FIELD FRESH FOODS PVT LTD

LUDHIANA
Design for Anchor Bolts in Moment Condition Detail A
Node No. 1
LOADING : - REFER COMPUTER OUTPUT FOR FORCES IN Page No. 8
INPUTS:
Load Case Shear (S) KN Axial (P) KN Moment (M) KN-m
Dead Load 10 45 50
Max Wind Load 70 100 150

Anchor Bolt is Design For (DL - WL) Condition.


M = 100.0 KN-m
P = 55.0 KN
S = 60.0 KN
No of Bolts = 10
Dia of Bolt = 24 mm

Column Size : Web = 800 X 8 mm


A
Flange= 550 X 16 mm

X1 = 858 mm

X2 = 758 mm

X3 = 408 mm

X4 = 58 mm

a= 800 mm
X1 = 858 mm
X2 = 758 mm A
X3 = 408 mm
X4= 58 mm

DESIGN:
P * (a/2) + 2*T(X1) + 2*T(X2)+ 2*T(X3)+ 2*T(X4) = M @ A-A

P * (a/2) + 2*T(X1+ X2+ X3 + X4) = M @ A-A

T = M/[2*(X1 + X2 + X3 + X4)] - P*a / [4* (X1 + X2 + X3 + X4)]

Tension in each Bolt , T = 1.91 Tons

{ 3vf , cal/ 3 vf + Ntf, cal / Ntf} < 1.4

where :

3vf, cal = Calculated Shear Stress in Bolt in Kg/cm^2


Ntf, cal = Calculated Axial Stress in Bolt in Kg/cm^2
3vf = Permissible Shear in Bolt = 800 Kg/cm^2
Ntf = Permissible Axial Tension in Bolt = 1200 Kg/cm^2

6.12 * 1000 + 19107 = 0.02 + 0.352 = 0.37 < 1.4


10 * 452.2 1 * 452.2
80 120 [HENCE SAFE]

Therefore provide 10 Nos. 24 mm Dia. Bolts

Calculation for Anchor Bolt Length

M= 10.2 T-m
P= 1.91 T

No. of Anchor Bolts Provided = 10

Tension in each bolt = 1.91 T

Refering IS: 456 - Table 15 :

Permissible Bond Stress for Plain Bars in Tension = 0.8

Therefore , Anchor Length = 1.91 * 10000 / ( 3.14 * 24 * 0.8 ) = 317 mm


Provide Anchor Length of 400 mm for 24 mm A. B.