Panel de Incendio D7024

Ver. 2.02 y superiores

Instalacion

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 2
copying and passing on to third parties.
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 3
copying and passing on to third parties. Department
Panel de Incendio D7024

Propiedades Sistema
Teclado LCD incorporado
Hasta 4 teclados adicionales
Hasta 8 anunciadores remotos adicionales
Comunicador Doble Linea Incorporado
4 Puntos On-Board (Expandible a 8)
247 Direcciones Off-Board (para entradas y/o salidas)
16 Codigos Usuario (Expandible a 100)
Numeros PIN 4 Digitos
Niveles Autoridad Programables
Buffer de Memoria 99 Eventos (Expandible a 499)
Programacion Libre Display Alfanumerico
Programacion Dirigida a traves de Menus
Programable con RAM IV
Aprobaciones UL, CSFM, MEA
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 4
copying and passing on to third parties.
Panel de Incendio D7024

Especificaciones
Corriente
Entrada Corriente:
120 V, 60 Hz, 1.5 A
Corriente Notification Appliance Circuit (NAC):
Cada NAC tiene 24 VDC nominal, corriente no filtrada
con hasta 2.5 A capacidad (4.0 A max.)
Corriente Auxiliar:
24 VDC nominal, no filtrada, 1.0 A
Corriente Circuito Iniciacion (Humo):
24 VDC nominal, filtrada, 1.0 A.
Corriente Bus Option:
12 VDC nominal, 500 mA
Baterias Opcionales Standby:
Dos 12 V (en serie), 7 40 Ah

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 5
copying and passing on to third parties.
Panel de Incendio D7024

Cont. Especificaciones
Notification Appliance Circuits (NACs)
Dos circuitos notificacion on-board - NAC 1 y NAC 2.
Cableado para estandares Class B, Estilo de operation Y
(use modelo de convertidor NACD7015 Clase B a Clase A
para convertir a Clase A, Estilo Z como se necesita).

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 6
copying and passing on to third parties.
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 7
copying and passing on to third parties. Department
Panel de Incendio D7024

Modulos
D7014 Convertidor Zona Clase A
D7015 Convertidor NAC
D7030 Anunciador Remoto LED
D7031 Keyswitch Remoto
D7033 Teclado LCD
D7034 Expansor 4 Puntos
D7035 Modulo Relevo Remoto
D7036 Teclado Anunciador Fuego
D7038 Fuente Poder Remota NAC
D7039 Modulo Expansion Multiplex
D7042 Modulo 8 Entradas
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 8
copying and passing on to third parties.
Panel de Incendio D7024

ModulosConvertidor Zona Clase A D7014

Convertidor Zona Clase A


Convierte un Clase B a Clase A

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 9
copying and passing on to third parties.
Panel de Incendio D7024

Modulos Convertidor NAC D7015

Convierte Circuito NAC Clase B


a circuito Clase A.
Compatible con circuitos NAC 24V

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 10
copying and passing on to third parties.
Panel de Incendio D7024

Modulos Anunciador Remoto D7030

8 LEDs Personalizables
Indica Sitios Alarma
LEDs Corriente y Fallo
Cables cuatro hilos

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 11
copying and passing on to third parties.
Panel de Incendio D7024

Modulos Teclado LCD D7033

Display Alfa/Numerico
2 Lineas, 32 Caracteres
Sistema Control Remoto
4 LEDs de Estado
Proteccion con clave

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 12
copying and passing on to third parties.
Panel de Incendio D7024

Modulos Expansor Puntos D7034

Expansor 4 Puntos
Usa dispositivos N/O o N/C
Detectores 2 o 4 hilos
20 circuitos 2 hilos

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 13
copying and passing on to third parties.
Panel de Incendio D7024

Modulos Modulo Relevo Remoto D7035

8 Salidas Forma C
Cada Relevo Programable
Hasta 2 Modulos/7024

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 14
copying and passing on to third parties.
Panel de Incendio D7024

Modulos Teclado Anunciador Fuego D7036

Teclado/Anunc LCD.
2 Lineas/16 Carac./linea
Buzzer incorporado
Resetea Panel desp. Alarma

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 15
copying and passing on to third parties.
Panel de Incendio D7024

Modulos Expansor Multiplex D7039

Modulo Expansor Puntos


2 Buses Mux Clase B
o
1 Bus Mux Clase A
Expande a 100 PINs
Expande Memoria a 499

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 16
copying and passing on to third parties.
Panel de Incendio D7024

Dispositivos Puntos Off-Board


D7042 Modulo 8 Entradas
D7044(M)-Entrada Sencilla Direccionable /M = mini
D7050(TH)- Cabeza Humo Direccionable Photo-elect.
D7050B Base 2 hilos 6 TH = 135f sensor seguro calor
D7045- Estacion Manual Direccionable
D7052- Entrada Doble Direccionable/Total 60
D7053- Entrada/Salida Direccionable [5a @ 28vdc]
(Total 40 (20 en cada lazo aislado clase b SLC)
(Relevo usa funciones programable sistema)
D243P- Cabeza Detectora Direccionable para Ductos con/D7050DH Total 70
D344-RT Plato Remoto Pruebas Total 40
D344-RL Anunciador Remoto LED Total 50
Primeros 10 puntos perdidos anuncian individualmente si hay mas de 10 Common Bus Failure

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 17
copying and passing on to third parties.
Panel de Incendio D7024

Modulos Modulo 8 Entradas D7042

8 Entradas Remotas Modulo Address Sw.


Tamper
Mux
Tamper
8 Circuitos Iniciacion Clase B Bypass

Hasta 76 mt en Circuitos
Iniciacion
Direccionable Dip Switch
Tamper w/bypass para pruebas

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 18
copying and passing on to third parties.
Panel de Incendio D7024

Modules Fuente Poder Remota D7038


6 Amps de Corriente
4 Lazos Clase B
Salida Regulada 24VDC
Total/ Protegida/Supervisada

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 19
copying and passing on to third parties.
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 20
copying and passing on to third parties. Department
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Instalacion y Puesta en Marcha


En la caja de envio, usted encontrara:

Un Control/Comunicador D7024 en paquete resistente estatica


Una Caja con transformador

Un paquete hardware

Una cerradura, anillo sujeccion, y llaves

Seis Resistencias Fin-de-Linea (EOL)

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 21
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Instalando la caja
Usando la base como plantilla, marque los hoyos de montaje

Pre-fije los tornillos montaje para estos dos hoyos.

Deslice la caja sobre estos tornillos

Aprete los tornillos.

Fije con dos tornillos los hoyos inferiores.

Quite las entradas deseadas de cable

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 22
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Instalando el Control/Communicator

Inserte los 3 postes soporte en los hoyos retenedores

Presione los soportes de nylon 1/8" dentro de los hoyos retenedores


Deslice la parte superior de la caja en los tabs.

Asegure las dos esquinas inferiores a traves de los


hoyos retenedores

Conecte el cable de tierra inserto

Conecte la tierra de AC.

Asegurese de tocar tierra antes de manipular la tarjeta controladora


| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 23
copying and passing on to third parties.
Panel de Incendio D7024

Cableado

120VAC xfmr

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 24
copying and passing on to third parties.
Panel de Incendio D7024

Terminales Funcion
1 NAC 1 + +24V en alarma; tierra mientras en standby

2 NAC 1 - Tierra en alarma; voltaje supervisado en standby

3 NAC 2 + +24V en alarma; tierra mientras en standby

4 NAC 2 - Tierra en alarma; voltaje supervisado en standby

5 Bateria -
Requires 2 12 V batteries in series; combined
6 Bateria + voltage 24 V; Charge Current 1.1 A max.

Todo el cableado exceptuando puntas bateria y entrada AC esta limitada


por corriente.
Separar estos de otros cables por lo menos 1/4, y asegurelos

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 25
copying and passing on to third parties.
Panel de Incendio D7024
D7024 Installation

Terminales Funcion

7 12 V + Bus A Option

8 Com Bus A Option

9 Data Bus A Option

10 Data Bus A Option [amarillo]

11 12 V + Bus B Option

12 Com Bus B Option

13 Data Bus B Option

14 Data Bus B Option [amarillo]

*Puede usar solamente un bus option al tiempo


| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 26
copying and passing on to third parties.
Panel de Incendio D7024
D7024 Installation

Terminales Funcion

21 Earth Ground

20 Loop 4 -

19 Loop +
All EOL resistors 2.21k-ohm
18 Loop 3 -
Initiating Devices Class B, Style B
17 Loop 2 - 2-wire Compatibility Identifier A

16 Loop +

15 Loop 1 -

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 27
copying and passing on to third parties.
Panel de Incendio D7024
D7024 Installation

Terminales Funcion

25 SMK + Corriente Humos 24 V, 1.0A max. [filtrada]

24 SMK - Switchada Supervisada

23 AUX + Corriente Auxiliar 24 V, 1.0A [sin filtrar]

22 AUX - No switchada No Supervisada

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 28
copying and passing on to third parties.
Panel de Incendio D7024
D7024 Installation

Terminales Funcion

31 NC 2
Relay 2 30 COM 2
For connection to listed
29 NO 2 power limited Class 2 or
Class 3 sources only.
Contacts rated at
28 NC 1 5.0A, 28 V.
Relay 1
27 COM 1

26 NO 1

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 29
copying and passing on to third parties.
Panel de Incendio D7024
D7024 Installation

Terminales Funcion

39 R2
Phone 2
38
37
HR 2
HT 2

36 T2

Phone 1 35 R1

34

33
HR 1

HT 1

32 T1

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 30
copying and passing on to third parties.
Panel de Incendio D7024

Expansion

D7034
Expansor 4 Zonas
Puntos On-Board

D7039
Expansor Multiplex
240 Puntos Off-Board

Modulo I/O

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 31
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Instalacion Equipo Opcional


Hay tres opciones de expansion que pueden conectarse directamente al panel

Expansor D7034 Cuatro Entradas

Expansor Multiplex D7039

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 32
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Instalacion Equipo Opcional cont.


Cuando el panel es re-energizado, el panel mostrara lo siguiente:

y/o

y/o

Presione la tecla [Clear] para confirmar la instalacion de los dispositivos

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 33
copying and passing on to third parties.
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 34
copying and passing on to third parties. Department
Panel de IncendioD7024
D7024Programming

Programacion
Teclas de Programacion Alfanumerica

1 2 3 Drill Teclas Numero usadas para


Silence
entrar valores alfanumericos

4 5 6 Disable

7 8 9 Test Tecla Silence un espacio


Reset derecho
##
Tecla Disable un espacio
*
Clear
0
Prog
Cmnd History izquierda tecla #/Cmnd
acepta datos cuando esta en
modo programacion
Tecla */Clear usada para:
Salir programacion alpha
Exit entra modo program
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 35
copying and passing on to third parties.
Panel de Incendio D7024

Programacion

RAMIV - Adiciona la habilidad para programar remotamente,


diagnosticar remotamente, recuperar historico remotamente

Programacion En sitio puede ser hecha usando un PC con RAMIV y


un modem externo. Modem conexion Directa para deteccion tip/ring de
lineas telefonicas entrantes en linea uno. Use RAMIV para conectar.
Presione el boton Test en teclado D7024, presione 5 para Respuesta
Remota, coloque nivel PIN maxima autoridad.
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 36
copying and passing on to third parties.
Panel de IncendioD7024
D7024Programming

Programacion
Programacion Alpha Desde Teclado
Presione la 1 tecla

Una = SPACE
Dos = 1
Tres veces = ,
Cuatro veces =
Cinco veces = &
Seis veces = /
Siete veces = #
Ocho veces = !
Nueve veces = -

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 37
copying and passing on to third parties.
Panel de IncendioD7024
D7024Programming

Programacion
Programacion Alpha Desde Teclado
1ra vez 2da vez 3ra vez 4ta vez
2
A B C 2

3 D E F 3

4 G H I 4

5 J K L 5

6 M N O 6

P R S 7
7

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 38
copying and passing on to third parties.
Panel de IncendioD7024
D7024Programming

Programacion
Programacion Alpha Desde Teclado
1ra vez 2da vez 3ra vez 4ta vez

8 T U V 8

9 W X Y 9

0 Q Z 0
Prog

# Entra descripcion & returna a menu programacion.


Cmd

*
Clear
Returna a menu programacion sin hacer cambios.

Disable
Mueve cursor un espacio izquierda. Silence

Mueve cursor un espacio derecha


| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 39
copying and passing on to third parties.
Panel de Incendio D7024 Menu Tree
D7024 Program

Programacion
Nivel 1 es Menu Principal. Seleccione Programar con Tecla. 0
Prog

Nivel 2
1- PROG TIME
2- SECURITY
3- PROG SYSTEM
4- PROG INPUTS
5- PROG OUTPUTS
6- PROG ACCNTS
7- PROG FORMATS
8- HISTORY DEFLTS
9- PROGRAM MUX
Arbol Programacion RAMIV, tiene igual info al display navegacion
| ZVW2, 22.12.00 en teclado, excluyendo Nivel 2 item
8.
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 40
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Arbol Menu Programacion

Program/ Hora

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 41
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Arbol Menu Programacion

Seguridad

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 42
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Arbol Menu Programacion

Program/ Sistema

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 43
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Arbol Menu Programacion

Program/ Entradas

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 44
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Arbol Menu Programacion

Programar Salidas

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 45
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Arbol Menu Programacion

Programar Cuentas

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 46
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Arbol Menu Programacion

Formatos Program/

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 47
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Arbol Menu Programacion

Historicos/Deflts

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 48
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Arbol Menu Programacion

Program Mux

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 49
copying and passing on to third parties.
Panel de IncendioD7024
D7024Programming

Programacion RAM IV
D7024s equipados con versiones software inferiores a

2.02 no pueden ser programados remotamente.

RAM IV Software Programacion Remota, Ver. 3.1.18 y

superior, es el programador remoto para el D7024

[Ver. 2.02 y superior].

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 50
copying and passing on to third parties.
Panel de IncendioD7024
D7024Programming

Programacion RAM IV
Programming Shortcuts
Programacion Remota
Sistema permanece Operacional
Systema muestra SYSTEM TROUBLE
Sirenas no activan RMT PRG ACTIVE

Otras salidas programadas en Zona 62 se activaran


Problemas no se anuncian hasta sesion de programacion
finalice, pero apareceran en diagnosticos programador
Nuevas Alarmas terminan sesiones programacion & reportan
normalmente

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 51
copying and passing on to third parties.
Panel de IncendioD7024
D7024Programming

D7024 Guia Rapida Programacion


Para preparar el panel y poder programar con RAM IV usted
debe habilitar la opcion programacion remota:
Presione 0 en el teclado
Pulse 9876 #
Seleccione opcion 3 Programar Sistema
Pulse 7 para Programacion Remota
Para Habilitar Presione 1
Presione la tecla * dos veces
Presione 6 para Programar Cuentas
Seleccione 4 para Conteo Rings
Colocar Auto Respuesta Conteo Rings 3 o 5

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 52
copying and passing on to third parties.
Panel de IncendioD7024
D7024Programming

D7024 Guia Rapida Programacion cont.


Para responder la llamada entrante desde RAM IV
Presione la tecla Test despues 5
Preguntara para entrar un codigo. Teclee 9876
Pantalla mostrara Remote Program Active

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 53
copying and passing on to third parties.
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 54
copying and passing on to third parties. Department
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Modos de Operacion
Existen tres modos de operar el sistema en el
Control/Comunicador D7024 :
ALARM
TROUBLE
NORMAL

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 55
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Modos de Operacion - Alarma

ALARMA

Cuando una alarma ocurre, la linea superior de la


pantalla mostrara FIRE ALARM, o un mensaje similar.
La segunda linea de la pantalla mostrara el numero de el
punto que esta en alarma, alternando con la descripcion
programada en el punto afectado.
Si mas de una alarma esta activa, se mostrara en la
segunda linea de la pantalla, una despues de otra.
La sirena interna se activara con tono continuo, y las
salidas programadas se activaran con la condicion de
alarma actual que se active.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 56
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Modos de Operacion - Trouble

TROUBLE

Cuando una condicion de trouble sucede, la sirena se


activara con un beep cada 10 segundos.
El LED de Trouble iluminara y el LCD mostrara SYSTEM
TROUBLE, seguido por una descripcion de la condicion
de trouble.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 57
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Modos de Operacion Seales Trouble

TROUBLE

1. FIRE ALARM: Uno o mas puntos estan en alarma.


2. SUP'VISORY ALARM: Una condicion supervisada existe
3. SYSTEM TROUBLE: Una condicion trouble existe
4. POINT TROUBLE: Uno de los puntos no responde
5. DISABLED DEVICE: Un dispositivo de entrada o salida
fue desabilitado.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 58
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Modos de Operacion - Normal

NORMAL

Cuando el sistema esta operando normalmente, este


mostrara SYSTEM NORMAL.
En la linea superior de la pantalla, el LED de corriente
estara encendido, y no otros LEDs alumbraran.

Si la programacion requiere un PIN, la segunda linea de


la pantalla LCD mostrara ENTER PIN:

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 59
copying and passing on to third parties.
Panel
D7024de Incendio
Fuse D7024
re Alarm Control / Communicator

USO DEL SISTEMA NAVEGANDO MENUS

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 60
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

USO DEL SISTEMA NAVEGANDO MENUS


Existen diferentes formas para seleccionar un item:
1. En el menu principal, TEST, HISTORY, DISABLE, y DRILL cada uno
tiene un boton exclusivo en el teclado.

2. Las teclas PROG y CMND no son exclusivas, pero compartiran con


otros caracteres. El caracter compartira la tecla correspondiente
mostrada en la segunda linea seguida por un slash.

3. La tecla correspondiente al item sub-menu puede ser mostrada en la


segunda linea precedido por un guion.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 61
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

OPERACION SISTEMA :
Una vez el Item Menu Principal Item fue seleccionado
Cuando un item del Menu principal es seleccionado, el teclado
podra preguntarle para entrar el PIN.
Devolviendose a travez del Menu
Para returnar a la pantalla previa en cualquier momento,
presione la tecla [*/Clear].
Entrar Datos
Cuando un item del submenu se muestra para entrar el dato,
hacerlo seguido por la tecla [#].
Drill
El comando drill activa todos los NACs y no los relays.
Desabilitar
El comando desabilitar se usa para desabilitar puntos
entradas/salidas, o el discador
Historia
La opcion HISTORIA es una lista de eventos que han occurrido.
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 62
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

HISTORIA ABREVIATURAS

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 63
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

TECLADO INCORPORADO

LED Corriente LED Problema


LED Silenciar
LED Alarma

Tecla Drill
Tecla Desabilitar
Tecla Silenciar

Tecla Prueba
Tecla Reset
Tecla Limpiar Tecla Historia

Tecla Programar Tecla Comando


| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 64
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

TECLADO REMOTO

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 65
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

PRUEBA
Para entrar en Modo Prueba presione la tecla Test
Seleccione una de las siguientes funciones de prueba

Test Caminado
Test Comunicador
Test Programacion Remota
Test Circuito Batteria/NAC
Test Activacion Salidas Manuales
Test Nivel Entradas Zona
Test Puntos Direccionables

Para salir del modo test presione la Tecla Clear

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 66
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Test Caminado

Cuando seleccione esta opcion, tres opciones


seran ofrecidas para la activacion de las salidas.
SHORT ACTIVE: 1 segundo activacion
LONG ACTIVE: 5 segundos activacion
NO ACTIVE: salidas no seran activadas

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 67
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Test Comunicador
El comunicador enviara un reporte de prueba.
El LED de corriente alumbrara durante la comunicacion.
Cuando la comunicacion se produce:
un beep largo en el teclado se escuchara,
el LED de Corriente retornara a normal,
y la pantalla retornara a modo normal.
Terminando la funcion de prueba del comunicador se
reseteara el comunicador y se descartaran los reportes
no enviados.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 68
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Test Programador Remoto

El panel llamara al numero telefonico 3 e


intentara conectarse para el downloading.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 69
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Test Circuito Bateria/NAC

En este modo de prueba, el sistema operara los circuitos locales NAC


y probara la bateria por dos segundos.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 70
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Test Activacion Salidas Manuales

Permite seleccionar una salida para ser activada y desactivada


manualmente.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 71
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Test Nivel Entradas Zona

Muestra el estado de los puntos on-board seleccionados.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 72
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Test Puntos Direccionables


El test de puntos direccionables, o modo test mux,
permite activacion de los modos especiales de prueba para
dispositivos direccionables, multiplex.

Cuando este modo de prueba es seleccionado,


el sistema pregunta cual bus es probado. El
sistema entonces presenta 5 opciones:
Lista Dispositivos
Muestra Hoyos
Muestra Extras
Muestra Perdidos
Muestra Estado

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 73
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Ejemplo: X0L0R0D0M0T0F0A0
X: reservado para uso futuro
traduccion =
L: estado relay comandado
relay debe estar off
R: estado relevo actual
relay is off
D: detector sucio
no sucio
M: dispositivo perdido
no perdido
T: tamper
no tamper
F: falla loop
no falla
A: loop de alarma
no alarma.

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 74
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

MAPEO PUNTO/ZONA
El panel soporta un sist. Flex. para direccionar puntos entrada a puntos salida

Dispositivos seran designados como:


Puntos Entrada: Detectores Humo, estaciones manuales, etc.
Zona: Un grupo de puntos entrada (Zonas 1-50 son
configurables, 52-63 son activadas automaticamente).
Puntos Salida : NACs (campanas, strobes, etc.) y relevos.

Activacion zonas entrada

Activacion salidas

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 75
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Ejemplo Mapeo

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 76
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Zonas Pre-asignadas

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 77
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

NUMEROS PIN
El Numero de Identificacion Personal (PIN) es el codigo 4 digitos
que el usuario entra en el teclado para ganar acceso al sistema

D7024 Panel Usuarios 00 a 15


D7039 Modulo Expansion Usuarios 16 a 99

| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 78
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

OPERACION COMUNICADOR

D7024 contiene un comunicador integrado que puede ser habilitado


para enviar reportes a una estacion de monitoreo.

Alarmas de Fuego y flujo aguaseran enviadas primero,


seguidas por:
alarmas supervision y reportes prueba
y finalmente todos los demas reportes.

Lineas telefonicas para controles/comunicadores de fuego


no deben ser compartidas
| ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as 79
copying and passing on to third parties.
Panel
D7024de Incendio
Fire D7024 / Communicator
Alarm Control

Gracias