You are on page 1of 4

Product Specification

03249E

MFR 12
Multi Function Relay
Protection

APPLICATIONS DESCRIPTION

The MFR 1 Series is a family of industrial grade Features True RMS sensing
protective relays that offer multiple protective Configurable trip set points
features in a single package. Configurable delays for each alarm 3 phase independent
Two-line LC display time-overcurrent
Using a digital processor to measure true RMS protection (3Irated)
values enables the control to have a high Package CP
measuring accuracy, regardless of harmonics, 3 configurable relays Programmable relay
transients or disturbing pulses. True RMS current (generator) outputs
Independent time-overcurrent (50/51#)
The MFR 12 model is a complete generator Ground fault (calculated) (50GS/51#GS) Discrete input for
protection unit packaged into one compact IE = IL1 + IL2 + IL3 enabling or remote
device. Typical applications are generators and acknowledgement
switchgear equipment that require independent Package 51V
protection architecture. Different packages offer 8 configurable relays PC and front panel
additional functionality. True RMS current (generator) configurable
True RMS voltage (generator)
The MFR 12/CP is for independent time- Independent time-overcurrent (50/51#) Microprocessor
overcurrent protection (TOC) with configurable Ground fault (calculated) (50GS/51#GS) technology for
tripping times for two different current values. It
Inverse time-overcurrent (IEC255) accurate, repeatable
also includes protection for calculated ground
Inverse time-overcurrent with and reliable
fault.
voltage restraint (51V)
operation
The MFR 12/51V is designed to protect the Package 50-51GN
generator for (independent time-overcurrent Programmable
3 configurable relays
[TOC], calculated ground fault, inverse time- threshold setpoints
overcurrent (acc. to IEC255) and inverse time- Ground fault (measured via current
transformer ../1A or 5A) (50/51GN) with individual time
overcurrent with voltage restraint.
delays
The MFR 12/50-51GN package includes CE marked
protection for measured ground faults via #
not according to ANSI guidelines (three-step protection
current transformer. instead of inverse time characteristic) UL/cUL Listed
The compact size and multiple functions of the GL Approval
MFR 12 help to simplify switchgear design. The
digital display offers a user-friendly interface to
set up the unit as well as monitor the operation
and display of alarms.
SPECIFICATIONS
Accuracy .......................................................................................... Class 1 Relay outputs ................................................................................ isolated
Power supply ............................................................. 24 Vdc (18 to 30 Vdc) Contact material ............................................................................... AgCdO
Intrinsic consumption ..................................................................max. 12 W Load (GP) .................................................24 Vdc@2 Adc, 250 Vac@2 Aac
Ambient temperature ................................................................ -20 to 70 C Pilot duty (PD) ......................................................................24 Vdc@1 Adc
Ambient humidity...................................................... 95 %, non-condensing Housing ...................................................... Type APRANORM DIN 43 700
Voltage ................Rated value /: 66/115 Vac Dimensions .........................................................................9672130 mm
Maximum value (Vmax): 150 Vac Front cut-out ................................................................................9167 mm
Rated voltage Vph-ground: 150 Vac Connection ................................................ screw/plug terminals depending
Rated surge voltage: 2.5 kV on connector 1.5 mm, 2.5 mm or 4mm
Linear measuring range up to ....................................................... 1.3Vrated Front .................................................................................insulating surface
Measuring frequency ................................................50/60 Hz (40 to 70 Hz) Protection system................................................................................ IP 21
Input resistance ........................................................................ [1] 0.21 M Weight ............................................... depending on version, approx. 800 g
Max. power consumption per path ................................................ < 0.15 W Disturbance test (CE) .................................................. tested according to
Current (Irated) .............................................................. [1] ../1 A or [5] ../5 A applicable EN guidelines
Linear measuring range up to ........................................................ 3.0Irated Listings ..................................... UL/cUL listed (note: max. voltages apply)
Load ............................................................................................. < 0.15 VA for ordinary loc., file E231544
Rated short-time cur. (1 s)...............................[1] 100.0Irated, [5] 20.0Irated Approvals........................................................... GL (Germanischer Lloyd)
Discrete inputs .............................................................................. isolated
Input range ....................................................................18 to 250 Vac or dc
Input resistance .....................................................................approx. 68 k

DIMENSIONS
Front view

Configuration port
35 mm
65 mm
72 mm

27 mm

Back plate mounting


optional (please order
brackets P/N 8923-1023)
Bottom view
130 mm 50 mm
Back view with
connecting terminals
8

Configuration port
1 16

40 45
96 mm

90 mm

130 mm

70 75

32 17

Configuration port 2005-09-13 | MFR 12 Dimensions r1ww-3705-ab.skf


WIRING DIAGRAM
FEATURES OVERVIEW
CONTACT MFR 12

North & Central America


Tel.: +1 970 962 7331

50-51GN
SalesPGD_NAandCA@woodward.com

51V
CP
ANSI
South America
Tel.: +55 19 3708 4800 Measuring/Display
SalesPGD_SA@woodward.com Voltage
Current
Europe Accessories
Tel. Stuttgart: +49 711 78954 510 Configuration via PC #1
Tel. Kempen: +49 2152 145 331 Protection
SalesPGD_EUROPE@woodward.com
Independent time-overcurrent monitoring (TOC) 50/51*
Inverse time-overcurrent monit. (acc. to IEC255) #2
Middle East & Africa
Inverse time-overcurrent monit. with volt. restraint #3 51V
Tel.: +971 2 6275185
Ground fault monitoring, calculated 50GS/51GS*
SalesPGD_MEA@woodward.com
Ground fault monitoring, measured (1A or 5A) 50/51GN
Russia I/O's
Tel.: +7 812 319 3007 Output relays (configurable) 74 3 8 3
SalesPGD_RUSSIA@woodward.com Listings/Approvals
CE marked
China UL/cUL listed
Tel.: +86 512 8818 5515 GL (Marine)
SalesPGD_CHINA@woodward.com
Part Numbers P/N
Measuring inputs ../1 A 8441-1106 8441-1132
India
Measuring inputs ../5 A 5448-883 8441-1008
Tel.: +91 124 4399 500
SalesPGD_INDIA@woodward.com
Measuring inputs 100 Vac, ../1 A 8441-1082
Measuring inputs 100 Vac, ../5 A 8441-1006
ASEAN & Oceania
* not according to ANSI guidelines (three-step protection instead of inverse time characteristic)
Tel.: +49 711 78954 510 #1 Configuration software LeoPC available free at www.woodward.com,
SalesPGD_ASEAN@woodward.com connection requires Woodward DPC cable P/N 5417-1251
#2 only when inverse time-overcurrent monitoring with voltage restraint is disabled
#3 measured via 100 Vac measuring input

www.woodward.com

Subject to alterations,
errors excepted.

Subject to technical modifications.

This document is distributed for


informational purposes only. It is not
to be construed as creating or
becoming part of any Woodward
Company contractual or warranty
obligation unless expressly stated in
a written sales contract.

We appreciate your comments about


the content of our publications.
Please send comments including the
document number below to
stgt-doc@woodward.com

Woodward

All Rights Reserved

03249E - 2013/7/Stuttgart