You are on page 1of 63

Power Technologies Division

ProtectIT Multifunctional Protection


Medium Voltage switchgear Control unit

Model REF542plus
(Rel. 2.0)
1VCP000060 – Rev.A, en – 2004.10
Presentation
REF542plus – presentation contents Contents

ˆ REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values

REF542plus Rel 2.0 presentation , 2 of 62


EC V2.0 10/10/04
REF542plus
ABB first in Intelligent Switchgear General

ABB first introduced in the


market integrated numerical combined
protection and control in MV switchgear

ˆ Cost effectiveness
ˆ Engineering
and wiring reduction
ˆ Hardware variants minimization
ˆ High Integration
ˆ Fault possibilities reduction
ˆ Easier modifications
ˆ Easier expansions

REF542plus Rel 2.0 presentation , 3 of 62


EC V2.0 10/10/04
REF542plus
REF542plus The History General

SCU => REF542 => REF542plus


z From thousands of installations
Evolution and enhacements of a proven technology
z PTMV-wide product

REF542plus is ABB standard solution for AIS and GIS switchgear

REF542plus Rel 2.0 presentation , 4 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Yearly volumes General

10000
8000
Volume (pcs)

6000
REF542plus
4000
REF542
2000
0
93
94
95
96
97
98
99
00
01
02
03
19
19
19

19
19
20
20
20
20
19
19

REF542plus Rel 2.0 presentation , 5 of 62


EC V2.0 10/10/04
REF542plus
REF542plus - Licensee companies General

ˆ WE
z DECMS - ITSCB - CHSEC
ˆ CEE
z CZEJF
ˆ CN
z CNDMX
ˆ MENA
z TRABB - EGARC
ˆ SEA
z AUTIL - MYTAD – KRABB
ˆ INDIA
z INABB

REF542plus Rel 2.0 presentation , 6 of 62


EC V2.0 10/10/04
REF542plus
REF542plus - Hardware Hardware

ˆ REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values

REF542plus Rel 2.0 presentation , 7 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware Structure Hardware

REF542plus is composed of 2 parts: Base Unit and LD HMI


ˆ High flexibility due to separation of HMI and Base Unit
– Blind Unit (without HMI) possible
– One HMI shared for several Base Units
ˆ HMI easy integration on panel front door
ˆ Base Unit easy integration in low voltage cubicle
ˆ Independent operation of Base Unit and HMI
– HMI can be disconnected without affecting Base Unit operation

Base Unit LD HMI: Local Detached Human


REF542plus Rel 2.0 presentation , 8 of 62 Machine Interface
EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, HMI Hardware

Alarm LED Interlocking error LED


Network communication LED
3 LED bars
Unit Ready LED
for measurements

Optical Interface

CB fast opening button

Electronic key for:


- remote / local
- operational / set
FREE programmable commands
Select-, off-, on-buttons configurable with the config tool
8 x 4 pages user programmable LEDs
Menu navigation buttons
REF542plus Rel 2.0 presentation , 9 of 62
EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Base Unit Hardware

Analog Output 4..20mA Module Analog Input 4..20mA Module Communication Module

RX TX
0/4...20mA 4...20mA
CP
Communication Processor

Analog Input Module


IL1
IL2 DSP µC
IL3
start L1

Time Synch.
UL1 start L2 Control
Protections,
UL2 start L3
UL3
Measurements
Release/Trip
Io Autoreclosure
Vo
CAN Eth.
(exemplary inputs)
Main Board

Binary Binary
inputs outputs

Binary Input Output Module(s)


REF542plus Rel 2.0 presentation , 10 of 62
EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Connector plates Hardware

CT, VT connector

Wide housing, mixed analog input

Sensor inputs

Small housing

HMI

REF542plus Rel 2.0 presentation , 11 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Modules Hardware

Components

Analog input module

Main Board module


Analog output module

1... 3 x binary I/O module

Power supply module

REF542plus Rel 2.0 presentation , 12 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Main Board 5 Module Hardware

ƒ20% faster than previous MainBoard 4 (MB4)


ƒMotorola ColdFire processor (32 bits) @ 66MHZ
ƒMotorola 56307 DSP (24 bits) @ 150MHZ
ƒBackward compatible with MB4

3 Versions:
‰BASE
•RS232 Service port, RS485 for HMI, RJ45 Ethernet 10Base T
‰STANDARD
•Like BASE plus CAN and Irig–B optical input port for time synchronization
‰FULL
ƒ Like STANDARD plus fast digital I/0 ports (2 inputs - 1 output)

REF542plus Rel 2.0 presentation , 13 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Analog Input Module Hardware

Conventional VTs and CTS

Sensors analog inputs

Mixed modules available


(Sensors+conventional CTs and VTs)

8 channels for protection and measurements,


(AD 20bits, 16 MSB used)
Channels can be supervised against wire cuts
REF542plus Rel 2.0 presentation , 14 of 62
EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Analog input modules Hardware

Group 1 Group 2 Group 3


REF542plus can have a maximum of 8 analogue input channels. These inputs are divided CT CT CT VT VT VT CT2 VT
into three measurement groups: VT VT VT VT VT VT CT2 CT2
•Measurement Group 1: channel 1, channel 2, channel 3 CT CT CT CT CT CT
•Measurement Group 2: channel 4, channel 5, channel 6 CT CT CT CT CT CT CT2 VT
•Measurement Group 3: channel 7, channel 8 CT CT CT CT CT CT CT
CT CT CT VT VT VT VT
Group 1 and group 2 have to be homogeneous, that means they can measure 3 currents CT CT CT VT VT VT CT
or 3 voltages. For example, measurement of 1 current and 2 voltages is not allowed. CT CT CT VT VT VT CT VT
Group 3 can get any type of signals: 2 currents, 2 voltages, 1 current and 1 voltage, etc. CT CT CT VT VT VT CT CT
CT CT CT VT VT VT CT2 CT2
The input CT 0.2A is commonly used with a toroidal transformer for sensitive earth fault CT CT CT VT VT VT VT VT
current measurement. CT CT CT VT VT VT
CT CT CT CT CT CT CT CT
CT means input for current transformer (CT2 is the 0.2A input). The instrument CT CT CT CT CT CT CT VT
transformer can have ratio /1 or /5 . The ratio and the nominal current (e.g. 100/5) are S S S S S S S S
selected via software in the configuration tool. The input module is the same; a different S S S S S S CT2 VT
pin on the connector is wired depending on the ratio /1 or /5. S S S VT VT VT CT2 VT
S S S S S S CT
VT means input for voltage transformer. Both Phase-to-ground or phase-to-phase VT can S S S S S S CT VT
be used.
S S S S S S CT2
S S S S S S VT VT
SI means sensor input. The rogowsky coil is used for current sensing. The correct ratio of
S S S CT CT CT CT2 VT
the rogowsky coil is selected by the configuration tool. The resistive divider is used for
voltage sensing. The ratio is selected by the configuration tool. The input is the same both
for voltage and current sensing, the selection is done via the configuration tool. So, it is
possible to use 6 rogowsky coils, or 6 voltage dividers, or 3 rogowsky coils and 3 voltage
dividers.

REF542plus Rel 2.0 presentation , 15 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Electromech. BIO module Hardware

Up to three binary Input Output


modules BIO3 with mechanical contacts
in the wide housing (two in the standard housing)

14 Binary Inputs, 24-90 VDC (threshold 14VDC) or 85-220 VDC (threshold 50VDC)
6 Power Outputs, Load current 12A, operate time 9ms
2 Signal Outputs, Load current 2A, operate time 5ms
1 Optional Static Output instead of mechanical, Load current 0.7A, operate time 1ms
1 coil supervision circuit
1 watchdog contact
The module is also available with the minus (‘-’) of the
binary inputs interconnected, to semplify wiring

REF542plus Rel 2.0 presentation , 16 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Static BIO module Hardware

Up to three Static binary Input Output


modules in the wide housing
(two in the standard housing)

14 Binary Inputs, 48-285 VDC


2 Power Outputs, Load current 12A, operate time 1ms
4 Power Outputs, Load current 10A, operate time 1ms
2 Static Outputs,Operate voltage max.250V, operate time 1ms
2 coil supervision circuits
1 watchdog contact

REF542plus Rel 2.0 presentation , 17 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Power supplies Hardware

Hardware – Power Supply

Fixed 110 or 220 V DC


Tolerance -30% + 15%

Full range 48... 220 V DC


Tolerance -15% + 10%

REF542plus Rel 2.0 presentation , 18 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Analog Output module Hardware

Hardware – Analog Output 0..20mA module

4 freely programmable output channels (I, V, Power, cosphi)

REF542plus Rel 2.0 presentation , 19 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, 4...20mA Analog Input Module Hardware

Hardware – 4..20mA Analog Input Module

General purpose inputs for 4..20mA sensors, e.g.:


•Temperature
•SF6 density
•...
6 channels available
The module can be used in the wide housing only

REF542plus Rel 2.0 presentation , 20 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Communication modules Hardware

SPA-Bus Protocol (plastic fiber snap in, glass fiber SMA,


glass fiber ST)

LON LAG 1.4 (glass fiber, ST)

Dual channel SPA-Bus/MODBus RTU


(glass fiber, ST or
RS 485, screw terminals)

IEC 60 870-5-103 (glass fiber, ST)

REF542plus Rel 2.0 presentation , 21 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Summary Hardware

Binary input and output: at most 3 modules


z 14 (28,42) binary inputs
z 6 (12, 18) power outputs
z 2 (4, 6) signal outputs
z 1 (2, 3) watchdog outputs
Analog Input
z 8 analog inputs for current and voltage
4…20mA Analog Input
z 6 x 4...20mA channels
Analog Output
z 4 x 4/0...20mA channels

Communication
z SPABUS (optical glass, optical plastic)
z LON LAG 1.4 (optical glass)
z IEC 103 (optical glass)
z MODBUS RTU (two independent channels, optical glass, RS 485)
z WEB SERVER

REF542plus Rel 2.0 presentation , 22 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Hardware, Summary Hardware

ˆ Always required with any housing:


z HMI, power supply, MainBoard, Analog Input,1 x binary IO
ˆ Standard housing:
z At most 2 binary IO, alternatively communication or Analog Output board
– backplane differs in case analog output or communication module is inserted
ˆ Wide housing:
z At most 3 binary IO, communication, Analog Output, Analog Input 0..20nA
module instead of Analog Output module or one of the binary IO
– The Analog Input 0..20mA module can be inserted in the Analog Output slot.
Analog input and analog output are mutually exclusive.

REF542plus Rel 2.0 presentation , 23 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Features Features

ˆ REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values

REF542plus Rel 2.0 presentation , 24 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Features Features

Protections Visualization
– overcurrent – bay single line diagram
– measurement
– overvoltage / undervoltage
– events and alarms Motor specific protections
– earthfault – parameters and settings – thermal overload
– distance – directional power
– differential for transformers and – unbalanced load
motors – low load
–restricted differential – inrush blocking

Control
– control, interlocking
– alarm handling Aditional functions
– local control and indication – synchro-check
– 5 shots auto-reclosing
– fault recording
Supervision Power Quality -communication to SCADA
– self diagnosis – Power factor controller with -WEB SERVER
resonance protection
– switchgear faults - CAN digital bus interface
– THD protection
–data transmission failure -Frequency protection
-High speed transfer

REF542plus Rel 2.0 presentation , 25 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Feeder Local Control Features

„ REF542plus provides an easy and pratical local control with complete


interlocking.
„ The operator interface carries out the following functions:
„Status of the different primary objects
„Activation of the primary object by means of control push-buttons
„Events, alarms, measurements visualization
„User programmable buttons

REF542plus Rel 2.0 presentation , 26 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Protection Functions (I) Features

ˆ Current Protection Functions:


ˆ Voltage Protection Functions:
z Inrush (68)
z Undervoltage istantaneous (27)
z Overcurrent istantaneous (50)
z Undervoltage definite time (27 High, 27
z Overcurrent definite time and IDMT (51 Low)
High, 51 Low, 51 IDMT) z Overvoltage istantaneous (59)
z Directional Overcurrent protection (67 z Overvoltage definite time (59 High, 59
Low)
High, 67 Low)
z Residual Overvoltage definite time (59N
z Earthfault protection definite time and
High, 59N Low)
IDMT (51N High, 51N Low, 51N IDMT)
z Directional earth fault protection (67N
High, 67N Low, 67N sensitive,67N
sector)

REF542plus Rel 2.0 presentation , 27 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Protection Functions (II) Features

ˆ Motor Protection Functions: ˆ Other protection, control and


supervision functions:
z Number of starts (66)
z Differential (87)
z Motor Start (51 MS)
z Restricted earth fault (87N)
z Locked Rotor (51 LR)
z Distance protection (21)
z Thermal Overload (49)
z Synchrocheck (25)
z Unbalanced Load (46)
z Autoreclosing (79)
z Directional Power (32) z Fault recorder
z Low Load (37) z Interlocking
z PLC-like automation functions
ˆPower Quality Functions: z Measurements
zPower factor controller (55) with resonance protection z Switch gear monitoring
zTHD protection z Self-diagnosis

zFrequency protection z CAN

zHigh Speed Transfer System (HSTS)

REF542plus Rel 2.0 presentation , 28 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Measurements Features

„ Line currents IL1, IL2, IL3, A


„ Circuit-Breaker electrical and mechanical life:
„ Earth-fault current Ilo ,A
„ Operating hours
„ Phase to earth voltages U1N, U2N, U3N, V
„ Operating cycles
„ Phase to phase voltages U12, U23, U31, V
„ Interrupted currents sum
„ Residual voltage Uo, V
„ Mean and peak current in the
„ Frequency f, Hz
observation period
„ Power factor cos phi
„ Recording of 30 protection events (visible
„ Active power P, Watt
from HMI):
„ Reactive power Q, VAR
„ Involved protection
„ Active energy, Watth
„ Faulty phase
„ Reactive energy, VARh
„ Tripping time
„ Tripping values

REF542plus Rel 2.0 presentation , 29 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Fault Recorder Features

„ Analogue channels 8
„ Digital channels 32
„ Acquisition rate 1,2 kHz
„ Pre fault time 100ms..2s
„ Min Recording time 1sec
„ Max Recording time 5sec
„ Max num of records 5

Fault records are retrieved and converted into the COMTRADE format

REF542plus Rel 2.0 presentation , 30 of 62


EC V2.0 10/10/04
REF542plus
Programmable electronic key Features

ˆ Multiple codes for different access authorization levels


z 8 characters custom code for authenticated HMI access
z Possibility of “Super User” key code
ˆ Increased security
z Recording of access operations (log-book)

ˆ SW programmer for custom HMI -key programming

REF542plus Rel 2.0 presentation , 31 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Communication protocols Features

ˆLON according to LAG 1.4


ˆIEC 60 870-5-103 protocol with VDEW extension
ˆMODBUS RTU or SPA protocol on dual channels interface
ˆSPA bus protocol
ˆEmbedded WEB server

REF542plus Rel 2.0 presentation , 32 of 62


EC V2.0 10/10/04
REF542plus
REF542plus, WEBREF Embedded Web tecnology Features

ˆ Integrated WEB technology goals:


ˆ Flexible, virtual HMI running on a commercial Web Browser.
z Easy adaptation to local languages
z System condition acquisition
z Low cost replacement of SCADA monitoring functions
z Alarm alert with SMS messaging

REF542plus Rel 2.0 presentation , 33 of 62


EC V2.0 10/10/04
REF542plus
REF542plus, WEBREF Application example Features

„ Working activities
cause a short circuit
in the medium
voltage system

„ REF542plus trips
„ Local alarm indication
=> SMS is sent

„ SMS:
Alarm is delivered
directly to the
operator’s mobile
phone
REF542plus Rel 2.0 presentation , 34 of 62
EC V2.0 10/10/04
REF542plus
REF542plus, WebREF Application example Features

„ Operator connects to REF542plus

„ Operator finds out what happened

Advantages:
Operator is alerted nearly in real time, he/she could
verify and assess the fault type and reason even from home.
No need of expensive equipment, no dedicated network,
No human surveillance.

REF542plus Rel 2.0 presentation , 35 of 62


EC V2.0 10/10/04
REF542plus
REF542plus, CAN process bus Features

ˆ Standard CAN Open network interface


ˆ Up to 1 Mbit/s (40 m)
ˆ Goals:
z Digital I/O system for signalling
z Interlocking signals exchange among REFs in the same panel
– Horizontal communication of real time information
z Increase automation capabilities
– Access to the huge market of off-the-shelf CAN automation
products (terminal blocks, actuators, PLCs, PCs, ...)
z Analog objects for RTD or 4-20 mA sensors

REF542plus Rel 2.0 presentation , 36 of 62


EC V2.0 10/10/04
REF542plus
A new switchboard concept Features

ˆ Digital bus (CAN) as replacement of hard-wiring for inter


panel control applications
z Interlocking, automated transfer switch
z Horizontal communication

REF542plus Rel 2.0 presentation , 37 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – CAN application example Features

ˆ REF542plus’s exchange interlocking information via CAN


z Reduced interpanel wiring
ˆ Additional, intelligent CAN I/O modules are placed in empty panels.
z CAN I/O modules used for signalling and data acquisition (e.g. aux contacts
multiplication, external devices status acquisition).

REF542plus Rel 2.0 presentation , 38 of 62


EC V2.0 10/10/04
REF542plus
Time synchronization possibilities with REF542plus Features

z In case of fault, it is fundamental to ˆ Spabus communication: time setting, date and


understand: time up to seconds.
– What happened z Accuracy about 50 ms
– Where the fault started ˆ Modbus communication: time setting, date and
– How the fault started time up to seconds.
z Fault records and events from z Accuracy about 50ms
several units must be placed in ˆ IEC 103 communication: time
precise chronological order synchronization, date and time up to
seconds.
z Accuracy 10ms
ˆ LON LAG 1.4 VATS: time synchronization
z Accuracy 1ms
ˆ Direct GPS input: time synchronization
z Accuracy better than 200us

REF542plus Rel 2.0 presentation , 39 of 62


EC V2.0 10/10/04
REF542plus
REF542plus time synchronization with direct input Features

ˆ Synchronization accuracy better than 1ms


ˆ Events absolute time stamp
ˆ Fiber optic dedicated input on REF542plus MainBoard 5
ˆ IRIG-B protocol (B000, B002,B003)
ˆ Star topology signal distribution

REF542plus Rel 2.0 presentation , 40 of 62


EC V2.0 10/10/04
REF542plus
A compatible GPS: Meinberg GPS167BGT Features

ˆ Http://www.meinberg.de
ˆ 20 REF542plus can be directly synchronized
ˆ For more REF, make a connection among several GPS racks

Connector X74 on the mainboard


Transducer HFBR-0400 Series
type

Wavelength 820 nm

Max. distance 1500m

Connector ST
type
Supported IRIG, time format B000, B002, B003
protocol
Signal type Digital

REF542plus Rel 2.0 presentation , 41 of 62


EC V2.0 10/10/04
REF542plus
Integrated power factor controller Features

ˆ Turn key solution


Shunt capacitor bank integrated in the MV
switchgear
z No additional panels
z No additional control units

ˆ Several technical and economical benefits:


„ Reduced electric utility billing and penalties
„ Released system capacity
„ Increased voltage control on the load
„ Decreased I2R losses

REF542plus Rel 2.0 presentation , 42 of 62


EC V2.0 10/10/04
REF542plus
REF542plus power factor controller Features

ˆ One REF542plus controls up to 4 capacitor banks


– While it is implementing the control and protection functions for the
panel

ˆ Three different operational modes:


– Automatic mode on instantaneous Q values
– Automatic mode on integral Q value
– Manual mode by the local HMI
Feeder 3~

I
3~
V
PFC x x x

C&P

REF542plus Rel 2.0 presentation , 43 of 62


EC V2.0 10/10/04
Load
REF542plus
PFC with Resonance Protection Features

ˆ The problem
– Network parameters changes may cause resonance behaviour at capacitor or
load switching
– Resonance frequencies originates current and voltage distorsion with increase
of power losses
ˆ REF542plus resonance protection monitors continuosly the network
total harmonic distorsion (THD)
– Resonance protection detects harmonics caused by PFC operation (switching
resonance).
– Resonance protection clears the oscillation by de-energizing the capacitor
banks (PFC coordination)
Case 1 Voltage waveform at BUS9A
1.5

1
Feeder
0.5
I

V (pu)
V 0
PFC
Control -0.5

-1

Load -1.5
0.1 0.15 0.2 0.25 0.3 0.35 0.4
t (sec)

REF542plus Rel 2.0 presentation , 44 of 62


EC V2.0 10/10/04
REF542plus
THD protection Features

ˆ THD protection detects frequencies up to 25th harmonics


(sample rate 4.8 kHz)
ˆ Minimum operating time 50 ms
ˆ The protection detects high harmonic content condition based
on THD calculation

REF542plus Rel 2.0 presentation , 45 of 62


EC V2.0 10/10/04
REF542plus
High speed transfer system Features

Target
z To ensure continuous power supply
to essential electrical equipment by
Feeder A Feeder B
changing over from a main to a
stand-by feeder as fast as possible

Prerequisites HSTS
U1 U2
z Existence of at least two- usually U3
independent – synchronous feeders
S1 S2
z Circuit-breakers with short operating
times
z Suitability of consumers for network
change-over
M M

REF542plus Rel 2.0 presentation , 46 of 62


EC V2.0 10/10/04
REF542plus
HSTS based on REF542plus/SUE3000 Features

Feeder 1 Feeder terminals Feeder 2

VS/FDI VS/FDI
Init (IRQ)

Fast Fast
VM 1 VM 1

Busbar

•Fast mode total transfer time = 30ms


•Based on fast VM1-T Circuit Breaker
•HSTS is integrated in the MV switchgear:
•No need of dedicated panels
•No supplementary equipment

REF542plus Rel 2.0 presentation , 47 of 62


EC V2.0 10/10/04
REF542plus
HSTS Available Configuration Features

ˆ 2-Circuit breaker-configuration
z One busbar
z Transfer takes place between
the 2 feeders

ˆ 3-Circuit breaker-configuration
z 2 busbar sections, Busbar
coupling breaker
z Transfer between feeder and
busbar coupling breaker

REF542plus Rel 2.0 presentation , 48 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Applications Applications

ˆ Industrial IT Overview
ˆ REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values

REF542plus Rel 2.0 presentation , 49 of 62


EC V2.0 10/10/04
REF542plus
REF542plus - Applications Applications

ˆ Typical Applications for:


z Any kind of medium voltage switchgear (Incoming, Trafo, Overhead lines,
Motor, Bus Tie, ...)
z High voltage switchgear up to 170kV and three pole op. mechanism
z Low voltage switchgear with complex automation requirements
ˆ All the switchgear secondary functions integrated in one single unit:
z Control
z Protection
z Measurements
z Monitoring
z Communications

REF542plus Rel 2.0 presentation , 50 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Feeder Automation Applications

„ REF542plus equipped switchgear are a complete and effective system


for distribution networks.
„ Among others, the following automation sequences are possible:
„ Automatic switching from a double radial to a simple distribution system (ATS).
„ Performing manual switching by paralleling the feeders with the synchro-chek
function (25).
„ Motors shutdown upon temporary voltage loss/drop.
„ Prompt re-acceleration on voltage restoring within the pre-set time.
„ Motors restarting according to the pre-set sequence after voltage loss.

REF542plus Rel 2.0 presentation , 51 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Protection sets, example Applications
Type Protection functions Meas.
Basic
Non directional overcurrent 50, 51, 51N, 49 I,V, energy,
protection cosphi, power
Non directional overcurrent 50, 51, 51N, 49, 27, 59, 59N I,V, energy,
protection, voltage protections cosphi, power

Standard
Directional overcurrent 50, 51, 51N, 49, 67, 67N, 67N I,V, energy, power,
protection sensitive cosphi
Directional overcurrent 50, 51,51N, 49, 67, 67N, 67N I,V, energy, power,
protection, voltage protection sensitive, 27, 59, 59N cosphi

Application
specific
Transformer
Undervoltage protection 50, 51,51N, 49, 27, 68 I,V
Differential protection 50, 51, 51IDMT, 51N, 49, 68, I
87T,87N
Motor
Basic 50, 51, 51IDMT,51N, 51MS, I
51LR, 49, 46, 66
Differential protection 50, 51, 51IDMT, 51N, 46, 49, I
51MS, 51LR, 66, 87M
Undervoltage protection, 50, 51, 51IDMT,51N, 51MS, I,V, energy, power,
motor restart 51LR, 49, 46, 66, 27 cosphi
Full, motor restart 50, 51, 51IDMT,51N,51MS, I,V, energy, power,
51LR, 49, 46, 66, 27, 37, 32 cosphi
Generator
Basic 50, 51,51N, 49, 46 I
Standard 50, 51,51N, 49, 46, 32 I,V, energy, power,
cosphi
Full 50, 51, 51N, 51IDMT,49, 46, 32, I,V, energy, power,
27, 59, 59N cosphi
Bus tie/rise
Voltage protection 27,59,59N,50, 51 I,V
Bus tie, voltage protection 27,59,59N right side; 27,59,59N V,V
both sides left side
Bus tie, voltage protection one 27, 59, 59N, ATS V
side, ATS
Voltage protection, 27, 59, 59N, 25, ATS V, V
synchrocheck, ATS
Bus tie, voltage protection 27,59,59N right side; 27,59,59N V,V
both sides, ATS left side, ATS
Bus tie, voltage protection 27, 59, 59N right side; 27, 59, V,V
both sides, synchrocheck, 59N left side; 25, ATS
ATS
Line
Distance protection 21, 51, 67N, 79 I,V, energy, power,
cosphi

Option
Autoreclosing 79
Fault recorder
Frequency protection 81
Frequency monitoring
PFC & resonance protection 55
THD protection

Internet
WEBREF
(*) (*) Evaluation/visualization sw package for comtrade files is not included.

REF542plus Rel 2.0 presentation , 52 of 62


At most 24 protection functions can be activated
EC V2.0 10/10/04
REF542plus
REF542plus – Integration in SCADA system Applications

„ Four different communication protocols are available.


„ REF542plus can thus be easily integrated in any SCADA systems.
„ Distributed intelligence architectures result in a high degree of plant automation to:
„ Manage different loads and plant configurations
„ Change and modify the power network distribution
„ Acquire measurements and status information
„ Advanced functions are also possible:
„ Primary parts status verification
„ Circuit breaker electrical and mechanical life analysis
„ Preventive maintenance plans

REF542plus Rel 2.0 presentation , 53 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Engineering Engineering

ˆ Industrial IT Overview
ˆ REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values

REF542plus Rel 2.0 presentation , 54 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Engineering Environment Engineering

ˆ REF542plus software tools run on a PC, 2 Versions


z Configuration Tool: can manage protection functions
z Operating Tool: control functions only
ˆ REF542plus software tools have the same version of the
REF542plus firmware

REF542plus configuration tool

REF542plus Rel 2.0 presentation , 55 of 62


EC V2.0 10/10/04
REF542plus
REF542plus - Engineering Environment Engineering

ˆ Protection functions are function blocks


ˆ Circuit breaker etc modeled with switching objects
ˆ Wealth of logic functions (And, Or, Flip-flop, ...)
ˆ Programming is done linking the objects with wires

REF542plus Rel 2.0 presentation , 56 of 62


EC V2.0 10/10/04
REF542plus
REF542plus - Engineering Environment Engineering

Function block diagram programming

PLC-Style programming
REF542plus Rel 2.0 presentation , 57 of 62
EC V2.0 10/10/04
REF542plus
REF542plus – Tests and certifications Tests & certif.

ˆ Industrial IT Overview
ˆ REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values

REF542plus Rel 2.0 presentation , 58 of 62


EC V2.0 10/10/04
REF542plus
REF542plus - Type tests and certifications Tests & certif.

ˆ All relevant tests according to: ˆ ATEX (PTB 02 ATEX 3000)


z IEC 60255 series z According to Directive 94/9/EC for
explosive environments
z EN 61000 (basic EMC
standards)
z IEC 6094 (common ˆ EC Conformity
specifications for HV switchgear
and control gear standards)
ˆ Panorama Verification Centre
z EN 50263 ( New product
z (ABB Internal compliance for
standard ) Substation Automation Integration)
- 6767 E 26-03-02 -

REF542plus Rel 2.0 presentation , 59 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Customer Values Tests & certif.

ˆ Industrial IT Overview
ˆ REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values

REF542plus Rel 2.0 presentation , 60 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Customer Values Customer Values

ˆ Flexibility and advanced functions:


z Very complex automation sequences possible.
z Flexibility also after commissioning: software changes, no new wiring.
z Wealth of information in case of primary faults (fault recorder, event time, etc).

ˆ Everything in one box, which is always the same:


z Trafo feeder, motor feeder, overhead lines feeder, etc.: the box is always the
same.
z One kind only of spare part.
z One human machine interface only to learn.

REF542plus Rel 2.0 presentation , 61 of 62


EC V2.0 10/10/04
REF542plus
REF542plus – Customer Values Customer Values

ˆ Open connectivity to any automation systems:


z 4 different protocols (Modbus RTU, IEC 103, LON Lag 1.4, Spabus).
z WEBInterface for intranet/internet applications. REF542plus
z 4...20mA analog input and output. General

ˆ State of the art technology


z E.G. innovative sensors supported according to new IEC 60044-8.
z Wealth of protection and control functions.
z User friendliness.

REF542plus Rel 2.0 presentation , 62 of 62


EC V2.0 10/10/04
A global leader in power and automation technologies
that enable utility and industry customers to improve
performance while lowering environmental impact