3TL Vacuum Contactors Medium-Voltage
Equipment

3TL Vacuum Contactors


General Description
1
3TL8 Vacuum Contactors
as Economy Contactors
2
3TL6 Vacuum Contactors
as Universal Contactors
3
Appendix
Catalog Index
Conditions of Sale and Delivery
A

Catalog HG 11.21 1997


Supersedes: Catalog HG 11 1991, Section 4 Siemens AG 1997
3TL
Vacuum Contactors

3TL vacuum contactors (selection)

3TL8
vacuum contactors
as economy
contactors up to
7.2 kV / 400 A

R-HG11-084 eps

3TL6
vacuum contactors
as universal
contactors up to
12 kV / 450 A

Excavator 292 of Rheinbraun AG

Features

Quality standard
DIN EN ISO 9001
3TL vacuum contactors are
routine tested to specifications
that go beyond those laid down
R-HG11-085 eps

by the relevant standards:


Continuous testing during the
manufacturing processes
Several operating cycles per
routine test
Current measured-value ac-
quisition such as, for
example, operating speed
and contact travel com-
pared with the values from
the long-term tests

Other features:
Stable measured values with
tight tolerances
Low power loss
Constant long-term thermal
stability.

0/2Siemens HG 11.21 1997


3TL
Vacuum Contactors
General Description

R-HG11-086 eps
R-HG11-087 eps

Contents Page

Environmental Freedom from Application,


compatibility maintenance fields of application 1/2

DIN EN ISO 14001 3TL vacuum contactors Switching duties,


3TL vacuum contactors are are maintenance-free cases of application 1/2 1/4

Environmentally compa- Under normal


ambient conditions in Technical specifications
tible with respect to the in comparison 1/5
materials used and manu- line with IEC 694
facturing processes and DIN VDE 0670
Part 1000 in the Construction principle
Environment-neutral with temperature range in comparison 1/6
respect to how they stated (see page 1/8)
operate and during Vacuum interrupter 1/7
switching operations Through to the end
of the vacuum inter- Standards 1/8
Simple to dispose of at rupters service life.
the end of their service
life.

Siemens 8BK30 medium-


voltage withdrawable switch-
gear with 3TL6 vacuum
contactor on central truck

Siemens HG 11.21 19971/1


3TL 3TL Vacuum Contactors
Vacuum Contactors
General Description

Application Fields of application

3TL vacuum contactors are


Application, For operating Vacuum Mechanical Application
3-pole contactors with solenoid- switching voltage and contactor operating examples
operated mechanism for of loads normal current type cycles
medium-voltage switchgear
systems. Medium-voltage up to 7.2 kV 3TL8 1 mill. Conveyor and lift
They are load-break switchgear three-phase motors up to 400 A systems, compressors,
pump stations, ventilation
with a limited short-circuit M 3TL6 3 mill. and heating
up to 12 kV
making and short-circuit break- 3~
up to 450 A
ing capacity and are used for
high switching frequencies
(> 10,000 operating cycles).
Transformers up to 7.2 kV 3TL8 1 mill. Secondary distribution
The vacuum contactors are up to 400 A switchgear, industrial
suitable for the operational network distribution
switching of AC loads in indoor up to 12 kV 3TL6 3 mill. systems

1 systems and can perform, for


example, the following switch-
ing duties:
up to 450 A

Industrial network
Switching of three-phase Reactors up to 7.2 kV 3TL8 1 mill. distribution systems,
up to 400 A
motors in AC-3 and AC-4 DC link reactors,
operation reactive-power compen-
up to 12 kV 3TL6 3 mill. sation systems
Switching of transformers up to 450 A

Switching of reactors
Switching of ohmic loads Ohmic up to 7.2 kV 3TL8 1 mill. Heating resistors
(e. g. arc furnaces) loads up to 400 A
Switching of capacitors 3TL6 3 mill. Arc furnaces
up to 12 kV
up to 450 A
With reversing contactor combi-
nations, only one contactor is
required for each direction of
rotation, if HV HRC fuses are Capacitors up to 7.2 kV 3TL8 1 mill. Reactive-power
HG11-2278 eps

up to 250 A
used for short-circuit protection. compensation systems,
capacitor banks
up to 12 kV 3TL6 3 mill.
Application examples up to 250 A
Conveyor and lift systems
Pump stations
Ventilation and heating
Systems for reactive-power Switching duties Switchgear used with vacuum contactors
compensation

for the following branches of Cases of switching line


industry: and load-side operating states
Mining Switching Unloaded transformers
inductive (neutral earthing transformers) Switch-
Steel circuits
Loaded transformers HV HRC Circuit- discon-
Gas and petrochemicals fuses breaker nector
Overloaded transformers with
Paper Transformers in rush HV HRC
Cement fuses
Furnace transformers
Motors normally operating
Versions
Motors starting up Vacuum contactor
3TL8 vacuum contactors
as economy contactors Switching Capacitors
Up to 1 mill. mechanical capacitive Surge arrester
Back-to-back switching of capacitors
circuits
operating cycles
Up to 7.2 kV Switching on Fault making 1)
short-circuit
Locked motor rotor
3TL6 vacuum contactors
HG11-2279b eps

as universal contactors Switching Fault on the line side:


under earth- unloaded cables, overhead lines Load
Up to 3 mill. mechanical
fault conditions loaded cables, overhead lines
operating cycles
Up to 12 kV Fault on the load side:
unloaded cables, overhead lines
loaded cables, overhead lines

1) Limited fault breaking capacity.

1/2Siemens HG 11.21 1997


3TL Vacuum Contactors 3TL-
Vacuum Contactors-
General Description

Switching duties, cases of application

Switching of motors
3TL vacuum contactors are Motor version (insulation) Operating mode
particularly suitable for the modern insulation system Older design or unknown
frequent switching of motors. insulation level
As the chopping current of
the contactors is 5 A, no im- Switching of

HG11-2281a eps
permissibly high overvoltages U1 V1 W1
started-up motors
U1 V1 W1
occur in the operational
switching of started-up motors. M M
If, however, high-voltage 3~ 3~
motors with a starting current
of 600 A are switched off
during start-up, overvoltages
may occur. The level of these
overvoltages can be reduced 1 1 Occasional switching of
to safe values by means of
special surge limiters (see
Catalog HG 21 Overvoltage
Protection, catalog section: U1 V1 W1 U1 V1 W1
motors just started-up
(on fault)
1
Type 3EF Surge Limiters). M M
The 3EF surge limiters are pref- 3~ 3~
erably arranged in the cable
termination compartment paral-
lel to the cable sealing end. 1 2 Frequent switching
The surge limiters are made up during AC-4 operation
of non-linear discharge resis- -R
tors (SIOV metal-oxide varis- U1 V1 W1 U1 V1 W1
tors) and a series-connected
spark gap. M M -C
3~ 3~
Care must be taken during
installation that for mechanical
reasons the surge limiter is
connected flexibly on one side. 1 With surge limiter
2 With surge limiter and additional RC circuit
Utilization categories
Circuit examples for overvoltage protection for three-phase motors with starting current 600 A
Utilization Typical
categories applications
AC-3 Squirrel-cage motors: Overvoltage protection Overvoltage protection Switching of transformers
starting, de-energizing
while running
by means of limiters by means of RC circuit In case of switching of induc-
AC-4 Squirrel-cage motors: Overvoltages can be caused by The following guide values tive currents, current chopping
starting, braking by multiple re-ignition in the first apply to components of the RC at the contact gap may give
plugging 1), pole to clear or virtual current circuit: rise to overvoltages. However
reversing 1), jogging 2) chopping in the last pole to Capa- 0.25 F per phase, due to the special contact
1) The terms braking by plugging clear, for example when switch- citor C protective capacitor material used in 3TL contac-
and reversing of the motor refer ing stalled motors or motors in version tors, the chopping current is
to rapid braking or reversing of the the course of start-up. limited to 5 A. This means
direction of rotation by swapping Resis- 30 to 50 that no dangerous overvoltages
over two supply wires while the Those components endanger- tor R 100 W per phase,
ed are the input windings of develop when unloaded trans-
motor is running. low-inductance
squirrel-cage and slip-ring formers are switched off.
2) Jogging refers to one-off or version
repeated brief energizing of a motors with a starting current
motor in order to actuate small of 600 A. Siemens must be contacted to
movements of machines. ensure perfect configuration of Switching of capacitors
Surge limiters assure positive the RC circuit to suit the type
protection against overvoltage; 3TL vacuum contactors can, at
of attachment and cable length rated voltages of up to 7.2 kV,
see above for circuit examples. (see above for circuit cut off capacitive currents of
examples). up to 250 A without restrike
If voltage tests are carried out and therefore without over-
on the motor, the RC circuit voltages.
and surge limiters must be When the rated voltage is
disconnected to prevent them 12 kV, 3EF surge limiters must
from becoming damaged. be used (see Catalog HG 21
When used in conjunction with Overvoltage Protection,
withdrawable-type vacuum catalog section: Type 3EF
contactors, the RC circuit must Surge Limiters).
be constructed separately.

Siemens HG 11.21 19971/3


3TL 3TL Vacuum Contactors
Vacuum Contactors
General Description

Switching duties, cases of application

Short-circuit protection Short-circuit protection for


3
The 3TL vacuum contactors are Class E2 controller in ac- 10
cordance with UL 347 / CSA s
not designed to switch short- 5 125 A
circuit currents. It is therefore C22.2
2 2

Time t
absolutely essential to provide When using 3TL vacuum con- 2
short-circuit protection. tactors as Class E2 control- 10

The best protection is provided lers for 7.2 kV, Siemens fuses 5
of type 3GD1 150-UD (7.2 kV/ B
by HV HRC fuses, but circuit- 2
breakers can also be used sub- 250 A) or other fuses with a
1
ject to the conditions described comparable current/time curve 10
must be used to provide short- 3
in short-circuit protection by 5 A
means of circuit-breakers on circuit protection.
2
this page. If 2 fuse links are connected in 0
10
parallel, the symmetrical short- 1
Short-circuit protection by circuit current measured is 5

1 means of HV HRC fuses


HV HRC fuses have a current-
limiting effect with high short-
divided by 2 and this value used
to determine the cut-off current
for one fuse link. This value
2
10
-1 4
must then be multiplied by 2 in

HG11-2280b eps
circuit currents, i.e. the fuse 5
limits the short-circuit current order to arrive at the total cut-
2
to the cut-off current. off current, which must not -2
exceed the permissible value 10 2 3
When the fuses are selected, 10 2 5 10 2 A 5
for the vacuum contactor.
the type of load must be taken Sustained short-circuit AC current (r.m.s. value) IK
into account, for example, mo- Parallel connection should be
tor, transformer or capacitors. configured such that the 1 Characteristic curve of HV HRC fuse 3GD1125-4D
resistance in the two branches 2 Characteristic curve of maximum-current/time protection device
For an example of coordination is, if possible, identical. 3 Motor starting time
of an HV HRC fuse with
When the fuses blow, this must 4 Motor starting current
overcurrent-time protection,
see the chart on the right. result in the vacuum contactor
being opened. An appropriate Coordination of the motor circuit components:
device that is actuated by The time/current curve must lie to the right of the motor starting
Requirements current (point A )
the release bolt of the HV HRC
The cut-off current ID must fuse link must be installed. The rated current of the HV HRC fuse link must exceed the normal
not exceed 50 kA at 7.2 kV. current of the motor.
The current that prevails at the point of intersection B of the HV
With an LV power supply via Fuse monitoring HRC fuse links curve and the curve of the maximum-current/time
a control power transformer, The fuse bases can be supplied protection device must be greater than the lowest breaking
short-circuit currents must be with a fuse monitor in order to current of the HV HRC fuse link.
interrupted between the If this cannot be achieved, make sure that overload currents lower
prevent a three-phase load (e.g. than the lowest breaking current of the HV HRC fuse link are cut
switching capacity limit (5 kA) a motor) from being supplied off by the switchgear by means of the striker. This prevents
and 30 x Ir (12 kA) within on only two phases when a thermal overloading of the HV HRC fuse link, which would
80 ms. This stipulation does fuse blows. This fuse monitor otherwise destroy it.
not apply if can be used either to initiate an The HV HRC fuse link selected limits the sustained short-circuit
there is mechanical latching or alarm signal or to open the AC current IK to the cut-off current ID which must be taken from
the opening times have been vacuum contactor. the peak let-through current chart (for ID as a factor of IK for the
extended so much that in HV HRC fuse links of different rated currents, see Catalog HG 12
the above-mentioned current Switch-Disconnectors, Vacuum Switches, High-Voltage HRC
Short-circuit protection by Fuses). The maximum permissible cut-off current ID = 50 kA.
range the contactor cannot means of circuit-breakers
open until the fuse has inter-
rupted the current. Loads for which no suitable
fuses are available can also be
For further specifications, see protected by means of circuit-
Catalog HG 12 Switch-Dis- Example for coordination of a 125 A HV HRC fuse curve with a motor curve
breakers.
connectors, Vacuum Switches,
High-Voltage HRC Fuses. Due to the longer break time
of the circuit-breakers (maxi-
When the motors are ener- mum permissible 120 ms), the Overload protection Trip-free mechanism
gized, the HV HRC fuse is short-circuit current must not It is possible to use thermally All the switching contacts of
loaded most by the motor exceed the maximum permis- delayed overload relays in con- the vacuum contactors operate
starting current that occurs. sible value for the vacuum junction with suitable current trip-free.
It must neither blow nor be- contactor (20 kA at 7.2 kV). transformers for protecting
come damaged under these The OPEN command inter-
As a result of the longer break high-voltage motors against rupts the CLOSE command,
loads. overload.
time, the interrupters must i.e. the moment of the OPEN
Other factors that influence be replaced immediately in command determines whether
loading of the HV HRC fuses the case where the maximum the contacts close or not.
are the starting time and permissible short-circuit current
starting frequency of the value has been reached, since
motors. this causes a severe reduction
in their service life.

1/4Siemens HG 11.21 1997


3TL Vacuum Contactors 3TL-
Vacuum Contactors-
General Description

Technical specifications in comparison

Overview
3TL8 vacuum contactor 3TL6 vacuum contactor

Rated voltage up to 7.2 kV up to 12 kV

Rated normal current 400 A 450 A

Switching frequency up to 1200 operating cycles/h up to 1200 operating cycles/h

Service life operating cycles operating cycles


Contactor mech. service life: 1 mill. mech. service life: 3 mill.
Vacuum mech. service life: 0.25 mill. mech. service life: 2 mill.
interrupter electr. service life: 0.25 mill. electr. service life: 1 mill.

Chopping current 0.6 A <5A

Electronic economy
circuit
classification into voltage
ranges
24 V to 60 V
none
1
110 V to 250 V
irrespective of DC or AC actuation

Auxiliary contacts positively driven auxiliary switch; positively driven auxiliary switch;
4NO, 4NC 6NO, 5NC

Operating mechanism underneath to the vacuum at rear to the vacuum


interrupters interrupters

Type of construction slim-line compact

Main conductor at rear on the vacuum at front on the vacuum


terminals interrupters interrupters

Auxiliary conductor direct tapping at the terminals terminal block with testing
terminals (optional: wiring of the auxiliary options in installed state
contacts on the central (optional: withdrawable terminal
terminal block) block)

Additional modules mechanical closing latching mechanical closing latching


long operating mechanism shaft mechanical closing lock-out
for powerless, external built-on extension or reduction of the
accessories break time

4
065
3167
Nr.S

A00 A
400 A
810 0 -1B 0...60 Hz Ie 4 400
/A C
3TL 4
AC 3 AC 4
/
A
360 A
00 A Ue 2 kV AC 3 360
I th 4 7,
kV
7 0 7, 2 V


4 k
IE C 775 7, 2 V V
BS 347 2 5, 0
k V 7,2 k
.250 V
110.. 5,0 k


.
UL C 22 C /DC
CS A A
ge Us
a
volt 350 500
trol
Con city A
capa . MV 400
ing s sym
t e r rupt it h fuse r e 1997
In w tu
n t a ctor 2 4R a n ufac N Y
Co F M of m A
2 151 Year RM
3GC GE
C IN
0/75 DE
g 6 MA
Wirin
Nameplate
(example)

Siemens HG 11.21 19971/5


3TL 3TL Vacuum Contactors
Vacuum Contactors
General Description

Construction principle in comparison

The 3TL vacuum contactors


are made up of the following
assemblies:
Medium-voltage section with Main conductor terminal, rear
Vacuum interrupters
Main conductor terminals
Low-voltage section with Vacuum interrupter
Operating mechanism
(magnetic system) Medium-
Electronic module voltage
(electronic economy circuit) section
Mechanical closing latching Main conductor terminal, rear
Auxiliary contact block.

For further details about the Mechanical connection between

1 construction of the vacuum con-


tactors, see catalog sections 2
and 3. Low-
voltage
medium and low-voltage sections
HG11-2282a eps

section Operating mechanism (magnetic


system), below

3TL8 vacuum contactor (side view)

Low-voltage Medium-voltage
section section
Mechanical connection between
medium and low-voltage sections

Main conductor terminal, front

Operating mechanism (magnetic


system), rear

Vacuum interrupter
HG11-2283a eps

Main conductor terminal, front

3TL6 vacuum contactor (side view)

1/6Siemens HG 11.21 1997


3TL Vacuum Contactors 3TL-
Vacuum Contactors-
General Description

Vacuum interrupter

Arc-quenching system Due to the rapid recovery of In the case of all the conven- With the vacuum contactor,
As the contacts open, the the dielectric strength of the tional methods of arc-quench- on the other hand, the arc is
current that is to be interrupted contact gap, the arc is safely ing this means that the arc is not cooled. The metal-vapour
initiates a metal-vapour arc quenched even in cases where being cooled even before the plasma has a high conductivity
discharge. Current continues contact separation occurs minimum quenching gap and which results in an extremely
flowing through the metal va- immediately before a current the subsequent current zero low arc voltage with values
pour plasma until the next cur- zero. Consequently, the arcing are reached. As a result, the from only 20 to 50 V.
rent zero. The arc extinguishes time of the last poles to clear arc power is unintentionally in- For this reason, and due to the
at approximately current zero. is no more than 15 ms. creased to a considerable short arcing times, the amount
The metal vapour loses its con- With AC circuit-breakers, the degree. of energy conversion in the
ductivity within a few micro- actual task of the arc-quench- contact gap is very low. This
seconds, which very quickly ing system is to deionize the relatively low stress level
reestablishes the dielectric contact gap immediately after means that the quenching
strength of the contact gap. current zero. system is maintenance-free
A certain minimum current is and allows up to 1 million
needed in order to maintain the
metal-vapor arc discharge. The
arc will be chopped before
electrical operating cycles.
Due to the very low pressures
of less than 109 bar in the
1
the natural current zero if the interrupter under steady-state
current falls below this value. conditions, contact gaps of
In order to prevent impermis- only 5 to 7 mm are required
sible overvoltages when per- to achieve a high dielectric
forming switching operations in strength in 3TL vacuum con-
inductive circuits, the chopping
Fixed bolt tactors.
current must be limited to the
lowest possible value. Due
to the use of a special contact Contacts
material, the chopping current
in the 3TL vacuum contactor is
only 5 A. Arcing
chamber

Insulator
HG11-2284 eps

Metal
bellows

Guide
bearing

Moving
bolt

Vacuum interrupter
(example)

Siemens HG 11.21 19971/7


3TL 3TL Vacuum Contactors
Vacuum Contactors
General Description

Standards

Design Insulating capacity Ambient conditions The ambient air must not be
3TL vacuum contactors are 3TL vacuum contactors are Vacuum contactors can be contaminated with excessive
of an open design, degree of suitable for site altitudes be- used in buildings with low amounts of dust, smoke,
protection IP00 according to tween 1250 m below sea level thermal insulation or low heat corrosive or flammable gases,
DIN VDE 0470 Part 1 and and 2500 m above sea level. storage capacity, heated or vapors or salt.
IEC 144. The specified values are refer- cooled, without temperature
monitoring. The heating or For further specifications about
They comply with the red to sea level. When installed the ambient conditions, refer to
standards for high-voltage AC at altitudes above 1000 m, cooling may fail for a period of
several days. the technical specifications in
contactors of between an allowance must be made catalog sections 2 and 3.
1 kV and 12 kV: for the resulting decrease in The vacuum contactors fulfill
IEC Publication 470 1974 insulating capacity (see correc- the following ambient con-
DIN VDE 0660 tion factor a in the diagram ditions in accordance with
Part 103 3.84 below) IEC 721, Part 3.3, 1990:
UL Standard 347 1 Climatic:

HG11-2271 eps
CSA C22.2 Class 3K4 (minimum
1 0.9
temperature limit 25 C)
Correction factor a

Tests 0.8 Class 3K6 (without ice


We have our own accredited 0.7 formation and wind-driven
test bays which we can use to 0.6
precipitation)
develop and type-test high- Class 3Z2
0.1 Class 3Z5
capacity switchgear in accord-
0
ance with the relevant 0 m 1000 2000 3000 4000 5000 Biological:
standards: Class 3B1
Altitude above sea level
High power electrical testing Chemically active materials:
Testing of: Class 3C2 (without occur-
Mechanical operation The following expression thus rence of saline fog with
Reliability applies for the selection of the simultaneous moisture
Insulating capacity devices and equipment: condensation)
Temperature rise Mechanically active
Rated withstand voltage
Climatic withstand capability to be selected 1)
materials:
Extensive series of tests are Class 3S2 (restriction acc. to
carried out for the type-tests Required operating instructions: clean
specified in the relevant
rated withstand voltage 1) insulating components)

standards in order to achieve 1.1 a Mechanical:
reliable results. Class SM2.
If a customer requests tests
that are to be conducted in test If, however, the actual insulat- Ambient temperature 3)
bays not owned by Siemens, ing capacity must be deter-
mined at the installation site Temperature for vacuum
there are other accredited value contactor
testing institutes who can be the withstand voltage the
reduction of the insulating ca- 3TL8 3TL6
engaged.
pacity from that for an altitude Maximum value +65 C +80 C
The tests encompass switching of 0 m (sea level) must be Maximum value
capacity, current-carrying capa- calculated as follows: of 24-hour mean +60 C +75 C
city and, where applicable, in- Minimum value 25 C 25 C
sulating capacity. The fees for Withstand voltage 2)

these tests are charged by = a rated withstand voltage 1)


of the selected switching device.
PEHLA according to their cur- Relative humidity
rent price schedule. (measured averages):
Over 24 hours: max. 95 %
Definitions: Over 1 month: max. 90 %
Ratedwithstand voltage 1)
= target value according to Condensation may occasionally
VDE, IEC etc. referred to sea occur under these conditions.
level. Occasional exposure to
withstand voltage 2) condensation once per month
= actual value for approximately 2 hours is
at the respective height. permitted (tested according to
DIN 50016, FW24).

1) Rated lightning impulse withstand 3) For permissible mechanical service


voltage, rated power-frequency life, see Technical specifications,
withstand voltage pages 2/4 and 3/4.
2) Lightning impulse withstand
voltage, power-frequency
withstand voltage

1/8Siemens HG 11.21 1997


3TL8 3TL-
Vacuum Contactors-
Vacuum Contactors
as Economy
Contactors

R-HG11-088 eps
Rolling mill, Hylsa in Mexico

Features Contents Page


R-HG11-084 eps

7.2 kV rated voltage Suitable for switch- Construction and


Maintenance-free ing, for example, mode of operation 2/2, 2/3
through to the end of the Transformers
vacuum interrupters Capacitors Technical specifications 2/4
service life Filter circuits
Motors Selection and
Mechanical service life ordering data 2/5
of the contactor: 1 mill. Reactors
operating cycles Ohmic loads
Spare parts and
accessories 2/6

Internal connection
diagrams 2/7
3TL8 vacuum contactor
7.2 kV/400 A
Circuit diagrams 2/8, 2/9

Dimensions
and weights 2/10

Shipping 2/11

Enquiry form 2/12

Siemens HG 11.21 19972/1


3TL 3TL8 Vacuum Contactors
Vacuum Contactors
as Economy Contactors

Construction and mode of operation

Construction
The 3TL8 vacuum contactor
consists of:
Medium-voltage section with
Insulating plastic housing (1) 8
Vacuum interrupters (2)
Main conductor terminals 2 1
(8 and 9)
Low-voltage section with
Magnetic system (11)
R-HG11-084 eps

Electronic economy circuit


(14)
Auxiliary contact blocks 9
(12 and 13)
Mechanical closing latching 12
(6) as an additional module

Mode of operation 5 11
The magnetic system (11) of 14 13

2 the 3TL8 vacuum contactor


opens and closes the contacts 6

R-HG11-089 eps
of the vacuum interrupters (2).
Due to the use of the elec-
tronic economy circuit (14), the
magnetic system (11) is inde- 3TL8 vacuum contactor
pendent of the voltage type 7.2 kV/400 A Main conductor terminals
and level across a wide range. located at rear
(1 pole shown)
Mechanical closing latching
The mechanical closing
latching (6) holds the vacuum
contactor in the closed state
even without excitation of the
R-HG11-093 eps

R-HG11-109 eps

magnetic system (11).


The latching module of the Legend
(see page 2/3)
mechanical closing latching (6)
Electronic module (14) Mechanical closing
is fitted inside the mechanism latching (6)
housing (5). When the magnetic
system (11) is excited, the va-
cuum interrupter (2) is latched
mechanically by means of a
lever and roller system into the
CLOSED position. The con-
tactor is unlatched electrically Permissible installation positions
by means of an unlatching
HG11-2285 eps

solenoid or mechanically by
means of a release bolt (the
coupling must be provided * *
by the customer). *
The command duration for the
unlatching solenoid must be
between 100 ms and 1 s. An
external command ending unit
must be provided.

Wall assembly Floor assembly


vertical layout vertical layout horizontal layout

* Position of the main conductor terminals


Position of the terminal block

2/2Siemens HG 11.21 1997


3TL8 Vacuum Contactors 3TL-
Vacuum Contactors-
as Economy Contactors

Continued
HG11-2314a eps

1 8

Medium-voltage section
2

3
9

Low-voltage section
10
5

14 6
11 2
7

Structure of the 3TL8 vacuum contactor (front view) Side view from left (sectional view)

Legend
1 Insulating plastic housing
2 Vacuum interrupter *
3 Position indicator O - I
4 Operating shaft (short or long version)
5 Mechanism housing
6 Mechanical closing latching *
(optional) with rectifier module *
for AC operation
7 Terminal block (optional)
8 Top main conductor terminal
9 Bottom main conductor terminal
10 Mechanical connection between medium
and low-voltage sections
3
11 Magnetic system (solenoid *)
12 Top auxiliary contact block * 12
13 Bottom auxiliary contact block *
14 Electronic module * (electronic economy
circuit) with terminals 13

Side view from right

* Also available as a spare part.

Siemens HG 11.21 19972/3


3TL 3TL8 Vacuum Contactors
Vacuum Contactors
as Economy Contactors

Technical specifications

Medium-voltage section Low-voltage section


Rated operational voltage Ue 7.2 kV Power consumption of the solenoid
Rated frequency 50 to 60 Hz (AC and DC operation)
Rated continuous current Iu to DIN VDE 0660 400 A Pickup power 600 W
Holding power 90 W
Rated normal current Ie
according to utilization categories AC-1, AC-2, AC-3 and AC-4 Voltage range of the solenoid
at ambient temperatures up to +55 C 400 A Operating voltage
+65 C 360 A (AC and DC operation) 0.85 to 1.1 Uc
Switching capacity Minimum closing command
according to utilization category AC-4 (p. f. = 0.35) for the solenoid 300 ms
Rated making current 4000 A Make time 1) 200 ms at 0.85 x 110 V
Rated breaking current 3200 A (AC and DC operation 150 ms at 1.0 x 110 V
110 V to 250 V) 50 ms at 1.1 x 250 V
Max. permissible switching capacity 5 kA
Break time 2) 325 75 ms
Rated short-time current 1 s (r.m.s. value) 8 kA (AC and DC operation or 50 ms 3)
(For short-time current for longer periods, 110 V to 250 V) depending on the
see short-time current load-period curve) electronic economy circuit
Switching of capacitors Mechanical closing latching (optional)
Rated capacitor current 250 A (AC and DC operation)
Maximum permissible making current peak 10 kA Service life 100,000 operating cycles
Switching frequency 1200 operating cycles/h Switching frequency 60 operating cycles/h
(AC and DC operation) Power consumption of unlatching solenoid 900 W

2 without mechanical closing latching


Mechanical service life of the contactor
according to class D3
1 mill. operating cycles
Voltage range of unlatching solenoid
Tripping pulse
(by external circuit provided by customer)
Break time
0.85 to 1.1 Uc

0.2 to max. 1 s
< 45 ms
as defined in DIN VDE 0660
Mechanical service life 0.25 mill. operating cycles
of the vacuum interrupter Auxiliary contacts
Electrical service life 0.25 mill. operating cycles Number of auxiliary contacts 2NO + 2NC or 4NO + 4NC
of the vacuum interrupter Rated continuous current Iu 10 A
at rated normal current Rated normal current Ie
Insulation level Utilization category for AC-11 125 V AC, 10 A
Rated lightning impulse withstand voltage at rated voltage 230 V AC, 10 A
(to DIN VDE 0670, IEC 56): 500 V AC, 4 A
to earthed parts and between poles 60 kV 600 V AC, 2 A
across the open contact gap 40 kV Utilization category for DC-11 24 V DC, 10 A
Rated power-frequency withstand voltage 50 Hz (r.m.s.) at rated voltage 110 V DC, 5 A
to earthed parts and between poles 20 kV 125 V DC, 0.9 A
across the open contact gap 20 kV 220 V DC, 0.45 A
Cross-sections of the main conductor terminals 440 V DC, 0.25 A
600 V DC, 0.2 A
Terminal screw M10
Stranded conductors with cable lug 50 to 240 mm2 Cross-sections of the auxiliary contacts
Copper rail to DIN 43 671 30 x 5 mm to EN 60 947 Part 1
Aluminium rail to DIN 43 670 20 x 10 mm (screw terminal, two-wire connection possible)
solid 0.6 to 4 mm2
finely stranded with end sleeve 0.5 to 2.5 mm2

Ambient conditions
Ambient temperature
Storage at 40 to + 65 C 20 years
Operation at 5 to + 65 C 1 mill. operating cycles
at 25 to 5 C 0.5 mill. operating cycles
Site altitude 200 m below sea level
107 to 1250 m above sea level
HG11-2289a eps

5 Shock resistance (square impact) 5 x g, 10 ms or


2 10 x g, 5 ms
No. of operating cycles of vacuum interrupter

106
5
2,5
2
105
5
2
104 1) Make time =
5 Time from the instant of
2 application of a control
kA 103 A pulse (command) to the
HG11-2287 eps

HG11-2333 eps

5
8 600 instand when the
2
rated thermal

contacts touch.
102
Short-time current

7 550
Permissible

5 2) Break time =
6 500 Time from the instant
current

2
(r.m.s. value)

5 101 450 of application of the


5
4 400 OPEN control pulse
2
3 100 350 to the instant of contact
0 1 2 3 4 5s 6 2 5 2 5 2 5 0 10 20 30 40 C 60 separation.
Load 101 102 4 103 A 104 Ambient 3) Possible by means of
period Breaking current temperature external circuit.

2/4Siemens HG 11.21 1997


3TL8 Vacuum Contactors 3TL-
Vacuum Contactors-
as Economy Contactors

Selection and ordering data

7.2 kV Rated
operational
voltage
Ue
Rated lightning
impulse withstand
voltage
to across
Rated power- Rated
frequency with- normal
stand voltage current
Ie
Order No. Order
code

earth open con-


tact gap
kV kV kV kV A
7.2 60 40 20 400 3TL8 10
   
R-HG11-084 eps

Versions
Short operating shaft 0
Long operating shaft for powerless, external built-on accessories 1

Auxiliary contacts, additional modules


2NO + 2NC, without auxiliary contact wiring 0
4NO + 4NC, without auxiliary contact wiring 1
4NO + 4NC, without closing latching *, without auxiliary contact wiring 2
4NO + 4NC, low-voltage contacts connected to terminal block 5

Operating voltages of the solenoid


110 V to 250 V AC/DC B

Operating voltages for releasing


the mechanical closing latching
2
Without mechanical closing latching A
110/115 V AC 50/60 Hz L
120/127 V AC 50/60 Hz M
Versions 220/240 V AC 50/60 Hz N
380 V AC 50/60 Hz P

24 V DC B
30 V DC C
48 V DC D
R-HG11-091 eps

R-HG11-092 eps

60 V DC E
110 V DC F
125 V DC G
Short operating shaft Long operating shaft 220 V to 250 V DC H

Break time
325 75 ms (without using the mechanical closing latching) 0

Operating instructions
Without routine test report German / English 0
French / Spanish 1
With routine test report German / English 5
French / Spanish 6

Special version

Wiring
Conductors, halogen-free and flame-resistant Z A 1 0

* External contactor relay, e.g. type 3TH4,


not included in the scope of delivery. For
selection and ordering data, see page
2/6, internal connection diagrams see
page 2/7.

Siemens HG 11.21 19972/5


3TL 3TL8 Vacuum Contactors
Vacuum Contactors
as Economy Contactors

Spare parts and accessories (when placing an order, please also state the type and serial number of the vacuum contactor)

Scope of delivery Operating voltage Order No.


or contacts

Vacuum interrupter 3TY5 810-0AA0

R-HG11-107 eps
(up to serial no.
31 670 935)

3TY5 810-1AA0
(as of serial no.
31 670 936)

R-HG11-098 eps
Auxiliary contact block top 2NO + 2NC 3TY7 561-1SA0

bottom 2NO + 2NC 3TY7 561-1NA0

Solenoid 24 V 60 V AC/DC 3TY5 811-0AA0


R-HG11-108 eps

110 V 250 V AC/DC 3TY5 811-0BA0

2
R-HG11-093 eps

Electronic module 24 V 60 V AC/DC 3TY5 812-0AA0

110 V 250 V AC/DC 3TY5 812-0BA0

Contactor relay (accessory) 110 V AC 50/60 Hz 3TH40 92-0AG1


R-HG11-102 eps

115 V AC 50/60 Hz 3TH40 92-0AJ1


120 V AC 50/60 Hz 3TH40 92-0AK1
125/127 V AC 50 Hz 3TH40 92-0AL0

220 V AC 50/60 Hz 3TH40 92-0AN1


230 V AC 50/60 Hz 3TH40 92-0AL1
240 V AC 50/60 Hz 3TH40 92-0AP1
400 V AC 50 Hz 3TH40 92-0AV0

24 V DC 3TH40 92-0BB4
60 V DC 3TH40 92-0BE4
110 V DC 3TH40 92-0BF4
125 V DC 3TH40 92-0BG4
220 V DC 3TH40 92-0BM4

Mechanical closing 110 V 115 V AC 50/60 Hz 3TY5 892-0AG7


R-HG11-109 eps

latching (accessory) 120 V 127 V AC 50/60 Hz 3TY5 892-0AL7


220 V 240 V AC 50/60 Hz 3TY5 892-0AN7
380 V AC 50/60 Hz 3TY5 892-0AQ2

24 V DC 3TY5 892-0BB4
30 V DC 3TY5 892-0BC4
48 V DC 3TY5 892-0BD4
60 V DC 3TY5 892-0BE4

110 V DC 3TY5 892-0BF4


125 V DC 3TY5 892-0BG4
220 V 250 V DC 3TY5 892-0BM4

Rectifier module 3AX15 25-1F


R-HG11-106 eps

(accessory) for mechanical


closing latching

2/6Siemens HG 11.21 1997


3TL8 Vacuum Contactors 3TL-
Vacuum Contactors-
as Economy Contactors

Internal connection diagrams

AC operation
48 47 17 18
Voltage ranges
24 V to 60 V AC 1L1 3L2 5L3
-K2E -K2E
110 V to 250 V AC -K1 -K1

HG11-2290b eps
-X1 A1 71 83 61 53 22 14 32 44 E1
Without mechanical ~
-H1 -H2 -G
closing latching: +
Opening delay 50 ms by -K2S A1 ~
means of external circuit -K1M A2
Opening delay
325 75 ms
Auxiliary contact block -X1 A2 72 84 62 54 21 13 31 43 E2
2NO + 2NC
2T1 4T2 6T3 A2
Optional: 4NO + 4NC -K2E
A1
Optional: with mechan- Vacuum contactor Closing
ical closing latching without closing latching latching (optional)
(K2S) (only in conjunc-
tion with auxiliary contact
block 4NO + 4NC) and
with rectifier

48 47 17 18
-K2E -K2E
DC operation -K1 1L1 3L2 5L3 -K1
HG11-2329a eps

A1 71 83 61 53 22 14 32 44 E1
Voltage ranges -X1
24 V to 60 V DC -H1 -H2
110 V to 250 V DC
-K2S A1
Without mechanical -K1M A2
closing latching:
Opening delay 50 ms by
means of external circuit
Opening delay -X1 A2 72 84 62 54 21 13 31 43 E2
325 75 ms 2T1 4T2 6T3 A2
-K2E
Auxiliary contact block A1
2NO + 2NC Vacuum contactor Closing
without closing latching latching (optional)
Optional: 4NO + 4NC
Optional: with mechan-
ical closing latching
(K2S) (only in conjunc-
tion with auxiliary contact
block 4NO + 4NC)

Legend
-G Rectifier module
-H1 Bottom auxiliary contact block
-H2 Top auxiliary contact block (optional)
-K1 Vacuum contactor
-K1M Solenoid-operated mechanism for vacuum contactor
-K2E External contactor relay (e.g. Siemens type 3TH4)
-K2S Unlatching solenoid (optional)
-X1 Terminal block for auxiliary conductor connection

Siemens HG 11.21 19972/7


3TL 3TL8 Vacuum Contactors
Vacuum Contactors
as Economy Contactors

Circuit diagrams (examples)

AC and DC operation
Momentary-contact control Maintained-contact control
Without mechanical
closing latching -F -F
L1(L+) L1(L+)
Opening delay -K2E -K2E
Without Without
50 ms by means of -S0Q -K2E -K2E time-delay -S1Q -K2E -K2E time-delay
external circuits relay for relay for
325 75 ms A1 2 2 1 1 -K1 minimum A1 2 2 1 1 -K1 minimum
-S1Q -K2E motor start- motor
ing time, starting time,
HG11-2291 eps

HG11-2292 eps
-K1M -K1M opening -K1M -K1M opening
-K2E delay -K2E delay
<
50 ms <
50 ms
A2 A2

N (L2,L-) Fig. 1 N (L2,L-) Fig. 3

-F -F
L1(L+) L1(L+)
-K2E Without -K2E Without
-S0Q time-delay -S1Q time-delay
A1 -K1 relay for A1 -K1 relay for
minimum minimum
-S1Q -K2E motor start- motor
HG11-2293 eps

HG11-2294 eps
ing time,

2
starting time,
opening opening
-K2E A2 delay -K2E A2
delay
325 75 ms 325 75 ms

N (L2,L-) Fig. 2 N (L2,L-) Fig. 4

Legend
-F Fuse
-K1 Vacuum contactor
-K2E External contactor relay
(e.g. Siemens type 3TH4)
-K1M Solenoid-operated mechanism
-S0Q External OPEN pushbutton
-S1Q External CLOSED pushbutton

2/8Siemens HG 11.21 1997


3TL8 Vacuum Contactors 3TL-
Vacuum Contactors-
as Economy Contactors

Circuit diagrams (examples for motor start-up)

Short-circuit protection
by means of circuit- Main circuit Control circuit, momentary-contact control
breaker
3~50/60 Hz -F1
Control of a high-voltage L1 L1/L+
Legend
L2

HG11-2300 eps
motor with reversing L3
11 21 21
-F1 Fuse/m.c.b.
contactor combination -S3Q -K3M -K1M
12 22 22 -K1M, Vacuum contactors
for 2 directions of -Q1F -K2M,
rotation 11 11 21 21
-K4M -K2M -K3M,
-S2Q -S1Q
with four 3TL8 contactors 12 12 22 22
-K4M
13 13 -K5A, Contactor relays
-K1M -K3M 13 13 23 23
-S1Q -K5A -S2Q -K6A -K5A -K6A -K6A
14 14 14 14 24 24 -M1 Motor
-K2M -K4M
-Q1F Circuit-breaker
41 41 13 13 -S1Q CLOSE pushbutton,
-K6A -K5A -K1M -K3M direction of rotation 1
42 42 14 14
U1 V1 W1 -S2Q CLOSE pushbutton,
HG11-2301a eps

-K5A A1 -K6A A1 -K1M A1 -K2M A1 -K3M A1 -K4M A1


M direction of rotation 2
-M1
3~ A2 A2 A2 A2 A2 A2 -S3Q OPEN pushbutton
N(L2)/L-

Main circuit Control circuit, momentary-contact control


2
Short-circuit protection 3~50/60 Hz -F1
by means of HV HRC L1 L1/L+
Legend
L2

HG11-2298 eps
fuses 11 21 21
L3 -F1 Fuse/m.c.b.
-S3Q -K3M -K1M
Control of a high-voltage -F1F 12 22 22 -F1F HV HRC fuses
motor with reversing 11 11 -K1M, Vacuum contactors
contactor combination -S2Q -S1Q -K3M
12 12
for 2 directions of -K5A, Contactor relays
rotation 13 13 13 13 21 21 -K6A
with two 3TL8 contactors -S1Q -K5A -S2Q -K6A -K5A -K6A -M1 Motor
-K1M -K3M 14 14 14 14 22 22
-S1Q CLOSE pushbutton,
direction of rotation 1
41 41 -S2Q CLOSE pushbutton,
-K6A -K5A
42 42 direction of rotation 2
U1 V1 W1
HG11-2299a eps

-K5A A1 -K6A A1 -K1M A1 -K3M A1 -S3Q OPEN pushbutton


M
-M1
3~ A2 A2 A2 A2
N(L2)/L-

Overload protection by Short-circuit protection by Short-circuit protection by


means of overload relays means of HV HRC fuses means of circuit-breakers
Overload and short-
circuit protection 3~50/60 Hz L1 3~50/60 Hz 3~50/60 Hz
L1 L2 L3 L1 L1
N
for 1 direction of rotation L2 L2
with one 3TL8 contactor 1 L3 L3
HG11-2295b eps
HG11-2296a eps

-S1 1 5

-S0

2 2

4
M M
2
3~ 3~

3 Legend
1 HV HRC fuses
2 Vacuum contactor
HG11-2297a eps

M 3 Main current transformer


3~ 4 Overload relay
5 Circuit-breaker

Siemens HG 11.21 19972/9


3TL 3TL8 Vacuum Contactors
Vacuum Contactors
as Economy Contactors

Dimensions and weights

3TL8 vacuum contactor


For AC and DC operation
386
Weight 32 kg.
115 115 200

HG11-2302b eps

130*

371
217*
126
2 344
374 17
11 195
215
392 217,5

3TL8 100 vacuum contactor with short operating shaft

386
115 115 200
HG11-2330a eps

130*

371
217*
126

344 11 195
374 47 215
442 217,5

3TL8 101 vacuum contactor with long operating shaft

* Fixing dimensions

2/10Siemens HG 11.21 1997


3TL8 Vacuum Contactors 3TL-
Vacuum Contactors-
as Economy Contactors

Shipping

Packaging Package type Destination


The 3TL8 vacuum contac- Germany Europe Overseas Overseas/Europe
tors are packed in accord- Shipping Shipping Shipping Shipping
ance with the customers by means of by means of by means of by means of
order specifications and truck rail truck rail ship air freight
shipped anywhere in the Individual package
world in the mode deter- Lot-size package
mined by the customer.
Cardboard box with inner box
If the customer has not to suit unit
specified the manner of Cardboard box with sealed packaging
packaging and mode of and inner box to suit unit
shipping, the most eco-
nomic option is chosen Skeleton container with cardboard
boxes and inner box to suit unit
depending on the size of
the lot ordered. Plywood box + cardboard boxes
with sealed packaging and inner
box to suit unit

Preferred package type

Shipping dimensions
Package type

Cardboard with inner box


for no. of
vacuum contactors
1
Length
mm
490
Width
mm
300
Height
mm
400
Volume
m3
0.059
Gross weight
kg
23
2
and weights
to suit unit 2 800 780 670 0.42 62
Shipping by truck or rail 34 1020 620 670 0.42 100 130
Cardboard box with sealed packaging 12 800 780 670 0.42 45 70
and inner box to suit unit 34 1020 620 670 0.42 105 135
Skeleton container with cardboard 3 12 1200 800 800 0.77 125 360
boxes and inner box to suit unit
Plywood box + cardboard boxes 13 920 620 720 0.41 50 100
with sealed packaging and inner 7 10 1020 1020 1020 1.06 240 310
box to suit unit

Shipping by ship Package type for no. of Length Width Height Volume Gross weight
vacuum contactors mm mm mm m3 kg
Cardboard box with inner box
to suit unit
Cardboard box with sealed packaging 12 800 780 670 0.42 45 70
and inner box to suit unit 34 1020 620 670 0.42 105 135
Skeleton container with cardboard
boxes and inner box to suit unit
Plywood box + cardboard boxes 13 920 620 720 0.41 50 100
with sealed packaging and inner 7 10 1020 1020 1020 1.06 240 310
box to suit unit

Shipping by air freight Package type for no. of Length Width Height Volume Gross weight
vacuum contactors mm mm mm m3 kg
Cardboard box with inner box 1 490 300 400 0.059 23
to suit unit 2 800 780 670 0.42 62
34 1020 620 670 0.42 100 130
Cardboard box with sealed packaging 12 800 780 670 0.42 45 70
and inner box to suit unit 34 1020 620 670 0.42 105 135
Skeleton container with cardboard
boxes and inner box to suit unit
Plywood box + cardboard boxes 13 920 620 720 0.41 50 100
with sealed packaging and inner 7 10 1020 1020 1020 1.06 240 310
box to suit unit

Siemens HG 11.21 19972/11


3TL 3TL8 Vacuum Contactors
Vacuum Contactors
as Economy Contactors
Ple
ase
Enquiry form c
c pyo
o th
t mp is f
To your Siemens office Your personal details r o you lete orm
et r it
Company Siemens AG Company Sie urn i requ acco
Department Department me t to irem rdin
ns yo g
Name Name off ur ents
ice
Street Street
City, postal code City, postal code
Fax Tel.
Fax

We request the following:  Quotation  Call  Visit  Order/Delivery

Technical Other Other


specifications requirements requirements
See page 2/4.
 7.2 kV rated operational voltage   Mechanical service life of the 
 50/60 Hz rated frequency  vacuum contactor, 1 mill.
 400 A rated normal current   Mechanical service life of the 

2  8 kA rated short-time current


 250 A rated capacitor current


vacuum interrupter, 0.25 mill.
 Electrical service life of the
vacuum interrupter, 0.25 mill.

(switching of capacitors)
 Chopping current 0.6 A 
 Switching frequency 1200/h 
 Max. permissible switching 
capacity 5 kA

Additional/secondary Version Operating voltage for releasing the


equipment  With short operating shaft  mechanical closing latching
See page 2/5.  With long operating shaft  Without closing latching 
 24 V DC  30 V DC 
Auxiliary switches, additional modules
 48 V DC  60 V DC
 2NO+2NC  4NO+4NC   110 V DC  125 V DC
 4NO+4NC + closing latching  220 to 250 V DC
Operating voltage of the solenoid  110/115 V AC 50/60 Hz 
 120/127 V AC 50/60 Hz
 24 V to 60 V AC/DC   220/240 V AC 50/60 Hz
 110 V to 250 V AC/DC  380 V AC 50/60 Hz
Break time Operating instructions
 325 75 ms   Without  German/ 
routine test English
report  French/
Wiring
Spanish
 Auxiliary switches 
 With  German/ 
on terminal block
routine test English
 Conductors, halogen-free  report  French/
and flame-resistant Spanish

Order No. 3 T L 8 1 0
Quantity

Field of application  Motors


and other  Transformers
requirements
 Reactors
 Ohmic loads
 Capacitors
 Filter circuits

2/12Siemens HG 11.21 1997


3TL6
Vacuum Contactors
as Universal
Contactors

R-HG11-090 eps
Transrapid MAGLEV vehicle, test track at Lathen, Germany

Features Contents Page


R-HG11-085 eps

Rated voltages up to Suitable for switching, Construction and


12 kV for example: mode of operation 3/2, 3/3
Maintenance-free Transformers
through to the end of the Capacitors Technical specifications 3/4
vacuum interrupters Filter circuits
service life Motors Selection and
Reactors ordering data 3/5
Mechanical service life of
the contactor up to 3 mill. Ohmic loads
Spare parts and
operating cycles accessories 3/6

Internal connection
3TL6 vacuum contactor diagrams 3/7
7.2 kV/450 A

Circuit diagrams 3/8, 3/9

Dimensions and weights 3/10

Shipping 3/11

Enquiry form 3/12

Siemens HG 11.21 19973/1


3TL 3TL6 Vacuum Contactors
Vacuum Contactors
as Universal Contactors

Construction and mode of operation

Construction
The 3TL6 vacuum contactor
consists of: 10
Medium-voltage section with
Insulating plastic housing (15)
Vacuum interrupters (13) 11
Main conductor terminals
(12 and 14)
Low-voltage section with 12
Mechanism housing (1) 16
made of sheet steel
Magnetic system (2) 15
Central terminal block (3) for
auxiliary and control circuits 1
Contactor relay (external)
Auxiliary contact blocks 13
Mechanical closing latching
(7 to 9) and mechanical clos-
ing lock-out (5) as additional
14
modules
R-HG11-085 eps

Integral rocker (10) as con-


nection between the magne-
tic system and the vacuum
interrupters.
3TL6 vacuum contactor
Mode of operation 7.2 kV/450 A
(see figure on page 3/3)
3 The atmospheric pressure ex-
erts a force on the metal bel-
lows of the vacuum interrupter.
Without the influence of the
operating mechanism, the con-
R-HG11-094 eps

R-HG11-096 eps

tact gap would close. The


opening springs (6) keep the
Legend
moving contact piece in the See page 3/3
open position by means of the Terminal block (3) Adjusting controls (at rear of unit) for
integral rocker (10). (Optional: withdrawable from side) adapting to a site altitude between
To close the vacuum contactor, 1250 m below and 2500 m above
sea level
the pressure force of the open-
ing springs (6) is overcome by
the magnetic system (2). The
solenoid armature (4) is attract-
ed and thereby moves the Permissible installation positions
integral rocker (10) which re-
leases the moving interrupter * * *
contact piece from the open
position. The atmospheric
pressure closes the contact
pieces. The integral rocker (10)
then presses the contact pres-
sure springs (16) together and
thereby produces the neces-
HG11-2286a eps

sary contact force.


After de-energization of the
electromagnetic excitation, the
opening springs (6) open the Wall assembly Floor assembly
contact gap by means of the vertical layout vertical layout horizontal layout
integral rocker (10) and the (rotated through180)
moving interrupter contact
piece.
The DC magnetic system func-
tions as an economy circuit.
This leads to a longer mechan-
ical service life and reduces
both pick-up and holding power.

* Position of the main conductor terminals


Position of the terminal block

3/2Siemens HG 11.21 1997


3TL6 Vacuum Contactors 3TL-
Vacuum Contactors-
as Universal Contactors

Continued

Adapting to the site altitude


The vacuum contactor is
factory-set for a site altitude

HG11-2303 eps
between 200 m below and 10
1250 m above sea level. If it is
to be used at altitudes not
within this range, the altitude 11
range must be adapted by
means of adjusting controls
12
(see figure on page 3/2) at the
rear of the end unit.
Adjusting ranges above sea
level:
+ 1250 m to + 2500 m
200 m to + 1250 m 13
1250 m to + 200 m.

Mechanical closing latching


The latching lever (7) holds the
vacuum contactor in the closed
state even without excitation 14
of the magnetic system. When
the magnetic system is excited,
15 Front
the integral rocker is latched view
mechanically by means of a
lever and roller system into the
CLOSEDposition. The con-
tactor is unlatched electrically
by means of an unlatching
solenoid (9) or mechanically by
Low-voltage section Medium-voltage section
3
means of the release bolt (8).
10
Mechanical closing lock-out
The mechanical closing lock- 1 16
out (5) prevents unintentional
closing of the vacuum contac- 2
tor, for example, due to vibra- 12
tions or when the withdraw- 3
able unit is moved. This lock
remains inoperative during 4
operational switching.
5
Blocking element for inter-
locking of two contactors 13
6
A mechanically functioning
blocking element is available 7
on request (for rated voltages
up to 7.2 kV only) for mutual 8 14
interlocking of two contactors
in reversing operation. The 9 Side view
blocking element is fixed be- 15 from left
tween the two contactors and (sectional
view)
intervenes in a mutually con-
trolling and blocking manner in Design of a 3TL6 vacuum contactor in the OPEN state
the movement of the integral (the arrows show the CLOSED direction of movement
rocker of both contactors. This
rules out a phase short-circuit
as a result of simultaneous
activation of both directions of Legend
rotation in the event of mecha- 1 Mechanism housing 6 Opening spring 10 Integral rocker
nical impact and electrical mal- 2 Magnetic system (solenoid *) Mechanical closing latching 11 Position indicator O I
operations. with rectifier * (optional) and (7 to 9) 12 Top main conductor terminal
economy resistor *
7 Latching lever 13 Vacuum interrupter *
3 Terminal block (optional: with-
drawable from side)
8 Release bolt 14 Bottom main conductor terminal
4 Solenoid armature 9 Unlatching solenoid * with 15 Insulating plastic housing
rectifier and varistor modules *
5 Mechanical closing lock-out * (optional)
16 Contact pressure spring

* Also available as a spare part.

Siemens HG 11.21 19973/3


3TL 3TL6 Vacuum Contactors
Vacuum Contactors
as Universal Contactors

Technical specifications

Medium-voltage section Low-voltage section


Vacuum contactor type Vacuum contactor type
3TL61 3TL65 3TL61 3TL65
Rated operational voltage Ue 7.2 kV 12 kV Power consumption of the solenoid
Rated frequency 50 to 60 Hz (AC and DC operation)
Rated continuous current Iu to DIN VDE 0660 450 A Pickup power 650 W
Holding power 90 W
Rated normal current Ie
according to utilization categories AC-1, AC-2, AC-3 and AC-4 Voltage range of the solenoid 0.8 to 1.1 Uc
Operating voltage
at ambient temperatures up to + 55 C 450 A (AC and DC operation)
+ 80 C 315 A
Minimum closing command 100 ms
Switching capacity for the solenoid
according to utilization category AC-4 (p. f. = 0.35)
Make time 1) 100 ms at 0.85 x Uc
Rated making current 4500 A (AC and DC operation) 80 ms at 1.0 x Uc
Rated breaking current 3600 A 60 ms at 1.1 x Uc
Max. permissible switching capacity 5 kA Break time 2) 30 ms at 0.8 x Uc
Rated short-time current 1 s (r.m.s. value) 8 kA (AC and DC operation) 50 ms at 1.0 x Uc
(For short-time current for longer periods, Other opening delay times possible 50 ms at 1.1 x Uc
see short-time current load-period curve) as special version: see page 3/5
Switching of capacitors Mechanical closing latching (optional)
(AC and DC operation)
Rated capacitor current 250 A 250 A 3)
Maximum permissible making current peak 10 kA 10 kA Service life 100,000 operating cycles
Switching frequency 60 operating cycles/h
Switching frequency 1200 600 Power consumption of unlatching soleonid 900 W
(AC and DC operation) operating operating
Voltage range of unlatching soleonid 0.85 to 1.1 Uc
without mechanical closing latching cycles/h cycles/h
Tripping pulse
Mechanical service life of the contactor 3 mill. 1 mill. (by external circuit provided by customer) 0.2 to max. 1 s
according to class D3 operating operating Break time < 45 ms
as defined in DIN VDE 0660 cycles cycles

3 Mechanical service life


of the vacuum interrupter

Electrical service life


2 mill.
operating
cycles
1 mill.
1 mill.
operating
cycles
0.5 mill.
Auxiliary contacts
Number of auxiliary contacts 4NO + 3NC
(optional: 6NO + 5NC)
Rated continuous current Iu 10 A
of the vacuum interrupter operating operating
at rated normal current cycles cycles Rated normal current Ie
Utilization category for AC-11 125 V AC, 10 A
Insulation level at rated voltage 230 V AC, 10 A
Rated lightning impulse withstand voltage 500 V AC, 4 A
(to DIN VDE 0670, IEC 56): 600 V AC, 2 A
to earthed parts and between poles 60 kV 75 kV Utilization category for DC-11 24 V DC, 10 A
across the open contact gap 40 kV 60 kV at rated voltage 110 V DC, 5 A
Rated power-frequency withstand voltage 50 Hz (r.m.s.) 125 V DC, 0.9 A
to earthed parts and between poles 20 kV 28 kV 220 V DC, 0.45 A
across the open contact gap 20 kV 28 kV 440 V DC, 0.25 A
600 V DC, 0.2 A
Cross-sections of the main conductor terminals
Cross-sections of the auxiliary contacts
Terminal screw M10 M10
to EN 60 947 Part 1
Stranded conductors with cable lug 50 to 240 mm2 50 to 185 mm2
(screw terminal, two wire connection possible)
Copper rail to DIN 43 671 30 x 5 mm 30 x 5 mm
Aluminium rail to DIN 43 670 20 x 10 mm 20 x 10 mm solid 0.6 to 4 mm2
finely stranded with end sleeve 0.5 to 2.5 mm2

Ambient conditions
Ambient temperature
Storage at 40 to + 65 C 20 years 20 years
107 Operation at 5 to + 55 C Operating cycles 2 mill. 1 mill.
HG11-2288 eps

5 3TL60, 3TL61 at + 55 to + 80 C Operating cycles 1 mill. 1 mill.


6 2
at 25 to 5 C Operating cycles 0.5 mill. 0.25 mill.
No. of operating cycles of vacuum interrupter

10
5 Site altitude (adjustable) 1250 m below sea level
3TL65
2
to 2500 m above sea level
5
10 Shock resistance (square impact) 5 x g, 10 ms or
5
10 x g, 5 ms
4 2
10
5 1) Make time = Time
2 from the instant of appli-
kA 103 A cation of a control pulse
HG11-2287 eps

HG11-2316a eps

5
8 650 (command) to the instant
2
rated thermal

102 when the contacts touch.


Short-time current

7 600
Permissible

5 2) Break time = Time


6 550
current

2
(r.m.s. value)

from the instant of appli-


5 101 500 cation of the OPEN
5
4 450 control pulse to the in-
2
3 100 400 stant of contact separ-
0 1 2 3 4 5s 6 2 5 2 5 2 5 0 10 20 30 40 C 60 ation.
Load 101 102 4,5 103 A 104 Ambient 3) 3EF3 surge limiter
period Breaking current temperature required.

3/4Siemens HG 11.21 1997


3TL6 Vacuum Contactors 3TL-
Vacuum Contactors-
as Universal Contactors

Selection and ordering data

up to 12 kV Rated operational Rated lightning im-


voltage
Ue
pulse withstand
voltage
to across
Rated power-
frequency
withstand
voltage
Rated
normal
current
Ie
Order No. Order
code

earth open con-


tact gap
kV kV kV kV A
7.2 60 40 20 450 3TL6 1 3
12 75 60 28 450 3TL6 5 0
   

Terminal block Auxiliary contacts


Central 4NO + 3NC 1
Central 6NO + 5NC 2
Withdrawable 6NO + 5NC 3

Auxiliary
Additional modules contacts
R-HG11-085 eps

Without additional modules 0


Mechanical closing latching 1NO assigned 1
Mechanical closing lock-out 2
Mechanical closing latching and closing lock-out 1NO assigned 3
f-release with closing latching, without closing lock-out 1NO assigned 4
f-release with closing latching, with closing lock-out 1NO assigned 5

Type of operation
for solenoid and mechanical closing latching
AC operation for air-insulated systems A
DC operation for air-insulated systems B

Operating voltage
for solenoid and mechanical closing latching
110 V AC 50/60 Hz G 2
3
115 V AC 50/60 Hz J 2
120 V AC 50/60 Hz K 2
125/127 V AC 50 Hz L 0

220 V AC 50/60 Hz N 2
230 V AC 50/60 Hz L 2
240 V AC 50/60 Hz P 2
380 V AC 50 Hz Q 0

400 V AC 50 Hz V 0
415 V AC 50 Hz R 0
440 V AC 50/60 Hz R 2
500 V AC 50 Hz S 0

24 V DC B 4
60 V DC E 4
110 V DC F 4
125 V DC G 4
220 V DC M 4

Operating voltage of solenoid different


from that of mechanical closing latching 1) Z 0 K 1 Y

Operating instructions
German / English (standard)
French / Spanish Z L 0 1

Routine test report


German / English 2) Z F 2 0

Special versions

Break times
1) Ordering data: in addition to the Order No., 35 ms Z G 0 1
state the required operating voltage from the 120 ms Z G 0 2
above table in plain text (please make inquiry). 250 70 ms Z G 0 3
2) Other languages on request. 120/50 ms Z G 0 8

Overvoltage protection circuitry in secondary circuit


Varistor module Z A 0 0
Note: Rectifier module Z A 0 1
Due to a lack of space, the internal command ending
unit cannot be installed in 3TL6 vacuum contactors Wiring
with withdrawable terminal block. Conductors, halogen-free and flame-resistant Z A 1 0
Order No. 3TL6 133 and 3TL6 530.

Siemens HG 11.21 19973/5


3TL 3TL6 Vacuum Contactors
Vacuum Contactors
as Universal Contactors

Spare parts and accessories (when placing an order, please also state the type and serial number of the vacuum contactor)

Scope of delivery Operating voltage Order No. Operating Order No.


or contacts voltage

Vacuum interrupter 3TY5 610-2AA0

R-HG11-097 eps
3TY5 650-0AA0

R-HG11-098 eps
Auxiliary contact block left 2NO + 2NC 3TY7 561-1NA0
3NO + 3NC 3TY7 561-1QA0
right 2NO + 2NC 3TY7 561-1PA0
3NO + 3NC 3TY7 561-1RA0

R-HG11-101 eps
Solenoid 110/115 V AC 50/60 Hz 3TY5 651-0AG7 500 V AC 50 Hz 3TY5 651-0AU7
from year of manu- 120 V AC 50/60 Hz 3TY5 651-0AL7
125/127 V AC 50 Hz 3TY5 651-0AL7 24 V DC 3TY5 651-0BB4
facture 10.90, 220 V AC 50/60 Hz 3TY5 651-0AN2 60 V DC 3TY5 651-0BE4
from serial no. 31 375 035 230/240 V AC 50/60 Hz 3TY5 651-0AN7 110 V DC 3TY5 651-0BF4
380 V AC 50 Hz 3TY5 651-0AQ2 125 V DC 3TY5 651-0BG4
400/415 V AC 50 Hz 3TY5 651-0AR7 220 V DC 3TY5 651-0BM4
440 V AC 50/60 Hz 3TY5 651-0AR7
R-HG11-101 eps

Solenoids 110/115 V AC 50/60 Hz 3TY5 656-0AG7 500 V AC 50 Hz 3TY5 656-0AU7


with resistor 120 V AC 50/60 Hz 3TY5 656-0AL7
125/127 V AC 50 Hz 3TY5 656-0AL7 24 V DC 3TY5 656-0BB4
(complete kit only) 220 V AC 50/60 Hz 3TY5 656-0AN2 60 V DC 3TY5 656-0BE4
up to year of manu- 230/240 V AC 50/60 Hz 3TY5 656-0AN7 110 V DC 3TY5 656-0BF4
facture 09.90, 380 V AC 50 Hz 3TY5 656-0AQ2 125 V DC 3TY5 656-0BG4
up to serial no. 31 375 034 400/415 V AC 50 Hz 3TY5 656-0AR7 220 V DC 3TY5 656-0BM4
440 V AC 50/60 Hz 3TY5 656-0AR7
R-HG11-100 eps

3
Resistor (accessory) 110/115 V AC 3TY5 664-1DA0 500 V AC 3TY5 664-1KA0
R-HG11-100 eps

for economy circuit 120/125/127 V AC 3TY5 664-1EA0


220 V AC 3TY5 664-1FA0 24 V DC 3TY5 664-0AA0
from year of manu- 230/240 V AC 3TY5 664-1GA0 60 V DC 3TY5 664-0CA0
facture 10.90, 110 V DC 3TY5 664-0DA0
380 V AC 3TY5 664-1HA0
from serial no. 31 375 035 400/415/440 V AC 3TY5 664-1JA0 125 V DC 3TY5 664-0EA0
220 V DC 3TY5 664-0FA0

Contactor relay 110 V AC 50/60 Hz 3TH40 92-0AG1 500 V AC 50 Hz 3TH40 92-0AS0


R-HG11-102 eps

115 V AC 50/60 Hz 3TH40 92-0AJ1


120 V AC 50/60 Hz 3TH40 92-0AK1 24 V DC 3TH40 92-0BB4
125/127 V AC 50 Hz 3TH40 92-0AL0 60 V DC 3TH40 92-0BE4
220 V AC 50/60 Hz 3TH40 92-0AN1 110 V DC 3TH40 92-0BF4
230 V AC 50/60 Hz 3TH40 92-0AL1 125 V DC 3TH40 92-0BG4
240 V AC 50/60 Hz 3TH40 92-0AP1 220 V DC 3TH40 92-0BM4
400 V AC 50 Hz 3TH40 92-0AV0
415 V AC 50 Hz 3TH40 92-0AR0
440 V AC 50/60 Hz 3TH40 92-0AR1

Mechanical closing 110/115 V AC 50/60 Hz 3TY5 692-0AG7 500 V AC 50 Hz 3TY5 692-0AU7


R-HG11-103 eps

latching (accessory) 120 V AC 50/60 Hz 3TY5 692-0AL7


125/127 V AC 50 Hz 3TY5 692-0AL7 24 V DC 3TY5 692-0BB4
220 V AC 50/60 Hz 3TY5 692-0AN2 60 V DC 3TY5 692-0BE4
230/240 V AC 50/60 Hz 3TY5 692-0AN7 110 V DC 3TY5 692-0BF4
380 V AC 50 Hz 3TY5 692-0AQ2 125 V DC 3TY5 692-0BG4
400/415 V AC 50 Hz 3TY5 692-0AR7 220 V DC 3TY5 692-0BM4
440 V AC 050/60 Hz 3TY5 692-0AR7

Mechanical closing 3TY5 693-0AA0


R-HG11-
104 eps

lock-out (accessory)

Blocking element (acc. for 3TX5 111-0AA0


R-HG11-
105 eps

mechanical interlocking of two


3TL6 contactors up to 7.2 kV)
Rectifier module 3AX15 25-1F
R-HG11-106 eps

(accessory) with varistor


Varistor module 3AX15 26-0F
(accessory)
Rectifier 3TY5 694-2AA0

Adapting parts (accessories), for main conductor connection 3TY5 610-1AA0


1 set when substituting 3TL50 and 3TL51
contactors with 3TL61

3/6Siemens HG 11.21 1997


3TL6 Vacuum Contactors 3TL-
Vacuum Contactors-
as Universal Contactors

Internal connection diagrams

AC operation
Voltage range
110 V to 500 V AC
50/60 Hz -K1 1L1 3L2 5L3 -K1

HG11-2305b eps
E1
Opening delay -X1 A1 83 61 53 22 14 32 44
~
-R
35 ms 1 2
-H1 71 -H2 -G +
approximately 50 ms 47 48 17 18
A1 ~ 48
~ -K2S -K2E
250 70 ms -G -K1E -K1E A1
+ -K1M A2 47
Rectifier ~ A2
17
Resistor A2 -K2E
for economy circuit -K1E 72 18
A1
-X1 A2 84 62 54 21 13 31 43 E2
Auxiliary contact block 2T1 4T2 6T3 A2
4NO + 3NC or -K2E
6NO + 5NC A1
Vacuum contactor (with auxiliary contact 4NO + 3NC) Closing
without closing latching latching (optional)
Optional: rectifier module
or varistor module
Optional: with mechanical -K1 1L1 3L2 5L3 -K1
closing latching
HG11-2331a eps

-X1 A1 83 61 53 121 113 102 94 22 14 32 44 E1


1 -R 2 ~
-H1 71 -H2 -G +
47 48 17 18 48
~ -K2S A1 ~ -K2E
-G -K1E -K1E A1
+ -K1M A2 47
~ A2
17
A2 -K2E
-K1E 72 18
A1

3
-X1 A2 84 62 54 122 114 101 93 21 13 31 43 E2

2T1 4T2 6T3 A2


-K2E
A1
Vacuum contactor (with auxiliary contact 6NO + 5NC) Closing
without closing latching latching (optional)

48 47 17 18
-K2E -K2E
DC operation -K1 1L1 3L2 5L3 -K1
E1
HG11-2306b eps

Voltage range -X1 A1 83 61 53 22 14 32 44


1 -R 2
24 V to 220 V DC -H1 71 -H2
47 48 17 18
Opening delay -K2S A1
35 ms -K1E -K1E A1
A2
-K1M
approximately 50 ms A2
250 70 ms A2
-K1E
Resistor A1
72
E2
-X1 A2 84 62 54 21 13 31 43
for economy circuit
2T1 4T2 6T3 A2
Auxiliary contact block -K2E
4NO + 3NC or Vacuum contactor (with auxiliary contact 4NO + 3NC) A1 Closing
6NO + 5NC without closing latching latching (optional)

Optional: with mechanical 48 47 17 18

closing latching 1L1 3L2 5L3 -K2E -K2E


-K1 -K1
HG11-2332a eps

-X1 A1 83 61 53 121 113 102 94 22 14 32 44 E1


1 -R 2
-H1 71 -H2
47 48 17 18
-K2S A1
-K1E -K1E A1
-K1M A2
A2
A2
-K1E 72
A1
-X1 A2 84 62 54 122 114 101 93 21 13 31 43 E2

2T1 4T2 6T3 A2


-K2E
Vacuum contactor (with auxiliary contact 6NO + 5NC) A1 Closing
without closing latching latching (optional)

Legend -G Rectifier -K1M Solenoid-operated mechanism for vacuum contactor


-H1 Right-hand auxiliary contact block -K2S Unlatching solenoid (optional)
-H2 Left-hand auxiliary contact block -R Economy resistor
-K1 Vacuum contactor -X1 Terminal block for auxiliary conductor connection
-K1E Contactor relay for economy circuit

Siemens HG 11.21 19973/7


3TL 3TL6 Vacuum Contactors
Vacuum Contactors
as Universal Contactors

Circuit diagrams (examples)

AC operation
Momentary-contact control Maintained-contact control
Without mechanical -F -F
closing latching L1(L+) L1(L+)
-S0Q -K2E -K2E Without -K2E -K2E Without
Opening delay
time-delay time-delay
35 ms A1 A1 S S -K1 relay for A1 A1 S S -K1 relay for
approximately 50 ms -G ~ + minimum -G ~ + minimum
-S1Q -K1E -S1Q -K1E
250 70 ms -K2E ~ -R motor ~ -R motor
starting starting

HG11-2323a eps
Rectifier -K1M -K1E -K1M -K1E
HG11-2317 eps

time; open- time; open-


Resistor -K2E -K1E -K1M ing delay -K2E -K1E -K1M ing delay
<
35 ms <
35 ms
for economy circuit
A2 A2 A2 A2
N(L2,L-) Fig. 1 N(L2,L-) Fig. 4
-F -F
L1(L+) Without L1(L+)
Without
-S0Q -K2E time-delay -K2E time-delay
relay for relay for
A1 A1 -K1 A1 A1 -K1
minimum minimum
-G ~ + -K1E motor -G ~ + -K1E motor
-S1Q -S1Q
-K2E ~ -R starting ~ -R starting
time; open- time; open-

HG11-2324a eps
HG11-2318 eps

-K1M -K1E -K1M -K1E


ing delay ing delay
-K2E -K1E -K1M approx. -K2E -K1E -K1M approx.
50 ms 50 ms
A2 A2 A2 A2
N(L2,L-) Fig. 2 N(L2,L-) Fig. 5
-F -F
L1(L+) L1(L+)
-S0Q -K2E Without -K2E Without
time-delay time-delay

3
A1 A1 -K1 A1 A1 -K1
relay for relay for
-G ~ + -K1E minimum -G ~ + -K1E minimum
-S1Q -S1Q
-K2E ~ -R motor ~ -R motor
starting starting
HG11-2325a eps

-K1M -K1E
HG11-2319 eps

-K1M -K1E
time; open- time; open-
-K2E -K1E -K1M ing delay -K2E -K1E -K1M ing delay
-D 250 70 ms -D 250 70 ms
A2 A2 A2 A2
N(L2,L-) Fig. 3 N(L2,L-) Fig. 6

-F -F
L1(L+) L1(L+)
DC operation -S0Q -K2E -K2E Without -K2E -K2E Without
time-delay time-delay
Without mechanical A1 A1 S S -K1 relay for A1 A1 S S -K1 relay for
closing latching -K1M minimum -K1M minimum
-S1Q -K1E -S1Q -K1E
-K2E -R motor -R motor
Opening delay -K1E -K1E
starting starting
35 ms
HG11-2326a eps


HG11-2320 eps

-K1E -K1E
time; open- time; open-
approximately 50 ms -K2E -K1M ing delay -K2E -K1M ing delay
250 70 ms <
35 ms <
35 ms
A2 A2 A2 A2
Resistor Fig. 7 Fig. 10
for economy circuit N(L2,L-) N(L2,L-)
-F -F
L1(L+) Without L1(L+) Without
-S0Q -K2E time-delay -K2E time-delay
relay for relay for
A1 A1 -K1 minimum A1 A1 -K1 minimum
-K1M -K1E motor -S1Q -K1M -K1E motor
-S1Q
-K2E -R starting -R starting
-K1E time; open- -K1E time; open-
HG11-2327a eps

-K1E
HG11-2321 eps

Legend -K1E ing delay ing delay


-F Fuse -K2E -K1M approx. -K2E -K1M approx.
-K1 Vacuum contactor 50 ms 50 ms
A2 A2 A2 A2
-K2E External contactor relay Fig. 8 Fig. 11
(e.g. Siemens type 3TH4) N(L2,L-) N(L2,L-)
-F -F
-K1E Internal contactor relay L1(L+) L1(L+)
-K1M Solenoid-operated -S0Q -K2E Without -K2E Without
mechanism time-delay time-delay
A1 A1 -K1 relay for A1 A1 -K1 relay for
-R Economy resistor
-S1Q -K1M -K1E minimum -S1Q -K1M -K1E minimum
-G Rectifier -K2E -R motor -R motor
-D Free-wheeling diode -K1E starting -K1E starting
HG11-2328a eps

-K1E -K1E
HG11-2322 eps

time; open- time; open-


-S0Q External OPEN ing delay ing delay
pushbutton -K2E -K1M -K2E -K1M
-D 250 70 ms -D 250 70 ms
-S1Q External CLOSED A2 A2 A2 A2
pushbutton N(L2,L-) Fig. 9 N(L2,L-) Fig. 12

3/8Siemens HG 11.21 1997


3TL6 Vacuum Contactors 3TL-
Vacuum Contactors-
as Universal Contactors

Circuit diagrams (examples for motor start-up)

Short-circuit protection
by means of circuit- Main circuit Control circuit, momentary-contact control
breaker
3~50/60 Hz -F1
Control of a high-voltage L1 L1/L+
Legend
L2

HG11-2300 eps
motor with reversing L3
11 21 21
-F1 Fuse/m.c.b.
contactor combination -S3Q -K3M -K1M
12 22 22 -K1M, Vacuum contactors
for 2 directions of -Q1F -K2M,
rotation 11 11 21 21
-K4M -K2M -K3M,
-S2Q -S1Q
with four 3TL6 contactors 12 12 22 22
-K4M
13 13 -K5A, Contactor relays
-K1M -K3M 13 13 23 23
-S1Q -K5A -S2Q -K6A -K5A -K6A -K6A
14 14 14 14 24 24 -M1 Motor
-K2M -K4M
-Q1F Circuit-breaker
41 41 13 13 -S1Q CLOSE pushbutton,
-K6A -K5A -K1M -K3M direction of rotation 1
42 42 14 14
U1 V1 W1 -S2Q CLOSE pushbutton,
HG11-2301a eps

-K5A A1 -K6A A1 -K1M A1 -K2M A1 -K3M A1 -K4M A1


M direction of rotation 2
-M1
3~ A2 A2 A2 A2 A2 A2 -S3Q OPEN pushbutton
N(L2)/L-

Main circuit Control circuit, momentary-contact control

Short-circuit protection 3~50/60 Hz -F1


by means of HV HRC L1 L1/L+
Legend
L2

HG11-2298 eps
fuses 11 21 21

3
L3 -F1 Fuse/m.c.b.
-S3Q -K3M -K1M
Control of a high-voltage -F1F 12 22 22 -F1F HV HRC fuses
motor with reversing 11 11 -K1M, Vacuum contactors
contactor combination -S2Q -S1Q -K3M
12 12
for 2 directions of -K5A, Contactor relays
rotation 13 13 13 13 21 21 -K6A
with two 3TL6 contactors -S1Q -K5A -S2Q -K6A -K5A -K6A -M1 Motor
-K1M -K3M 14 14 14 14 22 22
-S1Q CLOSE pushbutton,
direction of rotation 1
41 41 -S2Q CLOSE pushbutton,
-K6A -K5A
42 42 direction of rotation 2
U1 V1 W1
HG11-2299a eps

-K5A A1 -K6A A1 -K1M A1 -K3M A1 -S3Q OPEN pushbutton


M
-M1
3~ A2 A2 A2 A2
N(L2)/L-

Overload protection by Short-circuit protection by Short-circuit protection by


means of overload relays means of HV HRC fuses means of circuit-breakers
Overload and short-
circuit protection 3~50/60 Hz L1 3~50/60 Hz 3~50/60 Hz
L1 L2 L3 L1 L1
N
for 1 direction of rotation L2 L2
with one 3TL6 contactor 1 L3 L3
HG11-2295b eps
HG11-2296a eps

-S1 1 5

-S0

2 2

4
M M
2
3~ 3~

3 Legend
1 HV HRC fuses
2 Vacuum contactor
HG11-2297a eps

M 3 Main current transformer


3~ 4 Overload relay
5 Circuit-breaker

Siemens HG 11.21 19973/9


3TL 3TL6 Vacuum Contactors
Vacuum Contactors
as Universal Contactors

Dimensions and weights

3TL6 vacuum contactors

7
for AC and DC operation

37
4
1
Weights
Rated Vacuum Weight
voltage contactor
kV type approx. kg

210*
288
325

256
7.2 3TL61 28
12 3TL65 30
2

39*
12
42

16
30 11 68
Legend

HG11-2116b eps
120 120 50 236*
1 Travel of the integral rocker 250 265
during switching operation for
340 280
external interlock and position
indicator; max. permissible 3TL61 vacuum contactor
counterforce 10 N

7
2 Opening for insertion of aux-
iliary wires into central terminal

37
block 4
3 Mechanical unlatching, bolt

3
with internal thread 1
M5 x 10
4 Terminal block withdrawn (only
possible with 3TL63 -
contactor)

254*
288
325

256

12

17*
42
16

30 11 68

HG11-2128b eps
120 120 50 236*
250 265
* Fixing dimensions 340 280
3TL65 vacuum contactor

5 5
11

Adapter parts 6 6
for 3TL61 vacuum contac- 12
tor (replacement for 3TL50 7
and 3TL51 contactors)

Legend
256

5 System-internal conductor rails


6 Set of adapter parts 3TY5 618-0
7 Mounting 3TL5 and 3TL6
8 New mounting 3TL6
HG11-2115b eps

9 Insulating plate 8
10 Previous mounting 3TL5
12
11 New terminal 3TL6
44

6 9 6
12 Previous terminal 3TL5
5
13 Terminal 3TL5 5 13
and new terminal 3TL6 107 107 10 175

3/10Siemens HG 11.21 1997


3TL6 Vacuum Contactors 3TL-
Vacuum Conductors-
as Universal Contactors

Shipping

Packaging Package type Destination


The 3TL6 vacuum contac- Germany Europe Overseas Overseas/Europe
tors are packed in accord- Shipping Shipping Shipping Shipping
ance with the customers by means of by means of by means of by means of
order specifications and truck rail truck rail ship air freight
shipped anywhere in the Individual package
world in the mode deter- Lot-size package
mined by the customer.
Cardboard box with inner box
If the customer has not to suit unit
specified the manner of Cardboard box with sealed packaging
packaging and mode of and inner box to suit unit
shipping, the most
economic option is chosen Skeleton container with cardboard
boxes and inner box to suit unit
depending on the size of
the lot ordered. Plywood box + cardboard boxes
with sealed packaging and inner
box to suit unit

Preferred package type

Package type for no. of Length Width Height Volume Gross weight
vacuum contactors mm mm mm m3 kg
Shipping dimensions
and weights Cardboard box with inner box 1 500 400 400 0.08 32
to suit unit 2 840 570 640 0.3 87
Shipping by truck 34 920 820 930 0.7 137 170
or rail 58 1120 820 950 0.87 197 293
Cardboard box with sealed packaging
and inner box to suit unit
12
34
58
840
920
1120
570
820
820
640
930
950
0.3
0.7
0.87
92
142 175
202 298
3
Skeleton container with cardboard 38 1200 800 800 0.77 176 333
boxes and inner box to suit unit
Plywood box + cardboard boxes 12 920 620 670 0.38 59 91
with sealed packaging and inner 34 920 820 930 0.7 141 173
box to suit unit 58 1220 860 960 1.0 205 305

Shipping by ship Package type for no. of Length Width Height Volume Gross weight
vacuum contactors mm mm mm m3 kg
Cardboard box with inner box
to suit unit
Cardboard box with sealed packaging 12 840 570 640 0.3 92
and inner box to suit unit 34 920 820 930 0.7 142 175
58 1120 820 950 0.87 202 298
Skeleton container with cardboard
boxes and inner box to suit unit
Plywood box + cardboard boxes 12 920 620 670 0.38 59 91
with sealed packaging and inner 34 920 820 930 0.7 141 173
box to suit unit 58 1220 860 960 1.0 205 305

Shipping by air freight Package type for no. of Length Width Height Volume Gross weight
vacuum contactors mm mm mm m3 kg
Cardboard box with inner box 1 500 400 400 0.08 32
to suit unit 2 840 570 640 0.3 87
34 920 820 930 0.7 137 170
58 1120 820 950 0.87 197 293
Cardboard box with sealed packaging 12 840 570 640 0.3 92
and inner box to suit unit 34 920 820 930 0.7 142 175
58 1120 820 950 0.87 202 298
Skeleton container with cardboard
boxes and inner box to suit unit
Plywood box + cardboard boxes 12 920 620 670 0.38 59 91
with sealed packaging and inner 34 920 820 930 0.7 141 173
box to suit unit 58 1220 860 960 1.0 205 305

Siemens HG 11.21 19973/11


3TL 3TL6 Vacuum Contactors
Vacuum Contactors
as Universal Contactors
Ple
ase
Enquiry form c
c pyo
o th
y mp is f
To your Siemens office Your personal details r our r lete orm
et e it
Company Siemens AG Company off urn i quire acco
Department Department
ice t to me rdin
yo nts g t
Name Name ur o
Sie
Street Street me
ns
City, postal code City, postal code
Fax Tel.
Fax

We request the following:  Quotation  Call  Visit  Order/Delivery

Technical Other requirements


specifications Vacuum contactor type  3TL61  3TL65 
See page 3/4. Rated operational voltage  7.2 kV  12 kV 
Rated frequency  50/60 Hz  50/60 Hz 
Rated normal current  450 A  450 A 
Rated short-time current  8 kA  8 kA 
Rated capacitor current  250 A  250 A 
Switching frequency  1200/h  600/h 
Mechanical service life  3 mill.  1 mill. 
of the contactor

3 Mechanical service life


of the vacuum interrupter
 2 mill.  1 mill. 

Electrical service life  1 mill.  0.5 mill. 


of the vacuum interrupter
Chopping current 5A 5A 
Max. permissible switching capacity  5 kA  5 kA 

Additional/secondary Central terminal block, auxiliary contacts  4NO+3NC  6NO+5NC 


equipment Withdrawable terminal block, auxiliary contacts  6NO+5NC
See page 3/5. Without additional modules  
Mechanical closing latching  with  without
Mechanical closing lock-out  with  without
f-release  with  without
Operating voltage of  _____V AC  _____ V DC 
the solenoid _____Hz
Operating voltage for releasing the  _____V AC  _____ V DC 
mechanical closing latching _____Hz
Operating instructions  German / English 
 French / Spanish
Routine test report  German / English 
Break times Standard:  50 ms 
Special versions:  35 ms  120 ms  250 ms  120/50 ms

Order No. 3 T L 6
Quantity

Field of application  Motors


and other  Transformers
requirements
 Reactors
 Ohmic loads
 Capacitors
 Filter circuits

3/12Siemens HG 11.21 1997


Appendix

Contents Page

Catalog Index A/2 A/4

Conditions of Sale
and Delivery,
Export Regulations,
Trademarks,
Dimensions A/6

Customer
Training Program

Siemens HG 11.21 1997A/1


3TL Catalog Index Please contact your
Siemens Representative
Vacuum Contactors

Catalog Index of the Power Transmission and Distribution Group

Title Designation Order No.

High Voltage High-Voltage Equipment (Above 52 kV)


Type 3EM2 Surge Arresters with Current-Limiting Series Spark Gap
for HV System Voltages up to 245 kV HG 21.3.1 E86010-K1521-A311-A1-7600
Type 3EM3 Surge Arresters with Current-Limiting Series Spark Gap
for HV System Voltages up to 525 kV HG 21.3.2 E86010-K1521-A321-A1-7600
Type 3EP2 Surge Arresters without Gaps for HV System Voltages
up to 362 kV HG 21.3.4 E50001-K1521-A341-A1-7600
Type 3EP3 Surge Arresters without Gaps for HV System Voltages
up to 525 kV HG 21.3.5 E86010-K1521-A351-A1-7600
Surge Counting Devices for Surge Arresters HG 21.4 E50001-K1521-A401-A1-7600
High-Voltage Porcelain Insulators HG 23 E50001-K1523-A101-A2-7600

Medium Voltage Medium-Voltage Switchgear (High-Voltage Indoor Distribution Switchgear)


Metal-Enclosed Truck-Type Switchboards
for Indoor Installation 8BC1, 8BD1 HA 21 E86010-K1421-A101-A3-7600
Type 8BK20 Switchgear up to 24 kV
with Withdrawable Circuit-Breakers (Metal-Clad) HA 25.21 E50001-K1425-A311-A5-7600
Type 8BK40 Switchgear up to 17.5 kV/63 kA with
Withdrawable Circuit-Breakers HA 25.31 E50001-K1425-A411-A2-7600
Generator Circuit-Breaker Units up to 17.5 kV/80 kA, Type 8BK41 HA 25.41 E50001-K1425-A511-A1-7600
Type 8BJ50 Switchgear up to 24 kV with Withdrawable Circuit-Breakers* HA 25.61 E50001-K1425-A711-A2-7600
36/38 kV Switchgear
with Withdrawable Vacuum Circuit-Breakers, HA 26.1 Siemens Den Haag,
Type 8BK20 Dept.CMS DMS
Type 8BK30 Switchgear up to 12 kV
with Draw-Out Vacuum Contactors HA 27.11 E50001-K1427-A111-A2-7600
Panels up to 36 kV with Fixed-Mounted Circuit-Breakers,
SF6-Insulated, Types 8DA10 and 8DB10
Single-Pole, Metal-Enclosed, Metal-Clad
Single-Busbar Switchgear
Duplicate-Busbar Switchgear HA 35.11 E50001-K1535-A101-A6-7600
Type 8DC11 Panels up to 24 kV, Fixed-Mounted Vacuum

A Circuit-Breaker Switchgear, SF6-Insulated


Spline-Shaft Drive 8UG for Torque Transmission up to 200 Nm
Motor Drive 8UH for Torque Requirements up to 250 Nm
HA 35.41
HA 39.1
HA 39.3
E50001-K1435-A401-A3-7600
E86010-K1439-A111-A2-7600
E86010-K1439-A131-A1-7600
Fixed-Mounted Ring-Main Units up to 24 kV, SF6-Insulated,
Type 8DH10 HA 41.11 E50001-K1441-A101-A2-7600
Fixed-Mounted Ring-Main Units up to 24 kV, SF6-Insulated,
Type 8DJ10 HA 45.11 E50001-K1445-A111-A6-7600
Type 8FB1 Compact Transformer Substations up to 24 kV HA 51.1 E50001-K1451-A111-A2-7600
Factory-Built Container Stations, Type 8FF1 HA 52.1 E50001-K1452-A111-A1-7600

Medium-Voltage Equipment (High-Voltage Equipment up to 52 kV)


3AH Vacuum Circuit-Breakers HG 11.11 E50001-K1511-A111-A3-7600
3TL Vacuum Contactors HG 11.21 E50001-K1511-A211-A1-7600
Disconnectors and Earthing Switches HG 11.31 E50001-K1511-A311-A1-7600
Vacuum Switches, Switch-Disconnectors, HV HRC Fuse HG 12 E50001-K1512-A101-A4-7600
Switchgear Interlock Units, Control Valves,
Compressed Air Systems HG 13 E86010-K1513-A101-A1-7600
Overvoltage Protection HG 21 E50001-K1521-A101-A1-7600
Insulators of Cast Resin (Excerpt) HG 22 E50001-K1522-A111-A1-7600
Current and Voltage Transformers HG 24 E50001-K1524-A101-A2-7600
Air-Cored Reactors, High-Voltage Capacitors HG 25 E86010-K1525-A101-A4-7600

Low Voltage Power Factor Correction


Low-Voltage Power Capacitors and Power Factor Correction Units
Selection and Ordering Data K1.2 E50001-K1600-A121-A5-7600

Power Cables Power Cables


Flexible Electric Cables for Cranes and Material Handling Equipment SK 1.12 E50001-K8112-A101-A1-7600
SIENOPYR Power Cables SK 3.30 E50001-K8133-A101-A1-7600
Installation Cables, Power Cables SK 3.40 E50001-K8134-A101-A1-7600
Special-Purpose Cables for Industrial Applications SK 4.20 E50001-K8142-A101-A1-7600

Stand 07.10.1997 (VO)

A/2Siemens HG 11.21 1997


Please contact your
Siemens Representative Catalog Index 3TL-
Vacuum Contactors-

Title Designation Order No.

Protection and Numerical Protective Relaying


Substation Numerical Protection Devices LSA 2.0.1 E50001-K5702-A011-A1-7600
Control Systems
Operation and Evaluation Software for Numerical Protection Devices LSA 2.0.2 E50001-K5702-A121-A1-7600
Relay Selection Guide LSA 2.0.3 E50001-K5702-A031-A1-7600
SIPROTEC 7SJ600 Overcurrent, Motor and Overload Protection LSA 2.1.15 E50001-K5712-A251-A2-7600
SIPROTEC 7SJ601 Overcurrent Protection LSA 2.1.16 E50001-K5712-A261-A1-7600
7SJ41 Definite-Time Overcurrent Protection Relay LSA 2.1.10 E50001-K5712-A201-A2-7600
7SJ511 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.3 E50001-K5712-A131-A3-7600
7SJ512 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.4 E50001-K5712-A141-A3-7600
7SJ512 Numerical Feeder Protection LSA 2.1.30 E50001-K5712-A411-A1-7600
SIPROTEC 7SJ531 Numerical Line and Motor Protection with
Control Function LSA 2.1.9 E50001-K5712-A191-A3-7600
7SJ551 Multi-Function Protection Relay LSA 2.4.2 E50001-K5742-A121-A3-7600
SIPROTEC 7SA510 Distance Protection Relay (Version V3) LSA 2.1.17 E50001-K5712-A271-A1-7600
SIPROTEC 7SA511 Distance Protection Relay (Version V3) LSA 2.1.11 E50001-K5712-A211-A2-7600
7SA513 Line Protection Relay (Version V3) LSA 2.1.12 E50001-K5712-A221-A1-7600
7SA518/519 Overhead Control-Line Protection Relay (Version V3) LSA 2.1.14 E50001-K5712-A241-A1-7600
3VU13 Miniature Circuit-Breaker LSA 2.1.8 E50001-K5712-A181-A2-7600
7SD502 Line Differential Protection with Two Pilot Wires LSA 2.2.1 E50001-K5722-A111-A2-7600
7SD503 Line Differential Proteciton with Three Pilot Wires LSA 2.2.2 E50001-K5722-A121-A2-7600
7SD511/512 Current Comparison Protection Relay (Version V3)
for Overhead Lines and Cables LSA 2.2.3 E50001-K5722-A131-A2-7600
7UT512/513 Differential Protection Relay (Version V3)
for Transformers, Generators and Motors LSA 2.2.4 E50001-K5722-A141-A2-7600
7SS5 Station Protection LSA 2.2.5 E50001-K5722-A151-A2-7600
Auxiliary Current Transformers 4AM50, 4AM51, 4AM52
and Isolating Transformers 7XR95 LSA 2.2.6 E50001-K5722-A161-A1-7600
Introduction to Earth-Fault Detection LSA 2.3.1 E50001-K5732-A111-A1-7600
7SN71 Transient Earth-Fault Relay LSA 2.3.2 E50001-K5732-A121-A1-7600

A
7XR96 Toroidal Current Transformer LSA 2.3.3 E50001-K5732-A131-A1-7600
7VC1637 Earth-Leakage Monitor LSA 2.3.4 E50001-K5732-A141-A1-7600
Introduction to Generator Protection LSA 2.5.1 E50001-K5752-A111-A1-7600
7UM511 Generator Protection Relay (Version V3) LSA 2.5.2 E50001-K5752-A121-A2-7600
7UM512 Generator Protection Relay (Version V3) LSA 2.5.3 E50001-K5752-A131-A2-7600
7UM515 Generator Protection Relay (Version V3) LSA 2.5.4 E50001-K5752-A141-A2-7600
7UM516 Generator Protection Relay (Version V3) LSA 2.5.5 E50001-K5752-A151-A1-7600
7UW50 Tripping Matrix LSA 2.5.6 E50001-K5752-A161-A1-7600
7VE51 Synchronizing Unit LSA 2.5.7 E50001-K5752-A171-A1-7600
7VP151 Three-Phase Portable Test Set (Omicron CMC56) LSA 2.6.1 E50001-K5762-A111-A2-7600
7XV72 Test Switch LSA 2.6.2 E50001-K5762-A121-A1-7600
7SV50 Numerical Circuit-Breaker Failure Protection Relay LSA 2.7.1 E50001-K5772-A111-A1-7600
7SV512 Numerical Circuit-Breaker Failure Protection Relay LSA 2.7.2 E50001-K5772-A121-A1-7600
7VK512 Numerical Auto-Reclose/Check-Synchronism Relay LSA 2.7.3 E50001-K5772-A131-A1-7600
7SM70 Analog Output Unit LSA 2.7.5 E50001-K5772-A151-A1-7600
7SM71 Analog Output Unit LSA 2.7.6 E50001-K5772-A161-A1-7600
7VR50 Protection Signalling Equipment for
Digital Communication Links LSA 2.7.7 E50001-K5772-A171-A1-7600
7SV7220 Power Supply Unit LSA 2.7.9 E50001-K5772-A191-A1-7600
SIPROTEC 7RW600 Numerical Voltage, Frequency and
Overexcitation Relay LSA 2.7.10 E50001-K5772-A201-A1-7600
Centralized and Remote Control of Siemens Protection Relays (Overview) LSA 2.8.1 E50001-K5782-A111-A1-7600
Operating and Analysis Software DIGSI V3 LSA 2.8.2 E50001-K5782-A121-A1-7600

Transformers Distribution Transformers


GEAFOL Buchholz Relays to DIN 42 566 with Change-over Contacts A19100-T5101-A9A-7600
Cast-Resin Transformers 100 to 2500 kVA TV 1 E50001-K7101-A101-A2-7600
TUMETIC and TUNORMA Oil-Immersed Distribution Transformers
50 to 2500 kVA TV 2 E50001-K7102-A101-A1-7600

Stand 07.10.1997 (VO)

Siemens HG 11.21 1997A/3


3TL Catalog Index Please contact your
Siemens Representative
Vacuum Contactors

Catalog Index of the Power Transmission and Distribution Group

Title Designation Order No.

Protection and Measurement and Recording Systems


Substation Fault Recorder OSCILLOSTORE SR 10.1 E50001-K4010-A101-A1-7600
Control Systems Power System Quality Analysis OSCILLOSTORE SR 10.2 E50001-K4020-A101-A1-7600

Analog Protective Relaying


Static Analog Network Protection Relays R 1.1 E50001-K4501-A111-A1-7600
Static Analog Machine Protection Relays R 1.2 E50001-K4501-A121-A1-7600
Static Analog Ancillary Protection Equipment R 1.3 E50001-K4501-A131-A1-7600
Hand and Electrical Reset Tripping Relay 7PA20 R (Extract) E86010-K4500-A151-A1-7600
Trip Circuit Supervision Relay 7PA21 R (Extract) E86010-K4500-A161-A1-7600
Pilot-Wire Differential Relay 7SD24 R (Extract) E86010-K4500-A131-A1-7600
Microprocessor Based Overcurrent Relay 7SJ55 R (Extract) E50001-K4500-A361-A2-7600
High-Speed Busbar Differential Relay 7SS10 R (Extract) E50001-K4500-A241-A2-7600
High Impedance Differential Relay 7VH80 R (Extract) E86010-K4500-A321-A1-7600
Auto-Reclose Relay 7VK14 R (Extract) E86010-K4500-A141-A1-7600

Substation Control and Protection


Input/Output Unit 6MB522 LSA 1.1.1 E50001-K5701-A111-A4-7600
Input/Output Unit 6MB523 LSA 1.1.2 E50001-K5701-A121-A2-7600
6MB511/6MB512 Substation Control Master Unit and
7SW511/7SW512 Relay Data Concentrator LSA 1.1.3 E50001-K5701-A131-A2-7600
6MB520/6MB521 Input/Output Units LSA 1.1.4 E50001-K5701-A141-A1-7600
6MB513/514 Compact Control Master Unit
and Relay Data Concentrator LSA 1.1.6 E50001-K5701-A161-A1-7600
6MB524 Bay Control Unit LSA 1.1.7 E50001-K5701-A171-A1-7600
6MB525 Mini Bay Unit (MBU) LSA 1.1.8 E50001-K5701-A181-A1-7600
6MB5510 Station Control Unit LSA 1.2.1 E50001-K5701-A211-A2-7600
6MB552 Compact Remote Terminal Unit LSA 1.2.2 E50001-K5701-A221-A1-7600
6MB5530-0 Minicompact Remote Terminal Unit LSA 1.2.3 E50001-K5701-A231-A1-7600

A 6MB5530-1 Minicompact Remote Terminal Unit for


Cable Shield Communication
6MB5540 SINAUT LSA COMPACT Remote Terminal Unit
LSA 1.2.4
LSA 1.2.5
E50001-K5701-A241-A1-7600
E50001-K5701-A251-A1-7600
6MB5515 Station Control Unit LSA 1.2.6 E50001-K5701-A261-A1-7600
Control in SINAUT LSA Substation Control and Protection LSA 1.4.1 E50001-K5701-A411-A1-7600
Status Indications in SINAUT LSA Substation Control and Protection LSA 1.4.2 E50001-K5701-A421-A1-7600
Analog Values in SINAUT LSA Substation Control and Protection LSA 1.4.3 E50001-K5701-A431-A1-7600
Metering in SINAUT LSA Substation Control and Protection LSA 1.4.4 E50001-K5701-A441-A1-7600
Voltage Control with Input/Output Units 6MB520/6MB521 LSA 1.4.5 E50001-K5701-A451-A1-7600
Network Synchronization with Input/Output Units 6MB520/521 LSA 1.4.6 E50001-K5701-A461-A1-7600
Operation with Two Control Master Units LSA 1.4.7 E50001-K5701-A471-A1-7600
Node Functions in SINAUT LSA Substation Control and Protection LSA 1.4.8 E50001-K5701-A481-A1-7600
System Management with the SINAUT LSA Substation Control
and Protection System LSA 1.4.9 E50001-K5701-A491-A1-7600
LSADIAG - Testing and Diagnostics System for SINAUT LSA LSA 1.5.2 E50001-K5701-A521-A1-7600
Substation Control and Protection
LSACONTROL - Control and Monitoring LSA 1.5.3 E50001-K5701-A531-A1-7600
LSAPROCESS - Process Information Analysis LSA 1.5.5 E50001-K5701-A551-A1-7600
LSA 678 Standard Cubicle LSA 1.6.1 E50001-K5701-A611-A1-7600

Energy Meters Energy Meters


7EC48 Solid-State 3-Phase Meter with Drum-Type Registers Z 9.1.1 E50001-K8991-A101-A1-7600
7E.62/63 Static Multifunction Meters Z 9.1.2 E50001-K8991-A111-A2-7600
7EC49 Electronic 3-Phase Meter with Drum-Type Registers Z 9.1.3 E50001-K8991-A121-A1-7600
7EC60/61 Multi-Tariff Maximum Demand Meter Z 9.1.4 E50001-K8991-A131-A1-7600
7E.64/65 Electronic Precision Meters Z 9.1.5 E50001-K8991-A141-A1-7600
DATAREG 48 Data Recording and Transmission Unit Z 9.2.2 E50001-K8992-A111-A1-7600
7FM803/804 Universal Tariff Unit Z 9.2.3 E50001-K8992-A121-A1-7600

Stand 07.10.1997 (VO)

A/4Siemens HG 11.21 1997


Notes 3TL-
Vacuum Contactors-

Siemens HG 11.21 1997A/5


Vakuum-
3TL
Leistungsschalter
Conditions of Sale and Delivery
Vacuum Contactors
3AH

Conditions of Sale and Delivery

Subject to the 
General Conditions of Supply
The technical data, dimensions We reserve the right to adjust
and Delivery
and weights are subject to the prices and shall charge the
for Products and Services of
change unless otherwise prices applying on the date of
the Electrical and Electronic
stated on the individual pages delivery.
Industry and to any other
conditions agreed upon with of this catalog.
the recipients of catalogs. The illustrations are for
reference only. A En 1.91a

Export Regulations Trademarks Dimensions

In accordance with the present An export licence may however All product designations used All dimensions in this catalog
provisions of the German Export be required due to country- are trademarks or product are given in mm.
List and the US Commercial specific application and final names of Siemens AG or of
Control List, export licences are destination of the products. other suppliers.
not required for the products
Relevant are the export criteria
listed in this catalog.
stated in the delivery note and
the invoice regarding a possible
export and reexport licence.
Subject to change without notice.

Responsible for:
Technical contents: General editing:
Hermann Bierfelder, Gabriele Pollok,
Siemens AG, Dept. EV MNK V, Siemens AG, Dept. EV BK T,
Erlangen Erlangen
Printed in Germany
A/6Siemens HG 11.21 1997 KGK 1297 5.0 40 En 100080 6101/U662
Our
Customer Training Program

It is worthwhile and im-


portant for every user to
be knowledgeable about Medium-voltage Technical
switchgear used.
technology information course
Besides our products, we
therefore offer training Switching devices and Medium-voltage
courses on all application switchgear circuit-breakers
and functional aspects
of our vacuum circuit-
breakers. The course provides planning and The course provides information
selection criteria for switching on medium-voltage vacuum circuit-
Engineers and technicians devices and switchgear in medium- breakers, covering the salient
will receive extensive voltage systems. technical aspects.
information on planning
and selection of switching It is intended for engineers and It is intended for operating and
devices and switchgear, technicians working for the power maintenance personnel, field service
while operating and main- supply in industry and public utilities. staff and engineers.
tenance personnel will
learn all about the techno- Focal Focal
logy, design, layout and points points
functions.
 Principles of switching devices  Modules
Are you interested? Yes.  Types of switching devices  Function and operating
Then copy this page,  Planning of switchgear mechanism principles
enter the information  Types of switchgear  Control and monitoring
requested and send it to  Switchgear accessories  Maintenance and service
your Siemens office.  Environmental protection

We will then send you


further information. Organization Organization

Siemens AG Siemens AG
Dept. SQT FSK, Mrs. Gulden Dept. EV HWS, Mrs. Buerlein
P.O.Box 32 40 P.O.Box 32 20
D-91050 Erlangen D-91050 Erlangen
Germany Germany
Tel.: (++49) 91 31/7-4 38 05 Tel.: (++49) 91 31/7-3 36 04
Fax: (++49) 91 31/7-4 35 09 Fax: (++49) 91 31/7-3 44 49

Duration Duration

2 days 1 week

Location Location

In the Erlangen area Berlin, Training centre


or locally

To your Siemens office Your data Your data

Company Siemens AG Company Company


Department Department Department
Name Name Name
Street Street Street
City City City
Fax Fax Fax