You are on page 1of 9

1418 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO.

3, JULY 2010

Fault-Location System for Multiterminal


Transmission Lines
Giovanni Manassero, Jr., Eduardo Cesar Senger, Renato Mikio Nakagomi, Eduardo Lorenzetti Pellini, and
Emlio Csar Neves Rodrigues

AbstractThis research presents the development and imple-


mentation in a computational routine of algorithms for fault loca-
tion in multiterminal transmission lines. These algorithms are part
of a fault-location system, which is capable of correctly identifying
the fault point based on voltage and current phasor quantities, cal-
culated by using measurements of voltage and current signals from
intelligent electronic devices, located on the transmission-line ter-
minals. The algorithms have access to the electrical parameters of
the transmission lines and to information about the transformers
loading and their connection type. This paper also presents the de-
velopment of phase component models for the power system ele- Fig. 1. Multiterminal transmission network.
ments used by the fault-location algorithms.
Index TermsFault location, power transmission lines, substa-
tions. for operating the transmission line and, due to commercial rea-
sons, the information available at these substations (voltage and
current measurements), which might improve the fault-location
NOMENCLATURE process, is not shared with the transmission company.

A. Transmission System
EMTP Electromagnetic Transients Program.
Multiterminal transmission networks may use single- or
ATP Alternative Transients Program. double-circuit lines. As a result, the main branch may use a
GPS Global positioning system. single transmission line or a double-circuit line (both circuits at
the same towers, circuits at different towers and at the same cor-
IED Intelligent electronic device. ridor, or circuits at different towers and at different corridors).
ACSR Aluminum cable steel reinforced. Fig. 1 illustrates a typical multiterminal transmission network.
The main branch connects two terminals ( and ). Along
I. INTRODUCTION the main branch, there are tap points ( to ) where lateral
branches are connected. These lateral branches terminate at
RANSMISSION lines, responsible for connecting gener- distribution or industrial substations (terminals to ).
T ation plants to consumers, are classified according to their
voltage level. Usually, high-voltage transmission lines have only
IEDs installed at and are responsible for recording
voltage and current signals. These records may or may not be
two terminals. However, subtransmission lines may have lateral available at other terminals ( to ). Nonetheless, the pro-
branches connected to tap points along their main branch, ter- posed system is capable of correctly identifying the fault point
minating at distribution substations. based only on the signals recorded at and , with or without
When a permanent fault occurs in these lines, maintenance time synchronization. In addition, if the records are available at
crews usually spend more time to locate the fault point, since other terminals, the proposed system uses them in order to im-
prove the accuracy of the results.
there is no indication of the line section where the fault occurred.
Therefore, maintenance costs may increase while the reliability Although voltage and current records may not be available
of the system diminishes. at one or more terminals ( to ), the proposed system is
The deregulation process contributed to increasing the com- capable of correctly estimating the load connected to them in
order to proceed with the fault location. In addition, it is impor-
plexity of the problem. Normally, the substations connected to
the line branches do not belong to the company responsible tant to point out that the transformers connected to these termi-
nals may have a grounded-wye/delta/grounded-wye connection
type. As a result, a significant part of the fault current may flow
Manuscript received October 31, 2008; revised March 16, 2009. First
through the primary winding of these transformers, for faults
published June 10, 2010; current version published June 23, 2010. Paper no. involving the ground. This scenario increases the complexity of
TPWRD-00825-2008. the problem and since voltage and current records may not be
The authors are with Universidade de So Paulo, So Paulo 5508-900, available at these terminals, the mathematical model used to rep-
Brazil (e-mail: giomanjr@pea.usp.br; senger@pea.usp.br; rmikio@pea.usp.br;
epellini@pea.usp.br; ecrodrigues@cteep.com.br). resent the transformers must implicitly consider the current flow
Digital Object Identifier 10.1109/TPWRD.2010.2047412 through the primary winding.
0885-8977/$26.00 2010 IEEE
MANASSERO et al.: FAULT LOCATION SYSTEM FOR MULTI-TERMINAL TRANSMISSION LINES 1419

B. Fault-Location Methods

Several algorithms for fault location in three terminal trans-


mission lines have been proposed [1][6]. However, due to the
complexity of the problem, only a few algorithms for fault lo-
cation in multiterminal transmission lines have been proposed
[7][10]. In addition, these algorithms do not address all of the Fig. 2. Line sectionPi model.
requirements described in Section II.
References [7] and [8] present fault-location algorithms
for multiterminal single-circuit transmission lines. These And, according to [11]
algorithms are based on synchronized voltage and current mea-
surements at all terminals and on the short transmission-line
model. As a result, these algorithms may present accuracy
errors when handling medium and long multiterminal trans-
mission lines.
References [9] and [10] present fault-location algorithms for
multiterminal double-circuit transmission lines. These algo-
rithms are also based on voltage and current measurements at all
terminals and on the short transmission-line model; therefore, (3)
both algorithms may present accuracy errors when handling
medium and long multiterminal transmission lines. The first where
one presents two different approaches based on synchronized
voltage and current phasor quantities at all line terminals. eigenvectors of ;
The second one was developed according to certain unusual
assumptions, which are difficult to verify, and it is not clear if eigenvalues of ;
it depends on time synchronization. diagonal matrix notation.
Due to these reasons, the main goal of the fault-location
method proposed in this paper is to address all of the problems
It is possible to calculate the parameters described in (3) for
described before in order to present an accurate solution for
single- and double-circuit transmission lines. With regards to
fault location in multiterminal transmission lines.
double-circuit lines, the equations consider implicitly the elec-
tromagnetic coupling (matrices and are 6 6 in
size) and, with regards to transposed lines, different and
II. SYSTEM MODELING
matrices are used to represent each line section.
The fault-location method proposed in this paper is based on
voltage and current phase components. In order to improve the
B. Load and Three-Phase Transformer Combination
accuracy of the results, it was necessary to develop precise math-
ematical models for transmission lines, loads, and transformers. The load model, in phase components, considers that the load
The following sections describe these models. is balanced and can be represented by constant delta-connected
impedances. However, it is important to point out that the pro-
posed fault-location system may use any other type of load con-
A. Transmission Line
nection. In addition, there is no significant generating units in
Fig. 2 illustrates the three-phase pi-model of a single-circuit parallel to this load. In other words, the load does not contribute
transmission line, whose line length is . The transmission-line to the fault current.
series impedance and shunt admittance matrices, per unit length, The transformers models, in phase components, depend on
are and , respectively. Equation (1) describes the the windings connection schemes and may derive from their
mathematical relation of the voltage and current phasors at local zero-, positive-, and negative-sequence network diagrams [12].
and remote ends Therefore, it is possible to obtain the load and transformer com-
bination from both sequence admittance matrices.
As an example, consider the sequence network diagrams de-
picted in Fig. 3. These diagrams represent the load model de-
and scribed before, connected to a three-phase grounded-wye/delta/
grounded-wye transformer. Equation (4) presents the resulting
(1) admittance matrix of the respective combination
where

(4)
(2)
1420 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

Fig. 5. Double-line fault (BC).

Substituting (9) in the first equation of system (8)

(10)

Substituting (9) and (10) in the second equation of system


(8), results in (11). This equation describes the mathematical
relation between voltage and current phasor quantities at the
remote terminal

(11)

Fig. 3. Load and transformer combinationsequence network diagrams. (a) where


Zero sequence. (b) Positive sequence. (c) Negative sequence.

(12)

D. Fault Models
The fault models, in phase components, depend on the fault
type and on the phases involved. A mathematical relation be-
Fig. 4. Line sectionestimation of [Y ] .
tween voltage and current phasor quantities at the fault point is
able to describe all fault types and phases involved, as in

(13)
Furthermore, it is possible to calculate the phase components
of the voltage and current phasors using (5) and (6), where where
is the transformation matrix
fault admittance matrix;
(5)
voltage phasor quantities at the fault point;
(6)
fault current phasor quantities.
As a result, (4) evolves to
It is possible to obtain different fault admittance matrices that
(7) represent voltage and current mathematical relations for all dif-
ferent fault types and phases involved. As an example, consider
C. Line Section, Load, and Transformer Combination the double-line fault depicted in Fig. 5. The respective fault ad-
mittance matrix is presented in
In addition to the admittance matrix that describes the load
and transformer combination, the proposed system uses an
equivalent matrix that represents the combination of the load, (14)
transformer, and line section. This matrix is derived from the
mathematical relation between the current and voltage phasor
quantities at the tap points.
Fig. 4 depicts a line section delimited by two terminals (local III. FAULT-LOCATION SYSTEM
and remote). The line length is and the voltage and current The fault-location system proposed in this paper addresses
phasors at the remote terminal are derived from (1) as in
all requirements described in Section II. The identification of
the fault point is based on four stages, which are detailed in the
(8)
following sections.
To exemplify the proposed system, consider the network de-
Rewriting (7) picted in Fig. 6. This network is composed by single-circuit
transmission-line sections. Along the main branch, which con-
(9) nects terminals and , there are three tap points where lat-
MANASSERO et al.: FAULT LOCATION SYSTEM FOR MULTI-TERMINAL TRANSMISSION LINES 1421

lating the active and reactive prefault injected power ( and


) using the voltage and current phasor quantities at termi-
nals , , and . The calculated injected power corresponds
to the sum of the line losses and the load power consumption at
terminals and .
2) Initial Estimative of the Load Impedances: After calcu-
lating the injected power, the algorithm estimates the initial
Fig. 6. Transmission network. value of the load impedances at terminals and by
assuming that the transformers connected to these terminals
operate proportionally to their nominal apparent power, as in

and

(15)

(16)

where

and ;
transformer nominal apparent power at terminal ;
active power at terminal ;
reactive power at terminal ;
initial estimative of the load impedance at terminal
Fig. 7. Prefault processing. ;
nominal phase voltage at terminal .
eral branches are connected. These lateral branches end at ter- 3) Estimation of the Line Losses and Loads Complex Power:
minals , , and . Unsynchronized voltage and current This stage is based on a prefault load flow that depends on the
measurements are available only at terminals , , and , current and voltage phasor quantities at terminals , , and
which means that the relative phases of these measurements are , and on the load impedances at terminals and .
unknown. From the voltage and current phasor quantities at the refer-
ence terminal , it is possible to calculate voltage and phasor
A. Digital Signal Processing
quantities at the tap point and the losses of the line section
This stage consists of filtering pre and postfault voltage and by using (1). In addition, from the voltage phasor quan-
current signals at terminals , , and in order to reduce tities at , it is possible to calculate the losses of the line section
the effect of the exponential components that take place during and the load complex power at by using (11). This
the fault [13]. After this step, pre and postfault voltage and cur- procedure enables the estimation of all line sections losses and
rent phasor quantities at the respective terminals are calculated all loads complex power ( and ).
by using the one cycle discrete Fourier transform method. 4) Phase-Shift Adjustment: The procedure described in the
previous section enables the calculation of the voltage and cur-
B. Prefault Data Processing rent phasor quantities at terminals and by using the
The prefault processing stage is a recursive algorithm that voltage and current phasor quantities at terminal and the esti-
consists of synchronizing voltage and current phasor quantities mated load impedances at terminals and . Therefore, it
at terminals , , and , and estimating the load imped- is possible to determine the phase shift of and with ref-
ances at the remaining terminals ( and ). erence to by comparing the measured and calculated voltage
This algorithm is depicted in Fig. 7 and is based on the five and current phasor quantities at these terminals as in [7] and
steps presented in Sections III-B1B5. [14].
1) Calculation of the Injected Power: The algorithm starts 5) Estimation of the Load Impedances: The initial estima-
by selecting the reference terminal ( , for instance) and calcu- tion of the load impedances may differ from the actual values.
1422 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

Therefore, it is necessary to correct it in order to adapt the com-


plex power of the loads and the line losses to the total amount of
injected power. In each iteration, the load impedances are cor-
rected as in

(17)
Fig. 8. Line section b 0b .
where

load admittance at terminal ; respectively. Thus, it is possible to estimate the postfault voltage
and current phasor quantities at the fault point, according to
iteration number.

C. Postfault Processing (18)

The postfault processing stage consists of calculating two


(19)
sets of postfault voltage and current phasor quantities at all tap
points. One of them using postfault voltage and current phasor
quantities at terminals and the other using postfault voltage Therefore, in order to estimate the fault distance , it is nec-
and current phasor quantities at terminal . This stage is based essary to compare the postfault voltage phasor quantities at the
on (1) and (11). It depends on the load impedances at terminals fault point, calculated by using (18) for the same phasor quan-
and and on the postfault voltage and current phasor tities, which is calculated by using (19) as
quantities at terminal . It also considers that the system is
not faulted in order to perform the calculations.
Using this approach, it is possible to determine whether the
fault occurred at any lateral branch or at the main branch. In
other words: (20)
if the fault has occurred at a lateral branch, the postfault
voltage phasor quantities at the respective tap point, from The proposed algorithm uses the golden section search tech-
both sets, must be equal. In this case, the fault-location nique to solve (20), as in [16]. Since this algorithm is based only
system investigates only the respective lateral branch; on the difference of voltage phasor quantities at the fault point,
otherwise, the fault occurred at the main branch and all line the fault distance is independent of fault type, fault resistance(s),
sections belonging to it must be investigated. and source impedances.
Two algorithms were developed in order to estimate the fault
location. The first one is based on the postfault voltage and cur- E. Fault-Location AlgorithmVoltage and Current at One End
rent phasor quantities at both ends (Section III-D). Hence, it is
The algorithm proposed in this section is used to locate faults
used to locate faults at line sections from the main branch or
at line sections where voltage and current phasor quantities are
lateral branches where voltage and phasor quantities are avail-
available only at one end.
able at the respective substation terminals. The second one is
As an example, consider the line section depicted in Fig. 9,
based on the postfault voltage and current phasor quantities at
which is part of the system illustrated in Fig. 6. This line section
one end (Section III-E). Thus, it is used to locate faults at lateral
is delimited by tap point and terminal has a length of
branches where voltage and current phasor quantities are avail-
and the fault point is located at an unknown distance from .
able only at the tap point.
From (1) and (11), it is possible to calculate the postfault voltage
and current phasor quantities at by using the postfault voltage
D. Fault-Location AlgorithmVoltage and Current at Both and current phasor quantities at terminals and . Thus, it
Ends is possible to estimate the postfault voltage and current phasor
quantities at the fault point, as in
The algorithm proposed in this section is used to locate faults
at line sections where voltage and current phasor quantities are
available at both ends [15].
(21)
As an example, consider the line section depicted in Fig. 8,
which is part of the system illustrated in Fig. 6. This line section
is delimited by tap points and , has a length of , and (22)
the fault point is located at an unknown distance from .
From (1) and (11), it is possible to calculate the postfault voltage where
and current phasor quantities at and by using the postfault
voltage and current phasor quantities at terminals and , (23)
MANASSERO et al.: FAULT LOCATION SYSTEM FOR MULTI-TERMINAL TRANSMISSION LINES 1423

fault distance and the element of the fault admittance matrix


as in

(28)

In order to estimate and , the proposed algorithm starts


with an initial guess of both variables and proceeds with a re-
Fig. 9. Line section b 0T . cursive procedure, where these values are corrected at each it-
eration, as in

(29)
(30)

where is the iteration number and and can


be obtained by solving

Fig. 10. Simulation network. (31)

Since the number of equations is larger than the number of


Substituting (23) in (22) variables (three real equations plus three imaginary equations
and two variables), it is necessary to use a fitting data method to
solve the system. The algorithm proposed in this paper uses the
(24) least-squares method, and it is detailed in [14].

In order to estimate the fault location, it is necessary to use F. Determination of the Faulted Line Section
the voltage and current phasor quantities at tap point . There-
The fault-location system proposed in this paper indicates two
fore, substituting (21) in (24), it is possible to relate these phasor
possible fault points. One of them is at the investigated lateral
quantities to the fault admittance matrix and to the equivalent
branch and the other is at a line section of the main branch, as
matrix , as in
described in Section III-C.
(25) It is important to point out that the investigation of the main
branch results in a fault distance and a value of the function
where presented in (20), to each line section. If the fault has occurred
at the main branch, the value of this function at the faulted line
section must be zero. Thus, after investigating all sections, only
one is the possible candidate (the one that presents the lowest
(26) value for the function).

Since the loads impedances were estimated at the prefault IV. SIMULATION RESULTS
data-processing stage, the equivalent impedance matrix is
only a function of the distance and the elements of the fault A. Subtransmission System
admittance matrix, as in
The fault-location system was simulated by using test data
(27) produced by ATP. Several simulations were performed by using
a subtransmission network whose topology is depicted in Fig.
Therefore, the fault-location algorithm consists of estimating 10. This network has a nominal voltage of 138 [kV] and is com-
the distance and the elements of the equivalent impedance ma- posed of a double-circuit main branch that connects terminals
trix that solve (25). To accomplish this task, the fault-location and . Along the main branch, there are five tap points where
algorithm uses the NewtonRaphson method and since there are double-circuit lateral branches are connected. These branches
different equivalent impedance matrices that represent all dif- end at distribution substations to .
ferent fault types and phases involved, there are different solu- The tower and conductors used in the simulation cases are
tions for (25). typical of the 138 [kV] voltage level and are depicted in Fig. 11.
As an example, consider a line-to-ground fault involving The line sections were simulated by using the ATP line constants
phase A. The equivalent impedance matrix is a function of the supporting routine and these sections are composed of 266.8
1424 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

TABLE II
FAULT-LOCATION RESULTSMEASUREMENTS AT ALL LINE TERMINALS

TABLE III
FAULT-LOCATION RESULTSMEASUREMENTS AT TERMINALS T AND T

Fig. 11. Electric tower used in the simulations.

TABLE I
SIMULATION DATA

Table III presents the fault distance location errors consid-


ering line-to-ground faults (fault resistances from 0 up to 50
), double-line, double-line-to-ground, and three-phase faults.
As detailed, the algorithm described in Section III-D presented
errors lower than 600 [m] for line-to-ground faults, lower than
55 [m] for double-line and double-line-to-ground faults, and
MCM ACSR phase conductors (with a midspan sag of 6.5 [m]) lower than 135 [m] for three-phase faults. On the other hand,
and a 1/2 HS ground wire (midspan sag of 6.0 [m]). the algorithm described in Section III-E presented errors lower
Table I presents the fault parameters used in the ATP simu- than 1710 [m] for line-to-ground faults, lower than 1050 [m]
lations. Four fault types, with fault resistances varying from 0 for double-line and double-line-to-ground faults, and lower than
up to 100 , were simulated in 22 different fault points. The 900 [m] for three-phase faults. It can be noticed that the response
loads were modeled as constant impedances, according to the of the first algorithm presents a higher level of accuracy. This is
loads power depicted in Fig. 10. As a result, 440 simulation due to the fact that the accuracy of the loads impedances estima-
cases were produced. tion may interfere with the accuracy of the second fault-location
The system accuracy was checked against the simulation algorithm. Nevertheless, the errors presented by both algorithms
cases described in Table I and the results are presented in are considerably small when compared to the line length.
Sections IV-BD.
D. Influence of the Fault Resistance
B. Voltage and Current Measurements at All Terminals
In order to analyze the influence of the fault resistance, sev-
This section presents the results of the fault-location system, eral line-to-ground faults were simulated, with fault resistances
considering that the voltage and current measurements are avail- varying from 0 to 100 . The fault distance location errors are
able at all line terminals. presented in Table IV.
Table II presents the fault distance location errors considering As detailed in this table, the algorithm described in Sec-
line-to-ground faults (fault resistances from 0 to 50 ), double- tion III-D presented errors lower than 1000 [m], considering
line, double-line-to-ground, and three-phase faults. As detailed, all fault resistances. On the other hand, the algorithm described
the absolute errors are lower than 440 [m] for all fault types. The in Section III-E presented errors lower than 1710 [m] for fault
mean errors are similar when considering double-line, double- resistances up to 50 and lower than 3070 [m] for fault
line-to-ground, and three-phase faults. However, line-to-ground resistances of 100 . This is due to the fact that the loads
faults present a mean error that is slightly higher than the other impedances may interfere significantly with the accuracy of the
faults (111 [m]). However, these errors are considerably small fault-location algorithm for smaller fault currents.
when compared to the line length. The influence of the fault resistance in the performance of the
algorithm described in Section III-D is depicted in Fig. 12. This
C. Voltage and Current Measurements at Terminals and figure illustrates the behavior of the function described by (20)
This section presents the results of the fault-location system, at the faulted line section for fault resistances from 0 to 100 .
considering that the voltage and current measurements are avail- Fig. 12(a) was produced by using the actual values of the
able only at terminals and . loads impedances employed in the simulations while Fig. 12(b)
MANASSERO et al.: FAULT LOCATION SYSTEM FOR MULTI-TERMINAL TRANSMISSION LINES 1425

TABLE IV As presented in Section IV, the accuracy of the proposed


INFLUENCE OF THE FAULT RESISTANCE system depends on the details of the models used by the al-
gorithms, and on the information available at all line terminals
(load impedances, voltage, and current signals). Consequently,
the results described in Section IV-B present a higher level of
accuracy than the results described in Section IV-C. This is due
to the fact that in Section IV-B, there are voltage and current sig-
nals available at all line terminals, while in Section IV-C, these
signals are available only at and .
In Section IV-D, it can be noticed that for fault resistances
larger than 50 , the estimation of the load impedances affects
the proposed fault-location system. However, the results are still
accurate.

REFERENCES

[1] R. K. Aggarwal, D. V. Coury, A. T. Johns, and A. Kalam, A practical


approach to accurate fault location on extra high voltage teed feeders,
IEEE Trans. Power Del., vol. 8, no. 3, pp. 874883, Jul. 1993.
[2] A. Girgis, D. Hart, and W. Peterson, A new fault location technique
for two and three terminal lines, IEEE Trans. Power Del., vol. 7, no.
1, pp. 98107, Jan. 1992.
[3] C. Yu, C. Liu, and Y. Lin, A fault location algorithm for transmis-
sion lines with tapped legPMU based approach, in Proc. IEEE
Power Eng. Soc. Summer Meeting, Vancouver, BC, Canada, 2001, pp.
915920.
[4] A. D. Tziouvaras, J. B. Roberts, and G. Benmouyal, New multi-ended
fault location design for two- or three-terminal lines, in Proc. 7th Inst.
Elect. Eng., Developments in Power System Protection Int. Conf., Am-
sterdam, The Netherlands, 2001, no. 479, pp. 395398.
[5] Y. Lin, C. Liu, and C. Yu, A new fault locator for three-terminal trans-
mission lines using two-terminal synchronized voltage and current pha-
sors, IEEE Trans. Power Del., vol. 17, no. 2, pp. 452459, Apr. 2002.
[6] L. L. Lai, N. Rajkumar, E. Vaseekar, H. Subasinghe, A. Carter, and B.
J. Gwyn, Wavelet transform and neural networks for fault location of
a teed-network, in Proc. Int. Conf. Power System Technology, Perth,
Austrlia, Jul. 2000, vol. 2, pp. 807811, PowerCon 2000.
[7] M. Abe, N. Otsuzuki, T. Emura, and M. Takeuchi, Development of a
new fault location system for multi-terminal single transmission lines,
IEEE Trans. Power Del., vol. 10, no. 1, pp. 159168, Jan. 1995.
[8] S. M. Brahma, Fault location scheme for a multi-terminal transmis-
Fig. 12. Value of the function described by (20). sion line using synchronized voltage measurements, IEEE Trans.
Power Del., vol. 20, no. 2, pt. 2, pp. 13251331, Apr. 2005.
[9] T. Nagasawa, M. Abe, N. Otsuzuki, T. Emura, Y. Jikihara, and M.
Takeuchi, Development of a new fault location algorithm for multi-
was produced by using the estimated loads impedances. In the terminal two-parallel transmission lines, IEEE Trans. Power Del., vol.
7, no. 3, pp. 15161532, Jul. 1992.
first case, the fault location is independent of the fault resistance; [10] T. Funabashi, H. Otoguro, Y. Mizuma, L. Dube, and A. Ametani, Dig-
in other words, the minimum of the function is the same for all ital fault location for parallel double-circuit multi-terminal transmis-
fault resistances. However, in the second case, the fault location sion lines, IEEE Trans. Power Del., vol. 15, no. 2, pp. 531537, Apr.
2000.
slides to the right. Comparing both figures, it is possible to affirm [11] W. I. Bowman and J. M. McNamee, Development of equivalent Pi
that this effect is derived from the errors in the estimation of the and T matrix circuits for long untransposed transmission lines, IEEE
loads impedances, not from the fault-location algorithm. Trans. Power App. Syst., vol. PAS-83, no. 6, pp. 625632, Jun. 1964,
653-657.
[12] D. S. Ramos and E. M. Dias, Sistemas eltricos de potnciaRegime
permanente, G. Dios, Ed. Rio de Janeiro, Brazil: Ed. Guanabara
V. CONCLUSION Dois, 1983, vol. 2.
[13] N. N. de Santana, Pr-filtragem da componente aperidica exponen-
cial para os algoritmos utilizados em rels digitais de distncia, M.Sc.
This paper presented the development, implementation, and dissertation, Escola Politcnica da USP, So Paulo, Brazil, 1998.
test results of a fault-location system for multiterminal trans- [14] G. Manassero, Jr., Sistema Para localizao de faltas em linhas de
mission lines. It also presented, in detail, the algorithms that are transmisso com subestaes conectadas em derivao, Ph.D. disser-
tation, Escola Politcnica da USP, So Paulo, Brazil, 2006.
part of the proposed system. [15] A. T. Johns and S. Jamali, Accurate fault location technique for power
The results indicate that the algorithms accuracy is adequate. transmission lines, Proc. Inst. Elect. Eng., Gen., Transm. Distrib., vol.
The maximum error of the algorithm described in Sections III-D 137, no. 6, pt. C, pp. 395402, Nov. 1990.
[16] W. H. Press, S. A. Teukolsky, W. T. Vetterling, and B. P. Flannery,
and E is less than 1000 m and 3100 m, respectively (0.4% and Numerical Recipes in C. Cambridge, MA: Cambridge Univ. Press,
1.2% of the total line length). 1992.
1426 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

Giovanni Manassero, Jr. was born in Brazil in 1974. He received the B.Sc., Eduardo Lorenzetti Pellini was born in Brazil in 1975. He received the B.Sc.
M.Sc., and Ph.D. degrees from Universidade de So Paulo, So Paulo, Brazil, and M.Sc. degrees from Universidade de So Paulo (USP), So Paulo, Brazil,
in 1999, 2001, and 2006, respectively. in 2000 and 2005, respectively.
He joined Universidade de So Paulo, Universidade Paulista, and Universi- Since 2000, he has been a Researcher at USP and is responsible for devel-
dade Cruzeiro do Sul in 2002, 2006, and 2009, respectively, where he is cur- oping hardware and software solutions for electrical automation, control, and
rently Assistant Professor. His research fields are power systems protection, protection.
modeling, and simulation.

Emlio Csar Neves Rodrigues was born in Brazil in 1963. He received the
Eduardo Cesar Senger was born in Brazil in 1954. He received the B.Sc., B.Sc. degree from Universidade Federal de Uberlndia in 1989 and the M.Sc.
M.Sc., and Ph.D. degrees from Universidade de So Paulo (USP), So Paulo, degree from Universidade Federal do Rio de Janeiro, Rio de Janeiro, Brazil, in
Brazil, in 1977, 1983, and 1990, respectively. 2004.
He joined USP in 1978 where he is currently Assistant Professor. His research From 1990 to 1994, he was Project Engineer with Figueiredo FerrazCon-
fields are power systems protection and control. sultoria e Engenharia de Projetos. Since 1994, he has been an Analysis Engineer
with Companhia de Transmisso de Energia Eltrica Paulista.

Renato Mikio Nakagomi was born in Brazil in 1976. He received the B.Sc.
and M.Sc. degrees from Universidade de So Paulo (USP), So Paulo, Brazil,
in 2000 and 2006, respectively.
Currently, he is an Assistant Professor with the Universidade Cruzeiro do Sul,
where he has been since 2005. He has been a Researcher with USP since 2002.
His research fields are power systems protection, modeling, and simulation.

You might also like