You are on page 1of 29

Verification Samples

Simply Supported Floor Joist


1 Objective
To check the safety of using the (925PJ250-43mil, 50ksi) TSN PrimeJoist section for a simply
supported floor joist, given the following data:-

Floor joist is designed for [1.2 x Dead Load + 1.6 x Live Load], based on the AISI-NASPEC 2001 with
2004 supplement and in accordance with LRFD method.

Web-crippling check is considered, and the bearing length (N) = 4 in.

The section web is unreinforced along the joist span.

Joist span (L) = 12 ft.

Loads on floor joist are given in Table 1-1.

Table 1-1 Loads on Floor Joist


Load Value Units
Dead Load (IDL) 30 psf
Live Load (ILL) 50 psf

Joist spacing (S) = 24 in.

The top flange is fully braced against lateral and torsional buckling.

Lateral and torsional bracing are provided at midspan for bottom flange.

The deflection limit = L/ 360 (for live load)

= L/ 240 (for total load)

The maximum absolute deflection is 0.6 in.

Effect of the standard punch-out (4" X 1.5") is not considered.

Strength increase due to cold-work of forming is considered (if applicable).

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 1 of 29
2 Modeling with SteelSmart System

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 2 of 29
3 Statical System, Loads, and Design Forces
3.1 Statical System
The statical system of the floor can be shown in Fig. 3-1.

L = 12 ft

Figure 3-1 Statical System of the Floor

3.2 Loads
W Dead = Nominal dead load on floor joist (Fig. 3-2)

= IDL X S

= 30 * (24/ 12) = 60 lbs/ ft

WDead = 60 lbs/ ft

L = 12 ft

Figure 3-2 Nominal Dead load on Floor Joist (WDead)

W Live = Nominal live load on floor joist (Fig. 3-3)

= ILL X S

= 50 * (24/ 12) = 100 lbs/ ft

WLive = 100 lbs/ ft

L = 12 ft

Figure 3-3 Nominal Live load on Floor Joist (WLive)

WS = Factored load on floor joist for strength design (Fig. 3-4)

= 1.2W Dead + 1.6W Live

= (1.2 * 60) + (1.6 * 100) = 232 lbs/ ft

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 3 of 29
WS = 232 lbs/ ft

L = 12 ft

Figure 3-4 Factored Load on Floor Joist for Strength Design (WS)
W Total = Nominal total load on floor joist for deflection check (Fig. 3-5)

= W Dead + W Live

= 60 + 100 = 160 lbs/ ft

WTotal = 160 lbs/ ft

L = 12 ft

Figure 3-5 Nominal Total Load on Floor Joist for Deflection Check (WTotal)

3.3 Design Forces


Ry = Typical factored vertical reaction on floor joist supports (Fig. 3-6)

WSL
=
2

232 * 12
= = 1392 lbs = 1.392 kips
2

Ry = 1.392 kips Ry = 1.392 kips

Figure 3-6 Factored Vertical Reactions on Floor Joist Supports

Mx = Required flexural strength of the floor joist (factored moment) at mid span (Fig. 3-7)

W S L2
=
8

232 * (12)
2

= = 4176 lbs.ft = 50.112 Kips.in.


8

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 4 of 29
Mx = 50.112 Kips.in

Figure 3-7 Factored Bending Moment Diagram of the Floor Joist

Vy = Required shear strength of the floor joist (factored shear) at support (Fig. 3-8)

= Ry

= 1.392 kips

Vy = 1.392 Kips

Vy = 1.392 Kips

Figure 3-8 Factored Shear Force Diagram of the Floor Joist

Py = Required crippling force on the floor joist at support (Fig. 3-9)

= Ry

= 1.392 kips

Py = 1.392 kips Py = 1.392 kips

Figure 3-9 Factored Crippling Forces on the Floor Joist at Supports

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 5 of 29
4 Dimensioning
Symbols of the basic dimensions of the floor joist section can be shown in Fig. 4-1, and their
values are summarized in Table 4-1.

R d1

d2

Figure 4-1 Basic Dimensions Symbols of the Floor Joist Section


Table 4-1 Basic Dimensions of Floor Joist Section
Dimension Definition Value (in.)
D Out-to-out section depth 9.25
B Out-to-out flange width 2.5
d1 Out-to-out vertical lip width 0.6102
d2 Out-to-out horizontal lip width 0.5
R Inside bend radius 0.105
t Thickness of the section 0.0451

To calculate the section strength in flexural moment, shear, and web crippling; the section can be divided
into labeled elements as shown in Fig. 4-2.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 6 of 29
3

1'

2'

3'

Figure 4-2 Labeled Elements of the Section


The flat widths of the section elements (shown in Fig. 4-3) can be calculated as follows:

W1 = Flat width of Element (1)

= d2 (t + R)

= 0.5 (0.0451 + 0.105) = 0.3499 in.

W 1' = Flat width of Element (1')

= W 1 = 0.3499 in.

W2 = Flat width of Element (2)

= d1 2(t + R)

= 0.6102 2 * (0.0451 + 0.105) = 0.31 in.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 7 of 29
W 2' = Flat width of Element (2')

= W 2 = 0.31 in.

W3 = Flat width of Element (3)

= B 2(t + R)

= 2.5 2 * (0.0451 + 0.105) = 2.1998 in.

W 3' = Flat width of Element (3')

= W 3 = 2.1998 in.

W4 = Flat width of Element (4)

= D 2(t + R)

= 9.25 2 * (0.0451 + 0.105) = 8.9498 in.


W
3
W2

W
1

W4

W1'
W
2'

W
3'

Figure 4-3 Flat Widths of Section Elements

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 8 of 29
5 Strength Check
5.1 Flexural Moment (Mx)
The major flexural strength of the floor joist member is the least of:

a) The strength at initiation of cross-section yielding.

b) The strength for lateral-torsional buckling.

Since the compression flange of the section is fully braced, the lateral-torsional buckling won't occur; and
the flexural strength is equal to the strength at initiation of cross-section yielding calculated in accordance
with Section C3.1.1 in the 2001 specification.

The effective properties of the section can be calculated by loading the section by a stress gradient
(tension-compression) which has the value of the yielding stress (Fy) at the extreme compression fiber of
the section (Fig. 5-1).

3 Fy
f3
f 2 and f 1-4
2

Ycg0= 4.625 in.

Mx
4 N.A.

1'

2'
f 2-4

3'

Figure 5-1 Initial Position of Neutral Axis and Stress Distribution on the Full Unreduced Section at
Initiation of Yielding

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 9 of 29
Iteration (1)

The section is assumed to be fully effective, i.e. the neutral axis (N.A.) is assumed located at a distance
equal to half the section depth, measured from the extreme compression fiber of the section towards the
tension flange (Fig. 5-1).

5.1.1 Effective Area Calculation


5.1.1.1 Element (1) and Element (2)
Element (1) can be classified as a uniformly compressed unstiffened element, thus, the
effective width of W 1 can be calculated in accordance with section B3.1 (a) in the 2001 specification as
follows:

K1 = 0.43

f1 = Compression stress at the centerline of W 1 (Fig. 5-1)

Ycgo d1 + 0.5t
= Fy
Ycgo

4.625 0.6102 + 0.5 * 0.0451


= * 50 = 43.64703 ksi
4.625
2
2E t
Fcr1 = K1 (Eq. B2.1-5)
2 W
12 (1 ) 1

2
2 * 29500 0.0451
= 0.43 * = 190.4727 ksi
12 (1 0.3 2 ) 0.3499

f1
1 = (Eq. B2.1-4)
Fcr1

43.64703
= = 0.4787 < 0.673
190.4727

d'1 = Effective width of (W 1)

= W1 (Eq. B2.1-1)

= 0.3499 in.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 10 of 29
Element (2) can be classified as a uniformly compressed element with an edge stiffener, where its
stiffener is Element (1); thus; the effective width of W 2 and the reduced effective width of W 1 can be
calculated in accordance with Section B4.2 in the 2001 specification as follows:

f2 = Compression stress at the top end of W 2 (Fig. 5-1)

Ycgo t R
= Fy
Y
cgo

4.625 0.0451 0.105


= * 50 = 48.3773 ksi
4.625

S = 1.28 E f2 (Eq. B4-1)

= 1.28 29500 48.3773 = 31.60823

W 2/ t = 0.31/ 0.0451 = 6.87361 < (0.328S = 10.36749963)

b2 = Effective width of W 2

= W2 (Eq. B4.2-1)

= 0.31 in.

b1-2 = b2/ 2 (Eq. B4.2-2)

= 0.31/ 2 = 0.155 in.

b2-2 = b2/ 2 (Eq. B4.2-2)

= 0.31/ 2 = 0.155 in.


d1 = Reduced effective width of (W 1)

= d1 (Eq. B4.2-3)

= 0.3499 in.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 11 of 29
5.1.1.2 Element (3) and the L-shape lip
Element (3) can be classified as a uniformly compressed element with an edge stiffener, where
its stiffener is the L-shape lip; thus; the effective width of W 3 and the reduced effective width of each flat
part of the L-shape lip can be calculated in accordance with Section B4.2 in the 2001 specification as
follows:

f3 = Compression stress at the centerline of W 3 (Fig. 5-1)

Ycgo 0.5t
= Fy
Y
cgo

4.625 0.5 * 0.0451


= * 50 = 49.75622 ksi
4.625

S1 = 1.28 E f 3 (Eq. B4-1)

= 1.28 29500 49.75622 = 31.16716

W 3/ t = 2.1998/ 0.0451 = 48.77605 > (0.328S1 = 10.2228297)

Rmean = R + 0.5t

= 0.105 + 0.5 * 0.0451 = 0.12755 in.

First moment of area of the L - shape lip parts


Y =
Total area of the L shape lip

= Distance from the bottom fiber of W 1 to the horizontal centroidal axis of the full unreduced L-
shape lip (the centroidal axis parallel to the longitudinal axis of the flange), as shown in (Fig. 5-2)

t [0.5tW1 + 1.57R mean (0.5t + 0.363R mean ) + W 2 (0.5W 2 + t + R)]


=
t [W1 + 1.57R mean + W 2 ]

= 0.5 * 0.0451 * 0.3499 + 1.57 * 0.12755(0.5 * 0.0451 + 0.363 * 0.12755) + 0.31(0.5 * 0.31 + 0.0451 + 0.105)
(0.3499 + 1.57 * 0.12755 + 0.31)

= 0.135161 in.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 12 of 29
3

2
Lip Neutral-Axis

Y = 0.135161 in. 1
Figure 5-2 Position of Horizontal Centroidal Axis of L-Shape Lip

= tW1 ( Y 0.5t ) 2 + 0.149 t (R mean ) + 1.57R mean t (Y 0.5t 0.363R mean ) +


3 2
Is-TL

t (W 2 ) 12 + tW 2 (t + R + 0.5 W 2 Y )
3 2

= 0.0451 * 0.3499(0.135161 0.5 * 0.0451)2 + 0.149 * 0.0451(0.12755)3 +

1.57 * 0.12755 * 0.0451 * (0.135161 0.5 * 0.0451 0.363 * 0.12755)2 +

0.0451(0.31)3 12 + 0.0451 * 0.31(0.0451 + 0.105 + 0.5 * 0.31 0.135161)2


-4 4
= 7.695 * 10 in.

3
4 W3 t
Ia = 399 t 0.328 (Eq. B4.2-10)
S1

3
4 48.77605
= 399 (0.0451) 0.328 = 3.124419 * 10 in.
-3 4

31.16716

W t
Ia-max = t 4 115 3 + 5
S1

4
= (0.0451) 115 *
48.77605
+ 5 = 7.652694 * 10 in. < Ia
-4 4
take Ia = Ia-max
31.16716

Is TL
RI = (Eq. B4.2-9)
Ia

7.695 * 10 -4
= = 1.00553 > 1.0 take RI = 1.0
7.652694 * 10 -4

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 13 of 29
W t
n = 0.582 3 (Eq. B4.2-11)
4S 1

48.77605
= 0.582 = 0.1907545 < (1/3) take n = 1/3
4 * 31.16716

Using Table B4.2 in the 2001 specification;


n
K3 = 3.57(RI) + 0.43 (Other Edge Stiffener Shapes)
0.333
= 3.57(1) + 0.43

= 4 (the upper limit)

2
2E t
Fcr3 = K3 (Eq. B2.1-5)
2 W
12 (1 ) 3

2
2 * 29500 0.0451
= 4* = 44.82763 ksi
12 (1 0.3 2 ) 2.1998

f3
3 = (Eq. B2.1-4)
Fcr 3

49.75622
= = 1.053539 > 0.673
44.82763

3 = (1 0.22 3 ) 3 (Eq. B2.1-3)

= (1 0.22 1.053539 ) 1.053539 = 0.7509734

b3 = Effective width of W 3

= 3W 3 (Eq. B2.1-2)

= 0.7509734 * 2.1998 = 1.651991 in.

b1-3 = (b3/ 2)RI (Eq. B4.2-5)

= (1.651991/ 2) * 1 = 0.8259955 in.

b2-3 = b3 b1-3 (Eq. B4.2-6)

= 1.651991 0.8259955 = 0.8259955 in.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 14 of 29
The reduced values of the effective parts b1-2, b2-2, and d1 can be calculated as follows:

b1-2* = Reduced width of b1-2

= b1-2RI

= 0.155 * 1 = 0.155 in.

b2-2* = Reduced width of b2-2

= b2-2RI

= 0.155 * 1 = 0.155 in.

d1* = Reduced width of d1

= d1RI

= 0.3499 * 1 = 0.3499 in.

The removed lengths from elements (1), (2), and (3) for this iteration can then be calculated as follows:

Rem1 = Removed width of W 1 due to local buckling

= W 1 d1*

= 0.3499 0.3499 = 0

Rem2 = Removed width of W 2 due to local buckling

= W 2 (b1-2* + b2-2*)

= 0.31 (0.155 + 0.155) = 0

Rem3 = Removed width of W 3 due to local buckling

= W 3 (b1-3 + b2-3)

= 2.1998 (0.8259955 + 0.8259955) = 0.547809 in.

The effective parts of W 1, W 2, and W 3 can be shown in Fig. 5-3.

b 2-3 b1-3

b1-2*
b 2-2*
d 1*
Figure 5-3 Effective Parts of W1, W2, and W3

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 15 of 29
5.1.1.3 Element (4)
Element (4) can be classified as a stiffened element under stress gradient (tension-
compression), thus, the effective width of W 4 can be calculated in accordance with section B2.3 (a) in the
2001 specification as follows:

f1-4 = Compression stress at the top end of W 4 (Fig. 5-1)

Ycgo t R
= Fy
Ycgo

4.625 0.0451 0.105


= * 50 = 48.3773 ksi
4.625

f2-4 = Tensile stress at the bottom end of W 4 (Fig. 5-1)

D Ycgo t R
= - Fy
Ycgo

9.25 4.625 0.0451 0.105


= - * 50 = -48.3773 ksi
4.625

4 = |f2-4/ f1-4| (Eq. B2.3-1)

= |-48.3773/ 48.3773| = 1

= 4 + 2(1 + ) + 2(1 + )
3
K4 (Eq. B2.3-2)
3
= 4 + 2(1 + 1) + 2(1 + 1) = 24

2
2E t
Fcr4 = K4 (Eq. B2.1-5)
2 W
12 (1 ) 4

2
2 * 29500 0.0451
= 24 * = 16.24938 ksi
12 (1 0.3 2 ) 8.9498

f1 4
4 = (Eq. B2.1-4)
Fcr 4

48.3773
= = 1.72545 > 0.673
16.24938

4 = (1 0.22 4 ) 4 (Eq. B2.1-3)

= (1 0.22 1.72545 ) 1.72545 = 0.5056634

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 16 of 29
b4 = Effective width of W 4

= 4W 4 (Eq. B2.1-2)

= 0.5056634 * 8.9498 = 4.525587 in.

D/ B = 9.25/ 2.5 = 3.7 < 4.0

b1-4 = b4/ (3 + 4) (Eq. B2.3-3)

= 4.525587/ (3 + 1) = 1.131397 in.

4 > 0.236
b2-4 = b4/ 2 (Eq. B2.3-4)

= 4.525587/ 2 = 2.262793 in.

b1-4 + b2-4 = Summation of the effective parts of Element (4)

= 1.131397 + 2.262793 = 3.39419 in.

Lwc = Flat portion of the web lying in compression zone

= D Ycg0 t R

= 9.25 4.625 0.0451 0.105 = 4.4749 in. > (b1-4 + b2-4)

Rem4 = Removed width from Lwc due to local buckling

= Lwc (b1-4 + b2-4)

= 4.4749 3.39419 = 1.08071 in.

The effective parts of the W 4 can be shown in Fig. 5-4.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 17 of 29
b1-4

b 2-4

N.A.

Figure 5-4 Effective Parts of W4

5.1.1.4 Effective area


Considering the parts lying in tension zone and the corners are fully effective, the effective
area of the section in flexural moment (Mx) can be calculated as follows:

Remt = Total removed length of the section due to local buckling

= Rem1 + Rem2 + Rem3 + Rem4

= 0 + 0 + 0.547809 + 1.08071 = 1.628519 in.

Ae = Effective area of the section

= Ag (Remt * t), where Ag is the gross area of the section


2
= 0.715741 (1.628519 * 0.0451) = 0.642295 in.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 18 of 29
5.1.2 Effective Section Modulus @ Major Axis
To calculate the effective section modulus of the section @ its major axis, we have firstly to
determine the neutral axis position of the effective section as follows:

Ycg1 = Neutral axis position of the effective section after Iteration 1, measured from the extreme
compression fiber towards the tension flange

n
= A i Xi Ae
i=1

Where,

Ai = Effective area of a part the section includes.

Xi = Distance between the centroid of the part and the extreme compression fiber of the section.

Ycg1 = 5.0145447 in. > (Ycg0 = 4.625 in.), (calculations are not shown).

cg1 = Ycg1 Ycg0

= 5.0145447 4.625 = 0.3895447 in.

Since cg1 has a significant value, iterations must be continued till cg becomes 0.0. This condition was
verified by doing eight more iterations, and the final value of Ycg was found equal to 5.1568252 in. (Fig. 5-
5).

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 19 of 29
3 Fy
f3
f 2 and f 1-4
2

Y cg= 5.1568252 in.

Mx 4
N.A.

1'

2'
f 2-4

3'

Figure 5-5 Final Position of Neutral Axis and Stress Distribution on the Effective Section at
Initiation of Yielding

The effective moment of inertia of the section @ its major axis (Ixe) can be calculated based on the final
4 4
position of the neutral axis, and was found = 7.752765 in. < (Ixg = 8.98444 in. ); where Ixg is the gross
moment of inertia @ major axis (calculations are not shown).

Sxe = Effective section modulus of the section relative to extreme compression fiber

= Ixe/ Ycg
3
= 7.752765/ 5.1568252 = 1.5033988 in.

5.1.3 Strength Increase due to Cold-Work of Forming


Since the quantities 3 and 4 are less than unity and the web is not fully effective, the yield
strength increase due to cold-work of forming; discussed in Section A7.2; won't be applicable.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 20 of 29
5.1.4 Flexural Strength Determination and Check of Safety
Mnx = Nominal major flexural strength of the member

= SxeFy (Eq. C3.1.1-1)

= 1.5033988 * 50 = 75.16994 kips.in.

Mx-all = Allowable major flexural strength of the member

= bMnxo

= 0.95 * 75.16994 = 71.41144 kips.in. > ( Mx = 50.112 kips.in.) Safe

Act/ All = Mx / Mx-all

= 50.112/ 71.41144 = 0.7017

5.2 Shear (Vy)


The shear strength of the section can be determined in accordance with Section C3.2.1 in the
2001 specification as discussed in the sections to follow.

5.2.1 Calculation of the Nominal Shear Stress (Fv)


h = Flat portion of the web

= W4

= 8.9498 in.

h/ t = 8.9498 / 0.0451 = 198.443459

Web is unreinforced Kv = shear buckling coefficient = 5.34.

EK v Fy = 29500 * 5.34 50 = 56.1302058

(h/ t) > ( 1.51 EK v Fy = 84.756612)

Fv = Nominal shear stress

= 0.904 EK v (h t )
2
(Eq. C3.2.1-4)

= 0.904 * 29500 * 5.34 (198.443459 )2 = 3.616248 ksi

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 21 of 29
5.2.2 Calculation of the Shear Resisting Area (Aw)
Aw = Area of web resisting shear

= ht
2
= 8.9498 * 0.0451 = 0.4036359 in.

5.2.3 Shear Strength Determination and Check of Safety


Vny = Nominal shear strength of the section

= A wF v (Eq. C3.2.1-1)

= 0.4036359 * 3.616248 = 1.459648 Kips

Vy-all = Allowable shear strength of the section

= vVny

= 0.95 * 1.459648 = 1.3867 kips < ( Vy = 1.392 kips) unsafe

Act/ All = Vy / Vy-all

= 1.392/ 1.3867 = 1.0038

5.3 Web-Crippling (Py)


The web-crippling must be checked, in accordance with Section C3.4.1 in the 2001 specification,
for the typical support reaction (case of End, One-Flange Loading) as follows:

Pny = Nominal web-crippling strength

R N h
= Ct 2 Fy Sin1 C R 1 + CN 1 Ch (Eq. C3.4.1-1)
t t t

0.105 4 8.9498
= 4 * (0.0451) * 50 * Sin901 0.14
2
1 + 0.35 1 0.02
0.0451 0.0451 0.0451

= 0.9871449 kips

Py-all = Allowable web-crippling strength

= wPny

= 0.85 * 0.9871449 = 0.8391 kips < ( Py = 1.392 kips) unsafe

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 22 of 29
Act/ All = Py / Py-all

= 1.392/ 0.8391 = 1.6589

5.4 Combined (Mx) and (Vy)


The critical combined corresponding values of bending moment (Mx) and shear force (Vy) were
found at left support (X/ L = 0/ 12 = 0), and can be checked in accordance with Section C3.3.2 in the
2004 supplement as follows:-

2 2
Mx Vy

M + V
1
Interaction = (Eq. C3.3.2-1)
b nxo v ny

2 2
0 1.392
= + = 1.0038 > (Upper Limit = 1.0) unsafe
71.41144 1.3867

Act/ All = Interaction/ Upper Limit

= 1.0038/ 1 = 1.0038

6 Serviceability Check
6.1 Total Load Deflection (Total)
The maximum actual deflection (act-Total) is at the mid span of the floor joist, and can be calculated
using the effective major moment of inertia (Ixe) and W Total as follows:

5 WTotalL4
act-Total =
384 EIxe

5 (160 12000) * (12 * 12)


4
= = 0.2963 in.
384 29500 * 8.5392

all-Total = Maximum allowed deflection for total load

= L/ 240

= (12 * 12)/ 240 = 0.60 in. > act-Total safe

Act/ All = act-Total/ all-Total

= 0.2963/ 0.60 = 0.4939

1
Supplement 2004 to the NASPEC-AISI 2001 for the Design of Cold-Formed Steel Structural Members

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 23 of 29
6.2 Live Load Deflection (Live)
The maximum actual deflection (act-Live) is at the mid span of the floor joist, and can be calculated
using the effective major moment of inertia (Ixe) and W Live as follows:

5 WLiveL4
act-Live =
384 EIxe

5 (100 12000) * (12 * 12)


4
= = 0.1852 in.
384 29500 * 8.5392

all-Live = Maximum allowed deflection for live load

= L/ 360

= (12 * 12)/ 360 = 0.40 in. > act-Live safe

Act/ All = act-Live/ all-Live

= 0.1852/ 0.40 = 0.4630

7 Conclusion
It is unsafe to use a (925PJ250-43mil, 50Ksi) section as a joist for this floor.

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 24 of 29
8 Verification of SteelSmart System
8.1 Forces and Deflection Diagrams
8.1.1 Bending Moment Diagram (kips.in.)

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 25 of 29
8.1.2 Shear Force Diagram (kips)

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 26 of 29
8.1.3 Deflection Diagram for Total Load (in.)

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 27 of 29
8.1.4 Deflection Diagram for Live load (in.)

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 28 of 29
8.2 Output

Simply Supported Floor Joist SteelSmart System 7.0 SP2


Page 29 of 29

You might also like