Voltage Drop Calculation

A Base Selection
Base KV 400 kV
Base MVA 100.0 MVA
Base Current = Base MVA *1000/ ( 1.732 X Base KV) Amp 144.34 A
Base Impedance = (Base KV) / Base MVA
2
1600.0000 Ohm

B Reactor Details
Rating of reactor in MVAr 50.0 MVAr
Voltage ( KV) 400 kV
Impedance of Reactor 3200 ohm
Voltage in pu 1 pu
Impedance of Reactor in pu 2 pu

C Source Details
Source Voltage (kV) 410.00 kV
Fault kA of source (kA) = 9.15 kA
Fault MVA of source = 6500.00 MVA
Voltage in pu 1.03 pu
Zsource = Source Impedance 25.86 ohm
Zsource in pu 0.0162 pu

D Thevenin voltage
Thevenin Voltage (VTH) in pu 1.0167826342 pu
Thevenin Impedance in pu 0.0160338844 pu
Percentage voltage drop (%) 0.802%
Voltage drop in pu 0.0082 pu
Voltage Drop Calculation
A Base Selection
Base KV 400 kV
Base MVA 100.0 MVA
Base Current = Base MVA *1000/ ( 1.732 X Base KV) Amp 144.34 A
Base Impedance = (Base KV) / Base MVA
2
1600.0000 Ohm

B Reactor Details
Rating of reactor in MVAr 50.0 MVAr
Voltage ( KV) 400 kV
Impedance of Reactor 3200 ohm
Voltage in pu 1 pu
Impedance of Reactor in pu 2 pu

C Source Details
Source Voltage (kV) 410.00 kV
Fault kA of source (kA) = 9.15 kA
Fault MVA of source = 6500.00 MVA
Voltage in pu 1.03 pu
Zsource = Source Impedance 25.86 ohm
Zsource in pu 0.0162 pu

D Thevenin voltage
Thevenin Voltage (VTH) in pu 1.0167826342 pu
Thevenin Impedance in pu 0.0160338844 pu
Percentage voltage drop (%) 0.802%
Voltage drop in pu 0.0082 pu