You are on page 1of 10

SWT 3000 Equipment Manual

Chapter 9: Technical Data


Technical Data SWT 3000 Equipment Manual

Table of contents:

Command Input/Output ---------------------------------------------------------------------------------------------------------- 3


Input IFC-P/IFC-D---------------------------------------------------------------------------------------------------------------- 3
Command output IFC-P ---------------------------------------------------------------------------------------------------------- 3
Command Output IFC-D--------------------------------------------------------------------------------------------------------- 3
Signaling Output IFC-S ---------------------------------------------------------------------------------------------------------- 3
Transmission via Digital Networks---------------------------------------------------------------------------------------------- 4
Digital Interface ------------------------------------------------------------------------------------------------------------------- 4
Transmission time * -------------------------------------------------------------------------------------------------------------- 4
Security----------------------------------------------------------------------------------------------------------------------------- 4
Dependability ---------------------------------------------------------------------------------------------------------------------- 4
Transmission via Analog Network ---------------------------------------------------------------------------------------------- 4
Modulation type ------------------------------------------------------------------------------------------------------------------- 4
Broadband equipments ----------------------------------------------------------------------------------------------------------- 4
Narrowband modulation---------------------------------------------------------------------------------------------------------- 4
Transmission time (SWT 3000 stand alone)* --------------------------------------------------------------------------------- 5
Transmission time (SWT 3000 integrated into PowerLink)* --------------------------------------------------------------- 5
SWT 3000 Fibre optic module FOM ------------------------------------------------------------------------------------------- 6
Technical data FOBox------------------------------------------------------------------------------------------------------------ 6
Security----------------------------------------------------------------------------------------------------------------------------- 7
Dependability ---------------------------------------------------------------------------------------------------------------------- 7
Voice frequency interface CLE ------------------------------------------------------------------------------------------------- 7
Power supply ------------------------------------------------------------------------------------------------------------------------ 7
Input voltage ----------------------------------------------------------------------------------------------------------------------- 7
Power consumption --------------------------------------------------------------------------------------------------------------- 7
Alarm output ALRS module----------------------------------------------------------------------------------------------------- 8
Alarm output ALR module ------------------------------------------------------------------------------------------------------ 8
Binary input ALR module ------------------------------------------------------------------------------------------------------- 8
Clock-Synchronization Input ---------------------------------------------------------------------------------------------------- 8
Network management ------------------------------------------------------------------------------------------------------------- 8
Service PC---------------------------------------------------------------------------------------------------------------------------- 9
Electromagnetic Compatibility EMC------------------------------------------------------------------------------------------- 9
Immunity --------------------------------------------------------------------------------------------------------------------------- 9
Emission---------------------------------------------------------------------------------------------------------------------------- 9
Mechanical design ------------------------------------------------------------------------------------------------------------------ 9
Dimensions ------------------------------------------------------------------------------------------------------------------------ 9
Weight ------------------------------------------------------------------------------------------------------------------------------ 9
Insulation Withstand Voltage---------------------------------------------------------------------------------------------------10
Impulse Withstand Level 1,2/50s --------------------------------------------------------------------------------------------10
Climatic Conditions--------------------------------------------------------------------------------------------------------------10
Mechanical Conditions ----------------------------------------------------------------------------------------------------------10
International Standards ----------------------------------------------------------------------------------------------------------10

Page - 2 Edition p3_3_2x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual Technical Data

Command Input/Output

Input IFC-P/IFC-D

Nominal input voltage *) 24V 250 V DC (tolerance -20% +15%)

Threshold 70% of the adjusted input voltage (24, 48/60, 110,


250V)

Polarity independence Yes

Pulse suppression 1 ms (up to max.100 ms programmable in steps of 1


ms)
*) Regardless of the adjusted input voltage the max. voltage 287,5 V DC can be connected

Command output IFC-P

Contact type Relay NO

Switching power (max.) 250 VA

Switching voltage (max.) 350 V DC or peak AC

Switching current (max.) 1,5 A DC or peak AC

Switching current (max.) <2,5 ms 5 A DC or peak AC

Carry current 2,5 A DC or peak AC

Insulation withstand voltage 2,5 kV rms

Command Output IFC-D

Contact type Relay NO, heavy duty

Switching power 150 W (DC)


1250 VA (AC)

Switching voltage (max.) 380 V DC or peak AC


220 V DC
Switching current (max.) 5 A DC or peak AC (30A0,5ms)

Carry current (max) 5 A DC or peak AC

Insulation withstand voltage 2,5 kV rms

Signaling Output IFC-S

See IFC-D

SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 3


Technical Data SWT 3000 Equipment Manual

Transmission via Digital Networks

Digital Interface

64 Kb/s X21 or
G703.1
2 Mb/s G703.6 sym. 120 Ohm
G703.6 asym. 75 Ohm

Transmission time *

64 Kb/s < 5ms

2 Mb/s < 3ms

*Values are given for the IFC-P module. If the IFC-D module is used all specified signal transmission delays are prolonged
by about 4 ms

Security

PUC < 10-8

Dependability

PMC < 10-4 at BER of 10-6

Transmission via Analog Network

Modulation type

F6 modulation (FSK) or coded tripping CT

Broadband equipments

Trip frequencies 0,3 to 2,03 kHz

Guard 2,61 or 3,81 kHz

Narrowband modulation

Channel 1 0,63 to 1,26 kHz

Channel 2 1,64 to 2,27 kHz

Channel 3 2,65 to 3,28 kHz

Channel 4 3,16 to 3,79 kHz

Page - 4 Edition p3_3_2x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual Technical Data

Transmission time (SWT 3000 stand alone)*

Broad band equipment


Single purpose < 10ms (F6, CT)
Alternate multi purpose F2 < 15ms (F6, CT)
Narrowband equipment < 15ms (F6)

* Values are given for the IFC-P module. If the IFC-D module is used all specified signal transmission delays are pro-
longed by about 4 ms
Operation via the PLC system ESB 2000i will prolong the transmission time by about 4ms

Transmission time (SWT 3000 integrated into PowerLink)*


Broad band equipment

Single purpose < 10ms (F6, CT)

Alternate multi purpose


F2 + AMP < 15ms (F6, CT)
Alternate multi purpose
DP + AMP < 19ms (F6, CT)
Simultaneous multipurpose < 10ms (F6, CT)
Narrow band equipments

Using speech-plus band < 19ms (F6, CT)

*Values are given for the IFC-P module. If the IFC-D module is used all specified signal transmission delays are prolonged
by about 4 ms
Operation via the PLC system ESB 2000i will prolong the transmission time by about 4ms

SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 5


Technical Data SWT 3000 Equipment Manual

SWT 3000 Fibre optic module FOM

Module Type FOL1 FOS1 FOS2


Long range SM Short range SM Short range MM
Optical module SFP-Transceiver
Connector Industry standard duplex LC connector
Wavelength class (nm) 1550 1310 850
Average output power (dBm) max: 0 -8 -3
min: -5 -15 -10
Maximum input power (dBm) -10 -8 0
64 kbit/s -48 -48 -17
Minimum input power (dBm) 2 Mbit/s -38 -32 -17
to PowerLink --- -28 -17
64 kbit/s 43 33 7
Optical budget (dB) 2 Mbit/s 33 17 7
to PowerLink --- 13 7
64 kbit/s 154 87 2
Range [km] 2 Mbit/s 118 45 2
Depending on the fiber to PowerLink --- 34 2

Used values for calculation 1550 nm SM 0,28 db/km


of the range in km 1310 nm SM 0,38 db/km
(incl. Splices) 850 nm MM 3,5 db/km
SM = single mode fiber
MM = multi mode fiber

Technical data FOBox

Power Supply
Input voltage 20 72 V DC / 22 60 V AC
Power Consumption max. 3,5 W

Alarm Output
Contact type Changeover contact
Switching power max. 1250 VA / 150 W
Switching voltage max. 380 V AC / 220 V DC
Continuous current 5 A AC/DC

Mechanical Design
Dimensions (approx) 230x110x60 mm
(mounting onto DIN rail)
Insulation withstand voltage
Power supply 2,5 kVrms
Alarm outputs 2,5 kVrms
Digital input/output
G703.6 sym. 500 Vrms

Page - 6 Edition p3_3_2x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual Technical Data

Security

improved by INC < 10-6

Dependability

improved by INC < 10-4 at SNR of 6 dB

Voice frequency interface CLE

Transmitter
Impedance 600 Ohm
Level (max.) +15 dBm
Receiver
Impedance 600 Ohm or 6 kOhm
Level range -40 dB to + 4 dB

Power supply

Input voltage

24/48/60 V DC (-20% / +15%)

110/220/250 V DC (-20% / +15%) or


115 /230 V AC (15% / +10%) 47 Hz 63 Hz

Power consumption

approx. 22 W / VA

SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 7


Technical Data SWT 3000 Equipment Manual

Alarm output ALRS module


Number of alarm outputs 3 or 6 relay contacts (with two modules)

Contact type Change over contact

Switching power max. 300 W (DC)


1000 VA

Switching voltage max. 250 V DC or peak AC

Switching current max 5 A DC or peak AC

Carry current 1 A DC or peak AC

Alarm output ALR module


Number of alarm outputs 3 or 6 relay contacts (with two modules)

Contact type Change over contact

Switching power max. 300 W (DC)


1000 VA

Switching voltage max. 250 V DC or peak AC

Switching current max 5 A DC or peak AC

Carry current 1 A DC or peak AC

Binary input ALR module


Nominal voltage Binary Input 1 *) 24V 250 V DC (tolerance -20% + 15%)

Polarity independence Yes

Nominal voltage IRIG-B input 5V; 12V, 24V (tolerance 15%)

Polarity independence No! Defined polarity required

Nominal voltage Binary Input 2 *) 24V 250 V DC (tolerance -20% + 15%)

Polarity independence Yes

*) Regardless of the adjusted input voltage the max. voltage of 287,5 V DC can be connected

Clock-Synchronization Input

Nominal input voltage 24 V 250 V DC (-20% / +15%)

Digital input IRIG-B 5V 250 V DC

Ethernet NTP, Network Time Protocol

Network management
SNMPv2 on Ethernet Interface 10/100 BaseT

Page - 8 Edition p3_3_2x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual Technical Data

Service PC

Interface 9,6 kbps


RS 232/Sub-D 9 pol.

Electromagnetic Compatibility EMC

Immunity

Electrostatic discharge 8kV (contact discharge)

Radiated electromagnetic fields 10 V/m (80 2000 MHz)

Bursts
Power supply 4 kV
Data lines 4 kV
Surges
Common mode (line-to-line) 4 kV
Differential mode (line-to-ground) 2 kV
Direct coupling into shield
(communication cable) 2 kV
Conducted disturbances 10 Veff (150 kHz 80 MHz)

Damped oscillatory waves


Common mode (line-to-line) 2,5 kV
Differential mode (line-to-ground) 2,5 kV
Direct coupling into shield
(communication cable) 2,5 kV

Emission

HF disturbance emission EN 50081-2


(20 1000 MHz) Limit Class B

Mechanical design

Dimensions
ES 902 C (19 inch)

482.6 240
37.4

132
132

57.15

84TE=426.72
465.1

Weight
approx. 5 kg (one SWT 3000 in ES 902 C frame)

SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 9


Technical Data SWT 3000 Equipment Manual

Insulation Withstand Voltage

VF input/output 500 Vrms

Power supply 2,5 kVrms

Command input / output 2,5 kVrms

Alarm outputs 2,5 kVrms

Digital input / output


G703.1 500 Vrms
G703.6 sym. 500 Vrms

Impulse Withstand Level 1,2/50s

VF input / output 1 kV

Digital input / output 1 kV

Power supply 5 kV

Command input / output 5 kV

Alarm outputs 5 kV

Climatic Conditions

During operation -5C to + 55C

During storage and transport -40C to +70C

Relative humidity 5 95%

max. abs. humidity (no condensation) 29 g/m3

Mechanical Conditions

Degree of protection IP 20

Vibration 5 9 Hz: 1,5 mm amplitude

9 200 Hz:
0,5 g acceleration
Shock 10 g acceleration

International Standards

Performance and testing of teleprotection transmis- IEC 60834-1 second edition 1999-10
sion equipments of power systems
Power supply and electromagnetic compatibility IEC 60870-2-1

Environmental conditions IEC 60870-2-2

Product safety EN 60950

Page - 10 Edition p3_3_2x 08/09 SIEMENS AG 2008