = Off, 1 = On)
0x00000040 Not Used (0 = Off, 1 = On)
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 48

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x00000080 Not Used (0 = Off, 1 = On)


0x00000100 Not Used (0 = Off, 1 = On)
0x00000200 Not Used (0 = Off, 1 = On)
0x00000400 Not Used (0 = Off, 1 = On)
0x00000800 Not Used (0 = Off, 1 = On)
0x00001000 Not Used (0 = Off, 1 = On)
0x00002000 Not Used (0 = Off, 1 = On)
0x00004000 Not Used (0 = Off, 1 = On)
0x00008000 Not Used (0 = Off, 1 = On)
0x00010000 Not Used (0 = Off, 1 = On)
0x00020000 Not Used (0 = Off, 1 = On)
0x00040000 Not Used (0 = Off, 1 = On)
0x00080000 Not Used (0 = Off, 1 = On)
0x00100000 Not Used (0 = Off, 1 = On)
0x00200000 Not Used (0 = Off, 1 = On)
0x00400000 Not Used (0 = Off, 1 = On)
0x00800000 Not Used (0 = Off, 1 = On)
0x01000000 Not Used (0 = Off, 1 = On)
0x02000000 Not Used (0 = Off, 1 = On)
0x04000000 Not Used (0 = Off, 1 = On)
0x08000000 Not Used (0 = Off, 1 = On)
0x10000000 Not Used (0 = Off, 1 = On)
0x20000000 Not Used (0 = Off, 1 = On)
0x40000000 Not Used (0 = Off, 1 = On)
0x80000000 Not Used (0 = Off, 1 = On)
G6 1 Register RECORD CONTROL COMMAND REGISTER * * * * *
Value
0 No Operation
1 Clear Event Records
2 Clear Fault Record
3 Clear Maintenance Records
4 Reset Indications
5 Clear Disturbance Records
G7 1 Register VTS INDICATE/BLOCK * * * * *
Value
0 Blocking
1 Indication
G8 2 Registers LOGIC INPUT STATUS (32 bits)
Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Opto 1 Input State (0=Off, 1=Energized) * * * * *
0x00000002 Opto 2 Input State (0=Off, 1=Energized) * * * * *
0x00000004 Opto 3 Input State (0=Off, 1=Energized) * * * * *
0x00000008 Opto 4 Input State (0=Off, 1=Energized) * * * * *
0x00000010 Opto 5 Input State (0=Off, 1=Energized) * * * * *
0x00000020 Opto 6 Input State (0=Off, 1=Energized) * * * * *
0x00000040 Opto 7 Input State (0=Off, 1=Energized) * * * * *
0x00000080 Opto 8 Input State (0=Off, 1=Energized) * * * * *
0x00000100 Opto 9 Input State (0=Off, 1=Energized) * * * * *
0x00000200 Opto 10 Input State (0=Off, 1=Energized) * * * * *
0x00000400 Opto 11 Input State (0=Off, 1=Energized) * * * * *
0x00000800 Opto 12 Input State (0=Off, 1=Energized) * * * * *
0x00001000 Opto 13 Input State (0=Off, 1=Energized) * * * * *
0x00002000 Opto 14 Input State (0=Off, 1=Energized) * * * * *
0x00004000 Opto 15 Input State (0=Off, 1=Energized) * * * * *
0x00008000 Opto 16 Input State (0=Off, 1=Energized) * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 49

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x00010000 Opto 17 Input State (0=Off, 1=Energized) * * * * *


0x00020000 Opto 18 Input State (0=Off, 1=Energized) * * * * *
0x00040000 Opto 19 Input State (0=Off, 1=Energized) * * * * *
0x00080000 Opto 20 Input State (0=Off, 1=Energized) * * * * *
0x00100000 Opto 21 Input State (0=Off, 1=Energized) * * * * *
0x00200000 Opto 22 Input State (0=Off, 1=Energized) * * * * *
0x00400000 Opto 23 Input State (0=Off, 1=Energized) * * * * *
0x00800000 Opto 24 Input State (0=Off, 1=Energized) * * * * *
0x01000000 Opto 25 Input State (0=Off, 1=Energized) * * *
0x02000000 Opto 26 Input State (0=Off, 1=Energized) * * *
0x04000000 Opto 27 Input State (0=Off, 1=Energized) * * *
0x08000000 Opto 28 Input State (0=Off, 1=Energized) * * *
0x10000000 Opto 29 Input State (0=Off, 1=Energized) * * *
0x20000000 Opto 30 Input State (0=Off, 1=Energized) * * *
0x40000000 Opto 31 Input State (0=Off, 1=Energized) * * *
0x80000000 Opto 32 Input State (0=Off, 1=Energized) * * *
G9 2 Registers RELAY OUTPUT STATUS (32 bits)
Bit Mask (hex) Data formatted as per data type G27
0x00000001 Relay 1 (0=Not Operated, 1=Operated) * * * * *
0x00000002 Relay 2 (0=Not Operated, 1=Operated) * * * * *
0x00000004 Relay 3 (0=Not Operated, 1=Operated) * * * * *
0x00000008 Relay 4 (0=Not Operated, 1=Operated) * * * * *
0x00000010 Relay 5 (0=Not Operated, 1=Operated) * * * * *
0x00000020 Relay 6 (0=Not Operated, 1=Operated) * * * * *
0x00000040 Relay 7 (0=Not Operated, 1=Operated) * * * * *
0x00000080 Relay 8 (0=Not Operated, 1=Operated) * * * * *
0x00000100 Relay 9 (0=Not Operated, 1=Operated) * * * * *
0x00000200 Relay 10 (0=Not Operated, 1=Operated) * * * * *
0x00000400 Relay 11 (0=Not Operated, 1=Operated) * * * * *
0x00000800 Relay 12 (0=Not Operated, 1=Operated) * * * * *
0x00001000 Relay 13 (0=Not Operated, 1=Operated) * * * * *
0x00002000 Relay 14 (0=Not Operated, 1=Operated) * * * * *
0x00004000 Relay 15 (0=Not Operated, 1=Operated) * * * * *
0x00008000 Relay 16 (0=Not Operated, 1=Operated) * * * * *
0x00010000 Relay 17 (0=Not Operated, 1=Operated) * * * * *
0x00020000 Relay 18 (0=Not Operated, 1=Operated) * * * * *
0x00040000 Relay 19 (0=Not Operated, 1=Operated) * * * * *
0x00080000 Relay 20 (0=Not Operated, 1=Operated) * * * * *
0x00100000 Relay 21 (0=Not Operated, 1=Operated) * * * * *
0x00200000 Relay 22 (0=Not Operated, 1=Operated) * * * * *
0x00400000 Relay 23 (0=Not Operated, 1=Operated) * * * * *
0x00800000 Relay 24 (0=Not Operated, 1=Operated) * * * * *
0x01000000 Relay 25 (0=Not Operated, 1=Operated) * * *
0x02000000 Relay 26 (0=Not Operated, 1=Operated) * * *
0x04000000 Relay 27 (0=Not Operated, 1=Operated) * * *
0x08000000 Relay 28 (0=Not Operated, 1=Operated) * * *
0x10000000 Relay 29 (0=Not Operated, 1=Operated) * * *
0x20000000 Relay 30 (0=Not Operated, 1=Operated) * * *
0x40000000 Relay 31 (0=Not Operated, 1=Operated) * * *
0x80000000 Relay 32 (0=Not Operated, 1=Operated) * * *

SIGNED FIXED POINT NUMBER WITH 1 DECIMAL PLACE (16 bits) i.e.
G10 1 Register * * * * *
divide register value by 10 to obtain actual value

G11 1 Register YES/NO * * * * *


Value
0 No
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 50

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

1 Yes
G12 4 Registers TIME AND DATE (MODBUS only) * * * * *

Bit Mask (hex) IEC60870-5-4 "Binary Time 2a" format "Standard" presentation form - see G238

0xFFFF First Register: (format bytes 1 + 2)


-- High Byte: Milli-seconds low byte
-- Low Byte: Milli-seconds high byte
0xBF9F Second Register: (format bytes 3 + 4)
-- High Byte: Validity (mask 0x80) and minutes (mask 0x3F)
-- Low byte: Summertime (mask 0x80) and hours (mask 0x1F)
0xFF0F Third register: (format bytes 5 + 6)
-- High Byte: Day of week (mask 0xE0) and day of month (mask 0x1F)
-- Low Byte: Month of year (mask 0x0F)
0x7F00 Fourth register: (format bytes 7 + "dummy")
-- High Byte: Years of century (mask 0x7F)
-- Low Byte: "dummy" byte (always zero in value)
"Reverse" presentation format - see G238
0x007F First register: (format bytes "dummy" + 7)
-- High Byte: "dummy" byte (always zero in value)
-- Low Byte: Years of century (mask 0x7F)
0x0FFF Second register: (format bytes 6 + 5)
-- High Byte: Month of year (mask 0x0F)
-- Low Byte: Day of week (mask 0xE0) and day of month (mask 0x1F)
0x9FBF Third Register: (format bytes 4 + 3)
-- High byte: Summertime (mask 0x80) and hours (mask 0x1F)
-- Low Byte: Validity (mask 0x80) and minutes (mask 0x3F)
0xFFFF Fourth Register: (format bytes 2 + 1)
-- High Byte: Milli-seconds High byte
-- Low Byte: Milli-seconds Low byte
N.B. High byte transmitted first, followed by low byte, for each register.
G13 1 Register EVENT RECORD TYPE * * * * *
Value
0 Latched alarm active
1 Latched alarm inactive
2 Self reset alarm active
3 Self reset alarm inactive
4 Relay contact event
5 Opto-isolated input event
6 Protection event
7 General event
8 Fault record event
9 Maintenance record event
G14 1 Register I> FUNCTION LINK * * * * *
Bit Mask (hex)
0x0001 I>1 VTS Block
0x0002 I>2 VTS Block
0x0004 I>3 VTS Block
0x0008 I>4 VTS Block
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used
G15 1 Register DISTURBANCE RECORD INDEX STATUS * * * * *
Value
0 No Record
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 51

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

1 Unextracted
2 Extracted
G16 1 Register FAULTED PHASE * * * * *
Bit Mask (hex)
0x0001 Start A
0x0002 Start B
0x0004 Start C
0x0008 Start N
0x0010 Trip A
0x0020 Trip B
0x0040 Trip C
0x0080 Trip N
G17 1 Register IRIG-B STATUS * * * * *
Value
0 Card not fitted
1 Card failed
2 Signal healthy
3 No signal
G18 1 Register RECORD SELECTION COMMAND REGISTER (MODBUS) * * * * *
Bit Mask (hex)
0x0000 No operation
0x0001 Select next event
0x0002 Accept event
0x0004 Select next disturbance record
0x0008 Accept disturbance record
0x0010 Select next disturbance record page
G19 1 Register LANGUAGE * * * * *
Value
0 English
1 Francais
2 Deutsch
3 Espanol Espanol (for P34xxxxxxx0xxx - EN/FR/DE/ES)
3 Russian (for P34xxxxxxx5xxx - EN/FR/DE/RU)
G20 2 Registers PASSWORD (4 characters packed into 32 bits) * * * * *
Bit Mask (hex) Data formatted as per data type G3
0xFF00 First register, first password character
0x00FF First register, second password character
0xFF00 Second register, third password character
0x00FF Second register, fourth password character

NOTE THAT WHEN REGISTERS OF THIS TYPE ARE READ THE SLAVE WILL
ALWAYS INDICATE AN "*" IN EACH CHARACTER POSITION TO PRESERVE THE
PASSWORD SECURITY

G21 1 Register REAR PORT 1 INTERFACE SELECTION * * * * *


Value
0 Copper
1 Fiber Optic
G22 1 Register PASSWORD CONTROL ACCESS LEVEL * * * * *
Value
0 Level 0 - Passwords required for levels 1 & 2
1 Level 1 - Password required for level 2
2 Level 2 - No passwords required
G23 1 Register VOLTAGE CURVE SELECTION * * * * *
Value
0 Disabled
1 DT
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 52

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

2 IDMT

UNSIGNED FIXED POINT NUMBER WITH 3 DECIMAL PLACES (32 bits)


G24 2 Registers * * * * *
Data formatted as per data type G27

i.e. divide 'G27' value by 1000 to obtain actual value


Current 0 - 4,000,000A Resolution 1mA
Voltage 0 - 4MV Resolution 1mV
G25 1 Register UNSIGNED FIXED POINT NUMBER WITH 3 DECIMAL PLACES (16 bits) * * * * *
i.e. divide register value by 1000 to obtain actual value
Time Interval 0.000 - 655.000s Resolution 1ms
Frequency 0.000 - 655.000Hz Resolution 0.001Hz
G26 1 Register MODBUS RELAY STATUS REGISTER * * * * *
Bit Mask (hex)
0x0001 In Service Status (1= In service, 0= Out of service)
0x0002 Minor self test failure (=1, 0 otherwise)
0x0004 New auto-extraction event available (=1, 0 otherwise)

Time Synchronized (=1 after MODBUS time sync. Resets to 0 after 5 minutes unless
0x0008
re-time sync'd. Other time sync. sources do not affect this bit)

0x0010 New auto-extraction disturbance record available (=1, 0 otherwise)


0x0020 Fault (not used, always zero)
0x0040 Trip LED status (1=LED On, 0 = LED Off)
0x0080 Alarm status summary (logical OR of all alarm status bits)
0x0100 Unused
0x0200 Unused
0x0400 Unused
0x0800 Unused
0x1000 Unused
0x2000 Unused
0x4000 Unused
0x8000 Unused
G27 2 Registers UNSIGNED LONG (32 bit) VALUE * * * * *
High order word stored in 1st register
Low order word stored in 2nd register
G28 1 Register SIGNED INTEGER (16 bit) * * * * *
G29 3 Registers INTEGER POWER/ENERGY WITH MULTIPLIER * * * * *
First register Per unit value formatted as a G28
Second & third registers Scalar, formatted as a G27
Overall value = 'G28'x'G27' see Section 3.9 of Chapter 5 of Technical Guide for
details

SIGNED VALUE, 2 DECIMAL PLACES


G30 1 Register * * * * *
i.e. divide register value by 100 to obtain actual value

G31 1 Register ANALOG CHANNEL ASSIGNMENT SELECTOR (generator specific)


Value Value Value Value Value
Unused 0 0 0 0 0
VAN 1 1 1 1 1
VBN 2 2 2 2 2
VCN 3 3 3 3 3
VN1 4 4 4 4 4
IA 5 5
IA-1 5 5 5
IB 6 6
IB-1 6 6 6
IC 7 7
IC-1 7 7 7
IN 8 8 8 8
I Sensitive 8 9 9 9 9
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 53

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

IA-2 10 10 10
IB-2 11 11 11
IC-2 12 12 12
VN2 12 13 13
V64S 14
I64S 15
Frequency 9 10 13 14 16
64R CL Input Raw 10 11 14 15 17
64R R Fault Raw 11 12 15 16 18
64R R Fault 12 13 16 17 19
G32 1 Register DISTURBANCE RECORD DIGITAL CHANNEL ASSIGNMENT SELECTOR * * * * *
Value
0 Not used (i.e. nothing recorded for the channel)
1 onwards See separate G32 DDB Table
G34 1 Register TRIGGER MODE * * * * *
Value
0 Single
1 Extended
G35 2 Registers NUMERIC SETTING (unsigned 32 bit) * * * * *

Used for floating point settings. The setting value is represented as the number of
step increments from the minimum value (see also G2)

Data formatted as per data type G27


i.e. Setting value = (setting minimum) + (('G27' value) x (setting step size))
G36 1 Register REAL NUMBERS * * * * *
Value
0 Polar
1 Rectangular
G37 1 Register ENABLED/DISABLED * * * * *
Value
0 Disabled
1 Enabled
G38c COMMUNICATION BAUD RATE (COURIER) * * * * *
Value
0 9600 bits/s
1 19200 bits/s
2 38400 bits/s
G38m COMMUNICATION BAUD RATE (MODBUS) * * * * *
Value
0 9600 bits/s
1 19200 bits/s
2 38400 bits/s
G38v COMMUNICATION BAUD RATE (IEC60870-5-103) * * * * *
Value
0 9600 bits/s
1 19200 bits/s
G38d COMMUNICATION BAUD RATE (DNP 3.0) * * * * *
Value
0 1200 bits/s
1 2400 bits/s
2 4800 bits/s
3 9600 bits/s
4 19200 bits/s
5 38400 bits/s
G39 1 Register COMMUNICATIONS PARITY * * * * *
Value
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 54

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0 Odd
1 Even
2 None
G43 1 Register IDMT CURVE TYPE (obsolete - see G150-G152) * * * * *
Value
0 Disabled
1 DT
2 IEC S Inverse
3 IEC V Inverse
4 IEC E Inverse
5 UK LT Inverse
6 IEEE M Inverse
7 IEEE V Inverse
8 IEEE E Inverse
9 US Inverse
10 US ST Inverse
G44 1 Register DIRECTION * * * * *
Value
0 Non-Directional
1 Directional Fwd
2 Directional Rev
G45 1 Register VTS BLOCK * * * * *
Value
0 Block
1 Non-Directional
G46 1 Register POLARIZATION *
Value
0 Zero Sequence
1 Neg Sequence
G47 1 Register MEASURING MODE * * * * *
Value
0 Phase-Phase
1 Phase-Neutral
G48 1 Register OPERATION MODE * * * * *
Value
0 Any Phase
1 Three Phase
G49 1 Register VN OR IN INPUT * * * * *
Value
0 Measured
1 Derived
G50 1 Register RTD SELECT * * * *
Bit Mask (hex)
0x0001 RTD Input #1
0x0002 RTD Input #2
0x0004 RTD Input #3
0x0008 RTD Input #4
0x0010 RTD Input #5
0x0020 RTD Input #6
0x0040 RTD Input #7
0x0080 RTD Input #8
0x0100 RTD Input #9
0x0200 RTD Input #10
G52 1 Register DEFAULT DISPLAY * * * * *
Value
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 55

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0 3Ph + N Current
1 3 Ph-neutral Voltage
2 Power
3 Date and Time
4 Description
5 Plant Reference
6 Frequency
7 Access Level
G53 1 Register SELECT FACTORY DEFAULTS * * * * *
Value
0 No Operation
1 All Settings
2 Setting Group 1
3 Setting Group 2
4 Setting Group 3
5 Setting Group 4
G54 1 Register SELECT PRIMARY SECONDARY MEASUREMENTS * * * * *
Value
0 Primary
1 Secondary
G55 1 Register CIRCUIT BREAKER CONTROL *
Value
0 No Operation
1 Trip
2 Close
G56 1 Register PHASE MEASUREMENT REFERENCE * * * * *
Value
0 VA
1 VB
2 VC
3 IA
4 IB
5 IC
G57 1 Register DATA TRANSFER DOMAIN * * * * *
Value
0 PSL Settings
1 PSL Configuration
G58 1 Register SEF/REF SELECTION
Value
0 SEF * * * * *
1 SEF cos(PHI) * * * * *
2 SEF sin(PHI) * * * * *
3 Wattmetric * * * * *
4 Hi Z REF * * * * *
5 Lo Z REF * * * *
6 Lo Z REF+SEF * * * *
7 Lo Z REF+Wattmet * * * *
G59 1 Register BATTERY STATUS * * * * *
Value
0 Dead
1 Healthy
G60 1 Register TIME DELAY SELECTION * * * * *
Value
0 DT
1 Inverse
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 56

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

G61 1 Register ACTIVE GROUP CONTROL * * * * *


Value
0 Select via Menu
1 Select via PSL
G62 1 Register SAVE AS * * * * *
Value
0 No Operation
1 Save
2 Abort
G63 1 Register IN> FUNCTION LINK
Bit Mask (hex)
0x0001 IN>1 VTS Block *
0x0002 IN>2 VTS Block *
0x0004 IN>3 VTS Block *
0x0008 IN>4 VTS Block *
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used
G64 1 Register ISEF> FUNC LINK
Bit Mask (hex)
0x0001 ISEF>1 VTS Block * * * * *
0x0002 ISEF>2 VTS Block *
0x0004 ISEF>3 VTS Block *
0x0008 ISEF>4 VTS Block *
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used
G65 1 Register F< FUNCTION LINK * * * * *
Bit Mask (hex)
0x0001 F<1 Poledead Blk
0x0002 F<2 Poledead Blk
0x0004 F<3 Poledead Blk
0x0008 F<4 Poledead Blk
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used
G66 1 Register DISTURBANCE RECORDER DIGITAL CHANNEL TRIGGER * * * * *
Value
0 No Trigger
1 Trigger L/H
2 Trigger H/L
G67 1 Register THERMAL OVERLOAD * * * * *
Value
0 Single
1 Dual
G68 1 Register CB FAIL RESET OPTIONS * * * * *
Value
0 I< Only
1 CB Open & I<
2 Prot Reset & I<
G69 1 Register VTS RESET MODE * * * * *
Value
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 57

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0 Manual
1 Auto
G71 1 Register PROTOCOL * * * * *
Value
0 Courier
1 IEC870-5-103
2 MODBUS
3 DNP 3.0
G76 1 Register TRANSFER MODE * * * * *
Value
0 Prepare Rx
1 Complete Rx
2 Prepare Tx
3 Complete Tx
4 Rx Prepared
5 Tx Prepared
6 OK
7 Error
G79 1 Register CUSTOM SETTINGS * * * * *
Value
0 Disabled
1 Basic
2 Complete
G80 1 Register VISIBLE/INVISIBLE * * * * *
Value
0 Invisible
1 Visible
G81 1 Register RESET LOCKOUT BY * * * * *
Value
0 User Interface
1 CB Close
G84 2 Registers STARTED ELEMENTS - 1 (32 bits)

(For fault record use only. The associated MODBUS registers cannot be
accessed unless a fault record is selected)

Bit Mask (hex) Data formatted as per data type G27


0x00000001 General Start * * * * *
0x00000002 Start Power1 * * * * *
0x00000004 Start Power2 * * * * *
0x00000008 Start FFail1 * * * *
0x00000010 Start FFail2 * * * *
0x00000020 Start V Dep O/C * * * *
0x00000040 Start I>1 * * * * *
0x00000080 Start I>2 * * * * *
0x00000100 Start I>3 * * * * *
0x00000200 Start I>4 * * * * *
0x00000400 Start IN>1 * * * * *
0x00000800 Start IN>2 * * * * *
0x00001000 Start IN>3 *
0x00002000 Start IN>4 *
0x00004000 Start ISEF>1 * * * * *
0x00008000 Start ISEF>2 *
0x00010000 Start ISEF>3 *
0x00020000 Start ISEF>4 *
0x00040000 Start NVD VN>1 * * * * *
0x00080000 Start NVD VN>2 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 58

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x00100000 Start 100% StEF3H * * *


0x00200000 Start Sen Power1 * * * * *
0x00400000 Start Sen Power2 * * * * *
0x00800000 Start z PSlip Z1 * * *
0x01000000 Start z PSlip Z2 * * *
0x02000000 Start Z<1 * * * *
0x04000000 Start Z<2 * * * *
0x08000000
0x10000000
0x20000000
0x40000000
0x80000000
G85 2 Registers TRIPPED ELEMENTS - 1 (32 bits)

(For fault record use only. The associated MODBUS registers cannot be
accessed unless a fault record is selected)

Bit Mask (hex) Data formatted as per data type G27


0x00000001 Any Trip * * * * *
0x00000002 Trip Gen Diff * * *
0x00000004 Trip Power1 * * * * *
0x00000008 Trip Power2 * * * * *
0x00000010 Trip FFail1 * * * *
0x00000020 Trip FFail2 * * * *
0x00000040 Trip NPS Thermal * * * *
0x00000080 Trip V Dep O/C * * * *
0x00000100 Trip I>1 * * * * *
0x00000200 Trip I>2 * * * * *
0x00000400 Trip I>3 * * * * *
0x00000800 Trip I>4 * * * * *
0x00001000 Trip IN>1 * * * * *
0x00002000 Trip IN>2 * * * * *
0x00004000 Trip IN>3 *
0x00008000 Trip IN>4 *
0x00010000 Trip ISEF>1 * * * * *
0x00020000 Trip ISEF>2 *
0x00040000 Trip ISEF>3 *
0x00080000 Trip ISEF>4 *
0x00100000 Trip IREF> * * * * *
0x00200000 Trip NVD VN>1 * * * * *
0x00400000 Trip NVD VN>2 * * * * *
0x00800000 Trip 100% StEF3H * * *
0x01000000 Trip Dead Mach * * *
0x02000000 Trip Sen Power1 * * * * *
0x04000000 Trip Sen Power2 * * * * *
0x08000000 Trip z PSlip Z1 * * *
0x10000000 Trip z PSlip Z2 * * *
0x20000000 Trip Thermal O/L * * * * *
0x40000000 Trip Z<1 * * * *
0x80000000 Trip Z<2 * * * *
G86 2 Registers TRIPPED ELEMENTS - 2 (32 bits)

(For fault record use only. The associated MODBUS registers cannot be
accessed unless a fault record is selected)

Bit Mask (hex) Data formatted as per data type G27


0x00000001 Trip V<1 * * * * *
0x00000002 Trip V<2 * * * * *
0x00000004 Trip V< A/AB * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 59

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x00000008 Trip V< B/BC * * * * *


0x00000010 Trip V< C/CA * * * * *
0x00000020 Trip V>1 * * * * *
0x00000040 Trip V>2 * * * * *
0x00000080 Trip V> A/AB * * * * *
0x00000100 Trip V> B/BC * * * * *
0x00000200 Trip V> C/CA * * * * *
0x00000400 Trip F<1 * * * * *
0x00000800 Trip F<2 * * * * *
0x00001000 Trip F<3 * * * * *
0x00002000 Trip F<4 * * * * *
0x00004000 Trip F>1 * * * * *
0x00008000 Trip F>2 * * * * *
0x00010000 Trip V/Hz * * * *
0x00010000 Trip V Shift *
0x00020000 Trip df/dt *
0x00040000 Trip RTD 1 * * * *
0x00080000 Trip RTD 2 * * * *
0x00100000 Trip RTD 3 * * * *
0x00200000 Trip RTD 4 * * * *
0x00400000 Trip RTD 5 * * * *
0x00800000 Trip RTD 6 * * * *
0x01000000 Trip RTD 7 * * * *
0x02000000 Trip RTD 8 * * * *
0x04000000 Trip RTD 9 * * * *
0x08000000 Trip RTD 10 * * * *
0x10000000 Trip CL Input 1 * * * * *
0x20000000 Trip CL Input 2 * * * * *
0x40000000 Trip CL Input 3 * * * * *
0x80000000 Trip CL Input 4 * * * * *
G87 2 Registers FAULT ALARMS (32 bit)

(For fault record use only. The associated MODBUS registers cannot be
accessed unless a fault record is selected)

Bit Mask (hex) Data formatted as per data type G27


0x00000001 CB Fail 1 * * * * *
0x00000002 CB Fail 2 * * * * *
0x00000004 VTS * * * * *
0x00000008 CTS-1 * * * * *
0x00000010 Alarm FFail * * * *
0x00000020 Alm NPS Thermal * * * *
0x00000040 Alarm V/Hz * * * *
0x00000080 Alarm RTD 1 * * * *
0x00000100 Alarm RTD 2 * * * *
0x00000200 Alarm RTD 3 * * * *
0x00000400 Alarm RTD 4 * * * *
0x00000800 Alarm RTD 5 * * * *
0x00001000 Alarm RTD 6 * * * *
0x00002000 Alarm RTD 7 * * * *
0x00004000 Alarm RTD 8 * * * *
0x00008000 Alarm RTD 9 * * * *
0x00010000 Alarm RTD 10 * * * *
0x00020000 Alarm Thermal * * * * *
0x00040000 Alarm CL Input 1 * * * * *
0x00080000 Alarm CL Input 2 * * * * *
0x00100000 Alarm CL Input 3 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 60

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x00200000 Alarm CL Input 4 * * * * *


0x00400000 CTS-2 * * *
0x00800000 64S R<1 Alarm *
0x01000000 64S Fail Alarm *
0x02000000 64R R<1 Alarm * * * *
0x04000000 64R CL I/P Fail * * * *
0x08000000
0x10000000
0x20000000
0x40000000
0x80000000
G88 1 Register ALARMS * * * * *
Value
0 Alarm Disabled
1 Alarm Enabled
G90 1 Register GROUP SELECTION * * * * *
Value
0 Group 1
1 Group 2
2 Group 3
3 Group 4
G93 1 Register OUTPUT CONTACT COMMISSION TEST * * * * *
Value
0 No Operation
1 Apply Test
2 Remove Test
G94 1 Register COMMISSION TEST * * * * *
Value
0 No Operation
1 Apply Test
G95 1 Register SYSTEM FN LINKS * * * * *
Bit Mask (hex)
0x0001 Trip LED self reset (1 = enable self reset)
0x0002 Not Used
0x0004 Not Used
0x0008 Not used
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used
G96 2 Registers ALARM STATUS (alarms 1 - 32) (32 bits)
Bit Mask (hex) Data formatted as per data type G27
0x00000001 Not Used * * * * *
0x00000002 Not Used * * * * *
0x00000004 SG-opto Invalid * * * * *
0x00000008 Prot'n Disabled * * * * *
0x00000010 VT Fail Alarm * * * * *
0x00000020 CTS Fail Alarm * *
0x00000020 CTS-1 Fail Alarm * * *
0x00000040 CB Fail * * * * *
0x00000080 I^ Maint Alarm * * * * *
0x00000100 I^ Maint Lockout * * * * *
0x00000200 CB OPs Maint * * * * *
0x00000400 CB OPs Lock * * * * *
0x00000800 CB Time Maint * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 61

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x00001000 CB Time Lockout * * * * *


0x00002000 Fault Freq Lock * * * * *
0x00004000 CB Status Alarm * * * * *
0x00008000 CB Trip Fail *
0x00010000 CB Close Fail *
0x00020000 Man CB Unhealthy *
0x00040000 F out of Range *
0x00040000 NPS Alarm * * * *
0x00080000 Thermal Alarm * * * * *
0x00100000 V/Hz Alarm * * * *
0x00200000 Field Fail Alarm * * * *
0x00400000 RTD Thermal Alm * * * *
0x00800000 RTD Open Cct * * * *
0x01000000 RTD short Cct * * * *
0x02000000 RTD Data Error * * * *
0x04000000 RTD Board Fail * * * *
0x08000000 Freq Prot Alm * * * * *
0x10000000 Voltage Prot Alm * * * * *
0x20000000 CTS-2 Fail Alarm * * *
0x40000000 64S R<1 Alarm *
0x80000000 64S Fail Alarm *
G98 1 Register COPY TO * * * * *
Value
0 No Operation
1 Group 1
2 Group 2
3 Group 3
4 Group 4
G99 1 Register CB CONTROL *
Value
0 Disabled
1 Local
2 Remote
3 Local+Remote
4 Opto
5 Opto+local
6 Opto+Remote
7 Opto+Rem+local
G100 Not used
G101 1 Register GEN DIFF FUNCTION SELECT * * *
Value
0 Disabled
1 Percentage Bias
2 High Impedance
3 Interturn
G102 1 Register POWER FUNCTION SELECT * * * * *
Value
0 Disabled
1 Reverse
2 Low Forward
3 Over
G103 1 Register SYSTEM BACK-UP FUNCTION SELECT * * * *
Value
0 Disabled
1 Underimpedance
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 62

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

2 Volt Controlled
3 Volt Restrained
G104 1 Register SYSTEM BACK-UP VECTOR ROTATION * * * *
Value
0 None
1 Delta-Star
G105 1 Register DEFINITE TIME OVERCURRENT SELECTION * * * * *
Value
0 Disabled
1 DT
G107 2 Registers STARTED ELEMENTS - 2 (32 bits)

(For fault record use only. The associated MODBUS registers cannot be
accessed unless a fault record is selected)

Bit Mask (hex) Data formatted as per data type G27


0x00000001 Start V<1 * * * * *
0x00000002 Start V<2 * * * * *
0x00000004 Start V< A/AB * * * * *
0x00000008 Start V< B/BC * * * * *
0x00000010 Start V< C/CA * * * * *
0x00000020 Start V>1 * * * * *
0x00000040 Start V>2 * * * * *
0x00000080 Start V> A/AB * * * * *
0x00000100 Start V> B/BC * * * * *
0x00000200 Start V> C/CA * * * * *
0x00000400 Start F<1 * * * * *
0x00000800 Start F<2 * * * * *
0x00001000 Start F<3 * * * * *
0x00002000 Start F<4 * * * * *
0x00004000 Start F>1 * * * * *
0x00008000 Start F>2 * * * * *
0x00010000 Start V/Hz>1 * * * *
0x00020000 Start df/dt *
0x00040000 Start CLI1 Alarm * * * * *
0x00080000 Start CLI2 Alarm * * * * *
0x00100000 Start CLI3 Alarm * * * * *
0x00200000 Start CLI4 Alarm * * * * *
0x00400000 Start CLI1 Trip * * * * *
0x00800000 Start CLI2 Trip * * * * *
0x01000000 Start CLI3 Trip * * * * *
0x02000000 Start CLI4 Trip * * * * *
0x04000000
0x08000000
0x10000000
0x20000000
0x40000000
0x80000000
G108 1 Register RTD OPEN CIRCUIT FLAGS * * * *
Bit Mask (hex)
0x0001 RTD 1 label
0x0002 RTD 2 label
0x0004 RTD 3 label
0x0008 RTD 4 label
0x0010 RTD 5 label
0x0020 RTD 6 label
0x0040 RTD 7 label
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 63

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x0080 RTD 8 label


0x0100 RTD 9 label
0x0200 RTD 10 label
G109 1 Register RTD SHORT CIRCUIT FLAGS * * * *
Bit Mask (hex)
0x0001 RTD 1 label
0x0002 RTD 2 label
0x0004 RTD 3 label
0x0008 RTD 4 label
0x0010 RTD 5 label
0x0020 RTD 6 label
0x0040 RTD 7 label
0x0080 RTD 8 label
0x0100 RTD 9 label
0x0200 RTD 10 label
G110 1 Register RTD DATA ERROR * * * *
Bit Mask (hex)
0x0001 RTD 1 label
0x0002 RTD 2 label
0x0004 RTD 3 label
0x0008 RTD 4 label
0x0010 RTD 5 label
0x0020 RTD 6 label
0x0040 RTD 7 label
0x0080 RTD 8 label
0x0100 RTD 9 label
0x0200 RTD 10 label
G111 1 Register SYSTEM BACK-UP V DEP OC IDMT CURVE TYPE * * * *
Value
0 DT (DT)
1 IEC S Inverse (TMS)
2 IEC V Inverse (TMS)
3 IEC E Inverse (TMS)
4 UK LT Inverse (TMS)
5 Rectifier (TMS)
6 RI (K)
7 IEEE M Inverse (TD)
8 IEEE V Inverse (TD)
9 IEEE E Inverse (TD)
10 US Inverse (TD)
11 US ST Inverse (TD)
G112 1 Register 100% STATOR EARTH FAULT STATUS * * *
Value
0 Disabled
1 VN3H< Enabled
2 VN3H> Enabled
G113 1 Register POLE SLIPPING OPERATING MODE * * *
Value
0 Generating
1 Motoring
2 Both
G114 1 Register SEF/REF/SPOWER SELECTION * * * * *
Value
0 Disabled
1 SEF/REF
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 64

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

2 Sensitive Power
G115 1 Register POWER PROTECTION OPERATING MODE * * * * *
Value
0 Generating
1 Motoring
G116 1 Register CB FAIL PHASE UNDERCURRENT CURRENT INPUTS * * * * *
Value
0 IA-1 IB-1 IC-1
1 IA-2 IB-2 IC-2
G118 1 Register CB CONTROL LOGIC INPUT ASSIGNMENTS * * * * *
Value
0 None
1 52A
2 52B
3 Both 52A and 52B
G119 1 Register TEST MODE * * * * *
Value
0 Disabled
1 Test Mode
2 Blocked
G125 2 Registers IEEE FLOATING POINT FORMAT (short float; 32 bits) * * * * *
Bit 31 = sign
Bits 30-23 = e7 - e0
Implicit 1
Bits 22-0 = f22 - f0
(32 bit value formatted as per data type G27)
G128 2 Registers ALARM STATUS (alarms 33 - 64) (32 bits) * * * * *
Bit Mask (hex) Data formatted as per data type G27
0x00000001 CL Card I/P Fail * * * * *
0x00000002 CL Card O/P Fail * * * * *
0x00000004 CL Input 1 Alarm * * * * *
0x00000008 CL Input 2 Alarm * * * * *
0x00000010 CL Input 3 Alarm * * * * *
0x00000020 CL Input 4 Alarm * * * * *
0x00000040 CLI1 I< Fail Alm * * * * *
0x00000080 CLI2 I< Fail Alm * * * * *
0x00000100 CLI3 I< Fail Alm * * * * *
0x00000200 CLI4 I< Fail Alm * * * * *
0x00000400 64R R<1 Alarm * * * *
0x00000800 64R CL I/P Fail * * * *
0x00001000 Not Used
0x00002000 Not Used
0x00004000 Not Used
0x00008000 Not Used
0x00010000 MR User Alarm 16 * * * * *
0x00020000 MR User Alarm 15 * * * * *
0x00040000 MR User Alarm 14 * * * * *
0x00080000 MR User Alarm 13 * * * * *
0x00100000 MR User Alarm 12 * * * * *
0x00200000 MR User Alarm 11 * * * * *
0x00400000 MR User Alarm 10 * * * * *
0x00800000 MR User Alarm 9 * * * * *
0x01000000 MR User Alarm 8 * * * * *
0x02000000 MR User Alarm 7 * * * * *
0x04000000 MR User Alarm 6 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 65

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x08000000 MR User Alarm 5 * * * * *


0x10000000 SR User Alarm 4 * * * * *
0x20000000 SR User Alarm 3 * * * * *
0x40000000 SR User Alarm 2 * * * * *
0x80000000 SR User Alarm 1 * * * * *
G129 2 Registers STARTED ELEMENTS - 3 (32 bits) * * * * *

(For fault record use only. The associated MODBUS registers cannot be
accessed unless a fault record is selected)

Bit Mask (hex) Data formatted as per data type G27


0x00000001 Start NVD VN>3 * * * * *
0x00000002 Start NVD VN>4 * * * * *
0x00000004 Start NVD VN>5 * *
0x00000008 Start NVD VN>6 * *
0x00000010 Start S2>1 * * * *
0x00000020 Start Freq Band1 * * * *
0x00000040 Start Freq Band2 * * * *
0x00000080 Start Freq Band3 * * * *
0x00000100 Start Freq Band4 * * * *
0x00000200 Start Freq Band5 * * * *
0x00000400 Start Freq Band6 * * * *
0x00000800 Start I2>1 * * * * *
0x00001000 Start I2>2 * * * * *
0x00002000 Start I2>3 * * * * *
0x00004000 Start I2>4 * * * * *
0x00008000 Start V2>1 * * * * *
0x00010000 Start V/Hz>2 * * * *
0x00020000 Start V/Hz>3 * * * *
0x00040000 Start V/Hz>4 * * * *
0x00080000 Start 64S I>1 *
0x00100000 Start64S R<1 Alm *
0x00200000 Start 64S R<2 *
0x00400000 Start64R R<1 Alm * * * *
0x00800000 Start 64R R<2 * * * *
0x01000000
0x02000000
0x04000000
0x08000000
0x10000000
0x20000000
0x40000000
0x80000000
G130 2 Registers TRIPPED ELEMENTS - 3 (32 bits) * * * * *

(For fault record use only. The associated MODBUS registers cannot be
accessed unless a fault record is selected)

Bit Mask (hex) Data formatted as per data type G27


0x00000001 Trip NVD VN>3
0x00000002 Trip NVD VN>4 * * * * *
0x00000004 Trip NVD VN>5 * * * * *
0x00000008 Trip NVD VN>6 * *
0x00000010 Trip S2>1 * *
0x00000020 Trip Freq Band1 * * * *
0x00000040 Trip Freq Band2 * * * *
0x00000080 Trip Freq Band3 * * * *
0x00000100 Trip Freq Band4 * * * *
0x00000200 Trip Freq Band5 * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 66

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x00000400 Trip Freq Band6 * * * *


0x00000800 Trip I2>1 * * * * *
0x00001000 Trip I2>2 * * * * *
0x00002000 Trip I2>3 * * * * *
0x00004000 Trip I2>4 * * * * *
0x00008000 Trip V2>1 * * * * *
0x00010000 Trip V/Hz>2 * * * *
0x00020000 Trip V/Hz>3 * * * *
0x00040000 Trip V/Hz>4 * * * *
0x00080000 Trip 64S I>1 *
0x00100000 Trip 64S R<2 *
0x00200000 Trip 64R R<2 * * * *
0x00400000
0x00800000
0x01000000
0x02000000
0x04000000
0x08000000
0x10000000
0x20000000
0x40000000
0x80000000
G150 1 Register POC IDMT CURVE TYPE * * * * *
Value
0 Disabled
1 DT (DT)
2 IEC S Inverse (TMS)
3 IEC V Inverse (TMS)
4 IEC E Inverse (TMS)
5 UK LT Inverse (TMS)
6 Rectifier (TMS)
7 RI (K)
8 IEEE M Inverse (TD)
9 IEEE V Inverse (TD)
10 IEEE E Inverse (TD)
11 US Inverse (TD)
12 US ST Inverse (TD)
G151 1 Register EF IDMT CURVE TYPE * * * * *
Value
0 Disabled
1 DT (DT)
2 IEC S Inverse (TMS)
3 IEC V Inverse (TMS)
4 IEC E Inverse (TMS)
5 UK LT Inverse (TMS)
6 RI (K)
7 IEEE M Inverse (TD)
8 IEEE V Inverse (TD)
9 IEEE E Inverse (TD)
10 US Inverse (TD)
11 US ST Inverse (TD)
12 IDG
G152 1 Register SEF IDMT CURVE TYPE * * * * *
Value
0 Disabled
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 67

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

1 DT (DT)
2 IEC S Inverse (TMS)
3 IEC V Inverse (TMS)
4 IEC E Inverse (TMS)
5 UK LT Inverse (TMS)
6 IEEE M Inverse (TD)
7 IEEE V Inverse (TD)
8 IEEE E Inverse (TD)
9 US Inverse (TD)
10 US ST Inverse (TD)
11 IDG
G153 1 Register CLIO INPUT RANGE * * * * *
Value
0 0 - 1mA
1 0 - 10mA
2 0 - 20mA
3 4 - 20mA
G154 1 Register CLIO TRIP/ALARM OPERATING MODE * * * * *
Value
0 Under
1 Over
G155 1 Register CLIO OUTPUT MEASUREMENT
Value Value Value Value Value
IA Magnitude 0 0 0 0 0
IB Magnitude 1 1 1 1 1
IC Magnitude 2 2 2 2 2
IN Measured Mag 3 3 3 3
IN Derived Mag 3
I Sen Magnitude 4 4 4 4 4
I1 Magnitude 5 5 5 5 5
I2 Magnitude 6 6 6 6 6
I0 Magnitude 7 7 7 7 7
IA RMS 8 8 8 8 8
IB RMS 9 9 9 9 9
IC RMS 10 10 10 10 10
VAB Magnitude 11 11 11 11 11
VBC Magnitude 12 12 12 12 12
VCA Magnitude 13 13 13 13 13
VAN Magnitude 14 14 14 14 14
VBN Magnitude 15 15 15 15 15
VCN Magnitude 16 16 16 16 16
VN1 Magnitude 17 17 17 17 17
VN Derived Mag 18 18 18 18 18
V1 Magnitude 19 19 19 19 19
V2 Magnitude 20 20 20 20 20
V0 Magnitude 21 21 21 21 21
VAN RMS 22 22 22 22 22
VBN RMS 23 23 23 23 23
VCN RMS 24 24 24 24 24
Frequency 25 25 25 25 25
3 Phase Watts 26 26 26 26 26
A Phase Watts 27 27 27 27 27
B Phase Watts 28 28 28 28 28
C Phase Watts 29 29 29 29 29
3 Phase Vars 30 30 30 30 30
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 68

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

A Phase Vars 31 31 31 31 31
B Phase Vars 32 32 32 32 32
C Phase Vars 33 33 33 33 33
3 Phase VA 34 34 34 34 34
A Phase VA 35 35 35 35 35
B Phase VA 36 36 36 36 36
C Phase VA 37 37 37 37 37
3Ph Power Factor 38 38 38 38 38
APh Power Factor 39 39 39 39 39
BPh Power Factor 40 40 40 40 40
CPh Power Factor 41 41 41 41 41
3Ph W Fix Demand 42 42 42 42 42
3Ph Vars Fix Dem 43 43 43 43 43
IA Fixed Demand 44 44 44 44 44
IB Fixed Demand 45 45 45 45 45
IC Fixed Demand 46 46 46 46 46
3 Ph W Roll Dem 47 47 47 47 47
3Ph Vars RollDem 48 48 48 48 48
IA Roll Demand 49 49 49 49 49
IB Roll Demand 50 50 50 50 50
IC Roll Demand 51 51 51 51 51
3Ph W Peak Dem 52 52 52 52 52
3Ph Var Peak Dem 53 53 53 53 53
IA Peak Demand 54 54 54 54 54
IB Peak Demand 55 55 55 55 55
IC Peak Demand 56 56 56 56 56
VN 3rd Harmonic 57 57 57
NPS Thermal 57 58 58 58
Thermal Overload 57 58 59 59 59
RTD 1 59 60 60 60
RTD 2 60 61 61 61
RTD 3 61 62 62 62
RTD 4 62 63 63 63
RTD 5 63 64 64 64
RTD 6 64 65 65 65
RTD 7 65 66 66 66
RTD 8 66 67 67 67
RTD 9 67 68 68 68
RTD 10 68 69 69 69
CL Input 1 58 69 70 70 70
CL Input 2 59 70 71 71 71
CL Input 3 60 71 72 72 72
CL Input 4 61 72 73 73 73
IN Derived Mag 73
IN-1 Derived Mag 74 74 74
IN-2 Derived Mag 75 75 75
VN2 Magnitude 76 76
Volts/Hz 74 76 77 77
G158 1 Register I2> FUNCTION LINK * * * * *
Bit Mask (hex)
0x0001 I2>1 VTS Block
0x0002 I2>2 VTS Block
0x0004 I2>3 VTS Block
0x0008 I2>4 VTS Block
0x0010 Not Used
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 69

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x0020 Not Used


0x0040 Not Used
0x0080 Not Used
G159 1 Register VN INPUT SELECTION * * * * *
Value
0 Derived * * * * *
1 VN1 * * * * *
2 VN2 * *
G160 1 Register V/Hz CURVE SELECTION * * * *
Value
0 DT
1 IDMT
G161 1 Register NVD (RESIDUAL OV) CURVE SELECTION * * * * *
Value
0 DT
1 IDMT
G163 1 Register PHASE SEQUENCE * * * * *
Value
0 Standard ABC
1 Reverse ACB
G164 1 Register CT/VT 3-PHASE PHASE-REVERSAL SWAP * * * * *
Value
0 No Swap
1 A-B Swapped
2 B-C Swapped
3 C-A Swapped
G166 1 Register CURRENT LOOP SELECTION * * * *
Value
0 Current Loop CL1
1 Current Loop CL2
2 Current Loop CL3
3 Current Loop CL4
G168 1 Register INJECTION FREQUENCY * * * *
Value
0 0.25 Hz
1 0.5 Hz
2 1.0 Hz
G200 1 Register GLOBAL OPTO NOMINAL VOLTAGE SELECTION * * * * *
Value
0 24 - 27V
1 30 - 34V
2 48 - 54V
3 110 - 125V
4 220 - 250V
5 Custom
G201 1 Register SINGLE OPTO NOMINAL VOLTAGE SELECTION * * * * *
Value
0 24 - 27V
1 30 - 34V
2 48 - 54V
3 110 - 125V
4 220 - 250V
G202 2 Registers CONTROL INPUT STATUS (32 bits) * * * * *
Bit Mask (hex) Data formatted as per data type G27
0x00000001 Control Input 1 (0 = Reset, 1 = Set)
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 70

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x00000002 Control Input 2 (0 = Reset, 1 = Set)


0x00000004 Control Input 3 (0 = Reset, 1 = Set)
0x00000008 Control Input 4 (0 = Reset, 1 = Set)
0x00000010 Control Input 5 (0 = Reset, 1 = Set)
0x00000020 Control Input 6 (0 = Reset, 1 = Set)
0x00000040 Control Input 7 (0 = Reset, 1 = Set)
0x00000080 Control Input 8 (0 = Reset, 1 = Set)
0x00000100 Control Input 9 (0 = Reset, 1 = Set)
0x00000200 Control Input 10 (0 = Reset, 1 = Set)
0x00000400 Control Input 11 (0 = Reset, 1 = Set)
0x00000800 Control Input 12 (0 = Reset, 1 = Set)
0x00001000 Control Input 13 (0 = Reset, 1 = Set)
0x00002000 Control Input 14 (0 = Reset, 1 = Set)
0x00004000 Control Input 15 (0 = Reset, 1 = Set)
0x00008000 Control Input 16 (0 = Reset, 1 = Set)
0x00010000 Control Input 17 (0 = Reset, 1 = Set)
0x00020000 Control Input 18 (0 = Reset, 1 = Set)
0x00040000 Control Input 19 (0 = Reset, 1 = Set)
0x00080000 Control Input 20 (0 = Reset, 1 = Set)
0x00100000 Control Input 21 (0 = Reset, 1 = Set)
0x00200000 Control Input 22 (0 = Reset, 1 = Set)
0x00400000 Control Input 23 (0 = Reset, 1 = Set)
0x00800000 Control Input 24 (0 = Reset, 1 = Set)
0x01000000 Control Input 25 (0 = Reset, 1 = Set)
0x02000000 Control Input 26 (0 = Reset, 1 = Set)
0x04000000 Control Input 27 (0 = Reset, 1 = Set)
0x08000000 Control Input 28 (0 = Reset, 1 = Set)
0x10000000 Control Input 29 (0 = Reset, 1 = Set)
0x20000000 Control Input 30 (0 = Reset, 1 = Set)
0x40000000 Control Input 31 (0 = Reset, 1 = Set)
0x80000000 Control Input 32 (0 = Reset, 1 = Set)
G203 1 Register VIRTUAL INPUT * * * * *
Value
0 No Operation
1 Set
2 Reset
G204 1 Register REAR COMMS CARD STATUS * * * * *
Value
0 Unsupported
1 Card Not Fitted
2 EIA232 OK
3 EIA485 OK
4 K-Bus OK
G205 1 Register SECOND REAR COMMUNICATIONS PORT CONFIGURATION (model option) * * * * *
Value
0 EIA232 (RS232)
1 EIA485 (RS485)
2 K-Bus
G206 1 Register COMMS MODE (IEC60870-5-2) * * * * *
Value
0 IEC60870 FT1.2
1 10-bit no parity
G207 PORT CONFIG (FIRST REAR PORT) * * * * *
Value
0 K-Bus
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 71

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

1 EIA485 (RS485)
G208 FIRST REAR PORT (RP1) STATUS * * * * *
Value
0 K-Bus OK
1 EIA485 OK
2 Fiber Optic OK
G210 1 Register CS103 BLOCKING * * * * *
Value
0 Disabled
1 Monitor Blocking
2 Command Blocking
G221 GOOSE STARTUP MODE * * * * *
0 Promiscuous
1 Broadcast
G222 AE QUALIFIER SELECTOR (Reserved) * * * * *
0 Not Used
1 Used
G223 IED STATISTICS RESET * * * * *
0 None
1 Local IED
2 Viewed IED
2 All Enrolled
3 All Enrolled + Local
G224 ETHERNET LOOPBACK MODE (Reserved) * * * * *
0 Loopback Off
1 Internal Loop
2 External Loop
G225 SOFTWARE RELOAD MODE * * * * *
0 No Action
1 Reload Software
G226 LINK STATUS REPORT MODE * * * * *
0 Alarm
1 Event
2 None
G227 GOOSE VIP STATUS * * * * *
0 GOOSE VIP 1
1 GOOSE VIP 2
2 GOOSE VIP 3
3 GOOSE VIP 4
4 GOOSE VIP 5
5 GOOSE VIP 6
6 GOOSE VIP 7
7 GOOSE VIP 8
8 GOOSE VIP 9
9 GOOSE VIP 10
10 GOOSE VIP 11
11 GOOSE VIP 12
12 GOOSE VIP 13
13 GOOSE VIP 14
14 GOOSE VIP 15
15 GOOSE VIP 16
16 GOOSE VIP 17
17 GOOSE VIP 18
18 GOOSE VIP 19
19 GOOSE VIP 20
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 72

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

20 GOOSE VIP 21
21 GOOSE VIP 22
22 GOOSE VIP 23
23 GOOSE VIP 24
24 GOOSE VIP 25
25 GOOSE VIP 26
26 GOOSE VIP 27
27 GOOSE VIP 28
28 GOOSE VIP 29
29 GOOSE VIP 30
30 GOOSE VIP 31
31 GOOSE VIP 32
G228 2 Registers ALARM STATUS 3 (alarms 65 - 96) (32 bits) * * * * *
Bit Mask (hex) Data formatted as per data type G27
0x00000001 Battery Fail
0x00000002 Field Volt Fail
0x00000004 Rear Comm 2 Fail
0x00000008 GOOSE IED Absent
0x00000010 NIC Not Fitted
0x00000020 NIC No Response
0x00000040 NIC Fatal Error
0x00000080 NIC Soft. Reload
0x00000100 Bad TCP/IP Cfg.
0x00000200 Bad OSI Config.
0x00000400 NIC Link Fail
0x00000800 NIC SW Mis-Match
0x00001000 IP Addr Conflict
0x00002000 Unused
0x00004000 Unused
0x00008000 Unused
0x00010000 Unused
0x00020000 Unused
0x00040000 Unused
0x00080000 Unused
0x00100000 Unused
0x00200000 Bad Opto Charact
0x00400000 Unused
0x00800000 Unused
0x01000000 Unused
0x02000000 Unused
0x04000000 Unused
0x08000000 Unused
0x10000000 Unused
0x20000000 Unused
0x40000000 Unused
0x80000000 Unused
G229 ENROLLED FLAGS * * * * *
0 IED Status 1
1 IED Status 2
2 IED Status 3
3 IED Status 4
4 IED Status 5
5 IED Status 6
6 IED Status 7
7 IED Status 8
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 73

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

8 IED Status 9
9 IED Status 10
10 IED Status 11
11 IED Status 12
12 IED Status 13
13 IED Status 14
14 IED Status 15
15 IED Status 16
16 IED Status 17
17 IED Status 18
18 IED Status 19
19 IED Status 20
20 IED Status 21
21 IED Status 22
22 IED Status 23
23 IED Status 24
24 IED Status 25
25 IED Status 26
26 IED Status 27
27 IED Status 28
28 IED Status 29
29 IED Status 30
30 IED Status 31
31 IED Status 32
G231 DIRECT ACCESS KEYS * * * * *
Value
0 Disabled
1 Enabled
2 Hotkey Only
3 CB Ctrl Only
G232 CONTROL INPUT COMMAND TEXT * * * * *
Value
0 On/Off
1 Set/Reset
2 In/Out
3 Enabled/Disabled
G233 HOTKEY ENABLED CONTROL INPUTS * * * * *
0x00000001 Control Input 01
0x00000002 Control Input 02
0x00000004 Control Input 03
0x00000008 Control Input 04
0x00000010 Control Input 05
0x00000020 Control Input 06
0x00000040 Control Input 07
0x00000080 Control Input 08
0x00000100 Control Input 09
0x00000200 Control Input 10
0x00000400 Control Input 11
0x00000800 Control Input 12
0x00001000 Control Input 13
0x00002000 Control Input 14
0x00004000 Control Input 15
0x00008000 Control Input 16
0x00010000 Control Input 17
0x00020000 Control Input 18
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 74

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

0x00040000 Control Input 19


0x00080000 Control Input 20
0x00100000 Control Input 21
0x00200000 Control Input 22
0x00400000 Control Input 23
0x00800000 Control Input 24
0x01000000 Control Input 25
0x02000000 Control Input 26
0x04000000 Control Input 27
0x08000000 Control Input 28
0x10000000 Control Input 29
0x20000000 Control Input 30
0x40000000 Control Input 31
0x80000000 Control Input 32
G234 CONTROL INPUT SIGNAL TYPE * * * * *
Value
0 Latched
1 Pulsed
G235 ETHERNET PROTOCOL * * * * *
0 UCA 2.0
1 UCA 2.0 GOOSE
2 IEC61850
G237 OPTO ISOLATED STATUS INPUT CHARACTERISTIC * * * * *
Value
0 Standard 60% - 80%
1 50% - 70%
G238 TIME & DATE (TYPE G12) FORMAT SELECTOR * * * * *
Value MODBUS only
0 Standard
1 Reverse
G244 NOT USED * * * * *
G245 IEC 61850 DATA TYPES * * * * *
0 None
1 BSTR2
2 BOOL
3 INT8
4 INT16
5 INT32
6 UINT8
7 UINT16
8 UINT32
9 SPS
10 DPS
11 INS
G246 IEC 61850 TEST MODE * * * * *
0 Disabled
1 Pass Through
2 Forced
G247 SNTP STATUS * * * * *
0 Disabled
1 Trying Server 1
2 Trying Server 2
3 Server 1 OK
4 Server 2 OK
5 No response
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 75

Model
Type Value / Bit mask Description
P341 P342 P343 P344 P345

6 No valid clock
G248 IEC 61850 SETTING BANKS * * * * *
0 No Action
2 Switch Banks
G249 DNP3 Measurment Scaling * * * * *
0 Normalised
1 Primary
2 Secondary
G250 DAYS OF THE WEEK * * * * *
0 Sunday
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
G251 MONTHS OF THE YEAR * * * * *
0 January
1 February
2 March
3 April
4 May
5 June
6 July
7 August
8 September
9 October
10 November
11 December
G252 WEEK NUMBER * * * * *
0 First
1 Second
2 Third
3 Fourth
4 Last
G253 0 UTC * * * * *
1 Local
G254 Local Time * * * * *
0 Disabled
1 Fixed
2 Flexible
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 76

G32 Digital channel assignment selector

P341 P342 P343 P344 P345

0 Unused Unused Unused Unused Unused


1 see 4B01 see 4B01 see 4B01 see 4B01 see 4B01
2 see 4B02 see 4B02 see 4B02 see 4B02 see 4B02
3 see 4B03 see 4B03 see 4B03 see 4B03 see 4B03
4 see 4B04 see 4B04 see 4B04 see 4B04 see 4B04
5 see 4B05 see 4B05 see 4B05 see 4B05 see 4B05
6 see 4B06 see 4B06 see 4B06 see 4B06 see 4B06
7 see 4B07 see 4B07 see 4B07 see 4B07 see 4B07
8 see 4B08 see 4B08 see 4B08 see 4B08 see 4B08
9 see 4B09 see 4B09 see 4B09 see 4B09 see 4B09
10 see 4B0A see 4B0A see 4B0A see 4B0A see 4B0A
11 see 4B0B see 4B0B see 4B0B see 4B0B see 4B0B
12 see 4B0C see 4B0C see 4B0C see 4B0C see 4B0C
13 see 4B0D see 4B0D see 4B0D see 4B0D see 4B0D
14 see 4B0E see 4B0E see 4B0E see 4B0E see 4B0E
15 see 4B0F see 4B0F see 4B0F see 4B0F see 4B0F
16 see 4B10 see 4B10 see 4B10 see 4B10 see 4B10
17 see 4B11 see 4B11 see 4B11 see 4B11 see 4B11
18 see 4B12 see 4B12 see 4B12 see 4B12 see 4B12
19 see 4B13 see 4B13 see 4B13 see 4B13 see 4B13
20 see 4B14 see 4B14 see 4B14 see 4B14 see 4B14
21 see 4B15 see 4B15 see 4B15 see 4B15 see 4B15
22 see 4B16 see 4B16 see 4B16 see 4B16 see 4B16
23 see 4B17 see 4B17 see 4B17 see 4B17 see 4B17
24 see 4B18 see 4B18 see 4B18 see 4B18 see 4B18
25 see 4A01 see 4A01 see 4B19 see 4B19 see 4B19
26 see 4A02 see 4A02 see 4B1A see 4B1A see 4B1A
27 see 4A03 see 4A03 see 4B1B see 4B1B see 4B1B
28 see 4A04 see 4A04 see 4B1C see 4B1C see 4B1C
29 see 4A05 see 4A05 see 4B1D see 4B1D see 4B1D
30 see 4A06 see 4A06 see 4B1E see 4B1E see 4B1E
31 see 4A07 see 4A07 see 4B1F see 4B1F see 4B1F
32 see 4A08 see 4A08 see 4B20 see 4B20 see 4B20
33 see 4A09 see 4A09 see 4A01 see 4A01 see 4A01
34 see 4A0A see 4A0A see 4A02 see 4A02 see 4A02
35 see 4A0B see 4A0B see 4A03 see 4A03 see 4A03
36 see 4A0C see 4A0C see 4A04 see 4A04 see 4A04
37 see 4A0D see 4A0D see 4A05 see 4A05 see 4A05
38 see 4A0E see 4A0E see 4A06 see 4A06 see 4A06
39 see 4A0F see 4A0F see 4A07 see 4A07 see 4A07
40 see 4A10 see 4A10 see 4A08 see 4A08 see 4A08
41 see 4A11 see 4A11 see 4A09 see 4A09 see 4A09
42 see 4A12 see 4A12 see 4A0A see 4A0A see 4A0A
43 see 4A13 see 4A13 see 4A0B see 4A0B see 4A0B
44 see 4A14 see 4A14 see 4A0C see 4A0C see 4A0C
45 see 4A15 see 4A15 see 4A0D see 4A0D see 4A0D
46 see 4A16 see 4A16 see 4A0E see 4A0E see 4A0E
47 see 4A17 see 4A17 see 4A0F see 4A0F see 4A0F
48 see 4A18 see 4A18 see 4A10 see 4A10 see 4A10
49 LED 1 LED 1 see 4A11 see 4A11 see 4A11
50 LED 2 LED 2 see 4A12 see 4A12 see 4A12
51 LED 3 LED 3 see 4A13 see 4A13 see 4A13
52 LED 4 LED 4 see 4A14 see 4A14 see 4A14
53 LED 5 LED 5 see 4A15 see 4A15 see 4A15
54 LED 6 LED 6 see 4A16 see 4A16 see 4A16
55 LED 7 LED 7 see 4A17 see 4A17 see 4A17
56 LED 8 LED 8 see 4A18 see 4A18 see 4A18
57 SG-DDB Invalid SG-DDB Invalid see 4A19 see 4A19 see 4A19
58 Prot'n Disabled Prot'n Disabled see 4A1A see 4A1A see 4A1A
59 VT Fail Alarm VT Fail Alarm see 4A1B see 4A1B see 4A1B
60 CT-1 Fail Alarm CT-1 Fail Alarm see 4A1C see 4A1C see 4A1C
61 CB Fail Alarm CB Fail Alarm see 4A1D see 4A1D see 4A1D
62 I^ Maint Alarm I^ Maint Alarm see 4A1E see 4A1E see 4A1E
63 I^ Lockout Alarm I^ Lockout Alarm see 4A1F see 4A1F see 4A1F
64 CB Ops Maint CB Ops Maint see 4A20 see 4A20 see 4A20
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 77

P341 P342 P343 P344 P345

65 CB Ops Lockout CB Ops Lockout LED 1 LED 1 LED1 Red


66 CB Op Time Maint CB Op Time Maint LED 2 LED 2 LED1 Grn
67 CB Op Time Lock CB Op Time Lock LED 3 LED 3 LED2 Red
68 Fault Freq Lock Fault Freq Lock LED 4 LED 4 LED2 Grn
69 CB Status Alarm CB Status Alarm LED 5 LED 5 LED3 Red
70 Man CB Trip Fail NPS Thermal Alm LED 6 LED 6 LED3 Grn
71 Man CB Cls Fail Thermal Alarm LED 7 LED 7 LED4 Red
72 Man CB Unhealthy V/Hz Alarm LED 8 LED 8 LED4 Grn
73 F out of Range Field Fail Alarm SG-DDB Invalid SG-DDB Invalid LED5 Red
74 Thermal Alarm RTD Thermal Alm Prot'n Disabled Prot'n Disabled LED5 Grn
75 Freq Prot Alm RTD Open Cct VT Fail Alarm VT Fail Alarm LED6 Red
76 Voltage Prot Alm RTD short Cct CT-1 Fail Alarm CT-1 Fail Alarm LED6 Grn
77 CL Card I/P Fail RTD Data Error CB Fail Alarm CB Fail Alarm LED7 Red
78 CL Card O/P Fail RTD Board Fail I^ Maint Alarm I^ Maint Alarm LED7 Grn
79 CL Input 1 Alarm Freq Prot Alm I^ Lockout Alarm I^ Lockout Alarm LED8 Red
80 CL Input 2 Alarm Voltage Prot Alm CB Ops Maint CB Ops Maint LED8 Grn
81 CL Input 3 Alarm CL Card I/P Fail CB Ops Lockout CB Ops Lockout FnKey LED1 Red
82 CL Input 4 Alarm CL Card O/P Fail CB Op Time Maint CB Op Time Maint FnKey LED1 Grn
83 CLI1 I< Fail Alm CL Input 1 Alarm CB Op Time Lock CB Op Time Lock FnKey LED2 Red
84 CLI2 I< Fail Alm CL Input 2 Alarm Fault Freq Lock Fault Freq Lock FnKey LED2 Grn
85 CLI3 I< Fail Alm CL Input 3 Alarm CB Status Alarm CB Status Alarm FnKey LED3 Red
86 CLI4 I< Fail Alm CL Input 4 Alarm NPS Thermal Alm NPS Thermal Alm FnKey LED3 Grn
87 MR User Alarm 16 CLI1 I< Fail Alm Thermal Alarm Thermal Alarm FnKey LED4 Red
88 MR User Alarm 15 CLI2 I< Fail Alm V/Hz Alarm V/Hz Alarm FnKey LED4 Grn
89 MR User Alarm 14 CLI3 I< Fail Alm Field Fail Alarm Field Fail Alarm FnKey LED5 Red
90 MR User Alarm 13 CLI4 I< Fail Alm RTD Thermal Alm RTD Thermal Alm FnKey LED5 Grn
91 MR User Alarm 12 64R R<1 Alarm RTD Open Cct RTD Open Cct FnKey LED6 Red
92 MR User Alarm 11 64R CL I/P Fail RTD short Cct RTD short Cct FnKey LED6 Grn
93 MR User Alarm 10 MR User Alarm 16 RTD Data Error RTD Data Error FnKey LED7 Red
94 MR User Alarm 9 MR User Alarm 15 RTD Board Fail RTD Board Fail FnKey LED7 Grn
95 MR User Alarm 8 MR User Alarm 14 Freq Prot Alm Freq Prot Alm FnKey LED8 Red
96 MR User Alarm 7 MR User Alarm 13 Voltage Prot Alm Voltage Prot Alm FnKey LED8 Grn
97 MR User Alarm 6 MR User Alarm 12 CT-2 Fail Alarm CT-2 Fail Alarm FnKey LED9 Red
98 MR User Alarm 5 MR User Alarm 11 CL Card I/P Fail CL Card I/P Fail FnKey LED9 Grn
99 SR User Alarm 4 MR User Alarm 10 CL Card O/P Fail CL Card O/P Fail FnKey LED10 Red
100 SR User Alarm 3 MR User Alarm 9 CL Input 1 Alarm CL Input 1 Alarm FnKey LED10 Grn
101 SR User Alarm 2 MR User Alarm 8 CL Input 2 Alarm CL Input 2 Alarm Function Key 1
102 SR User Alarm 1 MR User Alarm 7 CL Input 3 Alarm CL Input 3 Alarm Function Key 2
103 Battery Fail MR User Alarm 6 CL Input 4 Alarm CL Input 4 Alarm Function Key 3
104 Field Volts Fail MR User Alarm 5 CLI1 I< Fail Alm CLI1 I< Fail Alm Function Key 4
105 GOOSE IED Absent SR User Alarm 4 CLI2 I< Fail Alm CLI2 I< Fail Alm Function Key 5
106 NIC Not Fitted SR User Alarm 3 CLI3 I< Fail Alm CLI3 I< Fail Alm Function Key 6
107 NIC No Response SR User Alarm 2 CLI4 I< Fail Alm CLI4 I< Fail Alm Function Key 7
108 NIC Fatal Error SR User Alarm 1 64R R<1 Alarm 64R R<1 Alarm Function Key 8
109 NIC Soft. Reload Battery Fail 64R CL I/P Fail 64R CL I/P Fail Function Key 9
110 Bad TCP/IP Cfg. Field Volts Fail MR User Alarm 16 MR User Alarm 16 Function Key 10
111 Bad OSI Config. GOOSE IED Absent MR User Alarm 15 MR User Alarm 15 SG-DDB Invalid
112 NIC Link Fail NIC Not Fitted MR User Alarm 14 MR User Alarm 14 Prot'n Disabled
113 NIC SW Mis-Match NIC No Response MR User Alarm 13 MR User Alarm 13 VT Fail Alarm
114 IP Addr Conflict NIC Fatal Error MR User Alarm 12 MR User Alarm 12 CT-1 Fail Alarm
115 Any Trip NIC Soft. Reload MR User Alarm 11 MR User Alarm 11 CB Fail Alarm
116 df/dt Trip Bad TCP/IP Cfg. MR User Alarm 10 MR User Alarm 10 I^ Maint Alarm
117 V Shift Trip Bad OSI Config. MR User Alarm 9 MR User Alarm 9 I^ Lockout Alarm
118 IN>1 Trip NIC Link Fail MR User Alarm 8 MR User Alarm 8 CB Ops Maint
119 IN>2 Trip NIC SW Mis-Match MR User Alarm 7 MR User Alarm 7 CB Ops Lockout
120 IN>3 Trip IP Addr Conflict MR User Alarm 6 MR User Alarm 6 CB Op Time Maint
121 IN>4 Trip Any Trip MR User Alarm 5 MR User Alarm 5 CB Op Time Lock
122 IREF> Trip Field Fail1 Trip SR User Alarm 4 SR User Alarm 4 Fault Freq Lock
123 ISEF>1 Trip Field Fail2 Trip SR User Alarm 3 SR User Alarm 3 CB Status Alarm
124 ISEF>2 Trip V/Hz>1 Trip SR User Alarm 2 SR User Alarm 2 NPS Thermal Alm
125 ISEF>3 Trip V/Hz>2 Trip SR User Alarm 1 SR User Alarm 1 Thermal Alarm
126 ISEF>4 Trip V/Hz>3 Trip Battery Fail Battery Fail V/Hz Alarm
127 VN>1 Trip V/Hz>4 Trip Field Volts Fail Field Volts Fail Field Fail Alarm
128 VN>2 Trip RTD 1 Trip GOOSE IED Absent GOOSE IED Absent RTD Thermal Alm
129 VN>3 Trip RTD 2 Trip NIC Not Fitted NIC Not Fitted RTD Open Cct
130 VN>4 Trip RTD 3 Trip NIC No Response NIC No Response RTD short Cct
131 V<1 Trip RTD 4 Trip NIC Fatal Error NIC Fatal Error RTD Data Error
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 78

P341 P342 P343 P344 P345

132 V<1 Trip A/AB RTD 5 Trip NIC Soft. Reload NIC Soft. Reload RTD Board Fail
133 V<1 Trip B/BC RTD 6 Trip Bad TCP/IP Cfg. Bad TCP/IP Cfg. Freq Prot Alm
134 V<1 Trip C/CA RTD 7 Trip Bad OSI Config. Bad OSI Config. Voltage Prot Alm
135 V<2 Trip RTD 8 Trip NIC Link Fail NIC Link Fail CT-2 Fail Alarm
136 V<2 Trip A/AB RTD 9 Trip NIC SW Mis-Match NIC SW Mis-Match 64S R<1 Alarm
137 V<2 Trip B/BC RTD 10 Trip IP Addr Conflict IP Addr Conflict 64S Fail Alarm
138 V<2 Trip C/CA Any RTD Trip Any Trip Any Trip CL Card I/P Fail
139 V>1 Trip IN>1 Trip Gen Diff Trip Gen Diff Trip CL Card O/P Fail
140 V>1 Trip A/AB IN>2 Trip Gen Diff Trip A Gen Diff Trip A CL Input 1 Alarm
141 V>1 Trip B/BC IREF> Trip Gen Diff Trip B Gen Diff Trip B CL Input 2 Alarm
142 V>1 Trip C/CA ISEF>1 Trip Gen Diff Trip C Gen Diff Trip C CL Input 3 Alarm
143 V>2 Trip VN>1 Trip Field Fail1 Trip Field Fail1 Trip CL Input 4 Alarm
144 V>2 Trip A/AB VN>2 Trip Field Fail2 Trip Field Fail2 Trip CLI1 I< Fail Alm
145 V>2 Trip B/BC VN>3 Trip V/Hz>1 Trip V/Hz>1 Trip CLI2 I< Fail Alm
146 V>2 Trip C/CA VN>4 Trip V/Hz>2 Trip V/Hz>2 Trip CLI3 I< Fail Alm
147 F<1 Trip V<1 Trip V/Hz>3 Trip V/Hz>3 Trip CLI4 I< Fail Alm
148 F<2 Trip V<1 Trip A/AB V/Hz>4 Trip V/Hz>4 Trip 64R R<1 Alarm
149 F<3 Trip V<1 Trip B/BC RTD 1 Trip RTD 1 Trip 64R CL I/P Fail
150 F<4 Trip V<1 Trip C/CA RTD 2 Trip RTD 2 Trip MR User Alarm 16
151 F>1 Trip V<2 Trip RTD 3 Trip RTD 3 Trip MR User Alarm 15
152 F>2 Trip V<2 Trip A/AB RTD 4 Trip RTD 4 Trip MR User Alarm 14
153 Power1 Trip V<2 Trip B/BC RTD 5 Trip RTD 5 Trip MR User Alarm 13
154 Power2 Trip V<2 Trip C/CA RTD 6 Trip RTD 6 Trip MR User Alarm 12
155 Thermal O/L Trip V>1 Trip RTD 7 Trip RTD 7 Trip MR User Alarm 11
156 I>1 Trip V>1 Trip A/AB RTD 8 Trip RTD 8 Trip MR User Alarm 10
157 I>1 Trip A V>1 Trip B/BC RTD 9 Trip RTD 9 Trip MR User Alarm 9
158 I>1 Trip B V>1 Trip C/CA RTD 10 Trip RTD 10 Trip MR User Alarm 8
159 I>1 Trip C V>2 Trip Any RTD Trip Any RTD Trip MR User Alarm 7
160 I>2 Trip V>2 Trip A/AB IN>1 Trip IN>1 Trip MR User Alarm 6
161 I>2 Trip A V>2 Trip B/BC IN>2 Trip IN>2 Trip MR User Alarm 5
162 I>2 Trip B V>2 Trip C/CA IREF> Trip IREF> Trip SR User Alarm 4
163 I>2 Trip C F<1 Trip ISEF>1 Trip ISEF>1 Trip SR User Alarm 3
164 I>3 Trip F<2 Trip VN>1 Trip VN>1 Trip SR User Alarm 2
165 I>3 Trip A F<3 Trip VN>2 Trip VN>2 Trip SR User Alarm 1
166 I>3 Trip B F<4 Trip VN>3 Trip VN>3 Trip Battery Fail
167 I>3 Trip C F>1 Trip VN>4 Trip VN>4 Trip Field Volts Fail
168 I>4 Trip F>2 Trip V<1 Trip VN>5 Trip GOOSE IED Absent
169 I>4 Trip A Power1 Trip V<1 Trip A/AB VN>6 Trip NIC Not Fitted
170 I>4 Trip B Power2 Trip V<1 Trip B/BC V<1 Trip NIC No Response
171 I>4 Trip C NPS Thermal Trip V<1 Trip C/CA V<1 Trip A/AB NIC Fatal Error
172 SPower1 Trip Thermal O/L Trip V<2 Trip V<1 Trip B/BC NIC Soft. Reload
173 SPower2 Trip I>1 Trip V<2 Trip A/AB V<1 Trip C/CA Bad TCP/IP Cfg.
174 Bfail1 Trip 3ph I>1 Trip A V<2 Trip B/BC V<2 Trip Bad OSI Config.
175 Bfail2 Trip 3ph I>1 Trip B V<2 Trip C/CA V<2 Trip A/AB NIC Link Fail
176 CL Input 1 Trip I>1 Trip C V>1 Trip V<2 Trip B/BC NIC SW Mis-Match
177 CL Input 2 Trip I>2 Trip V>1 Trip A/AB V<2 Trip C/CA IP Addr Conflict
178 CL Input 3 Trip I>2 Trip A V>1 Trip B/BC V>1 Trip Any Trip
179 CL Input 4 Trip I>2 Trip B V>1 Trip C/CA V>1 Trip A/AB Gen Diff Trip
180 I2>1 Trip I>2 Trip C V>2 Trip V>1 Trip B/BC Gen Diff Trip A
181 I2>2 Trip I>3 Trip V>2 Trip A/AB V>1 Trip C/CA Gen Diff Trip B
182 I2>3 Trip I>3 Trip A V>2 Trip B/BC V>2 Trip Gen Diff Trip C
183 I2>4 Trip I>3 Trip B V>2 Trip C/CA V>2 Trip A/AB Field Fail1 Trip
184 V2>1 Trip I>3 Trip C F<1 Trip V>2 Trip B/BC Field Fail2 Trip
185 Any Start I>4 Trip F<2 Trip V>2 Trip C/CA V/Hz>1 Trip
186 IA< Start I>4 Trip A F<3 Trip F<1 Trip V/Hz>2 Trip
187 IB< Start I>4 Trip B F<4 Trip F<2 Trip V/Hz>3 Trip
188 IC< Start I>4 Trip C F>1 Trip F<3 Trip V/Hz>4 Trip
189 ISEF< Start SPower1 Trip F>2 Trip F<4 Trip RTD 1 Trip
190 I> BlockStart SPower2 Trip Power1 Trip F>1 Trip RTD 2 Trip
191 IN/SEF>Blk Start V Dep OC Trip Power2 Trip F>2 Trip RTD 3 Trip
192 CLI1 Alarm Start V Dep OC Trip A NPS Thermal Trip Power1 Trip RTD 4 Trip
193 CLI2 Alarm Start V Dep OC Trip B Thermal O/L Trip Power2 Trip RTD 5 Trip
194 CLI3 Alarm Start V Dep OC Trip C I>1 Trip NPS Thermal Trip RTD 6 Trip
195 CLI4 Alarm Start Z<1 Trip I>1 Trip A Thermal O/L Trip RTD 7 Trip
196 CLI1 Trip Start Z<1 Trip A I>1 Trip B I>1 Trip RTD 8 Trip
197 CLI2 Trip Start Z<1 Trip B I>1 Trip C I>1 Trip A RTD 9 Trip
198 CLI3 Trip Start Z<1 Trip C I>2 Trip I>1 Trip B RTD 10 Trip
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 79

P341 P342 P343 P344 P345

199 CLI4 Trip Start Z<2 Trip I>2 Trip A I>1 Trip C Any RTD Trip
200 df/dt Start Z<2 Trip A I>2 Trip B I>2 Trip IN>1 Trip
201 IN>1 Start Z<2 Trip B I>2 Trip C I>2 Trip A IN>2 Trip
202 IN>2 Start Z<2 Trip C I>3 Trip I>2 Trip B IREF> Trip
203 IN>3 Start Bfail1 Trip 3ph I>3 Trip A I>2 Trip C ISEF>1 Trip
204 IN>4 Start Bfail2 Trip 3ph I>3 Trip B I>3 Trip VN>1 Trip
205 ISEF>1 Start CL Input 1 Trip I>3 Trip C I>3 Trip A VN>2 Trip
206 ISEF>2 Start CL Input 2 Trip I>4 Trip I>3 Trip B VN>3 Trip
207 ISEF>3 Start CL Input 3 Trip I>4 Trip A I>3 Trip C VN>4 Trip
208 ISEF>4 Start CL Input 4 Trip I>4 Trip B I>4 Trip VN>5 Trip
209 VN>1 Start S2>1 Trip I>4 Trip C I>4 Trip A VN>6 Trip
210 VN>2 Start Freq Band1 Trip SPower1 Trip I>4 Trip B V<1 Trip
211 VN>3 Start Freq Band2 Trip SPower2 Trip I>4 Trip C V<1 Trip A/AB
212 VN>4 Start Freq Band3 Trip PSlipz Z1 Trip SPower1 Trip V<1 Trip B/BC
213 V<1 Start Freq Band4 Trip PSlipz Z2 Trip SPower2 Trip V<1 Trip C/CA
214 V<1 Start A/AB Freq Band5 Trip V Dep OC Trip PSlipz Z1 Trip V<2 Trip
215 V<1 Start B/BC Freq Band6 Trip V Dep OC Trip A PSlipz Z2 Trip V<2 Trip A/AB
216 V<1 Start C/CA I2>1 Trip V Dep OC Trip B V Dep OC Trip V<2 Trip B/BC
217 V<2 Start I2>2 Trip V Dep OC Trip C V Dep OC Trip A V<2 Trip C/CA
218 V<2 Start A/AB I2>3 Trip Z<1 Trip V Dep OC Trip B V>1 Trip
219 V<2 Start B/BC I2>4 Trip Z<1 Trip A V Dep OC Trip C V>1 Trip A/AB
220 V<2 Start C/CA V2>1 Trip Z<1 Trip B Z<1 Trip V>1 Trip B/BC
221 V>1 Start 64R R<2 Trip Z<1 Trip C Z<1 Trip A V>1 Trip C/CA
222 V>1 Start A/AB Any Start Z<2 Trip Z<1 Trip B V>2 Trip
223 V>1 Start B/BC IA< Start Z<2 Trip A Z<1 Trip C V>2 Trip A/AB
224 V>1 Start C/CA IB< Start Z<2 Trip B Z<2 Trip V>2 Trip B/BC
225 V>2 Start IC< Start Z<2 Trip C Z<2 Trip A V>2 Trip C/CA
226 V>2 Start A/AB ISEF< Start Bfail1 Trip 3ph Z<2 Trip B F<1 Trip
227 V>2 Start B/BC IN< Start Bfail2 Trip 3ph Z<2 Trip C F<2 Trip
228 V>2 Start C/CA CLI1 Alarm Start 100%StEF3H Trip Bfail1 Trip 3ph F<3 Trip
229 F<1 Start CLI2 Alarm Start CL Input 1 Trip Bfail2 Trip 3ph F<4 Trip
230 F<2 Start CLI3 Alarm Start CL Input 2 Trip 100%StEF3H Trip F>1 Trip
231 F<3 Start CLI4 Alarm Start CL Input 3 Trip CL Input 1 Trip F>2 Trip
232 F<4 Start CLI1 Trip Start CL Input 4 Trip CL Input 2 Trip Power1 Trip
233 F>1 Start CLI2 Trip Start S2>1 Trip CL Input 3 Trip Power2 Trip
234 F>2 Start CLI3 Trip Start Freq Band1 Trip CL Input 4 Trip NPS Thermal Trip
235 Power1 Start CLI4 Trip Start Freq Band2 Trip S2>1 Trip Thermal O/L Trip
236 Power2 Start FFail1 Start Freq Band3 Trip Freq Band1 Trip I>1 Trip
237 I>1 Start FFail2 Start Freq Band4 Trip Freq Band2 Trip I>1 Trip A
238 I>1 Start A V/Hz>1 Start Freq Band5 Trip Freq Band3 Trip I>1 Trip B
239 I>1 Start B V/Hz>2 Start Freq Band6 Trip Freq Band4 Trip I>1 Trip C
240 I>1 Start C V/Hz>3 Start I2>1 Trip Freq Band5 Trip I>2 Trip
241 I>2 Start V/Hz>4 Start I2>2 Trip Freq Band6 Trip I>2 Trip A
242 I>2 Start A IN>1 Start I2>3 Trip I2>1 Trip I>2 Trip B
243 I>2 Start B IN>2 Start I2>4 Trip I2>2 Trip I>2 Trip C
244 I>2 Start C ISEF>1 Start V2>1 Trip I2>3 Trip I>3 Trip
245 I>3 Start VN>1 Start DeadMachine Trip I2>4 Trip I>3 Trip A
246 I>3 Start A VN>2 Start 64R R<2 Trip V2>1 Trip I>3 Trip B
247 I>3 Start B VN>3 Start Any Start DeadMachine Trip I>3 Trip C
248 I>3 Start C VN>4 Start IA< Start 64R R<2 Trip I>4 Trip
249 I>4 Start V<1 Start IB< Start Any Start I>4 Trip A
250 I>4 Start A V<1 Start A/AB IC< Start IA< Start I>4 Trip B
251 I>4 Start B V<1 Start B/BC ISEF< Start IB< Start I>4 Trip C
252 I>4 Start C V<1 Start C/CA IN< Start IC< Start SPower1 Trip
253 SPower1 Start V<2 Start CLI1 Alarm Start ISEF< Start SPower2 Trip
254 SPower2 Start V<2 Start A/AB CLI2 Alarm Start IN< Start PSlipz Z1 Trip
255 I2>1 Start V<2 Start B/BC CLI3 Alarm Start CLI1 Alarm Start PSlipz Z2 Trip
256 I2>2 Start V<2 Start C/CA CLI4 Alarm Start CLI2 Alarm Start V Dep OC Trip
257 I2>3 Start V>1 Start CLI1 Trip Start CLI3 Alarm Start V Dep OC Trip A
258 I2>4 Start V>1 Start A/AB CLI2 Trip Start CLI4 Alarm Start V Dep OC Trip B
259 V2>1 Start V>1 Start B/BC CLI3 Trip Start CLI1 Trip Start V Dep OC Trip C
260 VTS Fast Block V>1 Start C/CA CLI4 Trip Start CLI2 Trip Start Z<1 Trip
261 VTS Slow Block V>2 Start FFail1 Start CLI3 Trip Start Z<1 Trip A
262 CTS-1 Block V>2 Start A/AB FFail2 Start CLI4 Trip Start Z<1 Trip B
263 Control Trip V>2 Start B/BC V/Hz>1 Start FFail1 Start Z<1 Trip C
264 Control Close V>2 Start C/CA V/Hz>2 Start FFail2 Start Z<2 Trip
265 Close in Prog F<1 Start V/Hz>3 Start V/Hz>1 Start Z<2 Trip A
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 80

P341 P342 P343 P344 P345

266 Reconnection F<2 Start V/Hz>4 Start V/Hz>2 Start Z<2 Trip B
267 Lockout Alarm F<3 Start IN>1 Start V/Hz>3 Start Z<2 Trip C
268 CB Open 3 ph F<4 Start IN>2 Start V/Hz>4 Start Bfail1 Trip 3ph
269 CB Closed 3 ph F>1 Start ISEF>1 Start IN>1 Start Bfail2 Trip 3ph
270 All Poles Dead F>2 Start VN>1 Start IN>2 Start 100%StEF3H Trip
271 Any Pole Dead Power1 Start VN>2 Start ISEF>1 Start CL Input 1 Trip
272 Pole Dead A Power2 Start VN>3 Start VN>1 Start CL Input 2 Trip
273 Pole Dead B I>1 Start VN>4 Start VN>2 Start CL Input 3 Trip
274 Pole Dead C I>1 Start A V<1 Start VN>3 Start CL Input 4 Trip
275 Freq High I>1 Start B V<1 Start A/AB VN>4 Start S2>1 Trip
276 Freq Low I>1 Start C V<1 Start B/BC VN>5 Start Freq Band1 Trip
277 Freq Not found I>2 Start V<1 Start C/CA VN>6 Start Freq Band2 Trip
278 Control Input 1 I>2 Start A V<2 Start V<1 Start Freq Band3 Trip
279 Control Input 2 I>2 Start B V<2 Start A/AB V<1 Start A/AB Freq Band4 Trip
280 Control Input 3 I>2 Start C V<2 Start B/BC V<1 Start B/BC Freq Band5 Trip
281 Control Input 4 I>3 Start V<2 Start C/CA V<1 Start C/CA Freq Band6 Trip
282 Control Input 5 I>3 Start A V>1 Start V<2 Start I2>1 Trip
283 Control Input 6 I>3 Start B V>1 Start A/AB V<2 Start A/AB I2>2 Trip
284 Control Input 7 I>3 Start C V>1 Start B/BC V<2 Start B/BC I2>3 Trip
285 Control Input 8 I>4 Start V>1 Start C/CA V<2 Start C/CA I2>4 Trip
286 Control Input 9 I>4 Start A V>2 Start V>1 Start V2>1 Trip
287 Control Input 10 I>4 Start B V>2 Start A/AB V>1 Start A/AB DeadMachine Trip
288 Control Input 11 I>4 Start C V>2 Start B/BC V>1 Start B/BC 64S I>1 Trip
289 Control Input 12 SPower1 Start V>2 Start C/CA V>1 Start C/CA 64S R<2 Trip
290 Control Input 13 SPower2 Start F<1 Start V>2 Start 64R R<2 Trip
291 Control Input 14 Freq Band1 Start F<2 Start V>2 Start A/AB Any Start
292 Control Input 15 Freq Band2 Start F<3 Start V>2 Start B/BC IA< Start
293 Control Input 16 Freq Band3 Start F<4 Start V>2 Start C/CA IB< Start
294 Control Input 17 Freq Band4 Start F>1 Start F<1 Start IC< Start
295 Control Input 18 Freq Band5 Start F>2 Start F<2 Start ISEF< Start
296 Control Input 19 Freq Band6 Start Power1 Start F<3 Start IN< Start
297 Control Input 20 V Dep OC Start Power2 Start F<4 Start CLI1 Alarm Start
298 Control Input 21 V Dep OC Start A I>1 Start F>1 Start CLI2 Alarm Start
299 Control Input 22 V Dep OC Start B I>1 Start A F>2 Start CLI3 Alarm Start
300 Control Input 23 V Dep OC Start C I>1 Start B Power1 Start CLI4 Alarm Start
301 Control Input 24 Z<1 Start I>1 Start C Power2 Start CLI1 Trip Start
302 Control Input 25 Z<1 Start A I>2 Start I>1 Start CLI2 Trip Start
303 Control Input 26 Z<1 Start B I>2 Start A I>1 Start A CLI3 Trip Start
304 Control Input 27 Z<1 Start C I>2 Start B I>1 Start B CLI4 Trip Start
305 Control Input 28 Z<2 Start I>2 Start C I>1 Start C FFail1 Start
306 Control Input 29 Z<2 Start A I>3 Start I>2 Start FFail2 Start
307 Control Input 30 Z<2 Start B I>3 Start A I>2 Start A V/Hz>1 Start
308 Control Input 31 Z<2 Start C I>3 Start B I>2 Start B V/Hz>2 Start
309 Control Input 32 S2>1 Start I>3 Start C I>2 Start C V/Hz>3 Start
310 Virtual Input 01 I2>1 Start I>4 Start I>3 Start V/Hz>4 Start
311 Virtual Input 02 I2>2 Start I>4 Start A I>3 Start A IN>1 Start
312 Virtual Input 03 I2>3 Start I>4 Start B I>3 Start B IN>2 Start
313 Virtual Input 04 I2>4 Start I>4 Start C I>3 Start C ISEF>1 Start
314 Virtual Input 05 V2>1 Start SPower1 Start I>4 Start VN>1 Start
315 Virtual Input 06 64R Start R<1Alm SPower2 Start I>4 Start A VN>2 Start
316 Virtual Input 07 64R R<2 Start PSlipz Z1 Start I>4 Start B VN>3 Start
317 Virtual Input 08 VTS Fast Block PSlipz Z2 Start I>4 Start C VN>4 Start
318 Virtual Input 09 VTS Slow Block PSlipz LensStart SPower1 Start VN>5 Start
319 Virtual Input 10 CTS-1 Block PSlipz BlindStrt SPower2 Start VN>6 Start
320 Virtual Input 11 RTD 1 Alarm PSlipz ReactStrt PSlipz Z1 Start V<1 Start
321 Virtual Input 12 RTD 2 Alarm Freq Band1 Start PSlipz Z2 Start V<1 Start A/AB
322 Virtual Input 13 RTD 3 Alarm Freq Band2 Start PSlipz LensStart V<1 Start B/BC
323 Virtual Input 14 RTD 4 Alarm Freq Band3 Start PSlipz BlindStrt V<1 Start C/CA
324 Virtual Input 15 RTD 5 Alarm Freq Band4 Start PSlipz ReactStrt V<2 Start
325 Virtual Input 16 RTD 6 Alarm Freq Band5 Start Freq Band1 Start V<2 Start A/AB
326 Virtual Input 17 RTD 7 Alarm Freq Band6 Start Freq Band2 Start V<2 Start B/BC
327 Virtual Input 18 RTD 8 Alarm V Dep OC Start Freq Band3 Start V<2 Start C/CA
328 Virtual Input 19 RTD 9 Alarm V Dep OC Start A Freq Band4 Start V>1 Start
329 Virtual Input 20 RTD 10 Alarm V Dep OC Start B Freq Band5 Start V>1 Start A/AB
330 Virtual Input 21 Lockout Alarm V Dep OC Start C Freq Band6 Start V>1 Start B/BC
331 Virtual Input 22 CB Open 3 ph Z<1 Start V Dep OC Start V>1 Start C/CA
332 Virtual Input 23 CB Closed 3 ph Z<1 Start A V Dep OC Start A V>2 Start
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 81

P341 P342 P343 P344 P345

333 Virtual Input 24 All Poles Dead Z<1 Start B V Dep OC Start B V>2 Start A/AB
334 Virtual Input 25 Any Pole Dead Z<1 Start C V Dep OC Start C V>2 Start B/BC
335 Virtual Input 26 Pole Dead A Z<2 Start Z<1 Start V>2 Start C/CA
336 Virtual Input 27 Pole Dead B Z<2 Start A Z<1 Start A F<1 Start
337 Virtual Input 28 Pole Dead C Z<2 Start B Z<1 Start B F<2 Start
338 Virtual Input 29 Freq High Z<2 Start C Z<1 Start C F<3 Start
339 Virtual Input 30 Freq Low 100%StEF3H Start Z<2 Start F<4 Start
340 Virtual Input 31 Freq Not found S2>1 Start Z<2 Start A F>1 Start
341 Virtual Input 32 Control Input 1 I2>1 Start Z<2 Start B F>2 Start
342 Virtual Output01 Control Input 2 I2>2 Start Z<2 Start C Power1 Start
343 Virtual Output02 Control Input 3 I2>3 Start 100%StEF3H Start Power2 Start
344 Virtual Output03 Control Input 4 I2>4 Start S2>1 Start I>1 Start
345 Virtual Output04 Control Input 5 V2>1 Start I2>1 Start I>1 Start A
346 Virtual Output05 Control Input 6 64R Start R<1Alm I2>2 Start I>1 Start B
347 Virtual Output06 Control Input 7 64R R<2 Start I2>3 Start I>1 Start C
348 Virtual Output07 Control Input 8 VTS Fast Block I2>4 Start I>2 Start
349 Virtual Output08 Control Input 9 VTS Slow Block V2>1 Start I>2 Start A
350 Virtual Output09 Control Input 10 CTS-1 Block 64R Start R<1Alm I>2 Start B
351 Virtual Output10 Control Input 11 RTD 1 Alarm 64R R<2 Start I>2 Start C
352 Virtual Output11 Control Input 12 RTD 2 Alarm VTS Fast Block I>3 Start
353 Virtual Output12 Control Input 13 RTD 3 Alarm VTS Slow Block I>3 Start A
354 Virtual Output13 Control Input 14 RTD 4 Alarm CTS-1 Block I>3 Start B
355 Virtual Output14 Control Input 15 RTD 5 Alarm RTD 1 Alarm I>3 Start C
356 Virtual Output15 Control Input 16 RTD 6 Alarm RTD 2 Alarm I>4 Start
357 Virtual Output16 Control Input 17 RTD 7 Alarm RTD 3 Alarm I>4 Start A
358 Virtual Output17 Control Input 18 RTD 8 Alarm RTD 4 Alarm I>4 Start B
359 Virtual Output18 Control Input 19 RTD 9 Alarm RTD 5 Alarm I>4 Start C
360 Virtual Output19 Control Input 20 RTD 10 Alarm RTD 6 Alarm SPower1 Start
361 Virtual Output20 Control Input 21 Lockout Alarm RTD 7 Alarm SPower2 Start
362 Virtual Output21 Control Input 22 CB Open 3 ph RTD 8 Alarm PSlipz Z1 Start
363 Virtual Output22 Control Input 23 CB Closed 3 ph RTD 9 Alarm PSlipz Z2 Start
364 Virtual Output23 Control Input 24 All Poles Dead RTD 10 Alarm PSlipz LensStart
365 Virtual Output24 Control Input 25 Any Pole Dead Lockout Alarm PSlipz BlindStrt
366 Virtual Output25 Control Input 26 Pole Dead A CB Open 3 ph PSlipz ReactStrt
367 Virtual Output26 Control Input 27 Pole Dead B CB Closed 3 ph Freq Band1 Start
368 Virtual Output27 Control Input 28 Pole Dead C All Poles Dead Freq Band2 Start
369 Virtual Output28 Control Input 29 Freq High Any Pole Dead Freq Band3 Start
370 Virtual Output29 Control Input 30 Freq Low Pole Dead A Freq Band4 Start
371 Virtual Output30 Control Input 31 Freq Not found Pole Dead B Freq Band5 Start
372 Virtual Output31 Control Input 32 CTS-2 Block Pole Dead C Freq Band6 Start
373 Virtual Output32 Virtual Input 01 Control Input 1 Freq High V Dep OC Start
374 Virtual Input 02 Control Input 2 Freq Low V Dep OC Start A
375 Virtual Input 03 Control Input 3 Freq Not found V Dep OC Start B
376 Virtual Input 04 Control Input 4 CTS-2 Block V Dep OC Start C
377 Virtual Input 05 Control Input 5 Control Input 1 Z<1 Start
378 Virtual Input 06 Control Input 6 Control Input 2 Z<1 Start A
379 Virtual Input 07 Control Input 7 Control Input 3 Z<1 Start B
380 Virtual Input 08 Control Input 8 Control Input 4 Z<1 Start C
381 Virtual Input 09 Control Input 9 Control Input 5 Z<2 Start
382 Virtual Input 10 Control Input 10 Control Input 6 Z<2 Start A
383 Virtual Input 11 Control Input 11 Control Input 7 Z<2 Start B
384 Virtual Input 12 Control Input 12 Control Input 8 Z<2 Start C
385 Virtual Input 13 Control Input 13 Control Input 9 100%StEF3H Start
386 Virtual Input 14 Control Input 14 Control Input 10 S2>1 Start
387 Virtual Input 15 Control Input 15 Control Input 11 I2>1 Start
388 Virtual Input 16 Control Input 16 Control Input 12 I2>2 Start
389 Virtual Input 17 Control Input 17 Control Input 13 I2>3 Start
390 Virtual Input 18 Control Input 18 Control Input 14 I2>4 Start
391 Virtual Input 19 Control Input 19 Control Input 15 V2>1 Start
392 Virtual Input 20 Control Input 20 Control Input 16 64S I< Start
393 Virtual Input 21 Control Input 21 Control Input 17 64S V< Start
394 Virtual Input 22 Control Input 22 Control Input 18 64S I>1 Start
395 Virtual Input 23 Control Input 23 Control Input 19 64S Start R<1Alm
396 Virtual Input 24 Control Input 24 Control Input 20 64S R<2 Start
397 Virtual Input 25 Control Input 25 Control Input 21 64R Start R<1Alm
398 Virtual Input 26 Control Input 26 Control Input 22 64R R<2 Start
399 Virtual Input 27 Control Input 27 Control Input 23 VTS Fast Block
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 82

P341 P342 P343 P344 P345

400 Virtual Input 28 Control Input 28 Control Input 24 VTS Slow Block
401 Virtual Input 29 Control Input 29 Control Input 25 CTS-1 Block
402 Virtual Input 30 Control Input 30 Control Input 26 RTD 1 Alarm
403 Virtual Input 31 Control Input 31 Control Input 27 RTD 2 Alarm
404 Virtual Input 32 Control Input 32 Control Input 28 RTD 3 Alarm
405 Virtual Output01 Virtual Input 01 Control Input 29 RTD 4 Alarm
406 Virtual Output02 Virtual Input 02 Control Input 30 RTD 5 Alarm
407 Virtual Output03 Virtual Input 03 Control Input 31 RTD 6 Alarm
408 Virtual Output04 Virtual Input 04 Control Input 32 RTD 7 Alarm
409 Virtual Output05 Virtual Input 05 Virtual Input 01 RTD 8 Alarm
410 Virtual Output06 Virtual Input 06 Virtual Input 02 RTD 9 Alarm
411 Virtual Output07 Virtual Input 07 Virtual Input 03 RTD 10 Alarm
412 Virtual Output08 Virtual Input 08 Virtual Input 04 Lockout Alarm
413 Virtual Output09 Virtual Input 09 Virtual Input 05 CB Open 3 ph
414 Virtual Output10 Virtual Input 10 Virtual Input 06 CB Closed 3 ph
415 Virtual Output11 Virtual Input 11 Virtual Input 07 All Poles Dead
416 Virtual Output12 Virtual Input 12 Virtual Input 08 Any Pole Dead
417 Virtual Output13 Virtual Input 13 Virtual Input 09 Pole Dead A
418 Virtual Output14 Virtual Input 14 Virtual Input 10 Pole Dead B
419 Virtual Output15 Virtual Input 15 Virtual Input 11 Pole Dead C
420 Virtual Output16 Virtual Input 16 Virtual Input 12 Freq High
421 Virtual Output17 Virtual Input 17 Virtual Input 13 Freq Low
422 Virtual Output18 Virtual Input 18 Virtual Input 14 Freq Not found
423 Virtual Output19 Virtual Input 19 Virtual Input 15 CTS-2 Block
424 Virtual Output20 Virtual Input 20 Virtual Input 16 64S F Band Block
425 Virtual Output21 Virtual Input 21 Virtual Input 17 64S Fail
426 Virtual Output22 Virtual Input 22 Virtual Input 18 Control Input 1
427 Virtual Output23 Virtual Input 23 Virtual Input 19 Control Input 2
428 Virtual Output24 Virtual Input 24 Virtual Input 20 Control Input 3
429 Virtual Output25 Virtual Input 25 Virtual Input 21 Control Input 4
430 Virtual Output26 Virtual Input 26 Virtual Input 22 Control Input 5
431 Virtual Output27 Virtual Input 27 Virtual Input 23 Control Input 6
432 Virtual Output28 Virtual Input 28 Virtual Input 24 Control Input 7
433 Virtual Output29 Virtual Input 29 Virtual Input 25 Control Input 8
434 Virtual Output30 Virtual Input 30 Virtual Input 26 Control Input 9
435 Virtual Output31 Virtual Input 31 Virtual Input 27 Control Input 10
436 Virtual Output32 Virtual Input 32 Virtual Input 28 Control Input 11
437 Virtual Output01 Virtual Input 29 Control Input 12
438 Virtual Output02 Virtual Input 30 Control Input 13
439 Virtual Output03 Virtual Input 31 Control Input 14
440 Virtual Output04 Virtual Input 32 Control Input 15
441 Virtual Output05 Virtual Output01 Control Input 16
442 Virtual Output06 Virtual Output02 Control Input 17
443 Virtual Output07 Virtual Output03 Control Input 18
444 Virtual Output08 Virtual Output04 Control Input 19
445 Virtual Output09 Virtual Output05 Control Input 20
446 Virtual Output10 Virtual Output06 Control Input 21
447 Virtual Output11 Virtual Output07 Control Input 22
448 Virtual Output12 Virtual Output08 Control Input 23
449 Virtual Output13 Virtual Output09 Control Input 24
450 Virtual Output14 Virtual Output10 Control Input 25
451 Virtual Output15 Virtual Output11 Control Input 26
452 Virtual Output16 Virtual Output12 Control Input 27
453 Virtual Output17 Virtual Output13 Control Input 28
454 Virtual Output18 Virtual Output14 Control Input 29
455 Virtual Output19 Virtual Output15 Control Input 30
456 Virtual Output20 Virtual Output16 Control Input 31
457 Virtual Output21 Virtual Output17 Control Input 32
458 Virtual Output22 Virtual Output18 Virtual Input 01
459 Virtual Output23 Virtual Output19 Virtual Input 02
460 Virtual Output24 Virtual Output20 Virtual Input 03
461 Virtual Output25 Virtual Output21 Virtual Input 04
462 Virtual Output26 Virtual Output22 Virtual Input 05
463 Virtual Output27 Virtual Output23 Virtual Input 06
464 Virtual Output28 Virtual Output24 Virtual Input 07
465 Virtual Output29 Virtual Output25 Virtual Input 08
466 Virtual Output30 Virtual Output26 Virtual Input 09
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 83

P341 P342 P343 P344 P345

467 Virtual Output31 Virtual Output27 Virtual Input 10


468 Virtual Output32 Virtual Output28 Virtual Input 11
469 Virtual Output29 Virtual Input 12
470 Virtual Output30 Virtual Input 13
471 Virtual Output31 Virtual Input 14
472 Virtual Output32 Virtual Input 15
473 Virtual Input 16
474 Virtual Input 17
475 Virtual Input 18
476 Virtual Input 19
477 Virtual Input 20
478 Virtual Input 21
479 Virtual Input 22
480 Virtual Input 23
481 Virtual Input 24
482 Virtual Input 25
483 Virtual Input 26
484 Virtual Input 27
485 Virtual Input 28
486 Virtual Input 29
487 Virtual Input 30
488 Virtual Input 31
489 Virtual Input 32
490 Virtual Output01
491 Virtual Output02
492 Virtual Output03
493 Virtual Output04
494 Virtual Output05
495 Virtual Output06
496 Virtual Output07
497 Virtual Output08
498 Virtual Output09
499 Virtual Output10
500 Virtual Output11
501 Virtual Output12
502 Virtual Output13
503 Virtual Output14
504 Virtual Output15
505 Virtual Output16
506 Virtual Output17
507 Virtual Output18
508 Virtual Output19
509 Virtual Output20
510 Virtual Output21
511 Virtual Output22
512 Virtual Output23
513 Virtual Output24
514 Virtual Output25
515 Virtual Output26
516 Virtual Output27
517 Virtual Output28
518 Virtual Output29
519 Virtual Output30
520 Virtual Output31
521 Virtual Output32
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 84

Measurements range for each G155 selection

Default Default
CLIO output measurement Unit Minimum Maximum Step size Pri/Sec multiplier
minimum maximum

IA Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IB Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IC Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IN Measured Mag A 0*I2 16*I2 0.01*I2 0*I2 1.2*I2 M5

IN Derived Mag A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IN-1 Derived Mag A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IN-2 Derived Mag A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

I Sen Magnitude A 0*I3 16*I3 0.01*I3 0*I3 1.2*I3 M6

I1 Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

I2 Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

I0 Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IA RMS A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IB RMS A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IC RMS A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

VAB Magnitude V 0*V1 200*V1 0.1*V1 0*V1 140*V1 M1

VBC Magnitude V 0*V1 200*V1 0.1*V1 0*V1 140*V1 M1

VCA Magnitude V 0*V1 200*V1 0.1*V1 0*V1 140*V1 M1

VAN Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

VBN Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

VCN Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

VN1 Magnitude V 0*V3 200*V3 0.1*V3 0*V3 80*V3 M3

VN Derived Mag V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

VN2 Magnitude V 0*V2 200*V2 0.1*V2 0*V2 80*V2 M2

V1 Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

V2 Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

V0 Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

VAN RMS V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

VBN RMS V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

VCN RMS V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1

Frequency Hz 0 70 0.01 45 65

Volts/Hz V/Hz 0*V1 20*V1 0.01*V1 0*V1 4*V1 M1

3 Phase Watts W -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4

A Phase Watts W -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4

B Phase Watts W -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4


Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 85

Default Default
CLIO output measurement Unit Minimum Maximum Step size Pri/Sec multiplier
minimum maximum

C Phase Watts W -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4

3 Phase Vars Var -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4

A Phase Vars Var -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4

B Phase Vars Var -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4

C Phase Vars Var -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4

3 Phase VA VA 0*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4

A Phase VA VA 0*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4

B Phase VA VA 0*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4

C Phase VA VA 0*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4

3Ph Power Factor -1 1 0.01 0 1

APh Power Factor -1 1 0.01 0 1

BPh Power Factor -1 1 0.01 0 1

CPh Power Factor -1 1 0.01 0 1

3Ph W Fix Demand W -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4

3Ph Vars Fix Dem Var -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4

IA Fixed Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IB Fixed Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IC Fixed Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

3 Ph W Roll Dem W -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4

3Ph Vars RollDem Var -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4

IA Roll Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IB Roll Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IC Roll Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

3Ph W Peak Dem W -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4

3Ph Var Peak Dem Var -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4

IA Peak Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IB Peak Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

IC Peak Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4

VN 3rd Harmonic V 0*V3 200*V3 0.1*V3 0*V3 80*V3 M3

NPS Thermal % 0 200 0.01 0 120

Thermal Overload % 0 200 0.01 0 120

RTD 1 C -40 300 0.1 0 200

RTD 2 C -40 300 0.1 0 200

RTD 3 C -40 300 0.1 0 200

RTD 4 C -40 300 0.1 0 200

RTD 5 C -40 300 0.1 0 200


Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 86

Default Default
CLIO output measurement Unit Minimum Maximum Step size Pri/Sec multiplier
minimum maximum

RTD 6 C -40 300 0.1 0 200

RTD 7 C -40 300 0.1 0 200

RTD 8 C -40 300 0.1 0 200

RTD 9 C -40 300 0.1 0 200

RTD 10 C -40 300 0.1 0 200

CL Input 1 -9999 9999 0.1 0 9999

CL Input 2 -9999 9999 0.1 0 9999

CL Input 3 -9999 9999 0.1 0 9999

CL Input 4 -9999 9999 0.1 0 9999


Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 87

Digital Data Bus

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

0 Relay Conditioner 1 Output Relay 1 * see 4B01 * * * * *


1 Relay Conditioner 2 Output Relay 2 * see 4B02 * * * * *
2 Relay Conditioner 3 Output Relay 3 * see 4B03 * * * * *
3 Relay Conditioner 4 Output Relay 4 * see 4B04 * * * * *
4 Relay Conditioner 5 Output Relay 5 * see 4B05 * * * * *
5 Relay Conditioner 6 Output Relay 6 * see 4B06 * * * * *
6 Relay Conditioner 7 Output Relay 7 * see 4B07 * * * * *
7 Relay Conditioner 8 Output Relay 8 * see 4B08 * * * * *
8 Relay Conditioner 9 Output Relay 9 * see 4B09 * * * * *
9 Relay Conditioner 10 Output Relay 10 * see 4B0A * * * * *
10 Relay Conditioner 11 Output Relay 11 * see 4B0B * * * * *
11 Relay Conditioner 12 Output Relay 12 * see 4B0C * * * * *
12 Relay Conditioner 13 Output Relay 13 * see 4B0D * * * * *
13 Relay Conditioner 14 Output Relay 14 * see 4B0E * * * * *
14 Relay Conditioner 15 Output Relay 15 * see 4B0F * * * * *
15 Relay Conditioner 16 Output Relay 16 * see 4B10 * * * * *
16 Relay Conditioner 17 Output Relay 17 * see 4B11 * * * * *
17 Relay Conditioner 18 Output Relay 18 * see 4B12 * * * * *
18 Relay Conditioner 19 Output Relay 19 * see 4B13 * * * * *
19 Relay Conditioner 20 Output Relay 20 * see 4B14 * * * * *
20 Relay Conditioner 21 Output Relay 21 * see 4B15 * * * * *
21 Relay Conditioner 22 Output Relay 22 * see 4B16 * * * * *
22 Relay Conditioner 23 Output Relay 23 * see 4B17 * * * * *
23 Relay Conditioner 24 Output Relay 24 * see 4B18 * * * * *
24 Relay Conditioner 25 Output Relay 25 * see 4B19 * * *
25 Relay Conditioner 26 Output Relay 26 * see 4B1A * * *
26 Relay Conditioner 27 Output Relay 27 * see 4B1B * * *
27 Relay Conditioner 28 Output Relay 28 * see 4B1C * * *
28 Relay Conditioner 29 Output Relay 29 * see 4B1D * * *
29 Relay Conditioner 30 Output Relay 30 * see 4B1E * * *
30 Relay Conditioner 31 Output Relay 31 * see 4B1F * * *
31 Relay Conditioner 32 Output Relay 32 * see 4B20 * * *
32 Opto Isolator Input 1 Opto Isolator Input 1 * see 4A01 * * * * *
33 Opto Isolator Input 2 Opto Isolator Input 2 * see 4A02 * * * * *
34 Opto Isolator Input 3 Opto Isolator Input 3 * see 4A03 * * * * *
35 Opto Isolator Input 4 Opto Isolator Input 4 * see 4A04 * * * * *
36 Opto Isolator Input 5 Opto Isolator Input 5 * see 4A05 * * * * *
37 Opto Isolator Input 6 Opto Isolator Input 6 * see 4A06 * * * * *
38 Opto Isolator Input 7 Opto Isolator Input 7 * see 4A07 * * * * *
39 Opto Isolator Input 8 Opto Isolator Input 8 * see 4A08 * * * * *
40 Opto Isolator Input 9 Opto Isolator Input 9 * see 4A09 * * * * *
41 Opto Isolator Input 10 Opto Isolator Input 10 * see 4A0A * * * * *
42 Opto Isolator Input 11 Opto Isolator Input 11 * see 4A0B * * * * *
43 Opto Isolator Input 12 Opto Isolator Input 12 * see 4A0C * * * * *
44 Opto Isolator Input 13 Opto Isolator Input 13 * see 4A0D * * * * *
45 Opto Isolator Input 14 Opto Isolator Input 14 * see 4A0E * * * * *
46 Opto Isolator Input 15 Opto Isolator Input 15 * see 4A0F * * * * *
47 Opto Isolator Input 16 Opto Isolator Input 16 * see 4A10 * * * * *
48 Opto Isolator Input 17 Opto Isolator Input 17 * see 4A11 * * * * *
49 Opto Isolator Input 18 Opto Isolator Input 18 * see 4A12 * * * * *
50 Opto Isolator Input 19 Opto Isolator Input 19 * see 4A13 * * * * *
51 Opto Isolator Input 20 Opto Isolator Input 20 * see 4A14 * * * * *
52 Opto Isolator Input 21 Opto Isolator Input 21 * see 4A15 * * * * *
53 Opto Isolator Input 22 Opto Isolator Input 22 * see 4A16 * * * * *
54 Opto Isolator Input 23 Opto Isolator Input 23 * see 4A17 * * * * *
55 Opto Isolator Input 24 Opto Isolator Input 24 * see 4A18 * * * * *
56 Opto Isolator Input 25 Opto Isolator Input 25 * see 4A19 * * *
57 Opto Isolator Input 26 Opto Isolator Input 26 * see 4A1A * * *
58 Opto Isolator Input 27 Opto Isolator Input 27 * see 4A1B * * *
59 Opto Isolator Input 28 Opto Isolator Input 28 * see 4A1C * * *
60 Opto Isolator Input 29 Opto Isolator Input 29 * see 4A1D * * *
61 Opto Isolator Input 30 Opto Isolator Input 30 * see 4A1E * * *
62 Opto Isolator Input 31 Opto Isolator Input 31 * see 4A1F * * *
63 Opto Isolator Input 32 Opto Isolator Input 32 * see 4A20 * * *
64 PSL Relay Conditioner 1 Relay Cond 1 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 88

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

65 PSL Relay Conditioner 2 Relay Cond 2 * * * * *


66 PSL Relay Conditioner 3 Relay Cond 3 * * * * *
67 PSL Relay Conditioner 4 Relay Cond 4 * * * * *
68 PSL Relay Conditioner 5 Relay Cond 5 * * * * *
69 PSL Relay Conditioner 6 Relay Cond 6 * * * * *
70 PSL Relay Conditioner 7 Relay Cond 7 * * * * *
71 PSL Relay Conditioner 8 Relay Cond 8 * * * * *
72 PSL Relay Conditioner 9 Relay Cond 9 * * * * *
73 PSL Relay Conditioner 10 Relay Cond 10 * * * * *
74 PSL Relay Conditioner 11 Relay Cond 11 * * * * *
75 PSL Relay Conditioner 12 Relay Cond 12 * * * * *
76 PSL Relay Conditioner 13 Relay Cond 13 * * * * *
77 PSL Relay Conditioner 14 Relay Cond 14 * * * * *
78 PSL Relay Conditioner 15 Relay Cond 15 * * * * *
79 PSL Relay Conditioner 16 Relay Cond 16 * * * * *
80 PSL Relay Conditioner 17 Relay Cond 17 * * * * *
81 PSL Relay Conditioner 18 Relay Cond 18 * * * * *
82 PSL Relay Conditioner 19 Relay Cond 19 * * * * *
83 PSL Relay Conditioner 20 Relay Cond 20 * * * * *
84 PSL Relay Conditioner 21 Relay Cond 21 * * * * *
85 PSL Relay Conditioner 22 Relay Cond 22 * * * * *
86 PSL Relay Conditioner 23 Relay Cond 23 * * * * *
87 PSL Relay Conditioner 24 Relay Cond 24 * * * * *
88 PSL Relay Conditioner 25 Relay Cond 25 * * *
89 PSL Relay Conditioner 26 Relay Cond 26 * * *
90 PSL Relay Conditioner 27 Relay Cond 27 * * *
91 PSL Relay Conditioner 28 Relay Cond 28 * * *
92 PSL Relay Conditioner 29 Relay Cond 29 * * *
93 PSL Relay Conditioner 30 Relay Cond 30 * * *
94 PSL Relay Conditioner 31 Relay Cond 31 * * *
95 PSL Relay Conditioner 32 Relay Cond 32 * * *
96 Tri-LED - 1 - Red Tri-LED - 1 - Red LED1 Red *
97 Tri-LED - 1 - Green Tri-LED - 1 - Green LED1 Grn *
98 Tri-LED - 2 - Red Tri-LED - 2 - Red LED2 Red *
99 Tri-LED - 2 - Green Tri-LED - 2 - Green LED2 Grn *
100 Tri-LED - 3 - Red Tri-LED - 3 - Red LED3 Red *
101 Tri-LED - 3 - Green Tri-LED - 3 - Green LED3 Grn *
102 Tri-LED - 4 - Red Tri-LED - 4 - Red LED4 Red *
103 Tri-LED - 4 - Green Tri-LED - 4 - Green LED4 Grn *
104 Tri-LED - 5 - Red Tri-LED - 5 - Red LED5 Red *
105 Tri-LED - 5 - Green Tri-LED - 5 - Green LED5 Grn *
106 Tri-LED - 6 - Red Tri-LED - 6 - Red LED6 Red *
107 Tri-LED - 6 - Green Tri-LED - 6 - Green LED6 Grn *
108 Tri-LED - 7 - Red Tri-LED - 7 - Red LED7 Red *
109 Tri-LED - 7 - Green Tri-LED - 7 - Green LED7 Grn *
110 Tri-LED - 8 - Red Tri-LED - 8 - Red LED8 Red *
111 Tri-LED - 8 - Green Tri-LED - 8 - Green LED8 Grn *
112 Tri-LED - 9 - Red Tri-LED - 9 - Red FnKey LED1 Red *
113 Tri-LED - 9 - Green Tri-LED - 9 - Green FnKey LED1 Grn *
114 Tri-LED - 10 - Red Tri-LED - 10 - Red FnKey LED2 Red *
115 Tri-LED - 10 - Green Tri-LED - 10 - Green FnKey LED2 Grn *
116 Tri-LED - 11 - Red Tri-LED - 11 - Red FnKey LED3 Red *
117 Tri-LED - 11 - Green Tri-LED - 11 - Green FnKey LED3 Grn *
118 Tri-LED - 12 - Red Tri-LED - 12 - Red FnKey LED4 Red *
119 Tri-LED - 12 - Green Tri-LED - 12 - Green FnKey LED4 Grn *
120 Tri-LED - 13 - Red Tri-LED - 13 - Red FnKey LED5 Red *
121 Tri-LED - 13 - Green Tri-LED - 13 - Green FnKey LED5 Grn *
122 Tri-LED - 14 - Red Tri-LED - 14 - Red FnKey LED6 Red *
123 Tri-LED - 14 - Green Tri-LED - 14 - Green FnKey LED6 Grn *
124 Tri-LED - 15 - Red Tri-LED - 15 - Red FnKey LED7 Red *
125 Tri-LED - 15 - Green Tri-LED - 15 - Green FnKey LED7 Grn *
126 Tri-LED - 16 - Red Tri-LED - 16 - Red FnKey LED8 Red *
127 Tri-LED - 16 - Green Tri-LED - 16 - Green FnKey LED8 Grn *
128 Tri-LED - 17 - Red Tri-LED - 17 - Red FnKey LED9 Red *
129 Tri-LED - 17 - Green Tri-LED - 17 - Green FnKey LED9 Grn *
130 Tri-LED - 18 - Red Tri-LED - 18 - Red FnKey LED10 Red *
131 Tri-LED - 18 - Green Tri-LED - 18 - Green FnKey LED10 Grn *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 89

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

132 - Unused
133 - Unused
134 - Unused
135 - Unused
136 - Unused
137 - Unused
138 - Unused
139 - Unused
140 - Unused
141 - Unused
142 - Unused
143 - Unused
144 - Unused
145 - Unused
146 - Unused
147 - Unused
148 - Unused
149 - Unused
150 - Unused
151 - Unused
152 - Unused
153 - Unused
154 - Unused
155 - Unused
156 - Unused
157 - Unused
158 - Unused
159 - Unused
160 PSL Tri-LED Conditioner - 1 - Red LED1 Con R *
161 PSL Tri-LED Conditioner- 1 - Green LED1 Con G *
162 PSL Tri-LED Conditioner - 2 - Red LED2 Con R *
163 PSL Tri-LED Conditioner - 2 - Green LED2 Con G *
164 PSL Tri-LED Conditioner - 3 - Red LED3 Con R *
165 PSL Tri-LED Conditioner - 3 - Green LED3 Con G *
166 PSL Tri-LED Conditioner - 4 - Red LED4 Con R *
167 PSL Tri-LED Conditioner - 4 - Green LED4 Con G *
168 PSL Tri-LED Conditioner - 5 - Red LED5 Con R *
169 PSL Tri-LED Conditioner - 5 - Green LED5 Con G *
170 PSL Tri-LED Conditioner - 6 - Red LED6 Con R *
171 PSL Tri-LED Conditioner - 6 - Green LED6 Con G *
172 PSL Tri-LED Conditioner - 7 - Red LED7 Con R *
173 PSL Tri-LED Conditioner - 7 - Green LED7 Con G *
174 PSL Tri-LED Conditioner - 8 - Red LED8 Con R *
175 PSL Tri-LED Conditioner - 8 - Green LED8 Con G *
176 PSL Tri-LED Conditioner - 9 - Red FnKey LED1 ConR *
177 PSL Tri-LED Conditioner - 9 - Green FnKey LED1 ConG *
178 PSL Tri-LED Conditioner - 10 - Red FnKey LED2 ConR *
179 PSL Tri-LED Conditioner - 10 - Green FnKey LED2 ConG *
180 PSL Tri-LED Conditioner - 11 - Red FnKey LED3 ConR *
181 PSL Tri-LED Conditioner - 11 - Green FnKey LED3 ConG *
182 PSL Tri-LED Conditioner - 12 - Red FnKey LED4 ConR *
183 PSL Tri-LED Conditioner - 12 - Green FnKey LED4 ConG *
184 PSL Tri-LED Conditioner - 13 - Red FnKey LED5 ConR *
185 PSL Tri-LED Conditioner - 13 - Green FnKey LED5 ConG *
186 PSL Tri-LED Conditioner - 14 - Red FnKey LED6 ConR *
187 PSL Tri-LED Conditioner - 14 - Green FnKey LED6 ConG *
188 PSL Tri-LED Conditioner - 15 - Red FnKey LED7 ConR *
189 PSL Tri-LED Conditioner - 15 - Green FnKey LED7 ConG *
190 PSL Tri-LED Conditioner - 16 - Red FnKey LED8 ConR *
191 PSL Tri-LED Conditioner - 16 - Green FnKey LED8 ConG *
192 PSL Tri-LED Conditioner - 17 - Red FnKey LED9 ConR *
193 PSL Tri-LED Conditioner - 17 - Green FnKey LED9 ConG *
194 PSL Tri-LED Conditioner - 18 - Red FnKey LED10 ConR *
195 PSL Tri-LED Conditioner - 18 - Green FnKey LED10 ConG *
196 - Unused
197 - Unused
198 - Unused
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 90

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

199 - Unused
200 - Unused
201 - Unused
202 - Unused
203 - Unused
204 - Unused
205 - Unused
206 - Unused
207 - Unused
208 - Unused
209 - Unused
210 - Unused
211 - Unused
212 - Unused
213 - Unused
214 - Unused
215 - Unused
216 - Unused
217 - Unused
218 - Unused
219 - Unused
220 - Unused
221 - Unused
222 - Unused
223 - Unused
224 LED Conditioner IN 1 LED 1 LED 1 * * * * *
225 LED Conditioner IN 2 LED 2 LED 2 * * * * *
226 LED Conditioner IN 3 LED 3 LED 3 * * * * *
227 LED Conditioner IN 4 LED 4 LED 4 * * * * *
228 LED Conditioner IN 5 LED 5 LED 5 * * * * *
229 LED Conditioner IN 6 LED 6 LED 6 * * * * *
230 LED Conditioner IN 7 LED 7 LED 7 * * * * *
231 LED Conditioner IN 8 LED 8 LED 8 * * * * *
232 PSL LED Conditioner IN 1 LED Cond IN 1 * * * * *
233 PSL LED Conditioner IN 2 LED Cond IN 2 * * * * *
234 PSL LED Conditioner IN 3 LED Cond IN 3 * * * * *
235 PSL LED Conditioner IN 4 LED Cond IN 4 * * * * *
236 PSL LED Conditioner IN 5 LED Cond IN 5 * * * * *
237 PSL LED Conditioner IN 6 LED Cond IN 6 * * * * *
238 PSL LED Conditioner IN 7 LED Cond IN 7 * * * * *
239 PSL LED Conditioner IN 8 LED Cond IN 8 * * * * *
240 - Unused
241 - Unused
242 - Unused
243 - Unused
244 - Unused
245 - Unused
246 - Unused
247 - Unused
248 - Unused
249 - Unused
250 - Unused
251 - Unused
252 - Unused
253 - Unused
254 - Unused
255 - Unused
256 Function Key 1 Function Key 1 * Function Key 1 *
257 Function Key 2 Function Key 2 * Function Key 2 *
258 Function Key 3 Function Key 3 * Function Key 3 *
259 Function Key 4 Function Key 4 * Function Key 4 *
260 Function Key 5 Function Key 5 * Function Key 5 *
261 Function Key 6 Function Key 6 * Function Key 6 *
262 Function Key 7 Function Key 7 * Function Key 7 *
263 Function Key 8 Function Key 8 * Function Key 8 *
264 Function Key 9 Function Key 9 * Function Key 9 *
265 Function Key 10 Function Key 10 * Function Key 10 *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 91

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

266 - Unused
267 - Unused
268 - Unused
269 - Unused
270 - Unused
271 - Unused
272 - Unused
273 - Unused
274 - Unused
275 - Unused
276 - Unused
277 - Unused
278 - Unused
279 - Unused
280 - Unused
281 - Unused
282 - Unused
283 - Unused
284 - Unused
285 - Unused
286 - Unused
287 - Unused
288 Auxiliary Timer 1 Auxiliary Timer out 1 Timer out 1 * * * * *
289 Auxiliary Timer 2 Auxiliary Timer out 2 Timer out 2 * * * * *
290 Auxiliary Timer 3 Auxiliary Timer out 3 Timer out 3 * * * * *
291 Auxiliary Timer 4 Auxiliary Timer out 4 Timer out 4 * * * * *
292 Auxiliary Timer 5 Auxiliary Timer out 5 Timer out 5 * * * * *
293 Auxiliary Timer 6 Auxiliary Timer out 6 Timer out 6 * * * * *
294 Auxiliary Timer 7 Auxiliary Timer out 7 Timer out 7 * * * * *
295 Auxiliary Timer 8 Auxiliary Timer out 8 Timer out 8 * * * * *
296 Auxiliary Timer 9 Auxiliary Timer out 9 Timer out 9 * * * * *
297 Auxiliary Timer 10 Auxiliary Timer out 10 Timer out 10 * * * * *
298 Auxiliary Timer 11 Auxiliary Timer out 11 Timer out 11 * * * * *
299 Auxiliary Timer 12 Auxiliary Timer out 12 Timer out 12 * * * * *
300 Auxiliary Timer 13 Auxiliary Timer out 13 Timer out 13 * * * * *
301 Auxiliary Timer 14 Auxiliary Timer out 14 Timer out 14 * * * * *
302 Auxiliary Timer 15 Auxiliary Timer out 15 Timer out 15 * * * * *
303 Auxiliary Timer 16 Auxiliary Timer out 16 Timer out 16 * * * * *
304 - Unused
305 - Unused
306 - Unused
307 - Unused
308 - Unused
309 - Unused
310 - Unused
311 - Unused
312 - Unused
313 - Unused
314 - Unused
315 - Unused
316 - Unused
317 - Unused
318 - Unused
319 - Unused
320 PSL Auxiliary Timer in 1 Timer in 1 * * * * *
321 PSL Auxiliary Timer in 2 Timer in 2 * * * * *
322 PSL Auxiliary Timer in 3 Timer in 3 * * * * *
323 PSL Auxiliary Timer in 4 Timer in 4 * * * * *
324 PSL Auxiliary Timer in 5 Timer in 5 * * * * *
325 PSL Auxiliary Timer in 6 Timer in 6 * * * * *
326 PSL Auxiliary Timer in 7 Timer in 7 * * * * *
327 PSL Auxiliary Timer in 8 Timer in 8 * * * * *
328 PSL Auxiliary Timer in 9 Timer in 9 * * * * *
329 PSL Auxiliary Timer in 10 Timer in 10 * * * * *
330 PSL Auxiliary Timer in 11 Timer in 11 * * * * *
331 PSL Auxiliary Timer in 12 Timer in 12 * * * * *
332 PSL Auxiliary Timer in 13 Timer in 13 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 92

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

333 PSL Auxiliary Timer in 14 Timer in 14 * * * * *


334 PSL Auxiliary Timer in 15 Timer in 15 * * * * *
335 PSL Auxiliary Timer in 16 Timer in 16 * * * * *
336 - Unused
337 - Unused
338 - Unused
339 - Unused
340 - Unused
341 - Unused
342 - Unused
343 - Unused
344 - Unused
345 - Unused
346 - Unused
347 - Unused
348 - Unused
349 - Unused
350 - Unused
351 - Unused
352 - Unused
353 - Unused
354 Group Selection Setting Group selection by DDB inputs invalid * SG-DDB Invalid * * * * *
355 Commission Test Test Mode Enabled * Prot'n Disabled * * * * *
356 VT Supervision VTS VT Fail Alarm * VT Fail Alarm * * * * *
357 CT Supervision CTS-1 CT-1 Fail Alarm * CT-1 Fail Alarm * * * * *
358 Breaker Fail Breaker Fail Any Trip * CB Fail Alarm * * * * *
359 CB Monitoring Broken Current Maintenance Alarm * I^ Maint Alarm * * * * *
360 CB Monitoring Broken Current Lockout Alarm * I^ Lockout Alarm * * * * *
361 CB Monitoring Number of CB Operations Maintenance Alarm * CB Ops Maint * * * * *

362 CB Monitoring Number of CB Operations Maintenance Lockout * CB Ops Lockout * * * * *

Excessive CB Operation Time Maintenance


363 CB Monitoring * CB Op Time Maint * * * * *
Alarm
364 CB Monitoring Excessive CB Operation Time Lockout Alarm * CB Op Time Lock * * * * *
365 CB Monitoring Excessive Fault Frequency Lockout Alarm * Fault Freq Lock * * * * *
366 CB Status CB Status Alarm * CB Status Alarm * * * * *
367 CB Control CB Failed to Trip * Man CB Trip Fail *
368 CB Control CB Failed to Close * Man CB Cls Fail *
369 CB Control Control CB Unhealthy * Man CB Unhealthy *
370 Frequency Tracking Frequency Out of Range * F out of Range *
370 NPS Thermal Negative Phase Sequence thermal Alarm * NPS Thermal Alm * * * *
371 Thermal Overload Thermal Overload Alarm * Thermal Alarm * * * * *
372 Over Fluxing Volts Per Hz Alarm * V/Hz Alarm * * * *
373 Field Failure Field Failure Alarm * Field Fail Alarm * * * *
374 RTD Thermal RTD Thermal Alarm * RTD Thermal Alm * * * *
375 RTD Thermal RTD Open Circuit Failure * RTD Open Cct * * * *
376 RTD Thermal RTD Short Circuit Failure * RTD short Cct * * * *
377 RTD Thermal RTD Data Inconsistency Error * RTD Data Error * * * *
378 RTD Thermal RTD Board Failure * RTD Board Fail * * * *
379 PSL Frequency Protection Alarm * Freq Prot Alm * * * * *
380 PSL Voltage Protection Alarm * Voltage Prot Alm * * * * *
381 CT Supervision CTS-2 CT-2 Fail Alarm * CT-2 Fail Alarm * * *
64S 100% St EF Under Resistance Stage 1
382 100% Stator Earth Fault * 64S R<1 Alarm *
Alarm
383 100% Stator Earth Fault 64S Injection Fail Alarm * 64S Fail Alarm *
384 Current Loop Inputs CLIO Input Board Failure * CL Card I/P Fail * * * * *
385 Current Loop Outputs CLIO Output Board Failure * CL Card O/P Fail * * * * *
386 Current Loop Inputs Current Loop Input 1 Alarm * CL Input 1 Alarm * * * * *
387 Current Loop Inputs Current Loop Input 2 Alarm * CL Input 2 Alarm * * * * *
388 Current Loop Inputs Current Loop Input 3 Alarm * CL Input 3 Alarm * * * * *
389 Current Loop Inputs Current Loop Input 4 Alarm * CL Input 4 Alarm * * * * *
390 Current Loop Inputs Current Loop Input 1 Undercurrent Fail Alarm * CLI1 I< Fail Alm * * * * *
391 Current Loop Inputs Current Loop Input 2 Undercurrent Fail Alarm * CLI2 I< Fail Alm * * * * *
392 Current Loop Inputs Current Loop Input 3 Undercurrent Fail Alarm * CLI3 I< Fail Alm * * * * *
393 Current Loop Inputs Current Loop Input 4 Undercurrent Fail Alarm * CLI4 I< Fail Alm * * * * *
394 64R Rotor Earth Fault 64R Rotor EF Under Resistance Stage 1 Alarm * 64R R<1 Alarm * * * *
395 64R Rotor Earth Fault 64R Rotor EF Current Loop Input Fail * 64R CL I/P Fail * * * *
396 - Unused
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 93

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

397 - Unused
398 - Unused
399 - Unused
400 PSL User Definable Alarm 16 (Manual Reset) * MR User Alarm 16 * * * * *
401 PSL User Definable Alarm 15 (Manual Reset) * MR User Alarm 15 * * * * *
402 PSL User Definable Alarm 14 (Manual Reset) * MR User Alarm 14 * * * * *
403 PSL User Definable Alarm 13 (Manual Reset) * MR User Alarm 13 * * * * *
404 PSL User Definable Alarm 12 (Manual Reset) * MR User Alarm 12 * * * * *
405 PSL User Definable Alarm 11 (Manual Reset) * MR User Alarm 11 * * * * *
406 PSL User Definable Alarm 10 (Manual Reset) * MR User Alarm 10 * * * * *
407 PSL User Definable Alarm 9 (Manual Reset) * MR User Alarm 9 * * * * *
408 PSL User Definable Alarm 8 (Manual Reset) * MR User Alarm 8 * * * * *
409 PSL User Definable Alarm 7 (Manual Reset) * MR User Alarm 7 * * * * *
410 PSL User Definable Alarm 6 (Manual Reset) * MR User Alarm 6 * * * * *
411 PSL User Definable Alarm 5 (Manual Reset) * MR User Alarm 5 * * * * *
412 PSL User Definable Alarm 4 (Self Reset) * SR User Alarm 4 * * * * *
413 PSL User Definable Alarm 3 (Self Reset) * SR User Alarm 3 * * * * *
414 PSL User Definable Alarm 2 (Self Reset) * SR User Alarm 2 * * * * *
415 PSL User Definable Alarm 1 (Self Reset) * SR User Alarm 1 * * * * *
416 Self Monitoring Battery Fail alarm indication Battery Fail * * * * *
417 Self Monitoring Field Voltage Failure Field Volts Fail * * * * *
418 - Unused
419 Px40 Platform Enrolled GOOSE IED absent alarm indication GOOSE IED Absent * * * * *
420 Px40 Platform Network Interface Card not fitted/failed alarm NIC Not Fitted * * * * *
421 Px40 Platform Network Interface Card not responding alarm NIC No Response * * * * *
Network Interface Card fatal error alarm
422 Px40 Platform NIC Fatal Error * * * * *
indication

423 Px40 Platform Network Interface Card software reload alarm NIC Soft. Reload * * * * *

424 Px40 Platform Bad TCP/IP Configuration Alarm Bad TCP/IP Cfg. * * * * *

425 Px40 Platform Bad OSI Configuration Alarm Bad OSI Config. * * * * *

426 Px40 Platform Network Interface Card link fail alarm indication NIC Link Fail * * * * *

Main card/NIC software mismatch alarm


427 Px40 Platform NIC SW Mis-Match * * * * *
indication
428 Px40 Platform IP address conflict alarm indication IP Addr Conflict * * * * *
429 - Unused
430 - Unused
431 - Unused
432 - Unused
433 - Unused
434 - Unused
435 - Unused
436 - Unused
437 - Unused
438 - Unused
439 - Unused
440 - Unused
441 - Unused
442 - Unused
443 - Unused
444 - Unused
445 - Unused
446 - Unused
447 - Unused
448 - Unused
449 - Unused
450 - Unused
451 - Unused
452 - Unused
453 - Unused
454 - Unused
455 - Unused
456 - Unused
457 - Unused
458 - Unused
459 - Unused
460 - Unused
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 94

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

461 - Unused
462 - Unused
463 - Unused
464 - Unused
465 - Unused
466 - Unused
467 - Unused
468 - Unused
469 - Unused
470 - Unused
471 - Unused
472 - Unused
473 - Unused
474 - Unused
475 - Unused
476 - Unused
477 - Unused
478 - Unused
479 - Unused
480 - Unused
481 - Unused
482 - Unused
483 - Unused
484 - Unused
485 - Unused
486 - Unused
487 - Unused
488 - Unused
489 - Unused
490 - Unused
491 - Unused
492 - Unused
493 - Unused
494 - Unused
495 - Unused
496 - Unused
497 - Unused
498 - Unused
499 - Unused
500 - Unused
501 - Unused
502 - Unused
503 - Unused
504 - Unused
505 - Unused
506 - Unused
507 - Unused
508 - Unused
509 - Unused
510 - Unused
511 - Unused
512 PSL Block Generator Differential Protection Gen Diff Block * * *
513 PSL Inhibit Volts per Hz Stage 1 V/Hz>1 Inhibit * * * *
514 PSL Block Earth Fault Stage 1 time delay IN>1 Timer Blk * * * * *
515 PSL Block Earth Fault Stage 2 time delay IN>2 Timer Blk * * * * *
516 PSL Block Earth Fault Stage 3 time delay IN>3 Timer Blk *
517 PSL Block Earth Fault Stage 4 time delay IN>4 Timer Blk *
518 PSL Block SEF Stage 1 time delay ISEF>1 Timer Blk * * * * *
519 PSL Block SEF Stage 2 time delay ISEF>2 Timer Blk *
520 PSL Block SEF Stage 3 time delay ISEF>3 Timer Blk *
521 PSL Block SEF Stage 4 time delay ISEF>4 Timer Blk *

522 PSL Block Residual Over Voltage Stage 1 time delay VN>1 Timer Blk * * * * *

523 PSL Block Residual Over Voltage Stage 2 time delay VN>2 Timer Blk * * * * *

524 PSL Block Residual Over Voltage Stage 3 Timer VN>3 Timer Block * * * * *
525 PSL Block Residual Over Voltage Stage 4 Timer VN>4 Timer Block * * * * *
526 PSL Block Residual Over Voltage Stage 5 Timer VN>5 Timer Block * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 95

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

527 PSL Block Residual Over Voltage Stage 6 Timer VN>6 Timer Block * *
528 PSL Block Phase Under Voltage Stage 1 time delay V<1 Timer Block * * * * *
529 PSL Block Phase Under Voltage Stage 2 time delay V<2 Timer Block * * * * *
530 PSL Block Phase Over Voltage Stage 1 time delay V>1 Timer Block * * * * *
531 PSL Block Phase Over Voltage Stage 2 time delay V>2 Timer Block * * * * *
532 PSL Block Under Frequency Stage 1 Timer F<1 Timer Block * * * * *
533 PSL Block Under Frequency Stage 2 Timer F<2 Timer Block * * * * *
534 PSL Block Under Frequency Stage 3 Timer F<3 Timer Block * * * * *
535 PSL Block Under Frequency Stage 4 Timer F<4 Timer Block * * * * *
536 PSL Block Over Frequency Stage 1 Timer F>1 Timer Block * * * * *
537 PSL Block Over Frequency Stage 2 Timer F>2 Timer Block * * * * *
538 PSL Block Phase Overcurrent Stage 1 time delay I>1 Timer Block * * * * *
539 PSL Block Phase Overcurrent Stage 2 time delay I>2 Timer Block * * * * *
540 PSL Block Phase Overcurrent Stage 3 time delay I>3 Timer Block * * * * *
541 PSL Block Phase Overcurrent Stage 4 time delay I>4 Timer Block * * * * *
542 PSL Voltage Dependant Overcurrent time delay VDepOC Timer Blk * * * *
543 PSL Under Impedance time delay UnderZ Timer Blk * * * *
544 PSL Block Current Loop Input 1 protection CL Input 1 Blk * * * * *
545 PSL Block Current Loop Input 2 protection CL Input 2 Blk * * * * *
546 PSL Block Current Loop Input 3 protection CL Input 3 Blk * * * * *
547 PSL Block Current Loop Input 4 protection CL Input 4 Blk * * * * *
548 PSL Inhibit Turbine Abnormal Frequency Protection Turbine F Inh * * * *
549 PSL Inhibit NPS Overcurrent protection I2> Inhibit * * * * *
550 PSL Block NPS Overcurrent Stage 1 Timer I2>1 Timer Block * * * * *
551 PSL Block NPS Overcurrent Stage 2 Timer I2>2 Timer Block * * * * *
552 PSL Block NPS Overcurrent Stage 3 Timer I2>3 Timer Block * * * * *
553 PSL Block NPS Overcurrent Stage 4 Timer I2>4 Timer Block * * * * *
554 PSL Accelerate NPS Over Voltage Stage 1 Start V2>1 Accelerate * * * * *
555 PSL Reset NPS Thermal State Reset I2 Thermal * * * *
556 PSL Reset Thermal Overload State Reset ThermalO/L * * * * *
557 - Unused
558 PSL Inhibit 64S Overcurrent Protection 64S I>1 Inhibit *
559 PSL Inhibit 64S Under Impedance Stage 1 64S R<1 Inhibit *
560 PSL Inhibit 64S Under Impedance Stage 2 64S R<2 Inhibit *
561 PSL Enable the 64S band pass filter permanently 64S Filter On *
562 PSL Inhibit 64R Under Impedance Stage 1 64R R<1 Inhibit * * * *
563 PSL Inhibit 64R Under Impedance Stage 2 64R R<2 Inhibit * * * *
564 - Unused
565 - Unused
566 - Unused
567 - Unused
568 - Unused
569 - Unused
570 - Unused
571 - Unused
572 - Unused
573 - Unused
574 - Unused
575 - Unused
576 - Unused
577 - Unused
578 - Unused
579 - Unused
580 - Unused
581 - Unused
582 - Unused
583 - Unused
584 - Unused
585 - Unused
586 - Unused
587 - Unused
588 - Unused
589 - Unused
590 - Unused
591 - Unused
592 - Unused
593 - Unused
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 96

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

594 - Unused
595 - Unused
596 - Unused
597 - Unused
598 - Unused
599 - Unused
600 - Unused
601 - Unused
602 - Unused
603 - Unused
604 - Unused
605 - Unused
606 - Unused
607 - Unused
608 PSL Logic Input Trip CB Init Trip CB *
609 PSL Logic Input Close CB Init Close CB *
610 PSL External Trip 3ph Ext. Trip 3ph * * * * *
611 PSL 52-A (3 phase) CB Aux 3ph(52-A) * * * * *
612 PSL 52-B (3 phase) CB Aux 3ph(52-B) * * * * *
613 PSL CB Healthy CB Healthy * * * * *
614 PSL MCB/VTS opto MCB/VTS * * * * *
615 PSL Reset Manual CB Close Time Delay Reset Close Dly * * * * *
616 PSL Reset Latched Relays & LEDs * Reset Relays/LED * * * * *
617 PSL Reset Lockout Opto Input Reset Lockout * * * * *
618 PSL Reset CB Maintenance Values Reset All Values * * * * *
619 PSL IEC60870-5-103 Monitor Blocking * Monitor Blocked * * * * *
620 PSL IEC60870-5-103 Command Blocking * Command Blocked * * * * *
Time synchronize to nearest minute on 0-1
621 PSL Time Synch * * * * *
change
622 PSL Initiate Test Mode Test Mode * * * * *
623 PSL Fault Record Trigger Input Fault REC TRIG * * * * *
624 PSL Setting Group Selector x1 (bit 0) * SG Select x1 * * * * *
625 PSL Setting Group Selector 1x (bit 1) * SG Select 1x * * * * *
626 PSL Any Trip * Any Trip * * * * *
627 - Unused
628 - Unused
629 - Unused
630 - Unused
631 - Unused
632 - Unused
633 - Unused
634 - Unused
635 - Unused
636 - Unused
637 - Unused
638 - Unused
639 - Unused
640 Generator Differential Generator Differential Trip 3ph * Gen Diff Trip * * *
641 Generator Differential Generator Differential Trip A * Gen Diff Trip A * * *
642 Generator Differential Generator Differential Trip B * Gen Diff Trip B * * *
643 Generator Differential Generator Differential Trip C * Gen Diff Trip C * * *
644 Field Failure Field Failure Stage 1 Trip * Field Fail1 Trip * * * *
645 Field Failure Field Failure Stage 2 Trip * Field Fail2 Trip * * * *
646 Over Fluxing 1st Stage Volts per Hz Trip * V/Hz>1 Trip * * * *
647 Over Fluxing Volts per Hz Stage 2 Trip * V/Hz>2 Trip * * * *
648 Over Fluxing Volts per Hz Stage 3 Trip * V/Hz>3 Trip * * * *
649 Over Fluxing Volts per Hz Stage 4 Trip * V/Hz>4 Trip * * * *
650 RTD Thermal RTD 1 Trip * RTD 1 Trip * * * *
651 RTD Thermal RTD 2 Trip * RTD 2 Trip * * * *
652 RTD Thermal RTD 3 Trip * RTD 3 Trip * * * *
653 RTD Thermal RTD 4 Trip * RTD 4 Trip * * * *
654 RTD Thermal RTD 5 Trip * RTD 5 Trip * * * *
655 RTD Thermal RTD 6 Trip * RTD 6 Trip * * * *
656 RTD Thermal RTD 7 Trip * RTD 7 Trip * * * *
657 RTD Thermal RTD 8 Trip * RTD 8 Trip * * * *
658 RTD Thermal RTD 9 Trip * RTD 9 Trip * * * *
659 RTD Thermal RTD 10 Trip * RTD 10 Trip * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 97

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

660 RTD Thermal Any RTD Trip * Any RTD Trip * * * *


661 df/dt Rate Of Change Of Frequency Trip * df/dt Trip *
662 Voltage Vector Shift Voltage Vector Shift Trip * V Shift Trip *
663 Earth Fault 1st Stage EF Trip * IN>1 Trip * * * * *
664 Earth Fault 2nd Stage EF Trip * IN>2 Trip * * * * *
665 Earth Fault 3rd Stage EF Trip * IN>3 Trip *
666 Earth Fault 4th Stage EF Trip * IN>4 Trip *
667 Restricted Earth Fault REF Trip * IREF> Trip * * * * *
668 Sensitive Earth Fault 1st Stage SEF Trip * ISEF>1 Trip * * * * *
669 Sensitive Earth Fault 2nd Stage SEF Trip * ISEF>2 Trip *
670 Sensitive Earth Fault 3rd Stage SEF Trip * ISEF>3 Trip *
671 Sensitive Earth Fault 4th Stage SEF Trip * ISEF>4 Trip *
672 Neutral Displacement 1st Stage Residual O/V Trip * VN>1 Trip * * * * *
673 Neutral Displacement 2nd Stage Residual O/V Trip * VN>2 Trip * * * * *
674 Neutral Displacement Residual O/V Stage 3 Trip * VN>3 Trip * * * * *
675 Neutral Displacement Residual O/V Stage 4 Trip * VN>4 Trip * * * * *
676 Neutral Displacement Residual O/V Stage 5 Trip * VN>5 Trip * *
677 Neutral Displacement Residual O/V Stage 6 Trip * VN>6 Trip * *
678 Phase Under Voltage 1st Stage Phase U/V Trip 3ph * V<1 Trip * * * * *
679 Phase Under Voltage 1st Stage Phase U/V Trip A/AB * V<1 Trip A/AB * * * * *
680 Phase Under Voltage 1st Stage Phase U/V Trip B/BC * V<1 Trip B/BC * * * * *
681 Phase Under Voltage 1st Stage Phase U/V Trip C/CA * V<1 Trip C/CA * * * * *
682 Phase Under Voltage 2nd Stage Phase U/V Trip 3ph * V<2 Trip * * * * *
683 Phase Under Voltage 2nd Stage Phase U/V Trip A/AB * V<2 Trip A/AB * * * * *
684 Phase Under Voltage 2nd Stage Phase U/V Trip B/BC * V<2 Trip B/BC * * * * *
685 Phase Under Voltage 2nd Stage Phase U/V Trip C/CA * V<2 Trip C/CA * * * * *
686 Phase Over Voltage 1st Stage Phase O/V Trip 3ph * V>1 Trip * * * * *
687 Phase Over Voltage 1st Stage Phase O/V Trip A/AB * V>1 Trip A/AB * * * * *
688 Phase Over Voltage 1st Stage Phase O/V Trip B/BC * V>1 Trip B/BC * * * * *
689 Phase Over Voltage 1st Stage Phase O/V Trip C/CA * V>1 Trip C/CA * * * * *
690 Phase Over Voltage 2nd Stage Phase O/V Trip 3ph * V>2 Trip * * * * *
691 Phase Over Voltage 2nd Stage Phase O/V Trip A/AB * V>2 Trip A/AB * * * * *
692 Phase Over Voltage 2nd Stage Phase O/V Trip B/BC * V>2 Trip B/BC * * * * *
693 Phase Over Voltage 2nd Stage Phase O/V Trip C/CA * V>2 Trip C/CA * * * * *
694 Under Frequency Under Frequency Stage 1 Trip * F<1 Trip * * * * *
695 Under Frequency Under Frequency Stage 2 Trip * F<2 Trip * * * * *
696 Under Frequency Under Frequency Stage 3 Trip * F<3 Trip * * * * *
697 Under Frequency Under Frequency Stage 4 Trip * F<4 Trip * * * * *
698 Over Frequency Over Frequency Stage 1 Trip * F>1 Trip * * * * *
699 Over Frequency Over Frequency Stage 2 Trip * F>2 Trip * * * * *
700 Power Power Stage 1 Trip * Power1 Trip * * * * *
701 Power Power Stage 2 Trip * Power2 Trip * * * * *
702 NPS Thermal Negative Phase Sequence Thermal Trip * NPS Thermal Trip * * * *
703 Thermal Overload Thermal Overload Trip * Thermal O/L Trip * * * * *
704 Phase Over Current 1st Stage O/C Trip 3ph * I>1 Trip * * * * *
705 Phase Over Current 1st Stage O/C Trip A * I>1 Trip A * * * * *
706 Phase Over Current 1st Stage O/C Trip B * I>1 Trip B * * * * *
707 Phase Over Current 1st Stage O/C Trip C * I>1 Trip C * * * * *
708 Phase Over Current 2nd Stage O/C Trip 3ph * I>2 Trip * * * * *
709 Phase Over Current 2nd Stage O/C Trip A * I>2 Trip A * * * * *
710 Phase Over Current 2nd Stage O/C Trip B * I>2 Trip B * * * * *
711 Phase Over Current 2nd Stage O/C Trip C * I>2 Trip C * * * * *
712 Phase Over Current 3rd Stage O/C Trip 3ph * I>3 Trip * * * * *
713 Phase Over Current 3rd Stage O/C Trip A * I>3 Trip A * * * * *
714 Phase Over Current 3rd Stage O/C Trip B * I>3 Trip B * * * * *
715 Phase Over Current 3rd Stage O/C Trip C * I>3 Trip C * * * * *
716 Phase Over Current 4th Stage O/C Trip 3ph * I>4 Trip * * * * *
717 Phase Over Current 4th Stage O/C Trip A * I>4 Trip A * * * * *
718 Phase Over Current 4th Stage O/C Trip B * I>4 Trip B * * * * *
719 Phase Over Current 4th Stage O/C Trip C * I>4 Trip C * * * * *
720 Sensitive Power Sensitive A Phase Power Stage 1 Trip * SPower1 Trip * * * * *
721 Sensitive Power Sensitive A Phase Power Stage 2 Trip * SPower2 Trip * * * * *
722 Z based Pole Slipping Pole Slip (Impedance) Zone1 Trip * PSlipz Z1 Trip * * *
723 Z based Pole Slipping Pole Slip (Impedance) Zone2 Trip * PSlipz Z2 Trip * * *
724 System Backup Voltage Dependant Overcurrent Trip 3ph * V Dep OC Trip * * * *
725 System Backup Voltage Dependant Overcurrent Trip A * V Dep OC Trip A * * * *
726 System Backup Voltage Dependant Overcurrent Trip B * V Dep OC Trip B * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 98

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

727 System Backup Voltage Dependant Overcurrent Trip C * V Dep OC Trip C * * * *


728 System Backup Under Impedance 3Phase Stage 1 Trip * Z<1 Trip * * * *
729 System Backup Under Impedance Phase A Stage 1 Trip * Z<1 Trip A * * * *
730 System Backup Under Impedance Phase B Stage 1 Trip * Z<1 Trip B * * * *
731 System Backup Under Impedance Phase C Stage 1 Trip * Z<1 Trip C * * * *
732 System Backup Under Impedance 3Phase Stage 2 Trip * Z<2 Trip * * * *
733 System Backup Under Impedance Phase A Stage 2 Trip * Z<2 Trip A * * * *
734 System Backup Under Impedance Phase B Stage 2 Trip * Z<2 Trip B * * * *
735 System Backup Under Impedance Phase C Stage 2 Trip * Z<2 Trip C * * * *
736 Breaker failure tBF1 Trip 3ph * Bfail1 Trip 3ph * * * * *
737 Breaker failure tBF2 Trip 3ph * Bfail2 Trip 3ph * * * * *
738 100% Stator Earth Fault 100% Stator Earth Fault (3rd harmonic) Trip * 100%StEF3H Trip * * *
739 Current Loop Inputs Current Loop Input 1 Trip * CL Input 1 Trip * * * * *
740 Current Loop Inputs Current Loop Input 2 Trip * CL Input 2 Trip * * * * *
741 Current Loop Inputs Current Loop Input 3 Trip * CL Input 3 Trip * * * * *
742 Current Loop Inputs Current Loop Input 4 Trip * CL Input 4 Trip * * * * *
743 NPS Over Power NPS Overpower Stage 1 trip * S2>1 Trip * * * *
Turbine Abnormal
744 Turbine Abnormal Frequency Band 1 Trip * Freq Band1 Trip * * * *
Frequency
Turbine Abnormal
745 Turbine Abnormal Frequency Band 2 Trip * Freq Band2 Trip * * * *
Frequency
Turbine Abnormal
746 Turbine Abnormal Frequency Band 3 Trip * Freq Band3 Trip * * * *
Frequency
Turbine Abnormal
747 Turbine Abnormal Frequency Band 4 Trip * Freq Band4 Trip * * * *
Frequency
Turbine Abnormal
748 Turbine Abnormal Frequency Band 5 Trip * Freq Band5 Trip * * * *
Frequency
Turbine Abnormal
749 Turbine Abnormal Frequency Band 6 Trip * Freq Band6 Trip * * * *
Frequency
750 NPS Over Current NPS Overcurrent Stage 1 Trip * I2>1 Trip * * * * *
751 NPS Over Current NPS Overcurrent Stage 2 Trip * I2>2 Trip * * * * *
752 NPS Over Current NPS Overcurrent Stage 3 Trip * I2>3 Trip * * * * *
753 NPS Over Current NPS Overcurrent Stage 4 Trip * I2>4 Trip * * * * *
754 NPS Over Voltage NPS Over Voltage Stage 1 Trip * V2>1 Trip * * * * *
755 Dead Machine Dead Machine Protection Trip * DeadMachine Trip * * *
756 100% Stator Earth Fault 64S 100% Stator Earth Fault Overcurrent Trip * 64S I>1 Trip *

757 100% Stator Earth Fault 64S 100% St EF Under Resistance Stage 2 Trip * 64S R<2 Trip *

758 64R Rotor Earth Fault 64R Rotor Earth Fault Under Resistance Stage 2 T * 64R R<2 Trip * * * *
759 - Unused
760 - Unused
761 - Unused
762 - Unused
763 - Unused
764 - Unused
765 - Unused
766 - Unused
767 - Unused
768 - Unused
769 - Unused
770 - Unused
771 - Unused
772 - Unused
773 - Unused
774 - Unused
775 - Unused
776 - Unused
777 - Unused
778 - Unused
779 - Unused
780 - Unused
781 - Unused
782 - Unused
783 - Unused
784 - Unused
785 - Unused
786 - Unused
787 - Unused
788 - Unused
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 99

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

789 - Unused
790 - Unused
791 - Unused
792 - Unused
793 - Unused
794 - Unused
795 - Unused
796 - Unused
797 - Unused
798 - Unused
799 - Unused
800 - Unused
801 - Unused
802 - Unused
803 - Unused
804 - Unused
805 - Unused
806 - Unused
807 - Unused
808 - Unused
809 - Unused
810 - Unused
811 - Unused
812 - Unused
813 - Unused
814 - Unused
815 - Unused
816 - Unused
817 - Unused
818 - Unused
819 - Unused
820 - Unused
821 - Unused
822 - Unused
823 - Unused
824 - Unused
825 - Unused
826 - Unused
827 - Unused
828 - Unused
829 - Unused
830 - Unused
831 - Unused
832 Protection Starts (most) Any Start * Any Start * * * * *
833 Under Current Fast under current: Phase A IA< Start * * * * *
834 Under Current Fast under current: Phase B IB< Start * * * * *
835 Under Current Fast under current: Phase C IC< Start * * * * *
836 Under Current ISEF< Operate ISEF< Start * * * * *
837 Under Current IN< Operate IN< Start * * * *
838 Phase Over Current I> Blocked O/C Start * I> BlockStart *
839 EF & SEF IN/ISEF> Blocked O/C Start * IN/SEF>Blk Start *
840 Current Loop Inputs Current Loop Input 1 Alarm Start * CLI1 Alarm Start * * * * *
841 Current Loop Inputs Current Loop Input 2 Alarm Start * CLI2 Alarm Start * * * * *
842 Current Loop Inputs Current Loop Input 3 Alarm Start * CLI3 Alarm Start * * * * *
843 Current Loop Inputs Current Loop Input 4 Alarm Start * CLI4 Alarm Start * * * * *
844 Current Loop Inputs Current Loop Input 1 Trip Start * CLI1 Trip Start * * * * *
845 Current Loop Inputs Current Loop Input 2 Trip Start * CLI2 Trip Start * * * * *
846 Current Loop Inputs Current Loop Input 3 Trip Start * CLI3 Trip Start * * * * *
847 Current Loop Inputs Current Loop Input 4 Trip Start * CLI4 Trip Start * * * * *
848 Field Failure Field Failure Stage 1 Start * FFail1 Start * * * *
849 Field Failure Field Failure Stage 2 Start * FFail2 Start * * * *
850 Over Fluxing 1st Stage Volts per Hz Start * V/Hz>1 Start * * * *
851 Over Fluxing Volts per Hz Stage 2 Start * V/Hz>2 Start * * * *
852 Over Fluxing Volts per Hz Stage 3 Start * V/Hz>3 Start * * * *
853 Over Fluxing Volts per Hz Stage 4 Start * V/Hz>4 Start * * * *
854 df/dt Rate Of Change Of Frequency Start * df/dt Start *
855 Earth Fault 1st Stage EF Start * IN>1 Start * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 100

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

856 Earth Fault 2nd Stage EF Start * IN>2 Start * * * * *


857 Earth Fault 3rd Stage EF Start * IN>3 Start *
858 Earth Fault 4th Stage EF Start * IN>4 Start *
859 Sensitive Earth Fault 1st Stage SEF Start * ISEF>1 Start * * * * *
860 Sensitive Earth Fault 2nd Stage SEF Start * ISEF>2 Start *
861 Sensitive Earth Fault 3rd Stage SEF Start * ISEF>3 Start *
862 Sensitive Earth Fault 4th Stage SEF Start * ISEF>4 Start *
863 - Unused
864 Neutral Voltage 1st Stage Residual O/V Start * VN>1 Start * * * * *
865 Neutral Voltage 2nd Stage Residual O/V Start * VN>2 Start * * * * *
866 Neutral Voltage Residual O/V Stage 3 Start * VN>3 Start * * * * *
867 Neutral Voltage Residual O/V Stage 4 Start * VN>4 Start * * * * *
868 Neutral Voltage Residual O/V Stage 5 Start * VN>5 Start * *
869 Neutral Voltage Residual O/V Stage 6 Start * VN>6 Start * *
870 Phase Under Voltage 1st Stage Phase U/V Start 3ph * V<1 Start * * * * *
871 Phase Under Voltage 1st Stage Phase U/V Start A/AB * V<1 Start A/AB * * * * *
872 Phase Under Voltage 1st Stage Phase U/V Start B/BC * V<1 Start B/BC * * * * *
873 Phase Under Voltage 1st Stage Phase U/V Start C/CA * V<1 Start C/CA * * * * *
874 Phase Under Voltage 2nd Stage Phase U/V Start 3ph * V<2 Start * * * * *
875 Phase Under Voltage 2nd Stage Phase U/V Start A/AB * V<2 Start A/AB * * * * *
876 Phase Under Voltage 2nd Stage Phase U/V Start B/BC * V<2 Start B/BC * * * * *
877 Phase Under Voltage 2nd Stage Phase U/V Start C/CA * V<2 Start C/CA * * * * *
878 Phase Over Voltage 1st Stage Phase O/V Start 3ph * V>1 Start * * * * *
879 Phase Over Voltage 1st Stage Phase O/V Start A/AB * V>1 Start A/AB * * * * *
880 Phase Over Voltage 1st Stage Phase O/V Start B/BC * V>1 Start B/BC * * * * *
881 Phase Over Voltage 1st Stage Phase O/V Start C/CA * V>1 Start C/CA * * * * *
882 Phase Over Voltage 2nd Stage Phase O/V Start 3ph * V>2 Start * * * * *
883 Phase Over Voltage 2nd Stage Phase O/V Start A/AB * V>2 Start A/AB * * * * *
884 Phase Over Voltage 2nd Stage Phase O/V Start B/BC * V>2 Start B/BC * * * * *
885 Phase Over Voltage 2nd Stage Phase O/V Start C/CA * V>2 Start C/CA * * * * *
886 Under Frequency Under Frequency Stage 1 Start * F<1 Start * * * * *
887 Under Frequency Under Frequency Stage 2 Start * F<2 Start * * * * *
888 Under Frequency Under Frequency Stage 3 Start * F<3 Start * * * * *
889 Under Frequency Under Frequency Stage 4 Start * F<4 Start * * * * *
890 Over Frequency Over Frequency Stage 1 Start * F>1 Start * * * * *
891 Over Frequency Over Frequency Stage 2 Start * F>2 Start * * * * *
892 Power Power Stage 1 Start * Power1 Start * * * * *
893 Power Power Stage 2 Start * Power2 Start * * * * *
894 - Unused
895 - Unused
896 Phase Over Current 1st Stage O/C Start 3ph * I>1 Start * * * * *
897 Phase Over Current 1st Stage O/C Start A * I>1 Start A * * * * *
898 Phase Over Current 1st Stage O/C Start B * I>1 Start B * * * * *
899 Phase Over Current 1st Stage O/C Start C * I>1 Start C * * * * *
900 Phase Over Current 2nd Stage O/C Start 3ph * I>2 Start * * * * *
901 Phase Over Current 2nd Stage O/C Start A * I>2 Start A * * * * *
902 Phase Over Current 2nd Stage O/C Start B * I>2 Start B * * * * *
903 Phase Over Current 2nd Stage O/C Start C * I>2 Start C * * * * *
904 Phase Over Current 3rd Stage O/C Start 3ph * I>3 Start * * * * *
905 Phase Over Current 3rd Stage O/C Start A * I>3 Start A * * * * *
906 Phase Over Current 3rd Stage O/C Start B * I>3 Start B * * * * *
907 Phase Over Current 3rd Stage O/C Start C * I>3 Start C * * * * *
908 Phase Over Current 4th Stage O/C Start 3ph * I>4 Start * * * * *
909 Phase Over Current 4th Stage O/C Start A * I>4 Start A * * * * *
910 Phase Over Current 4th Stage O/C Start B * I>4 Start B * * * * *
911 Phase Over Current 4th Stage O/C Start C * I>4 Start C * * * * *
912 Sensitive Power Sensitive A Phase Power Stage 1 Start * SPower1 Start * * * * *
913 Sensitive Power Sensitive A Phase Power Stage 2 Start * SPower2 Start * * * * *
914 Z based Pole Slipping Pole Slip (Impedance) Zone1 Start * PSlipz Z1 Start * * *
915 Z based Pole Slipping Pole Slip (Impedance) Zone2 Start * PSlipz Z2 Start * * *
916 Z based Pole Slipping Pole Slip (impedance) Lens Start * PSlipz LensStart * * *
917 Z based Pole Slipping Pole Slip (impedance) Blinder Start * PSlipz BlindStrt * * *
918 Z based Pole Slipping Pole Slip (impedance) Reactance Line Start PSlipz ReactStrt * * *
Turbine Abnormal
919 Turbine Abnormal Frequency Band 1 Start * Freq Band1 Start * * * *
Frequency
Turbine Abnormal
920 Turbine Abnormal Frequency Band 2 Start * Freq Band2 Start * * * *
Frequency
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 101

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

Turbine Abnormal
921 Turbine Abnormal Frequency Band 3 Start * Freq Band3 Start * * * *
Frequency
Turbine Abnormal
922 Turbine Abnormal Frequency Band 4 Start * Freq Band4 Start * * * *
Frequency
Turbine Abnormal
923 Turbine Abnormal Frequency Band 5 Start * Freq Band5 Start * * * *
Frequency
Turbine Abnormal
924 Turbine Abnormal Frequency Band 6 Start * Freq Band6 Start * * * *
Frequency
925 - Unused
926 - Unused
927 - Unused
928 System Backup Voltage Dependant Overcurrent Start 3Ph * V Dep OC Start * * * *
929 System Backup Voltage Dependant Overcurrent Start A * V Dep OC Start A * * * *
930 System Backup Voltage Dependant Overcurrent Start B * V Dep OC Start B * * * *
931 System Backup Voltage Dependant Overcurrent Start C * V Dep OC Start C * * * *
932 System Backup Under Impedance 3Phase Stage 1 Start * Z<1 Start * * * *
933 System Backup Under Impedance Phase A Stage 1 Start * Z<1 Start A * * * *
934 System Backup Under Impedance Phase B Stage 1 Start * Z<1 Start B * * * *
935 System Backup Under Impedance Phase C Stage 1 Start * Z<1 Start C * * * *
936 System Backup Under Impedance 3Phase Stage 2 Start * Z<2 Start * * * *
937 System Backup Under Impedance Phase A Stage 2 Start * Z<2 Start A * * * *
938 System Backup Under Impedance Phase B Stage 2 Start * Z<2 Start B * * * *
939 System Backup Under Impedance Phase C Stage 2 Start * Z<2 Start C * * * *
940 100% Stator Earth Fault 100% Stator Earth Fault (3rd harmonic) Start * 100%StEF3H Start * * *
941 NPS Power NPS Overpower Stage 1 Start * S2>1 Start * * * *
942 NPS Over Current NPS Overcurrent Stage 1 Start * I2>1 Start * * * * *
943 NPS Over Current NPS Overcurrent Stage 2 Start * I2>2 Start * * * * *
944 NPS Over Current NPS Overcurrent Stage 3 Start * I2>3 Start * * * * *
945 NPS Over Current NPS Overcurrent Stage 4 Start * I2>4 Start * * * * *
946 NPS Over Voltage NPS Over Voltage Stage 1 Start * V2>1 Start * * * * *

947 100% Stator Earth Fault 64S 100% Stator Earth Fault Undercurrent Start * 64S I< Start *

948 100% Stator Earth Fault 64S 100% Stator Earth Fault Undervoltage Start * 64S V< Start *

949 100% Stator Earth Fault 64S 100% Stator Earth Fault Overcurrent Start * 64S I>1 Start *

64S 100% St EF Under Resistance Stg 1 Alm


950 100% Stator Earth Fault * 64S Start R<1Alm *
Start
64S 100% St EF Under Resistance Stg 2 Trip
951 100% Stator Earth Fault * 64S R<2 Start *
Start

952 64R Rotor Earth Fault 64R Rotor EF Under Resistance Stg 1 Alm Start * 64R Start R<1Alm * * * *

953 64R Rotor Earth Fault 64R Rotor EF Under Resistance Stg 2 Trip Start * 64R R<2 Start * * * *

954 - Unused
955 - Unused
956 - Unused
957 - Unused
958 - Unused
959 - Unused
960 - Unused
961 - Unused
962 - Unused
963 - Unused
964 - Unused
965 - Unused
966 - Unused
967 - Unused
968 - Unused
969 - Unused
970 - Unused
971 - Unused
972 - Unused
973 - Unused
974 - Unused
975 - Unused
976 - Unused
977 - Unused
978 - Unused
979 - Unused
980 - Unused
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 102

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

981 - Unused
982 - Unused
983 - Unused
984 - Unused
985 - Unused
986 - Unused
987 - Unused
988 - Unused
989 - Unused
990 - Unused
991 - Unused
992 - Unused
993 - Unused
994 - Unused
995 - Unused
996 - Unused
997 - Unused
998 - Unused
999 - Unused
1000 - Unused
1001 - Unused
1002 - Unused
1003 - Unused
1004 - Unused
1005 - Unused
1006 - Unused
1007 - Unused
1008 - Unused
1009 - Unused
1010 - Unused
1011 - Unused
1012 - Unused
1013 - Unused
1014 - Unused
1015 - Unused
1016 - Unused
1017 - Unused
1018 - Unused
1019 - Unused
1020 - Unused
1021 - Unused
1022 - Unused
1023 - Unused
1024 VT Supervision VTS Fast Block * VTS Fast Block * * * * *
1025 VT Supervision VTS Slow Block * VTS Slow Block * * * * *
1026 CT Supervision CTS-1 Block * CTS-1 Block * * * * *
1027 CB Control Control Trip * Control Trip *
1028 CB Control Control Close * Control Close *
1029 CB Control Control Close in Progress * Close in Prog *
1030 Reconnection Reconnection Time Delay Output * Reconnection *
1031 RTD Thermal RTD 1 Alarm * RTD 1 Alarm * * * *
1032 RTD Thermal RTD 2 Alarm * RTD 2 Alarm * * * *
1033 RTD Thermal RTD 3 Alarm * RTD 3 Alarm * * * *
1034 RTD Thermal RTD 4 Alarm * RTD 4 Alarm * * * *
1035 RTD Thermal RTD 5 Alarm * RTD 5 Alarm * * * *
1036 RTD Thermal RTD 6 Alarm * RTD 6 Alarm * * * *
1037 RTD Thermal RTD 7 Alarm * RTD 7 Alarm * * * *
1038 RTD Thermal RTD 8 Alarm * RTD 8 Alarm * * * *
1039 RTD Thermal RTD 9 Alarm * RTD 9 Alarm * * * *
1040 RTD Thermal RTD 10 Alarm * RTD 10 Alarm * * * *
1041 CB Monitoring Composite Lockout Alarm * Lockout Alarm * * * * *
1042 CB Status Monitor 3 ph CB Open * CB Open 3 ph * * * * *
1043 CB Status Monitor 3 ph CB Closed * CB Closed 3 ph * * * * *
1044 Pole Dead All Poles Dead * All Poles Dead * * * * *
1045 Pole Dead Any Pole Dead * Any Pole Dead * * * * *
1046 Pole Dead Phase A Pole Dead * Pole Dead A * * * * *
1047 Pole Dead Phase B Pole Dead * Pole Dead B * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 103

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

1048 Pole Dead Phase C Pole Dead * Pole Dead C * * * * *


1049 - Unused
1050 - Unused
1051 - Unused
1052 - Unused
1053 - Unused
1054 - Unused
1055 - Unused
1056 - Unused
1057 - Unused
1058 - Unused
1059 - Unused
1060 - Unused
1061 - Unused
1062 - Unused
1063 - Unused
1064 - Unused
1065 - Unused
1066 Frequency Tracking Freq High Freq High * * * * *
1067 Frequency Tracking Freq Low Freq Low * * * * *
1068 Frequency Tracking Freq Not Found Freq Not found * * * * *
1069 - Unused
1070 - Unused
1071 - Unused
1072 - Unused
1073 - Unused
1074 CT Supervision CTS-2 Block * CTS-2 Block * * *
64S 100% Stator Earth Fault - System frequency
1075 100% Stator Earth Fault * 64S F Band Block *
in blocking band
1076 100% Stator Earth Fault 64S 100% Stator Earth Fault - Injection failure * 64S Fail *
1077 - Unused
1078 - Unused
1079 - Unused
1080 - Unused
1081 - Unused
1082 - Unused
1083 - Unused
1084 - Unused
1085 - Unused
1086 - Unused
1087 - Unused
1088 - Unused
1089 - Unused
1090 - Unused
1091 - Unused
1092 - Unused
1093 - Unused
1094 - Unused
1095 - Unused
1096 - Unused
1097 - Unused
1098 - Unused
1099 - Unused
1100 - Unused
1101 - Unused
1102 - Unused
1103 - Unused
1104 - Unused
1105 - Unused
1106 - Unused
1107 - Unused
1108 - Unused
1109 - Unused
1110 - Unused
1111 - Unused
1112 - Unused
1113 - Unused
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 104

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

1114 - Unused
1115 - Unused
1116 - Unused
1117 - Unused
1118 - Unused
1119 - Unused
1120 - Unused
1121 - Unused
1122 - Unused
1123 - Unused
1124 - Unused
1125 - Unused
1126 - Unused
1127 - Unused
1128 - Unused
1129 - Unused
1130 - Unused
1131 - Unused
1132 - Unused
1133 - Unused
1134 - Unused
1135 - Unused
1136 - Unused
1137 - Unused
1138 - Unused
1139 - Unused
1140 - Unused
1141 - Unused
1142 - Unused
1143 - Unused
1144 - Unused
1145 - Unused
1146 - Unused
1147 - Unused
1148 - Unused
1149 - Unused
1150 - Unused
1151 - Unused
1152 User Control 1 Control Input 1 * Control Input 1 * * * * *
1153 User Control 2 Control Input 2 * Control Input 2 * * * * *
1154 User Control 3 Control Input 3 * Control Input 3 * * * * *
1155 User Control 4 Control Input 4 * Control Input 4 * * * * *
1156 User Control 5 Control Input 5 * Control Input 5 * * * * *
1157 User Control 6 Control Input 6 * Control Input 6 * * * * *
1158 User Control 7 Control Input 7 * Control Input 7 * * * * *
1159 User Control 8 Control Input 8 * Control Input 8 * * * * *
1160 User Control 9 Control Input 9 * Control Input 9 * * * * *
1161 User Control 10 Control Input 10 * Control Input 10 * * * * *
1162 User Control 11 Control Input 11 * Control Input 11 * * * * *
1163 User Control 12 Control Input 12 * Control Input 12 * * * * *
1164 User Control 13 Control Input 13 * Control Input 13 * * * * *
1165 User Control 14 Control Input 14 * Control Input 14 * * * * *
1166 User Control 15 Control Input 15 * Control Input 15 * * * * *
1167 User Control 16 Control Input 16 * Control Input 16 * * * * *
1168 User Control 17 Control Input 17 * Control Input 17 * * * * *
1169 User Control 18 Control Input 18 * Control Input 18 * * * * *
1170 User Control 19 Control Input 19 * Control Input 19 * * * * *
1171 User Control 20 Control Input 20 * Control Input 20 * * * * *
1172 User Control 21 Control Input 21 * Control Input 21 * * * * *
1173 User Control 22 Control Input 22 * Control Input 22 * * * * *
1174 User Control 23 Control Input 23 * Control Input 23 * * * * *
1175 User Control 24 Control Input 24 * Control Input 24 * * * * *
1176 User Control 25 Control Input 25 * Control Input 25 * * * * *
1177 User Control 26 Control Input 26 * Control Input 26 * * * * *
1178 User Control 27 Control Input 27 * Control Input 27 * * * * *
1179 User Control 28 Control Input 28 * Control Input 28 * * * * *
1180 User Control 29 Control Input 29 * Control Input 29 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 105

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

1181 User Control 30 Control Input 30 * Control Input 30 * * * * *


1182 User Control 31 Control Input 31 * Control Input 31 * * * * *
1183 User Control 32 Control Input 32 * Control Input 32 * * * * *
1184 GOOSE Input Command Virtual Input 01 * Virtual Input 01 * * * * *
1185 GOOSE Input Command Virtual Input 02 * Virtual Input 02 * * * * *
1186 GOOSE Input Command Virtual Input 03 * Virtual Input 03 * * * * *
1187 GOOSE Input Command Virtual Input 04 * Virtual Input 04 * * * * *
1188 GOOSE Input Command Virtual Input 05 * Virtual Input 05 * * * * *
1189 GOOSE Input Command Virtual Input 06 * Virtual Input 06 * * * * *
1190 GOOSE Input Command Virtual Input 07 * Virtual Input 07 * * * * *
1191 GOOSE Input Command Virtual Input 08 * Virtual Input 08 * * * * *
1192 GOOSE Input Command Virtual Input 09 * Virtual Input 09 * * * * *
1193 GOOSE Input Command Virtual Input 10 * Virtual Input 10 * * * * *
1194 GOOSE Input Command Virtual Input 11 * Virtual Input 11 * * * * *
1195 GOOSE Input Command Virtual Input 12 * Virtual Input 12 * * * * *
1196 GOOSE Input Command Virtual Input 13 * Virtual Input 13 * * * * *
1197 GOOSE Input Command Virtual Input 14 * Virtual Input 14 * * * * *
1198 GOOSE Input Command Virtual Input 15 * Virtual Input 15 * * * * *
1199 GOOSE Input Command Virtual Input 16 * Virtual Input 16 * * * * *
1200 GOOSE Input Command Virtual Input 17 * Virtual Input 17 * * * * *
1201 GOOSE Input Command Virtual Input 18 * Virtual Input 18 * * * * *
1202 GOOSE Input Command Virtual Input 19 * Virtual Input 19 * * * * *
1203 GOOSE Input Command Virtual Input 20 * Virtual Input 20 * * * * *
1204 GOOSE Input Command Virtual Input 21 * Virtual Input 21 * * * * *
1205 GOOSE Input Command Virtual Input 22 * Virtual Input 22 * * * * *
1206 GOOSE Input Command Virtual Input 23 * Virtual Input 23 * * * * *
1207 GOOSE Input Command Virtual Input 24 * Virtual Input 24 * * * * *
1208 GOOSE Input Command Virtual Input 25 * Virtual Input 25 * * * * *
1209 GOOSE Input Command Virtual Input 26 * Virtual Input 26 * * * * *
1210 GOOSE Input Command Virtual Input 27 * Virtual Input 27 * * * * *
1211 GOOSE Input Command Virtual Input 28 * Virtual Input 28 * * * * *
1212 GOOSE Input Command Virtual Input 29 * Virtual Input 29 * * * * *
1213 GOOSE Input Command Virtual Input 30 * Virtual Input 30 * * * * *
1214 GOOSE Input Command Virtual Input 31 * Virtual Input 31 * * * * *
1215 GOOSE Input Command Virtual Input 32 * Virtual Input 32 * * * * *
1216 PSL Virtual Output 01 * Virtual Output01 * * * * *
1217 PSL Virtual Output 02 * Virtual Output02 * * * * *
1218 PSL Virtual Output 03 * Virtual Output03 * * * * *
1219 PSL Virtual Output 04 * Virtual Output04 * * * * *
1220 PSL Virtual Output 05 * Virtual Output05 * * * * *
1221 PSL Virtual Output 06 * Virtual Output06 * * * * *
1222 PSL Virtual Output 07 * Virtual Output07 * * * * *
1223 PSL Virtual Output 08 * Virtual Output08 * * * * *
1224 PSL Virtual Output 09 * Virtual Output09 * * * * *
1225 PSL Virtual Output 10 * Virtual Output10 * * * * *
1226 PSL Virtual Output 11 * Virtual Output11 * * * * *
1227 PSL Virtual Output 12 * Virtual Output12 * * * * *
1228 PSL Virtual Output 13 * Virtual Output13 * * * * *
1229 PSL Virtual Output 14 * Virtual Output14 * * * * *
1230 PSL Virtual Output 15 * Virtual Output15 * * * * *
1231 PSL Virtual Output 16 * Virtual Output16 * * * * *
1232 PSL Virtual Output 17 * Virtual Output17 * * * * *
1233 PSL Virtual Output 18 * Virtual Output18 * * * * *
1234 PSL Virtual Output 19 * Virtual Output19 * * * * *
1235 PSL Virtual Output 20 * Virtual Output20 * * * * *
1236 PSL Virtual Output 21 * Virtual Output21 * * * * *
1237 PSL Virtual Output 22 * Virtual Output22 * * * * *
1238 PSL Virtual Output 23 * Virtual Output23 * * * * *
1239 PSL Virtual Output 24 * Virtual Output24 * * * * *
1240 PSL Virtual Output 25 * Virtual Output25 * * * * *
1241 PSL Virtual Output 26 * Virtual Output26 * * * * *
1242 PSL Virtual Output 27 * Virtual Output27 * * * * *
1243 PSL Virtual Output 28 * Virtual Output28 * * * * *
1244 PSL Virtual Output 29 * Virtual Output29 * * * * *
1245 PSL Virtual Output 30 * Virtual Output30 * * * * *
1246 PSL Virtual Output 31 * Virtual Output31 * * * * *
1247 PSL Virtual Output 32 * Virtual Output32 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 106

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

1248 PSL PSL Internal Connection PSL Int. 1 * * * * *


1249 PSL PSL Internal Connection PSL Int. 2 * * * * *
1250 PSL PSL Internal Connection PSL Int. 3 * * * * *
1251 PSL PSL Internal Connection PSL Int. 4 * * * * *
1252 PSL PSL Internal Connection PSL Int. 5 * * * * *
1253 PSL PSL Internal Connection PSL Int. 6 * * * * *
1254 PSL PSL Internal Connection PSL Int. 7 * * * * *
1255 PSL PSL Internal Connection PSL Int. 8 * * * * *
1256 PSL PSL Internal Connection PSL Int. 9 * * * * *
1257 PSL PSL Internal Connection PSL Int. 10 * * * * *
1258 PSL PSL Internal Connection PSL Int. 11 * * * * *
1259 PSL PSL Internal Connection PSL Int. 12 * * * * *
1260 PSL PSL Internal Connection PSL Int. 13 * * * * *
1261 PSL PSL Internal Connection PSL Int. 14 * * * * *
1262 PSL PSL Internal Connection PSL Int. 15 * * * * *
1263 PSL PSL Internal Connection PSL Int. 16 * * * * *
1264 PSL PSL Internal Connection PSL Int. 17 * * * * *
1265 PSL PSL Internal Connection PSL Int. 18 * * * * *
1266 PSL PSL Internal Connection PSL Int. 19 * * * * *
1267 PSL PSL Internal Connection PSL Int. 20 * * * * *
1268 PSL PSL Internal Connection PSL Int. 21 * * * * *
1269 PSL PSL Internal Connection PSL Int. 22 * * * * *
1270 PSL PSL Internal Connection PSL Int. 23 * * * * *
1271 PSL PSL Internal Connection PSL Int. 24 * * * * *
1272 PSL PSL Internal Connection PSL Int. 25 * * * * *
1273 PSL PSL Internal Connection PSL Int. 26 * * * * *
1274 PSL PSL Internal Connection PSL Int. 27 * * * * *
1275 PSL PSL Internal Connection PSL Int. 28 * * * * *
1276 PSL PSL Internal Connection PSL Int. 29 * * * * *
1277 PSL PSL Internal Connection PSL Int. 30 * * * * *
1278 PSL PSL Internal Connection PSL Int. 31 * * * * *
1279 PSL PSL Internal Connection PSL Int. 32 * * * * *
1280 PSL PSL Internal Connection PSL Int. 33 * * * * *
1281 PSL PSL Internal Connection PSL Int. 34 * * * * *
1282 PSL PSL Internal Connection PSL Int. 35 * * * * *
1283 PSL PSL Internal Connection PSL Int. 36 * * * * *
1284 PSL PSL Internal Connection PSL Int. 37 * * * * *
1285 PSL PSL Internal Connection PSL Int. 38 * * * * *
1286 PSL PSL Internal Connection PSL Int. 39 * * * * *
1287 PSL PSL Internal Connection PSL Int. 40 * * * * *
1288 PSL PSL Internal Connection PSL Int. 41 * * * * *
1289 PSL PSL Internal Connection PSL Int. 42 * * * * *
1290 PSL PSL Internal Connection PSL Int. 43 * * * * *
1291 PSL PSL Internal Connection PSL Int. 44 * * * * *
1292 PSL PSL Internal Connection PSL Int. 45 * * * * *
1293 PSL PSL Internal Connection PSL Int. 46 * * * * *
1294 PSL PSL Internal Connection PSL Int. 47 * * * * *
1295 PSL PSL Internal Connection PSL Int. 48 * * * * *
1296 PSL PSL Internal Connection PSL Int. 49 * * * * *
1297 PSL PSL Internal Connection PSL Int. 50 * * * * *
1298 PSL PSL Internal Connection PSL Int. 51 * * * * *
1299 PSL PSL Internal Connection PSL Int. 52 * * * * *
1300 PSL PSL Internal Connection PSL Int. 53 * * * * *
1301 PSL PSL Internal Connection PSL Int. 54 * * * * *
1302 PSL PSL Internal Connection PSL Int. 55 * * * * *
1303 PSL PSL Internal Connection PSL Int. 56 * * * * *
1304 PSL PSL Internal Connection PSL Int. 57 * * * * *
1305 PSL PSL Internal Connection PSL Int. 58 * * * * *
1306 PSL PSL Internal Connection PSL Int. 59 * * * * *
1307 PSL PSL Internal Connection PSL Int. 60 * * * * *
1308 PSL PSL Internal Connection PSL Int. 61 * * * * *
1309 PSL PSL Internal Connection PSL Int. 62 * * * * *
1310 PSL PSL Internal Connection PSL Int. 63 * * * * *
1311 PSL PSL Internal Connection PSL Int. 64 * * * * *
1312 PSL PSL Internal Connection PSL Int. 65 * * * * *
1313 PSL PSL Internal Connection PSL Int. 66 * * * * *
1314 PSL PSL Internal Connection PSL Int. 67 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 107

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

1315 PSL PSL Internal Connection PSL Int. 68 * * * * *


1316 PSL PSL Internal Connection PSL Int. 69 * * * * *
1317 PSL PSL Internal Connection PSL Int. 70 * * * * *
1318 PSL PSL Internal Connection PSL Int. 71 * * * * *
1319 PSL PSL Internal Connection PSL Int. 72 * * * * *
1320 PSL PSL Internal Connection PSL Int. 73 * * * * *
1321 PSL PSL Internal Connection PSL Int. 74 * * * * *
1322 PSL PSL Internal Connection PSL Int. 75 * * * * *
1323 PSL PSL Internal Connection PSL Int. 76 * * * * *
1324 PSL PSL Internal Connection PSL Int. 77 * * * * *
1325 PSL PSL Internal Connection PSL Int. 78 * * * * *
1326 PSL PSL Internal Connection PSL Int. 79 * * * * *
1327 PSL PSL Internal Connection PSL Int. 80 * * * * *
1328 PSL PSL Internal Connection PSL Int. 81 * * * * *
1329 PSL PSL Internal Connection PSL Int. 82 * * * * *
1330 PSL PSL Internal Connection PSL Int. 83 * * * * *
1331 PSL PSL Internal Connection PSL Int. 84 * * * * *
1332 PSL PSL Internal Connection PSL Int. 85 * * * * *
1333 PSL PSL Internal Connection PSL Int. 86 * * * * *
1334 PSL PSL Internal Connection PSL Int. 87 * * * * *
1335 PSL PSL Internal Connection PSL Int. 88 * * * * *
1336 PSL PSL Internal Connection PSL Int. 89 * * * * *
1337 PSL PSL Internal Connection PSL Int. 90 * * * * *
1338 PSL PSL Internal Connection PSL Int. 91 * * * * *
1339 PSL PSL Internal Connection PSL Int. 92 * * * * *
1340 PSL PSL Internal Connection PSL Int. 93 * * * * *
1341 PSL PSL Internal Connection PSL Int. 94 * * * * *
1342 PSL PSL Internal Connection PSL Int. 95 * * * * *
1343 PSL PSL Internal Connection PSL Int. 96 * * * * *
1344 PSL PSL Internal Connection PSL Int. 97 * * * * *
1345 PSL PSL Internal Connection PSL Int. 98 * * * * *
1346 PSL PSL Internal Connection PSL Int. 99 * * * * *
1347 PSL PSL Internal Connection PSL Int. 100 * * * * *
1348 PSL PSL Internal Connection PSL Int. 101 * * * * *
1349 PSL PSL Internal Connection PSL Int. 102 * * * * *
1350 PSL PSL Internal Connection PSL Int. 103 * * * * *
1351 PSL PSL Internal Connection PSL Int. 104 * * * * *
1352 PSL PSL Internal Connection PSL Int. 105 * * * * *
1353 PSL PSL Internal Connection PSL Int. 106 * * * * *
1354 PSL PSL Internal Connection PSL Int. 107 * * * * *
1355 PSL PSL Internal Connection PSL Int. 108 * * * * *
1356 PSL PSL Internal Connection PSL Int. 109 * * * * *
1357 PSL PSL Internal Connection PSL Int. 110 * * * * *
1358 PSL PSL Internal Connection PSL Int. 111 * * * * *
1359 PSL PSL Internal Connection PSL Int. 112 * * * * *
1360 PSL PSL Internal Connection PSL Int. 113 * * * * *
1361 PSL PSL Internal Connection PSL Int. 114 * * * * *
1362 PSL PSL Internal Connection PSL Int. 115 * * * * *
1363 PSL PSL Internal Connection PSL Int. 116 * * * * *
1364 PSL PSL Internal Connection PSL Int. 117 * * * * *
1365 PSL PSL Internal Connection PSL Int. 118 * * * * *
1366 PSL PSL Internal Connection PSL Int. 119 * * * * *
1367 PSL PSL Internal Connection PSL Int. 120 * * * * *
1368 PSL PSL Internal Connection PSL Int. 121 * * * * *
1369 PSL PSL Internal Connection PSL Int. 122 * * * * *
1370 PSL PSL Internal Connection PSL Int. 123 * * * * *
1371 PSL PSL Internal Connection PSL Int. 124 * * * * *
1372 PSL PSL Internal Connection PSL Int. 125 * * * * *
1373 PSL PSL Internal Connection PSL Int. 126 * * * * *
1374 PSL PSL Internal Connection PSL Int. 127 * * * * *
1375 PSL PSL Internal Connection PSL Int. 128 * * * * *
1376 PSL PSL Internal Connection PSL Int. 129 * * * * *
1377 PSL PSL Internal Connection PSL Int. 130 * * * * *
1378 PSL PSL Internal Connection PSL Int. 131 * * * * *
1379 PSL PSL Internal Connection PSL Int. 132 * * * * *
1380 PSL PSL Internal Connection PSL Int. 133 * * * * *
1381 PSL PSL Internal Connection PSL Int. 134 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 108

DDB no. Source Description Event logged English text P341 P342 P343 P344 P345

1382 PSL PSL Internal Connection PSL Int. 135 * * * * *


1383 PSL PSL Internal Connection PSL Int. 136 * * * * *
1384 PSL PSL Internal Connection PSL Int. 137 * * * * *
1385 PSL PSL Internal Connection PSL Int. 138 * * * * *
1386 PSL PSL Internal Connection PSL Int. 139 * * * * *
1387 PSL PSL Internal Connection PSL Int. 140 * * * * *
1388 PSL PSL Internal Connection PSL Int. 141 * * * * *
1389 PSL PSL Internal Connection PSL Int. 142 * * * * *
1390 PSL PSL Internal Connection PSL Int. 143 * * * * *
1391 PSL PSL Internal Connection PSL Int. 144 * * * * *
1392 PSL PSL Internal Connection PSL Int. 145 * * * * *
1393 PSL PSL Internal Connection PSL Int. 146 * * * * *
1394 PSL PSL Internal Connection PSL Int. 147 * * * * *
1395 PSL PSL Internal Connection PSL Int. 148 * * * * *
1396 PSL PSL Internal Connection PSL Int. 149 * * * * *
1397 PSL PSL Internal Connection PSL Int. 150 * * * * *
1398 PSL PSL Internal Connection PSL Int. 151 * * * * *
1399 PSL PSL Internal Connection PSL Int. 152 * * * * *
1400 PSL PSL Internal Connection PSL Int. 153 * * * * *
1401 PSL PSL Internal Connection PSL Int. 154 * * * * *
1402 PSL PSL Internal Connection PSL Int. 155 * * * * *
1403 PSL PSL Internal Connection PSL Int. 156 * * * * *
1404 PSL PSL Internal Connection PSL Int. 157 * * * * *
1405 PSL PSL Internal Connection PSL Int. 158 * * * * *
1406 PSL PSL Internal Connection PSL Int. 159 * * * * *
1407 PSL PSL Internal Connection PSL Int. 160 * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 109

Event record specification for courier and MODBUS interfaces

Event Model Courier events MODBUS events

Options Event Event type MODBUS Additional

P341

P342

P343

P344

P345
Name Cell ref. extraction Text Value (Binary Flag) Bit (See G13) Event value 3x10008 register Event index 3x10011 data
column 3x10007 3x10010 3x10012
Opto-Isolated Status Input Events * * * * * 0020 Status Input user label + ON/OFF 32 bit binary flag value 5 32 bit binary flag value 311025 0 0
Relay Contact Output Events * * * * * 0021 Relay Contact user label + ON/OFF 32 bit binary flag value 4 32 bit binary flag value 311023 0 0
Alarm Status 1 Events (alarms 1 - 32):
Not Used * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000000001 0 - 00000000000000000000000000000001 30011 Bit 15=state, bits 0-14=0 0
Not Used * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000000010 1 - 00000000000000000000000000000010 30011 Bit 15=state, bits 0-14=1 0
SG-DDB Invalid * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000000100 2 2 or 3 00000000000000000000000000000100 30011 Bit 15=state, bits 0-14=2 0
Prot'n Disabled * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000001000 3 2 or 3 00000000000000000000000000001000 30011 Bit 15=state, bits 0-14=3 0
VT Fail Alarm * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000010000 4 2 or 3 00000000000000000000000000010000 30011 Bit 15=state, bits 0-14=4 0
CT-1 Fail Alarm * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000100000 5 2 or 3 00000000000000000000000000100000 30011 Bit 15=state, bits 0-14=5 0
CB Fail * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000001000000 6 0 or 1 00000000000000000000000001000000 30011 Bit 15=state, bits 0-14=6 0
I^ Maint Alarm * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000010000000 7 2 or 3 00000000000000000000000010000000 30011 Bit 15=state, bits 0-14=7 0
I^ Maint Lockout * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000100000000 8 2 or 3 00000000000000000000000100000000 30011 Bit 15=state, bits 0-14=8 0
CB OPs Maint * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000001000000000 9 2 or 3 00000000000000000000001000000000 30011 Bit 15=state, bits 0-14=9 0
CB OPs Lock * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000010000000000 10 2 or 3 00000000000000000000010000000000 30011 Bit 15=state, bits 0-14=10 0
CB Time Maint * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000100000000000 11 2 or 3 00000000000000000000100000000000 30011 Bit 15=state, bits 0-14=11 0
CB Time Lockout * * * * * 0022 Alarm Name + ON/OFF 00000000000000000001000000000000 12 2 or 3 00000000000000000001000000000000 30011 Bit 15=state, bits 0-14=12 0
Fault Freq Lock * * * * * 0022 Alarm Name + ON/OFF 00000000000000000010000000000000 13 2 or 3 00000000000000000010000000000000 30011 Bit 15=state, bits 0-14=13 0
CB Status Alarm * * * * * 0022 Alarm Name + ON/OFF 00000000000000000100000000000000 14 0 or 1 00000000000000000100000000000000 30011 Bit 15=state, bits 0-14=14 0
CB Trip Fail * 0022 Alarm Name + ON/OFF 00000000000000001000000000000000 15 0 or 1 00000000000000001000000000000000 30011 Bit 15=state, bits 0-14=15 0
CB Close Fail * 0022 Alarm Name + ON/OFF 00000000000000010000000000000000 16 0 or 1 00000000000000010000000000000000 30011 Bit 15=state, bits 0-14=16 0
Man CB Unhealthy * 0022 Alarm Name + ON/OFF 00000000000000100000000000000000 17 0 or 1 00000000000000100000000000000000 30011 Bit 15=state, bits 0-14=17 0
F out of Range * 0022 Alarm Name + ON/OFF 00000000000001000000000000000000 18 2 or 3 00000000000001000000000000000000 30011 Bit 15=state, bits 0-14=18 0
NPS thermal Alm * * * * 0022 Alarm Name + ON/OFF 00000000000001000000000000000000 18 0 or 1 00000000000001000000000000000000 30011 Bit 15=state, bits 0-14=18 0
Thermal Alarm * * * * * 0022 Alarm Name + ON/OFF 00000000000010000000000000000000 19 0 or 1 00000000000010000000000000000000 30011 Bit 15=state, bits 0-14=19 0
V/Hz Alarm * * * * * 0022 Alarm Name + ON/OFF 00000000000100000000000000000000 20 0 or 1 00000000000100000000000000000000 30011 Bit 15=state, bits 0-14=20 0
Field Fail Alarm * * * * * 0022 Alarm Name + ON/OFF 00000000001000000000000000000000 21 0 or 1 00000000001000000000000000000000 30011 Bit 15=state, bits 0-14=21 0
RTD Thermal Alm * * * * * 0022 Alarm Name + ON/OFF 00000000010000000000000000000000 22 0 or 1 00000000010000000000000000000000 30011 Bit 15=state, bits 0-14=22 0
RTD Open Cct * * * * * 0022 Alarm Name + ON/OFF 00000000100000000000000000000000 23 0 or 1 00000000100000000000000000000000 30011 Bit 15=state, bits 0-14=23 0
RTD short Cct * * * * * 0022 Alarm Name + ON/OFF 00000001000000000000000000000000 24 0 or 1 00000001000000000000000000000000 30011 Bit 15=state, bits 0-14=24 0
RTD Data Error * * * * * 0022 Alarm Name + ON/OFF 00000010000000000000000000000000 25 0 or 1 00000010000000000000000000000000 30011 Bit 15=state, bits 0-14=25 0
RTD Board Fail * * * * * 0022 Alarm Name + ON/OFF 00000100000000000000000000000000 26 0 or 1 00000100000000000000000000000000 30011 Bit 15=state, bits 0-14=26 0
Freq Prot Alm * * * * * 0022 Alarm Name + ON/OFF 00001000000000000000000000000000 27 0 or 1 00001000000000000000000000000000 30011 Bit 15=state, bits 0-14=27 0
Voltage Prot Alm * * * * * 0022 Alarm Name + ON/OFF 00010000000000000000000000000000 28 0 or 1 00010000000000000000000000000000 30011 Bit 15=state, bits 0-14=28 0
CT-2 Fail Alarm * * * 0022 Alarm Name + ON/OFF 00100000000000000000000000000000 29 2 or 3 00100000000000000000000000000000 30011 Bit 15=state, bits 0-14=29 0
64S R<1 Alarm * * * * * 0022 Alarm Name + ON/OFF 01000000000000000000000000000000 30 0 or 1 01000000000000000000000000000000 30011 Bit 15=state, bits 0-14=30 0
64S Fail Alarm * * * * * 0022 Alarm Name + ON/OFF 10000000000000000000000000000000 31 2 or 3 10000000000000000000000000000000 30011 Bit 15=state, bits 0-14=31 0
Alarm Status 2 Events (alarms 33 - 64):
CL Card I/P Fail * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000000001 0 0 or 1 00000000000000000000000000000001 30013 Bit 15=state, bits 0-14=32 0
CL Card O/P Fail * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000000010 1 0 or 1 00000000000000000000000000000010 30013 Bit 15=state, bits 0-14=33 0
CL Input 1 Alarm * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000000100 2 0 or 1 00000000000000000000000000000100 30013 Bit 15=state, bits 0-14=34 0
CL Input 2 Alarm * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000001000 3 0 or 1 00000000000000000000000000001000 30013 Bit 15=state, bits 0-14=35 0
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 110

Event Model Courier events MODBUS events

Options Event Event type MODBUS Additional

P341

P342

P343

P344

P345
Name Cell ref. extraction Text Value (Binary Flag) Bit (See G13) Event value 3x10008 register Event index 3x10011 data
column 3x10007 3x10010 3x10012
CL Input 3 Alarm * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000010000 4 0 or 1 00000000000000000000000000010000 30013 Bit 15=state, bits 0-14=36 0
CL Input 4 Alarm * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000100000 5 0 or 1 00000000000000000000000000100000 30013 Bit 15=state, bits 0-14=37 0
CLI1 I< Fail Alm * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000001000000 6 0 or 1 00000000000000000000000001000000 30013 Bit 15=state, bits 0-14=38 0
CLI2 I< Fail Alm * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000010000000 7 0 or 1 00000000000000000000000010000000 30013 Bit 15=state, bits 0-14=39 0
CLI3 I< Fail Alm * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000100000000 8 0 or 1 00000000000000000000000100000000 30013 Bit 15=state, bits 0-14=40 0
CLI4 I< Fail Alm * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000001000000000 9 0 or 1 00000000000000000000001000000000 30013 Bit 15=state, bits 0-14=41 0
64R R<1 Alarm * * * * 0051 Alarm Name + ON/OFF 00000000000000000000010000000000 10 - 00000000000000000000010000000000 30013 Bit 15=state, bits 0-14=42 0
64R CL I/P Fail * * * * 0051 Alarm Name + ON/OFF 00000000000000000000100000000000 11 - 00000000000000000000100000000000 30013 Bit 15=state, bits 0-14=43 0
Not Used * * * * * 0051 Alarm Name + ON/OFF 00000000000000000001000000000000 12 - 00000000000000000001000000000000 30013 Bit 15=state, bits 0-14=44 0
Not Used * * * * * 0051 Alarm Name + ON/OFF 00000000000000000010000000000000 13 - 00000000000000000010000000000000 30013 Bit 15=state, bits 0-14=45 0
Not Used * * * * * 0051 Alarm Name + ON/OFF 00000000000000000100000000000000 14 - 00000000000000000100000000000000 30013 Bit 15=state, bits 0-14=46 0
Not Used * * * * * 0051 Alarm Name + ON/OFF 00000000000000001000000000000000 15 - 00000000000000001000000000000000 30013 Bit 15=state, bits 0-14=47 0
MR User Alarm 16 * * * * * 0051 Alarm Name + ON/OFF 00000000000000010000000000000000 16 0 or 1 00000000000000010000000000000000 30013 Bit 15=state, bits 0-14=48 0
MR User Alarm 15 * * * * * 0051 Alarm Name + ON/OFF 00000000000000100000000000000000 17 0 or 1 00000000000000100000000000000000 30013 Bit 15=state, bits 0-14=49 0
MR User Alarm 14 * * * * * 0051 Alarm Name + ON/OFF 00000000000001000000000000000000 18 0 or 1 00000000000001000000000000000000 30013 Bit 15=state, bits 0-14=50 0
MR User Alarm 13 * * * * * 0051 Alarm Name + ON/OFF 00000000000010000000000000000000 19 0 or 1 00000000000010000000000000000000 30013 Bit 15=state, bits 0-14=51 0
MR User Alarm 12 * * * * * 0051 Alarm Name + ON/OFF 00000000000100000000000000000000 20 0 or 1 00000000000100000000000000000000 30013 Bit 15=state, bits 0-14=52 0
MR User Alarm 11 * * * * * 0051 Alarm Name + ON/OFF 00000000001000000000000000000000 21 0 or 1 00000000001000000000000000000000 30013 Bit 15=state, bits 0-14=53 0
MR User Alarm 10 * * * * * 0051 Alarm Name + ON/OFF 00000000010000000000000000000000 22 0 or 1 00000000010000000000000000000000 30013 Bit 15=state, bits 0-14=54 0
MR User Alarm 9 * * * * * 0051 Alarm Name + ON/OFF 00000000100000000000000000000000 23 0 or 1 00000000100000000000000000000000 30013 Bit 15=state, bits 0-14=55 0
MR User Alarm 8 * * * * * 0051 Alarm Name + ON/OFF 00000001000000000000000000000000 24 0 or 1 00000001000000000000000000000000 30013 Bit 15=state, bits 0-14=56 0
MR User Alarm 7 * * * * * 0051 Alarm Name + ON/OFF 00000010000000000000000000000000 25 0 or 1 00000010000000000000000000000000 30013 Bit 15=state, bits 0-14=57 0
MR User Alarm 6 * * * * * 0051 Alarm Name + ON/OFF 00000100000000000000000000000000 26 0 or 1 00000100000000000000000000000000 30013 Bit 15=state, bits 0-14=58 0
MR User Alarm 5 * * * * * 0051 Alarm Name + ON/OFF 00001000000000000000000000000000 27 0 or 1 00001000000000000000000000000000 30013 Bit 15=state, bits 0-14=59 0
SR User Alarm 4 * * * * * 0051 Alarm Name + ON/OFF 00010000000000000000000000000000 28 2 or 3 00010000000000000000000000000000 30013 Bit 15=state, bits 0-14=60 0
SR User Alarm 3 * * * * * 0051 Alarm Name + ON/OFF 00100000000000000000000000000000 29 2 or 3 00100000000000000000000000000000 30013 Bit 15=state, bits 0-14=61 0
SR User Alarm 2 * * * * * 0051 Alarm Name + ON/OFF 01000000000000000000000000000000 30 2 or 3 01000000000000000000000000000000 30013 Bit 15=state, bits 0-14=62 0
SR User Alarm 1 * * * * * 0051 Alarm Name + ON/OFF 10000000000000000000000000000000 31 2 or 3 10000000000000000000000000000000 30013 Bit 15=state, bits 0-14=63 0
Alarm Status 3 Events (alarms 65 - 96):
Battery Fail * * * * * 0052 Alarm Name + ON/OFF 00000000000000000000000000000001 0 2 or 3 00000000000000000000000000000001 30015 Bit 15=state, bits 0-14=64 0
Field Volt Fail * * * * * 0052 Alarm Name + ON/OFF 00000000000000000000000000000010 1 2 or 3 00000000000000000000000000000010 30015 Bit 15=state, bits 0-14=65 0
Rear Comm 2 Fail InterMiCOM 0052 Alarm Name + ON/OFF 00000000000000000000000000000100 2 2 or 3 00000000000000000000000000000100 30015 Bit 15=state, bits 0-14=66 0
GOOSE IED Absent * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000000001000 3 2 or 3 00000000000000000000000000001000 30015 Bit 15=state, bits 0-14=67 0
NIC Not Fitted * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000000010000 4 2 or 3 00000000000000000000000000010000 30015 Bit 15=state, bits 0-14=68 0
NIC No Response * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000000100000 5 2 or 3 00000000000000000000000000100000 30015 Bit 15=state, bits 0-14=69 0
NIC Fatal Error * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000001000000 6 2 or 3 00000000000000000000000001000000 30015 Bit 15=state, bits 0-14=70 0
NIC Soft. Reload * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000010000000 7 2 or 3 00000000000000000000000010000000 30015 Bit 15=state, bits 0-14=71 0
Bad TCP/IP Cfg. * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000100000000 8 2 or 3 00000000000000000000000100000000 30015 Bit 15=state, bits 0-14=72 0
Bad OSI Config. * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000001000000000 9 2 or 3 00000000000000000000001000000000 30015 Bit 15=state, bits 0-14=73 0
NIC Link Fail * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000010000000000 10 2 or 3 00000000000000000000010000000000 30015 Bit 15=state, bits 0-14=74 0
NIC SW Mis-Match * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000100000000000 11 2 or 3 00000000000000000000100000000000 30015 Bit 15=state, bits 0-14=75 0
IP Addr Conflict * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000001000000000000 12 2 or 3 00000000000000000001000000000000 30015 Bit 15=state, bits 0-14=76 0
Unused 0052 Alarm Name + ON/OFF 00000000000000000010000000000000 13 - 00000000000000000010000000000000 30015 Bit 15=state, bits 0-14=77 0
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 111

Event Model Courier events MODBUS events

Options Event Event type MODBUS Additional

P341

P342

P343

P344

P345
Name Cell ref. extraction Text Value (Binary Flag) Bit (See G13) Event value 3x10008 register Event index 3x10011 data
column 3x10007 3x10010 3x10012
Unused 0052 Alarm Name + ON/OFF 00000000000000000100000000000000 14 - 00000000000000000100000000000000 30015 Bit 15=state, bits 0-14=78 0
Unused 0052 Alarm Name + ON/OFF 00000000000000001000000000000000 15 - 00000000000000001000000000000000 30015 Bit 15=state, bits 0-14=79 0
Unused 0052 Alarm Name + ON/OFF 00000000000000010000000000000000 16 - 00000000000000010000000000000000 30015 Bit 15=state, bits 0-14=80 0
Unused 0052 Alarm Name + ON/OFF 00000000000000100000000000000000 17 - 00000000000000100000000000000000 30015 Bit 15=state, bits 0-14=81 0
Unused 0052 Alarm Name + ON/OFF 00000000000001000000000000000000 18 - 00000000000001000000000000000000 30015 Bit 15=state, bits 0-14=82 0
Unused 0052 Alarm Name + ON/OFF 00000000000010000000000000000000 19 - 00000000000010000000000000000000 30015 Bit 15=state, bits 0-14=83 0
Unused 0052 Alarm Name + ON/OFF 00000000000100000000000000000000 20 - 00000000000100000000000000000000 30015 Bit 15=state, bits 0-14=84 0
Unused 0052 Alarm Name + ON/OFF 00000000001000000000000000000000 21 - 00000000001000000000000000000000 30015 Bit 15=state, bits 0-14=85 0
Unused 0052 Alarm Name + ON/OFF 00000000010000000000000000000000 22 - 00000000010000000000000000000000 30015 Bit 15=state, bits 0-14=86 0
Unused 0052 Alarm Name + ON/OFF 00000000100000000000000000000000 23 - 00000000100000000000000000000000 30015 Bit 15=state, bits 0-14=87 0
Unused 0052 Alarm Name + ON/OFF 00000001000000000000000000000000 24 - 00000001000000000000000000000000 30015 Bit 15=state, bits 0-14=88 0
Unused 0052 Alarm Name + ON/OFF 00000010000000000000000000000000 25 - 00000010000000000000000000000000 30015 Bit 15=state, bits 0-14=89 0
Unused 0052 Alarm Name + ON/OFF 00000100000000000000000000000000 26 - 00000100000000000000000000000000 30015 Bit 15=state, bits 0-14=90 0
Unused 0052 Alarm Name + ON/OFF 00001000000000000000000000000000 27 - 00001000000000000000000000000000 30015 Bit 15=state, bits 0-14=91 0
Unused 0052 Alarm Name + ON/OFF 00010000000000000000000000000000 28 - 00010000000000000000000000000000 30015 Bit 15=state, bits 0-14=92 0
Unused 0052 Alarm Name + ON/OFF 00100000000000000000000000000000 29 - 00100000000000000000000000000000 30015 Bit 15=state, bits 0-14=93 0
Unused 0052 Alarm Name + ON/OFF 01000000000000000000000000000000 30 - 01000000000000000000000000000000 30015 Bit 15=state, bits 0-14=94 0
Unused 0052 Alarm Name + ON/OFF 10000000000000000000000000000000 31 - 10000000000000000000000000000000 30015 Bit 15=state, bits 0-14=95 0
Protection Events * * * * * 0F26 - 0F3F DDB Signal Name + ON/OFF 32bit Binary Flag of the revelant packed DDB 6 32 bit binary flag value 311027 to 311109 Bit 15=state, bits 0-14=DDB ID 0
Fault Records * * * * * B000 Fault Record 8 0 0 0 1
Maintenance Record * * * * * B100 Maint Record 9 0 0 0 2
General Events:
Alarm log cleared * * * * * FFFF Alarms Cleared 0 7 0 0 0 0
Event log cleared * * * * * 0B01 Events Cleared 1 7 1 0 0 0
Fault log cleared * * * * * 0B02 Faults Cleared 2 7 2 0 0 0
Maintenance log cleared * * * * * 0B03 Maint Cleared 3 7 3 0 0 0
Front panel user interface password unlocked * * * * * 0002 PW Unlocked UI 4 7 4 0 0 0
Front panel user interface password invalid * * * * * 0002 PW Invalid UI 5 7 5 0 0 0

Front panel user interface password level 1


* * * * * 00D2 PW1 Modified UI 6 7 6 0 0 0
modified

Front panel user interface password level 2


* * * * * 00D3 PW2 Modified UI 7 7 7 0 0 0
modified

Front panel user interface password expired * * * * * 0002 PW Expired UI 8 7 8 0 0 0


Front port password unlocked * * * * * 0002 PW Unlocked F 9 7 9 0 0 0
Front port password invalid * * * * * 0002 PW Invalid F 10 7 10 0 0 0
Front port password level 1 modified * * * * * 00D2 PW1 Modified F 11 7 11 0 0 0
Front port password level 2 modified * * * * * 00D3 PW2 Modified F 12 7 12 0 0 0
Front port password expired * * * * * 0002 PW Expired F 13 7 13 0 0 0
Rear port 1 password unlocked * * * * * 0002 PW Unlocked R 14 7 14 0 0 0
Rear port 1 password invalid * * * * * 0002 PW Invalid R 15 7 15 0 0 0
Rear port 1 password level 1 modified * * * * * 00D2 PW1 Modified R 16 7 16 0 0 0
Rear port 1 password level 2 modified * * * * * 00D3 PW2 Modified R 17 7 17 0 0 0
Rear port 1 password expired * * * * * 0002 PW Expired R 18 7 18 0 0 0
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 112

Event Model Courier events MODBUS events

Options Event Event type MODBUS Additional

P341

P342

P343

P344

P345
Name Cell ref. extraction Text Value (Binary Flag) Bit (See G13) Event value 3x10008 register Event index 3x10011 data
column 3x10007 3x10010 3x10012
IRIG-B Active * * * * * IRIB-B 0805 IRIG-B Active 19 7 19 0 0 0
IRIG-B Inactive * * * * * IRIB-B 0805 IRIG-B Inactive 20 7 20 0 0 0
Time Synchronization * * * * * 0801 Time Synch 21 7 21 0 0 0
Control & Support Setting change * * * * * FFFF C&S Changed 22 7 22 0 0 0
Disturbance Recorder Setting change * * * * * 0C01 Dist Changed 23 7 23 0 0 0
Protection Group 1 setting change * * * * * 0905 Group 1 Changed 24 7 24 0 0 0
Protection Group 2 setting change * * * * * 0905 Group 2 Changed 25 7 25 0 0 0
Protection Group 3 setting change * * * * * 0905 Group 3 Changed 26 7 26 0 0 0
Protection Group 4 setting change * * * * * 0905 Group 4 Changed 27 7 27 0 0 0
Active Group Changed * * * * * 0904 Act Grp Changed 28 + (New active group * 65536) 7 28 + (New active group * 65536) 0 0 0
Front panel indications reset * * * * * 01FF Indication Reset 29 7 29 0 0 0
Power on * * * * * FFFF Power On 30 7 30 0 0 0
Bad GOOSE Scheme Logic (UCA2 Only) * * * * * UCA2 FFFF Bad GOOSE Logic 31 7 31 0 0 0
Bad Masks (UCA2 Only) * * * * * UCA2 FFFF Bad Masks 32 7 32 0 0 0
Bad Reporting Deadbands (UCA2 Only) * * * * * UCA2 FFFF Bad Deadbands 33 7 33 0 0 0
Bad Device Identity (UCA2 Only) * * * * * UCA2 FFFF Bad DI Object 34 7 34 0 0 0
Rear port 2 card failure * * * * * RP2 FFFF Rear Comm 2 Fail 35 7 35 0 0 0
Rear port 2 password unlocked * * * * * RP2 0002 PW Unlocked R2 36 7 36 0 0 0
Rear port 2 password invalid * * * * * RP2 0002 PW Invalid R2 37 7 37 0 0 0
Rear port 2 password level 1 modified * * * * * RP2 00D2 PW1 Modified R2 38 7 38 0 0 0
Rear port 2 password level 2 modified * * * * * RP2 00D3 PW2 Modified R2 39 7 39 0 0 0
Rear port 2 password expired * * * * * RP2 0002 PW Expired R2 40 7 40 0 0 0
Fiber-optic port not fitted * * * * * Fiber iface FFFF No Fiber Card 41 7 41 0 0 0
Ethernet link fail * * * * * UCA2 FFFF NIC Link Fail 42 7 42 0 0 0
Disturbance Records cleared * * * * * 0B30 Dist Rec Cleared 43 7 43 0 0 0
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 113

IEC60870-5-103: Device Profile


Vendor name: AREVA T&D Ltd. Automation & Information Systems
Device name: P340 Generator Protection
Models covered: P341****3**33**
P342****3**33**
P343****3**33**
P344****3**33**
P345****3**33**

Compatibility level: 2

Physical layer
Electrical Interface: EIA(RS)485
Number of Loads: 1 for one protection equipment
Optical Interface
Plastic fiber BFOC/2.5 type connector
(Order Option)
Transmission Speed: 9600 or 19200bps (User Setting)
Application layer
Common Address of ASDU = Link Address

Compatible range information numbers in monitor direction

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
System functions
8 10 255 0 End of General Interrogation * * * * *
6 8 255 0 Time Synchronization * * * * *
5 3 224 2 Reset FCB * * * * *
5 4 224 3 Reset CU * * * * *
5 5 224 4 Start/Restart * * * * *
5 6 224 5 Power On * * * * *

Note: Identification message in ASDU 5: "MiCOM P" + 16bit model + 8bit major version + 1 character minor version e.g. "MiCOM P" + 343 + 32 + 'A'

Status indications
1 1,7,9,11,12,20,21 224 16 Auto-recloser active *
1 1,7,9,11,12,20,21 224 17 Tele-protection active *
1 1,7,9,11,12,20,21 224 18 Protection active *
1 1,7,11,12,20, 21 224 19 LED Reset * * * * * Reset Indications
1 9,11 224 20 Monitor direction blocked * * * * * * 391
1 9,11 224 21 Test mode * * * * * * Protection Disabled 291
1 9,11 224 22 Local parameter setting *
1 1,7,9,11,12,20,21 224 23 Characteristic 1 * * * * * * PG1 Changed
1 1,7,9,11,12,20,21 224 24 Characteristic 2 * * * * * * PG2 Changed
1 1,7,9,11,12,20,21 224 25 Characteristic 3 * * * * * * PG3 Changed
1 1,7,9,11,12,20,21 224 26 Characteristic 4 * * * * * * PG4 Changed
1 1,7,9,11 224 27 Auxiliary input 1 * * * * * * Opto Input 1 32
1 1,7,9,11 224 28 Auxiliary input 2 * * * * * * Opto Input 2 33
1 1,7,9,11 224 29 Auxiliary input 3 * * * * * * Opto Input 3 34
1 1,7,9,11 224 30 Auxiliary input 4 * * * * * * Opto Input 4 35
Supervision indications
1 1,7,9 224 32 Measurand supervision I *
1 1,7,9 224 33 Measurand supervision V *
1 1,7,9 224 35 Phase sequence supervision *
1 1,7,9 224 36 Trip circuit supervision *
1 1,7,9 224 37 I>> back-up supervision *
1 1,7,9 224 38 VT fuse failure * * * * * * VTS Indication 292
1 1,7,9 224 39 Teleprotection disturbed *
1 1,7,9 224 46 Group warning *
1 1,7,9 224 47 Group alarm *
Earth fault indications
1 1,7,9 224 48 Earth Fault L1 *
1 1,7,9 224 49 Earth Fault L2 *
1 1,7,9 224 50 Earth Fault L3 *
1 1,7,9 224 51 Earth Fault Fwd *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 114

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
1 1,7,9 224 52 Earth Fault Rev *
Fault indications
2 1,7,9 224 64 Start/pickup L1 * * * * * * 1st Stage O/C Start A 598
2 1,7,9 224 65 Start/pickup L2 * * * * * * 1st Stage O/C Start B 599
2 1,7,9 224 66 Start/pickup L3 * * * * * * 1st Stage O/C Start C 600
2 1,7,9 224 67 Start/pickup N * * * * * * 1st Stage EF Start 613
2 1,7 224 68 General Trip * * * * * Any Trip 162
2 1,7 224 69 Trip L1 * * * * * 1st Stage O/C Trip A 478
2 1,7 224 70 Trip L2 * * * * * 1st Stage O/C Trip B 479
2 1,7 224 71 Trip L3 * * * * * 1st Stage O/C Trip C 480
2 1,7 224 72 Trip I>> (back up)
4 1,7 224 73 Fault Location in ohms
2 1,7 224 74 Fault forward
2 1,7 224 75 Fault reverse
2 1,7 224 76 Teleprotection signal sent
2 1,7 224 77 Teleprotection signal received
2 1,7 224 78 Zone 1
2 1,7 224 79 Zone 2
2 1,7 224 80 Zone 3
2 1,7 224 81 Zone 4
2 1,7 224 82 Zone 5
2 1,7 224 83 Zone 6
2 1,7,9 224 84 General Start * * * * * * Any Start 576
2 1,7 224 85 Breaker Failure * * * * * Breaker Fail Any Trip 294
2 1,7 224 86 Trip measuring system L1
2 1,7 224 87 Trip measuring system L2
2 1,7 224 88 Trip measuring system L3
2 1,7 224 89 Trip measuring system E
2 1,7 224 90 Trip I> * * * * * 1st Stage O/C Trip 3ph 477
2 1,7 224 91 Trip I>> * * * * * 2nd Stage O/C Trip 3ph 481
2 1,7 224 92 Trip IN> * * * * * 1st Stage EF Trip 442
2 1,7 224 93 Trip IN>> * * * * * 2nd Stage EF Trip 443
Auto-Reclose indications
1 1,7 224 128 CB 'on' by A/R
1 1,7 224 129 CB 'on' by long time A/R
1 1,7,9 224 130 AR blocked *
Measurands
3.1 2,7 224 144 Measurand I
3.2 2,7 224 145 Measurands I,V
3.3 2,7 224 146 Measurands I,V,P,Q
3.4 2,7 224 147 Measurands IN,VEN

Note: Unavailable
9 2,7 224 148 Measurands IL1,2,3,VL1,2,3,P,Q,f * * * * *
measurands sent as invalid

Generic functions
10 42,43 224 240 Read Headings
Read attributes of all entries of a
10 42,43 224 241
group
10 42,43 224 243 Read directory of entry
1,2,7,9,11,12,
10 224 244 Real attribute of entry *
42,43
10 10 224 245 End of GGI
10 41,44 224 249 Write entry with confirm
10 40,41 224 250 Write entry with execute
10 40 224 251 Write entry aborted
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 115

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
Compatible range information numbers in control direction
System functions
7 9 255 0 Init General Interrogation * * * * *
6 8 255 0 Time Synchronization * * * * *
General commands
20 20 224 16 Auto-recloser on/off Auto-reclose in Service
20 20 224 17 Teleprotection on/off
20 20 224 18 Protection on/off

20 20 224 19 LED Reset * * * * * Reset Indications and Latches

20 20 224 23 Activate characteristic 1 * * * * * Activate Setting Group 1


20 20 224 24 Activate characteristic 2 * * * * * Activate Setting Group 2
20 20 224 25 Activate characteristic 3 * * * * * Activate Setting Group 3
20 20 224 26 Activate characteristic 4 * * * * * Activate Setting Group 4
Generic functions
Read headings of all defined
21 42 224 240
groups

Read single attribute of all entries


21 42 224 241
of a group
21 42 224 243 Read directory of single entry
21 42 224 244 Read attribute of sngle entry
Generic General Interrogation
21 9 224 245
(GGI)
10 40 224 248 Write entry
10 40 224 249 Write with confirm
10 40 224 250 Write with execute
10 40 224 251 Write entry abort
Basic application functions
Test Mode * * * * * * *
Blocking of monitor direction * * * * * * *
Disturbance data * * * * * * *
Generic services * *
Private data * * * * * * *
Miscellaneous Max. MVAL = times rated value
Measurands 1.2 2.4
Current L1 *
Current L2 *
Current L3 *
Voltage L1-E *
Voltage L2-E *
Voltage L3-E *
Active Power P *
Reactive Power Q *
Frequency F *
Voltage L1-L2

Private range information numbers in monitor direction

Inf. Model number


ASDU TYPE COT FUN Display text (English) GI DDB signal description DDB ordinal
no. 1 2 3 4 5
1 1,7,9 226 0 see 4B01 * * * * * * Output Relay 1 0
1 1,7,9 226 1 see 4B02 * * * * * * Output Relay 2 1
1 1,7,9 226 2 see 4B03 * * * * * * Output Relay 3 2
1 1,7,9 226 3 see 4B04 * * * * * * Output Relay 4 3
1 1,7,9 226 4 see 4B05 * * * * * * Output Relay 5 4
1 1,7,9 226 5 see 4B06 * * * * * * Output Relay 6 5
1 1,7,9 226 6 see 4B07 * * * * * * Output Relay 7 6
1 1,7,9 226 7 see 4B08 * * * * * * Output Relay 8 7
1 1,7,9 226 8 see 4B09 * * * * * * Output Relay 9 8
1 1,7,9 226 9 see 4B0A * * * * * * Output Relay 10 9
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 116

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
1 1,7,9 226 10 see 4B0B * * * * * * Output Relay 11 10
1 1,7,9 226 11 see 4B0C * * * * * * Output Relay 12 11
1 1,7,9 226 12 see 4B0D * * * * * * Output Relay 13 12
1 1,7,9 226 13 see 4B0E * * * * * * Output Relay 14 13
1 1,7,9 226 14 see 4B0F * * * * * * Output Relay 15 14
1 1,7,9 226 15 see 4B10 * * * * * * Output Relay 16 15
1 1,7,9 226 16 see 4B11 * * * * * * Output Relay 17 16
1 1,7,9 226 17 see 4B12 * * * * * * Output Relay 18 17
1 1,7,9 226 18 see 4B13 * * * * * * Output Relay 19 18
1 1,7,9 226 19 see 4B14 * * * * * * Output Relay 20 19
1 1,7,9 226 20 see 4B15 * * * * * * Output Relay 21 20
1 1,7,9 226 21 see 4B16 * * * * * * Output Relay 22 21
1 1,7,9 226 22 see 4B17 * * * * * * Output Relay 23 22
1 1,7,9 226 23 see 4B18 * * * * * * Output Relay 24 23
1 1,7,9 226 24 see 4B19 * * * * Output Relay 25 24
1 1,7,9 226 25 see 4B1A * * * * Output Relay 26 25
1 1,7,9 226 26 see 4B1B * * * * Output Relay 27 26
1 1,7,9 226 27 see 4B1C * * * * Output Relay 28 27
1 1,7,9 226 28 see 4B1D * * * * Output Relay 29 28
1 1,7,9 226 29 see 4B1E * * * * Output Relay 30 29
1 1,7,9 226 30 see 4B1F * * * * Output Relay 31 30
1 1,7,9 226 31 see 4B20 * * * * Output Relay 32 31
1 1,7,9,11 224 27 see 4A01 * * * * * * Opto Isolator Input 1 32
1 1,7,9,11 224 28 see 4A02 * * * * * * Opto Isolator Input 2 33
1 1,7,9,11 224 29 see 4A03 * * * * * * Opto Isolator Input 3 34
1 1,7,9,11 224 30 see 4A04 * * * * * * Opto Isolator Input 4 35
1 1,7,9,11 226 36 see 4A05 * * * * * * Opto Isolator Input 5 36
1 1,7,9,11 226 37 see 4A06 * * * * * * Opto Isolator Input 6 37
1 1,7,9,11 226 38 see 4A07 * * * * * * Opto Isolator Input 7 38
1 1,7,9,11 226 39 see 4A08 * * * * * * Opto Isolator Input 8 39
1 1,7,9,11 226 40 see 4A09 * * * * * * Opto Isolator Input 9 40
1 1,7,9,11 226 41 see 4A0A * * * * * * Opto Isolator Input 10 41
1 1,7,9,11 226 42 see 4A0B * * * * * * Opto Isolator Input 11 42
1 1,7,9,11 226 43 see 4A0C * * * * * * Opto Isolator Input 12 43
1 1,7,9,11 226 44 see 4A0D * * * * * * Opto Isolator Input 13 44
1 1,7,9,11 226 45 see 4A0E * * * * * * Opto Isolator Input 14 45
1 1,7,9,11 226 46 see 4A0F * * * * * * Opto Isolator Input 15 46
1 1,7,9,11 226 47 see 4A10 * * * * * * Opto Isolator Input 16 47
1 1,7,9,11 226 48 see 4A11 * * * * * * Opto Isolator Input 17 48
1 1,7,9,11 226 49 see 4A12 * * * * * * Opto Isolator Input 18 49
1 1,7,9,11 226 50 see 4A13 * * * * * * Opto Isolator Input 19 50
1 1,7,9,11 226 51 see 4A14 * * * * * * Opto Isolator Input 20 51
1 1,7,9,11 226 52 see 4A15 * * * * * * Opto Isolator Input 21 52
1 1,7,9,11 226 53 see 4A16 * * * * * * Opto Isolator Input 22 53
1 1,7,9,11 226 54 see 4A17 * * * * * * Opto Isolator Input 23 54
1 1,7,9,11 226 55 see 4A18 * * * * * * Opto Isolator Input 24 55
1 1,7,9,11 226 56 see 4A19 * * * * Opto Isolator Input 25 56
1 1,7,9,11 226 57 see 4A1A * * * * Opto Isolator Input 26 57
1 1,7,9,11 226 58 see 4A1B * * * * Opto Isolator Input 27 58
1 1,7,9,11 226 59 see 4A1C * * * * Opto Isolator Input 28 59
1 1,7,9,11 226 60 see 4A1D * * * * Opto Isolator Input 29 60
1 1,7,9,11 226 61 see 4A1E * * * * Opto Isolator Input 30 61
1 1,7,9,11 226 62 see 4A1F * * * * Opto Isolator Input 31 62
1 1,7,9,11 226 63 see 4A20 * * * * Opto Isolator Input 32 63

Setting Group selection by


1 1,7,9 227 34 SG-DDB Invalid * * * * * * 354
DDB inputs invalid

1 9,11 224 21 Prot'n Disabled * * * * * * Test Mode Enabled 355


1 1,7,9 224 38 VT Fail Alarm * * * * * * VTS VT Fail Alarm 356
1 1,7,9 227 37 CT-1 Fail Alarm * * * * * * CTS-1 CT-1 Fail Alarm 357
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 117

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
2 1,7 224 85 CB Fail Alarm * * * * * Breaker Fail Any Trip 358
Broken Current Maintenance
1 1,7,9 227 39 I^ Maint Alarm * * * * * * 359
Alarm

1 1,7,9 227 40 I^ Lockout Alarm * * * * * * Broken Current Lockout Alarm 360

Number of CB Operations
1 1,7,9 227 41 CB Ops Maint * * * * * * 361
Maintenance Alarm
Number of CB Operations
1 1,7,9 227 42 CB Ops Lockout * * * * * * 362
Maintenance Lockout
Excessive CB Operation Time
1 1,7,9 227 43 CB Op Time Maint * * * * * * 363
Maintenance Alarm
Excessive CB Operation Time
1 1,7,9 227 44 CB Op Time Lock * * * * * * 364
Lockout Alarm
Excessive Fault Frequency
1 1,7,9 227 45 Fault Freq Lock * * * * * * 365
Lockout Alarm
1 1,7,9 227 46 CB Status Alarm * * * * * * CB Status Alarm 366
1 1,7 227 47 Man CB Trip Fail * * * * CB Failed to Trip 367
1 1,7 227 48 Man CB Cls Fail * * * * CB Failed to Close 368
1 1,7 227 49 Man CB Unhealthy * * * * Control CB Unhealthy 369
1 1,7,9 227 50 F out of Range * * Frequency Out of Range 370
Negative Phase Sequence
1 1,7,9 227 50 NPS Thermal Alm * * * * * 370
Thermal Alarm
1 1,7,9 227 51 Thermal Alarm * * * * * * Thermal Overload Alarm 371
1 1,7,9 227 52 V/Hz Alarm * * * * * Volts Per Hz Alarm 372
1 1,7,9 227 53 Field Fail Alarm * * * * * Field Failure Alarm 373
1 1,7,9 227 54 RTD Thermal Alm * * * * * RTD Thermal Alarm 374
1 1,7,9 227 55 RTD Open Cct * * * * * RTD Open Circuit Failure 375
1 1,7,9 227 56 RTD short Cct * * * * * RTD Short Circuit Failure 376
1 1,7,9 227 57 RTD Data Error * * * * * RTD Data Inconsistency Error 377
1 1,7,9 227 58 RTD Board Fail * * * * * RTD Board Failure 378
1 1,7,9 227 59 Freq Prot Alm * * * * * * Frequency Protection Alarm 379
1 1,7,9 227 60 Voltage Prot Alm * * * * * * Voltage Protection Alarm 380
1 1,7,9 227 61 CT-2 Fail Alarm * * * * CTS-2 CT-2 Fail Alarm 381
1 1,7,9 227 62 64S R<1 Alarm * * 64S 100% St EF Under Resista 382
1 1,7,9 227 63 64S Fail Alarm * * 64S Injection Fail Alarm 383
1 1,7,9 227 64 CL Card I/P Fail * * * * * * CLIO Input Board Failure 384
1 1,7,9 227 65 CL Card O/P Fail * * * * * * CLIO Output Board Failure 385
1 1, 7, 9 227 66 CL Input 1 Alarm * * * * * * Current Loop Input 1 Alarm 386
1 1, 7, 9 227 67 CL Input 2 Alarm * * * * * * Current Loop Input 2 Alarm 387
1 1, 7, 9 227 68 CL Input 3 Alarm * * * * * * Current Loop Input 3 Alarm 388
1 1, 7, 9 227 69 CL Input 4 Alarm * * * * * * Current Loop Input 4 Alarm 389
Current Loop Input 1
1 1, 7, 9 227 70 CLI1 I< Fail Alm * * * * * * 390
Undercurrent Fail Alarm
Current Loop Input 2
1 1, 7, 9 227 71 CLI2 I< Fail Alm * * * * * * 391
Undercurrent Fail Alarm
Current Loop Input 3
1 1, 7, 9 227 72 CLI3 I< Fail Alm * * * * * * 392
Undercurrent Fail Alarm
Current Loop Input 4
1 1, 7, 9 227 73 CLI4 I< Fail Alm * * * * * * 393
Undercurrent Fail Alarm
64R Rotor EF Under
1 1,7,9 227 74 64R R<1 Alarm * * * * * 394
Resistance Stage 1 Alarm
64R Rotor EF Current Loop
1 1,7,9 227 75 64R CL I/P Fail * * * * * 395
Input Fail
User Definable Alarm 16
1 1, 7, 9 227 80 MR User Alarm 16 * * * * * * 400
(Manual Reset)
User Definable Alarm 15
1 1, 7, 9 227 81 MR User Alarm 15 * * * * * * 401
(Manual Reset)
User Definable Alarm 14
1 1, 7, 9 227 82 MR User Alarm 14 * * * * * * 402
(Manual Reset)
User Definable Alarm 13
1 1, 7, 9 227 83 MR User Alarm 13 * * * * * * 403
(Manual Reset)
User Definable Alarm 12
1 1, 7, 9 227 84 MR User Alarm 12 * * * * * * 404
(Manual Reset)
User Definable Alarm 11
1 1, 7, 9 227 85 MR User Alarm 11 * * * * * * 405
(Manual Reset)
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 118

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
User Definable Alarm 10
1 1, 7, 9 227 86 MR User Alarm 10 * * * * * * 406
(Manual Reset)
User Definable Alarm 9
1 1, 7, 9 227 87 MR User Alarm 9 * * * * * * 407
(Manual Reset)
User Definable Alarm 8
1 1, 7, 9 227 88 MR User Alarm 8 * * * * * * 408
(Manual Reset)
User Definable Alarm 7
1 1, 7, 9 227 89 MR User Alarm 7 * * * * * * 409
(Manual Reset)
User Definable Alarm 6
1 1, 7, 9 227 90 MR User Alarm 6 * * * * * * 410
(Manual Reset)
User Definable Alarm 5
1 1, 7, 9 227 91 MR User Alarm 5 * * * * * * 411
(Manual Reset)
User Definable Alarm 4 (Self
1 1, 7, 9 227 92 SR User Alarm 4 * * * * * * 412
Reset)
User Definable Alarm 3 (Self
1 1, 7, 9 227 93 SR User Alarm 3 * * * * * * 413
Reset)
User Definable Alarm 2 (Self
1 1, 7, 9 227 94 SR User Alarm 2 * * * * * * 414
Reset)
User Definable Alarm 1 (Self
1 1, 7, 9 227 95 SR User Alarm 1 * * * * * * 415
Reset)
1 1, 7, 9 229 32 Battery Fail * * * * * * Battery Fail alarm indication 416
1 1, 7, 9 229 33 Field Volts Fail * * * * * * Field Voltage Failure 417
IEC60870-5-103 Monitor
1 9, 11 224 20 Monitor Blocked * * * * * * 619
Blocking
IEC60870-5-103 Command
1 9, 11 227 136 Command Blocked * * * * * * 620
Blocking
Setting Group Selector x1
1 1, 7, 9 230 130 SG Select x1 * * * * * 624
(bit 0)
Setting Group Selector 1x
1 1, 7, 9 230 131 SG Select 1x * * * * * 625
(bit 1)

2 1,7 224 68 Any Trip * * * * * Any Trip 626

2 1,7 227 162 Gen Diff Trip * * * Generator Differential Trip 3ph 640

2 1,7 227 163 Gen Diff Trip A * * * Generator Differential Trip A 641
2 1,7 227 164 Gen Diff Trip B * * * Generator Differential Trip B 642
2 1,7 227 165 Gen Diff Trip C * * * Generator Differential Trip C 643
2 1,7 227 166 Field Fail1 Trip * * * * Field Failure Stage 1 Trip 644
2 1,7 227 167 Field Fail2 Trip * * * * Field Failure Stage 2 Trip 645
2 1,7 227 173 V/Hz>1 Trip * * * * 1st Stage Volts per Hz Trip 646
2 1,7 228 16 V/Hz>2 Trip * * * * Volts per Hz Stage 2 Trip 647
2 1,7 228 17 V/Hz>3 Trip * * * * Volts per Hz Stage 3 Trip 648
2 1,7 228 18 V/Hz>4 Trip * * * * Volts per Hz Stage 4 Trip 649
2 1,7 227 174 RTD 1 Trip * * * * RTD 1 Trip 650
2 1,7 227 175 RTD 2 Trip * * * * RTD 2 Trip 651
2 1,7 227 176 RTD 3 Trip * * * * RTD 3 Trip 652
2 1,7 227 177 RTD 4 Trip * * * * RTD 4 Trip 653
2 1,7 227 178 RTD 5 Trip * * * * RTD 5 Trip 654
2 1,7 227 179 RTD 6 Trip * * * * RTD 6 Trip 655
2 1,7 227 180 RTD 7 Trip * * * * RTD 7 Trip 656
2 1,7 227 181 RTD 8 Trip * * * * RTD 8 Trip 657
2 1,7 227 182 RTD 9 Trip * * * * RTD 9 Trip 658
2 1,7 227 183 RTD 10 Trip * * * * RTD 10 Trip 659
2 1,7 227 184 Any RTD Trip * * * * Any RTD Trip 660
Rate Of Change Of
2 1,7 227 184 df/dt Trip * 661
Frequency Trip
2 1,7 227 185 V Shift Trip * Voltage Vector Shift Trip 662
2 1,7 224 92 IN>1 Trip * * * * * 1st Stage EF Trip 663
2 1,7 224 93 IN>2 Trip * * * * * 2nd Stage EF Trip 664
2 1,7 227 188 IN>3 Trip * 3rd Stage EF Trip 665
2 1,7 227 189 IN>4 Trip * 4th Stage EF Trip 666
2 1,7 227 190 IREF> Trip * * * * * REF Trip 667
2 1,7 227 191 ISEF>1 Trip * * * * * 1st Stage SEF Trip 668
2 1,7 227 192 ISEF>2 Trip * 2nd Stage SEF Trip 669
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 119

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
2 1,7 227 193 ISEF>3 Trip * 3rd Stage SEF Trip 670
2 1,7 227 194 ISEF>4 Trip * 4th Stage SEF Trip 671
2 1,7 227 195 VN>1 Trip * * * * * 1st Stage Residual O/V Trip 672
2 1,7 227 196 VN>2 Trip * * * * * 2nd Stage Residual O/V Trip 673
2 1,7 228 0 VN>3 Trip * * * * * Residual O/V Stage 3 Trip 674
2 1,7 228 1 VN>4 Trip * * * * * Residual O/V Stage 4 Trip 675
2 1,7 228 2 VN>5 Trip * * Residual O/V Stage 5 Trip 676
2 1,7 228 3 VN>6 Trip * * Residual O/V Stage 6 Trip 677

2 1,7 227 197 V<1 Trip * * * * * 1st Stage Phase U/V Trip 3ph 678

1st Stage Phase U/V Trip


2 1,7 227 198 V<1 Trip A/AB * * * * * 679
A/AB
1st Stage Phase U/V Trip
2 1,7 227 199 V<1 Trip B/BC * * * * * 680
B/BC
1st Stage Phase U/V Trip
2 1,7 227 200 V<1 Trip C/CA * * * * * 681
C/CA
2nd Stage Phase U/V Trip
2 1,7 227 201 V<2 Trip * * * * * 682
3ph
2nd Stage Phase U/V Trip
2 1,7 227 202 V<2 Trip A/AB * * * * * 683
A/AB
2nd Stage Phase U/V Trip
2 1,7 227 203 V<2 Trip B/BC * * * * * 684
B/BC
2nd Stage Phase U/V Trip
2 1,7 227 204 V<2 Trip C/CA * * * * * 685
C/CA

2 1,7 227 205 V>1 Trip * * * * * 1st Stage Phase O/V Trip 3ph 686

1st Stage Phase O/V Trip


2 1,7 227 206 V>1 Trip A/AB * * * * * 687
A/AB
1st Stage Phase O/V Trip
2 1,7 227 207 V>1 Trip B/BC * * * * * 688
B/BC
1st Stage Phase O/V Trip
2 1,7 227 208 V>1 Trip C/CA * * * * * 689
C/CA
2nd Stage Phase O/V Trip
2 1,7 227 209 V>2 Trip * * * * * 690
3ph
2nd Stage Phase O/V Trip
2 1,7 227 210 V>2 Trip A/AB * * * * * 691
A/AB
2nd Stage Phase O/V Trip
2 1,7 227 211 V>2 Trip B/BC * * * * * 692
B/BC
2nd Stage Phase O/V Trip
2 1,7 227 212 V>2 Trip C/CA * * * * * 693
C/CA

2 1,7 227 213 F<1 Trip * * * * * Under Frequency Stage 1 Trip 694

2 1,7 227 214 F<2 Trip * * * * * Under Frequency Stage 2 Trip 695

2 1,7 227 215 F<3 Trip * * * * * Under Frequency Stage 3 Trip 696

2 1,7 227 216 F<4 Trip * * * * * Under Frequency Stage 4 Trip 697

2 1,7 227 217 F>1 Trip * * * * * Over Frequency Stage 1 Trip 698

2 1,7 227 218 F>2 Trip * * * * * Over Frequency Stage 2 Trip 699

2 1,7 227 219 Power1 Trip * * * * * Power Stage 1 Trip 700


2 1,7 227 220 Power2 Trip * * * * * Power Stage 2 Trip 701
Negative Phase Sequence
2 1,7 227 168 NPS Thermal Trip * * * * 702
Thermal Trip
2 1,7 227 243 Thermal O/L Trip * * * * * Thermal Overload Trip 703
2 1,7 224 90 I>1 Trip * * * * * 1st Stage O/C Trip 3ph 704
2 1,7 224 69 I>1 Trip A * * * * * 1st Stage O/C Trip A 705
2 1,7 224 70 I>1 Trip B * * * * * 1st Stage O/C Trip B 706
2 1,7 224 71 I>1 Trip C * * * * * 1st Stage O/C Trip C 707
2 1,7 224 91 I>2 Trip * * * * * 2nd Stage O/C Trip 3ph 708
2 1,7 227 226 I>2 Trip A * * * * * 2nd Stage O/C Trip A 709
2 1,7 227 227 I>2 Trip B * * * * * 2nd Stage O/C Trip B 710
2 1,7 227 228 I>2 Trip C * * * * * 2nd Stage O/C Trip C 711
2 1,7 227 229 I>3 Trip * * * * * 3rd Stage O/C Trip 3ph 712
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 120

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
2 1,7 227 230 I>3 Trip A * * * * * 3rd Stage O/C Trip A 713
2 1,7 227 231 I>3 Trip B * * * * * 3rd Stage O/C Trip B 714
2 1,7 227 232 I>3 Trip C * * * * * 3rd Stage O/C Trip C 715
2 1,7 227 233 I>4 Trip * * * * * 4th Stage O/C Trip 3ph 716
2 1,7 227 234 I>4 Trip A * * * * * 4th Stage O/C Trip A 717
2 1,7 227 235 I>4 Trip B * * * * * 4th Stage O/C Trip B 718
2 1,7 227 236 I>4 Trip C * * * * * 4th Stage O/C Trip C 719
Sensitive A Phase Power
2 1,7 227 239 SPower1 Trip * * * * * 720
Stage 1 Trip
Sensitive A Phase Power
2 1,7 227 240 SPower2 Trip * * * * * 721
Stage 2 Trip
Pole Slip (Impedance) Zone1
2 1,7 227 241 PSlipz Z1 Trip * * * 722
Trip
Pole Slip (Impedance) Zone2
2 1,7 227 242 PSlipz Z2 Trip * * * 723
Trip
Voltage Dependant
2 1,7 227 169 V Dep OC Trip * * * * 724
Overcurrent Trip 3ph
Voltage Dependant
2 1,7 227 170 V Dep OC Trip A * * * * 725
Overcurrent Trip A
Voltage Dependant
2 1,7 227 171 V Dep OC Trip B * * * * 726
Overcurrent Trip B
Voltage Dependant
2 1,7 227 172 V Dep OC Trip C * * * * 727
Overcurrent Trip C
Under Impedance 3Phase
2 1,7 227 244 Z<1 Trip * * * * 728
Stage 1 Trip
Under Impedance Phase A
2 1,7 227 245 Z<1 Trip A * * * * 729
Stage 1 Trip
Under Impedance Phase B
2 1,7 227 246 Z<1 Trip B * * * * 730
Stage 1 Trip
Under Impedance Phase C
2 1,7 227 247 Z<1 Trip C * * * * 731
Stage 1 Trip
Under Impedance 3Phase
2 1,7 227 248 Z<2 Trip * * * * 732
Stage 2 Trip
Under Impedance Phase A
2 1,7 227 249 Z<2 Trip A * * * * 733
Stage 2 Trip
Under Impedance Phase B
2 1,7 227 250 Z<2 Trip B * * * * 734
Stage 2 Trip
Under Impedance Phase C
2 1,7 227 251 Z<2 Trip C * * * * 735
Stage 2 Trip
2 1,7 227 237 Bfail1 Trip 3ph * * * * * tBF1 Trip 3ph 736
2 1,7 227 238 Bfail2 Trip 3ph * * * * * tBF2 Trip 3ph 737
100% Stator Earth Fault
2 1,7 227 160 100%StEF3H Trip * * * 738
(3rd harmonic) Trip
2 1,7 227 252 CL Input 1 Trip * * * * * Current Loop Input 1 Trip 739
2 1,7 227 253 CL Input 2 Trip * * * * * Current Loop Input 2 Trip 740
2 1,7 227 254 CL Input 3 Trip * * * * * Current Loop Input 3 Trip 741
2 1,7 227 255 CL Input 4 Trip * * * * * Current Loop Input 4 Trip 742
2 1,7 228 4 S2>1 Trip * * * * NPS Overpower Stage 1 trip 743
Turbine Abnormal Frequency
2 1,7 228 5 Freq Band1 Trip * * * * 744
Band 1 Trip
Turbine Abnormal Frequency
2 1,7 228 6 Freq Band2 Trip * * * * 745
Band 2 Trip
Turbine Abnormal Frequency
2 1,7 228 7 Freq Band3 Trip * * * * 746
Band 3 Trip
Turbine Abnormal Frequency
2 1,7 228 8 Freq Band4 Trip * * * * 747
Band 4 Trip
Turbine Abnormal Frequency
2 1,7 228 9 Freq Band5 Trip * * * * 748
Band 5 Trip
Turbine Abnormal Frequency
2 1,7 228 10 Freq Band6 Trip * * * * 749
Band 6 Trip

2 1,7 228 11 I2>1 Trip * * * * * NPS Overcurrent Stage 1 Trip 750

2 1,7 228 12 I2>2 Trip * * * * * NPS Overcurrent Stage 2 Trip 751

2 1,7 228 13 I2>3 Trip * * * * * NPS Overcurrent Stage 3 Trip 752


Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 121

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5

2 1,7 228 14 I2>4 Trip * * * * * NPS Overcurrent Stage 4 Trip 753

NPS Over Voltage Stage 1


2 1,7 228 15 V2>1 Trip * * * * * 754
Trip

2 1,7 227 161 DeadMachine Trip * * * Dead Machine Protection Trip 755

64S 100% Stator Earth Fault


2 1,7 228 19 64S I>1 Trip * 756
Overcurrent Trip
64S 100% St EF Under
2 1,7 228 20 64S R<2 Trip * 757
Resistance Stage 2 Trip
64R Rotor Earth Fault Under
2 1,7 228 21 64R R<2 Trip * * * * 758
Resistance Stage 2 Trip
2 1,7,9 224 84 Any Start * * * * * * Any Start 832
2 1,7,9 228 116 I> BlockStart * * * I> Blocked O/C Start 838
2 1,7,9 228 117 IN/SEF>Blk Start * * * IN/ISEF> Blocked O/C Start 839
Current Loop Input 1 Alarm
2 1,7,9 228 146 CLI1 Alarm Start * * * * * * 840
Start
Current Loop Input 2 Alarm
2 1,7,9 228 147 CLI2 Alarm Start * * * * * * 841
Start
Current Loop Input 3 Alarm
2 1,7,9 228 148 CLI3 Alarm Start * * * * * * 842
Start
Current Loop Input 4 Alarm
2 1,7,9 228 149 CLI4 Alarm Start * * * * * * 843
Start

2 1,7,9 228 150 CLI1 Trip Start * * * * * * Current Loop Input 1 Trip Start 844

2 1,7,9 228 151 CLI2 Trip Start * * * * * * Current Loop Input 2 Trip Start 845

2 1,7,9 228 152 CLI3 Trip Start * * * * * * Current Loop Input 3 Trip Start 846

2 1,7,9 228 153 CLI4 Trip Start * * * * * * Current Loop Input 4 Trip Start 847

2 1,7,9 228 125 FFail1 Start * * * * * Field Failure Stage 1 Start 848
2 1,7,9 228 126 FFail2 Start * * * * * Field Failure Stage 2 Start 849
2 1,7,9 228 124 V/Hz>1 Start * * * * * 1st Stage Volts per Hz Start 850
2 1,7,9 228 171 V/Hz>2 Start * * * * * Volts per Hz Stage 2 Start 851
2 1,7,9 228 172 V/Hz>3 Start * * * * * Volts per Hz Stage 3 Start 852
2 1,7,9 228 173 V/Hz>4 Start * * * * * Volts per Hz Stage 4 Start 853
Rate Of Change Of
2 1,7,9 228 118 df/dt Start * * 854
Frequency Start
2 1,7,9 224 67 IN>1 Start * * * * * * 1st Stage EF Start 855
2 1,7,9 228 102 IN>2 Start * * * * * * 2nd Stage EF Start 856
2 1,7,9 228 103 IN>3 Start * * 3rd Stage EF Start 857
2 1,7,9 228 104 IN>4 Start * * 4th Stage EF Start 858
2 1,7,9 228 105 ISEF>1 Start * * * * * * 1st Stage SEF Start 859
2 1,7,9 228 106 ISEF>2 Start * * 2nd Stage SEF Start 860
2 1,7,9 228 107 ISEF>3 Start * * 3rd Stage SEF Start 861
2 1,7,9 228 108 ISEF>4 Start * * 4th Stage SEF Start 862
2 1,7,9 228 65 VN>1 Start * * * * * * 1st Stage Residual O/V Start 864

2 1,7,9 228 66 VN>2 Start * * * * * * 2nd Stage Residual O/V Start 865

2 1,7,9 228 154 VN>3 Start * * * * * * Residual O/V Stage 3 Start 866
2 1,7,9 228 155 VN>4 Start * * * * * * Residual O/V Stage 4 Start 867
2 1,7,9 228 156 VN>5 Start * * * Residual O/V Stage 5 Start 868
2 1,7,9 228 157 VN>6 Start * * * Residual O/V Stage 6 Start 869
1st Stage Phase U/V Start
2 1,7,9 228 67 V<1 Start * * * * * * 870
3ph
1st Stage Phase U/V Start
2 1,7,9 228 68 V<1 Start A/AB * * * * * * 871
A/AB
1st Stage Phase U/V Start
2 1,7,9 228 69 V<1 Start B/BC * * * * * * 872
B/BC
1st Stage Phase U/V Start
2 1,7,9 228 70 V<1 Start C/CA * * * * * * 873
C/CA
2nd Stage Phase U/V Start
2 1,7,9 228 71 V<2 Start * * * * * * 874
3ph
2nd Stage Phase U/V Start
2 1,7,9 228 72 V<2 Start A/AB * * * * * * 875
A/AB
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 122

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
2nd Stage Phase U/V Start
2 1,7,9 228 73 V<2 Start B/BC * * * * * * 876
B/BC
2nd Stage Phase U/V Start
2 1,7,9 228 74 V<2 Start C/CA * * * * * * 877
C/CA
1st Stage Phase O/V Start
2 1,7,9 228 75 V>1 Start * * * * * * 878
3ph
1st Stage Phase O/V Start
2 1,7,9 228 76 V>1 Start A/AB * * * * * * 879
A/AB
1st Stage Phase O/V Start
2 1,7,9 228 77 V>1 Start B/BC * * * * * * 880
B/BC
1st Stage Phase O/V Start
2 1,7,9 228 78 V>1 Start C/CA * * * * * * 881
C/CA
2nd Stage Phase O/V Start
2 1,7,9 228 79 V>2 Start * * * * * * 882
3ph
2nd Stage Phase O/V Start
2 1,7,9 228 80 V>2 Start A/AB * * * * * * 883
A/AB
2nd Stage Phase O/V Start
2 1,7,9 228 81 V>2 Start B/BC * * * * * * 884
B/BC
2nd Stage Phase O/V Start
2 1,7,9 228 82 V>2 Start C/CA * * * * * * 885
C/CA
Under Frequency Stage 1
2 1,7,9 228 110 F<1 Start * * * * * * 886
Start
Under Frequency Stage 2
2 1,7,9 228 111 F<2 Start * * * * * * 887
Start
Under Frequency Stage 3
2 1,7,9 228 112 F<3 Start * * * * * * 888
Start
Under Frequency Stage 4
2 1,7,9 228 113 F<4 Start * * * * * * 889
Start

2 1,7,9 228 114 F>1 Start * * * * * * Over Frequency Stage 1 Start 890

2 1,7,9 228 115 F>2 Start * * * * * * Over Frequency Stage 2 Start 891

2 1,7,9 228 83 Power1 Start * * * * * * Power Stage 1 Start 892


2 1,7,9 228 84 Power2 Start * * * * * * Power Stage 2 Start 893
2 1,7,9 228 85 I>1 Start * * * * * * 1st Stage O/C Start 3ph 896
2 1,7,9 224 64 I>1 Start A * * * * * * 1st Stage O/C Start A 897
2 1,7,9 224 65 I>1 Start B * * * * * * 1st Stage O/C Start B 898
2 1,7,9 224 66 I>1 Start C * * * * * * 1st Stage O/C Start C 899
2 1,7,9 228 89 I>2 Start * * * * * * 2nd Stage O/C Start 3ph 900
2 1,7,9 228 90 I>2 Start A * * * * * * 2nd Stage O/C Start A 901
2 1,7,9 228 91 I>2 Start B * * * * * * 2nd Stage O/C Start B 902
2 1,7,9 228 92 I>2 Start C * * * * * * 2nd Stage O/C Start C 903
2 1,7,9 228 93 I>3 Start * * * * * * 3rd Stage O/C Start 3ph 904
2 1,7,9 228 94 I>3 Start A * * * * * * 3rd Stage O/C Start A 905
2 1,7,9 228 95 I>3 Start B * * * * * * 3rd Stage O/C Start B 906
2 1,7,9 228 96 I>3 Start C * * * * * * 3rd Stage O/C Start C 907
2 1,7,9 228 97 I>4 Start * * * * * * 4th Stage O/C Start 3ph 908
2 1,7,9 228 98 I>4 Start A * * * * * * 4th Stage O/C Start A 909
2 1,7,9 228 99 I>4 Start B * * * * * * 4th Stage O/C Start B 910
2 1,7,9 228 100 I>4 Start C * * * * * * 4th Stage O/C Start C 911
Sensitive A Phase Power
2 1,7,9 228 131 SPower1 Start * * * * * * 912
Stage 1 Start
Sensitive A Phase Power
2 1,7,9 228 132 SPower2 Start * * * * * * 913
Stage 2 Start
Pole Slip (Impedance) Zone1
2 1,7,9 228 133 PSlipz Z1 Start * * * * 914
Start
Pole Slip (Impedance) Zone2
2 1,7,9 228 134 PSlipz Z2 Start * * * * 915
Start
Pole Slip (impedance) Lens
2 1,7,9 228 135 PSlipz LensStart * * * * 916
Start
Pole Slip (impedance) Blinder
2 1,7,9 228 136 PSlipz BlindStrt * * * * 917
Start
Pole Slip (impedance)
2 1,7,9 228 137 PSlipz ReactStrt * * * * 918
Reactance Line Start
Turbine Abnormal Frequency
2 1,7,9 228 160 Freq Band1 Start * * * * * 919
Band 1 Start
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 123

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
Turbine Abnormal Frequency
2 1,7,9 228 161 Freq Band2 Start * * * * * 920
Band 2 Start
Turbine Abnormal Frequency
2 1,7,9 228 162 Freq Band3 Start * * * * * 921
Band 3 Start
Turbine Abnormal Frequency
2 1,7,9 228 163 Freq Band4 Start * * * * * 922
Band 4 Start
Turbine Abnormal Frequency
2 1,7,9 228 164 Freq Band5 Start * * * * * 923
Band 5 Start
Turbine Abnormal Frequency
2 1,7,9 228 165 Freq Band6 Start * * * * * 924
Band 6 Start
Voltage Dependant
2 1,7,9 228 127 V Dep OC Start * * * * * 928
Overcurrent Start 3Ph
Voltage Dependant
2 1,7,9 228 128 V Dep OC Start A * * * * * 929
Overcurrent Start A
Voltage Dependant
2 1,7,9 228 129 V Dep OC Start B * * * * * 930
Overcurrent Start B
Voltage Dependant
2 1,7,9 228 130 V Dep OC Start C * * * * * 931
Overcurrent Start C
Under Impedance 3Phase
2 1,7,9 228 138 Z<1 Start * * * * * 932
Stage 1 Start
Under Impedance Phase A
2 1,7,9 228 139 Z<1 Start A * * * * * 933
Stage 1 Start
Under Impedance Phase B
2 1,7,9 228 140 Z<1 Start B * * * * * 934
Stage 1 Start
Under Impedance Phase C
2 1,7,9 228 141 Z<1 Start C * * * * * 935
Stage 1 Start
Under Impedance 3Phase
2 1,7,9 228 142 Z<2 Start * * * * * 936
Stage 2 Start
Under Impedance Phase A
2 1,7,9 228 143 Z<2 Start A * * * * * 937
Stage 2 Start
Under Impedance Phase B
2 1,7,9 228 144 Z<2 Start B * * * * * 938
Stage 2 Start
Under Impedance Phase C
2 1,7,9 228 145 Z<2 Start C * * * * * 939
Stage 2 Start
100% Stator Earth Fault
2 1,7,9 228 109 100%StEF3H Start * * * * 940
(3rd harmonic) Start

2 1,7,9 228 158 S2>1 Start * * * * * NPS Overpower Stage 1 Start 941

NPS Overcurrent Stage 1


2 1,7,9 228 166 I2>1 Start * * * * * * 942
Start
NPS Overcurrent Stage 2
2 1,7,9 228 167 I2>2 Start * * * * * * 943
Start
NPS Overcurrent Stage 3
2 1,7,9 228 168 I2>3 Start * * * * * * 944
Start
NPS Overcurrent Stage 4
2 1,7,9 228 169 I2>4 Start * * * * * * 945
Start
NPS Over Voltage Stage 1
2 1,7,9 228 170 V2>1 Start * * * * * * 946
Start
64S 100% Stator Earth Fault
2 1,7,9 228 174 64S I< Start * 947
Undercurrent Start

64S 100% Stator Earth Fault


2 1,7,9 228 175 64S V< Start * 948
Undervoltage Start

64S 100% Stator Earth Fault


2 1,7,9 228 176 64S I>1 Start * 949
Overcurrent Start

64S 100% St EF Under


2 1,7,9 228 177 64S Start R<1Alm * 950
Resistance Stg 1 Alm Start

64S 100% St EF Under


2 1,7,9 228 178 64S R<2 Start * 951
Resistance Stg 2 Trip Start

64R Rotor EF Under


2 1,7,9 228 184 64R Start R<1Alm * * * * * 952
Resistance Stg 1 Alm Start

64R Rotor EF Under


2 1,7,9 228 185 64R R<2 Start * * * * * 953
Resistance Stg 2 Trip Start
1 1,7,9 228 224 VTS Fast Block * * * * * * VTS Fast Block 1024
1 1,7,9 228 225 VTS Slow Block * * * * * * VTS Slow Block 1025
1 1,7,9 228 226 CTS-1 Block * * * * * * CTS-1 Block 1026
1 1,7,9 228 227 Control Trip * * Control Trip 1027
1 1,7,9 228 228 Control Close * * Control Close 1028
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 124

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
1 1,7,9 228 229 Close in Prog * * Control Close in Progress 1029
Reconnection Time Delay
1 1,7,9 228 230 Reconnection * * 1030
Output
1 1,7,9 228 231 RTD 1 Alarm * * * * * RTD 1 Alarm 1031
1 1,7,9 228 232 RTD 2 Alarm * * * * * RTD 2 Alarm 1032
1 1,7,9 228 233 RTD 3 Alarm * * * * * RTD 3 Alarm 1033
1 1,7,9 228 234 RTD 4 Alarm * * * * * RTD 4 Alarm 1034
1 1,7,9 228 235 RTD 5 Alarm * * * * * RTD 5 Alarm 1035
1 1,7,9 228 236 RTD 6 Alarm * * * * * RTD 6 Alarm 1036
1 1,7,9 228 237 RTD 7 Alarm * * * * * RTD 7 Alarm 1037
1 1,7,9 228 238 RTD 8 Alarm * * * * * RTD 8 Alarm 1038
1 1,7,9 228 239 RTD 9 Alarm * * * * * RTD 9 Alarm 1039
1 1,7,9 228 240 RTD 10 Alarm * * * * * RTD 10 Alarm 1040
1 1,7,9 228 241 Lockout Alarm * * * * * * Composite Lockout Alarm 1041
1 1,7,9 228 242 CB Open 3 ph * * * * * * 3 ph CB Open 1042
1 1,7,9 228 243 CB Closed 3 ph * * * * * * 3 ph CB Closed 1043
1 1,7,9 228 245 All Poles Dead * * * * * * All Poles Dead 1044
1 1,7,9 228 246 Any Pole Dead * * * * * * Any Pole Dead 1045
1 1,7,9 228 247 Pole Dead A * * * * * * Phase A Pole Dead 1046
1 1,7,9 228 248 Pole Dead B * * * * * * Phase B Pole Dead 1047
1 1,7,9 228 249 Pole Dead C * * * * * * Phase C Pole Dead 1048
1 1,7,9 229 19 CTS-2 Block * * * * CTS-2 Block 1074
64S 100% Stator Earth Fault -
1 1,7,9 229 20 64S F Band Block * System frequency in blocking 1075
band
64S 100% Stator Earth Fault -
1 1,7,9 229 21 64S Fail * 1076
Injection failure
1 9,11,12,20,21 229 64 Control Input 1 * * * * * * Control Input 1 1152
1 9,11,12,20,21 229 65 Control Input 2 * * * * * * Control Input 2 1153
1 9,11,12,20,21 229 66 Control Input 3 * * * * * * Control Input 3 1154
1 9,11,12,20,21 229 67 Control Input 4 * * * * * * Control Input 4 1155
1 9,11,12,20,21 229 68 Control Input 5 * * * * * * Control Input 5 1156
1 9,11,12,20,21 229 69 Control Input 6 * * * * * * Control Input 6 1157
1 9,11,12,20,21 229 70 Control Input 7 * * * * * * Control Input 7 1158
1 9,11,12,20,21 229 71 Control Input 8 * * * * * * Control Input 8 1159
1 9,11,12,20,21 229 72 Control Input 9 * * * * * * Control Input 9 1160
1 9,11,12,20,21 229 73 Control Input 10 * * * * * * Control Input 10 1161
1 9,11,12,20,21 229 74 Control Input 11 * * * * * * Control Input 11 1162
1 9,11,12,20,21 229 75 Control Input 12 * * * * * * Control Input 12 1163
1 9,11,12,20,21 229 76 Control Input 13 * * * * * * Control Input 13 1164
1 9,11,12,20,21 229 77 Control Input 14 * * * * * * Control Input 14 1165
1 9,11,12,20,21 229 78 Control Input 15 * * * * * * Control Input 15 1166
1 9,11,12,20,21 229 79 Control Input 16 * * * * * * Control Input 16 1167
1 9,11,12,20,21 229 80 Control Input 17 * * * * * * Control Input 17 1168
1 9,11,12,20,21 229 81 Control Input 18 * * * * * * Control Input 18 1169
1 9,11,12,20,21 229 82 Control Input 19 * * * * * * Control Input 19 1170
1 9,11,12,20,21 229 83 Control Input 20 * * * * * * Control Input 20 1171
1 9,11,12,20,21 229 84 Control Input 21 * * * * * * Control Input 21 1172
1 9,11,12,20,21 229 85 Control Input 22 * * * * * * Control Input 22 1173
1 9,11,12,20,21 229 86 Control Input 23 * * * * * * Control Input 23 1174
1 9,11,12,20,21 229 87 Control Input 24 * * * * * * Control Input 24 1175
1 9,11,12,20,21 229 88 Control Input 25 * * * * * * Control Input 25 1176
1 9,11,12,20,21 229 89 Control Input 26 * * * * * * Control Input 26 1177
1 9,11,12,20,21 229 90 Control Input 27 * * * * * * Control Input 27 1178
1 9,11,12,20,21 229 91 Control Input 28 * * * * * * Control Input 28 1179
1 9,11,12,20,21 229 92 Control Input 29 * * * * * * Control Input 29 1180
1 9,11,12,20,21 229 93 Control Input 30 * * * * * * Control Input 30 1181
1 9,11,12,20,21 229 94 Control Input 31 * * * * * * Control Input 31 1182
1 9,11,12,20,21 229 95 Control Input 32 * * * * * * Control Input 32 1183
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 125

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
1 1,7,9 229 96 Virtual Input 01 * * * * * * Virtual Input 01 1184
1 1,7,9 229 97 Virtual Input 02 * * * * * * Virtual Input 02 1185
1 1,7,9 229 98 Virtual Input 03 * * * * * * Virtual Input 03 1186
1 1,7,9 229 99 Virtual Input 04 * * * * * * Virtual Input 04 1187
1 1,7,9 229 100 Virtual Input 05 * * * * * * Virtual Input 05 1188
1 1,7,9 229 101 Virtual Input 06 * * * * * * Virtual Input 06 1189
1 1,7,9 229 102 Virtual Input 07 * * * * * * Virtual Input 07 1190
1 1,7,9 229 103 Virtual Input 08 * * * * * * Virtual Input 08 1191
1 1,7,9 229 104 Virtual Input 09 * * * * * * Virtual Input 09 1192
1 1,7,9 229 105 Virtual Input 10 * * * * * * Virtual Input 10 1193
1 1,7,9 229 106 Virtual Input 11 * * * * * * Virtual Input 11 1194
1 1,7,9 229 107 Virtual Input 12 * * * * * * Virtual Input 12 1195
1 1,7,9 229 108 Virtual Input 13 * * * * * * Virtual Input 13 1196
1 1,7,9 229 109 Virtual Input 14 * * * * * * Virtual Input 14 1197
1 1,7,9 229 110 Virtual Input 15 * * * * * * Virtual Input 15 1198
1 1,7,9 229 111 Virtual Input 16 * * * * * * Virtual Input 16 1199
1 1,7,9 229 112 Virtual Input 17 * * * * * * Virtual Input 17 1200
1 1,7,9 229 113 Virtual Input 18 * * * * * * Virtual Input 18 1201
1 1,7,9 229 114 Virtual Input 19 * * * * * * Virtual Input 19 1202
1 1,7,9 229 115 Virtual Input 20 * * * * * * Virtual Input 20 1203
1 1,7,9 229 116 Virtual Input 21 * * * * * * Virtual Input 21 1204
1 1,7,9 229 117 Virtual Input 22 * * * * * * Virtual Input 22 1205
1 1,7,9 229 118 Virtual Input 23 * * * * * * Virtual Input 23 1206
1 1,7,9 229 119 Virtual Input 24 * * * * * * Virtual Input 24 1207
1 1,7,9 229 120 Virtual Input 25 * * * * * * Virtual Input 25 1208
1 1,7,9 229 121 Virtual Input 26 * * * * * * Virtual Input 26 1209
1 1,7,9 229 122 Virtual Input 27 * * * * * * Virtual Input 27 1210
1 1,7,9 229 123 Virtual Input 28 * * * * * * Virtual Input 28 1211
1 1,7,9 229 124 Virtual Input 29 * * * * * * Virtual Input 29 1212
1 1,7,9 229 125 Virtual Input 30 * * * * * * Virtual Input 30 1213
1 1,7,9 229 126 Virtual Input 31 * * * * * * Virtual Input 31 1214
1 1,7,9 229 127 Virtual Input 32 * * * * * * Virtual Input 32 1215
1 1,7,9 229 128 Virtual Output01 * * * * * * Virtual Output 01 1216
1 1,7,9 229 129 Virtual Output02 * * * * * * Virtual Output 02 1217
1 1,7,9 229 130 Virtual Output03 * * * * * * Virtual Output 03 1218
1 1,7,9 229 131 Virtual Output04 * * * * * * Virtual Output 04 1219
1 1,7,9 229 132 Virtual Output05 * * * * * * Virtual Output 05 1220
1 1,7,9 229 133 Virtual Output06 * * * * * * Virtual Output 06 1221
1 1,7,9 229 134 Virtual Output07 * * * * * * Virtual Output 07 1222
1 1,7,9 229 135 Virtual Output08 * * * * * * Virtual Output 08 1223
1 1,7,9 229 136 Virtual Output09 * * * * * * Virtual Output 09 1224
1 1,7,9 229 137 Virtual Output10 * * * * * * Virtual Output 10 1225
1 1,7,9 229 138 Virtual Output11 * * * * * * Virtual Output 11 1226
1 1,7,9 229 139 Virtual Output12 * * * * * * Virtual Output 12 1227
1 1,7,9 229 140 Virtual Output13 * * * * * * Virtual Output 13 1228
1 1,7,9 229 141 Virtual Output14 * * * * * * Virtual Output 14 1229
1 1,7,9 229 142 Virtual Output15 * * * * * * Virtual Output 15 1230
1 1,7,9 229 143 Virtual Output16 * * * * * * Virtual Output 16 1231
1 1,7,9 229 144 Virtual Output17 * * * * * * Virtual Output 17 1232
1 1,7,9 229 145 Virtual Output18 * * * * * * Virtual Output 18 1233
1 1,7,9 229 146 Virtual Output19 * * * * * * Virtual Output 19 1234
1 1,7,9 229 147 Virtual Output20 * * * * * * Virtual Output 20 1235
1 1,7,9 229 148 Virtual Output21 * * * * * * Virtual Output 21 1236
1 1,7,9 229 149 Virtual Output22 * * * * * * Virtual Output 22 1237
1 1,7,9 229 150 Virtual Output23 * * * * * * Virtual Output 23 1238
1 1,7,9 229 151 Virtual Output24 * * * * * * Virtual Output 24 1239
1 1,7,9 229 152 Virtual Output25 * * * * * * Virtual Output 25 1240
1 1,7,9 229 153 Virtual Output26 * * * * * * Virtual Output 26 1241
1 1,7,9 229 154 Virtual Output27 * * * * * * Virtual Output 27 1242
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345, P391 (MD) - 126

Inf. Model number


ASDU TYPE COT FUN Description GI Interpretation DDB ordinal
no. 1 2 3 4 5
1 1,7,9 229 155 Virtual Output28 * * * * * * Virtual Output 28 1243
1 1,7,9 229 156 Virtual Output29 * * * * * * Virtual Output 29 1244
1 1,7,9 229 157 Virtual Output30 * * * * * * Virtual Output 30 1245
1 1,7,9 229 158 Virtual Output31 * * * * * * Virtual Output 31 1246
1 1,7,9 229 159 Virtual Output32 * * * * * * Virtual Output 32 1247

Private range information numbers in control direction

Inf. Model number


ASDU TYPE COT FUN Display text (English) GI DDB signal description DDB ordinal
no. 1 2 3 4 5
20 20 229 64 Control Input 1 * * * * Control Input 1152
20 20 229 65 Control Input 2 * * * * Control Input 1153
20 20 229 66 Control Input 3 * * * * Control Input 1154
20 20 229 67 Control Input 4 * * * * Control Input 1155
20 20 229 68 Control Input 5 * * * * Control Input 1156
20 20 229 69 Control Input 6 * * * * Control Input 1157
20 20 229 70 Control Input 7 * * * * Control Input 1158
20 20 229 71 Control Input 8 * * * * Control Input 1159
20 20 229 72 Control Input 9 * * * * Control Input 1160
20 20 229 73 Control Input 10 * * * * Control Input 1161
20 20 229 74 Control Input 11 * * * * Control Input 1162
20 20 229 75 Control Input 12 * * * * Control Input 1163
20 20 229 76 Control Input 13 * * * * Control Input 1164
20 20 229 77 Control Input 14 * * * * Control Input 1165
20 20 229 78 Control Input 15 * * * * Control Input 1166
20 20 229 79 Control Input 16 * * * * Control Input 1167
20 20 229 80 Control Input 17 * * * * Control Input 1168
20 20 229 81 Control Input 18 * * * * Control Input 1169
20 20 229 82 Control Input 19 * * * * Control Input 1170
20 20 229 83 Control Input 20 * * * * Control Input 1171
20 20 229 84 Control Input 21 * * * * Control Input 1172
20 20 229 85 Control Input 22 * * * * Control Input 1173
20 20 229 86 Control Input 23 * * * * Control Input 1174
20 20 229 87 Control Input 24 * * * * Control Input 1175
20 20 229 88 Control Input 25 * * * * Control Input 1176
20 20 229 89 Control Input 26 * * * * Control Input 1177
20 20 229 90 Control Input 27 * * * * Control Input 1178
20 20 229 91 Control Input 28 * * * * Control Input 1179
20 20 229 92 Control Input 29 * * * * Control Input 1180
20 20 229 93 Control Input 30 * * * * Control Input 1181
20 20 229 94 Control Input 31 * * * * Control Input 1182
20 20 229 95 Control Input 32 * * * * Control Input 1183

Disturbance data actual channel identifiers


ACC Standard Interpretation
0 Global Null Channel
1 IL1 IA
2 IL2 IB
3 IL3 IC
4 IN IN
5 VL1E VAN
6 VL2E VBN
7 VL3E VCN
8 VEN VN
64 - IN Sensitive
65 - IA-2
66 - IB-2
67 - IC-2
245 - SampleTime
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -127

1. INTRODUCTION
The purpose of this document is to describe the specific implementation of the Distributed
Network Protocol (DNP) version 3.0 within P34x MiCOM relays.
The MiCOM P34x uses the Triangle MicroWorks, Inc. DNP 3.0 Slave Source Code Library
version 3.00.
This document, in conjunction with the DNP 3.0 Basic 4 Document Set, and the DNP Subset
Definitions Document, provides complete information on how to communicate with P340
relays with the DNP 3.0 protocol.
This implementation of DNP 3.0 is fully compliant with DNP 3.0 Subset Definition Level 2. It
also contains many Subset Level 3 and above features.

2. DNP V3.0 DEVICE PROFILE


The following table provides a Device Profile Document in the standard format defined in
the DNP 3.0 Subset Definitions Document. While it is referred to in the DNP 3.0 Subset
Definitions as a Document, it is only a component of a total interoperability guide. This
table, in combination with the following should provide a complete
interoperability/configuration guide for the P34x range of MiCOM relays:

The Implementation Table provided in Section 3

The Point List Tables provided in Section 6


P34x/EN MD/J76 Relay Menu Database

(MD) -128 MiCOM P342, P343, P344, P345 & P391

DNP 3.0
Device Profile Document
Vendor Name: AREVA T&D UK Ltd. Automation & Information Systems
Device Name: MiCOM P340 Generator Protection
Models Covered: P341****4*0330*
P342****4*0330*
P343****4*0330*
P344****4*0330*
P345****4*0330*
Highest DNP Level Supported 1: Device Function:
For Requests: Level 2 Master
For Responses: Level 2 Slave
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP levels
supported (the complete list is described in the DNP 3.0 Implementation Table):

For static (non-change event) object requests, request qualifier codes 00 and 01
(start-stop), 07 and 08 (limited quantity), and 17 and 28 (index) are supported in addition to
the request qualifier code 06 (no range (all points)).
Static object requests sent with qualifiers 00, 01, 06, 07, or 08 will be responded with
qualifiers 00 or 01.
Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or
28.
For change-event object requests, qualifiers 17 or 28 are always responded.
16-bit and 32-bit analog change events with time may be requested.
The read function code for Object 50 (time and date) variation 1 is supported.
Analog Input Deadbands, Object 34, variations 1 through 3, are supported.
Floating Point Analog Output Status and Output Block Objects 40 and 41 are supported.
Sequential file transfer, Object 70, variations 2 through 7, are supported.
Device Attribute Object 0 is supported.
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets)
Transmitted: 292 Transmitted: Configurable (100 to 2048),
default 2048
Received: 292
Received: 249
Maximum Data Link Retries: Maximum Application Layer Retries:
None None
Fixed at 2 Configurable
Configurable
Requires Data Link Layer Confirmation: Requires Application Layer Confirmation:
Never Never
Always Always
Sometimes When reporting event data (Slave devices
Configurable only)
Configurable to Never or Always When sending multi-fragment
responses (Slave devices only)
Sometimes
Configurable

1 This is the highest DNP level FULLY supported. Parts of level 3 are also supported.
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -129

Timeouts while waiting for:


Data Link Confirm: None Fixed at ___ Variable Configurable
Complete Appl. Fragment: None Fixed at ___ Variable Configurable
Application Confirm: None Fixed at ___ Variable Configurable
Complete Appl. Response: None Fixed at ___ Variable Configurable
Others:
Data Link Confirm Timeout: Configurable from 0 (Disabled) to 120s, default 10s
Application Confirm Timeout: Configurable from 1 to 120s, default 2s
Select/Operate Arm Timeout: Configurable from 1 to 10s, default 10s
Application File Timeout: 60s
Binary Change Event Scan Period: 4 times per power system cycle
Analog Change Event Scan Period: 0.5s
Counter Change Event Scan Period: 0.5s
Frozen Counter Change Event Scan
1s
Period:
Configurable Disabled (default) or 1 to 30min
Need Time (Set IIN1-4):
(if enabled defaults to 30min)
Maximum delay measurement error: 2.5ms

Time base drift over a 10-minute 7ms


interval:

Maximum response time: Indeterminate


Never
Local Control (Set IIN1-5)
(Do no support placing binary outputs in a local state.)
Sends/Executes Control Operations 2:
Write Binary Outputs: Never Always Sometimes Configurable
Select/Operate: Never Always Sometimes Configurable
Direct Operate: Never Always Sometimes Configurable
Direct Operate No Ack: Never Always Sometimes Configurable

Count > 1 Never Always Sometimes Configurable


Pulse On Never Always Sometimes Configurable
Pulse Off Never Always Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable

Queue Never Always Sometimes Configurable


Clear Queue Never Always Sometimes Configurable
Maximum number of controls allowed in a single request 10
Paired Control points will accept Pulse On/Trip and Pulse On/Close, but only single point will accept
the Pulse Off control command.

2 It is recommended that all Control Relay Output Block (CROB) operations be accepted, as each
command will effectively perform the same operation. See DNP Technical bulletin TB2000-006 for
details.
P34x/EN MD/J76 Relay Menu Database

(MD) -130 MiCOM P342, P343, P344, P345 & P391

Reports Binary Input Change Events when no Reports time-tagged Binary Input Change
specific variation requested: Events when no specific variation requested:
Never Never
Only time-tagged Binary input change with time
Only non-time-tagged Binary input change with relative time
Configurable to send one or the other Configurable
Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:
Never Never
Configurable When device restarts
Certain objects only When status flags changes
Sometimes
Enable/Disable unsolicited functions codes No other options are permitted
supported
Default Counter Object/Variation: Counters Roll Over at:
No counters reported No counters reported
Configurable Configurable
Default object 16 bits
Default variation 32 bits
Point-by-point list attached Other value: _____
Point-by-point list attached
Sends multi-fragment responses:
Yes
No
Configurable
Support Self Address
No Configurable
Multi-drop Support Yes No
Collision Avoidance Yes No
Sequential File Transfer Support:

Append File Mode Yes No


Custom Status Code Strings Yes No
Permissions Field Yes No
File Events Assigned to Class Yes No
File Events Send Immediately Yes No
Multiple Blocks in a Fragment Yes No
Max Number of Files Open 1
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -131

3. IMPLEMENTATION TABLE
The following table identifies the variations, function codes, and qualifiers supported by the
P34x in both request and response messages.

Object Request Response

Object Variation Function Codes


Description Function Codes (dec) Qualifier Codes (hex) Qualifier Codes (hex)
Number Number (dec)

0 1-253 Device Attribute Specific 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)

06 (no range, or all) 17, 28


(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

0 254 Device Attribute - Non- 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Specific All Attributes
Request 06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

0 255 Device Attribute List of 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Attribute Variations
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

1 0 Binary Input Any 1 (read) 00, 01 (start-stop)


Variation
22 (assign class) 06 (no range, or all)

07, 08 (limited qty)

17, 27, 28 (index)

1 1 Binary Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)

(default 06 (no range, or all) 17, 28


see note 1) (index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

1 2 Binary Input with Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)

06 (no range, or all) 17, 28


(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

2 0 Binary Input Change 1 (read) 06 (no range, or all)


Any Variation
07, 08 (limited qty)

2 1 Binary Input Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time
07, 08 (limited qty)

2 2 Binary Input Change with 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time
07, 08 (limited qty)

10 0 Binary Output Status 1 (read) 00, 01 (start-stop)


Any Variation
06 (no range, or all)

07, 08 (limited qty)

17, 27, 28 (index)

10 2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)

(default 06 (no range, or all) 17, 28


see note 1) (index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

12 1 Control Relay Output 3 (select) 17, 28 (index) 129 (response) echo of request
Block
4 (operate)

5 (direct op)

6 (dir. op, noack)


P34x/EN MD/J76 Relay Menu Database

(MD) -132 MiCOM P342, P343, P344, P345 & P391

Object Request Response

Object Variation Function Codes


Description Function Codes (dec) Qualifier Codes (hex) Qualifier Codes (hex)
Number Number (dec)

20 0 Binary Counter Any 1 (read) 00, 01 (start-stop)


Variation
22 (assign class) 06 (no range, or all)

07, 08 (limited qty)

17, 27, 28 (index)

7 (freeze) 00, 01 (start-stop)

8 (freeze noack) 06 (no range, or all)

9 (freeze clear) 07, 08 (limited qty)

10 (frz. cl. noack)

20 1 32-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(with Flag)
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

20 2 16-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(with Flag)
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

20 5 32-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag
(default 06 (no range, or all) 17, 28
see note 1) (index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

20 6 16-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

21 0 Frozen Counter Any 1 (read) 00, 01 (start-stop)


Variation
06 (no range, or all)

07, 08 (limited qty)

17, 27, 28 (index)

21 1 32-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(with Flag)
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

21 2 16-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(with Flag)
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

21 5 32-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
with Time Of Freeze
06 (no range, or all) 17, 28
(index see note 1)
07, 08 (limited qty)

17, 27, 28 (index)

21 6 16-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
with Time Of Freeze
06 (no range, or all) 17, 28
(index see note 1)
07, 08 (limited qty)

17, 27, 28 (index)

21 9 32-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag
(default 06 (no range, or all) 17, 28
see note 1) (index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

21 10 16-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)


Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -133

Object Request Response

Object Variation Function Codes


Description Function Codes (dec) Qualifier Codes (hex) Qualifier Codes (hex)
Number Number (dec)

22 0 Counter Change Event 1 (read) 06 (no range, or all)


Any Variation
07, 08 (limited qty)

22 1 32-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event without Time
(default 07, 08 (limited qty)
see note 1)

22 2 16-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event without Time
07, 08 (limited qty)

22 5 32-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time
07, 08 (limited qty)

22 6 16-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time
07, 08 (limited qty)

23 0 Frozen Counter Event 1 (read) 06 (no range, or all)


(Variation 0 is used to
request default variation) 07, 08 (limited qty)

23 1 32-Bit Frozen Counter 1 (read) 06 (no range, or all) 129 (response) 17,28 (index)
Event
(default 07, 08 (limited qty)
see note 1)

23 2 16-Bit Frozen Counter 1 (read) 06 (no range, or all) 129 (response) 17,28 (index)
Event
07, 08 (limited qty)

23 5 32-Bit Frozen Counter 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time
07, 08 (limited qty)

23 6 16-Bit Frozen Counter 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time
07, 08 (limited qty)

30 0 Analog Input - Any 1 (read) 00, 01 (start-stop)


Variation
22 (assign class) 06 (no range, or all)

07, 08 (limited qty)

17, 27, 28 (index)

30 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)

06 (no range, or all) 17, 28


(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

30 2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)

06 (no range, or all) 17, 28


(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

30 3 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag
(default 06 (no range, or all) 17, 28
see note 1) (index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

30 4 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag
06 (no range, or all) 17, 28 (index

07, 08 (limited qty) see note 2)

17, 27, 28 (index)

30 5 short floating point 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)

06 (no range, or all) 17, 28


(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

32 0 Analog Change Event 1 (read) 06 (no range, or all)


Any Variation
07, 08 (limited qty)

32 1 32-Bit Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event without Time
(default 07, 08 (limited qty)
see note 1)

32 2 16-Bit Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event without Time
07, 08 (limited qty)
P34x/EN MD/J76 Relay Menu Database

(MD) -134 MiCOM P342, P343, P344, P345 & P391

Object Request Response

Object Variation Function Codes


Description Function Codes (dec) Qualifier Codes (hex) Qualifier Codes (hex)
Number Number (dec)

32 3 32-Bit Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time
07, 08 (limited qty)

32 4 16-Bit Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time
07, 08 (limited qty)

32 5 Short floating point 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Analog Change Event
without Time 07, 08 (limited qty)

32 7 Short floating point 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Analog Change Event
with Time 07, 08 (limited qty)

34 0 Analog Input Deadband 1 (read) 00, 01 (start-stop)


(Variation 0 is used to
request default variation) 06 (no range, or all)

07, 08 (limited qty)

17, 27, 28 (index)

34 1 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Deadband
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

2 (write) 00, 01 (start-stop)

07, 08 (limited qty)

17, 27, 28 (index)

34 2 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Deadband
(default 06 (no range, or all) 17, 28
see note 1) (index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

2 (write) 00, 01 (start-stop)

07, 08 (limited qty)

17, 27, 28 (index)

34 3 Short Floating Point 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Analog Input Deadband
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

2 (write) 00, 01 (start-stop)

07, 08 (limited qty)

17, 27, 28 (index)

40 0 Analog Output Status 1 (read) 00, 01 (start-stop)


(Variation 0 is used to
request default variation) 06 (no range, or all)

07, 08 (limited qty)

17, 27, 28 (index)

40 1 32-Bit Analog Output 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Status
(default 06 (no range, or all) 17, 28
see note 1) (index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

40 2 16-Bit Analog Output 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Status
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

40 3 Short floating point 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Analog Output Status
06 (no range, or all) 17, 28
(index see note 2)
07, 08 (limited qty)

17, 27, 28 (index)

41 1 32-Bit Analog Output 3 (select) 17, 28 (index) 129 (response) echo of request
Block
4 (operate) 27 (index)

5 (direct op)

6 (dir. op, noack)


Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -135

Object Request Response

Object Variation Function Codes


Description Function Codes (dec) Qualifier Codes (hex) Qualifier Codes (hex)
Number Number (dec)

41 2 16-Bit Analog Output 3 (select) 17, 28 (index) 129 (response) echo of request
Block
4 (operate) 27 (index)

5 (direct op)

6 (dir. op, noack)

41 3 Short floating point 3 (select) 17, 27, 28 (index) 129 (response) echo of request
Analog Output Block
4 (operate)

5 (direct op)

6 (dir. op, noack)

50 1 Time and Date 1 (read) 07, (limited qty = 1) 129 (response) 07 (limited qty = 1)

(default
see note 1)

2 (write) 07 (limited qty = 1)

60 0 Not Defined

60 1 Class 0 Data 1 (read) 06 (no range, or all)

60 2 Class 1 Data 1 (read) 06 (no range, or all)

07, 08 (limited qty)

22 (assign class) 06 (no range, or all)

60 3 Class 2 Data 1(read) 06 (no range, or all)

07, 08 (limited qty)

22 (assign class) 06 (no range, or all)

60 4 Class 3 Data 1 (read) 06 (no range, or all)

07, 08 (limited qty)

22 (assign class) 06 (no range, or all)

70 0 File Event Any 1 (read) 06 (no range, or all)


Variation
07, 08 (limited qty)

22 (assign class) 06 (no range, or all)

70 2 File Authentication 29 (authenticate) 5b (free-format) 129 (response) 5B (free-format)

70 3 File Command 25 (open) 5b (free-format)

27 (delete)

70 4 File Command Status 26 (close) 5b (free-format) 129 (response) 5B (free-format)

30 (abort)

70 5 File Transfer 1 (read) 5b (free-format) 129 (response) 5B (free-format)

70 6 File Transfer Status 129 (response) 5B (free-format)

70 7 File Descriptor 28 (get file info) 5b (free-format) 129 (response) 5B (free-format)

80 1 Internal Indications 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)

No Object 13 (cold restart)


(function code only)

No Object 14 (warm restart)


(function code only)

No Object 23 (delay meas.)


(function code only)
P34x/EN MD/J76 Relay Menu Database

(MD) -136 MiCOM P342, P343, P344, P345 & P391

Notes:
1. A Default variation refers to the variation responded when variation 0 is requested
and/or in class 0, 1, 2, or 3 scans.
2. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a
request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests
sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01.
For change-event objects, qualifiers 17 or 28 are always responded.

4. INTERNAL INDICATIONS
The following table lists the DNP3.0 Internal Indications (IIN) and identifies those that are
supported by the MiCOM P34x.
The IIN forms an information element used to convey the internal states and diagnostic
results of the responding device. The information can be used by the receiving station to
perform error recovery or other suitable functions. The IIN is a two-octet field that follows the
function code in all responses. When a request cannot be processed due to formatting
errors or the requested data is not available, the IIN is always returned with the appropriate
bits set.

IIN
Indication Description Supported
Octet Bit
Set when a request is received with the
destination address of the all stations address
(6553510). It is cleared after the next
response (even if a response to a global
0 All stations message received request is required).
This IIN is used to let the master station know
that a "broadcast" message was received by
the relay.
Set when data that has been configured as
Class 1 data is ready to be sent to the master.
1 Class 1 data available The master station should request this class
data from the relay when this bit is set in a
response.
Set when data that has been configured as
Class 2 data is ready to be sent to the master.
1
2 Class 2 data available The master station should request this class
data from the relay when this bit is set in a
response.
Set when data that has been configured as
Class 3 data is ready to be sent to the master.
3 Class 3 data available The master station should request this class
data from the relay when this bit is set in a
response.
The relay requires time synchronization from
the master station (using the Time and Date
object).
4 Time-synchronization required This IIN is cleared once the time has been
synchronized. It can also be cleared by
explicitly writing a 0 into this bit of the Internal
Indication object.
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -137

IIN
Indication Description Supported
Octet Bit
Set when some or all of the devices digital
output points (Object 10/12) are in the Local
state. That is, some or all of the devices
control outputs are NOT accessible through
5 Local the DNP protocol.
Clear when the device is in the Remote state.
That is, all of the devices control outputs are
accessible through the DNP protocol.
1 Set when an abnormal condition exists in the
device. This IIN is only used when the state
6 Device in trouble
can not be described by a combination of one
or more of the other IIN bits.
Set when the devices software application
restarts.
7 Device restart This IIN is cleared when the master station
explicitly writes a 0 into this bit of the Internal
Indications object.
The received function code is not implemented
0 Function code not implemented
within the relay.
The device does not have the specified objects
or there are no objects assigned to the
requested class.
1 Requested object(s) unknown
This IIN should be used for debugging
purposes and usually indicates a mismatch in
device profiles or configuration problems.
Parameters in the qualifier, range or data fields
are not valid or out of range. This is a
'catch-all' for application request formatting
2 Out of range errors. It should only be used for debugging
purposes.
This IIN usually indicates configuration
problems.
2
Event buffer(s), or other application buffers,
have overflowed.
The master station should attempt to recover
3 Buffer overflow as much data as possible and indicate to the
user that their may be lost data.
The appropriate error recovery procedures
should be initiated by the user.
The received request was understood but the
4 Already executing
requested operation is already executing.
Set to indicate that the current configuration in
5 Bad configuration the relay is corrupt. The master station may
download another configuration to the relay.
6 Reserved Always returned as zero.
7 Reserved Always returned as zero.
P34x/EN MD/J76 Relay Menu Database

(MD) -138 MiCOM P342, P343, P344, P345 & P391

5. RESPONSE STATUS CODES


The response to an Object 12 request includes a status code for each object-point in the
request. The complete list of the code values is presented in the following table:

Code
Identifier Name Description
Number
0 Success The received request has been accepted, initiated, or queued.
The request has not been accepted because the operate message was
received after the arm timer (Select Before Operate) timed out.
1 Timeout
The arm timer was started when the select operation for the same point
was received.
The request has not been accepted because no previous matching
2 No select select request exists. (An operate message was sent to activate an
output that was not previously armed with a matching select message).
The request has not been accepted because there were formatting
3 Format error
errors in the control request (select, operate, or direct operate).
The request has not been accepted because a control operation is not
4 Not supported
supported for this point.
The request has not been accepted because the control queue is full or
5 Already active
the point is already active.
The request has not been accepted because of control hardware
6 Hardware error
problems.
7 Local The request has not been accepted because local access is in progress.
The request has not been accepted because too many operations have
8 Too many operations
been requested in the same request.
The request has not been accepted because of insufficient
9 Not authorized
authorization.
The request not been accepted because of some other undefined
127 Undefined
reason.

Note: Code numbers 10 through to 126 are reserved for future use.

6. POINT LIST
The tables in the following sections identify all the individual data points provided by this
implementation of DNP 3.0.

6.1 Binary input points


The Binary Input objects (1 & 2) provide read-only access to a sub-set of the P340s digital
data bus (DDB).
By default, all the static object (object 1) points belong to the Class 0 data set. The default
allocation of the points in the change-event object (object 2) to a change-event class (1, 2, 3)
is indicated in the point-list table below. The MiCOM S1 Studio setting support software may
be used to alter both of these assignments. However, deselecting a point from class 0 also
has the effect of removing the point from the point-list of objects 1 & 2 and renumbering the
remaining points to ensure the point indices are contiguous.
The validity of each point is reported through the online bit in the flag, which is supplied
for each point with the with flag object variations. Points reported as being offline, will
typically be points that are invalid for the relays current configuration, which is a product of
its model number and current settings.
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -139

Generally, the accuracy of the time-stamp is with respect to when the DNP driver in the
device scans and detects a change. The scan interval is 0.5s, which can result in up to a
0.5s latency error between when the event actually occurred and its timestamp 3. However,
the time stamps associated with points that originate from the devices Digital Data Bus
(DDB) do not suffer from this latency error because their time of change is recorded at
source 4.

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description Event Class
if 5 NO
Index Index Index Index Index (1, 2, 3, or
none)
Output Relay Status
0 0 0 0 0 Output Relay 1 Always 0 2
1 1 1 1 1 Output Relay 2 Always 1 2
2 2 2 2 2 Output Relay 3 Always 2 2
3 3 3 3 3 Output Relay 4 Always 3 2
4 4 4 4 4 Output Relay 5 Always 4 2
5 5 5 5 5 Output Relay 6 Always 5 2
6 6 6 6 6 Output Relay 7 Always 6 2
7 7 7 7 7 Output Relay 8 Fitted 7 2
8 8 8 8 8 Output Relay 9 Fitted 8 2
9 9 9 9 9 Output Relay 10 Fitted 9 2
10 10 10 10 10 Output Relay 11 Fitted 10 2
11 11 11 11 11 Output Relay 12 Fitted 11 2
12 12 12 12 12 Output Relay 13 Fitted 12 2
13 13 13 13 13 Output Relay 14 Fitted 13 2
14 14 14 14 14 Output Relay 15 Fitted 14 2
15 15 15 15 15 Output Relay 16 Fitted 15 2
16 16 16 16 16 Output Relay 17 Fitted 16 2
17 17 17 17 17 Output Relay 18 Fitted 17 2
18 18 18 18 18 Output Relay 19 Fitted 18 2
19 19 19 19 19 Output Relay 20 Fitted 19 2
20 20 20 20 20 Output Relay 21 Fitted 20 2
21 21 21 21 21 Output Relay 22 Fitted 21 2

3 Note that this is in addition to any latency that the device might introduce in detecting changes to its
external inputs.
4 Object points associated with a DDB signal have their DDB number indicated in the point list table.
5 Note that points marked Never are inputs that have been forced offline but have not been removed
entirely in order to preserve point allocation compatibility with previous device software versions.
These points will always have a value of zero and will never generate an Object 2 change-event.
P34x/EN MD/J76 Relay Menu Database

(MD) -140 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
22 22 22 22 22 Output Relay 23 Fitted 22 2
23 23 23 23 23 Output Relay 24 Fitted 23 2
24 24 24 Output Relay 25 Fitted 24 2
25 25 25 Output Relay 26 Fitted 25 2
26 26 26 Output Relay 27 Fitted 26 2
27 27 27 Output Relay 28 Fitted 27 2
28 28 28 Output Relay 29 Fitted 28 2
29 29 29 Output Relay 30 Fitted 29 2
30 30 30 Output Relay 31 Fitted 30 2
31 31 31 Output Relay 32 Fitted 31 2
Opto Isolator Input Status
24 24 32 32 32 Opto Isolator Input 1 Always 32 2
25 25 33 33 33 Opto Isolator Input 2 Always 33 2
26 26 34 34 34 Opto Isolator Input 3 Always 34 2
27 27 35 35 35 Opto Isolator Input 4 Always 35 2
28 28 36 36 36 Opto Isolator Input 5 Always 36 2
29 29 37 37 37 Opto Isolator Input 6 Always 37 2
30 30 38 38 38 Opto Isolator Input 7 Always 38 2
31 31 39 39 39 Opto Isolator Input 8 Always 39 2
32 32 40 40 40 Opto Isolator Input 9 Fitted 40 2
33 33 41 41 41 Opto Isolator Input 10 Fitted 41 2
34 34 42 42 42 Opto Isolator Input 11 Fitted 42 2
35 35 43 43 43 Opto Isolator Input 12 Fitted 43 2
36 36 44 44 44 Opto Isolator Input 13 Fitted 44 2
37 37 45 45 45 Opto Isolator Input 14 Fitted 45 2
38 38 46 46 46 Opto Isolator Input 15 Fitted 46 2
39 39 47 47 47 Opto Isolator Input 16 Fitted 47 2
40 40 48 48 48 Opto Isolator Input 17 Fitted 48 2
41 41 49 49 49 Opto Isolator Input 18 Fitted 49 2
42 42 50 50 50 Opto Isolator Input 19 Fitted 50 2
43 43 51 51 51 Opto Isolator Input 20 Fitted 51 2
44 44 52 52 52 Opto Isolator Input 21 Fitted 52 2
45 45 53 53 53 Opto Isolator Input 22 Fitted 53 2
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -141

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
46 46 54 54 54 Opto Isolator Input 23 Fitted 54 2
47 47 55 55 55 Opto Isolator Input 24 Fitted 55 2
56 56 56 Opto Isolator Input 25 Fitted 56 2
57 57 57 Opto Isolator Input 26 Fitted 57 2
58 58 58 Opto Isolator Input 27 Fitted 58 2
59 59 59 Opto Isolator Input 28 Fitted 59 2
60 60 60 Opto Isolator Input 29 Fitted 60 2
61 61 61 Opto Isolator Input 30 Fitted 61 2
62 62 62 Opto Isolator Input 31 Fitted 62 2
63 63 63 Opto Isolator Input 32 Fitted 63 2
Alarm & Event Indications
Setting Group Selection by
48 48 64 64 64 Always 354 2
DDB Inputs Invalid
49 49 65 65 65 Test Mode Enabled Always 355 2
50 50 66 66 66 VTS VT Fail Alarm Always 356 2
51 51 67 67 67 CTS-1 CT-1 Fail Alarm Always 357 2
52 52 68 68 68 Breaker Fail Any Trip Always 358 2
Broken Current
53 53 69 69 69 Always 359 2
Maintenance Alarm
Broken Current Lockout
54 54 70 70 70 Always 360 2
Alarm
Number of CB Operations
55 55 71 71 71 Always 361 2
Maintenance Alarm
Number of CB Operations
56 56 72 72 72 Always 362 2
Maintenance Lockout
Excessive CB Operation
57 57 73 73 73 Always 363 2
Time Maintenance Alarm
Excessive CB Operation
58 58 74 74 74 Always 364 2
Time Lockout Alarm
Excessive Fault Frequency
59 59 75 75 75 Always 365 2
Lockout Alarm
60 60 76 76 76 CB Status Alarm Always 366 2
61 CB Failed to Trip Always 367 2
62 CB Failed to Close Always 368 2
63 Control CB Unhealthy Always 369 2
64 Frequency Out of Range Always 370 2
P34x/EN MD/J76 Relay Menu Database

(MD) -142 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
Negative Phase Sequence
61 77 77 77 Always 370 2
Alarm
65 62 78 78 78 Thermal Overload Alarm Always 371 2
63 79 79 79 Volts Per Hz Alarm Always 372 2
64 80 80 80 Field Failure Alarm Always 373 2
65 81 81 81 RTD Thermal Alarm Always 374 2
66 82 82 82 RTD Open Circuit Failure Always 375 2
67 83 83 83 RTD Short Circuit Failure Always 376 2
RTD Data Inconsistency
68 84 84 84 Always 377 2
Error
69 85 85 85 RTD Board Failure Always 378 2
Frequency Protection
66 70 86 86 86 Always 379 2
Alarm
67 71 87 87 87 Voltage Protection Alarm Always 380 2
User Definable Alarm 1
68 72 88 88 88 Always 415 2
(Self Reset)
User Definable Alarm 2
69 73 89 89 89 Always 414 2
(Self Reset)
User Definable Alarm 3
70 74 90 90 90 Always 413 2
(Self Reset)
75 91 91 91 RTD 1 Alarm Always 1031 2
76 92 92 92 RTD 2 Alarm Always 1032 2
77 93 93 93 RTD 3 Alarm Always 1033 2
78 94 94 94 RTD 4 Alarm Always 1034 2
79 95 95 95 RTD 5 Alarm Always 1035 2
80 96 96 96 RTD 6 Alarm Always 1036 2
81 97 97 97 RTD 7 Alarm Always 1037 2
82 98 98 98 RTD 8 Alarm Always 1038 2
83 99 99 99 RTD 9 Alarm Always 1039 2
84 100 100 100 RTD 10 Alarm Always 1040 2
71 85 101 101 101 Composite Lockout Alarm Always 1041 2
72 86 102 102 102 Field Voltage Failure Always 417 2
Miscellaneous Indications
73 87 103 103 103 Battery Status Always 2
Fitted &
74 88 104 104 104 IRIG-B Status 2
Enabled
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -143

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
Protection Operation Signals
75 89 105 105 105 Any Trip 6 Always 626 2
76 90 106 106 106 External Trip 3ph Never 610 2
100% Stator Earth Fault
107 107 107 Always 738 2
(3rd Harmonic) Trip
Dead Machine Protection
108 108 108 Always 755 2
Trip
Generator Differential Trip
109 109 109 Always 640 2
3ph
Generator Differential Trip
110 110 110 Always 641 2
A
Generator Differential
111 111 111 Always 642 2
Trip B
Generator Differential
112 112 112 Always 643 2
Trip C
91 113 113 113 Field Failure Stage 1 Trip Always 644 2
92 114 114 114 Field Failure Stage 2 Trip Always 645 2
Negative Phase Sequence
93 115 115 115 Always 702 2
Trip
Voltage Dependant Over
94 116 116 116 Always 724 2
Current Trip 3ph
Voltage Dependant Over
95 117 117 117 Always 725 2
Current Trip A
Voltage Dependant Over
96 118 118 118 Always 726 2
Current Trip B
Voltage Dependant Over
97 119 119 119 Always 727 2
Current Trip C
98 120 120 120 Volts per Hz Trip Always 646 2
99 121 121 121 RTD 1 Trip Always 650 2
100 122 122 122 RTD 2 Trip Always 651 2
101 123 123 123 RTD 3 Trip Always 652 2
102 124 124 124 RTD 4 Trip Always 653 2
103 125 125 125 RTD 5 Trip Always 654 2
104 126 126 126 RTD 6 Trip Always 655 2
105 127 127 127 RTD 7 Trip Always 656 2

6 Prior to Software version 32 this functionality was implicit in the operation of output relay 3.
P34x/EN MD/J76 Relay Menu Database

(MD) -144 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
106 128 128 128 RTD 8 Trip Always 657 2
107 129 129 129 RTD 9 Trip Always 658 2
108 130 130 130 RTD 10 Trip Always 659 2
109 131 131 131 Any RTD Trip Always 660 2
Rate Of Change Of
77 Always 661 2
Frequency Trip
78 Voltage Vector Shift Trip Always 662 2
79 110 132 132 132 1st Stage EF Trip Always 663 2
80 111 133 133 133 2nd Stage EF Trip Always 664 2
81 3rd Stage EF Trip Always 665 2
82 4th Stage EF Trip Always 666 2
83 112 134 134 134 REF Trip Always 667 2
84 113 135 135 135 1st Stage SEF Trip Always 668 2
85 2nd Stage SEF Trip Always 669 2
86 3rd Stage SEF Trip Always 670 2
87 4th Stage SEF Trip Always 671 2
1st Stage Residual O/V
88 114 136 136 136 Always 672 2
Trip
2nd Stage Residual O/V
89 115 137 137 137 Always 673 2
Trip
1st Stage Phase U/V Trip
90 116 138 138 138 Always 678 2
3ph
1st Stage Phase U/V Trip
91 117 139 139 139 Always 679 2
A/AB
1st Stage Phase U/V Trip
92 118 140 140 140 Always 680 2
B/BC
1st Stage Phase U/V Trip
93 119 141 141 141 Always 681 2
C/CA
2nd Stage Phase U/V Trip
94 120 142 142 142 Always 682 2
3ph
2nd Stage Phase U/V Trip
95 121 143 143 143 Always 683 2
A/AB
2nd Stage Phase U/V Trip
96 122 144 144 144 Always 684 2
B/BC
2nd Stage Phase U/V Trip
97 123 145 145 145 Always 685 2
C/CA
1st Stage Phase O/V Trip
98 124 146 146 146 Always 686 2
3ph
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -145

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
1st Stage Phase O/V Trip
99 125 147 147 147 Always 687 2
A/AB
1st Stage Phase O/V Trip
100 126 148 148 148 Always 688 2
B/BC
1st Stage Phase O/V Trip
101 127 149 149 149 Always 689 2
C/CA
2nd Stage Phase O/V Trip
102 128 150 150 150 Always 690 2
3ph
2nd Stage Phase O/V Trip
103 129 151 151 151 Always 691 2
A/AB
2nd Stage Phase O/V Trip
104 130 152 152 152 Always 692 2
B/BC
2nd Stage Phase O/V Trip
105 131 153 153 153 Always 693 2
C/CA
Under Frequency Stage 1
106 132 154 154 154 Always 694 2
Trip
Under Frequency Stage 2
107 133 155 155 155 Always 695 2
Trip
Under Frequency Stage 3
108 134 156 156 156 Always 696 2
Trip
Under Frequency Stage 4
109 135 157 157 157 Always 697 2
Trip
Over Frequency Stage 1
110 136 158 158 Always 698 2
Trip
Over Frequency Stage 2
111 137 159 159 Always 699 2
Trip
112 138 160 160 Power Stage 1 Trip Always 700 2
113 139 161 161 Power Stage 2 Trip Always 701 2
114 140 162 162 1st Stage O/C Trip 3ph Always 704 2
115 141 163 163 1st Stage O/C Trip A Always 705 2
116 142 164 164 1st Stage O/C Trip B Always 706 2
117 143 165 165 1st Stage O/C Trip C Always 707 2
118 144 166 166 2nd Stage O/C Trip 3ph Always 708 2
119 145 167 167 2nd Stage O/C Trip A Always 709 2
120 146 168 168 2nd Stage O/C Trip B Always 710 2
121 147 169 169 2nd Stage O/C Trip C Always 711 2
122 3rd Stage O/C Trip 3ph Always 712 2
123 3rd Stage O/C Trip A Always 713 2
P34x/EN MD/J76 Relay Menu Database

(MD) -146 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
124 3rd Stage O/C Trip B Always 714 2
125 3rd Stage O/C Trip C Always 715 2
126 4th Stage O/C Trip 3ph Always 716 2
127 4th Stage O/C Trip A Always 717 2
128 4th Stage O/C Trip B Always 718 2
129 4th Stage O/C Trip C Always 719 2
130 148 170 170 170 tBF1 Trip 3ph Always 736 2
131 149 171 171 171 tBF2 Trip 3ph Always 737 2
Sensitive A Phase Power
132 150 172 172 172 Always 720 2
Stage 1 Trip
Sensitive A Phase Power
133 151 173 173 173 Always 721 2
Stage 2 Trip
Pole Slip (Impedance)
174 174 174 Always 722 2
Zone1 Trip
Pole Slip (Impedance)
175 175 175 Always 723 2
Zone2 Trip
134 152 176 176 176 Thermal Overload Trip Always 703 2
Under Impedance 3 Phase
153 177 177 177 Always 728 2
Stage 1 Trip
Under Impedance Phase A
154 178 178 178 Always 729 2
Stage 1 Trip
Under Impedance Phase B
155 179 179 179 Always 730 2
Stage 1 Trip
Under Impedance Phase C
156 180 180 180 Always 731 2
Stage 1 Trip
Under Impedance 3 Phase
157 181 181 181 Always 732 2
Stage 2 Trip
Under Impedance Phase A
158 182 182 182 Always 733 2
Stage 2 Trip
Under Impedance Phase B
159 183 183 183 Always 734 2
Stage 2 Trip
Under Impedance Phase C
160 184 184 184 Always 735 2
Stage 2 Trip
135 161 185 185 185 Any Start Always 832 2
1st Stage Residual O/V
136 162 186 186 186 Always 864 2
Start
2nd Stage Residual O/V
137 163 187 187 187 Always 865 2
Start
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -147

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
1st Stage Phase U/V Start
138 164 188 188 188 Always 870 2
3ph
1st Stage Phase U/V Start
139 165 189 189 189 Always 871 2
A/AB
1st Stage Phase U/V Start
140 166 190 190 190 Always 872 2
B/BC
1st Stage Phase U/V Start
141 167 191 191 191 Always 873 2
C/CA
2nd Stage Phase U/V Start
142 168 192 192 192 Always 874 2
3ph
2nd Stage Phase U/V Start
143 169 193 193 193 Always 875 2
A/AB
2nd Stage Phase U/V Start
144 170 194 194 194 Always 876 2
B/BC
2nd Stage Phase U/V Start
145 171 195 195 195 Always 877 2
C/CA
1st Stage Phase O/V Start
146 172 196 196 196 Always 878 2
3ph
1st Stage Phase O/V Start
147 173 197 197 197 Always 879 2
A/AB
1st Stage Phase O/V Start
148 174 198 198 198 Always 880 2
B/BC
1st Stage Phase O/V Start
149 175 199 199 199 Always 881 2
C/CA
2nd Stage Phase O/V Start
150 176 200 200 200 Always 882 2
3ph
2nd Stage Phase O/V Start
151 177 201 201 201 Always 883 2
A/AB
2nd Stage Phase O/V Start
152 178 202 202 202 Always 884 2
B/BC
2nd Stage Phase O/V Start
153 179 203 203 203 Always 885 2
C/CA
154 180 204 204 204 Power Stage 1 Start Always 892 2
155 181 205 205 205 Power Stage 2 Start Always 893 2
156 182 206 206 206 1st Stage O/C Start 3ph Always 896 2
157 183 207 207 207 1st Stage O/C Start A Always 897 2
158 184 208 208 208 1st Stage O/C Start B Always 898 2
159 185 209 209 209 1st Stage O/C Start C Always 899 2
160 186 210 210 210 2nd Stage O/C Start 3ph Always 900 2
P34x/EN MD/J76 Relay Menu Database

(MD) -148 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
161 187 211 211 211 2nd Stage O/C Start A Always 901 2
162 188 212 212 212 2nd Stage O/C Start B Always 902 2
163 189 213 213 213 2nd Stage O/C Start C Always 903 2
164 3rd Stage O/C Start 3ph Always 904 2
165 3rd Stage O/C Start A Always 905 2
166 3rd Stage O/C Start B Always 906 2
167 3rd Stage O/C Start C Always 907 2
168 4th Stage O/C Start 3ph Always 908 2
169 4th Stage O/C Start A Always 909 2
170 4th Stage O/C Start B Always 910 2
171 4th Stage O/C Start C Always 911 2
172 190 214 214 214 1st Stage EF Start Always 855 2
173 191 215 215 215 2nd Stage EF Start Always 856 2
174 3rd Stage EF Start Always 857 2
175 4th Stage EF Start Always 858 2
176 192 216 216 216 1st Stage SEF Start Always 859 2
177 2nd Stage SEF Start Always 860 2
178 3rd Stage SEF Start Always 861 2
179 4th Stage SEF Start Always 862 2
100% Stator Earth Fault
217 217 217 Always 940 2
(3rd Harmonic) Start
Under Frequency Stage 1
180 193 218 218 218 Always 886 2
Start
Under Frequency Stage 2
181 194 219 219 219 Always 887 2
Start
Under Frequency Stage 3
182 195 220 220 220 Always 888 2
Start
Under Frequency Stage 4
183 196 221 221 221 Always 889 2
Start
Over Frequency Stage 1
184 197 222 222 222 Always 890 2
Start
Over Frequency Stage 2
185 198 223 223 223 Always 891 2
Start
186 I> Blocked O/C Start Always 838 2
IN/ISEF> Blocked O/C
187 Always 839 2
Start
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -149

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
Rate of Change of
188 Always 854 2
Frequency Start
199 224 224 224 Volts per Hz Start Always 850 2
200 225 225 225 Field Failure Stage 1 Start Always 848 2
201 226 226 226 Field Failure Stage 2 Start Always 849 2
Voltage Dependant Over
202 227 227 227 Always 928 2
Current Start 3Ph
Voltage Dependant Over
203 228 228 228 Always 929 2
Current Start A
Voltage Dependant Over
204 229 229 229 Always 930 2
Current Start B
Voltage Dependant Over
205 230 230 230 Always 931 2
Current Start C
Sensitive A Phase Power
189 206 231 231 231 Always 912 2
Stage 1 Start
Sensitive A Phase Power
190 207 232 232 232 Always 913 2
Stage 2 Start
Pole Slip (Impedance)
233 233 233 Always 914 2
Zone1 Start
Pole Slip (Impedance)
234 234 234 Always 915 2
Zone2 Start
Pole Slip (impedance)
235 235 235 Always 916 2
Lens Start
Pole Slip (impedance)
236 236 236 Always 917 2
Blinder Start
Pole Slip (impedance)
237 237 237 Never 918 2
Reactance Line Start
Under Impedance 3Phase
208 238 238 238 Always 932 2
Stage 1 Start
Under Impedance Phase A
209 239 239 239 Always 933 2
Stage 1 Start
Under Impedance Phase B
210 240 240 240 Always 934 2
Stage 1 Start
Under Impedance Phase C
211 241 241 241 Always 935 2
Stage 1 Start
Under Impedance 3Phase
212 242 242 242 Always 936 2
Stage 2 Start
Under Impedance Phase A
213 243 243 243 Always 937 2
Stage 2 Start
P34x/EN MD/J76 Relay Menu Database

(MD) -150 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
Under Impedance Phase B
214 244 244 244 Always 938 2
Stage 2 Start
Under Impedance Phase C
215 245 245 245 Always 939 2
Stage 2 Start
191 216 246 246 246 VTS Fast Block Always 1024 2
192 217 247 247 247 VTS Slow Block Always 1025 2
193 218 248 248 248 CTS-1 Block Always 1026 2
194 Control Trip Always 1027 2
195 Control Close Always 1028 2
196 Control Close in Progress Always 1029 2
Reconnection Time Delay
197 Always 1030 2
Output
CB Status
198 219 249 249 249 3 ph CB Open Always 1042 2
199 220 250 250 250 3 ph CB Closed Always 1043 2
200 221 251 251 251 IA< Operate Never 833 2
201 222 252 252 252 IB< Operate Never 834 2
202 223 253 253 253 IC< Operate Never 835 2
203 224 254 254 254 ISEF< Operate Never 836 2
225 255 255 255 IN< Operate Never 837 2
204 226 256 256 256 All Poles Dead Always 1044 2
205 227 257 257 257 Any Pole Dead Always 1045 2
206 228 258 258 258 Phase A Pole Dead Always 1046 2
207 229 259 259 259 Phase B Pole Dead Always 1047 2
208 230 260 260 260 Phase C Pole Dead Always 1048 2
New in Software Version
07
Alarm Signals
209 231 261 261 261 CLIO Input Board Failure Always 384 2
210 232 262 262 262 CLIO Output Board Failure Always 385 2
211 233 263 263 263 Current Loop Input 1 Alarm Always 386 2
212 234 264 264 264 Current Loop Input 2 Alarm Always 387 2
213 235 265 265 265 Current Loop Input 3 Alarm Always 388 2
214 236 266 266 266 Current Loop Input 4 Alarm Always 389 2
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -151

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
Current Loop Input 1
215 237 267 267 267 Always 390 2
Undercurrent Fail Alarm
Current Loop Input 2
216 238 268 268 268 Always 391 2
Undercurrent Fail Alarm
Current Loop Input 3
217 239 269 269 269 Always 392 2
Undercurrent Fail Alarm
Current Loop Input 4
218 240 270 270 270 Always 393 2
Undercurrent Fail Alarm
User Definable Alarm 16
219 241 271 271 271 Always 400 2
(Manual Reset)
User Definable Alarm 15
220 242 272 272 272 Always 401 2
(Manual Reset)
User Definable Alarm 14
221 243 273 273 273 Always 402 2
(Manual Reset)
User Definable Alarm 13
222 244 274 274 274 Always 403 2
(Manual Reset)
User Definable Alarm 12
223 245 275 275 275 Always 404 2
(Manual Reset)
User Definable Alarm 11
224 246 276 276 276 Always 405 2
(Manual Reset)
User Definable Alarm 10
225 247 277 277 277 Always 406 2
(Manual Reset)
User Definable Alarm 9
226 248 278 278 278 Always 407 2
(Manual Reset)
User Definable Alarm 8
227 249 279 279 279 Always 408 2
(Manual Reset)
User Definable Alarm 7
228 250 280 280 280 Always 409 2
(Manual Reset)
User Definable Alarm 6
229 251 281 281 281 Always 410 2
(Manual Reset)
User Definable Alarm 5
230 252 282 282 282 Always 411 2
(Manual Reset)
User Definable Alarm 4
231 253 283 283 283 Always 412 2
(Self Reset)
Trip Signals
232 254 284 284 284 Current Loop Input 1 Trip Always 739 2
233 255 285 285 285 Current Loop Input 2 Trip Always 740 2
234 256 286 286 286 Current Loop Input 3 Trip Always 741 2
235 257 287 287 287 Current Loop Input 4 Trip Always 742 2
P34x/EN MD/J76 Relay Menu Database

(MD) -152 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
Start Signals
Current Loop Input 1 Alarm
236 258 288 288 288 Always 840 2
Start
Current Loop Input 2 Alarm
237 259 289 289 289 Always 841 2
Start
Current Loop Input 3 Alarm
238 260 290 290 290 Always 842 2
Start
Current Loop Input 4 Alarm
239 261 291 291 291 Always 843 2
Start
Current Loop Input 1 Trip
240 262 292 292 292 Always 844 2
Start
Current Loop Input 2 Trip
241 263 293 293 293 Always 845 2
Start
Current Loop Input 3 Trip
242 264 294 294 294 Always 846 2
Start
Current Loop Input 4 Trip
243 265 295 295 295 Always 847 2
Start
New in Software Version
30
296 296 296 CTS-2 CT-2 Fail Alarm Always 381 2
297 297 297 CTS-2 Block Always 1074 2
244 266 298 298 298 Virtual Input 01 Always 1184 2
245 267 299 299 299 Virtual Input 02 Always 1185 2
246 268 300 300 300 Virtual Input 03 Always 1186 2
247 269 301 301 301 Virtual Input 04 Always 1187 2
248 270 302 302 302 Virtual Input 05 Always 1188 2
249 271 303 303 303 Virtual Input 06 Always 1189 2
250 272 304 304 304 Virtual Input 07 Always 1190 2
251 273 305 305 305 Virtual Input 08 Always 1191 2
252 274 306 306 306 Virtual Input 09 Always 1192 2
253 275 307 307 307 Virtual Input 10 Always 1193 2
254 276 308 308 308 Virtual Input 11 Always 1194 2
255 277 309 309 309 Virtual Input 12 Always 1195 2
256 278 310 310 310 Virtual Input 13 Always 1196 2
257 279 311 311 311 Virtual Input 14 Always 1197 2
258 280 312 312 312 Virtual Input 15 Always 1198 2
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -153

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
259 281 313 313 313 Virtual Input 16 Always 1199 2
260 282 314 314 314 Virtual Input 17 Always 1200 2
261 283 315 315 315 Virtual Input 18 Always 1201 2
262 284 316 316 316 Virtual Input 19 Always 1202 2
263 285 317 317 317 Virtual Input 20 Always 1203 2
264 286 318 318 318 Virtual Input 21 Always 1204 2
265 287 319 319 319 Virtual Input 22 Always 1205 2
266 288 320 320 320 Virtual Input 23 Always 1206 2
267 289 321 321 321 Virtual Input 24 Always 1207 2
268 290 322 322 322 Virtual Input 25 Always 1208 2
269 291 323 323 323 Virtual Input 26 Always 1209 2
270 292 324 324 324 Virtual Input 27 Always 1210 2
271 293 325 325 325 Virtual Input 28 Always 1211 2
272 294 326 326 326 Virtual Input 29 Always 1212 2
273 295 327 327 327 Virtual Input 30 Always 1213 2
274 296 328 328 328 Virtual Input 31 Always 1214 2
275 297 329 329 329 Virtual Input 32 Always 1215 2
276 298 330 330 330 Virtual Output 01 Always 1216 2
277 299 331 331 331 Virtual Output 02 Always 1217 2
278 300 332 332 332 Virtual Output 03 Always 1218 2
279 301 333 333 333 Virtual Output 04 Always 1219 2
280 302 334 334 334 Virtual Output 05 Always 1220 2
281 303 335 335 335 Virtual Output 06 Always 1221 2
282 304 336 336 336 Virtual Output 07 Always 1222 2
283 305 337 337 337 Virtual Output 08 Always 1223 2
284 306 338 338 338 Virtual Output 09 Always 1224 2
285 307 339 339 339 Virtual Output 10 Always 1225 2
286 308 340 340 340 Virtual Output 11 Always 1226 2
287 309 341 341 341 Virtual Output 12 Always 1227 2
288 310 342 342 342 Virtual Output 13 Always 1228 2
289 311 343 343 343 Virtual Output 14 Always 1229 2
290 312 344 344 344 Virtual Output 15 Always 1230 2
291 313 345 345 345 Virtual Output 16 Always 1231 2
P34x/EN MD/J76 Relay Menu Database

(MD) -154 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
292 314 346 346 346 Virtual Output 17 Always 1232 2
293 315 347 347 347 Virtual Output 18 Always 1233 2
294 316 348 348 348 Virtual Output 19 Always 1234 2
295 317 349 349 349 Virtual Output 20 Always 1235 2
296 318 350 350 350 Virtual Output 21 Always 1236 2
297 319 351 351 351 Virtual Output 22 Always 1237 2
298 320 352 352 352 Virtual Output 23 Always 1238 2
299 321 353 353 353 Virtual Output 24 Always 1239 2
300 322 354 354 354 Virtual Output 25 Always 1240 2
301 323 355 355 355 Virtual Output 26 Always 1241 2
302 324 356 356 356 Virtual Output 27 Always 1242 2
303 325 357 357 357 Virtual Output 28 Always 1243 2
304 326 358 358 358 Virtual Output 29 Always 1244 2
305 327 359 359 359 Virtual Output 30 Always 1245 2
306 328 360 360 360 Virtual Output 31 Always 1246 2
307 329 361 361 361 Virtual Output 32 Always 1247 2
New in Software Version
31
Trip Signals
330 362 362 362 3rd Stage O/C Trip 3ph Always 712 2
331 363 363 363 3rd Stage O/C Trip A Always 713 2
332 364 364 364 3rd Stage O/C Trip B Always 714 2
333 365 365 365 3rd Stage O/C Trip C Always 715 2
334 366 366 366 4th Stage O/C Trip 3ph Always 716 2
335 367 367 367 4th Stage O/C Trip A Always 717 2
336 368 368 368 4th Stage O/C Trip B Always 718 2
337 369 369 369 4th Stage O/C Trip C Always 719 2
308 338 370 370 370 Residual O/V Stage 3 Trip Always 674 2
309 339 371 371 371 Residual O/V Stage 4 Trip Always 675 2
372 372 Residual O/V Stage 5 Trip Always 676 2
373 373 Residual O/V Stage 6 Trip Always 677 2
NPS Overpower Stage 1
340 372 374 374 Always 743 2
trip
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -155

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
Turbine Abnormal
341 373 375 375 Always 744 2
Frequency Band 1 Trip
Turbine Abnormal
342 374 376 376 Always 745 2
Frequency Band 2 Trip
Turbine Abnormal
343 375 377 377 Always 746 2
Frequency Band 3 Trip
Turbine Abnormal
344 376 378 378 Always 747 2
Frequency Band 4 Trip
Turbine Abnormal
345 377 379 379 Always 748 2
Frequency Band 5 Trip
Turbine Abnormal
346 378 380 380 Always 749 2
Frequency Band 6 Trip
NPS Overcurrent Stage 1
310 347 379 381 381 Always 750 2
Trip
NPS Overcurrent Stage 2
311 348 380 382 382 Always 751 2
Trip
NPS Overcurrent Stage 3
312 349 381 383 383 Always 752 2
Trip
NPS Overcurrent Stage 4
313 350 382 384 384 Always 753 2
Trip
NPS Overvoltage Stage 1
314 351 383 385 385 Always 754 2
Trip
352 384 386 386 Volts per Hz Stage 2 Trip Always 647 2
353 385 387 387 Volts per Hz Stage 3 Trip Always 648 2
354 386 388 388 Volts per Hz Stage 4 Trip Always 649 2
Start Signals
355 387 389 389 3rd Stage O/C Start 3ph Always 904 2
356 388 390 390 3rd Stage O/C Start A Always 905 2
357 389 391 391 3rd Stage O/C Start B Always 906 2
358 390 392 392 3rd Stage O/C Start C Always 907 2
359 391 393 393 4th Stage O/C Start 3ph Always 908 2
360 392 394 394 4th Stage O/C Start A Always 909 2
361 393 395 395 4th Stage O/C Start B Always 910 2
362 394 396 396 4th Stage O/C Start C Always 911 2
315 363 395 397 397 Residual O/V Stage 3 Start Always 866 2
316 364 396 398 398 Residual O/V Stage 4 Start Always 867 2
399 399 Residual O/V Stage 5 Start Always 868 2
P34x/EN MD/J76 Relay Menu Database

(MD) -156 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
400 400 Residual O/V Stage 6 Start Always 869 2
NPS Overpower Stage 1
365 397 401 401 Always 941 2
Start
Turbine Abnormal
366 398 402 402 Always 919 2
Frequency Band 1 Start
Turbine Abnormal
367 399 403 403 Always 920 2
Frequency Band 2 Start
Turbine Abnormal
368 400 404 404 Always 921 2
Frequency Band 3 Start
Turbine Abnormal
369 401 405 405 Always 922 2
Frequency Band 4 Start
Turbine Abnormal
370 402 406 406 Always 923 2
Frequency Band 5 Start
Turbine Abnormal
371 403 407 407 Always 924 2
Frequency Band 6 Start
NPS Overcurrent Stage 1
317 372 404 408 408 Always 942 2
Start
NPS Overcurrent Stage 2
318 373 405 409 409 Always 943 2
Start
NPS Overcurrent Stage 3
319 374 406 410 410 Always 944 2
Start
NPS Overcurrent Stage 4
320 375 407 411 411 Always 945 2
Start
NPS Overvoltage Stage 1
321 376 408 412 412 Always 946 2
Start
377 409 413 413 Volts per Hz Stage 2 Start Always 851 2
378 410 414 414 Volts per Hz Stage 3 Start Always 852 2
379 411 415 415 Volts per Hz Stage 4 Start Always 853 2
New in Software Version
32
Setting Group Selector x1
322 380 412 416 416 7 Always 624 2
(bit 0)
Setting Group Selector 1x
323 381 413 417 417 7 Always 625 2
(bit 1)
418 Function Key 1 Always 256 2
419 Function Key 2 Always 257 2

7 Prior to Software version 32 this setting group selection functionality was a configuration option
associated with opto-inputs 1 & 2.
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -157

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
420 Function Key 3 Always 258 2
421 Function Key 4 Always 259 2
422 Function Key 5 Always 260 2
423 Function Key 6 Always 261 2
424 Function Key 7 Always 262 2
425 Function Key 8 Always 263 2
426 Function Key 9 Always 264 2
427 Function Key 10 Always 265 2
64S 100% St EF Under
428 Resistance Stage 1 Alm Always 950 2
Start
64S 100% St EF Under
429 Always 382 2
Resistance Stage 1 Alarm
64S 100% St EF Under
430 Resistance Stage 2 Trip Always 951 2
Start
64S 100% St EF Under
431 Always 757 2
Resistance Stage 2 Trip
64S 100% Stator Earth
432 Always 949 2
Fault Over Current Start
64S 100% Stator Earth
433 Always 756 2
Fault Over Current Trip
64S 100% Stator Earth
434 Always 947 2
Fault Under Current Start
64S 100% Stator Earth
435 Always 948 2
Fault Under Voltage Start
436 64S Injection Fail Alarm Always 383 2
64S 100% Stator Earth
437 Fault - System frequency Always 1075 2
in blocking band
New in software version 33

64R Rotor Under


382 414 418 438 Resistance Stage 1 Alarm Always 952 2
Start
64R Rotor Under
383 415 419 439 Always 394 2
Resistance Stage 1 Alarm
64R Rotor Under
384 416 420 440 Resistance Stage 2 Trip Always 953 2
Start
P34x/EN MD/J76 Relay Menu Database

(MD) -158 MiCOM P342, P343, P344, P345 & P391

Binary Input Points


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: Configurable:
1 Single bit binary input
2 Binary Input with status (Default)
Change Event Variation reported when variation 0 requested: Configurable:
1 Binary input change without time
2 Binary input change with time (Default)
Default
P341 P342 P343 P344 P345 Change
Online DDB
Point Point Point Point Point Name/Description O Event Class
if 5 N
Index Index Index Index Index (1, 2, 3, or
none)
64R Rotor Under
385 417 421 441 Always 758 2
Resistance Stage 2 Trip
64R Rotor CLIO Input Fail
386 418 422 442 Always 395 2
Alarm

6.1.1 Time Stamping


The real time clock within the relay provides the time tag for each binary change event, to a
resolution of 1ms.

6.2 Binary output status points and control relay output block
The following table lists both the Binary Output Status Points (Object 10) and the Control
Relay Output Block (Object 12).
Binary Output Status points are included in Class 0 data set. (Since there is not a change-
event object for the binary outputs, the binary output points are not part of the class 1, 2, or 3
data sets). It is not possible to configure the class 0 membership of this object with MiCOM
S1 Studio.
The validity of each point is reported through the online bit in the flag, which is supplied
for each point with the with flag object variations. Points reported as being offline, will
typically be points that are invalid for the relays current configuration, which is a product of
its model number and current settings.
The Control Relay Output Block (CROB) implementation is compliant with the DNP technical
bulletin TB2000-006, which rescinds CROB behaviors specified in the original four document
set and addendum sub-set documents.
The following text is a brief summary of DNP technical bulletin TB2000-006:
Each control point in the CROB may be either a "complimentary control function" or a "single
function".
Examples of complimentary control functions are:

Trip and close

On and Off
Examples of single-function controls are:

Trip

Activate
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -159

A point index cannot support both complimentary and single-function methods of operation.
Complimentary control function points require the use of a complementary control-code pair.
The CROB provides two sets of control pairs:

Code 0316 "Latch On" and code 0416 "Latch Off"

Code 4116 "Pulse On/Close" and code 8116 "Pulse On/Trip"


In DNP there is no significance to these codes; they do the same thing. A
complimentary-control point may "permit" either or both of these pairs. If a point permits
both pairs of codes then:

Latch On and Pulse Close must perform the same function

Latch Off and Pulse Trip must perform the same function
Single-function control points may permit one or more of the following control codes:

Code 0116 "Pulse On"

Code 0316 "Latch On"

Code 0416 "Latch Off"

Code 4116 "Pulse On/Close

Code 8116 "Pulse On/Trip"


There is no significance to these codes; they do the same thing. Each of the permitted
single-function codes must perform the same function on a given single-function point index.
The original DNP3.0 specification for the CROB "exposes the details of the device hardware
to the protocol stack. This is unnecessary and creates interoperability issues". Moreover,
"some IED vendors have implemented points that do different things based on the control
code that is sent. " E.g. a point latches for the latch codes and pulses for the pulse codes.
"This perverts the original intent of the CROB and makes it impossible for masters that
statically configure control codes to be interoperable with such [IEDs]. This type of
implementation is also not transportable across legacy protocol boundaries."
In the following table, point indices that are marked as unpaired will accept the
correspondingly marked control codes and treat them identically as a trigger for the
command action associated with the point. Unpaired points do not have a state value that
can be read and a read request, whilst completing successfully, will always return a value of
zero.
Points that are marked as paired behave as complimentary-controls and have a state value
that can be read. The Latch On and Pulse On/Close control-codes set the specified output
status point whilst the Latch Off and Pulse On/Trip codes reset it.
The Count field is not supported and must be either zero or one. The On-time, and Off-time
fields are ignored. The Queue and Clear bits in the Control-Code field are not supported and
must be zero. The Pulse Off control-code code is not supported.
The Alias Control Inputs operation, added in v33 software, are described in 7 APPENDIX
A.
P34x/EN MD/J76 Relay Menu Database

(MD) -160 MiCOM P342, P343, P344, P345 & P391

Binary Output Status Points


Object Number: 10
Request Function Code supported: 1 (read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks (CROB)
Object Number: 12
Request Function Code supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
Supported CROB
Fields

Pulse On/Close
P341 P342 P343 P344 P344

Pulse On/Trip
Online
Point Point Point Point Point Name/Description

Latch Off
Unpaired
Latch On

Pulse On
if

Paired
Index Index Index Index Index

Setting Group Control


Group 1
0 0 0 0 0 Activate Setting Group 1 Enabled
* * * * *

Group 2
1 1 1 1 1 Activate Setting Group 2 Enabled
* * * * *

Group 3
2 2 2 2 2 Activate Setting Group 3 Enabled
* * * * *

Group 4
3 3 3 3 3 Activate Setting Group 4 Enabled
* * * * *

Control Commands
Remote
CB
4 Initiate CB Trip Control
* * * * * *
Enabled
Remote
CB
5 Initiate CB Close Control
* * * * * *
Enabled

6 4 4 4 4 Reset Indication Always * * * * *


7 5 5 5 5 Reset Demand Always * * * * *
Reset Negative Phase
Function
6 6 6 6 Sequence Thermal Enabled
* * * * *
Replica
Reset Thermal Overload Function
8 7 7 7 7 Enabled
* * * * *
Replica
9 8 8 8 8 Clear Event Records Always * * * * *
10 9 9 9 9 Clear Fault Records Always * * * * *
Clear Maintenance
11 10 10 10 10 Always * * * * *
Records
12 11 11 11 11 Test LEDs Always * * * * *
13 12 12 12 12 Reset Lockout Always * * * * *
14 13 13 13 13 Reset CB Data Always * * * * *
14 14 14 14 Reset RTD Flags Always * * * * *
Scheme Logic Control
Input Signals
15 15 15 15 15 Control Input 1 Always * * * * *
16 16 16 16 16 Control Input 2 Always * * * * *
17 17 17 17 17 Control Input 3 Always * * * * *
18 18 18 18 18 Control Input 4 Always * * * * *
19 19 19 19 19 Control Input 5 Always * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -161

Binary Output Status Points


Object Number: 10
Request Function Code supported: 1 (read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks (CROB)
Object Number: 12
Request Function Code supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
Supported CROB
Fields

Pulse On/Close
P341 P342 P343 P344 P344

Pulse On/Trip
Online
Point Point Point Point Point Name/Description

Latch Off
Unpaired
Latch On

Pulse On
if

Paired
Index Index Index Index Index

20 20 20 20 20 Control Input 6 Always * * * * *

21 21 21 21 21 Control Input 7 Always * * * * *


22 22 22 22 22 Control Input 8 Always * * * * *
23 23 23 23 23 Control Input 9 Always * * * * *
24 24 24 24 24 Control Input 10 Always * * * * *
25 25 25 25 25 Control Input 11 Always * * * * *
26 26 26 26 26 Control Input 12 Always * * * * *
27 27 27 27 27 Control Input 13 Always * * * * *
28 28 28 28 28 Control Input 14 Always * * * * *
29 29 29 29 29 Control Input 15 Always * * * * *
30 30 30 30 30 Control Input 16 Always * * * * *
31 31 31 31 31 Control Input 17 Always * * * * *
32 32 32 32 32 Control Input 18 Always * * * * *
33 33 33 33 33 Control Input 19 Always * * * * *
34 34 34 34 34 Control Input 20 Always * * * * *
35 35 35 35 35 Control Input 21 Always * * * * *
36 36 36 36 36 Control Input 22 Always * * * * *
37 37 37 37 37 Control Input 23 Always * * * * *
38 38 38 38 38 Control Input 24 Always * * * * *
39 39 39 39 39 Control Input 25 Always * * * * *
40 40 40 40 40 Control Input 26 Always * * * * *
41 41 41 41 41 Control Input 27 Always * * * * *
42 42 42 42 42 Control Input 28 Always * * * * *
43 43 43 43 43 Control Input 29 Always * * * * *
44 44 44 44 20 Control Input 30 Always * * * * *
45 45 45 45 45 Control Input 31 Always * * * * *
46 46 46 46 46 Control Input 32 Always * * * * *
New in Software
Version 30
Clear all disturbance
47 47 47 47 47 Always * * * * *
records
P34x/EN MD/J76 Relay Menu Database

(MD) -162 MiCOM P342, P343, P344, P345 & P391

Binary Output Status Points


Object Number: 10
Request Function Code supported: 1 (read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks (CROB)
Object Number: 12
Request Function Code supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
Supported CROB
Fields

Pulse On/Close
P341 P342 P343 P344 P344

Pulse On/Trip
Online
Point Point Point Point Point Name/Description

Latch Off
Unpaired
Latch On

Pulse On
if

Paired
Index Index Index Index Index

New in Software
Version 31
Reset Turbine Freq
48 48 48 48 Always * * * * *
Band 1
Reset Turbine Freq
49 49 49 49 Always * * * * *
Band 2
50 50 50 50 Reset Turbine Freq Always * * * * *
Band 3
51 51 51 51 Reset Turbine Freq Always * * * * *
Band 4
Reset Turbine Freq
52 52 52 52 Always * * * * *
Band 5
Reset Turbine Freq
53 53 53 53 Always * * * * *
Band 6
New in software version
33
48 54 54 54 54 Alias Control Input 1 Always * * * * *
49 55 55 55 55 Alias Control Input 2 Always * * * * *
50 56 56 56 56 Alias Control Input 3 Always * * * * *
51 57 57 57 57 Alias Control Input 4 Always * * * * *
52 58 58 58 58 Alias Control Input 5 Always * * * * *
53 59 59 59 59 Alias Control Input 6 Always * * * * *
54 60 60 60 60 Alias Control Input 7 Always * * * * *
55 61 61 61 61 Alias Control Input 8 Always * * * * *
56 62 62 62 62 Alias Control Input 9 Always * * * * *
57 63 63 63 63 Alias Control Input 10 Always * * * * *
58 64 64 64 64 Alias Control Input 11 Always * * * * *
59 65 65 65 65 Alias Control Input 12 Always * * * * *
60 66 66 66 66 Alias Control Input 13 Always * * * * *
61 67 67 67 67 Alias Control Input 14 Always * * * * *
62 68 68 68 68 Alias Control Input 15 Always * * * * *
63 69 69 69 69 Alias Control Input 16 Always * * * * *
64 70 70 70 70 Alias Control Input 17 Always * * * * *
65 71 71 71 71 Alias Control Input 18 Always * * * * *
66 72 72 72 72 Alias Control Input 19 Always * * * * *
67 73 73 73 73 Alias Control Input 20 Always * * * * *
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -163

Binary Output Status Points


Object Number: 10
Request Function Code supported: 1 (read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks (CROB)
Object Number: 12
Request Function Code supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
Supported CROB
Fields

Pulse On/Close
P341 P342 P343 P344 P344

Pulse On/Trip
Online
Point Point Point Point Point Name/Description

Latch Off
Unpaired
Latch On

Pulse On
if

Paired
Index Index Index Index Index

68 74 74 74 74 Alias Control Input 21 Always * * * * *


69 75 75 75 75 Alias Control Input 22 Always * * * * *
70 76 76 76 76 Alias Control Input 23 Always * * * * *
71 77 77 77 77 Alias Control Input 24 Always * * * * *
72 78 78 78 78 Alias Control Input 25 Always * * * * *
73 79 79 79 79 Alias Control Input 26 Always * * * * *
74 80 80 80 80 Alias Control Input 27 Always * * * * *
75 81 81 81 81 Alias Control Input 28 Always * * * * *
76 82 82 82 82 Alias Control Input 29 Always * * * * *
77 83 83 83 83 Alias Control Input 30 Always * * * * *
78 84 84 84 84 Alias Control Input 31 Always * * * * *
79 85 85 85 85 Alias Control Input 32 Always * * * * *

6.3 Counters
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21).
When a freeze function is performed on a Binary Counter point, the frozen value is available
in the corresponding Frozen Counter point.
Frozen counter points (object 21) correspond to the same point index as the counters (object
20). Counter events objects (object 22) only report the most recent change, so the
maximum number of events supported is the same as the total number of counters. Frozen
counter points (object 23) are generated when ever a freeze operation is performed. The
frozen counter event queues will store the points for up to two freeze operations.
The Binary Counters (object 20) and Frozen Counters (object 21) are included in class 0
polls.
The validity of each point is reported through the online bit in the flag, which is supplied
for each point with the with flag object variations. Points reported as being offline, will
typically be points that are invalid for the relays current configuration, which is a product of
its model number and current settings.
P34x/EN MD/J76 Relay Menu Database

(MD) -164 MiCOM P342, P343, P344, P345 & P391

Binary Counters
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Static Variation reported when variation 0 requested: Configurable:
1 32-bit Binary Counter
2 16-bit Binary Counter
5 32-bit Binary Counter without flag (Default)
6 16-bit Binary Counter without flag
Change Event Variation reported when variation 0 requested: Configurable:
1 32-bit Binary Counter without time (Default)
2 16-bit Binary Counter without time
5 32-bit Binary Counter with time
6 16-bit Binary Counter with time
Frozen Counters
Static (Steady-State) Object Number: 21
Change Event Object Number: 23
Static Variation reported when variation 0 requested: Configurable:
1 32-bit Frozen Binary Counter
2 16-bit Frozen Binary Counter
5 32-bit Frozen Binary Counter with time
6 16-bit Frozen Binary Counter with time
9 32-bit Frozen Binary Counter without flag (Default)
10 16-bit Frozen Binary Counter without flag
Change Event Variation reported when variation 0 requested: Configurable:
1 32-bit Frozen Binary Counter without time (Default)
2 16-bit Frozen Binary Counter without time
5 32-bit Frozen Binary Counter with time
6 16-bit Frozen Binary Counter with time
P341 P342 P343 P344 P345
Point Point Point Point Point Name/Description Online if Data Type
Index Index Index Index Index
0 0 0 0 0 3Ph WHours Forward Always D10
1 1 1 1 1 3Ph WHours Reverse Always D10
2 2 2 2 2 3Ph VArHours Forward Always D10
3 3 3 3 3 3Ph VArHours Reverse Always D10
4 4 4 4 4 CB Operations Always -
New in Software Version 31
5 5 5 5 Freq Band 1 Time (s) Always -
6 6 6 6 Freq Band 2 Time (s) Always -
7 7 7 7 Freq Band 3 Time (s) Always -
8 8 8 8 Freq Band 4 Time (s) Always -
9 9 9 9 Freq Band 5 Time (s) Always -
10 10 10 10 Freq Band 6 Time (s) Always -

See section 6.4 for the definition of the data type. Points shown without a data type
designation are 32-bit unsigned integers.
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) -165

6.4 Analog inputs


The following table lists the Analog Inputs (Object 30).
Analogue input events report only the most recent change, so the maximum number of
analogue events is equal to the number of points.
The Default Deadband, and the Default Change Event Assigned Class columns are used
to represent the absolute amount by which the point must change before an analog change
event will be generated, and once generated in which class poll (1, 2, 3, or none) the change
event will be reported. The deadband columns shows values in terms of
(Primary/Secondary/Normalised scaling To be selected based on application default).
The integer scaling group column shows the index into the Integer scaling factor table that
applies to the analogue input. The integer scaling factor is the value that will be used to
convert a floating-point value into a scaled integer representation when 16-bit or 32-bit
variations are requested.
The measurement scaling setting in the communications column allows analogue values to
be scaled in terms of Primary, Secondary and Normalised (110V/1A) terms. This avoids the
need to provide scaling in the master station and also avoids the need for specific knowledge
of the connected transformer ratios. Note that the integer scaling factors are not
automatically adjusted to match the measurement scaling, so master stations that use
integer variations may need to adjust the values to avoid overflow in returned analogue
inputs.
The validity of each point is reported through the online bit in the flag, which is supplied
for each point with the with flag object variations. Points reported as being offline, will
typically be points that are invalid for the relays current configuration, which is a product of
its model number and current settings.

Analog Inputs
Static (Steady State) Object Number: 30
Change Event Object Number: 32
Deadband Object: 34
Static Variation reported when variation 0 requested: Configurable
1 32-bit Analogue Input
2 16-bit Analogue Input
3 32-bit Analogue Input without flag (Default)
4 16-bit Analogue Input without flag
5 Short floating-point Analogue Input
Change Event Variation reported when variation 0 requested: Configurable
1 32-bit Analogue change event without time (Default)
2 16-bit Analogue change event without time
3 32-bit Analogue change event with time
4 16-bit Analogue change event with time
5 Short floating-point analogue change event
7 Short floating-point analogue change event with time
Deadband Variation reported when variation 0 requested: Configurable
1 16-bit Analogue Input Reporting Deadband object
2 32-bit Analogue Input Reporting Deadband object (Default)
3 Short floating-point Analogue Input Reporting Deadband object
(AD) - 166

P341/EN AD/E53
Default
P341 Point

P342 Point

P343 Point

P344 Point

P345 Point
Change
Index

Index

Index

Index

Index
Name/ Online Data Type Valid Range Deadband Scaling Factor Event Class
Description if
Index (1, 2, 3 or
none)

Active Group
0 0 0 0 0 Active Group Always D9 14 1 Null 3

Measurements 1
1 1 IA Magnitude Always D1 0.00065.534 0.1 Phase Currents 3
2 2 IA Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
3 3 IB Magnitude Always D1 0.00065.534 0.1 Phase Currents 3
4 4 IB Phase Angle Always D4 -180.00+180.00 1 Phase Angles 3
5 5 IC Magnitude Always D1 0.00065.534 0.1 Phase Current 3
6 6 IC Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
1 1 1 IA-1 Magnitude Always D1 0.00065.534 0.1 Phase Current 3
2 2 2 IA-1 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
3 3 3 IB-1 Magnitude Always D1 0.00065.534 0.1 Phase Current 3
4 4 4 IB-1 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
5 5 5 IC-1 Magnitude Always D1 0.00065.534 0.1 Phase Current 3
6 6 6 IC-1 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
7 7 7 7 IN Measured Magnitude Always D1 0.00065.534 0.1 Phase Current 3
8 8 8 8 IN Measured Angle Always D4 -180.00+180.00 1 Phase Angle 3
7 IN Derived Magnitude Always D1 0.00065.534 0.1 Phase Current 3

Update Documentation
8 IN Derived Angle Always D4 -180.00+180.00 1 Phase Angle 3
9 9 9 9 9 I Sen Magnitude Always D2 0.00002.0000 0.01 Sensitive Current 3

MiCOM P341
10 10 10 10 10 I Sen Angle Always D4 -180.00+180.00 1 Phase Angle 3
11 11 11 11 11 I1 Magnitude Always D1 0.00065.534 0.1 Phase Current 3
12 12 12 12 12 I2 Magnitude Always D1 0.00065.534 0.1 Phase Current 3
13 13 13 13 13 I0 Magnitude Always D1 0.00065.534 0.1 Phase Current 3
14 14 14 14 14 IA RMS Always D1 0.00065.534 0.1 Phase Current 3
MiCOM P342, P343, P344, P345 & P391

Relay Menu Database


Default
P341 Point

P342 Point

P343 Point

P344 Point

P345 Point
Change
Index

Index

Index

Index

Index
Name/ Online Data Type Valid Range Deadband Scaling Factor Event Class
Description if
Index (1, 2, 3 or
none)

15 15 15 15 15 IB RMS Always D1 0.00065.534 0.1 Phase Current 3


16 16 16 16 16 IC RMS Always D1 0.00065.534 0.1 Phase Current 3
17 17 17 17 17 VAB Magnitude Always D3 0.00220.00 5 Phase Voltage 3
18 18 18 18 18 VAB Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
19 19 19 19 19 VBC Magnitude Always D3 0.00220.00 5 Phase Voltage 3
20 20 20 20 20 VBC Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
21 21 21 21 21 VCA Magnitude Always D3 0.00220.00 5 Phase Voltage 3
22 22 22 22 22 VCA Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
23 23 23 23 23 VAN Magnitude Always D3 0.00220.00 5 Phase Voltage 3
24 24 24 24 24 VAN Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
25 25 25 25 25 VBN Magnitude Always D3 0.00220.00 5 Phase Voltage 3
26 26 26 26 26 VBN Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
27 27 27 27 27 VCN Magnitude Always D3 0.00220.00 5 Phase Voltage 3
28 28 28 28 28 VCN Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
29 29 29 29 29 VN Measured Magnitude Always D3 0.00220.00 5 Phase Voltage 3
30 30 30 30 30 VN Measured Angle Always D4 -180.00+180.00 1 Phase Angle 3
31 31 31 31 31 VN Derived Magnitude Always D3 0.00220.00 5 Phase Voltage 3
32 32 32 32 32 VN Derived Angle Always D4 -180.00+180.00 1 Phase Angle 3
33 33 33 33 33 V1 Magnitude Always D3 0.00220.00 5 Phase Voltage 3
34 34 34 34 34 V2 Magnitude Always D3 0.00220.00 5 Phase Voltage 3

P34x/EN MD/J76
35 35 35 35 35 V0 Magnitude Always D3 0.00220.00 5 Phase Voltage 3
36 36 36 36 36 VAN RMS Always D3 0.00220.00 5 Phase Voltage 3

(MD) - 167
37 37 37 37 37 VBN RMS Always D3 0.00220.00 5 Phase Voltage 3
38 38 38 38 38 VCN RMS Always D3 0.00220.00 5 Phase Voltage 3
(MD) - 168

P34x/EN MD/J76
Default
P341 Point

P342 Point

P343 Point

P344 Point

P345 Point
Change
Index

Index

Index

Index

Index
Name/ Online Data Type Valid Range Deadband Scaling Factor Event Class
Description if
Index (1, 2, 3 or
none)

Measuret
Valid
39 39 39 39 39 Frequency (Device is D5 5.0070.00 0.5 Frequency 3
Frequency
Tracking)

Measurements 2
40 40 40 40 40 A Phase Watts Always D6 -3150.0+3150.0 1 Power 3
41 41 41 41 41 B Phase Watts Always D6 -3150.0+3150.0 1 Power 3
42 42 42 42 42 C Phase Watts Always D6 -3150.0+3150.0 1 Power 3
43 43 43 43 43 A Phase VArs Always D6 -3150.0+3150.0 1 Power 3
44 44 44 44 44 B Phase VArs Always D6 -3150.0+3150.0 1 Power 3
45 45 45 45 45 C Phase VArs Always D6 -3150.0+3150.0 1 Power 3
46 46 46 46 46 A Phase VA Always D6 -3150.0+3150.0 1 Power 3
47 47 47 47 47 B Phase VA Always D6 -3150.0+3150.0 1 Power 3
48 48 48 48 48 C Phase VA Always D6 -3150.0+3150.0 1 Power 3

MiCOM P342, P343, P344, P345 & P391


49 49 49 49 49 3 Phase Watts Always D6 -3150.0+3150.0 1 Power 3
50 50 50 50 50 3 Phase VArs Always D6 -3150.0+3150.0 1 Power 3
51 51 51 51 51 3 Phase VA Always D6 -3150.0+3150.0 1 Power 3
52 52 52 52 52 3Ph Power Factor Always D8 0.0001.000 0.1 Power Factor 3
53 53 53 53 53 APh Power Factor Always D8 0.0001.000 0.1 Power Factor 3

Relay Menu Database


54 54 54 54 54 BPh Power Factor Always D8 0.0001.000 0.1 Power Factor 3
55 55 55 55 55 CPh Power Factor Always D8 0.0001.000 0.1 Power Factor 3
56 56 56 56 56 3Ph W Fix Demand Always D6 -3150.0+3150.0 1 Power 3
57 57 57 57 57 3Ph VArs Fix Dem Always D6 -3150.0+3150.0 1 Power 3
58 58 58 58 58 IA Fixed Demand Always D1 0.00065.534 0.1 Phase Current 3
59 59 59 59 59 IB Fixed Demand Always D1 0.00065.534 0.1 Phase Current 3
MiCOM P342, P343, P344, P345 & P391

Relay Menu Database


Default
P341 Point

P342 Point

P343 Point

P344 Point

P345 Point
Change
Index

Index

Index

Index

Index
Name/ Online Data Type Valid Range Deadband Scaling Factor Event Class
Description if
Index (1, 2, 3 or
none)

60 60 60 60 60 IC Fixed Demand Always D1 0.00065.534 0.1 Phase Current 3


61 61 61 61 61 3 Ph W Roll Dem Always D6 -3150.0+3150.0 1 Power 3
62 62 62 62 62 3Ph VArs RollDem Always D6 -3150.0+3150.0 1 Power 3
63 63 63 63 63 IA Roll Demand Always D1 0.00065.534 0.1 Phase Current 3
64 64 64 64 64 IB Roll Demand Always D1 0.00065.534 0.1 Phase Current 3
65 65 65 65 65 IC Roll Demand Always D1 0.00065.534 0.1 Phase Current 3
66 66 66 66 66 3Ph W Peak Dem Always D6 -3150.0+3150.0 1 Power 3
67 67 67 67 67 3Ph VAr Peak Dem Always D6 -3150.0+3150.0 1 Power 3
68 68 68 68 68 IA Peak Demand Always D1 0.00065.534 0.1 Phase Current 3
69 69 69 69 69 IB Peak Demand Always D1 0.00065.534 0.1 Phase Current 3
70 70 70 70 70 IC Peak Demand Always D1 0.00065.534 0.1 Phase Current 3

Measurements 3
71 71 71 IA-2 Magnitude Always D1 0.00065.534 0.1 Phase Current 3
72 72 72 IA-2 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
73 73 73 IB-2 Magnitude Always D1 0.00065.534 0.1 Phase Current 3
74 74 74 IB-2 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
75 75 75 IC-2 Magnitude Always D1 0.00065.534 0.1 Phase Current 3
76 76 76 IC-2 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
Differential
77 77 77 IA Differential Protection D1 0.00065.534 0.1 Phase Current 3
Enabled

P34x/EN MD/J76
Differential
78 78 78 IB Differential Protection D1 0.00065.534 0.1 Phase Current 3
Enabled

(MD) - 169
Differential
79 79 79 IC Differential Protection D1 0.00065.534 0.1 Phase Current 3
Enabled
(MD) - 170

P34x/EN MD/J76
Default
P341 Point

P342 Point

P343 Point

P344 Point

P345 Point
Change
Index

Index

Index

Index

Index
Name/ Online Data Type Valid Range Deadband Scaling Factor Event Class
Description if
Index (1, 2, 3 or
none)

Differential
80 80 80 IA Bias Protection D1 0.00065.534 0.1 Phase Current 3
Enabled
Differential
81 81 81 IB Bias Protection D1 0.00065.534 0.1 Phase Current 3
Enabled
Differential
82 82 82 IC Bias Protection D1 0.00065.534 0.1 Phase Current 3
Enabled
REF
71 83 83 83 IREF Differential D2 0.00002.0000 0.01 Sensitive Current 3
Enabled
REF
72 84 84 84 IREF Bias D2 0.00002.0000 0.01 Sensitive Current 3
Enabled
85 85 85 VN 3rd Harmonic Always D3 0.00220.00 5 Phase Voltage 3
NPS
73 86 86 86 NPS Thermal Thermal D7 0.00327.67 10 Percentage 3
Enabled
RTD1
74 87 87 87 RTD 1 D14 -40.0300.0 1 Temperature 3

MiCOM P342, P343, P344, P345 & P391


Enabled
RTD 2
75 88 88 88 RTD 2 D14 -40.0300.0 1 Temperature 3
Enabled
RTD 3
76 89 89 89 RTD 3 D14 -40.0300.0 1 Temperature 3
Enabled
RTD 4
77 90 90 90 RTD 4 D14 -40.0300.0 1 Temperature 3

Relay Menu Database


Enabled
RTD 5
78 91 91 91 RTD 5 D14 -40.0300.0 1 Temperature 3
Enabled
RTD 6
79 92 92 92 RTD 6 D14 -40.0300.0 1 Temperature 3
Enabled
RTD 7
80 93 93 93 RTD 7 D14 -40.0300.0 1 Temperature 3
Enabled
MiCOM P342, P343, P344, P345 & P391

Relay Menu Database


Default
P341 Point

P342 Point

P343 Point

P344 Point

P345 Point
Change
Index

Index

Index

Index

Index
Name/ Online Data Type Valid Range Deadband Scaling Factor Event Class
Description if
Index (1, 2, 3 or
none)

RTD 8
81 94 94 94 RTD 8 D14 -40.0300.0 1 Temperature 3
Enabled
RTD 9
82 95 95 95 RTD 9 D14 -40.0300.0 1 Temperature 3
Enabled
RTD 10
83 96 96 96 RTD 10 D14 -40.0300.0 1 Temperature 3
Enabled
Sensitive
71 84 97 97 97 APh Sensitive Watts Power D6 -3150.0+3150.0 1 Power 3
Enabled
Sensitive
72 85 98 98 98 APh Sensitive Vars Power D6 -3150.0+3150.0 1 Power 3
Enabled
Sensitive
73 86 99 99 99 APh Power Angle Power D4 -180.00+180.00 1 Phase Angle 3
Enabled
Thermal
74 87 100 100 100 Thermal Overload Overload D7 0.00327.67 10 Percentage 3
Enabled

New in Software Version 06


75 88 101 101 101 I1 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
76 89 102 102 102 I2 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
77 90 103 103 103 I0 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
78 91 104 104 104 V1 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
79 92 105 105 105 V2 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3
80 93 106 106 106 V0 Phase Angle Always D4 -180.00+180.00 1 Phase Angle 3

P34x/EN MD/J76
(MD) - 171
(MD) - 172

P34x/EN MD/J76
Default
P341 Point

P342 Point

P343 Point

P344 Point

P345 Point
Change
Index

Index

Index

Index

Index
Name/ Online Data Type Valid Range Deadband Scaling Factor Event Class
Description if
Index (1, 2, 3 or
none)

New in Software Version 07


CLIO Input
81 94 107 107 107 CLIO Input 1 D16 -9999.9+9999.9 10 CLIO 3
1 Enabled
CLIO Input
82 95 108 108 108 CLIO Input 2 D16 -9999.9+9999.9 10 CLIO 3
2 Enabled
CLIO Input
83 96 109 109 109 CLIO Input 3 D16 -9999.9+9999.9 10 CLIO 3
3 Enabled
CLIO Input
84 97 110 110 110 CLIO Input 4 D16 -9999.9+9999.9 10 CLIO 3
4 Enabled

New in Software Version 30


98 111 111 111 IN-1 Derived Mag Always D1 0.00065.534 0.1 Phase Current 3
112 112 112 IN-2 Derived Mag Always D1 0.00065.534 0.1 Phase Current 3

New in Software Version 31


113 113 VN2 Magnitude Always D3 0.00220.00 5 Phase Voltage 3
114 114 VN2 Angle Always D4 -180.00+180.00 1 Phase Angle 3

MiCOM P342, P343, P344, P345 & P391


99 113 115 115 NPS Power S2 Always D6 -3150.0+3150.0 1 Power 3
100 114 116 116 Volts/Hz Always D17 0.00032.767 0.1 Volts/Hz 3

New in software version 32


64S 5 Phase Voltage
117 64S V Magnitude D3 0.00220.00 3
enabled

Relay Menu Database


64S 0.01 Sensitive Current
118 64S I Magnitude D2 0.00002.0000 3
enabled
64S 1 Phase Angle
119 64S I Angle D4 -180.00+180.00 3
enabled
64S 10 Resistance
120 64S R secondary D18 032767 3
enabled
MiCOM P342, P343, P344, P345 & P391

Relay Menu Database


Default
P341 Point

P342 Point

P343 Point

P344 Point

P345 Point
Change
Index

Index

Index

Index

Index
Name/ Online Data Type Valid Range Deadband Scaling Factor Event Class
Description if
Index (1, 2, 3 or
none)

New in software version 33


64R CL 0.01 Sensitive Current
101 115 117 121 3
Input 64R enabled 0.00002.0000
64R R 10 Resistance
102 116 118 122 3
Fault 64R enabled 032767

P34x/EN MD/J76
(MD) - 173
P34x/EN MD/J76 Relay Menu Database

(MD) - 174 MiCOM P342, P343, P344, P345 & P391

6.5 Analogue outputs (Integer Scaling Factors)


Each integer scaling factor is represented by two analogue output points. The first point in
the pair represents a multiplier and the second represents a divisor. These values control
the level of scaling applied to the associated analogue input points when integer variations
are requested. The real analogue value can be calculated using the following formula:
Analogue Input (real) = (Analogue Input (scaled) * 10Divisor)/Multiplier
Please note that these values are signed.

Analog Output Status Points (Refer to Section 3: Implementation Table)


Object Number: 40
Default Variation reported when variation 0 requested: Configurable:
1 32-bit Analogue Output Status
2 16-bit Analogue Output Status (Default)
3 Short floating-point Analogue Output Status
Analogue Output Blocks
Object Number: 41

Scaling Factor Multiplier Divisor Scale

Null 1 0 1
Phase Voltages 1 -2 100
Phase Currents 5 -2 500
Phase Angles 1 -2 100
Frequency 1 -2 100
Power 1 -1 10
Power Factor 1 -3 1000
Percentage 1 -2 100
Time(ms) 1 -4 10000
Sensitive Current 1 -4 10000
Temperature 1 -1 10
CLIO 1 -1 10
Volts/Hz 1 -3 1000
Resistance 1 1 0.1

6.6 File transfer


The support for file transfer object allows the extraction of disturbances in COMTRADE
binary data file format.
The directory structure presented by the relay is show below:

\ (root)
--------->\dist_records
--------->\all
--------->\binary
--------->\unextracted
--------->\binary
Relay Menu Database P34x/EN MD/J76

MiCOM P342, P343, P344, P345 & P391 (MD) - 175

Path names are tolerant to forward (/) or back (\) slashes as directory separators.
Directory \dist_records\all\binary contains all disturbance records present in the relay.
Directory \dist_records\unextracted\binary contains only records that have not yet been
extracted.
In order to mark a record as extracted, a file delete command should be issued to the
disturbance record .dat file.
As disturbance records come in file-pairs, (configuration and data file), both files should be
read before the delete8 command is issued.

8 Only the .dat file requires the delete command to be issued, .cfg file will be automatically deleted.
P34x/EN MD/J76 Relay Menu Database

(MD) - 176 MiCOM P342, P343, P344, P345 & P391

7. APPENDIX A
The Alias Control Input points shadow the Control Input points and have slightly different
properties. The changes are summarised as follows:
32 DNP3.0 Binary Output Status points have been created for Control Inputs 1 to 32, which
alias the existing Control Input points.

If the Control Input DDB signal is already SET and a new DNP SET command is sent to
that Control Input, the Control Input DDB signal pulses to RESET and then back to SET.

If the Control Input DDB signal is already RESET and a new DNP RESET command is
sent to that Control Input, the Control Input DDB signal pulses to SET and then back to
RESET.
Publication: P34x/EN MD/J76