SharingAbstracts,NotesonvariousElectricalEngineeringTopics.
CalculateSizeofInverter&BatteryBank
OCTOBER2,2015 23COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2015/10/02/CALCULATESIZEOF
INVERTERBATTERYBANK/#COMMENTS)
ElectricalLoaddetail:
2Noof60W,230V,0.8P.FFan.
1Noof200W,230V,0.8P.FComputer.
2Noof30W,230V,0.8P.FTubeLight.
Inverter/Ba eryDetail:
AdditionalFurtherLoadExpansion(Af)=20%
EciencyofInverter(Ie)=80%
RequiredBa eryBackup(Bb)=2Hours.
Ba eryBankVoltage=24VDC
LooseConnection/WireLossFactor(LF)=20%
Ba eryEciency(n)=90%
Ba eryAgingFactor(Ag)=20%
DepthofDischarge(DOD)=50%
Ba eryOperatingTemp=46C
Temp.C Factor
80 1.00
70 1.04
60 1.11
50 1.19
40 1.30
30 1.40
20 1.59
Calculation:
Step1:CalculateTotalLoad:
FanLoad=NoxWa =260=120Wa
FanLoad=(NoxWa )/P.F=(260)/0.8=150VA
ComputerLoad=NoxWa =1200=200Wa
ComputerLoad=(NoxWa )/P.F=(1200)/0.8=250VA
TubeLightLoad=NoxWa =230=60Wa
TubeLightLoad=(NoxWa )/P.F=(230)/0.8=75VA
TotalElectricalLoad=120+200+60=380Wa
TotalElectricalLoad=150+250+75=475VA
Step2:SizeofInverter:
SizeofInverter=TotalLoad+(1+Af)/IeVA
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 1/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
SizeofInverter=TotalLoad+(1+Af)/IeVA
SizeofInverter=475+(1+20%)/80%
SizeofInverter=712VA
Step3:SizeofBa ery:
Step4:ConnectionofBa ery:
SeriesConnection:
Seriescongurationswilladdthevoltageofthetwoba eriesbutkeeptheamperagerating(AmpHours)same.
ConditionI:
SelectionofBa eryforVoltage=VoltofEachBa ery<=VoltofBa eryBank
SelectionofBa eryforVoltage=12<24
ConditionIisO.K
NoofBa eryforVoltage=VoltofBa eryBank/VoltofEachBa ery
NoofBa eryforVoltage=24/12=2Nos
ConditionII:
SelectionofBa eryforAmpHr=AmpHrofBa eryBank<=AmpHrofEachBa ery
SelectionofBa eryforAmpHr=3<=120
ConditionIIisO.K
WecanuseSeriesConnectionforBa ery&NoofBa eryrequired2Nos
(h ps://electricalnotes.les.wordpress.com/2015/10/series_ba ery_cong.jpg)ParallelConguration
InParallelconnection,thecurrentratingwillincreasebutthevoltagewillbethesame.
Morethenumberofba eriesmorewillbetheamp/hour.Twoba erieswillproducetwicetheamp/hourofasingleba ery.
ConditionI:
SelectionofBa eryforAmpHr=AmpHrofBa eryBank/AmpHrofEachBa ery<=1
SelectionofBa eryforAmpHr=101/120=0.84=1Nos
ConditionIisO.K
ConditionII:
SelectionofBa eryforVoltage=VoltofBa eryBank=VoltofEachBa ery
ConditionII:SelectionofBa eryforVoltageforAmpHr=24<=12
ConditionIIisNotFullFill
WecannotuseParallelConnectionforBa eryasperourrequirementButIfWedoPracticallyItisPossibleanditwillgivemore
Hoursofback
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 2/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
(h ps://electricalnotes.les.wordpress.com/2015/10/parallel_ba ery_cong.jpg)SeriesParallelConnection:
Connectingtheba eriesupinserieswillincreaseboththevoltageandtheruntime.
ConditionI:
SelectionofBa eryforAmpHr=AmpHrofEachBa ery<=AmpHrofBa eryBank
SelectionofBa eryforAmpHr=120<=101
ConditionIisNotFullFill
ConditionII:
SelectionofBa eryforVoltage=VoltofEachBa ery<=VoltofBa eryBank
SelectionofBa eryforVoltage=12<=24
ConditionIIisOK
WecannotuseParallelConnectionforBa ery
SeriesConnection:
ParallelConguration
ConditionI:
SelectionofBa eryforAmpHr=AmpHrofBa eryBank/AmpHrofEachBa ery<=1
SelectionofBa eryforAmpHr=101/60=1.63=1Nos
ConditionIisO.K
ConditionII:
SelectionofBa eryforVoltage=VoltofBa eryBank=VoltofEachBa ery
ConditionII:SelectionofBa eryforVoltageforAmpHr=24=12
ConditionIIisNotFullFill
WecannotuseParallelConnectionforBa eryasperourrequirement.
SeriesParallelConnection:
ConditionI:
SelectionofBa eryforAmpHr=AmpHrofEachBa ery<=AmpHrofBa eryBank
SelectionofBa eryforAmpHr=120<=60
ConditionIisOK
NoofBa eryforAmpHr=AmpHrofBa eryBank/AmpHrofEachBa ery
NoofBa eryforAmpHr=120/60=1.68=2Nos
ConditionII:
SelectionofBa eryforVoltage=VoltofEachBa ery<=VoltofBa eryBank
SelectionofBa eryforVoltage=12<=24
ConditionIIisOK
NoofBa eryforVoltage=VoltofBa eryBank/VoltofEachBa ery
NoofBa eryforVoltage=24/12=2Nos
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 3/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
NoofBa eryforVoltage=24/12=2Nos
NoofBa eryRequired=NoofBa eryAmpHrxNoofBa eryforVoltage
NoofBa eryRequired=2x2=4Nos
WecanuseSeriesParallelConnectionforBa ery
(h ps://electricalnotes.les.wordpress.com/2015/10/seriesparallel_ba ery_cong.jpg)
Summary:
TotalElectricalLoad=380Wa
TotalElectricalLoad=475VA
SizeofInverter=712VA
SizeofBa eryBank=101.3Amp/Hr
For120Amp/Hr,12VDCBa ery:SeriesConnection&2NosofBa eryor
For60Amp/Hr,12VDCBa ery:SeriesParallelConnection&4NosofBa ery
Advertisements
FILEDUNDERUNCATEGORIZED
AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan14years
experienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectrical
Projects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputy
ManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectrical
EngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeand
helptechnicalenthusiaststondsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 4/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
23ResponsestoCalculateSizeofInverter&BatteryBank
KamalKhansays:
December2,2015at3:43pm
Good
Reply
says:
December2,2015at5:18pm
Ithinkthisecalculetionsitsverygood,,thereforelwilldependonthiscalculetionsinfuture.
Reply
kasssays:
December2,2015at8:27pm
thisiswow,goodwork.Ihavebeentryingtocalculatethesizeofaninverter,butnowumakemeknowthecalculations.thank
you
Reply
RobertBalukubalekesays:
December3,2015at3:00am
Thanks
Reply
electroninzsays:
December3,2015at5:01pm
HiMr.Parmar,
ThisisthersttimeIactuallyfollowandreviewthecontentofyourmails.Theresalotoferrorhere.
Firstly,youwontbeabletoget712VAwithyourformulaof475+(1+20%)/80%,unlessyoumultiply475torestsofthe
equation,notadd.
Secondly,totalloadofba erybankis31.66Ah,not32.66.
Thirdly,theunitforsizeofba erybankshouldremainAhnotAmp/Hour.
Ididnotnishtherestofthearticle.Theresprobablymoreerrordownthere.
Thanksfortheeort,anyway.
Bestregards,Ben
>
Reply
ravindrababuubasays:
December4,2015at5:46pm
howtopreparesinglelinediagram,slectionofpanels
Reply
prathapsinghsays:
January7,2016at9:26am
type2cordetationchart
Reply
S.Prashantsays:
December6,2015at5:22pm
Thankyousir,thesecalculationisrealyveryuseful.
Reply
VikasGsays:
December7,2015at7:33am
ThanksSir.
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 5/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
ThanksSir.
Itisagreathelp.
Regards,VikasGupta.
VikasGupta.
Reply
vilasharlapursays:
December7,2015at10:34am
Dearsir,willbethereanymajorproblemifoneba eryof1270Ahinabankof15ba eries(seriesparallelcombination)is
repalcedby12V75Ahba ery.withregards,
vkh
Reply
AjantaMahantasays:
December11,2015at5:23am
DearSir,
Asdirectedforexpert/OEMopinioniamjo ingdowntheschemesinwhichthe11.5MWMyntriangSmallHydroElectric
Project(MSHEP)run.
*1stScheme:*Originally21.5MWMSHEPgridorientedmachinesgetsynchronizedinthe33KVside.The33KVevacuationline
is8Kmwhichfeedthis3MWpowerfromthegeneratingstationto220KVgridsubstationthrougha220/33KVStationResesrve
Transformer(SRT).
*2ndScheme:*Duetononavailabilityof220/33KVSRTthis3MWpowerofMSHEPwassynchronizedwithanother33/132KV
gridsubstation.this33/132KVgridsubstationisaround40KmawayfromMSHEP.this40Km,33KVlinepassesviatwo
numbersof33/11Kvdistributionsubstations.Thefaultsofthis33KVlineisveryfrequent.
whetherthe*2ndscheme*ofevacuationforthisparticular21.5MWMSHEPmachinesisproper.Kindlysuggestsomemeasures
torunthemachinesin*2ndscheme*smoothly.
Withregards,A.MahantaDM,APGCL.
Reply
RenjithKumarsays:
December14,2015at11:19pm
nicecalculationusefullfornormalmanthangs
*Thankyouforyourkindnessandconsideration*,RENJITHPILLAI
Reply
AndreaAPsays:
December21,2015at9:25am
Thanksforsharing
Reply
B.D.says:
January2,2016at6:33am
Thispostisveryhelpful,thoughthecalculationsdoneforconditionIandIIarequiteconfusinglike
for60Ahba ery
ParallelConguration
ConditionI:
SelectionofBa eryforAmpHr=AmpHrofBa eryBank/AmpHrofEachBa ery<=1
SelectionofBa eryforAmpHr=101/60=1.63=1Nos
ConditionIisO.K
Reply
A.Balansays:
January4,2016at2:33pm
https://electricalnotes.wordpress.com/2015/10/02/calculatesizeofinverterbatterybank/ 6/7
3/15/2017 CalculateSizeofInverter&BatteryBank|ElectricalNotes&Articles
January4,2016at2:33pm
Thanksforaniceexplanation.Liketosecondconrmationwithyourpermissionforthefollowing:
1)parallelconnectionwithsimilarAhandsameVoltageofeachba ery:
(a)Ahisincreased&Voltageissame
2)Seriesconnectionfortheba eriesas(1):
(b)Ahissame&Voltageisincreased
Clarication:
ThelowestAhshouldbetakenintoanaccountforDIFFERENTAhwithsame/similarvoltageba eriestotheabove(1)&(2).
Advisemewithdiagramspl.
Reply
prathapsinghsays:
January5,2016at9:28am
dearsir
howtodesiredamphrofba erybankinseriesconnection3
andparallelconnection101
pleaseexplain
Reply
prathapsinghsays:
January5,2016at9:32am
dearsir
thisisveryexcellentexplanation.buthowtodesiredamphrofba erybankinseriesconnection3andparallelconnection101
Reply
prathapsinghsays:
January5,2016at9:35am
hithere
Reply
M.THIYAGARAJANsays:
January11,2016at8:59am
Thankssir,thiswillhelpmeindecidingthesizeofsolarpowerinstallationprojectstogovernmentbuildings.
Reply
FranciscoNinosays:
February7,2016at3:30am
DiagramseriesparallelconnectionOutputNO(240AH,24V),YES(120AH,24V)
Reply
FranciscoNinosays:
February7,2016at3:31am
WhyTemperatureCorrectionFactorfor46C(Tp)=1?
Reply
Baijusays:
February26,2016at6:28am
SinglephaseUPStaken16AinputcurrentwhichcapacityMCBneedininput
Reply
DineshShankersays:
June30,2016at6:40am
Hi,
mydoubtonthistopicisthatwhystartingKVAforthecomputerloadhasnotbeenconsidered?