You are on page 1of 32

Power Plant Generating Power : 45 MW

Generator Power/Unit : 5587 kW


Generator Unit Required : 8.05 Unit
Generator Unit Installed : 9 Unit
Total Plant Generated Power : 50283 kW; 50.283 MW
Generator Output Voltage : 11 kV
Power Factor : 0.8
Full Load Current : 366.5626 Ampere
Safety Factor (+25%) : 458.2032 Ampere
Bus Duct/Cable Rating Selected* : 1000 Ampere
Circuit Breaker Selected : 1000 Ampere

Number of Parallel Generator : 3 Unit Total Step Up Transformer


Total Generated Power : 16761 kW; 20951.250 kVA
Generator Transformer Selected : 22000 kW; 27500 kVA
Power Factor : 0.8
Vector Group : Ynd-
Low Voltage Side* : 11 kV
High Voltage Side** : 20 kV
Full Load Current* : 1443.418 Ampere
Safety Factor (+25%)* : 1804.273 Ampere
Bus Duct/Cable Rating Selected* : 2000 Ampere
Circuit Breaker Selected* : 2000 Ampere
Busbar Selected* : 2500 Ampere
Full Load Current** : 793.8799 Ampere
Safety Factor (+25%)** : 992.3499 Ampere
Bus Duct/Cable Rating Selected** : 1250 Ampere
Circuit Breaker Selected** : 1250 Ampere
PLTG 45 MW

Engine Type

Engine
Rated Output
Generator
Alternator Efficiency
Speed
Frequency
Heat Rate
Electrical Efficiency

Material : Cu
Type : VCB

: 3

Type : Liquid Immersed

Material : Cu
Type : VCB

Material : Cu
Type : VCB
12H35/40GV
Engine Type
Output (kW)
5760 Engine
Rated Output
5587 Generator
96.5 97 % Alternator Efficiency
750 rpm Speed
50 Hz Frequency
7574 kJ/kWhe Heat Rate
47.50% Electrical Efficiency
12H35/40GV
Output (kVA)
7300
6983,75
96.5 97 %
750 rpm
50 Hz
7574 kJ/kWhe
47.50%
No. Description Rating Qty Unit

Gas Engine
1 5587 kW 9 ea
Generator

Generator
2 25 MVA 3 ea
Transformer

Unit Auxiliary
3 TBA 4 ea
Transformer

4 Diesel Generator 500 kVA 1 ea

5 11 kV Switchgear Varies 12 set


6 20 kV Switchgear Varies 19 set

7 LVMDP Varies TBA set

8 Battery Charger TBA TBA set

9 UPS TBA TBA set


SPESIFICATION

Output Voltage 11kV, Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35

Cable Data :
Output Cable

Liquid Immersed Transformer 25MVA, ONAN, IP35 11/20kV, Ynd-, Cu/Cu (Step Up)

Cable Data :
20kV side

11kV side

Dry Type Cast Resin Transformer , AN/AF, IP31, 20/0.4kV, Dyn5, Cu/Cu (Step Down)

Cable Data :
20kV side

0.4kV side

Diesel Engine Generator, output voltage 400V, 3 phase

Cable Data :
Output Cable

GIS, Aux. Voltage 48VDC, IP65, c/w protection relay and measurement
GIS, Aux. Voltage 48VDC, IP65, c/w protection relay and measurement

ACB, Rated Voltage 400V, Aux. Voltage 48VDC, IP54, c/w protection relay and measurement, outgo
feeder (TBA)

Industrial Charger input 400VAC, 48 VDC, Autonomy 4 hour (batt. 12VDC, 120AH/C10), surge arres

Industrial UPS, input 400/220 Vac, Output 220 VAC, Isolation transformer, Back-up Time (autonomy
Unitary configuration
SPESIFICATION

age 11kV, Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35

: N2XSY 3x3C-300mm2
: Entry Cable from Above

ersed Transformer 25MVA, ONAN, IP35 11/20kV, Ynd-, Cu/Cu (Step Up)

: NA2XSY 3x1C-95 mm2


: Entry Cable from Top
: N2XSY 4x3x3C-300mm2 + 1x1C-300mm2 for Neutral
: Entry Cable from Above

st Resin Transformer , AN/AF, IP31, 20/0.4kV, Dyn5, Cu/Cu (Step Down)

: TBA
: Entry Cable from Bottom
: TBA
: Entry Cable from Bottom

ne Generator, output voltage 400V, 3 phase

: N2XY 3X3x3C-950mm2
: Entryfrom Above

oltage 48VDC, IP65, c/w protection relay and measurement


oltage 48VDC, IP65, c/w protection relay and measurement

Voltage 400V, Aux. Voltage 48VDC, IP54, c/w protection relay and measurement, outgoing
)

harger input 400VAC, 48 VDC, Autonomy 4 hour (batt. 12VDC, 120AH/C10), surge arrester

PS, input 400/220 Vac, Output 220 VAC, Isolation transformer, Back-up Time (autonomy) 4 jam,
figuration
Remarks

Copper Cable

Copper Cable

Cooper Cable (4 cables/phase)

Copper Cable
Power Plant Generating Power : 45 MW
Generator Power/Unit : 8381 kW
Generator Unit Required : 5.37 Unit
Generator Unit Installed : 6 Unit
Total Plant Generated Power : 50286 kW; 50.286 MW
Generator Output Voltage : 11 kV
Power Factor : 0.8
Full Load Current : 549.8767 Ampere
Safety Factor (+25%) : 687.3458 Ampere
Bus Duct/Cable Rating Selected* : 1000 Ampere
Circuit Breaker Selected : 1000 Ampere

Number of Parallel Generator : 2 Unit Total Step Up Transformer


Total Generated Power : 16762 kW; 20952.500 kVA
Generator Transformer Selected : 20000 kW; 25000 kVA
Power Factor : 0.8
Vector Group : Ynd-
Low Voltage Side* : 11 kV
High Voltage Side** : 20 kV
Full Load Current* : 1312.198 Ampere
Safety Factor (+25%)* : 1640.248 Ampere
Bus Duct/Cable Rating Selected* : 2000 Ampere
Circuit Breaker Selected* : 2000 Ampere
Busbar Selected* : 2500 Ampere
Full Load Current** : 721.709 Ampere
Safety Factor (+25%)** : 902.1363 Ampere
Bus Duct/Cable Rating Selected** : 1250 Ampere
Circuit Breaker Selected** : 1250 Ampere
PLTG 45 MW

Engine Type

Engine
Rated Output
Generator
Alternator Efficiency
Speed
Frequency
Heat Rate
Electrical Efficiency

Material : Cu
Type : VCB

: 3

Type : Liquid Immersed

Material : Cu
Type : VCB

Material : Cu
Type : VCB
12H35/40GV
Engine Type
Output (kW)
8640 Engine
Rated Output
8381 Generator
96.5 97 % Alternator Efficiency
750 rpm Speed
50 Hz Frequency
7574 kJ/kWhe Heat Rate
47.50% Electrical Efficiency
12H35/40GV
Output (kVA)
10800
10476.25
96.5 97 %
750 rpm
50 Hz
7574 kJ/kWhe
47.50%
No. Description Rating Qty Unit

Gas Engine
1 8381 kW 6 ea
Generator

Generator
2 25 MVA 3 ea
Transformer

Unit Auxiliary
3 TBA 4 ea
Transformer

4 Diesel Generator 500 kVA 1 ea

5 11 kV Switchgear Varies 9 set


6 20 kV Switchgear Varies 19 set

7 LVMDP Varies TBA set

8 Battery Charger TBA TBA set

9 UPS TBA TBA set


SPESIFICATION

Output Voltage 11kV, Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35

Cable Data :
Output Cable

Liquid Immersed Transformer 25MVA, ONAN, IP35 11/20kV, Ynd-, Cu/Cu (Step Up)

Cable Data :
20kV side

11kV side

Dry Type Cast Resin Transformer , AN/AF, IP31, 20/0.4kV, Dyn5, Cu/Cu (Step Down)

Cable Data :
20kV side

0.4kV side

Diesel Engine Generator, output voltage 400V, 3 phase

Cable Data :
Output Cable

GIS, Aux. Voltage 48VDC, IP65, c/w protection relay and measurement
GIS, Aux. Voltage 48VDC, IP65, c/w protection relay and measurement

ACB, Rated Voltage 400V, Aux. Voltage 48VDC, IP54, c/w protection relay and measurement, outgo
feeder (TBA)

Industrial Charger input 400VAC, 48 VDC, Autonomy 4 hour (batt. 12VDC, 120AH/C10), surge arres

Industrial UPS, input 400/220 Vac, Output 220 VAC, Isolation transformer, Back-up Time (autonomy
Unitary configuration
SPESIFICATION

age 11kV, Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35

: N2XSY 3x3x3C-120mm2
: Entry Cable from Above

ersed Transformer 25MVA, ONAN, IP35 11/20kV, Ynd-, Cu/Cu (Step Up)

: NA2XSY 3x1C-95 mm2


: Entry Cable from Top
: N2XSY 4x3x3C-300mm2 + 1x1C-300mm2 for Neutral
: Entry Cable from Above

st Resin Transformer , AN/AF, IP31, 20/0.4kV, Dyn5, Cu/Cu (Step Down)

: TBA
: Entry Cable from Bottom
: TBA
: Entry Cable from Bottom

ne Generator, output voltage 400V, 3 phase

: N2XY 3X3x3C-950mm2
: Entryfrom Above

oltage 48VDC, IP65, c/w protection relay and measurement


oltage 48VDC, IP65, c/w protection relay and measurement

Voltage 400V, Aux. Voltage 48VDC, IP54, c/w protection relay and measurement, outgoing
)

harger input 400VAC, 48 VDC, Autonomy 4 hour (batt. 12VDC, 120AH/C10), surge arrester

PS, input 400/220 Vac, Output 220 VAC, Isolation transformer, Back-up Time (autonomy) 4 jam,
figuration
Remarks

Cooper Cable (3 cables/phase)

Copper Cable

Cooper Cable (4 cables/phase)

Copper Cable
No. Description Rating Qty Unit

1 Lighting 230V 1 lot

Receptacles &
2 - 1 lot
Plugs

2 Grounding - 1 lot
Lightning
3 - 1 lot
Protection

4 Cable Ladder/Tray - 1 lot

Installation Cable
6 400/230V 1 lot
Inside Building
SPESIFICATION

Output Volt- Lighting fixtures covers the following type of fixtures:


Building Utility Lighting
Plant lighting,
Street lighting.
age 11kV, Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35
High pressure sodium (HPS) fixtures shall be used for the type of fixtures specified above except for b
utility lighting. Lighting fixtures shall be suitable for 230V 50Hz single phase.

Plant lighting fixtures shall be made of copper free aluminum alloy, and be of high power factor type w
reflector made of polished aluminum. Their outputs shall be limited to HPS 70W, 100W, and 150W.

Emergency lighting fixture shall be equipped with instant re-strike ballast type.

Street lighting fixtures shall be made of materials suitable for outdoor and corrosive environmental as
the manufacturer standard, and be of high power factor type. Their output shall be limited to HPS 250

Lighting fixtures for outdoor use shall be minimum IP55.

- Convenience receptacles and plugs shall be rated 16A, 230V AC, and have two poles (phase and neu
earth.
- All convenience receptacles and plugs shall be suitable for the area classifications as per the applica
codes and standards.
- Convenience receptacles and plugs shall have minimum IP 55.
- Welding outlets and plugs shall be rated 63A, 400V AC, and have three poles (3 phases) + earth.
- All welding outlets and plugs shall be suitable for the area classifications as per the applicable codes
standards.
- Welding outlets and plugs shall have minimum IP 55.

- Welding outlets and socket shall be made of copper free aluminum alloy or Grass reinforced plastic (

Earthing cables shall be installed in the cable trench or along conduits as far as routing permits.

Earthing conductors shall be of PVC covered hard drawn stranded copper


Conventional Lightning Protection

Cable Ladder/Tray shall be corrosion resistant material.

NYY distributed inside PVC Conduit.

In the case where lubrication is necessary, a powder lubricant such as micapowder, or anti-seizing thr
lubricant shall be used.
In pulling cables, care shall be taken to avoid the kinking of conductors.

Conductors shall be connected In junction boxes, canopy boxes or pull boxes. No connection In elbows
or similar conduit fittings shall be permitted.
SPESIFICATION

Lighting fixtures covers the following type of fixtures:


tility Lighting
ing,
hting.
Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35
re sodium (HPS) fixtures shall be used for the type of fixtures specified above except for building
ng. Lighting fixtures shall be suitable for 230V 50Hz single phase.

g fixtures shall be made of copper free aluminum alloy, and be of high power factor type with
ade of polished aluminum. Their outputs shall be limited to HPS 70W, 100W, and 150W.

lighting fixture shall be equipped with instant re-strike ballast type.

ng fixtures shall be made of materials suitable for outdoor and corrosive environmental as per
cturer standard, and be of high power factor type. Their output shall be limited to HPS 250W

tures for outdoor use shall be minimum IP55.

ce receptacles and plugs shall be rated 16A, 230V AC, and have two poles (phase and neutral) +

ience receptacles and plugs shall be suitable for the area classifications as per the applicable
tandards.
ce receptacles and plugs shall have minimum IP 55.
utlets and plugs shall be rated 63A, 400V AC, and have three poles (3 phases) + earth.
g outlets and plugs shall be suitable for the area classifications as per the applicable codes and
utlets and plugs shall have minimum IP 55.

utlets and socket shall be made of copper free aluminum alloy or Grass reinforced plastic (GRP).

bles shall be installed in the cable trench or along conduits as far as routing permits.

nductors shall be of PVC covered hard drawn stranded copper


al Lightning Protection

er/Tray shall be corrosion resistant material.

uted inside PVC Conduit.

where lubrication is necessary, a powder lubricant such as micapowder, or anti-seizing thread


all be used.
ables, care shall be taken to avoid the kinking of conductors.

shall be connected In junction boxes, canopy boxes or pull boxes. No connection In elbows, tees
onduit fittings shall be permitted.
Remarks

Cooper Ground Rod

Ground Pit
Bare Cooper Grid Conductor
PVC Insulated Green-Yellow Strip
Accessories (Clamp, thermowell, etc)

Air Terminal
Cooper Ground Rod
Ground Pit
Downconductor
Accessories (Clamp, air terminal base, etc)

c/w Accessories (Joint, Bonding Strip, Support)