Model REF542plus
(Rel. 2.0)
1VCP000060 – Rev.A, en – 2004.10
Presentation
REF542plus – presentation contents Contents
REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values
Cost effectiveness
Engineering
and wiring reduction
Hardware variants minimization
High Integration
Fault possibilities reduction
Easier modifications
Easier expansions
10000
8000
Volume (pcs)
6000
REF542plus
4000
REF542
2000
0
93
94
95
96
97
98
99
00
01
02
03
19
19
19
19
19
20
20
20
20
19
19
WE
z DECMS - ITSCB - CHSEC
CEE
z CZEJF
CN
z CNDMX
MENA
z TRABB - EGARC
SEA
z AUTIL - MYTAD – KRABB
INDIA
z INABB
REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values
Optical Interface
Analog Output 4..20mA Module Analog Input 4..20mA Module Communication Module
RX TX
0/4...20mA 4...20mA
CP
Communication Processor
Time Synch.
UL1 start L2 Control
Protections,
UL2 start L3
UL3
Measurements
Release/Trip
Io Autoreclosure
Vo
CAN Eth.
(exemplary inputs)
Main Board
Binary Binary
inputs outputs
CT, VT connector
Sensor inputs
Small housing
HMI
Components
3 Versions:
BASE
•RS232 Service port, RS485 for HMI, RJ45 Ethernet 10Base T
STANDARD
•Like BASE plus CAN and Irig–B optical input port for time synchronization
FULL
Like STANDARD plus fast digital I/0 ports (2 inputs - 1 output)
14 Binary Inputs, 24-90 VDC (threshold 14VDC) or 85-220 VDC (threshold 50VDC)
6 Power Outputs, Load current 12A, operate time 9ms
2 Signal Outputs, Load current 2A, operate time 5ms
1 Optional Static Output instead of mechanical, Load current 0.7A, operate time 1ms
1 coil supervision circuit
1 watchdog contact
The module is also available with the minus (‘-’) of the
binary inputs interconnected, to semplify wiring
Communication
z SPABUS (optical glass, optical plastic)
z LON LAG 1.4 (optical glass)
z IEC 103 (optical glass)
z MODBUS RTU (two independent channels, optical glass, RS 485)
z WEB SERVER
REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values
Protections Visualization
– overcurrent – bay single line diagram
– measurement
– overvoltage / undervoltage
– events and alarms Motor specific protections
– earthfault – parameters and settings – thermal overload
– distance – directional power
– differential for transformers and – unbalanced load
motors – low load
–restricted differential – inrush blocking
Control
– control, interlocking
– alarm handling Aditional functions
– local control and indication – synchro-check
– 5 shots auto-reclosing
– fault recording
Supervision Power Quality -communication to SCADA
– self diagnosis – Power factor controller with -WEB SERVER
resonance protection
– switchgear faults - CAN digital bus interface
– THD protection
–data transmission failure -Frequency protection
-High speed transfer
Analogue channels 8
Digital channels 32
Acquisition rate 1,2 kHz
Pre fault time 100ms..2s
Min Recording time 1sec
Max Recording time 5sec
Max num of records 5
Fault records are retrieved and converted into the COMTRADE format
Working activities
cause a short circuit
in the medium
voltage system
REF542plus trips
Local alarm indication
=> SMS is sent
SMS:
Alarm is delivered
directly to the
operator’s mobile
phone
REF542plus Rel 2.0 presentation , 34 of 62
EC V2.0 10/10/04
REF542plus
REF542plus, WebREF Application example Features
Advantages:
Operator is alerted nearly in real time, he/she could
verify and assess the fault type and reason even from home.
No need of expensive equipment, no dedicated network,
No human surveillance.
Http://www.meinberg.de
20 REF542plus can be directly synchronized
For more REF, make a connection among several GPS racks
Wavelength 820 nm
Connector ST
type
Supported IRIG, time format B000, B002, B003
protocol
Signal type Digital
I
3~
V
PFC x x x
C&P
The problem
– Network parameters changes may cause resonance behaviour at capacitor or
load switching
– Resonance frequencies originates current and voltage distorsion with increase
of power losses
REF542plus resonance protection monitors continuosly the network
total harmonic distorsion (THD)
– Resonance protection detects harmonics caused by PFC operation (switching
resonance).
– Resonance protection clears the oscillation by de-energizing the capacitor
banks (PFC coordination)
Case 1 Voltage waveform at BUS9A
1.5
1
Feeder
0.5
I
V (pu)
V 0
PFC
Control -0.5
-1
Load -1.5
0.1 0.15 0.2 0.25 0.3 0.35 0.4
t (sec)
Target
z To ensure continuous power supply
to essential electrical equipment by
Feeder A Feeder B
changing over from a main to a
stand-by feeder as fast as possible
Prerequisites HSTS
U1 U2
z Existence of at least two- usually U3
independent – synchronous feeders
S1 S2
z Circuit-breakers with short operating
times
z Suitability of consumers for network
change-over
M M
VS/FDI VS/FDI
Init (IRQ)
Fast Fast
VM 1 VM 1
Busbar
2-Circuit breaker-configuration
z One busbar
z Transfer takes place between
the 2 feeders
3-Circuit breaker-configuration
z 2 busbar sections, Busbar
coupling breaker
z Transfer between feeder and
busbar coupling breaker
Industrial IT Overview
REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values
Standard
Directional overcurrent 50, 51, 51N, 49, 67, 67N, 67N I,V, energy, power,
protection sensitive cosphi
Directional overcurrent 50, 51,51N, 49, 67, 67N, 67N I,V, energy, power,
protection, voltage protection sensitive, 27, 59, 59N cosphi
Application
specific
Transformer
Undervoltage protection 50, 51,51N, 49, 27, 68 I,V
Differential protection 50, 51, 51IDMT, 51N, 49, 68, I
87T,87N
Motor
Basic 50, 51, 51IDMT,51N, 51MS, I
51LR, 49, 46, 66
Differential protection 50, 51, 51IDMT, 51N, 46, 49, I
51MS, 51LR, 66, 87M
Undervoltage protection, 50, 51, 51IDMT,51N, 51MS, I,V, energy, power,
motor restart 51LR, 49, 46, 66, 27 cosphi
Full, motor restart 50, 51, 51IDMT,51N,51MS, I,V, energy, power,
51LR, 49, 46, 66, 27, 37, 32 cosphi
Generator
Basic 50, 51,51N, 49, 46 I
Standard 50, 51,51N, 49, 46, 32 I,V, energy, power,
cosphi
Full 50, 51, 51N, 51IDMT,49, 46, 32, I,V, energy, power,
27, 59, 59N cosphi
Bus tie/rise
Voltage protection 27,59,59N,50, 51 I,V
Bus tie, voltage protection 27,59,59N right side; 27,59,59N V,V
both sides left side
Bus tie, voltage protection one 27, 59, 59N, ATS V
side, ATS
Voltage protection, 27, 59, 59N, 25, ATS V, V
synchrocheck, ATS
Bus tie, voltage protection 27,59,59N right side; 27,59,59N V,V
both sides, ATS left side, ATS
Bus tie, voltage protection 27, 59, 59N right side; 27, 59, V,V
both sides, synchrocheck, 59N left side; 25, ATS
ATS
Line
Distance protection 21, 51, 67N, 79 I,V, energy, power,
cosphi
Option
Autoreclosing 79
Fault recorder
Frequency protection 81
Frequency monitoring
PFC & resonance protection 55
THD protection
Internet
WEBREF
(*) (*) Evaluation/visualization sw package for comtrade files is not included.
Industrial IT Overview
REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values
PLC-Style programming
REF542plus Rel 2.0 presentation , 57 of 62
EC V2.0 10/10/04
REF542plus
REF542plus – Tests and certifications Tests & certif.
Industrial IT Overview
REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values
Industrial IT Overview
REF542plus
z General
z Hardware
z Features
z Applications
z Engineering
z Tests and Certifications
z Customer values
Visit us at www.abb.com