IM 01C50B01-01E
12th Edition
Yokogawa Electric Corporation
CONTENTS
CONTENTS
REVISION RECORD
ii IM 01C50B01-01E
1. PREFACE
1. PREFACE
The YTA temperature transmitter is fully factory-tested No maintenance should be performed on explosion-
according to the specifications indicated on the order. proof type temperature transmitters while the
equipment is energized. If maintenance is required
In order for the YTA temperature transmitter to be
with the cover open, always first use a gas detector
fully functional and to operate in an efficient manner,
to check that no explosive gases are present.
the manual must be carefully read to become familiar
If the user attempts to repair or modify an
with the functions, operation, and handling of the
explosionproof type transmitter and is unable to
YTA.
restore it to its original condition, damage to the
This manual gives instructions on handling, wiring and explosionproof features result, leading to dangerous
maintenance of YTA110, YTA310 and YTA320 conditions. Contact your authorized Yokogawa
temperature transmitters. Changing the parameter Electric Corporation representative for repairs or
settings requires a terminal dedicated to the HART modifications of an explosionproof type transmitter.
protocol or the BRAIN protocol. For details on how to
set the parameters of these transmitters, refer to the
For Safe Use of Product
BRAIN Protocol IM 0lC50T03-01E or HART
Please give your attention to the followings.
Protocol IM 01C50T01-01E.
For FOUNDATION Fieldbus communication type, (a) Installation
please refer to IM 01C50T02-01E in addition to this The instrument must be installed by an expert
manual. engineer or a skilled personnel. The procedures
described about INSTALLATION are not permitted
Notes on the Users Manual for operators.
This manual should be delivered to the end user.
In case of high process temperature, care should be
The information contained in this manual is subject
taken not to burn yourself because the surface of the
to change without prior notice.
case reaches a high temperature.
The information contained in this manual, in whole
or part, shall not be transcribed or copied without All installation shall comply with local installation
notice. requirement and local electrical code.
In no case does this manual guarantee the merchant
ability of the transmitter or its adaptability to a (b) Wiring
specific client need. The instrument must be installed by an expert
Should any doubt or error be found in this manual, engineer or a skilled personnel. The procedures
submit inquiries to your local dealer. described about WIRING are not permitted for
No special specifications are contained in this operators.
manual.
Please confirm that voltages between the power
Changes to specifications, structure, and components
supply and the instrument before connecting the
used may not lead to the revision of this manual
power cables and that the cables are not powered
unless such changes affect the function and perfor-
before connecting.
mance of the transmitter.
(c) Maintenance
Notes on Safety and Modifications Please do not carry out except being written to a
Before handling the YTA, it is absolutely imperative maintenance descriptions. When these procedures
that users of this equipment read and observe the are needed, please contact nearest YOKOGAWA
safety instructions mentioned in each section of the office.
manual in order to ensure the protection and safety Care should be taken to prevent the build up of drift,
of operators, the YTA itself and the system contain- dust or other material on the display glass and
ing the transmitter. We are not liable for any name plate. In case of its maintenance, soft and dry
accidents arising out of handling that does not cloth is used.
adhere to the guidelines established in the safety
instructions.
1-1 IM 01C50B01-01E
1. PREFACE
1-2 IM 01C50B01-01E
1. PREFACE
ATEX Documentation
This procedure is only applicable to the countries in SF
European Union.
Kaikkien ATEX Ex -tyyppisten tuotteiden kytthjeet
ovat saatavilla englannin-, saksan- ja ranskankielisin.
GB Mikli tarvitsette Ex -tyyppisten tuotteiden ohjeita
omalla paikallisella kielellnnne, ottakaa yhteytt
All instruction manuals for ATEX Ex related products lhimpn Yokogawa-toimistoon tai -edustajaan.
are available in English, German and French. Should
you require Ex related instructions in your local
language, you are to contact your nearest Yokogawa P
office or representative.
Todos os manuais de instrues referentes aos produtos
Ex da ATEX esto disponveis em Ingls, Alemo e
DK Francs. Se necessitar de instrues na sua lngua
relacionadas com produtos Ex, dever entrar em
Alle brugervejledninger for produkter relateret til contacto com a delegao mais prxima ou com um
ATEX Ex er tilgngelige p engelsk, tysk og fransk. representante da Yokogawa.
Skulle De nske yderligere oplysninger om hndtering
af Ex produkter p eget sprog, kan De rette
henvendelse herom til den nrmeste Yokogawa F
afdeling eller forhandler.
Tous les manuels dinstruction des produits ATEX Ex
sont disponibles en langue anglaise, allemande et
I franaise. Si vous ncessitez des instructions relatives
aux produits Ex dans votre langue, veuillez bien
Tutti i manuali operativi di prodotti ATEX contacter votre reprsentant Yokogawa le plus proche.
contrassegnati con Ex sono disponibili in inglese,
tedesco e francese. Se si desidera ricevere i manuali
operativi di prodotti Ex in lingua locale, mettersi in D
contatto con lufficio Yokogawa pi vicino o con un
Alle Betriebsanleitungen fr ATEX Ex bezogene
rappresentante.
Produkte stehen in den Sprachen Englisch, Deutsch
und Franzsisch zur Verfgung. Sollten Sie die
E Betriebsanleitungen fr Ex-Produkte in Ihrer
Landessprache bentigen, setzen Sie sich bitte mit
Todos los manuales de instrucciones para los productos Ihrem rtlichen Yokogawa-Vertreter in Verbindung.
antiexplosivos de ATEX estn disponibles en ingls,
alemn y francs. Si desea solicitar las instrucciones de
estos artculos antiexplosivos en su idioma local, S
deber ponerse en contacto con la oficina o el
Alla instruktionsbcker fr ATEX Ex (explosionsskra)
representante de Yokogawa ms cercano.
produkter r tillgngliga p engelska, tyska och
franska. Om Ni behver instruktioner fr dessa
NL explosionsskra produkter p annat sprk, skall Ni
kontakta nrmaste Yokogawakontor eller representant.
Alle handleidingen voor producten die te maken
hebben met ATEX explosiebeveiliging (Ex) zijn
verkrijgbaar in het Engels, Duits en Frans. Neem, GR
indien u aanwijzingen op het gebied van
explosiebeveiliging nodig hebt in uw eigen taal, contact
ATEX Ex
op met de dichtstbijzijnde vestiging van Yokogawa of
, .
met een vertegenwoordiger.
Ex
Yokogawa
.
1-3 IM 01C50B01-01E
1. PREFACE
SK PL
CZ
SLO
LT H
BG
LV
EST RO
1-4 IM 01C50B01-01E
2. NOTES ON HANDLING
2. NOTES ON HANDLING
The YTA temperature transmitter is fully factory- 2.2 Transport
tested upon shipment. When the YTA is delivered,
check the appearance for damage, and also check that To prevent damage while in transit, leave the transmit-
the transmitter mounting parts shown in Figure 2.1 are ter in the original shipping container until it reaches
included with your shipment. If No Mounting the installation site.
Bracket is indicated, no transmitter mounting bracket
is included. 2.3 Storage
When an extended storage period is expected, observe
the following precautions:
Bracket 1. If at all possible, store the transmitter in factory-
fastening bolt shipped condition, that is, in the original shipping
U-bolt nut container.
2. Choose a storage location that satisfies the follow-
Horizontal ing requirements.
Spring pipe mounting
Vertical pipe washer bracket A location that is not exposed to rain or water.
mounting A location subject to a minimum of vibration or
bracket
impact.
Transmitter The following temperature and humidity range is
Spring fastening bolt
washer recommended. Ordinary temperature and humidity
U-bolt
(25C, 65%) are preferable.
Temperature: No Integral indicator 40 to 85C
Bracket U-bolt nut
fastening nut With Integral indicator 30 to 80C
F0201.EPS
Humidity: 5 to 100% RH (at 40C)
Figure 2.1 Transmitter mounting parts
3. The performance of the transmitter may be im-
2.1 Nameplate paired if stored in an area exposed to direct rain and
water. To avoid damage to the transmitter, install it
The model name and configuration are indicated on immediately after removal from shipping container.
the nameplate. Verify that the configuration indicated Follow wiring instructions in Chapter 5.
in the Model and Suffix Code in Chapter 7 is in
compliance with the specifications written on the order 2.4 Choosing the Installation
sheet.
Location
Model name
Specification code Serial No. Although the temperature transmitter is designed to
TEMPERATURE
operate in a vigorous environment, to maintain
TRANSMITTER 420 mA DC
YTA stability and accuracy, the following is recommended:
10.530 (42) V DC
:Refer to USERS MANUAL.
(1) Ambient Temperature
TOKYO 180-8750 JAPAN
2-1 IM 01C50B01-01E
2. NOTES ON HANDLING
(3) Impact and Vibration 4. Turn the power of the insulation resistance meter
It is recommended that the instrument be installed in a ON and measure the insulation resistance. The
location that is subject to a minimum amount of impact duration of the applied voltage must be the period
and vibration. during which 100M or more is confirmed (or
20M if the unit is equipped with a built-in
2.5 Use of a Transceiver arrester).
5. Upon completion of the test, remove the insulation
Although the temperature transmitter is designed to resistance meter, connect a 100K resistor between
resist influence from high frequency noise; use of a the transition wiring, and allow the electricity to
transceiver in the vicinity of installation may cause discharge. Do not touch the terminal with your bare
problems. Installing the transmitter in an area free from hands while the electricity is discharging for more
high frequency noise (RFI) is recommended. than 1 second.
Testing between the output terminal and
2.6 Insulation Resistance Test grounding terminal
and Withstand Voltage Test 1. Lay transition wiring between the + terminal, the -
terminal, and the check terminal of the terminal box,
then connect an insulation resistance meter (with the
CAUTION power turned OFF) between the transition wiring
and the grounding terminal. The polarity of the
(1) Overvoltage of the test voltage that is so transition wiring must be positive and that of the
small that it does not cause an dielectric grounding terminal must be negative.
breakdown may in fact deteriorate insulation 2. Turn the power of the insulation resistance meter
and lower the safety performance; to prevent ON and measure the insulation resistance. The
this it is recommended that the amount of duration of the applied voltage must be the period
testing be kept to a minimum. during which 100M or more is confirmed (or
(2) The voltage for the insulation resistance test 20M if the unit is equipped with a built-in
must be 500 VAC or lower, and the voltage arrester).
for the withstand voltage test must be 500 3. Upon completion of the test, remove the insulation
VAC or lower. Failure to heed these guide- resistance meter, connect a 100K resistor between
lines may cause faulty operation. the transition wiring and the grounding terminal, and
(3) Where a built-in arrester is provided (suffix allow the electricity to discharge. Do not touch the
code: /A), the voltage for the insulation terminal with your bare hands while the electricity is
resistance test must be 100 VDC or lower, discharging for more than 1 second.
and the voltage for the withstand voltage test
Testing between the input terminal and
must be 100 VAC or lower. Failure to heed grounding terminal
these guidelines may cause faulty operation. 1. Lay transition wiring between terminals 1, 2, 3, 4
and 5 of the terminal box, and connect the insulation
Follow the steps below to perform the test, the wiring resistor (with the power turned OFF) between the
of the transmission line must be removed before transition wiring and the grounding terminal. The
initiating testing. polarity of the transition wiring must be positive and
that of the grounding terminal must be negative.
2.6.1 Insulation resistance test procedure 2. Turn the power of the insulation resistance meter
ON and measure the insulation resistance. The
Testing between the output terminal and duration of the applied voltage must be the period
input terminal during which 100M or more is confirmed (or
1. Lay transition wiring between the + terminal, the - 20M if the unit is equipped with a built-in
terminal, and the check terminal of the terminal box. arrester).
2. Lay wiring across terminals 1, 2, 3, and 4 of the 3. Upon completion of the test, remove the insulation
terminal box. resistance meter, connect a 100K resistor between
3. Connect the insulation resistance meter (with the the transition wiring and the grounding terminal, and
power turned OFF) between the transition wiring of allow the electricity to discharge. Do not touch the
Steps 1 and 2 above. The polarity of the input terminal with your bare hands while the electricity is
terminals must be positive and that of the output discharging for more than 1 second.
terminals must be negative.
2-2 IM 01C50B01-01E
2. NOTES ON HANDLING
2-4 IM 01C50B01-01E
2. NOTES ON HANDLING
42 V DC Max.
Conduit Sealing Fitting 4 to 20 mA DC
Signal
2-5 IM 01C50B01-01E
2. NOTES ON HANDLING
Note 5. Special condition for safe use WARNING: AFTER DE-ENERGIZING, DELAY
Because the enclosure of the Temperature Transmit- 5 MINUTES BEFORE OPENING.
ter is made of aluminium, if it is mounted in an area WHEN THE AMBIENT TEMP.
where the use of category 1G apparatus is required, 70C, USE THE HEATRESISTING
it must be installed such, that, even in the event of CABLES OF HIGHER THAN 90C.
rare incidents, ignition source due to impact and Take care not to generate mechanical spark when
friction sparks are excluded. access to the instrument and peripheral devices in
hazardous location.
[Installation Diagram]
Note 5. Maintenance and Repair
Hazardous Nonhazardous
Location Location The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Transmitter Safety Barrier *1 Electric Corporation is prohibited and will void
1 + + KEMA Flameproof Certification.
2 Supply
3
4 Sensor
5
c) CENELEC ATEX Type of Protection n
F0208.EPS
WARNING
*1: In any safety barriers used the output current must be limited by When using a power supply not having a non-
a resistor R such that Imaxout-Uz/R.
incendive circuit, please pay attention not to
ignite in the surrounding flammable atmosphere.
b) CENELEC ATEX (KEMA) Flameproof Type In such a case, we recommend using wiring
and Dust Ignition Proof Type metal conduit in order to prevent the ignition.
Caution for CENELEC ATEX (KEMA) Flameproof
Type and Dust Ignition Proof Type Caution for CENELEC ATEX Type of Protection n
Note 1. Model YTA110/KU2, YTA310/KU2 and Note 1. Model YTA110/KU2, YTA310/KU2 and
YTA320/KU2 temperature transmitters YTA320/KU2 temperature transmitters for
are applicable for use in hazardous potentially explosive atmospheres:
locations: Applicable standard: EN60079-15:2003
No. KEMA 07ATEX0130 Referential standard: IEC60079-0:1998,
Applicable Standard: EN 60079-0, IEC 60079-1, IEC60079-11:1999
EN 61241-0, EN 61241-1 Type of Protection and Marking Code: II 3G EEx
Type of Protection and Marking Code: II 2G Ex d nL IIC T5, T4
IIC T6/T5, II 2D Ex tD A21 IP67 T70C, T90C Temperature Class: T5, T4
Ambient Temperature for Gas Atmospheres: Ambient Temperature: 40 to 50C for T5, 40 to
40 to 75C (T6), 40 to 80C (T5) 70C for T4
Ambient Temperature for Dust Atmospheres: Enclosure: IP67
40 to 65C (T70C), 40 to 80C (T90C) Note 2. Electrical Data
Enclosure: IP67 [Supply circuit]
Note 2. Electrical Data Ui = 30 V
Supply voltage: 42 V dc max. Effective internal capacitance, Ci = 20 nF
Output signal: 4 to 20 mA Effective internal inductance, Li = 660 H
Note 3. Installation [Sensor circuit]
All wiring shall comply with local installation Uo= 8.6 V Io = 30 mA Po = 70 mW
requirement. Max. allowed external capacitance, Co = 3 F
The cable entry devices shall be of a certified Max. allowed external inductance, Lo = 20 mH
flameproof type, suitable for the conditions of use. Note 3. Installation
Note 4. Operation All wiring shall comply with local installation
Keep strictly the WARNING on the label on the requirements. (refer to the installation diagram)
transmitter.
2-6 IM 01C50B01-01E
2. NOTES ON HANDLING
TRANSMITTER
YTA
420 mA DC
EEx ia IIC T5
Tamb -40 TO 50C
EEx ia IIC T4
Tamb -40 TO 70C
EEx d IIC T6
Tamb -40 TO 75C
EEx d IIC T5
Tamb -40 TO 80C
Tamb -40 TO 50C
EEx nL IIC T4
Tamb -40 TO 70C
ENCLOSURE: IP67
ENCLOSURE: IP67 ENCLOSURE: IP67 SUPPLY INPUT
SUPPLY INPUT WARNING Ui=30V
Ui=30V, Ii=165mA, Pi=900mV Ci=20nF, Li=660H
AFTER DE-ENERGIZING, DELAY SENSOR OUTPUT
Ci=20nF, Li=660H
5 MINUTES BEFORE OPENING.
SENSOR OUTPUT Uo=8.6V, Io=30mA
WHEN THE AMBIENT TEMP.70C,
0344 Uo=8.6V, Io=30mA, Po=70mW
USE THE HEAT-RESISTING
Po=70mW, Co=3F
10.530 (42) V DC Co=3F, Lo=20mH
CABLES90C.
Lo=20mH
:Refer to USERS MANUAL. Cross out unnecessary marking other than the selected type
TOKYO 180-8750 JAPAN of protection. When II 3G is selected, cross out 0344.
F0212.EPS
F0298.EPS
Ratings of the Power Supply are as follows:
Maximum Voltage: 30 V MODEL: Specified model code.
(2) Electrical Connection SUFFIX: Specified suffix code.
STYLE: Style code.
The type of electrical connection is stamped near
SUPPLY: Supply voltage.
the electrical connection port according to the
NO.: Serial number and year of production*1.
following marking.
OUTPUT: Output signal.
FACTORY CAL: Specified calibration range.
TOKYO 180-8750 JAPAN:
The manufacturer name and the
address*2.
*1: The third figure from the left shows the production
year. The relationship between the production year
Location of the marking and the third figure is shown below.
F0200.EPS
The third figure F G H J K L M
(3) Installation The year of
2006 2007 2008 2009 2010 2011 2012
Production
T0202.EPS
WARNING For example, the production year of the product
engraved in NO. column on the name plate as
All wiring shall comply with local installation follows is 2006.
requirement and local electrical code.
C2F616294
(4) Operation
The year 2006
WARNING *2: 180-8750 is a postal code which represents the
following address.
OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH 2-9-32 Nakacho, Musashino-shi, Tokyo Japan
THIS USERS MANUAL
Take care not to generate mechanical sparking
when access to the instrument and peripheral
devices in hazardous locations.
2-7 IM 01C50B01-01E
2. NOTES ON HANDLING
transmitter:
Supply Circuit (+ and ) Sensor Circuit ( 1 to 5 ) b) FM Non-incendive Type
Vmax : 30 V Voc/Vt : 9 V Caution for FM Non-incendive type.
Imax : 165 mA Isc/It : 40 mA Note 1. Model YTA /FU1 temperature transmitter
Pmax : 0.9 W Ca : 1 F is applicable for use in hazardous
Ci : 18 nF La : 10 mH locations
Li : 730 H Applicable Standard: FM 3600, FM 3610, FM 3611,
For the sensor input circuitry, these entity parameters FM 3810
must be taken into account when installed. Non-incendive for Class I, Division 2, Groups A, B,
Installation Requirements between temperature C & D.
transmitter and safety barrier: Class II, Division 2, Groups E, F & G and Class III,
Voc Vmax, Isc Imax, Ca Ci + Ccable, La Division 1 Hazardous Locations.
Li + Lcable Outdoor hazardous locations, NEMA 4X.
Voc, Isc, Ca and La are parameters of the safety Temperature Class: T4
barrier. Ambient temperature: 40 to 60C
Note 3. Installation Note 2. Non-incendive field wiring Parameters of
The safety barrier must be FM approved. the temperature transmitter:
Input voltage of the safety barrier must be less than Supply Circuit (+ and -) Sensor Circuit ( 1 to 5 )
250 Vrms/Vdc. Vmax : 30 V Voc/Vt : 9 V
Installation should be in accordance with ANSI/ISA Imax : 165 mA Isc/It : 40 mA
RP12.6 Installation of Intrinsically Safe Systems Pmax : 0.9 W Ca : 1 F
for Hazardous (Classified) Locations and the Ci : 18 nF La : 10 mH
National Electric Code (ANSI/NFPA 70). Li : 730 H
Intrinsically safe sensor must be FMRC Approved or For the sensor input circuitry, these non-incendive
be simple apparatus (a device which will neither parameters must be taken into account when
generate nor store more than 1.2 V, 0.1 A, 25 mW installed.
or 20 J, ex. switches, thermocouples, LEDs or Installation Requirements between temperature
RTDs). transmitter and general purpose equipment:
Dust-tight conduit seal must be used when installed Voc Vmax, Isc Imax, Ca Ci + Ccable, La
in a Class II and III environments. Li + Lcable
Note 4. Maintenance and Repair Voc , Isc, Ca and La are non-incendive field wiring
The instrument modification or parts replacement by parameters of general purpose equipment.
other than authorized representative of Yokogawa Note 3. Installation
Electric Corporation is prohibited and will void The general purpose equipment must be FM ap-
Factory Mutual Intrinsically safe and Nonincendive proved which have non-incendive field wiring
Approval. parameters.
2-8 IM 01C50B01-01E
2. NOTES ON HANDLING
2-9 IM 01C50B01-01E
2. NOTES ON HANDLING
series. The breaking capacity refers to the upper [Output parameters (terminals 1 to 5)]
limit of current that can be cut off. Normally, a Maximum Output Voltage(Uo) = 8.6 V
fuse or a circuit breaker having a breaking Maximum Output Current(Io) = 30 mA
capacity of greater than 5000 A is used in power Maximum Output Power(Po) = 62 mW
Maximum External Capacitance = 1 F
supply circuits. Confirm that this is true with your
Maximum External Inductance = 20 mH
factory. No extra measures need be taken after Maximum External Connected L/R = 0.5mH/
the confirmation. Note 3. Installation
Note that the rated current of the YTA series in All wiring shall comply with Australian Standards.
terms of explosion protection is 4 to 20 mA; The input and output cables are to be installed either
keep the input current of the YTA series within as seperate cables or as seperate screened circuits.
the appropriate range. Certified IP66/67 glands or plugs must be used on
the enclosure cable entries.
*1: Refers to a current that flows when a fuse in a circuit is Note 4. Maintenance and Repair
substituted with a connecting metal piece having virtually no The instrument modification or parts replacement by other
impedance and the circuit is then shorted. For AC circuits, this
current is represented by a root-mean-square value (JIS C6575).
than authorized representative of Yokogawa Electric
Corporation is prohibited and will void SAA Certification.
2.7.5 SAA Certification [Installation Diagram for intrinsically safe type]
Model YTA110/SU1, YTA310/SU1 and YTA320/SU1 Hazardous Location Nonhazardous Location
(Zone 0)
temperature transmitters can be selected the type of
Transmitter Safety Barrier *1
protection (SAA Intrinsically Safe, Type of Protection 1 + +
n or Flameproof) for use in hazardous locations. 2 Supply
Note 1. For the installation of this transmitter, 3
4 Sensor
once a particular type of protection is 5
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about [ Installation Diagram for Type n ]
the type of protection in this instruction Hazardous Location Nonhazardous Location
(Zone 2)
manual.
Transmitter
Note 2. In order to avoid confusion, cross out + +
unnecessary marking on the label other Suppry Power Supply
than the selected type of protection when
the transmitter is installed.
a) SAA Intrinsically Safe/Type N Type F2013.EPS
Caution for SAA Intrinsically safe/Type n type *1: In any safety barriers used the output current must be limited by
Note 1. Model YTA110/SU1, YTA310/SU1 and a resistor R such that Imaxout-Uz/R.
2-11 IM 01C50B01-01E
3. PART NAMES AND FUNCTIONS
Name plate
Stud bolt
CPU assembly
Terminal cover
LCD assembly
(with indicator)
Grounding
Amp. cover terminal
Tag plate
Grounding
terminal
Lock screw
(for CENELEC, SAA and Wiring connector
TIIS flameproof type) (output signal side)
Wiring connector
(input signal side)
F0301.EPS
3-1 IM 01C50B01-01E
3. PART NAMES AND FUNCTIONS
To change the direction of output arising from burnout, B.M.: Lit during burst mode transfer of HART commu-
switch the setting pin on the CPU assembly (see Figure nication specification.
3.1 and Table 3.1). To change the direction of output F.O.: Lit when manual mode is active.
arising out of sensor burnout, a dedicated hand-held
terminal is required to rewrite the parameters within W.P.: Lit when write protect status is active.
the transmitter. For details, refer to the separate
(4)Input display
instruction manual, IM 01C50T01-01E HART
Indicates the type of input in accordance with the value
Protocol or IM 01C50T03-01E BRAIN Protocol.
shown in the column in Item (5).
Table 3.1 Output Direction Setting Pins for Hardware
Error Burnout Sns1: Meant to show the process variable allocated to
Pin Hardware error Hardware error Remark
Sensor 1.
position burnout burnout
direction output Sns2: Meant to show the process variable allocated to
H HIGH 110% or more Set to HIGH upon Sensor 2. (Can be displayed only with the
(21.6 mA DC) shipment from the YTA320.) .
L factory
H LOW -5% or less Set to LOW when Term: Meant to show the temperature of the terminal
(3.2 mA DC) suffix code /C1 box of the temperature transmitter.
L is provided
T0301.EPS Avg: Meant to show the average of the process
variable allocated to Sensor1 and Sensor2. (Can
3.3 Built-in Indicator Display be displayed only with the YTA320.).
(6)Unit display Upon shipment from the factory, the indicator is set as
The unit specified as the unit of process in the process follows.
variable display column in Item (5) is lit. The output Table 3.2 Setting of Indicator upon Shipment from the
display is fixed to mA or %. Factory
3-3 IM 01C50B01-01E
4. INSTALLATION
4. INSTALLATION
U-bolt nut
Horizontal pipe
mounting bracket
Spring washer
Transmitter
fastening bolt
U-bolt
Bracket
fastening bolt
U-bolt nut
Spring washer
Bracket
U-bolt fastening nut
F0401.EPS
5. WIRING
5.1 Notes on Wiring <Hazardous location> <Nonhazardous location>
Input signal
(thermocouple,
Distributor
RTD, mV, etc.) (power supply unit) Receiver
IMPORTANT +
Apply a waterproofing sealant to the
threads of the connection port. (It is recom-
mended that you use non-hardening sealant
Output signal
made of silicon resin for waterproofing.)
F0501.EPS
Lay wiring as far away as possible from
electrical noise sources such as large trans- Figure 5.1 Loop Construction (for General-use Type and
Flameproof Type)
formers, motors and power supplies.
Remove the wiring connection dust-caps <Hazardous location> <Nonhazardous location>
before wiring. Input signal
To prevent electrical noise, the signal cable (thermocouple, Distributor
RTD, mV, etc.) (power supply unit) Receiver
and the power cable must not be housed in
+ Output signal
the same conduit.
The terminal box cover is locked by an Allen
Safety
head bolt (a shrouding bolt) on CENELEC, barrier
SAA and TIIS flameproof type transmitters.
When the shrouding bolt is driven clockwise
F0502.EPS
by an Allen wrench, it is going in and cover
lock is released, and then the cove can be Figure 5.2 Loop Construction (for Intrinsically Safe
Type)
opened by hands. See Subsection 6.3
Disassembly and Reassembly for details.
600
External R= E10.5
0.0236 Communication
load
5.2 Loop Construction resistance applicable range
BRAIN and HART
The YTA is a two-wire temperature transmitter that R 250
uses the output power supply wiring and signal wiring ()
alternately.
The transmission loop requires DC power. Connect the 10.5 16.4 24.7 42
transmitter with the distributor as shown in Figure 5.1 Power supply voltage E (V DC)
or Figure 5.2. F0503.EPS
5-1 IM 01C50B01-01E
5. WIRING
WARNING
If the YTA is TIIS flameproof and the ambient The temperature sensor is to be connected
temperature is 50C or more, use an external as shown in Figures 5.6 and 5.7.
cable having a maximum allowable heat resis-
tance of at least 70C in consideration of the
instruments generation of heat or the cables
self-heating.
5-2 IM 01C50B01-01E
5. WIRING
2 input (YTA320)
(A1)
1 (+) 1 (B1) Power
2 2 (B1) supply
3 () 3 +
(B2)
4 4 (B2)
5 (+)
5
(A2) F0509.EPS
Thermocouple and RTD and resistance
DC voltage (3-wire) Figure 5.9 Check Meter Connection
(A1)
1 (+) 1
(B1)
2 () 2
3 (B) 3
(B2)
4 (B) 4
(A2)
5 (A) 5
Thermocouple + RTD and resistance
RTD and resistance (2-wire)
(3-wire)
5-3 IM 01C50B01-01E
5. WIRING
5.5 Wiring Cautions Table 5.1 Flameproof Packing and Appropriate Cable
Outer Diameters
(1) General-use Type and Intrinsically Safe Wiring Port Appropriate Identifying Part
Type Thread Cable Outer Mark Number
Use metal conduit wiring or a waterproof gland Diameter Diameter (mm)
(metal wiring conduit JIS F 8801) for cable wiring. G1/2
8 -10 16 8-10
G9601AM
Apply nonhardening sealant to the threads of the 10.1-12 16 10-12
wiring tap and a flexible fitting for secure water- T0501.EPS
proofing. Figure 5.10 shows an example of wiring Follow the procedure below to install the flameproof
on the output side. This example also applies to the packing adapter.
wiring on the input side.
1. Screw the flameproof packing adapter into the
Flexible fitting terminal box until the O-ring touches the terminal
Wiring conduit
box wiring port (at least 6 full turns), and tighten the
lock nut.
2. Insert the cable through the union cover, the union
coupling, the gland the clamp nut, the clamp ring,
one washer, the rubber packing, and the packing
Tee box, in that order.
Apply a nonhardening
sealant to the threads for
3. Insert the end of the cable into the terminal box.
waterproofing. Drain plug 4. Tighten the union cover to grip the cable. When
F0510.EPS tightening the union cover, tighten approximately
Figure 5.10 Example of Wiring Using a Wiring Conduit one turn past the point where the cable will no
longer move up and down. Proper tightening is
important. If it is too tight, a circuit break in the
(2) TIIS Flameproof Type
cable may occur; if not tight enough, the flameproof
Wire cables through a flameproof packing adapter,
effectiveness will be compromised.
or using a flameproof metal conduit.
Wiring cable through flameproof packing
adapter for only TIIS flameproof type (see CAUTION
Figure 5.11)
Use only flameproof packing adapters approved by Tighten the union cover approximately one turn
Yokogawa. after the point where you can no longer shift the
Apply a nonhardening sealant to the terminal box cable up and down by hand. Take great care in
connection port and to the threads on the flame- this step, since proper tightening is very important.
proof packing adapter for waterproofing.
Flexible fitting
5. Fasten the cable with tightening the clamp nut.
6. Tighten the lock nut on the union cover.
Wiring conduit
7. Connect the cable wires to each terminal.
Union coupling
Lock nut
Clamp nut
Clamp ring
Grand
Tee Washer
Apply a nonhardening
Cable Rubber packing
sealant to the threads for
waterproofing. Drain plug
Packing box
F0510.EPS
Union cover
Lock nut
Figure 5.11 Typical Cable Wiring Using Flameproof Adapter body
Packing Adapter
O-ring
Measure the cable outer diameter in two directions CAUTION
to within 0.1mm. Be sure to apply non-
hardening sealant to
Calculate the average of the two diameters, and use the threads for water
packing with an internal diameter nearest to this proofing.
F0512.EPS
value from among the three provided (see
Figure 5.12 Flameproof Gland Packing Adapter
Table5.1). lnstallation
5-4 IM 01C50B01-01E
5. WIRING
Seal fitting
After wiring, impregnate the fitting Grounding
with a compound to seal tubing. F0513.EPS terminal
(Inside)
Figure 5.13 Typical Wiring Using Flameproof Metal
Conduit
Grounding
F0511.EPS
terminal
(Outside)
5-5 IM 01C50B01-01E
6. MAINTENANCE
6. MAINTENANCE
6.1 General Table 6.1 Calibration Equipment List
Voltmeter
6.2.2 Calibration Procedure Figure 6.1 Example of Wiring for Calibration Equipment
6-1 IM 01C50B01-01E
6. MAINTENANCE
3. For thermocouple input Table 6.2 Tools for Disassembly and Assembly
Since this instrument is equipped with a reference Tool name Quantity Remark
junction compensating function, use a reference Phillips screwdriver 1
junction compensating function in universal Standard screwdriver 1
calibrator in order to compensate for this function Hexagonal wrench 1
Crescent wrench 1
upon calibration. According to the reference Torque wrench 1
milivolt table for thermocouple, obtain milivolt Box wrench 1 For M10 screw
corresponding to 0, 25, 50, 75, or 100% of the Box screwdriver 1
Forceps 1
span, and use that power as the input value, then
T0602.EPS
deliver it from the universal calibrator to the
temperature transmitter. Measure the resulting
output signal with the voltage meter (digital CAUTION
multimeter) and check the output value relative to
Precautions for CENELEC, SAA and TIIS
the input value.
Flameproof Type Transmitters
4. Thermometer resistor (RTD)
For a withstand flameproof type transmitter, as
Using a thermometer resistor as input, calibration of
a rule, move the transmitter to a non-hazardous
the temperature transmitter is carried out via a 4-
location, then proceed with maintenance and
core wire connection.
restore the instrument to the original condition.
As defined the reference resistor value table of the
For a withstand CENELEC, SAA and TIIS
thermometer resistor (RTD), obtain resistance
flameproof type transmitter, turn the lock bolt
values corresponding to 0, 25, 50, 75 or 100% of
(hexagon socket bolt) clockwise with a wrench
the span, and use the obtained resistance as the
for hexagon head, unlock and remove the
input value, then deliver it to the temperature
cover. When installing the cover, it is the must
transmitter by means of a variable resistor. Measure
to turn the lock bolt counterclockwise and lock
the resulting output signal with the voltmeter
the cover (locked to a torque of 0.7 Nm).
(digital multimeter) and check the output value
For a withstand flameproof type transmitter, in
relative to the input value.
no case should the user be allowed to modify
5. In Steps 2 through 4, if the output signal deviates
the transmitter. Therefore, no user is allowed to
from the given range of accuracy when a given
add a built-in indicator, or use the transmitter
input signal is delivered, adjust the output using the
with the indicator removed. Contact us for any
handheld terminal. For details of how to adjust the
modification.
output, refer to the additional references, BRAIN
Protocol IM 01C50T03-01E or HART Protocol
IM 01C50T01-01E and the instruction manual for
each terminal.
Terminal cover
6-2 IM 01C50B01-01E
6. MAINTENANCE
IMPORTANT
F0603.EPS
6-3 IM 01C50B01-01E
6. MAINTENANCE
: Part supported
by self-diagnosis
Is the polarity NO
of the power supply
Measured value correct?
is found faulty
YES Check the polarity between the
power supply and terminal box and
YES correct it.
Error in process
variable?
Error in measurement
Inspect the process NO system Are the power
NO
Faulty supply voltage and load
area in measurement resistance correct?
system
Operating requirements
Is there a
disconnection in the loop? NO
Operating requirements: Do the loop numbers
check, study, correction correspond to the
counterpart?
F0604.EPS
Check for disconnection or faulty
wiring and take corrective
Figure 6.5 Basic Flow and Self-diagnosis YES measures.
6-4 IM 01C50B01-01E
6. MAINTENANCE
Input adjustment by user was Clear the user adjustment (Sensor J05:SNSR1 CLR Snsr1 Trim Act (123312)
not corrctly done. trim) value or set it to off. K05:SNSR2 CLR Snsr2 Trim Act (123322)
Output adjustment by user Clear the user adjustment (output L05:OUT CLR D/A Clr to Default
was not correctly done. trim) value or set it to off. (12343)
Transmitter outputs The transmitter is in manual Release manual mode. (Make the G10:OUTPUT MODE Loop test (122)
fixed current. (test output) mode. transmitter return to Automatic
Mode)
Input adjustment by user was Clear the user adjustment (Sensor J05:SNSR1 CLR Snsr1 Trim Act (123312)
not corrctly done. trim) value or set it to off. K05:SNSR2 CLR Snsr2 Trim Act (123322)
Output adjustment by user Clear the user adjustment (output L05:OUT CLR D/A Clr to Default
was not correctly done. trim) value or set it to off. (12343)
Output is reversed. LRV is greater than URV. Set the correct value to URV and F10:LRV PV LRV (4)
(See note 1) LRV. F20:URV PV URV (5)
Sensor backup Settings of Process Variables Set Sensor1 as PV and Sensor2 B10:PV is PV is (11211)
function doesnt work are not correct. as SV. B20:SV is SV is (11212)
correctly. Configuration of Sensor1 and Check the type and wire D10:SENSOR1 TYPE Snsr1 config (134)
Sensor2 is not correct. settings for Sensor1 and E10:SENSOR2 TYPE Snsr2 config (135)
Sensor2.
Check the connection of
Sensor1 and Sensor2.
Sensor Burnout is set to off. Check the Sensor Burnout setting. F40:BURN OUT Sensor barnout (14315)
Sensor backup mode is not Change the Sensor Backup H20:SNSR BACKUP Snsr backup (14141)
enabled. function to enable.
Output damping Damping time constant is set Set correct value. B12:PV DAMPING PV damp (1322)
doesnt work. to 0 second.
Setting for PV damping point If output fluctuation is great, set a B13:DMP POINT PV damp point (1323)
is too small. greater value for PV damping
point than current setting. (Initial
setting is 2% of output)
T0603.EPS
Note 1: If the reversed output is desired and necessary setting was done by user, it is not considered as a problem.
6-5 IM 01C50B01-01E
6. MAINTENANCE
6-6 IM 01C50B01-01E
7. GENERAL SPECIFICATIONS
7. GENERAL SPECIFICATIONS
7-1 IM 01C50B01-01E
7. GENERAL SPECIFICATIONS
Ambient humidity:
5 to 100%RH at 40C (104F)
Effect of supply voltage fluctuation:
0.005%/V
Insulation:
Input/output insulated at 500 V DC
Mounting:
Mounted on 2B pipes and wall
Degrees of Protection:
IP67, NEMA 4X, JIS C0920 immersion proof
Electrical connection:
Refer to Model and Specification Codes.
Case and cover:
Aluminum alloy casting
Painting:
Polyurethane resin baked finish
Deep sea moss green (equivalent of Munsell
0.6GY3.1/2.0)
Integral indicator (option):
LCD digital indicator (5-digit display)
Output bar graph; 0 to 100% display
Damping constant:
0 to 99 seconds (integer range that can be set)
Sensor burnout (Output Signal Code D&E) :
High (110%, 21.6 mA DC) or Low (2.5%, 3.6
mA DC)
Weight:
1.2 kg; without built-in indicator (without mount-
ing bracket)
1.4 kg; with Integral indicator (without mounting
bracket)
EMC compliant standard: ,
EN61326, AS/NZS CISPR11
7-2 IM 01C50B01-01E
7. GENERAL SPECIFICATIONS
7-3 IM 01C50B01-01E
7. GENERAL SPECIFICATIONS
Terminals
Terminal Configuration
Power Supply and output terminal
Communication
External Indicator (ammeter) terminal *2
Terminals (BT200 etc.)
Connection hook
Ground terminal
7-4 IM 01C50B01-01E
7. GENERAL SPECIFICATIONS
7-6 IM 01C50B01-01E
7. GENERAL SPECIFICATIONS
7-7 IM 01C50B01-01E
7. GENERAL SPECIFICATIONS
7.4 Dimensions
Unit: mm (Approx. inch)
2-inch horizontal pipe mounting
65.4(2.57)
93
102 (3.66)
(4.02)
164
(6.46)
56(2.21)
2-inch pipe, 60.5(2.38)
70(2.76)
90(3.54)
46(1.81) 65(2.56)
111(4.37) Electrical Connection 18.5
(Input signal) Terminal Cover
(0.73)
Electrical Connection
(Output signal)
With Indicator
(Optional)
93
Shrouding Bolt (3.66)
(For Explosionproof type)
209.5
(8.25)
191.5 Ground Terminal
(7.54)
Tag Plate
Vertical Pipe Mounting Bracket
(Optional)
46(1.81)
98(3.86)
F0701.EPS
7-8 IM 01C50B01-01E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT
To meet flameproof requirements, equipment that can be (4) Path length of joint surface
termed flameproof must: On a joint surface, the length of the shortest path through
(1) Be certified by a Japanese public authority in accordance which flame flows from the inside to outside of the
with the Labour Safety and Health Laws of Japan and flameproof enclosure. This definition cannot be applied to
have a certification label in an appropriate location on its threaded joints.
case, and
(5) Gaps between joint surfaces
(2) Be used in compliance with the specifications marked on
its certification label, equipment nameplate and The physical distance between two mating surfaces, or
precautionary information furnished. differences in diameters if the mating surfaces are cylindrical.
2. Electrical Apparatus of Flame- Note: The permissible sizes of gaps between joint surfaces, the path
length of a joint surface and the number of joint threads are
proof Type of Explosion-Pro- determined by such factors as the enclosures internal
tected Construction volume, joint and mating surface construction, and the
explosion classification of the specified gases and vapours.
Electrical apparatus which is of flameproof construction is
subjected to a type test and certified by the Japanese Ministry
of Labour aiming at preventing explosion caused by electrical
apparatus in a factory or any location where inflammable
gases or vapours may be present. The flameproof
1 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT
2 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT
CAUTION
3 EX-B03E
Customer YTA Series
Maintenance Temperature Transmitter
Parts List [ Style : S3 ]
7
8
2
1
13
12
20
2
11
5
3 9
10
18
6
4
3
2
1
17
29
16
28 14 15
21
15 26
19
23 6
22
YTA_CMPL.EPS
1 F9165EA 2 Cover
2 B1000ER 2 O-Ring
3 Y9406JB 2 Screw Machine
4 See Table 1 1 CPU Assembly for BRAIN or HART Communication type
5 B1002BT 2 Stud Bolt
25 F9165KF 2 Nut
26 F9165KD 2 Stud Bolt
27 F9284NZ 1 Bracket
28 F9165QB 1 Bracket
29 Y9616NU 4 Screw
30 Y9600SU 4 Washer
31 Y9601BU 4 Nut
Nov. 2007
Subject to change without notice. Printed in Japan.
CMPL 01C50B01-02E
REVISION RECORD
Title: Model YTA series Temperature Transmitter (Hardware) [Style: S3]
Manual No.: IM 01C50B01-01E
Edition Date Page Revised item
1st Sep. 1998 New Publication
2nd Nov. 1998 2-5 2.7.1 Add subsection 2.7.1 CSA certification.
2-7 2.7.2 Add subsection 2.7.2 CENELEC(KEMA) certificated.
2-9 2.8 Add subsection 2.8 EMC Conformity Standards.
5-5 5.5 Add wiring cautions for intrinsically safe type and flameproof type.
7-2 to 7-3 7.1 Correct errors.
4th June 1999 Contents Add Ex-B02E 'Installation and Operating Precautions for JIS Flameproof
Equipment'.
2-1 2.1 Add C-tick mark.
2-7 2.7.2 Add IEC (KEMA) Type of protection 'n'
2-10 2.7.3 Add FM Intrinsically Safe Type
2-12 2.7.4 Add JIS Flameproof Type
2-13 2.8 Add C-tick mark
5-1 5.1 Add 'IMPORTANT' for JIS Flameproof type.
5-3 5.3.2 Add 'WARNING' for JIS Flameproof type.
5-6 5.5(2) Add cable wiring procedure using Flameproof Packing adapter.
6-3 6.3 Add Figure 6.3.
7-4 7.3 Add optional code /CM1, /FU1, /JF3, /G11, and /G12.
Ex-B02E Add Ex-B02E 'Installation and Operating Precautions for JIS Flameproof
Equipment'.
CMPL Add item 18, 19, 20, and 21.
Rev.1.EPS
IM 01C50B01-01E
Edition Date Page Revised item
9th Apr. 2003 2-1 Add Vertical pipe mounting bracket.
4-1 Add Vertical pipe mounting bracket.
7-5 7.2 Add mounting bracket code D.
7-7 7.4 Change Dimensions.
CMPL CMPL 01C50B01-02E 8th to 9th
Add Part No.
Item Part No.
27 F9284NZ
28 F9165QB
29 F9616NU
30 Y9600SU
31 Y9601BU
12th Nov. 2007 2-6, 7-6 2.7.2 Change Applicable standards and add Dust Ignition Proof for KU2.
2-11, 7-7 2.7.6 Add IECEx Certification.
7-5 7.3 Add Option PR.
CMPL CMPL Add setting upon shipment for CPU Assembly.
Rev.2.EPS
IM 01C50B01-01E