Professional Documents
Culture Documents
Welcome to the Raritan 3-phase capacity planning tool. These vendor-agnostic spreadsheets aim to d
loading 3-phase rack power strips -- to ensure maximum power capacity while preventing overloading
Five power strip capacity options are found below (worksheet tabs). It is VERY IMPORTANT
1 sized for your rack power strip. Consult the spec sheet or engineering submittals of your rack
input current -- not just the input plug type.
For each outlet type (C13 or C19), per breaker -- enter in expected loads (in watts); and optio
2 drawing the load. For Tier II (and above) redundancy situations, complete the spreadsheet as
power strip in the cabinet is offline.
3 The capacity planning tool will automatically highlight any error conditions. So long as the field
righ of the spreadsheet reads "OK" (Green), your rack power strip has not exceeded its capac
4 Optionally, adjust the input voltage and power factor assumptions (defaulted to 208V and 97.5
common in North America).
Note that rack power strip vendors provide multiple products with 60A plugs (IEC 60309 60A 3
60A currents: either 48A or 45A. (This is because 45A units require smaller, 6# AWG cable -- while
plug AWG cable). Be sure to select the correct worksheet that corresponds to your power strip.
Note that rack power strip vendors provide products with 50A plugs (Hubbell CS8365C, "Califo
50A rated currents: either 40A or 35A. (This is because 35A units are equipped with only 3 branch
plug are equipped with 6 branch circuit breakers). Be sure to select the correct worksheet that corr
60A plugs (IEC 60309 60A 3P4W), but with two different rated
maller, 6# AWG cable -- while 48A units are equipped with 4#
onds to your power strip.
Input Voltage
L1/L2 [XY] L2/L3 [YZ] L3/L1 [XZ] 208
typical = 208
Type Device Name Watts Amps Type Device Name Watts Amps Type Device Name Watts Amps
Circuit Breaker A (L1/L2) Circuit Breaker B (L2/L3) Circuit Breaker C (L3/L1) Power Factor
C13 0.0 C13 0.0 C13 CorpWebSvr 1of5 250 1.2 97.5%
C13 0.0 C13 0.0 C13 CorpWebSvr 2of5 250 1.2 typical = above 95%
C13 0.0 C13 0.0 C13 CorpWebSvr 3of5 250 1.2
C13 ExchangeServer WEST 350 1.7 C13 0.0 C13 CorpWebSvr 4of5 250 1.2
C13 ExchangeServer EAST 350 1.7 C13 0.0 C13 CorpWebSvr 5of5 250 1.2
C13 0.0 C13 0.0 C13 0.0 Current by Line Pair
C13 0.0 C13 0.0 C13 0.0 L1/L2 10.6
C13 0.0 C13 0.0 C13 0.0 L2/L3 7.1
C13 0.0 C13 0.0 C13 0.0 L3/L1 6.2
C13 0.0 C13 0.0 C13 0.0
C13 0.0 C13 0.0 C13 0.0
C13 0.0 C13 0.0 C13 0.0 Phase Balance
C13 0.0 C13 0.0 C13 0.0 L1 106%
C13 0.0 C13 0.0 C13 0.0 L2 111%
C13 0.0 C13 0.0 C13 0.0 L3 83%
C13 0.0 C13 0.0 C13 0.0
maximize capacity by balancing load
C19 0.0 C19 0.0 C19 0.0
C19 0.0 C19 0.0 C19 0.0
C19 0.0 C19 0.0 C19 0.0 Capacity Remaining
C19 Cisco Nexus 7000, PS1 1450 7.1 C19 Cisco Nexus 7000, PS2 1450 7.1 C19 0.0 L1 8%
C13 cannot exceed 12A; C19 cannot exceed 16A C13 cannot exceed 12A; C19 cannot exceed 16A C13 cannot exceed 12A; C19 cannot exceed 16A L2 3%
OK OK OK L3 28%
Input Voltage
L1/L2 [XY] L2/L3 [YZ] L3/L1 [XZ] 208
typical = 208
Type Device Name Watts Amps Type Device Name Watts Amps Type Device Name Watts Amps
Circuit Breaker A (L1/L2) Circuit Breaker B (L2/L3) Circuit Breaker C (L3/L1) Power Factor
C13 0.0 C13 0.0 C13 CorpWebSvr 1of5 250 1.2 97.5%
C13 0.0 C13 RAID Array 1 275 1.4 C13 CorpWebSvr 2of5 250 1.2 typical = above 95%
C13 0.0 C13 RAID Array 2 275 1.4 C13 CorpWebSvr 3of5 250 1.2
C13 ExchangeServer WEST 350 1.7 C13 RAID Array 3 275 1.4 C13 CorpWebSvr 4of5 250 1.2 Current by Breaker
C13 ExchangeServer EAST 350 1.7 C13 RAID Array 4 275 1.4 C13 CorpWebSvr 5of5 250 1.2 A 10.6
C13 0.0 C13 RAID Array 5 275 1.4 C13 0.0 B 13.9
C13 0.0 C13 0.0 C13 0.0 C 12.1
C13 0.0 C13 0.0 C13 0.0 no breaker to exceed 20A
Capacity Remaining
L1 18%
19.7 21.3 22.5 7.6 OK L2 11%
L1 Current (A) L2 Current (A) L3 Current (A) Total Power (kVA) Capacity Check L3 6%
cannot exceed 24A cannot exceed 24A cannot exceed 24A cannot exceed 8.6kVA version 8
3-phase Capacity Planning Worksheet: 208V, 3phase / 50A (35A) per line 2016 Raritan Inc.
by Michael Suchoff and Henry Hsu;
Input Voltage
L1/L2 [XY] L2/L3 [YZ] L3/L1 [XZ] 208
typical = 208
Type Device Name Watts Amps Type Device Name Watts Amps Type Device Name Watts Amps
Circuit Breaker A (L1/L2) Circuit Breaker B (L2/L3) Circuit Breaker C (L3/L1) Power Factor
C13 0.0 C13 0.0 C13 CorpWebSvr 1of5 250 1.2 97.5%
C13 0.0 C13 RAID Array 1 275 1.4 C13 CorpWebSvr 2of5 250 1.2 typical = above 95%
C13 0.0 C13 RAID Array 2 275 1.4 C13 CorpWebSvr 3of5 250 1.2
C13 ExchangeServer WEST 350 1.7 C13 RAID Array 3 275 1.4 C13 CorpWebSvr 4of5 250 1.2 Current by Breaker
C13 ExchangeServer EAST 350 1.7 C13 RAID Array 4 275 1.4 C13 CorpWebSvr 5of5 250 1.2 A 10.6
C13 0.0 C13 RAID Array 5 275 1.4 C13 0.0 B 13.9
C13 0.0 C13 0.0 C13 0.0 C 15.0
C13 0.0 C13 0.0 C13 0.0 no breaker to exceed 20A
Capacity Remaining
L1 36%
22.3 21.3 25.1 8.2 OK L2 39%
L1 Current (A) L2 Current (A) L3 Current (A) Total Power (kVA) Capacity Check L3 28%
cannot exceed 35A cannot exceed 35A cannot exceed 35A cannot exceed 12.5kVA version 8
3-phase Capacity Planning Worksheet: 208V, 3phase / 50A (40A) per line 2016 Raritan Inc.
by Michael Suchoff and Henry Hsu;
Input Voltage
L1/L2 [XY] L2/L3 [YZ] L3/L1 [XZ] 208
typical = 208
Type Device Name Watts Amps Type Device Name Watts Amps Type Device Name Watts Amps
Circuit Breaker A (L1/L2) Circuit Breaker C (L2/L3) Circuit Breaker E (L3/L1) Power Factor
C13 0.0 C13 0.0 C13 CorpWebSvr 1of5 250 1.2 97.5%
C13 0.0 C13 48-port OOB Switch 275 1.4 C13 CorpWebSvr 2of5 250 1.2 typical = above 95%
C13 0.0 C13 0.0 C13 CorpWebSvr 3of5 250 1.2
C13 ExchangeServer WEST 350 1.7 C13 0.0 C13 0.0 Current by Breaker
Capacity Remaining
L1 23%
L2 18%
30.8 32.8 29.0 11.1 OK L3 28%
L1 Current (A) L2 Current (A) L3 Current (A) Total Power (kVA) Capacity Check
cannot exceed 40A cannot exceed 40A cannot exceed 40A cannot exceed 14.4kVA version 8
3-phase Capacity Planning Worksheet: 208V, 3phase / 60A (45A) per line 2016 Raritan Inc.
by Michael Suchoff and Henry Hsu;
Input Voltage
L1/L2 [XY] L2/L3 [YZ] L3/L1 [XZ] 208
typical = 208
Type Device Name Watts Amps Type Device Name Watts Amps Type Device Name Watts Amps
Circuit Breaker A (L1/L2) Circuit Breaker C (L2/L3) Circuit Breaker E (L3/L1) Power Factor
C13 0.0 C13 0.0 C13 CorpWebSvr 1of5 250 1.2 97.5%
C13 0.0 C13 48-port OOB Switch 275 1.4 C13 CorpWebSvr 2of5 250 1.2 typical = above 95%
C13 0.0 C13 0.0 C13 CorpWebSvr 3of5 250 1.2
C13 ExchangeServer WEST 350 1.7 C13 0.0 C13 0.0 Current by Breaker
Capacity Remaining
L1 31%
L2 9%
30.8 41.0 37.5 13.0 OK L3 17%
L1 Current (A) L2 Current (A) L3 Current (A) Total Power (kVA) Capacity Check
cannot exceed 45A cannot exceed 45A cannot exceed 45A cannot exceed 16.2kVA version 8
3-phase Capacity Planning Worksheet: 208V, 3phase / 60A (48A) per line 2016 Raritan Inc.
by Michael Suchoff and Henry Hsu;
Input Voltage
L1/L2 [XY] L2/L3 [YZ] L3/L1 [XZ] 208
typical = 208
Type Device Name Watts Amps Type Device Name Watts Amps Type Device Name Watts Amps
Circuit Breaker A (L1/L2) Circuit Breaker C (L2/L3) Circuit Breaker E (L3/L1) Power Factor
C13 0.0 C13 0.0 C13 CorpWebSvr 1of5 250 1.2 97.5%
C13 0.0 C13 48-port OOB Switch 275 1.4 C13 CorpWebSvr 2of5 250 1.2 typical = above 95%
C13 0.0 C13 0.0 C13 CorpWebSvr 3of5 250 1.2
C13 ExchangeServer WEST 350 1.7 C13 0.0 C13 0.0 Current by Breaker
Capacity Remaining
L1 36%
L2 15%
30.8 41.0 37.5 13.0 OK L3 22%
L1 Current (A) L2 Current (A) L3 Current (A) Total Power (kVA) Capacity Check
cannot exceed 48A cannot exceed 48A cannot exceed 48A cannot exceed 17.3kVA version 8