You are on page 1of 4

Relay Data

Relay 1 Relay 2 Relay 3 Relay 4


Main Electroboost
Tram Sub Recloser
Relay Name Incomer Tx
(Existing) (Existing)
(Existing) (Existing)
Voltage (kV) 22 22 22 22
Relay Type 7SJ 6111 Nulec ABB PR521 ABB PR521
Primary CT Ratio 800 50 50 50
Secondary Rating Ratio (In) 1 1 1 1
Curve type IEC-VI IEC-VI DT DT
Ipu (Sec.Amps) 0.2 1 0.15 0.15
CURVE 1

Tms or TD 0.3 0.05 0.4 0.4


High Set (Sec.Amps) 7 14 10000 10000
Scale Limit Multiplier 30 30 30 30
Ipu (Prim.Amps) 160 50 7.5 7.5
Iinst (Prim.Amps) 5600 700 N/A N/A

Relay 1 Relay 2 Relay 3 Relay 4


Main Electroboost
Tram Sub Recloser
Relay Name Incomer Tx
(Existing) (Existing)
(Existing) (Existing)
Voltage (kV) 22 22 22 22
Relay Type 7SJ 6111 Nulec ABB PR521 ABB PR521
Primary CT Ratio 800 50 50 50
Secondary Rating Ratio (In) 1 1 1 1
Curve type IEC-VI IEC-VI DT DT
Ipu (Sec.Amps) 0.2 1 0.7 0.5
CURVE 1

Tms or TD 0.3 0.2 0.1 0.1


High Set (Sec.Amps) 7 25 10000 10000
Scale Limit Multiplier 30 30 30 30
Ipu (Prim.Amps) 160 50 35 25
Iinst (Prim.Amps) 5600 700 N/A N/A

Relay 1 Relay 2 Relay 3 Relay 4


Main Electroboost
Tram Sub Recloser
Relay Name Incomer Tx
(Existing) (Existing)
(Existing) (Existing)
Voltage (kV) 22 22 22 22
Relay Type 7SJ 6111 Nulec ABB PR521 ABB PR521
Primary CT Ratio 800 150 250 80
Secondary Rating Ratio (In) 1 1 1 1
Curve type IEC-VI IEC-VI DT DT
Ipu (Sec.Amps) 1 1 1 1
CURVE 1
CURVE 1 Tms or TD 0.15 0.05 1.6 1.6
High Set (Sec.Amps) 7 5 8 8
Scale Limit Multiplier 30 30 30 30
Ipu (Prim.Amps) 800 150 250 80
Iinst (Prim.Amps) 5600 750 2000 640

Relay 1 Relay 2 Relay 3 Relay 4


Main Electroboost
Tram Sub Recloser
Relay Name Incomer Tx
(Existing) (Existing)
(Existing) (Existing)
Voltage (kV) 22 22 22 22
Relay Type 7SJ 6111 Nulec ABB PR521 ABB PR521
Primary CT Ratio 800 300 250 80
Secondary Rating Ratio (In) 1 1 1 1
Curve type IEC-VI IEC-VI IEC-VI IEC-VI
Ipu (Sec.Amps) 1 1 1 1
CURVE 1

Tms or TD 0.15 0.3 0.2 0.4


High Set (Sec.Amps) 7 9 9 17
Scale Limit Multiplier 30 30 30 30
Ipu (Prim.Amps) 800 300 250 80
Iinst (Prim.Amps) 5600 2700 2250 1360
Relay 5 Relay 6 Relay 7 Relay 8 Relay 9 Relay 10

MSB1 Tx MSB2 Tx Bus-tie


Not Used Not Used Not Used
(Existing) (Existing) (Existing)

22 22 22
ABB PR521 ABB PR521 ABB PR521
50 50 50
1 1 1
DT DT DT
0.15 0.15 0.15
0.75 0.4 0.4
10000 10000 10000
30 30 30
7.5 7.5 7.5
N/A N/A N/A

Relay 5 Relay 6 Relay 7 Relay 8 Relay 9 Relay 10

MSB1 Tx MSB2 Tx Bus-tie


Not Used Not Used Not Used
(Existing) (Existing) (Existing)

22
ABB PR521
50
1
DT
0.7
0.1
10000
30
35
N/A

Relay 5 Relay 6 Relay 7 Relay 8 Relay 9 Relay 10

MSB1 Tx MSB2 Tx Bus-tie


Not Used Not Used Not Used
(Existing) (Existing) (Existing)

22 22 22
ABB PR521 ABB PR521 ABB PR521
80 80 250
1 1 1
IEC-SI DT DT
1 1 1
0.2 1.6 1.6
9 9 8
30 30 30
80 80 250
720 720 2000

Relay 5 Relay 6 Relay 7 Relay 8 Relay 9 Relay 10

MSB1 Tx MSB2 Tx Bus-tie


Not Used Not Used Not Used
(Existing) (Existing) (Existing)

22
ABB PR521
250
1
IEC-VI
1
0.2
9
30
250
2250

You might also like