You are on page 1of 48

ED 01 - 214A

- Heat Pump -
GA-Series
ED01-214A

Split - System
Room Air Conditioners
GA - Series
FTY50GAV1A RY50GAV1A
Heat Pump
FTY60GAV1A RY60GAV1A

1. Power Supply ..........................................................................................2


1.1 Power Supply ...........................................................................................2
2. Functions.................................................................................................3
2.1 List of Functions .......................................................................................3
3. Specifications ..........................................................................................4
3.1 Heat Pump ...............................................................................................4
4. Dimensions .............................................................................................5
4.1 Heat Pump ...............................................................................................5
5. Wiring Diagrams......................................................................................7
5.1 Heat Pump ...............................................................................................7
6. Piping Diagrams......................................................................................9
6.1 Heat Pump ...............................................................................................9
7. Capacity Tables ....................................................................................11
7.1 Heat Pump .............................................................................................11
7.2 Capacity Correction Factor by the Length of Refrigerant Piping
(Reference) ............................................................................................13
8. Operation Limit......................................................................................14
8.1 Heat Pump .............................................................................................14
9. Sound Level ..........................................................................................15
9.1 Overall Sound Level ...............................................................................15
9.2 Octave Band Level .................................................................................16
10.Electric Characteristics..........................................................................18
10.1 Electric Characteristics...........................................................................18
11.Installation Manual ................................................................................19
11.1 FTY50 / 60GA ........................................................................................19
12.Operation Manual..................................................................................26
12.1 FTY50 / 60GA ........................................................................................26
13.Optional Accessories ............................................................................42
13.1 Option List ..............................................................................................42
13.2 Installation Manual .................................................................................43

Room Air Conditioners GA-Series 1


Power Supply ED01-214A

1. Power Supply
1.1 Power Supply

Indoor Unit Outdoor Unit Power Supply


FTY50GAV1A RY50GAV1A
1, 220/230/240V, 50Hz
FTY60GAV1A RY60GAV1A

Note: Power Supply Intake ; Outdoor Unit

2 Room Air Conditioners GA-Series


ED01-214A Functions

2. Functions
2.1 List of Functions

FTY5060GAV1A

FTY5060GAV1A
RY5060GAV1A

RY5060GAV1A
Category Functions Category Functions

Basic Inverter (with Inverter Power Control) Health & Air Purifying Filter with Bacteriostatic,
Function Clean Virustatic & Deodrizing Functions {

Operation Limit for Cooling (C) 19.4~46 Longlife Filter


Operation Limit for Heating (C) -10~15 Ultra-Longlife Filter (Option)
Microprocessor Control { Photocatalytic Deodrizing Filter
PAM Control Photocatalytic Filter with UV Lamp
Compressor Oval Scroll Compressor (DAIKIN Mould Proof Air Filter {
SCROLL)
Swing Compressor (DAIKIN ROTARY) Washable Grille {
Rotary Compressor { Filter Cleaning Indicator {
Reluctance DC Motor Good-Sleep Cooling Operation
Comfortable Dual Flaps { Timer 72-Hour On/Off Timer
Airflow
Power-Airflow Dual Flaps 24-Hour On/Off Timer {
Power-Airflow Diffuser { Night Set Mode {
Wide-Angle Louvers { Just Fit Thermostatic Timer
Vertical Auto-Swing (Up and Down) { Worry Free Auto-Restart (after Power Failure) {
Reliability &
Horizontal Auto-Swing (Right and Left) Durability Self-Diagnosis (Digital, LED) Display {
3-D Airflow The Remote Controller Loss
Prevention with the Chain (Option) {

3-Step Airflow (H/P Only) Wiring-Error Check


Comfort Auto Fan Speed Anticorrosion Treatment of Outdoor
Control { Heat Exchanger {

Silent Operation Control (Automatic) Flexibility Multi-Split / Split Type Compatible


Indoor Unit {

Outdoor Unit Silent Operation Flexible Voltage Correspondence


(Manual)
Intelligent Eye High Ceiling Application
Quick Warming Function Chargeless 10m
Hot-Start Function Remote 5-Rooms Centralized Controller
{ Control (Option) {

Automatic Defrosting {
Remote Control Adaptor (Option) {
(Normal Open-Pulse)
Operation Automatic Operation {
Remote Control Adaptor (Normal {
Open Contact)
Programme Dry Function { Dlll-NET Compatible (Adaptor)
Fan Only Remote Wireless {
Controller
Lifestyle New Powerful Operation (Non- {
Wired
Convenience Inverter)
Inverter Powerful Operation
Priority-Room Setting
Laundry Programme Operation
Home Leave Operation
Power Selection
Indoor Unit On/Off Switch {
Signal Reception Indicator {
Temperature Display
Note: { : Holding Functions
: No Functions

Room Air Conditioners GA-Series 3


Specifications ED01-214A

3. Specifications
3.1 Heat Pump
220-230-240V, 50Hz
Indoor Units FTY50GAV1A FTY60GAV1A
Model RY50GAV1A RY60GAV1A
Outdoor Units
Cooling Heating Cooling Heating
kW 5.20 5.80-6.07-6.07 6.15 7.00-7.16-7.16
Capacity Rated Btu/h 17,750 19,800-20,720-20,720 21,000 23,900-24,400-24,400
kcal/h 4,470 4,990-5,220-5,220 5,300 6,020-6,150-6,150
Moisture Removal L/h 2.2 3.9
Running Current (Rated) A 9.7-10.7-10.7 8.8-9.5-9.5 11.2-10.8-10.8 11.0-10.8-10.8
Power Consumption W 1,900-2,080-2,080 1,700-1,920-1,920 2,300-2,460-2,460 2,260-2,470-2,470
Power Factor % 89.0-84.5-81.0 87.8-87.9-84.2 93.3-99.0-94.9 93.3-99.4-95.3
COP W/W 2.74-2.50-2.50 3.41-3.16-3.16 2.67-2.50-2.50 3.10-2.90-2.90
Liquid mm 6.4 6.4
Piping Gas mm 15.9 15.9
Connections
Drain mm 18.0 18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Indoor Unit FTY50GAV1A FTY60GAV1A
Front Panel Color Almond White Almond White
H 14.0 (494) 16.3 (575) 14.0 (494) 16.3 (575)
Air Flow Rate m/min M 11.7 (413) 13.7 (484) 12.1 (427) 14.0 (494)
(cfm)
L 9.4 (332) 11.1 (392) 10.3 (364) 11.7 (413)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 54 54
Speed Steps 5 Steps and Auto 5 Steps and Auto
Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward
Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof
Running Current (Rated) A 0.19-0.18-0.17 0.19-0.18-0.17 0.19-0.18-0.17 0.19-0.18-0.17
Power Consumption (Rated) W 40 40 40 40
Power Factor % 95.7-96.6-98.0 95.7-96.6-98.0 95.7-96.6-98.0 95.7-96.6-98.0
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (HWD) mm 2981,050190 2981,050190
Packaged Dimensions (WDH) mm 1,183367289 1,183367289
Weight kg 12 12
Gross Weight kg 16 16
Operation H/M/L dBA 45/41/35 44/39/33 46/42/37 46/41/34
Sound
Outdoor Unit RY50GAV1A RY60GAV1A
Casing Color Ivory White Ivory White
Type Hermetically Sealed Rotary Type Hermetically Sealed Rotary Type
Compressor Model RC70AV1TRT NH41VMDT
Motor Output W 1,700 2,200
Type SUNISO 4GSD.I. MS-32
Refrigerant Oil
Charge L 1.00 1.20
Type R22 R22
Refrigerant
Charge kg 1.55 1.75
H 35-36.5-38 (1,236-1,288-1,341) 32-33.5-35 (1,130-1,183-1,236) 44-45-46 (1,553-1,589-1,624) 40-41.5-43 (1,412-1,465-1,518)
Air Flow Rate m/min (cfm)
L 16.5-17-17.5 (582-600-618) 15.5-16-16.5 (547-582-618) 38-38.5-39 (1,341-1,359-1,377) 34.5-35-35.5 (1,218-1,236-1,253)
Type Propeller Propeller
Fan
Motor Output W 35 53
Running Current (Rated) A 9.51-10.52-10.53 8.61-9.32-9.33 11.01-10.62-10.63 10.81-10.62-10.63
Power Consumption (Rated) W 1,860-2,040-2,040 1,660-1,880-1,880 2,260-2,420-2,420 2,220-2,430-2,430
Power Factor % 88.9-86.0-82.3 87.6-87.7-84.7 93.3-99.1-94.9 93.3-99.1-95.2
Starting Current A 43-44-45 55-58-60
Dimensions (HWD) mm 685800300 685880350
Packaged Dimensions (WDH) mm 955390732 1040460732
Weight kg 51 75
Gross Weight kg 55 79
Operation Sound dBA 49-50-50 51-52-52 54-56-56 54-56-56
Drawing No. 3D028523 3D028524

Conversion Formulae
Notes: MAX. interunit piping length: 30m
MAX. interunit height difference: 15m kcal/h=kW860
Btu/h=kW3414
Amount of additional refrigerant for piping length exceeding 10m : 30g/m(50class), 60g/m(60class) cfm=m/min35.3
The data are based on the conditions shows in the table below.
Standard Cooling Heating Piping Length Power Source

JIS C 9612 Indoor ; 27CDB/19CWB Indoor ; 20CDB 5m 50Hz 220V


Outdoor ; 35CDB/24CWB Outdoor ; 7CDB/6CWB
The data on the conditions (AS/NZS3823, 1)
(Conditions).
Standard Cooling Heating Piping Length Power Source

AS/NZS3823, 1 Indoor ; 27CDB/19CWB Indoor ; 20CDB 7.5m 50Hz 230/240V


Outdoor ; 35CDB/24CWB Outdoor ; 7CDB/6CWB

4 Room Air Conditioners GA-Series


ED01-214A Dimensions

4. Dimensions
4.1 Heat Pump
4.1.1 Indoor Unit

FTY50GAV1A / FTY60GAV1A

THE MARK () SHOWS PIPING DIRECTION AIR FLOW(INDOOR)


REQUIRED SPACE 50MIN
REAR REAR (FOR PERFORMANCE AND
MAINTENANCE) (SPACE FOR
1042
PERFORMANCE)
50MIN
(SPACE FOR
LEFT RIGHT 50MIN
MAINTENANCE)
(SPACE FOR
65 100MIN
1800MIN MAINTENANCE)
( INCLUDING
INSTALLATION PLATE ) (FOR SAFTY)
193 SPACE FOR DRAWING AIR FILTERS
1050 190

298 NAME PLATE


DIFFUSER TERMINAL STRIP
SIGNAL RECEIVER AND WITH EARTH
OPERATION SWITCH TERMINAL LIQUID PIPE 6.4CuT DRAIN HOSE
(THE LENGTH OF PIPE OUTSIDE (CONNECTING PART I.D.14.0, O.D.18.0)
UNDER CLEANING INDICATOR LAMP ROOM TEMP. THE UNIT: ABOUT 420) (THE HOSE LENGTH OF OUTSIDE
FLAP TIMER INDICATOR LAMP THERMISTOR THE UNIT IS APPROX. 620)
FRONT GRILLE FIXING SCREWS GAS PIPE CuT
OPERATION INDICATOR LAMP FTY45 12.7 (THE LENGTH OF PIPE OUTSIDE THE UNIT: ABOUT 380)
SIGNAL TRANSMITTER FTY50
FTY60 15.9
BLADE ANGLE (1050)
UP/DOWN:(AUTOMATIC) 1000 30

14
22
COOLING DRY HEATING
58 18
DIFFUSER
DAIKIN

175
20
167

20 20

(298)
FLAP 40
15 15
163

30

52
60 75 137
52

40 40
RIGHT/LEFT:(MANUAL) WALL HOLE FOR EMBEDDED PIPING WALL HOLE
80 HOLE 80 HOLE
(ARC423A17) STANDARD LOCATIONS OF WALL HOLES
60 3D028532
WIRELESS REMOTE CONTROLLER 60

Room Air Conditioners GA-Series 5


Dimensions ED01-214A

4.1.2 Outdoor Unit

RY50GAV1A
HOLES FOR ANCHOR BOLTS

31
(M8 OR M10) 2-DRAIN OUTLET 269

350
330
98
540 130

800 15 300 OUTDOOR TEMP. THERMISTOR


EARTH TERMINAL TERMINAL COVER
(M4)

POWER INTAKE
LIQUID PIPE
645

LIQUID (6.4CuT)
685

STOP VALVE

SERVICE PORT

95 70
GAS
75 STOP VALVE
NAME PLATE 100 GAS PIPE
(15.9CuT)

50
MINIMUM SPACE FOR AIR PASSAGE
50

50

100

100

50 3D004853B

RY60GAV1A
HOLES FOR ANCHOR BOLTS
(M8 OR M10)
90

370
410
128
40

TERMINAL COVER
177
40 120 500 190 15 350 OUTDOOR TEMP. THERMISTOR
3-DRAIN OUTLET EARTH TERMINAL
881 55 (M4)

POWER INTAKE
686

LIQUID STOP VALVE


(6.4CuT)
55

GAS STOP VALVE


(15.9CuT)
145

SERVICE PORT
30
NAME PLATE 40
120 110
MINIMUM SPACE FOR AIR PASSAGE
A
100

100

100

A
H

<1000 350
H=
H>1000 600
100 100
A

3D004852A

6 Room Air Conditioners GA-Series


ED01-214A Wiring Diagrams

5. Wiring Diagrams
5.1 Heat Pump
5.1.1 Indoor Unit

FTY50GAV1A / FTY60GAV1A

FIELD WIRING.
1
X1M 2
PCB3 PCB1 PCB2 H1
S25 S24 RED 1 3
Fu outdoor
WHT 2
LED LED LED 3.15A H2 BLK 3
S37 S36 GRN/YLW
H1P H2P H3P
H3
S8W
FG : FRAME GROUND
Fu : FUSE
H1~H3 : HARNESS
H1P~H3P : PILOT LAMP
FG M1F : FAN MOTOR
HA
M1S : SWING MOTOR
PCB4 PCB1~PCB4 : PRINTED CIRCUIT BOARD
S21 S201 R1T,R2T : THERMISTOR
S1W S6~S201 : CONNECTOR
S6
S27 S26 S1W : OPERATION SWITCH
S8W : CLEANING INDICATOR RESET
SIGNAL SWITCH
RECEIVER S31 S32 M M1S
X1M : TERMINAL STRIP
: PROTECTIVE EARTH
t t
NOTE
R1T R2T M ADDRESS JUMPER IS MARKED "JA" ON PCB.

WIRELESS M1F
REMOTE indoor
CONTROLLER

3D027719

Room Air Conditioners GA-Series 7


Wiring Diagrams ED01-214A

5.1.2 Outdoor Unit

RY50GAV1A

TO INDOOR UNIT X1M


S1 PCB
1 1 RED

RED
MRCW MRCC MRRH MRRL MRC MR2 T1R
2 2 WHT
135C
3 3 BLK S5 t

BLU
GRN/YLW SA
5A F1U
POWER SUPPLY
5A F2U

RED
AC220-240V GRN/YLW S3
~50Hz L L YLW

BLU
MRC
PNK
BLU X11A MRRL
N N RTH1
MRRH
RED

BLU Q1L MRCC


EARTH GRN/YLW WHT t MRCW
WHT S7
MR2
YLW
1 5 A1
K1M YLW

BRN
BRN

BLK
ORG
RED
BLU
PPL
2 6 A2 BRN C2R
t t
BRN

R2T R1T X10A X12A


C1R

BLU

BLU
BLK

BLK

WHT
RED
BLK
ORG
BLU

YLW

RED

C1R,C2R : RUNNING CAPACITOR


Y2S Y1R
F1U,F2U : FUSE X14A
K1M : COMPRESSOR RELAY
L : LIVE
M1C : COMPRESSOR MOTOR S M
C M
M1F : FAN MOTOR M S1~S7 : CONNECTOR ON PCB 1~ M1F
MR : MAGNETIC RELAY 1~ M1C SA : SURGE ARRESTER
N : NEUTRAL T1R : TRANSFORMER
PCB : PRINTED CIRCUIT BOARD X1M : TERMINAL STRIP
Q1L : OVERLOAD PROTECTOR X10A~X14A : CONNECTOR
R1T,R2T : THERMISTOR Y1R : REVERSING SOLENOID VALVE
RTH1 : THERMISTOR ON PCB Y2S : SOLENOID VALVE 3D028080

RY60GAV1A
X1M
TO INDOOR UNIT
1 RED
PCB
RED

1
2 WHT MRCW MRCC MRRH MRRL MRC MR1 MR2
2
3 3 BLK
BLU

S1
GRN/YLW 5A F1U
POWER SUPPLY
5A F2U T1R
RED

AC220-240V
~50Hz 135C
S5
BLU

L L t

N N
SA
EARTH
GRN/YLW
RED

BLU

YLW YLW S3
PNK MRC
YLW
1 5 A1 K1M X11A MRRL
C11R,C12R : RUNNING CAPACITOR MRRH
2 6 A2 GRN/YLW
F1U,F2U : FUSE RTH1 MRCC
BRN

K1M : COMPRESSOR RELAY MRCW


BLU

K1R : RELAY C11R t S7 MR2


L : LIVE MR1
RED

M1C : COMPRESSOR MOTOR


BLK

BLK
BRN

BRN

ORG
GRY

RED
BLU
PPL
YLW

M1F : FAN MOTOR C12R


BRN

BRN

MR : MAGNETIC RELAY t t X12A


N : NEUTRAL S R2T R1T
C R X10A
WHT
BLK

PCB : PRINTED CIRCUIT BOARD


ORG
RED

M
R1T,R2T : THERMISTOR 1~
WHT
BLU
BLU

BLK
BLU
BLU
YLW
BLK

RTH1 : THERMISTOR ON PCB X14A


S1~S7 : CONNECTOR ON PCB M1C Y1S Y1R Y2S
SA : SURGE ARRESTER
T1R : TRANSFORMER 7 8 M
K1R 1~ M1F
X1M : TERMINAL STRIP BLU
X10A~X14A : CONNECTOR 1 5
Y1R : REVERSING SOLENOID VALVE
3D028081
Y1S,Y2S : SOLENOID VALVE

8 Room Air Conditioners GA-Series


ED01-214A Piping Diagrams

6. Piping Diagrams
6.1 Heat Pump
6.1.1 Indoor Unit

FTY50GAV1A / FTY60GAV1A

INDOOR UNIT

HEAT EXCHANGER

THERMISTOR
ON HEAT EXCH.

FIELD PIPING
(6.4CuT) CROSS FLOW FAN

FAN MOTOR

FIELD PIPING
(15.9CuT)

REFRIGERANT FLOW

COOLING
HEATING 4D003943A

6.1.2 Outdoor Unit

RY50GAV1A

OUTDOOR UNIT

OUTDOOR TEMPERATURE
HEAT THERMISTOR
HEAT EXCHANGER
EXCHANGER
THERMISTOR

CAPILLARY TUBE(1) ONE WAY VALVE

CAPILLARY TUBE(2)

CAPILLARY TUBE(3)
M FAN MOTOR

PROPELLER
FAN FILTER LIQUID LINE
STOP VALVE
(6.4CuT)
FIELD
PIPING
(15.9CuT)
4-WAY VALVE
GAS LINE STOP VALVE
WITH SERVICE PORT
CAPILLARY
SV TUBE(6)

SOLENOID
VALVE

REFRIGERANT FLOW
ACCUMULATOR
COOLING
ACCUMULATOR
HEATING
FLOW DIRECTION
COMPRESSOR

C : 3D028561

Room Air Conditioners GA-Series 9


Piping Diagrams ED01-214A

RY60GAV1A

OUTDOOR UNIT

OUTDOOR TEMPERATURE
HEAT THERMISTOR
EXCHANGER HEAT EXCHANGER
THERMISTOR

CAPILLARY TUBE(1) ONE WAY VALVE

CAPILLARY TUBE(2)

CAPILLARY TUBE(3)
M FAN MOTOR

PROPELLER
FAN SOLENOID LIQUID LINE
SV VALVE (6.4CuT)
STOP VALVE FIELD
PIPING
FILTER (15.9CuT)

4-WAY VALVE GAS LINE STOP VALVE


WITH SERVICE PORT
CAPILLARY
SV TUBE(6)

SOLENOID
VALVE

REFRIGERANT FLOW
ACCUMULATOR
COOLING
ACCUMULATOR
HEATING

COMPRESSOR FLOW DIRECTION

C : 3D028562

10 Room Air Conditioners GA-Series


ED01-214A Capacity Tables

7. Capacity Tables
7.1 Heat Pump

FTY50GAV1A + RY50GAV1A 230-240V 50Hz


Cooling
AFR 14.0
BF 0.26

INDOOR OUTDOOR TEMPERATURE(CDB)


EWB EDB 20 25 32 35 40 46
C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 4.99 3.35 1.63 4.85 3.28 1.75 4.62 3.17 1.91 4.51 3.13 1.98 4.32 3.05 2.10 4.07 2.96 2.25
16.0 22 5.30 3.41 1.66 5.14 3.34 1.78 4.90 3.23 1.95 4.79 3.19 2.02 4.58 3.11 2.14 4.32 3.02 2.30
18.0 25 5.61 3.47 1.68 5.44 3.40 1.81 5.18 3.29 1.99 5.06 3.25 2.06 4.84 3.17 2.19 4.56 3.08 2.35
19.0 27 5.77 3.50 1.69 5.59 3.43 1.83 5.32 3.32 2.00 5.20 3.28 2.08 4.97 3.20 2.21 4.68 3.11 2.39
22.0 30 6.24 3.59 1.72 6.05 3.52 1.87 5.75 3.41 2.06 5.61 3.37 2.14 5.36 3.29 2.28 5.05 3.20 2.45
23.0 32 6.40 3.62 1.73 6.20 3.55 1.89 5.89 3.44 2.08 5.75 3.40 2.16 5.49 3.32 2.30 5.17 3.23 2.48

Heating
AFR 16.3

INDOOR OUTDOOR TEMPERATURE(CWB)


EDB -10 -5 0 6 10 15
C TC PI TC PI TC PI TC PI TC PI TC PI
16.0 3.97 1.25 4.60 1.41 5.28 1.58 6.15 1.82 6.83 1.99
18.0 3.96 1.29 4.59 1.45 5.26 1.62 6.12 1.86 6.79 2.03
20.0 3.94 1.33 4.58 1.49 5.24 1.66 6.07 1.92 6.74 2.06 7.59 2.26
21.0 3.93 1.35 4.58 1.51 5.23 1.68 6.06 1.93 6.73 2.08 7.58 2.28
22.0 3.92 1.37 4.57 1.53 5.22 1.70 6.05 1.95 6.71 2.10 7.55 2.30
24.0 3.91 1.41 4.55 1.57 5.20 1.74 6.02 1.98 6.67 2.14 7.50 2.34
26.0 3.90 1.42 4.53 1.61 5.18 1.78 5.98 2.02 6.63 2.18 7.46 2.38
28.0 3.89 1.49 4.51 1.65 5.16 1.82 5.94 2.06 6.59 2.22 7.42 2.42
3D029052

Symbols NOTES:
AFR : Air flow rate (m/min.) 1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat.
BF : Bypass factor 2. shows nominal capacities and power input.
EWB : Entering wet bulb temp. (C) 3. TC,PI and SHC must be calculated by interpolation using the figures
in the above tables. (Figures out of the tables should not be used for
EDB : Entering dry bulb temp. (C) calculation.)
TC : Total capacity (kW) 4. SHC is based on each EWB and EDB.
SHC=SHC correction for other dry bulb.
SHC : Sensible heat capacity (kW) =0.3460AFR(m/min.)(1-BF)(DB-EDB)
PI : Power input (kW) Add SHCTO SHC.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m at <AS / NZS3823.1>
Level difference : 0m
6. Maximum entering air temp. to condenser is 46C (115F)
7. Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Room Air Conditioners GA-Series 11


Capacity Tables ED01-214A

FTY60GAV1A + RY60GAV1A 230-240V 50Hz


Cooling
AFR 14.0
BF 0.22

INDOOR OUTDOOR TEMPERATURE(CDB)


EWB EDB 20 25 32 35 40 46
C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 5.97 3.95 1.71 5.77 3.87 1.89 5.46 3.77 2.18 5.32 3.72 2.32 5.08 3.65 2.54 4.77 3.56 2.82
16.0 22 6.32 4.01 1.75 6.11 3.93 1.94 5.79 3.83 2.24 5.64 3.78 2.37 5.39 3.71 2.60 5.06 3.62 2.89
18.0 25 6.69 4.07 1.79 6.47 3.99 1.99 6.13 3.89 2.29 5.98 3.84 2.43 5.71 3.77 2.66 5.36 3.68 2.96
19.0 27 6.88 4.10 1.81 6.66 4.02 2.01 6.31 3.92 2.32 6.15 3.87 2.46 5.87 3.80 2.70 5.51 3.71 2.99
22.0 30 7.47 4.19 1.88 7.23 4.11 2.09 6.86 4.01 2.41 6.68 3.96 2.56 6.38 3.89 2.81 5.99 3.80 3.10
23.0 32 7.87 4.25 1.93 7.62 4.17 2.14 7.24 4.07 2.47 7.05 4.02 2.62 6.73 3.95 2.86 6.32 3.86 3.17

Heating
AFR 16.3

INDOOR OUTDOOR TEMPERATURE(CWB)


EDB -10 -5 0 6 10 15
C TC PI TC PI TC PI TC PI TC PI TC PI
16.0 4.17 4.22 5.10 2.11 6.07 2.22 7.24 2.35 8.04 2.44
18.0 4.11 4.16 5.06 2.16 6.03 2.27 7.21 2.40 8.00 2.49
20.0 4.05 4.10 5.02 2.20 5.98 2.32 7.16 2.47 7.95 2.55 8.95 2.69
21.0 4.04 4.09 5.01 2.22 5.97 2.34 7.15 2.49 7.94 2.57 8.92 2.71
22.0 4.02 4.07 4.99 2.26 5.95 2.38 7.13 2.51 7.91 2.61 8.87 2.75
24.0 3.97 4.02 4.94 2.32 5.90 2.43 7.08 2.58 7.85 2.67 8.83 2.81
26.0 3.91 3.96 4.89 2.37 5.85 2.50 7.04 2.64 7.79 2.74 8.79 2.89
28.0 3.86 3.91 4.84 2.42 5.79 2.56 7.00 2.71 7.73 2.81 8.75 2.96
3D029054

Symbols NOTES:
AFR : Air flow rate (m/min.) 1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat.
BF : Bypass factor 2. shows nominal capacities and power input.
EWB : Entering wet bulb temp. (C) 3. TC,PI and SHC must be calculated by interpolation using the figures
in the above tables. (Figures out of the tables should not be used for
EDB : Entering dry bulb temp. (C) calculation.)
TC : Total capacity (kW) 4. SHC is based on each EWB and EDB.
SHC=SHC correction for other dry bulb.
SHC : Sensible heat capacity (kW) =0.3460AFR(m/min.)(1-BF)(DB-EDB)
PI : Power input (kW) Add SHCTO SHC.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m at <AS / NZS3823.1>
Level difference : 0m
6. Maximum entering air temp. to condenser is 46C (115F)
7. Air flow rate (AFR) and Bypass factor (BF) are taburated above.

12 Room Air Conditioners GA-Series


ED01-214A Capacity Tables

7.2 Capacity Correction Factor by the Length of Refrigerant Piping (Reference)


The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The
distance between the indoor unit and the outdoor unit)
Split system <line: For the indoor unit with capacity of 5.0 kW or more.>
Cooling Capacity

Note: The capacity in the range of the refrigerant additional charge shows when the additional refrigerant is
charged properly.

Room Air Conditioners GA-Series 13


Operation Limit ED01-214A

8. Operation Limit
8.1 Heat Pump

RY50GAV1A / RY60GAV1A
Cooling Heating
(50Hz)
50

46 20

40 15

Outdoor temp. (CWB)


Outdoor temp. (CDB)

Continuous operation

10
Pull-down period

Continuous operation
30
5

Warming up period
20 0
19.4

0 -10
(-10CDB)

10 14 20 23 28 30 10 14 20 28 30
Indoor temp. (CWB) Indoor temp. (CDB)

Notes:
The graphs are based on the following conditions.
Equivalent piping length 5m
Level difference 0m
Air flow rate High 3D006204B

14 Room Air Conditioners GA-Series


ED01-214A Sound Level

9. Sound Level
9.1 Overall Sound Level
9.1.1 Indoor Units (dBA)

220-240V (50Hz) Measuring Location


Model Cooling Heating
H L H L
1m
FTY50GAV1A 45 35 44 33

0.8m
FTY60GAV1A 46 37 46 34

9.1.2 Outdoor Units (dBA)

220-230-240V (50Hz) Measuring Location


Model
Cooling Heating

1m
RY50GAV1A 49-50-50 51-52-52

RY60GAV1A 54-56-56 54-56-56

Note: 1. Operation sound is measured in an anechoic chamber.


2. The data are based on the conditions shows in the table below.
Standard Cooling Heating Piping Length

JIS C9612 Indoor ; 27CDB/19CWB Indoor ; 20CDB 5m


Outdoor ; 35CDB/24CWB Outdoor ; 7CDB/6CWB

Room Air Conditioners GA-Series 15


Sound Level ED01-214A

9.2 Octave Band Level


9.2.1 Indoor Units
FTY50GAV1A (Cooling) FTY50GAV1A (Heating)
50Hz 240V(H) 50Hz 240V(H)
50Hz 240V(L) 50Hz 240V(L)
70 70
OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL


NC-60 NC-60
60 60

NC-50 NC-50
dB(0dB=0.0002 bar)

dB(0dB=0.0002bar)
50 50

NC-40 NC-40
40 40

NC-30 NC-30
30 30

NC-20 NC-20
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
3D005357A 3D005357A

FTY60GAV1A (Cooling) FTY60GAV1A (Heating)


50Hz 240V(H) 50Hz 240V(H)
50Hz 240V(L) 50Hz 240V(L)
70 70
OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

NC-60 NC-60
60 60

NC-50 NC-50
50 50
dB(0dB=0.0002bar)

dB(0dB=0.0002bar)

NC-40 NC-40
40 40

NC-30 NC-30
30 30

NC-20 NC-20
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
3D005359A 3D005359A

16 Room Air Conditioners GA-Series


ED01-214A Sound Level

9.2.2 Outdoor Units


RY50GAV1A (Cooling) RY50GAV1A (Heating)
50Hz 220V(H) 50Hz 220V(H)
50Hz 240V(L) 50Hz 240V(L)
70 70
OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL


NC-60 NC-60
60 60

NC-50 NC-50

dB(0dB=0.0002 bar)
dB(0dB=0.0002bar)

50 50

NC-40 NC-40
40 40

NC-30 NC-30
30 30

NC-20 NC-20
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
3D028537 3D028537

RY60GAV1A (Cooling) RY60GAV1A (Heating)


50Hz 220V(H) 50Hz 220V(H)
50Hz 240V(L) 50Hz 240V(L)
70 70
OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

NC-60 NC-60
60 60

NC-50 NC-50
dB(0dB=0.0002bar)

dB(0dB=0.0002bar)

50 50

NC-40 NC-40
40 40

NC-30 NC-30
30 30

NC-20 NC-20
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
3D028538 3D028538

Room Air Conditioners GA-Series 17


Electric Characteristics ED01-214A

10. Electric Characteristics


10.1 Electric Characteristics
Representative Unit Combination Power Supply COMP OFM IFM
Indoor Unit Outdoor Unit Hz-Volts Voltage Range MCA MFA LRA RLA W FLA W FLA
50Hz - 220V MAX. 50Hz 264V 36.5 8.70 0.24
FTY50GAV1A RY50GAV1A 50Hz - 230V MIN. 50Hz 198V 13.2 20 38.0 9.23 35 0.40 54 0.23
50Hz - 240V 40.0 9.75 0.21
50Hz - 220V MAX. 50Hz 264V 55 9.90 0.24
FTY60GAV1A RY60GAV1A 50Hz - 230V 13.7 20 57.5 9.73 53 0.70 54 0.23
MIN. 50Hz 198V
50Hz - 240V 60 9.55 0.21

SYMBOLS: NOTES:
MCA : MIN. CIRCUIT AMPS (A) 1. RLA is based on the following conditions.
Indoor temp. 27CDB/19CWB
MFA : MAX. FUSE AMPS (A) Outdoor temp. 35CDB.
LRA : LOCKED ROTOR AMPS (A) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
RLA : RATED LOAD AMPS (A) 4. Instead of fuse, use circuit breaker.
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)
3D029053
3D029055

18 Room Air Conditioners GA-Series


ED01-214A Installation Manual

11. Installation Manual


11.1 FTY50 / 60GA

SAFETY PRECAUTIONS
Read these SAFETY PRECAUTIONS carefully to ensure correct installation.
This manual classifies the precautions into WARNINGS and CAUTIONS.
Be sure to follow all the precautions below: they are all important for ensuring safety.
WARNINGS Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTIONS Failure to follow any of CAUTION may in some cases result in grave consequences.
The following safety symbols are used throughout this manual:

Be sure to observe this instruction. Be sure to establish an earth connection. Never attempt.

After completing installation, test the unit to check for installation errors. Give the user adequate instructions
concerning the use and cleaning of the unit according to the Operation Manual.

WARNINGS
Installation should be left to the dealer or another professional.
Improper installation may cause water leakage, electrical shock, or fire.
Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, or fire.
Be sure to use the supplied or specified installation parts.
Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire.
Install the air conditioner on a solid base that can support the units weight.
An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring
rules or code of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
For wiring, use a cable long enough to cover the entire distance with no connection.
Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock or fire.)
Use the specified types of wires for electrical connections between the indoor and outdoor units.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.
After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the
electrical covers or panels. Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.
When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified
refrigerant (R22), such as air. (Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)
The unit is out of reach of children at least 1.8m above the floor.
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)
After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)

Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.
Incomplete earth may cause electrical shock. A high surge current from lightning or other sources may cause damage to the air conditioner.

An earth leakage circuit breaker may be required depending on site condition to prevent electrical shock.
Failure to do so may cause electrical shock.

CAUTIONS
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.
Establish drain piping according to the instructions of this manual.
Inadequate piping may cause flooding.
Note for installing the outdoor unit. (For heat pump model only.)
In cold area where the outside air temperature keep below or around freezing-point for a few days, the outdoor units drain may freeze.
If so, it is recommended to install an electric heater in order to protect drain from freezing.

Room Air Conditioners GA-Series 19


Installation Manual ED01-214A

ACCESSORIES
A Mounting plate 1 E Remote controller holder 1 J Insulation tape 1
B Mounting plate fixing screw F Fixing screw for remote controller
M4 X 25L
10 holder M3 X 20L
2 K Operation manual 1

C Air purifying filter 2 G AAA dry-cell batteries 2 L Installation manual 1


H Indoor unit fixing screw
D Wireless remote controller 1 M4 X 12L
2

CHOOSING A SITE
Before choosing the installation site, obtain user approval.
Indoor unit Outdoor unit
The indoor unit should be sited in a place where: The outdoor unit should be sited in a place where:
the restrictions on installation specified in the the restrictions on installation specified in the outdoor unit installation diagram are
indoor unit installation drawings are met, met,
both air intake and exhaust have clear paths met, drain water causes no trouble or problem in particular,
the unit is not in the path of direct sunlight, both air intake and exhaust have clear paths of air (they should be free of snow in
the unit is away from the source of heat or steam, snowy districts),
there is no source of machine oil vapour (this may the unit is in a clear path of air but not directly exposed to rain, strong winds, or direct
shorten indoor unit life), sunlight,
cool (hot) air is circulated throughout the room, there is no fear of inflammable gas leakage,
the unit is away from electronic ignition type the unit is no directly exposed to salt, sulfidized gases, or machine oil vapour (they
fluorescent lamps (inverter or rapid start type) as may shorten outdoor unit life).
they may shorten the remote control range, operation noise or hot (cold) air flow does not cause trouble to neighbours, and
the unit is at least 1 metre away from any television the unit is at least 3 metres away from any television or radio antenna.
or radio set (unit may cause interference with the
picture or sound). Wireless Remote Controller
Turn on all the fluorescent lamps in the room, if any, and find the site where remote
control signals are properly received by the indoor unit (within 7 metres).

INSTALLATION TIPS
* The pipe port for left-side piping or in-wall piping can be * The removed pipe port cover can be Removed
accessed by removing the bottom cover from the bottom frame. kept in the mounting plate pocket. pipe port
cover
For easier piping work, you may
want to cut this bar away.
Cut here. Interconnecting wires Cut here.

C Mounting plate

Drain
hose A Mounting plate
Caulk this hole * When filling additional refrigerant, see the
with putty or
caulking material. Wrap insulating tape to the bent
Bind with plastic tape. portion of refrigerant pipe while
"INDOOR/OUTDOOR UNIT INSTALLATION DRAWINGS".
making a half lap or greater. * Be sure to use the vacuum pump for air purging.
Bottom cover
* When two indoor units are installed in one room, the two
* Indoor unit's lift from mounting plate surface is eliminated wireless remote controllers can be easily set for different
by screwing the bottom frame to the mounting plate. addresses.
* Indoor unit's terminal block can be accessed for wiring
just by removing the front grille (without having to remove
the front panel). J4
Wireless
remote
controller

J4 ADDRESS
EXIST 1 ADDRESS J2/JA
CUT 2 EXIST 1
CUT 2

20 Room Air Conditioners GA-Series


ED01-214A Installation Manual

INDOOR/OUTDOOR UNIT INSTALLATION DRAWINGS


A Mounting plate
The mounting plate should be installed
on a wall which can support the weight
of the indoor unit.
B M4X25L

indicates recommended spot for


attaching screws.

30 mm or more from ceiling

Front grille Cut thermal insulation pipe to an


appropriate length and wrap it with
tape, making sure that no gap is left
in the insulation pipes cut line.
50 mm or more from walls Caulk pipe Wrap the insulation
(on both sides) hole gap pipe with the finishing
Service lid with putty. tape from bottom to top.

Before screwing the remote


controller holder to the wall,
D Wireless make sure that control signals are
remote controller properly received by indoor unit.

E
Service lid
Remote
1 Insert. controller holder
Stop valve cover

F 250 mm
(M3 X 20L) from w
all

In sites with poor drainage, use block e


Z hol
bases for outdoor unit. olt- Allow space for piping
Adjust foot height until the unit is oot b res and electrical servicing.
F nt
leveled. Otherwise, water leakage
X ce
or pooling of water may occur. (Foot b
olt-hole Y
centres Where there is a danger of the
) (F unit falling, use foot bolts, or wires.
rom un
it's side
)

Heat pump Cooling only


Model RY50G RY60G R50G R60G

Max. allowable length 30 m


Max. allowable height 15 m
Additional refrigerant
required for pipe 30g/m 60g/m 20g/m
exceeding 10 m in
length.

X 540mm 500mm 530mm 540mm

Y 130mm 177mm 100mm 130mm

Z 330mm 370mm 290mm 330mm

Gas pipe O.D. 15.9 mm

Liquid pipe O.D. 6.4 mm


* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.

Room Air Conditioners GA-Series 21


Installation Manual ED01-214A

INDOOR UNIT
Outdoor Unit Installation Guidelines
Where a wall or other obstacle is in the path of outdoor
1 INSTALLING THE MOUNTING PLATE
units intake or exhaust airflow, follow the installation The mounting plate should be installed on a wall which can support the weight of the indoor unit.
guidelines below. (1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely
level, and mark the boring points on the wall.
Wall facing one side Walls facing two sides (2) Secure the mounting plate to the wall with screws.

More than
Details of Mounting Plate and Dimensions Leveling mounting plate
Dangle a weighted thread
A
More than a and align thread with (Bolt size : M10)
B Use tape measure as shown vertical arrow.
70 Place a leveler 125
Position the end of tape b
on raised tab.
measure at
Exhaust

40

40
More than
Side view C Top view

299

130
Walls facing three sides

75
More than
E

52
52
More than
D More than 75 105 Gas pipe end
H 389 53 80 137
Liquid pipe end
1050
More than
More than E Through-the-wall Keep here the piece cut out from the unit for piping
F hole 80mm Recommended mounting-plate
Drain hose position retention spots (8 spots in all) (unit: mm)
Top view Side view

(mm) (mm)
2 BORING A WALL HOLE AND INSTALLING WALL EMBEDDED PIPE
For walls containing metal frame or metal board, be sure to use a wall embedded pipe and
A B C D E F note 1 wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
H 1000 350 Be sure to caulk the gaps around the pipes with caulking Inside Outside
Wall embedded pipe
RY50G 50 50 100 50 100 50 material to prevent water leakage. (field supply)
Caulking
H 1000 600 (1) Bore a feed-through hole of 80mm in the wall so
RY60G 100 100 100 100 note 1 100 it has a down slope toward the outside.
(2) Insert a wall pipe into the hole. 80
note 2 Wall hole cover
(3) Insert a wall cover into wall pipe. (field supply)
R50G 50 100 50 150 note 2 50
H 1000 300 (4) After completing refrigerant piping, wiring, and drain Wall embedded pipe
(field supply)
piping, caulk pipe hole gap with putty.
R60G 50 100 50 150 note 2 50 H 1000 600

3 INSTALLING INDOOR UNIT


Installing Air Purifying Filter Right-Side, Right-Back, or Right-Bottom Piping

(1) Attach the drain hose to the underside of the


(1) Open front grille. refrigerant pipes with adhesive vinyl tape.
(2) Wrap the refrigerant pipes and drain hose
(2) Remove air filters.
together with insulation tape. Right-back piping
(3) Install air purifying filter into its frame Remove pipe port cover
Bind coolant pipe and
here for right-side piping
and install it on air filter. Right-bottom piping drain hose together with
insulating tape.
Remove pipe port cover here for right-bottom piping
(4) Install air filters on indoor unit.
(5) Stick the Electrostatic Filter Mounting plate
Instruction Label on the back (3) Pass the drain hose and refrigerant pipes through
of the grille. Air filter
the wall hole, then set the indoor unit on the
C Air purifying filter mounting plate hooks by using the markings at
the top of the indoor unit as a guide.

22 Room Air Conditioners GA-Series


ED01-214A Installation Manual

Inner wall
Insert drain hose to this
(4) Open the front grille, then open the service lid. Wall Embedded Piping depth so it wont be
pulled out of drain pipe.
Service
Hook Follow the instructions given under
Left-Side, Left-Back, or Left Bottom Piping . 50 mm Drain hose
or more
(1) Insert the drain hose to this depth so it wont be Vinyl chloride
drain pipe
pulled out of the drain pipe. Outer wall (VP-30)

4 WIRING
(1) Strip wire ends (15 mm).
(5) Pass the interconnecting wires from the outdoor unit
(2) Match wire colours with terminal numbers on indoor and outdoor units' terminal blocks and
through the feed-through wall hole and then through the Hang indoor unit's hook here.
firmly screw wires to the corresponding terminals.
back of the indoor unit. Pull them through the front side.
(3) Connect the earth wires to the corresponding terminals.
Bend the ends of tie wires upward in advance for easier
work. (If the interconnecting wire ends are to be stripped
first, bundle wire ends with adhesive tape.) Terminal block
(6) Press the indoor units bottom panel with both hands Electrical component box

to set it on the mounting plate hooks. Make sure the When stripping the
ends of interconnecting
Wire retainer
Interconnecting Firmly secure wire retainer so that wires
wires do not catch on the edge of the indoor unit. wires in advance, bind wires sustain no external stress.
right ends of wires with Wire guide
insulating tape.
Shape wires so that the service
lid will fit securely. Use the specified wire type.
Left-Side, Left-Back, or Left Bottom Piping
(1) Attach the drain hose to the underside of (4) Pull wires to make sure that they are securely latched up, then retain wires with wire retainer.
the refrigerant pipes with adhesive vinyl tape. Remove pipe
port cover here (5) Shape the wires so that the service lid fits securely, then close service lid.
for left-side
piping

Left-side
piping
Remove pipe port cover here for left-bottom piping Left-back
Warning
Outdoor unit
piping Do not use tapped
Left-bottom piping Firmly fix the wires with the terminal screws. 1 23 LN
The earth leakage circuit wires,stand wires,
When wire length exceeds
(2) Be sure to connect the drain hose to the drain How to set drain plug 10 m, use 2.0-mm wires.
breaker is required depending
on site environment.
extensioncords, or
port in place of a drain plug. starbust connections,
ap as they may cause
No g Do not apply lubricating
Indoor
unit
1
2
Safety Earth leakage Power overheating, electrical
oil (refrigerant machine breaker circuit breaker supply
3 20A shock,or fire.
oil) when inserting 50Hz 220-240V
H05VV 60Hz 220-230V
Application of causes Firmly fix the wires with the terminal screws. Earth
deterioration and drain
leakage of the plug
Insert a hexagon wrench (4 mm)

(3) Shape the refrigerant pipe along the pipe path marking on the mounting plate. 5 DRAIN PIPING
(4) Pass drain hose and refrigerant pipes through the wall hole, then set the indoor unit on Connect the drain hose, as described below Remove the air filters and pour some
mounting plate hooks, using the markings at the top of indoor unit as a guide. The drain hose should water into the drain pan to check
(5) Pull in the interconnecting wires. be inclined downward.
the water flows smoothly.
(6) Remove the bottom cover and cut the bar away to gain better access for piping work.
For easier piping work, you may
Cut here. want to cut this bar away. Cut here. No trap is permitted.
Interconnecting wires
Do not put the end
of the hose in water.

Drain
hose
(A) Mounting plate
When drain hose requires extension, obtain Indoor unit Extension drain hose
Caulk this hole drain hose
with putty or Wrap insulating tape around the bent portion of refrigerant pipe.
an extension hose commercially available.
caulking material. Bottom cover Bind with plastic tape. Overlap at least half the width of the tape with each turn. Be sure to thermally insulate the indoor
section of the extension hose. Heat insulation tube
(Field supply)
(7) Wrap the refrigerant pipes and drain hose together with Drain hose
insulation tape. When connecting a rigid polyvinyl chloride pipe (nominal diameter 13 mm) directly to the drain
(8) While exercising care so that the interconnecting wires hose attached to the indoor unit as with embedded piping work, use any commercially available
do not catch indoor unit, press the bottom edge of indoor drain socket (nominal diameter 13 mm) as a joint.
unit with both hands until it is firmly caught by the
mounting plate hooks. Secure indoor unit to the
Commercially available Commercially available rigid
mounting plate with screws (M4 x 12L). Hitch indoor unit to
Drain hose supplied with
the indoor unit drain socket polyvinyl chloride pipe
this hook (3 hooks). M4 x 12L (nominal diameter 13 mm) (nominal diameter 13 mm)

Room Air Conditioners GA-Series 23


Installation Manual ED01-214A

OUTDOOR UNIT
1 INSTALLING OUTDOOR UNIT 4 PURGING AIR AND CHECKING GAS LEAKAGE
For outdoor unit installation, see CHOOSING A SITE , Outdoor unit Warning Warning
and INDOOR/OUTDOOR UNIT INSTALLATION DRAWINGS . Do not mix any substance other than the specified Refrigerant gas leaks during air purging, ventilate
refrigerant (R22) into the refrigeration cycle. the room as soon as possible.

2 FLARING THE PIPE END To prevent air pollution, a vacuum pump should be used for air purging wherever possible.

1. Cut the pipe end with a pipe cutter. Compound Pressure meter
(Cut exactly at If using additional refrigerant, perform air purging from
2. Remove burrs with the cut surface facing downward right angles.) Remove burrs
pressure gauge
the refrigerant pipes and indoor unit using a vacuum
so that the chips do not enter the pipe. Flaring
Gauge
pump, then charge additional refrigerant. manifold
3. Put the flare nut on the pipe. Set exactly at the position shown below.
A A Use a hexagonal wrench (4 mm) to operate the shut-off valve rod. High-pressure Liquid
4. Flare the pipe.
RIGID 0.5 mm All refrigerant pipe joints should be tightened with a torque valve Valve lids shut-off
5. Check that the flaring is properly made. Low-pressure valve
Die IMPERIAL 1.0 mm wrench at the specified tightening torque. valve
Check Charging
Warning The pipe end must hoses Gas
Flare's inner surface be evenly flared in
Incomplete flaring may cause refrigerant gas leakage. must be flaw-free. shut-off
a perfect circle.
Vacuum pump Service port valve
Make sure that the *1. Pipe length vs. vacuum pump run time
flare nut is fitted. *2. If the compound pressure gauge pointer swings back, refrigerant
Pipe length Up to 15 metres More than 15 metres may have water content or a loose pipe joint may exists. Check
all pipe joints and retighten nuts as needed, then repeat steps (2)
Run time Not less than 10 min. Not less than 15 min. through (4).

3 REFRIGERANT PIPING
(1) Connect projection side (on which worm pin is pressed) of charging hose (which comes from gauge manifold) to
1. Align the centres of both flares and tighten the flare Flare nut tightening torque gas shut-off valve's service port.
Gas side(5/8 inch) Liquid side(1/4 inch)
nuts 3 or 4 turns by hand. Then tighten them fully
6180~7540Ncm 1420~1720Ncm
with the torque wrenches. (630~770kgfcm) (144~176kgfcm) (2) Fully open gauge manifold's low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
Use torque wrenches when tightening the flare nuts to (High-pressure valve subsequently requires no operation.)
prevent damage to the flare nuts and escaping gas. Valve cap tightening tolque

2. To prevent gas leakage, apply refrigeration machine 2740~3340Ncm


(279~341kgfcm)
oil on both inner and outer surfaces of the flare. (3) Do vacuum pumping and make sure that the compound pressure gauge reads -0.1MPa (-76 cmHg)*1.

Cautions on Pipe Handling (4) Close gauge manifold's low-pressure valve (Lo) and stop vacuum pump.
Protect the open end of the pipe against Wall (Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.
Be sure to
dust and moisture. place a cap.
Rain
All pipe bends should be as gentle as If no flare cap is (5) Remove covers from liquid shut-off value and gas shut-off valve.
possible. Use a pipe bender for bending. available, cover
the flare mouth
(Bending radius should be 30 to 40 mm or larger.) with tape to keep
dirt or water out.
(6) Turn the liquid shut-off valves rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit's flare and outdoor unit's flare and valve rods.
Selection of Copper and Heat Insulation materials After the check is complete, wipe all soapy water off.

When using commercial copper pipes and fittings, observe the following:
Insulation material: Polyethylene foam (7) Disconnect charging hose from gas shut-off valve's service port, then fully open liquid and gas shut-off valves.
Heat transfer rate: 0.041 to 0.052kW/mK (0.035 to 0.045 kcal/mhC) (Do not attempt to turn valve rod beyond its stop.)
Refrigerant gas pipe's surface temperature reaches 110C max.
Choose heat insulation materials that will withstand this temperature.
(8) Tighten valve lids and service port caps for the liquid and gas shut-off valves with a torque wrench at the specified torques.
Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation
O.D. 15.9mm
Thickness 1.0mm
O.D. 6.4mm
Thickness 0.8mm
I.D. 16-20mm
Thickness 10mm Min.
I.D. 8-10mm
Thickness 10mm Min.
5 WIRING
For interconnecting wire connections, see INDOOR UNIT , 4. WIRING .
Use separate thermal insulation pipes for gas and liquid Gas pipe Firmly tighten terminal Terminal block
Inter-unit wiring
refrigerant pipes. screws.
Supply Interconnecting wire
Firmly secure wire
retainer so wire
Liquid pipe
For wire termination at terminal block terminal block teminations will
terminal block, see the Wire not receive
figure at right. external stress.
For wire stripping, see
the figure at rigth. Use the specified
wire type for all
connecitions.
Gas pipe Wire retaine
insulation Liquid pipe Strip wire and this point.
insulation Excessive strip length may cause
Finishing tape Drain hose electrical shock or leskage. Shape wires so that the
service lid fits securely.
Be sure to estabish. Do not earth the utiilty pipe, arrester, or telephone earth.

24 Room Air Conditioners GA-Series


ED01-214A Installation Manual

6 DRAIN WORK
If the drain port is covered by a mounting base or floor surface, place additional foot bases
of at least 30 mm in height under the outdoor unit's feet.
In cold areas, do not use a drain hose with the outdoor unit. (Otherwise, drain water may
freeze, impairing heating performance.)

TRIAL OPERATION AND TESTING


Trial Operation and Testing
(1) Measure the supply voltage and make sure that it falls in the specified range.
(2) Trial operation should be carried out in either cooling or heating mode.

For Heat pump


In cooling mode, select the lowest programmable temperature; in heating mode, select the
highest programmable temperature.
Trial operation may be disabled in either mode depending on the room temperature.
After trial operation is complete, set the temperature to a normal level
(26 to 28C in cooling mode, 20 to 24C in heating mode).
For protection, the system disables restart operation for 3 minutes after it is turned off.
For Cooling-Only
Select the lowest programmable temperature.
Trial operation in cooling mode may be disabled depending on the room temperature.
Use the remote control for trial operation as described below.
Trial operation from Remote Controller
(1) Press ON/OFF button to turn on the system.
(2) Simultaneously press center of TEMP. and MODE buttons.
(3) Press MODE button twice.
(" " will appear on the display to indicate that Trial Operation mode is selected.)
(4) Trial run mode terminates in approx. 15 minutes and switches into normal mode. To quit a trial operation,
press ON/OFF button.

After trial operation is complete, set the temperature to a normal level (26 to 28C).
For protection, the unit disables restart operation for 3 minutes after it is turned off.
(3) Carry out the test operation in accordance with the Operation Manual to ensure that
all functions and parts, such as louver movement, are working properly.
* The air conditioner requires a small amount of power in its standby mode. If the system
is not to be used for some time after installation, shut off the circuit breaker to eliminate
unnecessary power consumption.
* Ifrestore
the circuit breaker trips to shut off the power to the air conditioner, the system will
the original operation mode when the circuit breaker is opened again.
Test Items
Symptom
Test Items (diagnostic display on RC) Check

Indoor and outdoor units are installed properly on solid bases. Fall, vibration, noise
No refrigerant gas leaks. Incomplete cooling/
heating function
Refrigerant gas and liquid pipes and indoor drain hose Water leakage
extension are thermally insulated.
Draining line is properly installed. Water leakage
System is properly earthed. Electrical leakage
The specified wires are used for interconnecting wire Inoperative or burn
connections. damage
Indoor or outdoor unit's air intake or exhaust has clear path of air. Incomplete cooling/
Shut-off valves are opened. heating function
Indoor unit properly receives remote control commands. Inoperative

1P064018-1B

Room Air Conditioners GA-Series 25


Operation Manual ED01-214A

12. Operation Manual


12.1 FTY50 / 60GA

Safety Precautions
Read the following warnings and cautions
carefully before operating the system and
WARNING
use it correctly. Failure to follow a warning is very likely to
This manual classifies the precautions to the result in such grave consequences as death or
serious injury.
user into two categories on the right.
Be sure to follow all as they are all important
to ensure safety. CAUTION
After reading this manual, keep it in a place Failure to follow a caution may result in
easily accessible to the user for future serious injury or property damage, and in
reference. certain conditions, may result in a grave
consequence.

WARNING
Do not expose your body to the cool (heat) air for a long time, do not cool (heat) the room too much.
It will affect your physical conditions and cause health problems.

Do not put a finger, a rod or other objects into the air outlet or inlet.
As the fan is rotating at a high speed, it will cause injury.

Do not attempt to repair, relocate, modify or reinstall the air conditioner by yourself.
Incorrect work will cause electric shocks, fire etc. For repairs and reinstallation, consult the shop
where you bought the air conditioner.

If anything abnormal such as a burning smell occurs, stop the operation immediately
and turn the breaker OFF.
Continued abnormal operation will cause troubles, electric shocks, fire etc. If anything is
abnormal, consult the shop where you bought the air conditioner.

If the air conditioner is not cooling or heating properly, the refrigerant may be leaking,
so see the dealer where the unit was purchased. Check with a qualified repairman
before attempting any repairs, which might accompany addition of refrigerant.
The refrigerant used in the air conditioner is safe. Although leaks should not occur, if for some
reason any refrigerant happens to leak into the room, make sure it does not come in contact with
any flame, such as fan heaters, kerosene heaters, or gas ranges, as this may result noxious
substances being generated.

CAUTION
Do not use the air conditioner for preservation purposes.
Do not use it for preserving precision instruments, foods, plants, animals, works of fine arts etc.
Performance or quality may deteriorate and animal or plant life may be shorter.

Do not operate the air conditioner with a wet hand.


It may cause an electric shock.

Ventilate the room from time to time.


Be careful especially when using a burning appliance in the same room. Insufficient ventilation
may cause shortage of oxygen.

Before cleaning, be sure to stop the operation and turn the breaker OFF.
As a fan is rotating at a high speed, cleaning during operation may cause injury.

After a long use, check the unit stand and fittings for damage.
The unit may drop and cause injury if damage is left unrepaired.

26 Room Air Conditioners GA-Series


ED01-214A Operation Manual

Do not stand or sit on the outdoor unit. Do not place any object on the unit.
The object or the person may fall down or drop, causing injury.

Do not place under the indoor or outdoor unit anything which must be kept away from moisture.
Indoor unit : moisture in the air may condense and drip in certain conditions.
outdoor : during cooling operation, condensation may drip from the piping connections.

Do not wash the unit with water.


It may cause an electric shock.

Do not place a burning appliance in places exposed to the air flow from the unit or
under the indoor unit.
It may cause incomplete combustion or deformation of the unit from heat.

Do not place a vessel containing water on the unit.


Water may penetrate into the unit and degrade electrical insulations, resulting in an electric shock.

Do not expose plants or animals directly to the air flow.


It may cause adverse effects on the plant or the animal.

Do not block air inlets nor outlets.


Impaired air flow may result in insufficient performance or troubles.

Do not allow children to mount on the outdoor unit or avoid placing any object on it.
Falling or tumbling may result in injury.

Installation
WARNING
Do not attempt to install the air conditioner by yourself.
Consult the service shop or a qualified technician.
Incorrect work will result in water leakage, electric shocks or fire. For installation, consult the
service shop where you bought the unit or a qualified technician.

The air conditioner must be earthed.


Incomplete earthing may result in electric shocks. Do not connect the earth line to a gas
pipe, water pipe, lightning rod, or a telephone earth line.

CAUTION
Depending on the environment, an earth leakage breaker must be installed.
Lack of an earth leakage breaker may result in electric shocks.

Do not install the air conditioner in places where flammable gas may leak.
If leaked gas should accumulate near the unit, fire may occur.

Arrange the drain hose to ensure smooth drainage.


Incomplete drainage may cause wetting of the building, furniture etc.

Do not connect the air conditioner to a power supply different from the specification.
It may cause trouble or fire.

Room Air Conditioners GA-Series 27


Operation Manual ED01-214A

Installation site
To install the air conditioner in the following types of environments, consult the shop.
Places with an oily ambient or where steam or soot occurs.
Salty environment such as coastal areas.
Places where sulfide gas occurs such as hot springs.
Places where snow may block the outdoor unit.
The drain from the outdoor unit must be discharged to a place of good drainage.

Consider nuisance to your neighbours from noises


For installation, choose a place as described below.
A place solid enough to bear the weight of the unit which does not amplify the
operation noise or vibration.
A place from where the air discharged from the outdoor unit or the operation noise
will not annoy your neighbours.

Electrical work
For power supply, be sure to use a separate power circuit dedicated to the air
conditioner.

System relocation
Relocating the air conditioner requires specialized knowledge and skills. Please
consult the shop where you bought the air conditioner if relocation is necessary for
moving or remodeling.

28 Room Air Conditioners GA-Series


ED01-214A Operation Manual

Names of Parts
Indoor unit
Air purifying filter Air inlet
Air purifying filters are
attached to the inside
of the air filters.
Front grille

Grille tab

DAIKIN

Diffuser

Air filter Louvre Air outlet Flap


(vertical blades) (Horizontal blade)
The louvre is inside of the air outlet. (See page 10.)
(See page 10.)
Indicator lamps

CLEANING lamp (red)


OPERATION lamp (green) Lights up when the air filters need cleaning.
(See page 13 Care and Cleaning.)

ON/OFF switch TIMER lamp (yellow)


(See page 12 Timer Operation.)

Control panel
Opening the front grille
Cleaning lamp
How to open the front grille : (See page 8.) reset button
Push this button
CAUTION to turn the
CLEANING lamp
Before opening the front grille, be sure to off.
stop the operation and turn the breaker
OFF. If the power is on, the fan may rotate
inside and may cause injury. Receiver:
It receives signals from the remote controller.
When the unit receives a signal, you will hear
a short beep.

Room temperature sensor:


It senses the air temperature around
the unit.

ON/OFF switch
Push this switch once to start operation. Push once again
to stop it.
The operation mode refer to the following table.
Mode Temperature setting Air flow rate
FT COOL 22C AUTO
FTY AUTO 25C AUTO
This switch is useful when the remote controller is missing.

Room Air Conditioners GA-Series 29


Operation Manual ED01-214A

Names of Parts
Remote controller
Transmitter
Display It sends signals to the indoor unit.
Open It displays the
the current settings.
cover. (In this illustration,
each section is
shown with all its
displays ON for the
ON
purpose of
explanation. Some
C
TEMPERATURE
models may not
adjustment buttons
show all its
indications.) It changes the temperature
setting.
AMPM AMPM
POWERFUL button
(See page 11 ON/OFF button
POWERFUL Operation) Press it once to start operation.
ON/OFF To stop it, press it once again.
MODE selector button POWERFUL TEMP
It selects the operation mode. FAN setting button
<FT> <FTY> It selects the air flow rate setting.
: DRY : AUTO MODE FAN SWING
: COOL : DRY SWING button
: FAN : COOL (See page 10 Adjusting the Air
: HEAT Flow Direction)
ON CANCEL
ON TIMER button TIMER CANCEL button
OFF
(See page 12 Timer Operation)
TIMER It cancels the timer setting.

OFF TIMER button


CLOCK button
(See page 8 Preparation
Before Operation - Setting
TIMER Setting button
the Clock)
It changes the time setting

<ARC423A17, ARC423A18>

Outdoor unit
Air inlet Earth terminal
(Back and side) It is inside of this part.

Air outlet Drain hose

Refrigerant piping
and inter-unit cable

30 Room Air Conditioners GA-Series


ED01-214A Operation Manual

Preparation Before Operation


Operating the remote controller
Remote controller
To use the remote controller, aim the transmitter at
Setting the batteries the indoor unit. If there is anything to block signals
between the unit and the remote controller, such as
a curtain, the unit will not operate.
Position + and Do not drop the remote controller. Do not get it wet.
correctly!
The maximum distance for communication is about
7 m.
2
+ +

3 Receiver

1
To fix the remote controller
holder on the wall
1 Choose a place from where the signals
reach the unit.
1 Press with a finger and slide the front
cover to take it off.
2 Fix the holder to a wall, a pillar, etc. with
the screws supplied with the holder.
2 Set two dry batteries (AAA). 3 Place the remote control in the remote
control holder.
3 Set the front cover as before.
This will cause the figures on the display
to flash. Set the clock at this point. Remote
controller
Set. holder

ATTENTION
About batteries
When replacing the batteries, use
batteries of the same type, and replace
To remove, pull it upwards.
the two old batteries together.
When the system is not used for a long
time, take the batteries out. ATTENTION
When the operation display screen of the About the remote controller
remote controller is hard to see and the Never expose the remote controller to
reception become hard, replace the direct sunlight.
batteries with new AAA batteries. Dust on the signal transmitter or receiver
The attached batteries are provided for the will reduce the sensitivity. Wipe off dust
initial use of the system. with soft cloth.
Signal communication may be disabled if
The usable period of the batteries may be an electronic-starter-type fluorescent lamp
short depending on the manufactured date (such as inverter-type lamps) is in the
of the air conditioner. room. Consult the shop if that is the case.
If the remote control signals happen to
operate another appliance, move that
appliance to somewhere else, or consult
the shop.

Room Air Conditioners GA-Series 31


Operation Manual ED01-214A

Preparation Before Operation


Indoor unit
Setting the air purifying filters Setting the clock
1 Open the front grille. 1 Press .
Hold the grille by the tabs on the two sides
and lift it until it stops with a click.
(about 60)
AM is displayed.

Display
AM
blinks.

2 Pull out the air filters. 2 Press


time.
to set the clock to the present
Push upwards the
tab at the center of TIMER
each air filter, then
pull it down.

Display
PM

Holding down ( ) or ( ) button


rapidly increases or decreases the time display.

3 Set the air purifying filters.


3 Press .
Attach an air purifying filter to each air filter.
(See page 13 Care and cleaning) blinks.
Display

4 Set the air filters in their original PM


positions and close the front grille. (Now the clock is set.)
Operation without air filters may result in Turn the breaker ON
troubles as dust will accumulate inside the
indoor unit. Turning ON the breaker opens the flap, then
closes it again. (This is a normal procedure.)
NOTE
Tips for saving energy Please note
Be careful not to cool the room too much. The air conditioner always consumes 7 watts of
Keeping the temperature setting at a electricity even while it is not operating.
If you are not going to use the air conditioner for a
moderate level helps save energy. long period, for example in spring or autumn, turn
the breaker OFF.
Recommended temperature setting Use the air conditioner in the following conditions.
Mode Operating conditions If operation is continued out of this range
For cooling: 26C 28C Outdoor temperature : 19 to 46 C A safety device may work to stop the operation.
For heating: 20C 24C Indoor temperature : 18 to 32 C (In multi system, it may work to stop
COOL Indoor humidity : 80% max. the operation of the outdoor unit only.)
Condensation may occur on the indoor unit and drip.
Cover windows with a blind or a curtain. Outdoor temperature : 10 to 21 C
HEAT A safety device may work to stop the operation.
Blocking sunlight and air from outdoors Indoor temperature : 27 C max.
increases the cooling effect. Outdoor temperature : 19 to 46 C A safety device may work to stop the operation.
Condensation may occur on the indoor unit and drip.
Clogged air filters cause inefficient DRY Indoor temperature : 18 to 32 C
Indoor humidity : 80% max.
operation and waste energy. Clean them
once in about every two weeks.

32 Room Air Conditioners GA-Series


ED01-214A Operation Manual

AUTO DRY COOL HEAT FAN Operation


The air conditioner operates with the settings of To change the air flow rate setting:
your choice.
From the next time on, the air conditioner will Press FAN .
operate with the same settings.
DRY mode AUTO or HEAT or COOL or FAN mode
1 Press MODE and select a mode. Five levels of air flow rate setting
The air flow rate
from to plus are
setting is not
Display

Display
variable. available.

Display
<FT> <FTY>
Each pressing of the button advances the
mode setting in sequence. At smaller air flow rates, the cooling effect is
<FT> also smaller.

<FTY>
NOTE
<Note on HEAT mode operation>
Since this air conditioner heats the room by
ON/OFF taking heat from outdoor air to indoors, the
2 Press . heating capacity becomes smaller in lower
outdoor temperatures. If the heating effect is
insufficient, it is recommended to use another
heating appliance in combination with the air
Then OPERATION conditioner.
lamp lights up. The heat pump system heats the room by
circulating hot air around all parts of the room.
After the start of heating operation, it takes
some time before the room gets warmer.
To stop: In heating operation, frost may occur on the
outdoor unit and lower the heating capacity. In
ON/OFF that case, the system switches into defrosting
Press once again.
operation to take away the frost.
During defrosting operation, hot air does not
Then OPERATION lamp goes off. flow out of indoor unit.
<Note on DRY mode operation>
To change the temperature setting:
This operation dehumidifies the indoor air when
DRY or FAN mode AUTO or HEAT or COOL mode it is humid.
<Note on AUTO operation>
Press to raise the temperature and In AUTO operation, the system selects a
temperature setting and an appropriate mode
The temperature press to lower the temperature. (COOL or HEAT) based on the room
temperature at the start of the operation.
setting is not
Set to the temperature you like. The system automatically reselects setting at a
variable.
regular interval to bring the room temperature
to user-seetting level.
Display

If you do not like AUTO operation, you can


C select manually, you like the mode and setting.

Room Air Conditioners GA-Series 33


Operation Manual ED01-214A

Adjusting the Air Flow Direction


You can adjust the air flow direction to increase Notes on flap angles
your comfort.
When SWING is selected, the flap swinging
range depends on the operation mode. (See
Adjusting the the figure.)
The real flap angles are differ from the
horizontal blade (flap) display of remote controller.

Press SWING .

Ever y time the button is pressed,


appears or disappears.

....... The flap automatically


DRY COOL
swings up and down. FAN

HEAT

....... To stop the flap at an angle


you like, press SWING .
ATTENTION
Always use a remote controller to adjust
the flap angle. If you attempt to move it
forcibly with hand when it is swinging,
the mechanism may be broken.

Adjusting the
vertical blade (louvre)

Hold the knob and move the louvre.


(You will find a knob on the left-side and the right-side blades.)
ATTENTION
Be careful when adjusting the louvre. Inside
the air outlet, a fan is rotating at a high speed.

10

34 Room Air Conditioners GA-Series


ED01-214A Operation Manual

POWERFUL
Operation
POWERFUL operation quickly maximizes the
cooling (heating) effect in any operation mode.
You can get the maximum capacity with a touch
of a button.
Pressing the (POWERFUL) button during
operation starts POWERFUL operation.
POWERFUL operation ends in 20 minutes.
Then the system automatically operates
again with the settings which were used
before POWERFUL operation.
During you use POWERFUL operation, the
other functions will not go on.

1 Press .
Display

To cancel POWERFUL operation:

Press .

Notes on POWERFUL operation


In COOL and HEAT mode
To maximize the cooling and heating effect,
the capacity of outdoor unit must be
increased and the air flow rate be fixed to the
maximum setting.
The temperature and air flow settings are not
variable.
In DRY mode
The temperature setting is lowered by 3C
and the air flow rate is slightly increased.
In FAN mode
The air flow rate is fixed to the maximum
setting.

11

Room Air Conditioners GA-Series 35


Operation Manual ED01-214A

Timer Operation
Timer functions are useful for automatically ON TIMER operation
switching the air conditioner on or off at night or in
the morning. You can also use OFF TIMER and Check that the clock is correct. If not, set the
ON TIMER in combination. clock to the present time (See page 8).

OFF TIMER operation 1 Press ON while the air conditioner is


not operating.
Check that the clock is correct. AM is displayed.

Display
If not, set the clock to the present time. (See page 8.)
AM
blinks.
1 Press OFF while the air conditioner
* Previous time setting
is operating. appears on display.

AM is displayed. 2 Press until the time setting


Display

AM TIMER
blinks.
reaches the point you like.
* Previous time setting Every pressing of either button increases or
appears on display. decreases the time setting by 10 minutes.
Holding down either button changes the
2 Press until the time setting setting rapidly.

TIMER
3 Press ON once again.
reaches the point you like.
Every pressing of either button
Display

increases or decreases the time setting AM


by 10 minutes. Holding down either
button changes the setting rapidly.

3 Press OFF once again.


Then the TIMER lamp lights up.
Combining ON TIMER and OFF TIMER
Display

AM A sample setting for combining the two timers is shown below.


(Example)
Present time: 11:00 PM
(The unit operating)
OFF TIMER at 0:00 a.m.
ON TIMER at 7:00 a.m. Combined
Then the TIMER lamp lights up.
To cancel the timer:
Display

Press CANCEL . AM AM

Then the TIMER lamp goes off. Notes on ON,OFF TIMER


When TIMER is set, the present time is not displayed.
Once you set ON,OFF TIMER, the time setting is
Notes on OFF TIMER kept in the memory. (The memory is canceled when
remote controller batteries are replaced.)
NIGHT SET MODE When operating the unit via the ON/OFF Timer, the
When the OFF TIMER is set, the air actual length of operation may vary from the time
conditioner automatically adjusts the entered by the user. (Maximum approx. 10 minutes.)
temperature setting (0.5C up in COOL,
2.0C down in HEAT) to prevent excessive ATTENTION
cooling (heating) for your pleasant sleep. In the following cases, set the timer again.
After a breaker has turned OFF.
After a power failure.
After replacing batteries in the remote controller.

12

36 Room Air Conditioners GA-Series


ED01-214A Operation Manual

Care and Cleaning


CAUTION Cleaning the indoor and outdoor
Before cleaning, be sure to stop the units and the remote controller
operation and turn the breaker OFF.
Wipe them with dry soft cloth.
For cleaning, do not use water hotter than
Cleaning the air filters 40C, benzine, gasoline, thinner, nor other
(It is recommended to clean them every two weeks.) volatile oils, polishing compound, scrubbing
brushes nor other hard stuff.
Clean the air filters,
when cleaning lamp
lights up. Replacing air purifying filters
(It is recommended to replace them every
1 Open the front grille.
Hold the grille by the tabs on the two sides three months.)
and lift it unitl it stops with a click. (about 60) Air purifying filters need to be replaced regularly.

1 Open the front grille and pull out


the air filters.

2 Push cleaning lamp 2 Take off the air


purifying filters.
3 Detach the
filter element
reset button.
(See page 5.) Air filter and attach a
Air purifying new one.
filter frame
3 Pull out the air filters.
Push a little upwards the
tab at the center of each
air filter, the pull it down.
Hold the recessed
4 Take off the air
purifying filters parts of the frame
and unhook the four
and clean them.
claws.
Wash them with
water, or clean
them with a
vacuum cleaner.
4 Attach the air
purifying filter.
5 Set the air
filters as they
If the dust does not come off easily, were and
wash them with neutral detergent close the front
thinned with lukewarm water, then dry grille.
them up in the shade. (Push the grille
at the 4 points,
5 Set the air purifying filters and the air
filters as they were and close the front
two at both sides
and in the
grille. Push middle.)
NOTE
To order air purifying filters, contact the
service shop where you bought the air
Insert claws of the filters into slots of the front conditioner.
Once the air purifying filter element gets
panel. The front grille should lock at both sides dirty, it is not reusable but must be thrown
and at the point in the middle. Push the grille at away.
the 4 points indicated by . Operation with dirty air purifying filters :
cannot clean the air.
NOTE results in poor cooling.
may cause odour.
In a dusty environment, clean the air
filters at least once in every two weeks. Item Part No.
Operation with dusty air filters lowers the Air purifying filter (with frame) KAF918A41
cooling capacity and wastes energy. Air purifying filter (without frame) KAF918A42

13

Room Air Conditioners GA-Series 37


Operation Manual ED01-214A

Care and Cleaning


Cleaning the front grille Check
You may remove the front grille for cleaning. Check that the base, stand and other
fittings of the outdoor unit are not
CAUTION decayed or corroded.
When removing or attaching the front grille, use a robust
and stable stool and watch your steps carefully. Check that nothing blocks the air
When removing or attaching the front grille, support the inlets and the outlets of the indoor unit
grille securely with hand to prevent it from falling. and the outdoor unit.
For cleaning, do not use water hotter than 40C, benzine,
gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes nor othe hard stuff. Check that the drain comes smoothly
After cleaning, make sure that the front grille is securely out of the drain hose during COOL or
fixed. DRY operation.
If no drain water is seen, water may be
1 Open the front grille.
leaking from the indoor unit. Stop
Hold the grille by the tabs on the two sides operation and consult the service shop if
and lift it until it stops with a click. this is the case.

Before a long idle period


1 Operate the fan alone for several
hours on a fine day to dry out the
2 Remove the front grille. inside.
Supporting the front grille with one hand, release <FT>
the lock by sliding down the knob with the other
hand.
To remove the front grille, pull it toward yourself 1 Press MODE and select .
with both hands.
ON/OFF
2 Press .

<FTY>

1 Press MODE and select .


3 Clean the front grille.
You may wipe it with a soft cloth soaked in water.
Only neutral detergent may be used.
2 Press TEMP and set the
You may wash the grille with water. After washing,
dry it with cloth, then dry it up in the shade. temperature to 32C
4 Attach the front grille. ON/OFF
Set the 3 keys of the front grille into the slots and 3 Press .
push them in all the way.
Supporting the front grille with one hand, fit the Perform this operation when the room
lock by sliding up the knob with the other hand. temperature is under 28C.
Close the front grille slowly in this state. (Push 2 After operation stops, turn off the
the grille at the 3 points, two at both sides and in
the middle.) breaker for the room air conditioner.
3 Clean the air filters and set them
again.
4 Take out batteries from the remote
Fit the key controller.
into the slot.

Side up the knob.

14

38 Room Air Conditioners GA-Series


ED01-214A Operation Manual

Trouble Shooting
These cases are not troubles.
The following cases are not air conditioner troubles but have some reasons. You may just continue
using it.

Case Explanation
Operation does not start soon. This is to protect the air conditioner.
When ON/OFF button was You should wait for about 3 minutes.
pressed soon after operation
was stopped.
When the mode was reselected.

Hot air does not flow out soon The air conditioner is warming up. You should wait for 1 to 4 minutes.
after the start of heating (The system is designed to start discharging air only after it has reached
operation. a certain temperature.)

The heating operation stops The system is taking away the frost on the outdoor unit.
suddenly and a flowing sound is You should wait for about 3 to 10 minutes.
heard.

The outdoor unit emits water or In HEAT mode


steam. The frost on the outdoor unit melts into water or steam when the air
conditioner is in defrost operation.
In COOL or DRY mode
Moisture in the air condenses into water on the cool surface of
outdoor unit piping and drips.

Mists come out of the indoor unit. This happens when the air in the room is cooled into mist by the cold
air flow during cooling operation.

The indoor unit gives out odour. This happens when smells of the room, furniture, or cigarettes are
absorbed into the unit and discharged with the air flow.
(If this happens, we recommend you to have the indoor unit washed
by a technician. Consult the service shop where you bought the air
conditioner.)

After operation is stopped:


The outdoor fan rotates while the The outdoor fan continues rotating for another 60 seconds for system
air conditioner is not in operation. protection.
While the air conditioner is not in operation:
When the outdoor temperature is very high, the out door fan starts
rotating for system protection.

The operation stopped suddenly. For system protection, the air conditioner may stop operating on a
(OPERATION lamp is on) sudden large voltage fluctuation.
It automatically resumes operation in about 3 minutes.

15

Room Air Conditioners GA-Series 39


Operation Manual ED01-214A

Trouble Shooting
Check again
Please check again before calling a repair person.

Case Check
The air conditioner does not Hasnt a breaker turned OFF or a fuse blown?
operate. Isnt it a power failure?
(OPERATION lamp is off) Are batteries set in the remote controller?
Is the timer setting correct?

Cooling or Heating effect is Are the air filters clean?


poor. Is there anything to block the air inlet or the outlet of the indoor and the
outdoor units?
Is the temperature setting appropriate?
Are the windows and doors closed?
Are the air flow rate and the air direction set appropriately?

Operation stops suddenly. Are the air filters clean?


(OPERATION lamp blinks.) Is there anything to block the air inlet or the outlet of the indoor and the
outdoor units?
Clean the air filters or take all obstacles away and turn the breaker OFF.
Then turn it ON again and try operating the air conditioner with the remote
controller. If the lamp still blinks, call the service shop where you bought the
air conditioner.

An abnormal functioning The air conditioner may malfunction with lightening or radio waves. Turn the
happens during operation. breaker OFF, turn it ON again and try operating the air conditioner with the
remote controller.

16

40 Room Air Conditioners GA-Series


ED01-214A Operation Manual

Trouble Shooting
Call the service shop immediately.
WARNING
When an abnormality (such as a burning smell) occurs, stop operation
and turn the breaker OFF.
Continued operation in an abnormal condition may result in troubles,
electric shocks or fire.
Consult the service shop where you bought the air conditioner.

Do not attempt to repair or modify the air conditioner by yourself.


Incorrect work may result in electric shocks or fire.
Consult the service shop where you bought the air conditioner.

If one of the following symptoms takes place, call the service shop immediately.
The power cord is abnormally hot or damaged.
An abnormal sound is heard during operation.
The safety breaker, a fuse, or the earth leakage
breaker cuts off the operation frequently. Turn the breaker
OFF and call the
A switch or a button often fails to work service shop.
properly.
There is a burning smell.
Water leaks from the indoor unit.

After a power failure Lightning


The air conditioner automatically If lightning may strike the
resumes operation in about three neighbouring area, stop operation
minutes. You should just wait for and turn the breaker OFF for
a while. system protection.

We recommend periodical maintenance


In certain operating conditions, the inside of the air conditioner may get foul
after several seasons of use, resulting in poor performance. It is recommended
to have periodical maintenance by a specialist aside from regular cleaning by
the user. For specialist maintenance, contact the service shop where you
bought the air conditioner.
The maintenance cost must be born by the user.

17

3P062628-7J

Room Air Conditioners GA-Series 41


Optional Accessories ED01-214A

13. Optional Accessories


13.1 Option List

Option Name Kit Name Applicable


Model
1 Centralized control board-up to 5 rooms 1 KRC72 Indoor Unit

2 Wiring adaptor for time clock/remote control 2 KRP413A1S Indoor Unit


(Normal open pulse contact / Normal open contact)
3 Air purifying filter with frame KAF918A41 Indoor Unit
4 Air purifying filter without frame KAF918A42 Indoor Unit
5 Remote controller loss prevention with the chain KKF917A4 Indoor Unit
6 Drain piping kit for outdoor unit KIS95 Outdoor Unit
1 Wiring adaptor is also required for each indoor unit.
2 Wiring adaptor supplied by DAIKIN. Time clock and other devices ; field supply.

42 Room Air Conditioners GA-Series


ED01-214A Optional Accessories

13.2 Installation Manual


13.2.1 KRP413A1S

Room Air Conditioners GA-Series 43


Optional Accessories ED01-214A

Installation

This product is available in two types. The KRP413A1S is for installation in a case independent of the indoor unit, and the KRP413A1 is for
installation within the indoor unit.

1. KRP413A1S 3. Attaching Adaptor Case Assy (for KRP413A1S)

1 Installation diagram 1 Using the screws (to mount on a wall, etc.)


Adaptor case
Use the 3 supplied screws to attach the case assy .
Indoor unit PCB

S21 Adopter case


Indoor unit

Local inter-unit Install the adaptor case assy as close to the indoor unit as possible.
Relay harness power cord, etc.
Removing case front

Case front
2 Components
Screw
Adaptor case assy Relay harness (approx. 0.8 m)
Adaptor PCB
(Adaptor (PCB) is attached in the adaptor case.) Screw cover

Remove the screw cover, one of the screws


and then the case front.
Attach the case back to the surface by
tightening the screws through the screw
holes (one round hole, two long holes).
Accessories
After connecting the cables (refer to the following sections), replace the
Tie-wrap (4 pcs.) case front. Be careful not to damage the harness in the case.
Velcro for attaching to the indoor unit (2 sets)
Screws for attaching the adaptor case (4 pcs.) Press in so that the prong catches
Screws for attaching to the wall (3 pcs.) the case back.

Installation manual
Wiring

2. KRP413A1

For this type, install the adaptor PCB within the indoor unit. The method of
installation and connection vary depending on the model of the air Screw
conditioner. See your air conditioner installation manual for details.

Screw cover
1 Components

Adaptor PCB Relay harness (approx. 0.25 m) 2 Using Velcro (to attach on the indoor unit)

Attach the adaptor case with the supplied Velcro.


Remove the case front (as for mounting on a wall).
After connecting the cables (see the following sections), replace the
case front. It can be screwed to the case back from the rear with the
four supplied screws.
Be careful not to damage the harness in the case.
Stick one end of the Velcro to the rear side of the case back, and stick
the other end to the indoor unit with the same space between them.
Installation manual

Velcro male Velcro female


(female) (male)

Indoor unit

To prevent the adaptor case assy from falling, do not use the Velcro for
attaching it to a wall or other surface.

44 Room Air Conditioners GA-Series


ED01-214A Optional Accessories

Room Air Conditioners GA-Series 45


Optional Accessories ED01-214A

46 Room Air Conditioners GA-Series


Dealer
Head Office:
Umeda Center Bldg., 4-12, Nakazaki-Nishi
2-chome, Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 18-1, Konan
2-chome, Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved

The specifications, designs, and information in this brochure are subject to change without notice.

ED 01-214A
Printed in Japan 05/2004 B AK

You might also like