VRV INDOOR UNITS

Maintenance Frequency
Description Comment Daily Monthly
1. REFNET Header Check for integrity.
1. Indoor Electronic Expansion Check operation of linear control and
Valve individual control.

2. Fans and Motors Check bearings and lubricate as


necessary. Inspect and check on fan
guard covers and inspection plates.
3. Heat Exchanger Check for damage and/or dust
accumulation. Clean as necessary.

4. Air Filter Wash, dry and refit. Renew if


required.

5. Electrical Tighten all terminal connections.


Check integrity of electrical insulation.

6. Liquid Crystal Remote Check operation of


Controller heating/cooling/timer/temperature/filter
/mode select/malfunction displays.
Return to tenant settings if correct.
quency
Quarterly H Yearly Yearly NOTES
x
x 0 pulse close, 200 pulse fully
open. When cooling stops 0
pulse. When heating stops 240
pulse.
x Ensure that all bolts, screws etc
are in place and tight.

x Do not use CFCs (refrigerant)


for cleaning fins.

x In a dirty environment more


frequent cleaning may be
required.
x Check all fuses for correct
amperages. Pay particular
attention to terminals.

x All operations must be recorded


whilst carrying out service.
Explain use of controller to a
competent person within
tenants demise.