SIPROTEC 7SN600
E50417-G1176-C128-A4
Transient earth-fault relay
SIPROTEC 7SN600
Copyright
The reproduction, transmission or use of this
document or its contents is not permitted without
express written authority. Offenders will be liable
for damages. All rights, including rights created by
patent grant or registration of a utility model or
design, are reserved.
Safety Instructions I
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
List of contents
1 Application............................................................................................................ 7
1.1 Earth fault directional determination ................................................................................................... 7
1.2 Detection of the fault location ............................................................................................................. 9
1.3 Functions and features ..................................................................................................................... 10
6 Connection diagram........................................................................................... 30
6.1 Panel flush mounting and panel surface mounting (terminals on the side)...................................... 30
6.2 Panel surface mounting (terminals on up / down) ............................................................................ 31
7 Appendix ............................................................................................................. 33
7.1 List of figures .................................................................................................................................... 33
Application 1
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
1 Application
1
2
3
4
Siemens AG 05.10.2002 7 - 36
1 Application
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
At measuring point A, as a result of the transformer earthed systems this occurs after a very short time
summation circuit, the earth current of the faulted (figure 1.2).
line is not included in the measurement, as this
In the case of a continuous earth fault, the
current portion flows though the summation
equalizing current in the non-earthed system
transformer of the relevant Holmgreen circuit and
changes into the mostly capacitive continuous
back, thereby cancelling itself out.
earth current or, in compensated systems, into the
It is the total of the capacitive earth currents from relatively low residual active current.
the non-faulted system which has an effect. In the
For the directional determination, the direction of
diagram they are summated on the upper line. The
the first transient of neutral current and
capacitive currents of the non-faulted lines 1, 3 and
displacement voltage is considered.
2, 4 accumulate vectorially, which is why only three
arrows instead of four are shown at measuring The device indicates the direction of the transient
point A. earth fault by LEDs (red = forward direction, yellow
= reverse direction) and the relevant signalling
With a transient earth fault, the equalizing current
relay picks up.
forming with a damped oscillation of 100 to more
than 1 000 Hz decays after only a few periods. Continuous earth faults are indicated after a
settable time by an LED on the device and
The displacement voltage UEM thereupon also
signalled by a signalling relay.
returns to zero. In earthed systems this takes place
after a number of periods (decay of the Petersen
coil earth capacitance oscillation circuit); in non-
Earth fault
Start
End
UEM
I0
t
t1
8 - 36 Siemens AG 05.10.2002
Application 1
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
Siemens AG 05.10.2002 9 - 36
1 Application
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
Device versions for panel surface mounting of Wide-range power supply for connection to
flush mounting, with terminals on the side, in 110 / 230 V AC systems, 60 250 V DC
7XP20 housing station batteries or 100 V AC voltage
transformers without switchover
Both fault directions indicated by LEDs and
signalled by relays Binary inputs for remote reset and blocking
with extremely wide input voltage range of
High pick-up sensitivity due to separate
24 to 250 V DC
detection and evaluation of total current and
displacement voltage Automatic reset of direction indications and
signals after 3 s or 10 s (selectable)
1 A and 5 A rated current selectable for current
transformer matching Automatic reset in case of intermittent earth
faults only after the last earth fault, i.e. the
16 selectable pickup thresholds for detection of
correct indication and signal of the first earth
transients in the current path even with higher
fault is preserved
steady-state total currents of 10 mA to 300 mA
Detection of the displacement voltage and
Fixed pickup threshold of 5 V for detection of
earth fault indication / signal, independent of a
transients in the voltage path even in case of
transient fault detection
higher steady-state displacement voltages
Signalling and indication of a continuous earth
4 selectable pickup thresholds for evaluation of
fault possible only in the forward direction
the displacement voltage of 10 V to 50 V
Command contacts of all signalling relays
Optional suppression of switching operations
by evaluation of the displacement voltage after Fault indication if sensitivity is set too high
a switching-induced transient has occurred.
10 - 36 Siemens AG 05.10.2002
Method of operation 2
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
2 Method of operation
Pickup
sensitivity
S3.3 - S3.6
I_pos.
Oscillating
Current transformer P
circuit
Limit stages
I0 N
X2
I_neg.
1A / 5A
I Test Subtractor
Siemens AG 05.10.2002 11 - 36
2 Method of operation
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
Summing unit
Voltage Oscillating
transformer circuit U_pos.
P
U0 Limit stages
N
Input protection
circuit U_Test U_neg.
Subtractor
Pickup
sensitivity
S3.7 - S3.8
Limit stage
Filter
U_Fund
P
U_Test
Figure 2.2: Detection of transients and of fundamental wave in the voltage path
12 - 36 Siemens AG 05.10.2002
Method of operation 2
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
I_pos. S Ip
R Ip
50/150s =1
Clock
pulse & =1 G_Reset
Block
S2.8 Filter =1
R In
I_neg. S In
&
50/150s
S3.2 =1 R_Rev
Time &
window 1/4ms Directional
determination
U_Reset &
& =1 R_Forw
& S Up &
U_pos.
R Up
=1 U_Reset
=1 Start 1
=1
R Un
& S Un
U_neg.
Input memory
Siemens AG 05.10.2002 13 - 36
2 Method of operation
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
If no transient voltage is detected within the time The information that has been frozen in the input
window, a reset signal "U_Reset" is generated. A memories is now evaluated. If the first transient
General Reset signal (which is generated if other current and voltage have the same direction, the
reset criteria are fulfilled as well) resets all fault is in reverse direction ("R_Rev"). If the
memories and makes the relay ready to operate directions are different, it is in forwards direction
again. Additionally, the Blocked LED is set for ("R_Forw").
500 ms. This LED allows to recognize during
"Start 1" starts further plausibility checks. The
commissioning whether repeated spurious pickups
"Block" signals allows to block the relay by
of the transient earth-fault relay are due to
disabling the clock pulse generator.
interference or to a pickup threshold in the current
path that is set too low. The alarm relay is not set.
Transient
earth fault
forward
R_Forw S
&
R
Transient
earth fault
reverse
Clock
G_Reset pulse
Transient
Start 1 earth fault
90ms 1ms &
forward
& TEF_Reset
U_Fund
=1
R Transient
S2.1
14 - 36 Siemens AG 05.10.2002
Method of operation 2
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
TEF_FR
TEF_Rev =1 &
G_Reset =1
TEF_Forw
U_Fund &
red Continuous
25/65ms R earth fault
Clock
pulse S
& Continuous
earth fault
& =1
S2.5
S2.3
S2.2
Siemens AG 05.10.2002 15 - 36
2 Method of operation
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
Auto_Reset:
Switches S2.6 and S2.7 can be used to start an
automatic reset after a settable delay of 3 or 10 s.
The automatic reset is started as soon as the
displacement voltage drops off.
Remote_Reset
U_Reset =1 =1 G_Reset
TEF_Reset
U_Fund
25/65ms
Local_Reset
S2.6
S2.7
on front panel
16 - 36 Siemens AG 05.10.2002
Method of operation 2
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
The inputs can be activated with a voltage As the inputs are galvanically separated, they can
between 24 V and 250 V DC and are protected be fed by different battery circuits.
against polarity reversal.
I const.
2mA R_Reset
X31
Remote_Reset
I const.
2mA Block
X30
Blocking
The green Service LED shines as long as the In that latter case, the sensitivity of the input
auxiliary voltage is present and the programmable should be reduced by means of the switches
logic device is working. S3.3-6.
The red Blocked LED shines to indicate the The alarm relay is of the NC type; it signals an
failure of an internal supply voltage or repeated internal or external failure of the auxiliary supply
voltage.
red Alarm
U_Reset
500ms =1
P5
P15 Alarm
N15 &
Siemens AG 05.10.2002 17 - 36
2 Method of operation
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
P 100Hz
P I_Test
&
Test P U_Test
forward
direction
P N
Test &
reverse
P
direction
18 - 36 Siemens AG 05.10.2002
Operating instructions 3
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
3 Operating instructions
Line protection
IN 1
IE 2
U L1 7
U L2 8
U L3 9
UE 10
30
AC/DC
Auxiliary
voltage 31
DC
Siemens AG 05.10.2002 19 - 36
3 Operating instructions
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
3.4 Settings
Switch off the auxiliary power supply and take Proceed in opposite order to reclose the
the necessary precautions against electrostatic device and switch the auxiliary voltage supply
discharges. The c.t. connectors are shorted on on again.
withdrawing the p.c.b. The device is ready for operation again as soon as
Slip away the covers at the top and bottom of the green Service LED shines and the red
the front panel to gain access to the fixing Blocked LED has gone out.
screws of the module.
3
S30
1
Terminal block
Voltage
transformer
Current
transformer
1 8 1 8
3 1 OFF
ON
X2 S3 S2
20 - 36 Siemens AG 05.10.2002
Operating instructions 3
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
3.4.3 Settings
The matching of the measuring circuits to the 1 A to the secondary-side value of the current
or 5 A primary current transformers is performed transformers. The sensitivity should be set to about
by setting jumper X2. half the value of the calculated current.
The pickup sensitivity is set by switches S3.3 - All other functions should be set as required
S3.6. The setting is determined by the systems according to the following table.
earth current IE in uncompensated state, converted
X2 X30 X31
X = Switch on 1-2 5 A rated current
Bold = Position as delivered 2-3 1 A rated current
1-2 19 V pickup voltage of the blocking input
2-3 75 V pickup voltage of the blocking input
1-2 19 V pickup voltage of the remote reset input
2-3 75 V pickup voltage of the remote reset input
Siemens AG 05.10.2002 21 - 36
3 Operating instructions
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
22 - 36 Siemens AG 05.10.2002
Operating instructions 3
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
M 0,1 UL U L1 7
U L2 8
230V AC S1 H1 U L3 9
UE UE 10
IN IN 1
7VP8300-0 7SN60
Siemens AG 05.10.2002 23 - 36
4 Technical data
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
4 Technical data
24 - 36 Siemens AG 05.10.2002
Technical data 4
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
50 Hz rated frequency 0
16 2/3 Hz rated frequency 1
Auxiliary voltage 60-250V DC and 0
100-220V AC without switchover
Auxiliary voltage 24-48V DC 1
Siemens AG 05.10.2002 25 - 36
5 Housing types and dimensions
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
244
Terminals
71 +2
Panel cutout
Dimensions in mm 6
56.5
5.4
7.3 +/-0.3
Figure 5.1: Dimensions for panel flush mounting
26 - 36 Siemens AG 05.10.2002
Housing types and dimensions 5
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
128 77 260
9 29.5
31 32
300
280
266
8
7
1
2
100 55
Dimensions in mm
Current connections (terminals 1 - 6)
Insulated ring cable lugs: for screws up to 6 mm
Maximum outer width 13 mm
Type e.g. PIDG from AMP Co.
Conductors with cross-section
2.7 mm2 to 6.6 mm2
Cable end sleeves are required for
stranded conductors
In parallel double leaf-
spring-crimp contact: for diameters of 2.5 to 4.0 mm2
Figure 5.2: Dimensions for panel surface mounting (terminals on the side)
Siemens AG 05.10.2002 27 - 36
5 Housing types and dimensions
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
92 260
27
15 21
22 28 29,5
9
280
360
266
Screw M4
1 7
8 14 Dimension in mm
77 75
28 - 36 Siemens AG 05.10.2002
Housing types and dimensions 5
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
SIEMENS
Red LED
Continuous earth fault
Red LED
Uo >
Displacement voltage
present
SIEMENS
Rating plate
7SN6000-0EA00
Slip cover downwards
to open
Siemens AG 05.10.2002 29 - 36
6 Connection diagram
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
6 Connection diagram
6.1 Panel flush mounting and panel surface mounting (terminals on the side)
17
IN 1 Transient
20 earth fault
forward
IE 2
16 1L+
U L1 7 19 2L+
U L2 8
U L3 9
15
Transient
UE 10 18 earth fault
reverse
L+/L1 30
21 1L+
AC/DC
Auxiliary
23 2L+
voltage
L-/N 31 DC
24
11 Continuous
L- Binary 22 earth fault
Blocking 12 input
L+
25 1L+
13
L- Binary-
Remote reset 14 input Auxiliary
Bus bar L+ 26 voltage
failure
30 - 36 Siemens AG 05.10.2002
Connection diagram 6
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
7SN600x-0DA00
Line protection
18
IN 1 Transient
15 earth fault
forward
IE 3
16 1L+
U L1 4 19 2L+
U L2 5
U L3 6
17
Transient
UE 7 20 earth fault
reverse
L+ 12
26 1L+
22 AC/DC
Auxiliary 11
voltage 2L+
L- 14 DC
23
13
28 Continuous
L- 27 earth fault
Blocking Binary-
L+ 21 input
24 1L+
10
L-
Binary-
Remote reset
9 input Auxiliary
Bus bar L+ 25 voltage
failure
Siemens AG 05.10.2002 31 - 36
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
32 - 36 Siemens AG 05.10.2002
Appendix 7
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
7 Appendix
Siemens AG 05.10.2002 33 - 36
Transient earth-fault relay 7SN60 Instruction Manual Order No. E50417-G1176-C128-A4
34 - 36 Siemens AG 05.10.2002
Siemens Companies and Representatives:
Siemens AG
Power Transmission and Distribution