FIELD FRESH, LUDHIANA

Design of Rafter Bracing

Length of Building = 105.00 m


Width of Building = 40.00 m
Bay Spacing = 7.0 m C/C
End Wall Spacing = 6.0 m C/C
Clear Height = 7.55 m
Eaves Height = 9.00 m
Brick Wall Height = 7.55 m
Wind Pressure = 115.00 kg/m2
Wind Coeff on Roof = 1.14
Wind Coeff on Wall = 0.90
Slope = 10 (1:10)
Number of Joints = 8 nos
Number of Sets = 4 nos

### Total Gable Wind Force = 115 x 0.9 x [0.5 x (40/2)x(40/(2x10)) + (40 / 2)x( 9 - 7.55 ) ]

= 5071.50 Kg

Considering connection of Gable Columns with Gable Rafter as fixed,

= 0.625 * 5071.50 = 3169.7 Kg is transferred in base of gable columns

and the rest of force which is 1901.8 Kg is transferred into rafter bracing.

Force per Joint = 1901.81 = 237.7 Kg


8

### Maximum force in Rafter = 22.80 T

Maximum moment in Rafter = 101.10 T-m

Lever Arm = 1262 mm = 1.26 m

Total force = (22.8 + 101.1/1.26) x 1000 x 0.075 = 7727.9 Kg

Force per Joint = 7728 = 966.0 Kg


8

### Frictional Drag for Rafter Bracing Joint = 105 x (40/2)x0.025x115x1.14


8x4

= 222.0 Kg
Total Force Per Joint = 237.7 + 966.0 + 221.97 = 1425.68 Kg
= 1.42 T

Force in Bracing F = R / Cos Q

Length of the Diagonal = 9.21 m


Cos Q = 0.76

Force in Bracing F = 1.42 / 0.76


F = 1.86 Tons

ASSUME: Angle 65x65x6

WT= 5.91 Kg/m

Area = 7.44 cm2


MI = 29.10 cm4
Z = 6.20 cm3

r = 29.1 / 7.44 = 1.98 cm


Eff Length ( l ) = 0.75 x 9.21 / 2
= 3.45 m

Slenderness Ratio = l / r = 174.63 < 250 [SAFE]

Permissible Stress in Axial Compression (As Per IS : 800 Table - 5.1)

Pac = 35 N/mm2
= 357 kg/cm2
Safe Load on Tube = 357 x 7.44 / 1000
= 2.7 Tons

Total Load Per Bracing = 1.42 Tons < 2.7 Tons [SAFE]

PROVIDE RAFTER BRACING SECTION = 65x65x6 Angle


Design of Column Bracing

### Force per Joint of Column Bracing = Force per Joint of Rafter Bracing
2
= 118.9 kgs
### Frictional Drag for Column Bracing Joint = 105 x 7.55 x0.025x115x0.9
4
= 512.8 kgs
### Reaction From Rafter Bracing = 1425.67 kgs

Total Force per Joint = 1425.67 + 512.81 - 118.86


= 1819.62 kgs

Force in Bracing F = R / Cos Q

Length of the Diagonal = 10.29 m


Cos Q = 0.68

Force in Bracing F = 1819.62 / 0.68


= 2675.91 kgs
F = 2.67 Tons

ASSUME: Angle 75x75x6

WT= 6.93 Kg/m

Area = 8.66 cm2


MI = 45.70 cm4
Z = 8.40 cm3

r = 45.7 / 8.66 = 2.30 cm


Eff Length ( l ) = 0.75 x 10.29 / 2
= 3.86 m

Slenderness Ratio = l / r = 167.98 < 250 [SAFE]

Permissible Stress in Axial Compression (As Per IS : 800 Table - 5.1)

Pac = 38 N/mm2
= 387.6 kg/cm2
Safe Load on Tube = 387.6 x 8.66 / 1000
= 3.4 Tons

Total Load Per Bracing = 2.67 Tons < 3.4 Tons [SAFE]

PROVIDE COLUMN BRACING SECTION = 75x75x6 Angle