How To Make Sure Your

Air Conditioner Keep Its Cool

So You Dont Have To Sweat Out A Summer Of Repairs

If youre going to have an air Our log forms cover four groups of
conditioning failure, its going to air conditioning and refrigeration
happen in the next few weeks. More installations: systems with a
Hartford Steam Boiler air conditioning breakdowns occur reciprocating compressor under 25
One State Street during early summer than any other HP, those with a reciprocating
P.O. Box 5024
time. compressor over 25 HP, those with a
Hartford, CT 06102-5024
centrifugal compressor, and
Tel: (800) 472-1866
www.munichre.com/HSB We know. We pay the insurance absorption systems.
claims on them. But you pay the
July 2016 price: in equipment downtime, Note: logs for larger systems feature
repairs, and heat from the categories for even more detailed
management. record keeping (Complex systems
require a complete set of readings
Thats why were offering tips from either daily, at the beginning of each
our field inspectors: how to avoid the eight-hour shift, or, for major
most common air conditioning commercial buildings, every hour.)
problems with a little strategic
maintenance. A. Annually check open or hermetic
motors for burn out.
How Our Complimentary
Logs Can Help You Head Off Check air ventilation openings on
open-type motors for obstruction.
Air Conditioning Problems. Check bearings on open-type
The better data you have on your motors for adequate and proper
systems performance, the better lubrication.
youre able to spot recurring Have insulation resistance meter
problems and extend your readings taken on motor windings.
equipments useful life. Hartford If resistance is less than one
Steam Boiler has created a megohm, dont start the motor. (For
complimentary air conditioning hermetic motors, be sure the crank
log to help you track operating case heater is energized at least
characteristics and alert you to eight hours before this test.)
impending trouble.
B. Annually inspect motor controls.
Logs and Checklists are available
on HSB.com in the Equipment Care Remove the covers on the motors
section. magnetic starters and examine the
contacts. Compressor cycling can
Hartford Steam Boiler Page 2/4
Air Conditioning Keeps Its Cool

Hermetic air-cooled reciprocating system (25 HP) G. Annually clean the condensers/
cooling towers.
C
Clean air cooled condensers, but
G
only with a solution marketed for
this specific use. Take care to
protect the fan motors from any
C
moisture.
Remove the heads on shell and
M tube condensers and clean the
tubes of scale and debris.
Clean the coils, sump, spray
D nozzles and overflow drain on
evaporative condensers.
B For cooling towers, clean the sump
J
and spray nozzles and check the
A baffles for tightness and
soundness.
Check the makeup water valve to
K, L be sure its operating properly.

E
H. Help prevent scrambled
H compressors.
I

At least eight hours before start-up,


make them deteriorate. Look for E. Annually check the oper ating hermetic compressors need to have
pitting or corrosion. and safety controls. their crank case heater energized.
Check all terminal connections for This step is vital. Preferably, leave
tightness. Theyre the heart of your the heaters energized for the rest of
Check the overload protection for equipment. Make sure theyre the season; when the compressor
defects and proper sizing properly calibrated and in working is idle, the heater will prevent
Make sure timing devices have the order. refrigerant from migrating to the
correct operating sequence. Immerse thermal sensing controls compressor.
Check mechanical linkage for in a cold medium to verify the Have the cylinder heads removed
binding and looseness. condition and setting of their and check the compressor valves
sensing elements. at least once every two years, or
C. Monthly check the fans. Test oil pressure differential every 10,000 hours. Valve failure is
switches mechanically and one of the biggest causes of
Check fans for broken, cracked, electrically. Flow switches should compressor break down. If you see
bent or loose blades and hubs. be removed from the well for signs of wear or fatigue, replace
Check the fan shaft and bearings. examination, be sure to look for them. (Valves are relatively
Check belt tension and condition. signs of corrosion on the paddle inexpensive.)
and linkage.
D. Annually check the thermostatic Avoid lubrication failure.
expansion valve. F. Monthly check the pumps.
Lubrication failure is one of the
Check it for proper superheat Check the condition of pump biggest causes of equipment
setting over its full range of bearings, packings, shaft couplings breakdown. Without proper
operation. If its not operating and seals. lubrication at all times, moving parts
within its design limits, it can affect in the motor-compressor wear out,
the safe operation of the overheat, burn and break.
equipment.
Hartford Steam Boiler Page 3/4
Air Conditioning Keeps Its Cool

Every year, have your service system, and installs proper liquid and To avoid pressure problems: try to
technician check the oil to make sure suction line filters and dryers. determine normal discharge and
its suitable: clean and non-acid. suction pressures. (Your air
Its even more important to conditioning unit may be equipped
Also have the technician leak test the determine the source of the moisture with pressure gauges.) As with
system regularly, and repair any point and to correct it right away. You may temperature changes, any increase
of leakage immediately. need to leak test any water-cooled in pressure is reason enough to call
condensers or chillers. the service technician at once.
I. Weekly check lubrication. When
the system is idle, look through the Normally, youll see a pattern of clear Dirty condensers are a key cause of
oil sight glass to check lubrication in liquid flow. If you notice other pressure and temperature problems.
the compressor crankcase. The oil changes in the flow pattern (such as Make sure the technician verifies
level should remain constant. If you gas bubbles in the liquid refrigerant), that the condenser is clean. If you
temporarily lose oil in the sight glass, have the system checked to see if its have a water-cooled or evaporate
you may have unwanted refrigerant properly charged with refrigerant. condenser, use an effective water
in the crank case. Call the service Control malfunction can also cause treatment to prevent scale, corrosion
technician at once. flow pattern changes. and algae.

Oil and refrigerant leaks often show Regularly check temperature (k) M. Keep air filters clean. Keep air
up as oil spots with dust and pressure (l) controls. Effective filters free of dust particles, smoke
accumulationsa symptom of air conditioning depends on reliable and dirt. Keep a careful log of
trouble. temperature and pressure controls. cleaning dates to maintain an
Each is calibrated to perform a effective cleaning schedule.
Check these likely leak spots every specific function. Periodically have
week: compressor shaft seals them serviced, adjusted and proof- If your system is an absorption unit:
piping joints coils vessels testedonly by qualified personnel. (not shown here) test and evaluate
compressors motors. the lithium bromide solution
When your system shuts down, concentration and the lithium
J. Avoid refrigerant circuit failure. check these areas. Above-normal bromide inhibitor.
Moisture hurts any refrigeration room temperatures invariably spell
system: preventing proper lubrication, trouble. If there hasnt been a power Check the absorption purge unit and
corroding or copper plating the interruption and all other purge system for proper operation.
moving parts, and freezing in the checkpoints appear normal, call the
expansion valves. The result: erratic service technician. Examine all canned motor pumps
performance, inefficiency, and even used on the absorber unit and check
breakdown. If the motor-compressor has shut the bearings for wear. Look carefully
down, dont attempt to restart the at the condition of the motor stator
Moisture can enter the system if system. Protective controls may have and rotor seals.
water-cooled condensers or water tripped it off; find and correct the
chillers leak. It can get in accidentally cause of the trip-off. Dont attempt to These diagrams can help you work
when youre charging refrigerant or oil restart the systemit could result in with service people to identify parts
into the system, unless you take severe equipment breakdown. needing replacement, points of
special care. Heres how to check for refrigerant leakage, regulating and
moisture problems: Dont attempt to adjust regulating protective control settings, and other
or protective controls yourself: This critical features.
Equip your refrigerant circuit (liquid is the time for an expert to diagnose
line) with a moisture sight glass and correct the problem.
indicator. Look for any change in the
indicator chemical color. If the color
changes toward wet, make sure
your service technician corrects the
problem, cleans and dries the
Hartford Steam Boiler Page 4/4
Air Conditioning Keeps Its Cool

If operating characteristics changewatch out.

Each system has its own normal pattern of noise, vibration, speed, temperature
and pressure. They vary, depending on the season and the heat load your
system handles. Once youve familiarized yourself with these normal
conditions, youll be able to spot trouble signs.

Any change in normal operating characteristics is a warning. Call the service


technician if you notice:

unusual noise or vibration


a strange odor
oil or water spots
sudden changes in temperature, speed or pressure.

Correct the problem at once.

Suspect a problem? Call your service firm.


Thats critical advice. Consult with a professional before undertaking any
maintenance steps or repairs. An adequate service program may cost a little
more up front, but it will pay off in long-term savings.

(Our advice is intended to complement the equipment manufacturers


recommendationnot replace them. If you have doubts about any particular
procedure, call an air conditioning service firm.)

Air Conditioning/Refrigeration Maintenance/Operations


Guide
Manufacturer: ___________________________________ Number: _______________________

Size: _______________ Location:_______________________________________________________

Service Company: ___________________________________________________________________

Service Technician: __________________________________________________________________

Date serviced: ________________________________________________________________________

2015 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved.