You are on page 1of 7

3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles

ElectricalNotes&Articles

SharingAbstracts,NotesonvariousElectricalEngineeringTopics.

CalculateSizeofInverter&BatteryBank

OCTOBER2,2015 23COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2015/10/02/CALCULATESIZEOF
INVERTERBATTERYBANK/#COMMENTS)

CalculateSizeofInverterforfollowingElectricalLoad.CalculateSizeofBa eryBankanddecideConnectionofBa ery.

ElectricalLoaddetail:

2Noof60W,230V,0.8P.FFan.
1Noof200W,230V,0.8P.FComputer.
2Noof30W,230V,0.8P.FTubeLight.

Inverter/Ba eryDetail:

AdditionalFurtherLoadExpansion(Af)=20%
EciencyofInverter(Ie)=80%
RequiredBa eryBackup(Bb)=2Hours.
Ba eryBankVoltage=24VDC
LooseConnection/WireLossFactor(LF)=20%
Ba eryEciency(n)=90%
Ba eryAgingFactor(Ag)=20%
DepthofDischarge(DOD)=50%
Ba eryOperatingTemp=46C

Temp.C Factor
80 1.00
70 1.04
60 1.11
50 1.19
40 1.30
30 1.40
20 1.59

Calculation:

Step1:CalculateTotalLoad:

FanLoad=NoxWa =260=120Wa
FanLoad=(NoxWa )/P.F=(260)/0.8=150VA
ComputerLoad=NoxWa =1200=200Wa
ComputerLoad=(NoxWa )/P.F=(1200)/0.8=250VA
TubeLightLoad=NoxWa =230=60Wa
TubeLightLoad=(NoxWa )/P.F=(230)/0.8=75VA
TotalElectricalLoad=120+200+60=380Wa
TotalElectricalLoad=150+250+75=475VA

Step2:SizeofInverter:

SizeofInverter=TotalLoad+(1+Af)/IeVA
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 1/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
SizeofInverter=TotalLoad+(1+Af)/IeVA
SizeofInverter=475+(1+20%)/80%
SizeofInverter=712VA

Step3:SizeofBa ery:

TotalLoadofBa eryBank=(TotalLoadxBackupCapacity)/Ba eryBankVolt


TotalLoadofBa eryBank=(380x2)/24AmpHr
TotalLoadofBa eryBank=32.66AmpHr
TemperatureCorrectionFactorfor46C(Tp)=1
SizeofBa eryBank=[(Load)x(1+LF)x(1+Ag)xTp]/[nxDOD]Amp/Hr
SizeofBa eryBank=(32.66x(1+20%)x(1+20%)x1)/(90%x50%)
SizeofBa eryBank=101.3Amp/Hr

Step4:ConnectionofBa ery:

IfWeSelect120AmpHr,12VDCBa eryforBa eryBank:

SeriesConnection:

Seriescongurationswilladdthevoltageofthetwoba eriesbutkeeptheamperagerating(AmpHours)same.
ConditionI:
SelectionofBa eryforVoltage=VoltofEachBa ery<=VoltofBa eryBank
SelectionofBa eryforVoltage=12<24
ConditionIisO.K
NoofBa eryforVoltage=VoltofBa eryBank/VoltofEachBa ery
NoofBa eryforVoltage=24/12=2Nos
ConditionII:
SelectionofBa eryforAmpHr=AmpHrofBa eryBank<=AmpHrofEachBa ery
SelectionofBa eryforAmpHr=3<=120
ConditionIIisO.K
WecanuseSeriesConnectionforBa ery&NoofBa eryrequired2Nos

(h ps://electricalnotes.les.wordpress.com/2015/10/series_ba ery_cong.jpg)ParallelConguration

InParallelconnection,thecurrentratingwillincreasebutthevoltagewillbethesame.
Morethenumberofba eriesmorewillbetheamp/hour.Twoba erieswillproducetwicetheamp/hourofasingleba ery.
ConditionI:
SelectionofBa eryforAmpHr=AmpHrofBa eryBank/AmpHrofEachBa ery<=1
SelectionofBa eryforAmpHr=101/120=0.84=1Nos
ConditionIisO.K
ConditionII:
SelectionofBa eryforVoltage=VoltofBa eryBank=VoltofEachBa ery
ConditionII:SelectionofBa eryforVoltageforAmpHr=24<=12
ConditionIIisNotFullFill
WecannotuseParallelConnectionforBa eryasperourrequirementButIfWedoPracticallyItisPossibleanditwillgivemore
Hoursofback

https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 2/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles

(h ps://electricalnotes.les.wordpress.com/2015/10/parallel_ba ery_cong.jpg)SeriesParallelConnection:

Connectingtheba eriesupinserieswillincreaseboththevoltageandtheruntime.
ConditionI:
SelectionofBa eryforAmpHr=AmpHrofEachBa ery<=AmpHrofBa eryBank
SelectionofBa eryforAmpHr=120<=101
ConditionIisNotFullFill
ConditionII:
SelectionofBa eryforVoltage=VoltofEachBa ery<=VoltofBa eryBank
SelectionofBa eryforVoltage=12<=24
ConditionIIisOK
WecannotuseParallelConnectionforBa ery

IfWeSelect60AmpHr,12VDCBa eryforBa eryBank:

SeriesConnection:

SelectionofBa eryforVoltage=VoltofEachBa ery<=VoltofBa eryBank


SelectionofBa eryforVoltage=12<24
ConditionIisO.K
NoofBa eryforVoltage=VoltofBa eryBank/VoltofEachBa ery
NoofBa eryforVoltage=24/12=2Nos
ConditionII:
SelectionofBa eryforAmpHr=AmpHrofBa eryBank<=AmpHrofEachBa ery
SelectionofBa eryforAmpHr=3<=60
ConditionIIisNotFullFill
WecanuseSeriesConnectionforBa ery

ParallelConguration

ConditionI:
SelectionofBa eryforAmpHr=AmpHrofBa eryBank/AmpHrofEachBa ery<=1
SelectionofBa eryforAmpHr=101/60=1.63=1Nos
ConditionIisO.K
ConditionII:
SelectionofBa eryforVoltage=VoltofBa eryBank=VoltofEachBa ery
ConditionII:SelectionofBa eryforVoltageforAmpHr=24=12
ConditionIIisNotFullFill
WecannotuseParallelConnectionforBa eryasperourrequirement.

SeriesParallelConnection:

ConditionI:
SelectionofBa eryforAmpHr=AmpHrofEachBa ery<=AmpHrofBa eryBank
SelectionofBa eryforAmpHr=120<=60
ConditionIisOK
NoofBa eryforAmpHr=AmpHrofBa eryBank/AmpHrofEachBa ery
NoofBa eryforAmpHr=120/60=1.68=2Nos
ConditionII:
SelectionofBa eryforVoltage=VoltofEachBa ery<=VoltofBa eryBank
SelectionofBa eryforVoltage=12<=24
ConditionIIisOK
NoofBa eryforVoltage=VoltofBa eryBank/VoltofEachBa ery
NoofBa eryforVoltage=24/12=2Nos
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 3/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
NoofBa eryforVoltage=24/12=2Nos
NoofBa eryRequired=NoofBa eryAmpHrxNoofBa eryforVoltage
NoofBa eryRequired=2x2=4Nos
WecanuseSeriesParallelConnectionforBa ery

(h ps://electricalnotes.les.wordpress.com/2015/10/seriesparallel_ba ery_cong.jpg)

Summary:

TotalElectricalLoad=380Wa
TotalElectricalLoad=475VA
SizeofInverter=712VA
SizeofBa eryBank=101.3Amp/Hr
For120Amp/Hr,12VDCBa ery:SeriesConnection&2NosofBa eryor
For60Amp/Hr,12VDCBa ery:SeriesParallelConnection&4NosofBa ery

Advertisements

FILEDUNDERUNCATEGORIZED

AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan14years
experienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectrical
Projects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputy
ManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectrical
EngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeand
helptechnicalenthusiaststondsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 4/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles

23ResponsestoCalculateSizeofInverter&BatteryBank

KamalKhansays:
December2,2015at3:43pm
Good

Reply
says:
December2,2015at5:18pm
Ithinkthisecalculetionsitsverygood,,thereforelwilldependonthiscalculetionsinfuture.

Reply
kasssays:
December2,2015at8:27pm
thisiswow,goodwork.Ihavebeentryingtocalculatethesizeofaninverter,butnowumakemeknowthecalculations.thank
you

Reply
RobertBalukubalekesays:
December3,2015at3:00am
Thanks

Reply
electroninzsays:
December3,2015at5:01pm
HiMr.Parmar,

ThisisthersttimeIactuallyfollowandreviewthecontentofyourmails.Theresalotoferrorhere.

Firstly,youwontbeabletoget712VAwithyourformulaof475+(1+20%)/80%,unlessyoumultiply475torestsofthe
equation,notadd.

Secondly,totalloadofba erybankis31.66Ah,not32.66.

Thirdly,theunitforsizeofba erybankshouldremainAhnotAmp/Hour.

Ididnotnishtherestofthearticle.Theresprobablymoreerrordownthere.

Thanksfortheeort,anyway.

Bestregards,Ben

>

Reply
ravindrababuubasays:
December4,2015at5:46pm
howtopreparesinglelinediagram,slectionofpanels

Reply
prathapsinghsays:
January7,2016at9:26am
type2cordetationchart

Reply
S.Prashantsays:
December6,2015at5:22pm
Thankyousir,thesecalculationisrealyveryuseful.

Reply
VikasGsays:
December7,2015at7:33am
ThanksSir.
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 5/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
ThanksSir.

Itisagreathelp.

Regards,VikasGupta.

VikasGupta.

Reply
vilasharlapursays:
December7,2015at10:34am
Dearsir,willbethereanymajorproblemifoneba eryof1270Ahinabankof15ba eries(seriesparallelcombination)is
repalcedby12V75Ahba ery.withregards,

vkh

Reply
AjantaMahantasays:
December11,2015at5:23am
DearSir,

Asdirectedforexpert/OEMopinioniamjo ingdowntheschemesinwhichthe11.5MWMyntriangSmallHydroElectric
Project(MSHEP)run.

*1stScheme:*Originally21.5MWMSHEPgridorientedmachinesgetsynchronizedinthe33KVside.The33KVevacuationline
is8Kmwhichfeedthis3MWpowerfromthegeneratingstationto220KVgridsubstationthrougha220/33KVStationResesrve
Transformer(SRT).

*2ndScheme:*Duetononavailabilityof220/33KVSRTthis3MWpowerofMSHEPwassynchronizedwithanother33/132KV
gridsubstation.this33/132KVgridsubstationisaround40KmawayfromMSHEP.this40Km,33KVlinepassesviatwo
numbersof33/11Kvdistributionsubstations.Thefaultsofthis33KVlineisveryfrequent.

whetherthe*2ndscheme*ofevacuationforthisparticular21.5MWMSHEPmachinesisproper.Kindlysuggestsomemeasures
torunthemachinesin*2ndscheme*smoothly.

Withregards,A.MahantaDM,APGCL.

Reply
RenjithKumarsays:
December14,2015at11:19pm
nicecalculationusefullfornormalmanthangs

*Thankyouforyourkindnessandconsideration*,RENJITHPILLAI

Reply
AndreaAPsays:
December21,2015at9:25am
Thanksforsharing

Reply
B.D.says:
January2,2016at6:33am
Thispostisveryhelpful,thoughthecalculationsdoneforconditionIandIIarequiteconfusinglike
for60Ahba ery
ParallelConguration
ConditionI:
SelectionofBa eryforAmpHr=AmpHrofBa eryBank/AmpHrofEachBa ery<=1
SelectionofBa eryforAmpHr=101/60=1.63=1Nos
ConditionIisO.K

How?itdoesnotfulllsAmpHrofBa eryBank/AmpHrofEachBa ery<=1


Therearelotmore

Reply
A.Balansays:
January4,2016at2:33pm
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 6/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
January4,2016at2:33pm
Thanksforaniceexplanation.Liketosecondconrmationwithyourpermissionforthefollowing:
1)parallelconnectionwithsimilarAhandsameVoltageofeachba ery:
(a)Ahisincreased&Voltageissame
2)Seriesconnectionfortheba eriesas(1):
(b)Ahissame&Voltageisincreased
Clarication:
ThelowestAhshouldbetakenintoanaccountforDIFFERENTAhwithsame/similarvoltageba eriestotheabove(1)&(2).
Advisemewithdiagramspl.

Reply
prathapsinghsays:
January5,2016at9:28am
dearsir
howtodesiredamphrofba erybankinseriesconnection3
andparallelconnection101
pleaseexplain

Reply
prathapsinghsays:
January5,2016at9:32am
dearsir
thisisveryexcellentexplanation.buthowtodesiredamphrofba erybankinseriesconnection3andparallelconnection101

Reply
prathapsinghsays:
January5,2016at9:35am
hithere

Reply
M.THIYAGARAJANsays:
January11,2016at8:59am
Thankssir,thiswillhelpmeindecidingthesizeofsolarpowerinstallationprojectstogovernmentbuildings.

Reply
FranciscoNinosays:
February7,2016at3:30am
DiagramseriesparallelconnectionOutputNO(240AH,24V),YES(120AH,24V)

Reply
FranciscoNinosays:
February7,2016at3:31am
WhyTemperatureCorrectionFactorfor46C(Tp)=1?

Reply
Baijusays:
February26,2016at6:28am
SinglephaseUPStaken16AinputcurrentwhichcapacityMCBneedininput

Reply
DineshShankersays:
June30,2016at6:40am
Hi,
mydoubtonthistopicisthatwhystartingKVAforthecomputerloadhasnotbeenconsidered?

Reply

BlogatWordPress.com.

https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 7/7

You might also like