Project: 3 STOREY APARTMENT-HOLTEL BUILDING

Location: General Trias, Cavite


Owner: Endozo, Justine M.

NARRATIVE DESCRIPTION

This is a Three Storey Apartment Hotel Building to be built at Barangay Navarro, General Trias
Cavite. Designed By Justine Endozo. It has a floor area of 701 square meter and composed of 24
rooms with toilet and bath, bedroom, kitchen area and living area, it has a mini coffee shop in the
first floor
It is a reinforced concrete structure designed in accordance and provisions of the National
Structural Code of the Philippines 2010, Volume I, 6th Edition. The steel truss of this residential
building was also designed with the provisions of the said structural code and by Allowable Stress
Design. It is a made up of special moment resisting space frame. The building is subjected to
vertical static loading and computer-generated earthquake loading per the Uniform Building Code
1997. Automated wind loads are also applied to the structure per the Uniform Building Code 1997.
The framing arrangement and column locations of the building were provided based on
architectural and structural requirements. The structure system of the residential building is a
reinforced concrete frame with a one-way, two-way slab and beam floor system. It is consists of
concrete beams and columns. The details of the design can be found within the report.
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

Project: 3 STOREY APARTMENT HOTEL BUILDING


Location: General Trias, Cavite
Owner: Endozo, Justine

DESIGN CRITERIA

1.0 LOADS

Design loads and forces are those resulting from dead loads, live loads and
environmental loads acting in the most critical combination, using the
appropriate load factors recommended by the governing codes. Reinforced
concrete sections shall be designed using the Ultimate Strength Design
Method. Load factors are as specified with the National Structural Code of
the Philippines. The basic load types and their corresponding magnitudes are
taken as follows:

1.1 DEAD LOADS

The dead load is the vertical load, which includes the weight of all
permanent construction and all materials, and equipment, which are
permanently fastened thereto and supported thereby.

Table 1 - DEAD LOAD

Material Dry Unit Weight


Structural steel 76.97 KN/m3
Reinforced concrete 24 KN/m3
Steel Deck .08 KPa
Floor finish & floor toppings 1.53 KPa
Ceiling & utilities 0.38 KPa
Mech/Elect 0.30 KPa
Exterior wall (200mm thk CHB) 4.36 KPa
Interior wall (150mm thk CHB) 3.3 KPa
Interior partitions (100mm thk CHB) 3.17 KPa

1
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

1.2 LIVE LOADS

The live load includes loads that may vary in magnitude, and/or
distribution during the life of the structure; not including wind load,
earthquake or dead load. The minimum values of these loads depend
on the occupancy of the structure and are normally specified by the
governing codes. Table 2 shows the live loads used in the design of
the building.

Table 2 - LIVE LOAD

Occupancy/Use Floor Live Load


Basic Floor Areas 1.90 KPa
Roof 4.80 KPa
Toilet 1.90 KPa
Stairs 12.0 KPa

Reduction of Live Loads

The live loads presented above may be reduced for the design of structural
members supporting more than 14 square meters, except for floors in places
with live loads greater than 4.78 KPa in accordance with the following
formula:

R = r (A-15)

The reduction shall not exceed 40 percent for members receiving load from
one level only, 60 percent for other members, nor R, as determined by the
following formula:

R = 23.1(1+D/L)
Where:
R = Reduction in percent
r = Rate of reduction equal to 0.86 percent for floors
A = Area of floor or roof supported by the member in sq.m.
D = Dead load per square meter of area supported by the
members
L = Unit Live load per square meter of area supported by the
members

2
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

For storage live loads exceeding 4.80 KPa no reduction shall be made except
that the design live loads on columns may be reduced 20 percent.

1.3 WIND LOADS

The evaluation of the effects of wind on an object in its path is complex


problem in aerodynamics. When the wind blows against a structure, it
exerts a pressure on the windward side and suction on the leeward
side. Every structure shall be designed and constructed to resist the
wind effects.

Wind load design provisions of the revised code are included in


Chapter 2, Section 207 of the National Structural code of the
Philippines, 5th Edition. This was based on the ASCE Code Provisions
for wind and adapted to Philippines conditions.

Basic Wind Speed, V is a three second gust speed at ten (10) meters
above the ground in Exposure C and associated with annual
probability of two percent (2%) of being equaled or exceeded (50 year
mean recurrence interval)

Design Force, F is the equivalent static force to be used in the


determination of wind loads for open buildings and other structures.

Design Pressure, P, is the equivalent static pressure to be used in the


determination of wind loads for building. The pressure is denoted as:

Pz pressure that varies with height in accordance with the velocity

pressure qz evaluated at height z

Ph - pressure that is uniform with respect to height as determined by


the
velocity pressure qh evaluated at mean roof height h.

Design Wind Pressure, p (kpa), and Forces, F (kn), refer to table 207-1

Velocity Pressure , the velocity pressure qz, in kilopascals, shall be.

3
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

calculated from the equation

qz = 47.3x10-6 Kz Kzt V2 Iw

Where the basic wind speed V, in km/hr, is selected in accordance


with the provisions of section 207.5.2, the importance factor Iw is set
forth in Table 207-2, and the velocity pressure exposure coefficients Kz
is given in Table 207-3 in accordance with the provisions of section
207.5.3. Provisions of section 207.5.5 shall be used to determine Kzt
shall be less than 1.0. The numerical coefficient, 47.3 x 10-6, shall be
used except where sufficient climatic data are available to justify the
selection of the different value of this factor for a specific design
application.

1.4 EARTHQUAKE LOADS

1.4.1 Static Lateral Force Procedure

Seismic forces were determined based on the equivalent static


force procedure and computed following the provisions of
NSCP 2010 Structures or part of the structure were analyzed to
resist minimum total service forces assumed to act non-
concurrently in the direction of each of the main axes of the
structure in accordance with the following formula:

1. V = CvIW
RT (208-4)

2. V = 2.5 Ca I W
R (208-5)

3. V=0.11 Ca I W (208-6)

4. Since we are on Seismic zone 4, the total base shear shall


also
not be less than the following:

V=.08 Z Nv I W
R

V= total force or shear at the base


I= Importance Factor, For Standard Occupancy
Structure = 1.0

4
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

Rw = Numerical coefficient representative of ductility and


overstrength
Nv = Near zone factor used in the determination of Cv in
seismic zone 4 related to both the proximity of the building or
structure to known faults with magnitudes and slip rates.
W = total seismic dead load
Ca= seismic coefficient, as set forth in Table 208-7, Ca=.44Na
Na= near source factor used in the determination of Ca in
Seismic
known faults with magnitudes a set forth in Table 208-4
and
208-6, Na =1.0
Cv= seismic coefficient, as set forth in Table 208-8, Cv=
T = elastic fundamental period of vibration in seconds of
structure in the direction under consideration.

Structure Period,

The value of T shall be determined from


one of the following methods

3/4
T = Ct hn
Where,
Ct = 0.0731 for reinforced concrete moment resisting
frames and eccentrically braced frames.

The total force shall be distributed over the height of the


building in conformance of the following:
n
Fx = [(V-Ft ) wx hx] / (wi hi)
i =1
where:

Ft = 0.07 TV < 0.25 V

and n
V = Ft + Fi
i=1

Ft may be considered zero if T is less than or equal to 0.70 sec.

5
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

The design storey shear in any storey shall be distributed to the


various elements of the lateral force-resisting system in
proportion to their rigidities assuming that the slab acts the
center of mass and center of rigidity.

1.4.2 SITE GEOLOGY AND SITE CHARACTERISTICS.

On Seismic Zone each site shall be assigned a soil profile type


based on properly substantiated geotechnical data using the site
categorization procedure

Soil Profile Type SA.

Being located in a seismic zone 4, the building shall be analyzed,


designed and detailed to be a ductile moment resisting space
frame; hence, all code requirements to meet the necessary
details as such shall be followed. The in-fill masonry stud
partitions are assumed to have no stiffening effect on the
structure; hence, detail for separation from the lateral resisting
force shall be made. The same shall be made for other non-
structural elements.

1.5 SOIL BEARING CAPACITY


In geotechnical engineering, bearing capacity is the capacity of soil to
support the loads applied to the ground. The bearing capacity of soil is
the maximum average contact pressure between the foundation and
the soil which should not produce shear failure in the soil. Ultimate
bearing capacity is the theoretical maximum pressure which can be
supported without failure; allowable bearing capacity is the ultimate
bearing capacity divided by a factor of safety. Sometimes, on soft soil
sites, large settlements may occur under loaded foundations without
actual shear failure occurring; in such cases, the allowable bearing
capacity is based on the maximum allowable settlement. The soil
bearing capacity of the soil is 300 kPa.

1.6 LOAD COMBINATIONS

6
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

Steel sections shall be designed using the Allowable Strength Design


method of National Structural Code of the Philippines. Where
allowable stress or allowable strength design is used, structures and all
portions thereof shall resist the most critical effects resulting from the
following combinations of loads:

U = D+F NSCP (203-8)


U = D+H+F+L+T NSCP
(203-9)
U = D + H + F + ( Lr or T ) NSCP
(203-10)
U = D + H + F + 0.75 ( L + T ( Lr or R )) NSCP (203-11)
U = D + H + F + ( W or E/1.4 ) NSCP (203-12)

No increase in allowable stresses shall be used with these load


combinations except as specifically permitted by Section 203.4.2.

1.7 DEFORMATION LIMITS

Structures or structural members shall be checked such that the


maximum deformation does not exceed the following:

a. Beams and Girders

The part of the total deflection, due to the additional live load and
sustained loads, after attachment of nonstructural elements shall not
exceed 1/480.

b. Building Drift

The displacement of one level to an adjacent level shall not exceed


0.04/Rw nor 0.005 times the storey height for structures having a
fundamental period less than 0.70 seconds. For structures having a
fundamental period of 0.7 seconds or greater, the calculated storey
drift shall not exceed 0.03/Rw or 0.004 times the storey height.

The design lateral forces used to determine storey drifts may be


derived from a C value resulting from detailed calculation of the
period neglecting the 80% limitation, and neglecting the lower
bound of 0.075 for C/Rw.

7
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

2.0 MATERIAL SPECIFICATIONS

The following material strengths shall be used in the structural analysis and
design of the building.

a. Concrete - The minimum concrete compressive strength fc

Concrete Element fc
Columns 69 MPA
Suspended slabs, beams 35 MPA
Shear Walls 52 MPA
Footings 21 MPA
Parapet Wall 21 MPA
Slab on Grad/Fill 21 MPA

b. Structural Steel, Bolts and Welds

Concrete hollow blocks has a compressive strength of 700 psi and is


plastered on both sides

Material Specification
Trusses, Purlins, Plates, ASTM A-36
Bracing , Etc Fy = 248 MPa
ASTM A-307
Bolts
Fv = 69 Mpa; fst = 96.60 Mpa
Welds 3.17 KPa

c. Floor Finishes

Marble and Mortar for floor finish.

Material Dry Unit Weight


Floor finish & floor toppings 1.53 KPa

d. Reinforcing Steel bars

8
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

Shall be deformed and shall conform to PNS 49/ASTM 615:

Diameter Grade fy
12 mm and smaller 60 60,000 psi
16 mm and larger 60 60,000 psi

e. Other Materials

Plaster on wood lath for ceiling.

Material Dry Unit Weight


Ceiling & utilities 0.38 KPa

3.0 COMPUTER PROGRAMS

The following are all structural software used in the analysis and design of
the building;

STAAD.Pro v8i

STAAD.Pro is the structural engineering professionals choice for steel,


concrete, timber, aluminum, and cold-formed steel design of virtually any
structure including culverts, petrochemical plants, tunnels, bridges, piles,
and much more through its flexible modeling environment, advanced
features, and fluent data collaboration. It can make use of various forms of
analysis from the traditional 1st order static analysis, 2nd order p-
delta analysis, geometric nonlinear analysis or a buckling analysis. It can also
make use of various forms of dynamic analysis from modal extraction to
time history and response spectrum analysis.

9
STRUCTURAL DESIGN CRITERIA PROPOSED BUNGALOW RESIDENTIAL BUILDING

4.0 REFERENCES

The following structural codes and specifications shall be used in the design
of the building:

a. National Structural Code of the Philippines (NSCP) C101-01, Volume 1,


Buildings, Towers and Other Vertical Structures, 6th Edition, 2010

b. Building Code Requirements for Reinforced Concrete, ACI 318-08,


American Concrete Institute (ACI).

c. Uniform Building Code (UBC) 1997 Edition.

d. American Institute of Steel Construction Inc., AISC-ASD/LRFD.

e. Elementary Theory of Structures by Wang/Eckel

f. Structural Analysis by Kassimali

10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1

4300.00 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1
F1/P1
BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1

9000.00 B

4300.00
F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1 BP1/SC1

C
F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1

3412.50 3412.50 3412.50 3412.50 3412.50 3402.50 2535.00 2525.00 3412.50 3412.50 3412.50 3412.50 3412.50 3412.50
D
F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1
3000.00

E
F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1
33000.00 3000.00

F
F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1
3000.00

G
F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1
3000.00

H
F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1
3000.00

I
F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1
3000.00

J
F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1
3000.00

K
F1/P1 F1/P1 F1/P1
BP1/SC1 BP1/SC1 BP1/SC1

55000.00

S-1
FOUNDATION PLAN
SCALE 1000 : 1M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

W16 X 40
A
W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40

W16 X 40
W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40
4300.00

W16 X 40

W16 X 40
W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40
9000.00 B

W16 X 40
W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40
4300.00

W16 X 40

W16 X 40
W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40
C

W16 X 40

W16 X 40

W16 X 40
3412.50 3412.50 3412.50 3412.50 3412.50 3402.50 2535.00 2525.00 3412.50 3412.50 3412.50 3412.50 3412.50 3412.50
W16 X 40 W16 X 40
D

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
E

W16 X 40

W16 X 40

W16 X 40
33000.00 3000.00
W16 X 40 W16 X 40
F

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
G

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
H

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
I

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
J

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
K

55000.00

FIRST FLOOR FRAMING PLAN


S-2
SCALE 1000 : 1M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

W16 X 40
A
W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40

W16 X 40
W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40
4300.00

W16 X 40

W16 X 40
W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40
9000.00 B

W16 X 40
W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40
4300.00

W16 X 40

W16 X 40
W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40
C

W16 X 40

W16 X 40

W16 X 40
3412.50 3412.50 3412.50 3412.50 3412.50 3402.50 2535.00 2525.00 3412.50 3412.50 3412.50 3412.50 3412.50 3412.50
W16 X 40 W16 X 40
D

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
E

W16 X 40

W16 X 40

W16 X 40
33000.00 3000.00
W16 X 40 W16 X 40
F

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
G

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
H

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
I

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
J

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
K

55000.00

SECOND FLOOR FRAMING PLAN


S-3
SCALE 1000 : 1M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

W16 X 40
A
W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40

W16 X 40
W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40
4300.00

W16 X 40

W16 X 40
W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40
9000.00 B

W16 X 40
W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40

W16 X 40
4300.00

W16 X 40

W16 X 40
W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40 W16 X 40
C

W16 X 40

W16 X 40

W16 X 40
3412.50 3412.50 3412.50 3412.50 3412.50 3402.50 2535.00 2525.00 3412.50 3412.50 3412.50 3412.50 3412.50 3412.50
W16 X 40 W16 X 40
D

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
E

W16 X 40

W16 X 40

W16 X 40
33000.00 3000.00
W16 X 40 W16 X 40
F

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
G

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
H

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
I

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
J

W16 X 40

W16 X 40

W16 X 40
3000.00
W16 X 40 W16 X 40
K

55000.00

S-4
THIRD FLOOR FRAMING PLAN
SCALE 1000 : 1M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

A A

4300.00

B B

4300.00

C C

3000.00

D D

3000.00 BUILDING LINE


GUTTER
E E

3000.00

F F

3000.00

G G

3000.00

H H

3000.00

I I

3000.00

J J

3000.06

K K

3412.50 3412.50 3412.50 3412.50 3412.50 3412.50 2525.00 4286.94 4313.06 2525.00
3412.50 3412.50 3412.50 3412.50 3412.50 3412.50

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

S-5
ROOF LAYOUT FLOOR PLAN
SCALE 1000 : 1M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

HT-3 HT-3
A A
HT-1 HT-1
4300.00 HT-3 HT-2 HT-3
T-1 T-1 T-1 T-1 T-1 T-1 T-1 T-1 HT-2
B 12000.00 HT-1 HT-1 B

4300.00 HT-2 HT-2 HT-2


HT-3 HT-2 HT-3 HT-3 HT-3
HT-1
C HT-3 C
HT-3 HT-3 HT-3
3000.00
T-1
D D

3000.00 BUILDING LINE


GUTTER
E E

3000.00 T-1
3
@ Midspan
F F

3000.00

G G
LC - 150 X 50 X 15 X 2.0 PURLINS SPACED @
3000.00 T-1 500mm O.C WITH SAGRODS @ MIDSPAN

H H

3000.00

I I

3000.00
T-1

J HT-2 HT-2 J

3000.06 HT-2 HT-2


HT-1
K K
HT-2 HT-2

3412.50 3412.50 3412.50 3412.50 3412.50 3412.50 2525.00 4286.94 4313.06 2525.00
3412.50 3412.50 3412.50 3412.50 3412.50 3412.50

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

12000.00

S-6
ROOF FRAMING FLOOR PLAN
SCALE 1000 : 1M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

A
DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23
LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 DL = 5.33 DL = 5.33 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63
LL = 2.06 LL = 2.06
DL = 6.2 DL = 6.2
4300.00 LL = 2.39 LL = 2.39

DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11
LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 DL = 5.33 DL = 5.33 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97
LL = 2.06 LL = 2.06

9000.00 B
DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 5.33 DL = 5.33 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23
LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 2.06 LL = 2.06 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63

DL = 6.2 DL = 6.2
4300.00 LL = 2.39 LL = 2.39

DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.33 DL = 5.33 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11
LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 2.06 LL = 2.06 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97

DL = 4.85 DL = 4.85
C
LL = 1.87 LL = 1.87

3412.50 3412.50 3412.50 3412.50 3412.50 3412.50 2525.00 DL = 3.72


LL = 1.44
DL = 3.72
LL = 1.44 2525.00 3412.50 3412.50 3412.50 3412.50 3412.50 3412.50
DL = 4.85 DL = 4.85
D
LL = 1.87 LL = 1.87

3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
E
LL = 1.87 LL = 1.87

33000.00 3000.00
DL = 3.72 DL = 3.72
LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
F
LL = 1.87 LL = 1.87

3000.00
DL = 3.72 DL = 3.72
LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
G
LL = 1.87 LL = 1.87

3000.00
DL = 3.72 DL = 3.72
LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
H
LL = 1.87 LL = 1.87

3000.00
DL = 3.72 DL = 3.72
LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
I
LL = 1.87 LL = 1.87

3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
J
LL = 1.87 LL = 1.87

3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

4286.94 4313.06
55000.00

S-7
SECOND LEVEL SLAB TO BEAM LOADING
SCALE 1000 : 1M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

A
DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23
LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 DL = 5.33 DL = 5.33 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63
LL = 2.06 LL = 2.06
DL = 6.2 DL = 6.2
4300.00 LL = 2.39 LL = 2.39

DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11
LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 DL = 5.33 DL = 5.33 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97
LL = 2.06 LL = 2.06

9000.00 B
DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 5.33 DL = 5.33 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23 DL = 4.23
LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 2.06 LL = 2.06 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63 LL = 1.63

DL = 6.2 DL = 6.2
4300.00 LL = 2.39 LL = 2.39

DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.33 DL = 5.33 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11 DL = 5.11
LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 2.06 LL = 2.06 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97 LL = 1.97

DL = 4.85 DL = 4.85
C
LL = 1.87 LL = 1.87

3412.50 3412.50 3412.50 3412.50 3412.50 3412.50 2525.00 DL = 3.72


LL = 1.44
DL = 3.72
LL = 1.44 2525.00 3412.50 3412.50 3412.50 3412.50 3412.50 3412.50
DL = 4.85 DL = 4.85
D
LL = 1.87 LL = 1.87

3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
E
LL = 1.87 LL = 1.87

33000.00 3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
F
LL = 1.87 LL = 1.87

3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
G
LL = 1.87 LL = 1.87

3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
H
LL = 1.87 LL = 1.87

3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
I
LL = 1.87 LL = 1.87

3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

DL = 4.85 DL = 4.85
J
LL = 1.87 LL = 1.87

3000.00 DL = 3.72 DL = 3.72


LL = 1.44 LL = 1.44

4286.94 4313.06
55000.00

THIRD LEVEL SLAB TO BEAM LOADING


S-8
SCALE 1000 : 1M
STEEL COLUMN CONNECTION DETAIL WALL FOOTING DETAIL
B C
SCALE 1000 : 1M SCALE 1000 : 1M

TYP. STEEL DECK SLAB DETAIL


A
SCALE 1000 : 1M
SCHEDULES OF FOOTING TIE BEAMS
FLOOR
BEAM BEAM SECTION LONGITUDINAL REINFORCEMENTS WEB STIRRUPS STIRRUPS
LEVEL BAR STIRRUPS SPACING REMARKS
LOCATION MARK HEIGHT WIDTH DISC. CONT. MIDSPAN CONT. DISC. BARS NO./SET

TB 8 2 8
FTB1 250 350 12 10 1 @ 50, REST @ 160 TO CL
BB 2 4 2
8 2 8
FOOTING

TB
FTB2 250 350 12 10 1 @ 50, REST @ 160 TO CL
BB 2 4 2
TB 8 2 8
FTB3 250 350 12 10 1 @ 50, REST @ 160 TO CL
BB 2 4 2
FTB4 TB 8 2 8
250 350 12 10 1 @ 50, REST @ 160 TO CL
BB 2 4 2
TYP. EXTERIOR WINDOW
TYP. SECTION OF MASONRY WALL INTERSECTION CORNER WALL DETAIL AND DOOR OPENING
B C D
PARTITION REINFORCEMENT SCALE 1000 : 1M SCALE 1000 : 1M SCALE 1000 : 1M
A
SCALE 1000 : 1M

TYP. REINFORCEMENT DETAIL


E
SCALE 1000 : 1M

DETAIL
F
SCALE 1000 : 1M
SEE AT CONNECTION
DETAILS

C B
S-3 S-3 D
S-3
A
A A A
6500 LEGEND : 6500
LEGEND : A A A
A A A - 2L 3'' x 3'' x 3/16'' C
A C C 2500
A - 2L 3 1/2'' x 3 1/2'' x 5/16'' C C C
A C C A 2500 B - 2L 3'' x 2 1/2'' x 3/16'' A C
B - 2L 3 1/2'' x 3'' x 5/16'' A C C A A C C C C
C C C C
A C C C C C C C C A C - L 3'' x 3'' x 3/16''
C - L 3 1/2'' x 2 1/2'' x 5/16'' C C C C B B B B B B
1000 1000 1000 1000 1000 1000
B B B B B B B B B B B B

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 6000

C HALF TRUSS-1 (HT-1) DETAILS


A TRUSS-1 (T-1) DETAILS
S2 SCALE
S2 SCALE
1000:1M
1000:1M

A
A
8841 A LEGEND : 3250 A
LEGEND : A A
A A - 2L 3'' x 3'' x 3/16'' C 1250
C C 2500 A C
A - 2L 3 1/2'' x 3'' x 1/4'' A
C C
A C C C B - 2L 3'' x 2 1/2'' x 3/16'' B B B
B - 2L 3 1/2'' x 2 1/2'' x 1/4'' C C
A C C
1000 1000 1000
C C C C - L 3'' x 3'' x 3/16''
C - L 3'' x 3'' x 1/2'' B B B B B B B B
3000
1480 1000 1000 1000 1000 1000 1000 1000

8480
D HALF TRUSS-3 (HT-3) DETAILS
B HALF TRUSS-2 (HT-2) DETAILS S2 SCALE
S2 SCALE 1000:1M
1000:1M
6mm Gusset Plate (Typical)
rd 6mm Gusset Plate (Typical)
rd To ho
ho p Ch pC
op
C
o To
T rd FULL WELD
FULL WELD

6mm Gusset Plate (Typical)


FULL WELD
KING POST

B TRUSS CONNECTION DETAILS C TRUSS CONNECTION DETAILS D TRUSS CONNECTION DETAILS


S3 S3 S3

1000 mm

LC - 150x50x15x2.0
PURLINS
MACHINEBOLT L - 2.5x2.5x 1/4

STANDARD NUTS & WASHER @ EACH END +- 1000mm

E PURLIN CONNECTION DETAILS F SAG ROD CONNECTION DETAILS


S3 S3

You might also like