You are on page 1of 7

A Review of Recent HVDC Tapping Topologies

Abdelrahman Ismail M.S. Hamad Amr El Zawawi Emtethal Negm Abdallah


Electrical Engineering Dept. Electrical and Control Engineering Dept. Electrical Engineering Dept. Electrical Engineering Dept.
University of Alexandria Arab Academy for Science and Technology University of Alexandria University of Alexandria
Alexandria, Egypt Alexandria, Egypt Alexandria, Egypt Alexandria, Egypt
abdelrahman_ismail@alexu.edu.eg mostafa.hamad@staff.aast.edu amr.elzawawi@yahoo.com emtethal_1934@yahoo.com

Abstract HVDC power tapping has proven to be the absorbed by the tapping station. So, power tapped Ptap is
appropriate solution for rural AC networks. This tapping can be determined by [5]:
achieved by using series or parallel HVDC tap stations. But,
many researchers have faced some technical and economic issues
Ptap = Itap Vdc (1)
when designing tapping stations with small power ratings. In this
paper, many topologies of tapping converters are reviewed
focusing on their designs and providing pros and cons of each Where, Vdc is the voltage of the main HVDC system
topology.
Itap
Index Terms HVDC tapping, series tapping, parallel tapping,
shunt tapping. Vdc

I. INTRODUCTION
HVDC transmission systems have proved to be the most Load GS
beneficial alternative to transmit bulk electrical power over
long distances when compared to the conventional alternating
current (AC) systems. It also allow the transfer of power Fig. 2. Parallel tap
between unsynchronized AC networks [1]. Parallel taps are associated with higher power ratings than
Although HVDC transmission systems have distinguished series taps and the power of these taps are changed by varying
advantages, most of these systems are based on a point to point its dc current. Also these taps must withstand the full line
transmission scheme. In addition, most of HVDC transmission voltage, so high voltage switches will be used. In addition, it is
lines pass over rural cities which have a relatively weak AC limited to use parallel taps for small loads because the high
networks and have no access to any transmission system. So, voltage and low current ratings of load will lead to high
these cities must be economically supplied from an HDVC installation cost per kW. Unlike the voltage source converter-
system by using HVDC tapping stations [1]. based (VSC) HVDC links, power of the line-commutated
HVDC tapping stations must achieve the following converters-based (LCC) HVDC links is reversed by reversing
requirements [1-7]: it is typically rated as 1-10% of the HVDC the polarity of the DC voltage. This cant be achieved by
links capacity, it must be cost effective and reliable by not reversing current direction [8-10]. So, mechanical switching
affecting the main HVDC line at any fault and taps control arrangement is required when reversing power in the tap
system should not interfere with the main HVDC control station [1-3, 11-14].
system. In this paper, the main types of tapping stations shown Generally, parallel taps can be one of the two types shown
in fig. 1 are reviewed and discussed throughout the paper. in fig. 3 [2]. The single-stage converters are more traditional in
these taps using conventional fully voltage rated, three-phase
II. PARALLEL TAPPING DC/AC converter and a three-phase transformer. The two-stage
The parallel tap shown in fig. 2 will cause a reduction in converters which are known as the parallel-cascaded tapping
current of the main HVDC system by a value of Itap which is stations, step down the voltage using DC/DC converter. It is

HVDC Tapping

Parallel Series

Single-stage Two-stages TPLC-CSC FC-CSC-TOC SCCI CFCSC CFISC ST-HB-CT

FC-CSC-SCRs TPTB-AC-G SSCFC ST-I

FC-VSC DSW-VSCs CTL-VSCs MMC- POPT MMC-PCTT SCPT ST-FC-VSC CF-PWM-C

NPC-VSC CCSCs P-DC/DC-C MMC-SOPT MMC- SCTT GI-ACT MI I-ESE

Fig. 1. Classification of HVDC tapping stations

978-1-4673-9063-7/16/$31.00 2016 IEEE


beneficial to perform the DC/AC conversion at lower voltage. without the 3rd harmonics and transformer connection
It is also provided that multi-stage converters dont affect the limitations [11].
dynamic performance of the main HVDC link. Some
topologies of parallel taps are presented in the following
subsections. Vdc

2

+ +
HVDC AC HVDC AC
link link link link
- -
Vdc

(a) (b) 2

Fig. 3. Parallel tapping types (a) single-stage converters, (b) two-stage converters
Local AC network

A. Single-Stage Converters
1) Forced-Commutated, FC-VSC Fig. 6. NPC VSC
Parallel diodes in the converter shown in fig. 4 are used to
fix voltage polarity of the converter and allow reverse current. 4) Cascaded Current Source Converters (CSCs)
It is also protects GTOs from reverse voltage stresses. In This tap used large inductor to ensure constant current. This
square-wave operation, the converter voltage is constant and current flows through series-connected capacitor-commutated
reversing current direction will reverse power flow. But, valve switch modules shown in fig. 7 (b), inside blocks to ground
voltage stress is low while transient fault current is high. Pulse [15]. The ac outputs from blocks G1 till G4, are connected in
width modulation (PWM) provides independent control of ac parallel to the 110 kV ac bus as shown in fig. 7 (a). Each block
voltage at the expense of higher control power and higher contains three switch modules, one for each phase. The used
frequency harmonic content [11]. tap avoids issue of commutation failure. It provides
independent control of active and reactive power, minimum
switching loss, and lower cost due to lower number of
thyristors. No filters are needed as harmonics are reduced by
time shifts and zig-zag connected transformers. But, this tap
3-phase
requires mechanical switches to reverse current, and a neutral
Transformer grounding transformer for protection [16].
6-pulse, forced
commutated, VSC
Local AC network Itap Itap

Fig. 4. The FC-VSC topology


G1
Local
2) Dual Square-Wave VSCs G2
AC network Output

Independent control of reactive power through controlling


the ac voltage is provided by the converter shown in fig. 5. G3
Grounding
This is done by the phase shift between the two bridges. The Transformer
Itap
phase voltages in the primary side of the transformer contain G4

3rd harmonics. Although, delta-connected transformer has high (a) (b)


circulating current, zero-sequence harmonic currents pass to
the ac network in case of grounded-neutrals wye transformer. Fig. 7. Cascaded CSCs (a) taps design, (b) capacitor-commutated switch module
For higher number of pulses, transformer connections will have
restrictions[11]. 5) Cascaded Two-Level VSCs
The voltage source inverters (VSIs) shown in fig. 8 are
GTO connected in series from their input side. The output of each
VSI is connected to a step-down transformer. The
transformers output is connected in parallel to share load
current. The controller is used to inject the required amount of
active and reactive powers to the network. It must also keep
the input voltages to the voltage source inverters equal and the
output current sharing equal. This topology avoids the series
Local AC network connection of switches and operates at lower dv/dt. It also
replaces one high-voltage high-current transformer with lower
Fig. 5. Dual square-wave VSCs
voltage and currents transformers. In addition, it can be used
3) Neutral Point Clamped (NPC) VSC in VSC-based HVDC as well as LCC-based HVDC links. In
As shown in fig. 6, this converter offers the same LCC-based HVDC link, an H-bridge circuit is used on the tap
advantages as the dual square-wave VSCs in subsection b to reverse polarity of voltage [7].
3) MMC-Based, Series Output Pole Tap
C The converter shown in fig. 10 contains two phase legs
2-level VSI
connected in series. The midpoint of each phase leg is
C
connected to the low DC voltage terminal. The cell stacks have
the same function and problems as in the parallel pole but with
Local
2-level VSI
AC network lower power capacity ratio [2].
C

Cell
Cell

Cell
2-level VSI
Vdc1

C 2 Cell
Cell

2-level VSI
Cell

Vdc2
Fig. 8. Cascaded 2-level VSCs Cell
Vdc1 3-phase VSI
Cell
2 Local
B. Two-Stages Converters Cell AC network

1) Primitive DC/DC Converter-Based Parallel Tap +

Cell

Cell
Cell
In this topology, IGBT is used as the switching device in Half-bridge

the VSC. The dc/dc converter steps the HVDC voltage down Fig. 10. MMC-based, series output pole tap
to lower voltage. It may use one of the following three
configurations: resistive voltage divider, capacitive voltage 4) MMC-Based, Parallel-Connected Transformer Tap
divider and modified buck divider. The low efficiency and the This converter contains transformer. Its primary is
high cost due to the special insulated resistors used, made the connected between the midpoints of a single phase leg and the
resistive voltage divider infeasible for tapping. Also capacitive midpoint of split Vdc1 link capacitors as shown in fig. 11. Cell
voltage divider has the same design as the resistive voltage stacks do not suffer from energy drift. Increasing the frequency
divider by replacing the two resistors with two capacitors, it of the AC link leads to reduced size transformer and reduces
suffered from the problem of different charge and discharge the fluctuations in voltages which means smaller size
rates of capacitors. But, this problem is solved by using a capacitors. In case of DC faults in either DC link, transformer
resistance and high voltage rated switch in parallel with the prevents the propagation of fault to the other dc link. This
capacitor. For the modified buck converter, its configuration converter has a minimum power capacity ratio due to
was not shown due to patent applications [17, 18]. transformer-stage, so it can be used with higher dc voltage
transformation ratios [2].
2) MMC-Based, Parallel Output Pole Tap
This converter is VSC-based and considered a dc version of Cell
Cell
the MMC. Each phase leg consists of two cell stacks and its Vdc1

2 Cell
midpoint is connected to one of the terminals of the low
voltage side Vdc2 as shown in fig. 9. In addition to the cell Vdc2
stacks, arm inductors set the rate of change of stack currents.
Besides, cell stacks provide the voltages required to Vdc1
Cell
Diode
Rectifier
3-phase VSI

interconnect the DC terminals. The half-bridge cells which 2


Cell Local
AC network
make stacks do not possess reverse voltage capability, may
+

Cell

lead to short circuit on Vdc2 terminals through diodes due to a Half-bridge

fault on Vdc1 terminals. This circuit needs an AC rebalancing


Fig. 11. MMC-based, parallel-connected transformer tap
current to solve the problem of energy drift on cell stacks. This
solution adds to the voltage and current rating of the cell stack.
But, this converter has reasonable power capacity factor at low 5) MMC-Based, Series-Connected Transformer Tap
DC voltage transformation ratios (less than 2). So, it is not This converter consists of two cell stacks which apply a
suitable for tapping small amount of power from HVDC link square-wave voltage across the transformer shown in fig. 12. It
[2]. has the same advantages of the parallel-connected type, but
with higher power capacity ratio [2].
Cell Cell
Cell
Cell Cell +

Vdc1 Cell
Vdc1
2 Cell Cell
Half-bridge 2 Cell

Vdc2
Vdc2

3-phase VSI
Vdc1 Diode 3-phase VSI
Cell Cell Local Vdc1 Rectifier
2 AC network Cell
Cell Cell 2
Cell Local
Cell Cell + AC network
Cell

Half-bridge

Fig. 9. MMC-based, parallel output pole tap


Fig. 12. MMC-based, series-connected transformer tap
6) Switched-Capacitor Parallel Tap withstand the full current rating of the HVDC line [3, 11]. The
This topology consists of dc/dc converter and low-voltage small voltage across the tap means use of low voltage
VSC. The dc/dc converter arm contains a high-voltage valve, elements, but it must be insulated to the full voltage rating [2,
and number of series-connected cells which is used for a 4, 21]. Some topologies of series taps are presented in the
monopole HVDC system as shown in fig. 13. Three IGBT following subsections
switches and a capacitor exist in each cell. This dc/dc converter
is based on Marx generator concept as some of capacitors are A. Twelve-Pulse, Line-Commutated, LC-CSC
connected in parallel across low voltage source and in series LCC operates into two quadrants with lagging power factor
across high voltage source [19]. Its control is achieved by for the topology shown in fig. 15. Tap changer and firing angle
fixed commutation pattern. This tap offers great scalability and control provides independent control of reactive power by
lower voltage isolation requirements because the high voltage varying the ratio between ac voltage and dc voltage. But,
VSC is replaced by a dc/dc converter with reduced number of increasing the reactive power by increasing ac voltage needs
components. It doesnt also need complex transformer higher-voltage converter and snubber circuits. Efficiency also
arrangements. But, this tap is unable to reverse the voltage decreases at lower dc voltage operation. Therefore, such
polarity when connected to LCC-based HVDC link. It also converters are used in low power or back-to-back operation
provides fixed voltage transformation ratio [20]. [11].

LHv

HV
Valve

Cell 1

Cell 2

Cell 3
Local
AC network
Cell n
LLv Fig. 15. Twelve-pulse, line-commutated, CSC
C Local
AC network B. Forced-Commutated, FC-CSC Using SCRs
3-phase VSI Forced commutated converters as shown in fig. 16, can be
operated with leading power factor. Also, commutation
Fig. 13. Switched-capacitor parallel tap capacitors provide commutation even if in the case of negative
transformers line voltages. But, it adds to the cost of the
III. SERIES TAPPING converter. Independent control of reactive power is not
The series tap shown in fig. 14 will cause voltage drop Vtap, possible with this converter. Also, higher valve and transformer
so the power tapped Ptap can be obtained by (2) [5]: stresses and voltage distortion exists in this converter when
compared to LCC [11].
Ptap = Vtap Idc (2)
Where, Idc is the line current of the HVDC system.
Vtap
Idc

Local
AC network

Fig. 16. Forced-commutated, CSC using SCRs


Load GS

C. Forced-Commutated, FC-CSC with turn-off capability


Capacitors shown in fig. 17 provide a low impedance
Fig. 14. Series tap commutation path to minimize turn-off power. Gate turn-off
Series taps are typically associated with lower power thyristors (GTOs), MOS-controlled thyristors (MCTs) or
ratings than parallel taps, which means lower compensation for insulated-gate bipolar transistors (IGBTs) can be used which
the voltage of the HVDC system. The power of series tap is are connected in parallel to suite the small series taps. But,
changed by varying its dc voltage, not by varying line current. square-wave operation does not offer independent control of
This affects the voltage profile along the dc line. So it may reactive power. While PWM operation provides independent
increase the rectifier and inverter thyristor valve losses and control of reactive power. But, stresses on the valves and
stresses of the main HVDC stations. This taps must be able to filtering requirements increase [11].
G. Current-Fed Capacitor-Switched Converter
The series tap shown in fig. 20 consists of four thyristors,
two capacitors, a single-phase transformer, and a single-phase
to three-phase converter feeding local load. Two control
schemes were suggested, variable frequency and constant
Local frequency. In variable frequency control, high frequency usage
AC network
reduces size of capacitors leading to lower cost and smaller tap
Fig. 17. Forced-commutated, CSC with turn-off capability station. An air-core transformer is used to maintain coupling
between windings and to keep on low iron losses [1, 22, 23].
D. Twelve-Pulse Thyristor Bridge and AC Generator
This tap consists of a twelve-pulse bridge converter and a
DC machine. This machine is connected to the DC line to drive
an AC generator. This AC generator is used to commutate the
Thyristor Bridge and provide reactive power control. Also a 1-phase
transformer
power transformer is used to isolate between the DC line and
Rectifier
the AC network [21].
E. Series Capacitor Commutated Inverters
Inverter
The series tap shown in fig. 18, is based on series capacitor
commutated inverter employing two six-pulse bridges in series
with the dc line. No ac generator is required to provide reactive Local
power control and successful commutation. This tap isnt AC network

sensitive to AC disturbances [12].


Fig. 20. Current-fed capacitor-switched converter
1-phase line-
commutated CSCs
H. Soft-Switch Current-Fed Converter
The converter shown in fig. 21 consists of two self-
commutated switches (MCT or IGBT), two diodes and a
1-phase snubber capacitor Ch. The H-bridge can operate at higher
transformers
switching frequencies as 5 KHz because of the zero current
switching conditions at turn ON and zero voltage conditions at
Local
AC network
turn OFF. The output of the air-core transformer is stepped
down and rectified to a dc voltage to be inverted with a 50 Hz
Fig. 18. Series capacitor commutated inverters inverter. The control of dc/dc converter is adjusted by duty
F. Series Tap with FC- VSC cycle with constant frequency. But, duty cycle must be
The line-commutated, single phase CSC is used on the high between 0.15 and 0.4 to achieve efficient operation. Because
voltage side as shown in fig. 19. A single-phase transformer is power transfer becomes very low at duty cycle higher than 0.4
used for the conversion between high dc-voltage and ground, and soft switching capability is lost for duty cycle lower than
which is the most expensive item in the station. The converters 0.15 [22, 24].
connected after the transformer are FC-VSCs. The frequency
of the single-phase commutation voltage can be freely selected
considering harmonics generation, cost and losses of 1-phase
transformer
transformer and converters. The dc-stage makes it easy to Ch
connect a battery or some other energy storage element, which
might be required for starting up and during disturbances in
Rectifier
either the local ac-system or the main HVDC system. But,
losses are increased because of the two stages [6].
Local
Inverter
AC network

1-phase
transformer Fig. 21. Soft-switch current-fed converter
1-phase
forced-
commutated I. Current-Fed Inductor-Switched Converter
VSC
3-phase forced- In fig. 22, the dc link voltage of the line-commutated CSC
commutated
VSC is controlled by the firing angle. Inductance L2 is the
Local
commutating reactance and C1 and L1 form a filter to reduce
AC network
the noise fed to the main line. Frequency must be low (300-400
Fig. 19. Series tap with forced-commutated, VSC. Hz), due to the switching of very high current [22].
L1
b) Mechanical Isolation
C1
L2 As shown in fig. 25 (b), a current-to-voltage converter is
connected to a motor-generator drive system. The length of the
1-phase shaft and the insulating material must be sufficient to provide
transformer
required isolation. This tap can be connected directly to the
Rectifier
local AC network. Additional control for the generator must be
included if the generator must synchronize with an existing AC
Inverter
network. But this tap will need maintenance due to the
mechanical part. This topology uses only one power electronic
Local converter [3, 13].
AC network
c) Isolation with Energy Storage Elements
Fig. 22. Current-fed inductor-switched converter This topology consists of a current to voltage converter
J. Current-Fed PWM Chopper connected with an energy storage units shown in fig. 25 (c).
The current-fed PWM chopper shown in fig. 23 is series This energy storage allows the local AC network to function
connected with the line. The voltage of the dc capacitor during low or no current conditions on the HVDC link by
supplied to the inverter, is kept constant by varying the connection and disconnection of these units using switches
frequency of the PWM and the dc current level [11, 22]. SW. The energy storage units which may be sodium Sulphur
batteries or super capacitors, are used to provide isolation. It
has low e ciency and this storage units increase cost [3, 13].

6-pulse 6-pulse
inverter inverter 1-phase VSI

C1

C2

Local Rectifier
AC network

Fig. 23. Current-fed PWM chopper Inverter

K. Seris Tap with H-Bridge and Current Transformer (CT) Local

In the topology shown in fig. 24, the H-bridge is made (a) AC network

from IGBT switches which feeds the current transformer


through the diagonal of it. The switching pattern guarantee
continuity of the main current so as that current flow is not
interrupted at any time [22]. In addition, the voltage
3-phase VSI
disturbance is small with respect to the high voltage of the
HVDC lines. M

Local
AC network
(b)
Rectifier
Current
transformer
Inverter
1-phase VSC

Local
AC network

Fig. 24. Series tap with H-bridge and CT SW

L. Series Tap with Isolation Energy


storage

a) Galvanic Isolation with Air-Core Transformer 3-phase VSC


units

As shown in fig. 25 (a), the current to voltage converter Local

charges a capacitor C. The full bridge utilizes the capacitor as (c)


AC network

voltage source to excite the air-core transformer. A diode


Fig. 25. Series tap with isolation (a) galvanic isolation with air-core transformer,
rectifier is used to rectify the output of the transformer and (b) mechanical isolation and (c) isolation with energy storage element
filtered by a bus capacitor. So, the isolated dc voltage source
created, is connected to the inverter. The transformer is used to IV. CONCLUSION
provide galvanic isolation and it is resonantly driven by For the past few decades, HVDC tapping stations have
capacitors C1 and C2. This tap has high efficiency and best been a promising solution for the electrification of rural
switch utilization for some switches [3, 13]. networks. But, many designs of the previous tapping stations
were limited to the available technology and resources. Now, [12] H.M. Turanli, R.W. Menzies, and D.A. Woodford, A forced
commutated inverter as a small series tap on a DC line, IEEE
advances in converter technologies are heading to provide Transactions on Power Electronics, vol. 4, no. 2, pp. 187-193, April
higher power ratings converters. This makes HVDC tapping 1989.
stations more feasible economically and technically. So, [13] A. Hartshorne, H. du T. Mouton, and U.K. Madawala, An investigation
several topologies for series and parallel taps have been into series power tapping options of HVDC transmission lines, 1st
discussed with a brief explanation of their benefits and International Future Energy Electronics Conference, IFEEC13, pp. 568-
573, Nov. 2013.
drawbacks.
[14] R.L. Vaughan, J.P. Bowles, and J. Dalzell, The control and
I. REFERENCES performance of a series connected multiterminal HVDC transmission
system, IEEE Transactions on Power Apparatus and Systems, vol. 94,
[1] M. R. Aghaebrahimi and R.W. Menzies, Small power tapping from no. 5, pp. 1868-1877, Sept. 1975.
HVDC transmission systems: a novel approach, IEEE Transactions on
[15] K.P. Phillips, Current-source converter for AC motor drives, IEEE
Power Delivery, vol. 12, no. 4, pp. 1698-1703, Oct. 1997.
Transactions on Industry Applications, vol. IA-8, no.6, pp. 679-683,
[2] T. Lth, M. M. C. Merlin and, T. C. Green, Modular multilevel DC/DC Nov. 1972.
converter architectures for HVDC taps, 16th European Conference on
[16] Q. Hao and B.T. Ooi, Tap for classical HVDC based on multilevel
Power Electronics and Applications, (EPE'14-ECCE Europe), pp. 1-10,
current-source inverters, IEEE Transactions on Power Delivery, vol.
Aug. 2014.
25, no. 4, pp. 2626-2632, April 2010.
[3] A. Hartshorne, Investigation into a proposed HVDC series tap
[17] L. Chetty, N.M. Ijumba, and A.C. Britten, Parallel-cascaded tapping
topology, Diss. Stellenbosch University, 2016.
station, International Conference on Power System Technology,
[4] L. Chetty and N. Ijumba, Rural electrification using overhead HVDC PowerCon04, Vol. 2, pp. 1874-1879, Nov. 2004.
transmission lines, Journal of Energy in Southern Africa, vol. 23, no. 2,
[18] L. Chetty and N. Ijumba, Tapping small amounts of power from HVDC
pp. 56-64, May 2012.
transmission lines using parallel cascaded converters, 7th Africon
[5] A. F. Nnachi, J. Munda, D.V. Nicolae, and A. M. Mabwe, Coordination conference in Africa, vol. 2, pp. 691-696, Sept. 2004.
of multiple-power tapping from existing HVDC link, 15th International
[19] N.N. Lopatkin, G.S. Zinoviev, and L.G. Zotov, Bi-directional high-
Conference on Environment and Electrical Engineering, ICEEE15, pp.
voltage DC-DC-converter for advanced railway locomotives, IEEE
576-580, June 2015.
Energy Conversion Congress and Exposition, pp. 1123-1128, Sept.
[6] A. Ekstrom and P. Lamell, HVDC tapping station: power tapping from 2010.
a DC transmission line to a local AC network, International Conference
[20] J. Maneiro, S. Tennakoon and C. Barker, Scalable shunt connected
on AC and DC Power Transmission, pp. 126-131, Sept. 1991.
HVDC tap using the DC transformer concept, 16th European
[7] A. Elserougi, A.M. Massoud, A.S. Abdel-Khalik and S. Ahmed, A Conference on Power Electronics and Applications, (EPE'14-ECCE
grid-connected HVDC shunt tap based on series-input parallel-output Europe), pp. 1-10, Aug. 2014.
DC-AC multi-module 2-level voltage source converters, IEEE 8th
[21] J. Bowles, H. Nakra and A. Turner, A small series tap on an HVDC
GCC Conference and Exhibition, GCCCE15, pp. 1-5, Feb. 2015.
line, IEEE Transactions on Power Apparatus and Systems, vol. PAS-
[8] S. Shah, R. Hassan and J. Sun, HVDC transmission system 100, no.2, pp. 857-862, 1981.
architectures and control - A review, COMPEL, 2013 IEEE 14th
[22] D. V. Nicolae, A. A. Jimoh, J. F. J. van Rensburg, DC current source to
Workshop on, pp. 1-8, June 2013.
voltage source CT-based converter, International Aegean Conference
[9] F. Schettler, H. Huang and N. Christl, HVDC transmission systems on Electrical Machines and Power Electronics, ACEMP'07, pp. 665-670,
using voltage sourced converters design and applications, IEEE Power Sept. 2007.
Engineering Society Summer Meeting, vol. 2, pp. 715-720, July 2000.
[23] M.R. Aghaebrahimi and R.W. Menzies, A customized air-core
[10] T. Navpreet, et.al., Voltage source converters as the building block of transformer for a small power tapping station, IEEE Transactions on
HVDC and FACTS technology in power transmission system: a Power Delivery, vol. 13, no. 4, pp. 1265-1270, Oct. 1998.
simulation based approach, Advances in Applied Science Research,
[24] M. Aredes, C. Portela and F.C. Machado, A 25-MW soft-switching
vol. 3, no. 5, pp. 3263-3278, 2012.
HVDC tap for 500-kV transmission lines, IEEE Transactions on
[11] M. Bahram, et.al., Integration of small taps into (existing) HVDC Power Delivery, vol. 19, no. 4, pp. 1835-1842, Oct. 2004.
links, IEEE Transactions on Power Delivery, vol. 10, no. 3, pp. 1699-
1706, July 1995.

You might also like