You are on page 1of 3

TRANSMISSION AND DISTRIBUTION

Surge protection of distribution


equipment
by Glen Medlin, e-LEK Engineering

This article examines the over-voltage protection of distribution equipment such as pole-top transformers and cable circuits using gapped
zinc-oxide surge arresters, and also considers the environmental benefits of using gapped arresters versus non-gapped arresters.

Surge arresters are constructed from


materials that exhibit a strong non-linear
voltage-current relationship. This means
that the resistance of the arrester should be
dependent on the voltage applied across
the block. To begin with, an ideal arrester
should have infinite resistance when
the voltage across it is normal and zero
resistance when the voltage exceeds the
turn on voltage. We do, however, live in a
real world where this ideal voltage-current
relationship is difficult to achieve.
The first over-voltage protection devices
w e r e s i m p l e s p a r k g a p s, w h e r e t h e
spacing was designed so that the gap
broke down during surge conditions. The
main drawback of such a gap is it could
not quench the power frequency arc
and required some form of upstream
protection to trip the line and remove the
fault. Later, expulsion tubes were added
to the gaps to provide a mechanism
to interrupt the power frequency arc.
However, these tubes had limited fault
current extinguishing capabilities. The
fast breakdown of simple spark gaps can
also cause inter-turn faults in transformer
windings due to the extremely high rates Fig. 1: Comparison between V-I characteristics of ZnO and SiC [2].
of voltage change associated with spark
gap breakdown.
The next innovation was the gapped silicon
carbide arrester which used blocks of
silicon carbide in series with a spark gap.
Silicon carbide exhibited a non-linear
voltage-current relationship, but at normal
voltage, the resistance across the arrester
element was too low and permitted
hundreds of Amps to flow to ground
(Fig. 1). A series gap was thus added so
that the entire voltage appeared across
the gap in normal conditions. When a
surge occurred, the gap would break
down and the surge would be conducted
to ground through the silicon carbide
blocks. After the surge passed, the silicon
carbide blocks would limit the current to
a value which the gap could naturally
extinguish. This enabled the arrester to
interrupt the power frequency current
after a surge, regardless of the available
fault current. Fig. 2: Construction and voltage distribution of gapped SiC, non-gapped MOV and gapped MOV [2].

An improvement on the arrester concept


arrived with the discovery that zinc oxide
(ZnO) had a more favourable non-linear current and this permitted the removal gapless arrester is required to operate at or
voltage-current relationship than silicon of the series spark gap, creating the so below a specific voltage since should this
carbide. Zinc oxide blocks could withstand called gapless arrester or metal oxide voltage be exceeded, the arrester begins
the entire voltage with very little leakage varistor (MOV) (Fig. 1). However, the to conduct. Zinc oxide also has a positive

energize - May 2009 - Page 12


TRANSMISSION AND DISTRIBUTION
temperature coefficient, which means that
the hotter it gets, the more conductive
it becomes. This property can lead to
a condition known as thermal runaway
where the temperature of the arrester and
the current through the arrester grow until
failure occurs. Gapless zinc oxide arresters
need to be sized to withstand temporary
over voltage without entering thermal
runaway. This requires compromise since,
to withstand the temporary overvoltage,
a higher rated arrester needs to be
specified. However, a higher rated arrester
has a higher discharge voltage and this
erodes the protective margin, which is the
difference between the basic insulation
level (BIL) of the equipment and the peak
discharge voltage of the arrester.
The latest innovation in arrester technology
combines the spark gap from the silicon
carbide arrester with the zinc oxide
elements of the gapless arrester. The
arrester blocks and the spark gaps share
the voltage in steady state conditions
by using resistively graded gaps. This
Fig. 3: TOV capability of non-gapped MOV [3].
combination improves the performance
of the arrester in impulse and temporary
over-voltage conditions. Fig. 2 shows how
the technologies were combined.

Steady state operation of gapped MOV


arresters
During steady state conditions where the
voltage across the arrester is the normal
system line to ground voltage, U n, the
voltage is shared equally between the
spark gap structure and the MOV disks.
This allows a reduction in the number of
spark gaps as they are now only required
to withstand half the voltage compared
to the silicon-carbide design. The number
of MOV disks is also reduced since they
are required to withstand half the voltage
compared to gapless arrester designs. The
voltage sharing is achieved by using silicon
carbide grading rings.

Temporary overvoltage ( TOV) operation of


gapped MOV arresters
When the voltage across the gapped MOV
arrester is increased during TOV conditions, Fig. 4: TOV capability of gapped MOV [3].
the voltage sharing between the MOV
elements and the gap structure changes
from the 50/50 distribution found during across the gap rather than the zinc oxide in the front-of-wave sparkover value
normal conditions. The voltage across disks. The zinc oxide disks do not begin compared to silicon carbide arresters.
the gap structure increases faster than to conduct and therefore cannot enter There is generally a slight increase in
the voltage across the MOV disks and thermal runaway. Fig. 3 shows the TOV the 50 Hz sparkover compared to silicon
this enables the arrester to withstand the capability of a non-gapped MOV arrester, carbide, which is a result of the superior
TOV better than non-gapped designs. The while Fig. 4 shows the TOV capability of a TOV capability of the gapped arrester. The
change in voltage distribution is caused gapped MOV arrester. front of wave sparkover is a result of the
by the silicon carbide resistive grading spark gap and the values are a function
Impulse operation of gapped MOV of the design of the spark gap. The voltage
rings responding differently to over-voltage
when compared to the MOV elements. To arresters sharing between the zinc-oxide disks and
explain, the non-linearity of the voltage- The gapped MOV arrester design has the spark gap result in lower sparkover
current characteristic of silicon carbide is fewer zinc oxide disks in series than the values during impulse conditions since it
lower than that of zinc oxide, which means non gapped arrester of the same rating has fewer gaps and a lower voltage across
that the resistance of silicon carbide, as a and this causes a desirable reduction is it at the instant of sparkover compared to
function of the applied voltage, decreases the discharge voltage for all discharge silicon carbide. Fig. 5 shows the voltage
at a lower rate than zinc oxide. Therefore, currents. The gapped MOV arrester also and current discharge characteristics for
as voltage across the gapped arrester uses fewer spark gaps than the silicon gapped silicon-carbide, non-gapped
increases, more voltage begins to appear carbide design and this causes a reduction MOV and gapped MOV. It can be seen

energize - May 2009 - Page 13


TRANSMISSION AND DISTRIBUTION
For example, a new 22 kV transformer with no remote end 1,5 kA discharge voltage. For
excess arrester lead length and protected example, for a 22 kV system protected by a
by a 24 kV rated gapless surge arrester will gapless arrester at the termination only, then
have 65% protective margin for a 40 kA the margin of protection is only 3%. Using a
8/20 s current impulse, assuming a BIL of gapped arrester of the same rating would
150 kV. This may appear sufficient, but two improve the protective margin to 28%. A
factors will tend to reduce this margin:
15 kV rated gapped arrester on the same
Excess arrester lead length system would improve the protective margin
If t h e ov e r h e ad l i n e i s take n to th e to 95% without causing TOV problems.
transformer bushing first, and then to
Other benefits
the arrester terminal, then the inductive
volt drop across the connection lead Reduction in inventory
will add to the discharge voltage of the
transformer. The ground connection of Due to the improved TOV and discharge
the surge arrester is, in almost all cases, in voltage characteristics of gapped surge
series with the arrester and thus also adds arresters, it is possible to use the same
to the discharge voltage. The inductive arrester on 11 and 22 kV resistively earthed
volt drop is a function of the inductance systems without significantly impacting
per unit length, length of the connection the 11 kV margins of protection or
lead and the rate of change of current as 22 kV TOV capability. A single 15 kV rated
per the well known formula: gapped arrester would provide 86%
(down from 94%) and 194% (up from
(2) 65%) protective margin on 11 and 22 kV
systems respectively. TOV capability of the
15 kV gapped arrester on 22 kV systems is
Where L is the inductance of the connection 22,6 kV for 24 hours.
wire (determined primarily by diameter and
length) Reduced environmental impact

For example, if we have a 1 cm diameter Gapless surge arresters typically dissipate


aluminium surge arrester lead of 1 m length, 50 mW per kV [6] rated voltage so a 24 kV
then the approximate volt drop for an rated arrester dissipates 1,2 W continuously.
8/20 s 40 kA current surge will be 5,2 kV. Conservative estimates place the number
Faster surges will increase the volt drop of pole top transformers in South Africa at
further. For our previous example, this approximately 325 000. If we assume they
additional voltage will drop the protective are all three phase 22 kV, then the upper
margin to 56%. limit for continuous surge arrester losses
is approximately 1,2 MW. Gapped surge
In general, this effect becomes more arresters typically dissipate 12 times less
significant on the lower voltage classes as the power than gapped surge arresters the
inductive volt drop is small in comparison to equivalent loss would have been 100 kW.
the discharge voltage for higher voltages.
Fig. 5: Discharge current and voltage Equipment age References
characteristics for Gapped SiC, non-gapped
[1] D A Gonzales, J A Bonner, K Argiropoulos:
MOV and gapped MOV [2]. As cellulose transformer insulation ages, it Benefits of gapped MOV arrester to improve
tends to show a decrease in the impulse system reliability and extend equipment life,
insulation strength. Studies [5] show that 12th International Conference on Electricity
that the peak discharge current is lower for Distribution, CIRED, pp. 2.14/1 2.14/5, Vol. 2,
the decrease is approximately 1% per year 1993.
the gapped MOV compared to the older
of operation. For example, a 30 year old
technologies. [2] D C Henr y, H E Fletcher: Protection of
22 kV pole top transformer with a 1 m surge underground circuits with gapped MOV
Applications of gapped MOV arresters arrester lead and a 24 kV rated gapless technology offers improved margins of
arrester would have 9% protective margin protection, presented at 43rd Annual Power
The gapped MOV arrester has application left. If this transformer was protected by a
Distribution Conference, October 23rd, 1990
in both the overhead and underground [3 Cooper Power Systems publication I235-5:
gapped arrester of the same rating, then
distribution network, where it will provide UltraSIL Housed VariSTAR Surge Arresters 5 kA
the protective margin would be 26%. and 10 kA Class 1 IEC 60099-4 (IEC99-4) for
lower discharge voltages and hence better
MV Systems to 36 kV.
protective margin, and an improved TOV Underground systems [4] Cooper Power Systems publication 235-99:
withstand capability compared to gapless
Water treed XLPE cables are sensitive UltraSIL Polymer-Housed Evolution (10kA) Surge
MOV arresters. Arresters.
to impulses and it is critical to keep the
[5] H Z Ding, Z D Wang, P N Jarman: Effect of
Overhead distribution equipment magnitude of impulses entering these
ageing on the impulse breakdown strength
protection cables as low as possible. If surge arresters of oil-impregnated pressboard used in
are only applied at the overhead line to power transformers, 2006 Annual Report
Overhead distribution equipment, is Conference on Electrical Insulation and
cable termination, then the protective
exposed to substantial surge events Dielectric Phenomena, pp. 497 500.
margin is given by Eqn. 2, except that the
originating from direct and induced [6 Cooper Power Systems publication B235-
lightning strikes. As such,it will benefit discharge voltage used is twice the 10 kA
08033: Taking Protection to the Extremes:
substantially from the improved protection arrester discharge voltage due to voltage UltraSIL Polymer-Housed Distribution-Class Surge
margin offered by gapped MOV arresters. doubling effects. If arresters are placed Arrester.
The protection margin is given by [2]: at the termination and the remote open [7] 2008 Eskom Annual Report, retrieved from www.
end, then Eqn. 2 is used, but the discharge eskom.co.za, May 2009.

(1) voltage is the 10 kA discharge voltage of Contact Glen Medlin, e-LEK Engineering,
the arrester at the termination plus half the Tel 012 349-2220, glen@elek.co.za v

energize - May 2009 - Page 14

You might also like