You are on page 1of 2

Full Colour Touchscreen Display

3 x Processors for Ultimate Reliability


3 x Status LEDs and Speed Off Operation
8 x Programmable LEDs All Protection Functions Included
USB Connections as Standard without Additional Costs

SYMAP-Compact
Stainless Steel Housing Control of Circuit Breaker
Pluggable Connections IEC61850, -103, Profibus, etc.
Multi Lingual SYMAP Parameter Tool Software
Customisable Menu Screens 4 x Parameter Sets
Self Diagnostic Remote Display (optional)
Digital Protection and Control Relays
SYMAP-Compact Technical Data
User-friendly, Flexible and Future Proof
Description Specification
Dimensions (H W D) 210 210 87 (mm)
Cut Out (H W) 192 192 (mm)
Weight 2.2 kg Protection for:
Auxiliary Supply 24/48/60/110/220V DC; 110/230V AC
Power Consumption < 20 W Motors and Generators
Climatic Conditions Operation -20C to +70C
Maximum -40C to +70C
Transformers
Shipping -40C to +70C Transmission & Distribution Systems
Rel. Humidity < 80 %
Housing Front IP54 (IEC529) Mains Decoupling
Rear IP20 (IEC529)
Max. Connections Spring Terminals Max. 1.5 mm
(incl. G59/G10/BDEW/VDN)
Current Terminals Max. 6 mm Feeders

Stucke Elektronik GmbH Stucke Elektronik GmbH offers The SYMAP-Compact range of relays offer flex-
Stucke Elektronik have designed and manufactured premium quality, high Future proof technical product solutions ible digital protection for a wide range of LV and HV
performance electronic devices in Hamburg since 1968. Our systems provi- Full service support including on site commissining applications.
de supervision, protection and control to ensure optimum reliability for your In depth product training
electrical supply. To guarantee the highest quality all our products are manu- At the heart of the SYMAP is a large, full colour, touch
Efficient after sales support and service
factured exclusively in Hamburg, Germany. screen display which quickly enables complete pro-
Ultra fast delivery times
Stucke have been specialists in electronic protection systems for over 40 years.
Subsidiaries and partners in key locations worldwide gramming of all protection and control functions.
Our company is certified according to DIN EN ISO 9001:2008. Alternatively you can do this via PC using the stand-
rmance
Stucke Elektronik GmbH Stucke Worldwide:
ard USB connection. The fully programmable nature
rfo
of these relays gives you an extremely versatile and

cla
GOOSE pe
DNV
Merkurring 26 22143 Hamburg Germany Dsseldorf Stuttgart Madrid Lisbon London Treviso Belgrade

ss P1
cost effective solution for all switchgear applications.
Phone +49(0)40 2274 68 11 Fax +49(0)40 2274 68 24 St. Petersburg Los Angeles Panama City

KEMA
mail@stuckegmbh.de www.stuckegmbh.com Seoul Ulsan Shanghai Singapore Mumbai Brisbane All SYMAP-Compact devices are made in Germany.

teste d
SYMAP-Compact Hardware-Versions SYMAP-Compact Protective Function SYMAP-Compact Protective Function by ANSI
Compact Compact

PT-GND1

CT-GND1
CT1-M/P
F0 F1 F2 F3 F4

PT2
PT1
F0 F1 F2 F3 F4 Scope of Supply avail.*
HMI 21 Distance () () o
21B Generator backup protection o
Full colour touchscreen display 21FL Fault locator 74TC 86
24 Overexcitation (U/F) o
Programmable Hotkeys 25 Synchronizing 5*
Trend Recorder
3 x Status LEDs 27 Undervoltage protection 12*

27Q Undervoltage-/ Reactive power protection


8 x programmable LEDs 27T Undervoltage protection, time-dependent
TIG
YG
Communication 32 Directional power protection 21** (1)
32N/G Zero power protection 21B
PROFIBUS DP (O) (O) (O) (O) (O) 37 Undercurrent protection o 21FL
40 Loss of Field o
MODBUS, RS485/422 46 Negative Phase Sequence Current protection (NPS)
24
25
IEC 60870-5-103 (O) (O) (O) (O) (O) 46BC Broken conductor: I2/I1 27
47 Phase sequence / Phase Balance o 27T
IEC 61850 (O) (O) (O) (O) (O) 48 Motor start-up monitoring: Incomplete sequence o 27Q (1)

Inputs / Outputs
49 Thermal replica 32 (1)

50/51 Overcurrent protection 32N/G (1)


Vector Diagram Ethernet / MiniUSB (rear) 50BF Breaker Failure protection 37

50/51G Ground Overcurrent protection 40 (1)


USB (front) 51LR Locked Rotor o 47 46

Digital Inputs 5/(12) 5/(12) 5/(12) 5/(12) 5/(12) 51MS Motor start protection o 48
49
51/46VR Overcurrent restrained
50BF
Relay Outputs 5/(19) 5/(19) 5/(19) 5/(19) 5/(19) 52 Pole disordance, e.g. phase seggragated undercurrent supervision o
50/51
55 Power factor protection o
Analogue Outputs 59 Overvoltage protection
50/51G
51LR
Analogue Outputs 4-20 mA (2) (2) (2) (2) (2) 59N/G Neutral Voltage Displacement (NVD) 51MS
59LV Low voltage: 10 minutes RMS-protection acc. to VDE-AR-N 4105 o 51/46VR
Analogue Output PWM or +/- 10V (1) (1) (1) (1) (1) 64REF Restricted Earth Fault Porotection 55 (1)

Analogue Inputs for Measurement and Protection


66 No. Of Starts (Motor) o 59
67 Directional Overcurrent protection 59 LV 52
Harmonics Bus Current Inputs (x3) 67G Directional Ground Overcurrent protection (2) 59 N/G CTS
74TC Trip Circuit Supervision PTS 64REF
Earth Fault Current Input (x1) 78 Vektor Surge 66

o
78S Power Swing / Out-Of-Step 67 (1)
Feeder Voltage Input (x3)
79 Automatic Reclose (AR) 67G (2)

BUS1 Voltage Inputs (x3) 81 Frequenzy protection 78


78S (1)
81R RoCoF (df/dt)
BUS2 Voltage Inputs (x3) 81RAV Frequency supervised average (dF/dT) o
79
81
Neutral Voltage Displacement Input (x1) 86 Lockout relay 81 R 87GH
87GH High impedance restricted ground fault protection o 87**
81 R A V
95i Harmonics stabilizer 95i

(O) optional
G59 for ANSI 78 and 81R () () ()
CLD Cold Load Detection CLD
Programmable Logic Functions CTS Current Transformer Supervision SOTF
PTS Potential Transformer Supervision SGF (2)
SGF 100% Stator Ground Fault protection o
Above are examples of SYMAP-Compact display capabilities SOTF Switch On To Fault (1) depending on power measurement at common changeover
TIG Transient/Intermittent Ground Fault protection () () () (2) measured or calculated
YG Neutral Admittance Ground Fault protection () () ()
* Function in development. Please request. o not yet available now available