Development of Technical Services Center at Mazyed Station,


Mazyed Branch, Al Ain
PLOT NO. 22-01-075-001

diagrams for interlock and control wiring required for final installation of
water heaters and controls. Differentiate between portions of wiring that are
factory installed and portions that are to be field installed.

1.4.4 Maintenance Data: Submit maintenance data and parts lists for each type and
size of water heater, control, and accessory; including troubleshooting
maintenance guide. Include this data, product data, shop drawings, and wiring
diagrams in maintenance manual.

1.4.5 Certificates: Submit appropriate certificate of shop inspection and data report
as required by provisions of ASME Boiler and Pessure Vessel Code.

1.5 Delivery, Storage and Handling

1.5.1 Handle water heaters and components carefully to prevent damage, breaking,
denting and scoring. Do not install damaged water heaters or components;
remove from site and replace with new.

1.5.2 Store water heaters and components in clean dry place. Protect from weather,
dirt, fumes, water, construction debris, and physical damage.

1.5.3 Comply with manufacturers rigging and installation instructions for unloading
water heaters, and moving units to final location for installation.

1.6 Warranty :

Contractor shall be responsible bo provide full warranty for five year operation
after PAC, complete in all respects including vessel, electronic elements &
controls etc. The warranty shall include parts and labour cost for the repair and
replacement of defected material or workmanship.

2.0 PRODUCTS

2.1 Materials

2.1.1 Domestic Water Heater

a) Hot water heater shall be horizontal type. Where specified these shall be
suitable for under sink installation. Vessel shall be glass lined steel.
Heating element shall be copper sheathed electric immersion type.

b) Each heater shall be provided with a thermostat with adjustable setting in


the range 32 to 82 deg. C and a safety thermal cut out operable at 90 deg.
C with manual reset and a non-return valve at water inlet to the heater.


15480 ELECTRIC HOT WATER STORAGE HEATERS PAGE 3 OF 10
VOLUME 3, PART B: MECHANICAL SPECIFICATIONS
Emirates Transport
Development of Technical Services Center at Mazyed Station,
Mazyed Branch, Al Ain
PLOT NO. 22-01-075-001

c) The vessel and electrical components shall be encased in a sheet metal


enclosure suitable for a working pressure of 600 Kpa with baked enamel
finish. Tank shall be insulated with polyurethane insulation. A
temperature indicator mounted on the casing shall display the
temperature of water. Each heater shall be supplied with drain cock and
20 dia safety valve , discharging to the building waste water drainage
system via a floor trap and an automatic air vent.


15480 ELECTRIC HOT WATER STORAGE HEATERS PAGE 4 OF 10
VOLUME 3, PART B: MECHANICAL SPECIFICATIONS