Professional Documents
Culture Documents
Engine Type
Engine
Rated Output
Generator
Alternator Efficiency
Speed
Frequency
Heat Rate
Electrical Efficiency
Material : Cu
Type : VCB
: 3
Material : Cu
Type : VCB
Material : Cu
Type : VCB
12H35/40GV
Engine Type
Output (kW)
5760 Engine
Rated Output
5587 Generator
96.5 97 % Alternator Efficiency
750 rpm Speed
50 Hz Frequency
7574 kJ/kWhe Heat Rate
47.50% Electrical Efficiency
12H35/40GV
Output (kVA)
7300
6983,75
96.5 97 %
750 rpm
50 Hz
7574 kJ/kWhe
47.50%
No. Description Rating Qty Unit
Gas Engine
1 5587 kW 9 ea
Generator
Generator
2 25 MVA 3 ea
Transformer
Unit Auxiliary
3 TBA 4 ea
Transformer
Output Voltage 11kV, Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35
Cable Data :
Output Cable
Liquid Immersed Transformer 25MVA, ONAN, IP35 11/20kV, Ynd-, Cu/Cu (Step Up)
Cable Data :
20kV side
11kV side
Dry Type Cast Resin Transformer , AN/AF, IP31, 20/0.4kV, Dyn5, Cu/Cu (Step Down)
Cable Data :
20kV side
0.4kV side
Cable Data :
Output Cable
GIS, Aux. Voltage 48VDC, IP65, c/w protection relay and measurement
GIS, Aux. Voltage 48VDC, IP65, c/w protection relay and measurement
ACB, Rated Voltage 400V, Aux. Voltage 48VDC, IP54, c/w protection relay and measurement, outgo
feeder (TBA)
Industrial Charger input 400VAC, 48 VDC, Autonomy 4 hour (batt. 12VDC, 120AH/C10), surge arres
Industrial UPS, input 400/220 Vac, Output 220 VAC, Isolation transformer, Back-up Time (autonomy
Unitary configuration
SPESIFICATION
age 11kV, Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35
: N2XSY 3x3C-300mm2
: Entry Cable from Above
ersed Transformer 25MVA, ONAN, IP35 11/20kV, Ynd-, Cu/Cu (Step Up)
: TBA
: Entry Cable from Bottom
: TBA
: Entry Cable from Bottom
: N2XY 3X3x3C-950mm2
: Entryfrom Above
Voltage 400V, Aux. Voltage 48VDC, IP54, c/w protection relay and measurement, outgoing
)
harger input 400VAC, 48 VDC, Autonomy 4 hour (batt. 12VDC, 120AH/C10), surge arrester
PS, input 400/220 Vac, Output 220 VAC, Isolation transformer, Back-up Time (autonomy) 4 jam,
figuration
Remarks
Copper Cable
Copper Cable
Copper Cable
Power Plant Generating Power : 45 MW
Generator Power/Unit : 8381 kW
Generator Unit Required : 5.37 Unit
Generator Unit Installed : 6 Unit
Total Plant Generated Power : 50286 kW; 50.286 MW
Generator Output Voltage : 11 kV
Power Factor : 0.8
Full Load Current : 549.8767 Ampere
Safety Factor (+25%) : 687.3458 Ampere
Bus Duct/Cable Rating Selected* : 1000 Ampere
Circuit Breaker Selected : 1000 Ampere
Engine Type
Engine
Rated Output
Generator
Alternator Efficiency
Speed
Frequency
Heat Rate
Electrical Efficiency
Material : Cu
Type : VCB
: 3
Material : Cu
Type : VCB
Material : Cu
Type : VCB
12H35/40GV
Engine Type
Output (kW)
8640 Engine
Rated Output
8381 Generator
96.5 97 % Alternator Efficiency
750 rpm Speed
50 Hz Frequency
7574 kJ/kWhe Heat Rate
47.50% Electrical Efficiency
12H35/40GV
Output (kVA)
10800
10476.25
96.5 97 %
750 rpm
50 Hz
7574 kJ/kWhe
47.50%
No. Description Rating Qty Unit
Gas Engine
1 8381 kW 6 ea
Generator
Generator
2 25 MVA 3 ea
Transformer
Unit Auxiliary
3 TBA 4 ea
Transformer
Output Voltage 11kV, Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35
Cable Data :
Output Cable
Liquid Immersed Transformer 25MVA, ONAN, IP35 11/20kV, Ynd-, Cu/Cu (Step Up)
Cable Data :
20kV side
11kV side
Dry Type Cast Resin Transformer , AN/AF, IP31, 20/0.4kV, Dyn5, Cu/Cu (Step Down)
Cable Data :
20kV side
0.4kV side
Cable Data :
Output Cable
GIS, Aux. Voltage 48VDC, IP65, c/w protection relay and measurement
GIS, Aux. Voltage 48VDC, IP65, c/w protection relay and measurement
ACB, Rated Voltage 400V, Aux. Voltage 48VDC, IP54, c/w protection relay and measurement, outgo
feeder (TBA)
Industrial Charger input 400VAC, 48 VDC, Autonomy 4 hour (batt. 12VDC, 120AH/C10), surge arres
Industrial UPS, input 400/220 Vac, Output 220 VAC, Isolation transformer, Back-up Time (autonomy
Unitary configuration
SPESIFICATION
age 11kV, Otput Power 480 kW/Cylinder, 50 Hz, 750 rpm, IP35
: N2XSY 3x3x3C-120mm2
: Entry Cable from Above
ersed Transformer 25MVA, ONAN, IP35 11/20kV, Ynd-, Cu/Cu (Step Up)
: TBA
: Entry Cable from Bottom
: TBA
: Entry Cable from Bottom
: N2XY 3X3x3C-950mm2
: Entryfrom Above
Voltage 400V, Aux. Voltage 48VDC, IP54, c/w protection relay and measurement, outgoing
)
harger input 400VAC, 48 VDC, Autonomy 4 hour (batt. 12VDC, 120AH/C10), surge arrester
PS, input 400/220 Vac, Output 220 VAC, Isolation transformer, Back-up Time (autonomy) 4 jam,
figuration
Remarks
Copper Cable
Copper Cable
No. Description Rating Qty Unit
Receptacles &
2 - 1 lot
Plugs
2 Grounding - 1 lot
Lightning
3 - 1 lot
Protection
Installation Cable
6 400/230V 1 lot
Inside Building
SPESIFICATION
Plant lighting fixtures shall be made of copper free aluminum alloy, and be of high power factor type w
reflector made of polished aluminum. Their outputs shall be limited to HPS 70W, 100W, and 150W.
Emergency lighting fixture shall be equipped with instant re-strike ballast type.
Street lighting fixtures shall be made of materials suitable for outdoor and corrosive environmental as
the manufacturer standard, and be of high power factor type. Their output shall be limited to HPS 250
- Convenience receptacles and plugs shall be rated 16A, 230V AC, and have two poles (phase and neu
earth.
- All convenience receptacles and plugs shall be suitable for the area classifications as per the applica
codes and standards.
- Convenience receptacles and plugs shall have minimum IP 55.
- Welding outlets and plugs shall be rated 63A, 400V AC, and have three poles (3 phases) + earth.
- All welding outlets and plugs shall be suitable for the area classifications as per the applicable codes
standards.
- Welding outlets and plugs shall have minimum IP 55.
- Welding outlets and socket shall be made of copper free aluminum alloy or Grass reinforced plastic (
Earthing cables shall be installed in the cable trench or along conduits as far as routing permits.
In the case where lubrication is necessary, a powder lubricant such as micapowder, or anti-seizing thr
lubricant shall be used.
In pulling cables, care shall be taken to avoid the kinking of conductors.
Conductors shall be connected In junction boxes, canopy boxes or pull boxes. No connection In elbows
or similar conduit fittings shall be permitted.
SPESIFICATION
g fixtures shall be made of copper free aluminum alloy, and be of high power factor type with
ade of polished aluminum. Their outputs shall be limited to HPS 70W, 100W, and 150W.
ng fixtures shall be made of materials suitable for outdoor and corrosive environmental as per
cturer standard, and be of high power factor type. Their output shall be limited to HPS 250W
ce receptacles and plugs shall be rated 16A, 230V AC, and have two poles (phase and neutral) +
ience receptacles and plugs shall be suitable for the area classifications as per the applicable
tandards.
ce receptacles and plugs shall have minimum IP 55.
utlets and plugs shall be rated 63A, 400V AC, and have three poles (3 phases) + earth.
g outlets and plugs shall be suitable for the area classifications as per the applicable codes and
utlets and plugs shall have minimum IP 55.
utlets and socket shall be made of copper free aluminum alloy or Grass reinforced plastic (GRP).
bles shall be installed in the cable trench or along conduits as far as routing permits.
shall be connected In junction boxes, canopy boxes or pull boxes. No connection In elbows, tees
onduit fittings shall be permitted.
Remarks
Ground Pit
Bare Cooper Grid Conductor
PVC Insulated Green-Yellow Strip
Accessories (Clamp, thermowell, etc)
Air Terminal
Cooper Ground Rod
Ground Pit
Downconductor
Accessories (Clamp, air terminal base, etc)