Professional Documents
Culture Documents
- Heat Pump -
GA-Series
ED01-214A
Split - System
Room Air Conditioners
GA - Series
FTY50GAV1A RY50GAV1A
Heat Pump
FTY60GAV1A RY60GAV1A
1. Power Supply
1.1 Power Supply
2. Functions
2.1 List of Functions
FTY5060GAV1A
FTY5060GAV1A
RY5060GAV1A
RY5060GAV1A
Category Functions Category Functions
Basic Inverter (with Inverter Power Control) Health & Air Purifying Filter with Bacteriostatic,
Function Clean Virustatic & Deodrizing Functions {
Automatic Defrosting {
Remote Control Adaptor (Option) {
(Normal Open-Pulse)
Operation Automatic Operation {
Remote Control Adaptor (Normal {
Open Contact)
Programme Dry Function { Dlll-NET Compatible (Adaptor)
Fan Only Remote Wireless {
Controller
Lifestyle New Powerful Operation (Non- {
Wired
Convenience Inverter)
Inverter Powerful Operation
Priority-Room Setting
Laundry Programme Operation
Home Leave Operation
Power Selection
Indoor Unit On/Off Switch {
Signal Reception Indicator {
Temperature Display
Note: { : Holding Functions
: No Functions
3. Specifications
3.1 Heat Pump
220-230-240V, 50Hz
Indoor Units FTY50GAV1A FTY60GAV1A
Model RY50GAV1A RY60GAV1A
Outdoor Units
Cooling Heating Cooling Heating
kW 5.20 5.80-6.07-6.07 6.15 7.00-7.16-7.16
Capacity Rated Btu/h 17,750 19,800-20,720-20,720 21,000 23,900-24,400-24,400
kcal/h 4,470 4,990-5,220-5,220 5,300 6,020-6,150-6,150
Moisture Removal L/h 2.2 3.9
Running Current (Rated) A 9.7-10.7-10.7 8.8-9.5-9.5 11.2-10.8-10.8 11.0-10.8-10.8
Power Consumption W 1,900-2,080-2,080 1,700-1,920-1,920 2,300-2,460-2,460 2,260-2,470-2,470
Power Factor % 89.0-84.5-81.0 87.8-87.9-84.2 93.3-99.0-94.9 93.3-99.4-95.3
COP W/W 2.74-2.50-2.50 3.41-3.16-3.16 2.67-2.50-2.50 3.10-2.90-2.90
Liquid mm 6.4 6.4
Piping Gas mm 15.9 15.9
Connections
Drain mm 18.0 18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Indoor Unit FTY50GAV1A FTY60GAV1A
Front Panel Color Almond White Almond White
H 14.0 (494) 16.3 (575) 14.0 (494) 16.3 (575)
Air Flow Rate m/min M 11.7 (413) 13.7 (484) 12.1 (427) 14.0 (494)
(cfm)
L 9.4 (332) 11.1 (392) 10.3 (364) 11.7 (413)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 54 54
Speed Steps 5 Steps and Auto 5 Steps and Auto
Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward
Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof
Running Current (Rated) A 0.19-0.18-0.17 0.19-0.18-0.17 0.19-0.18-0.17 0.19-0.18-0.17
Power Consumption (Rated) W 40 40 40 40
Power Factor % 95.7-96.6-98.0 95.7-96.6-98.0 95.7-96.6-98.0 95.7-96.6-98.0
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (HWD) mm 2981,050190 2981,050190
Packaged Dimensions (WDH) mm 1,183367289 1,183367289
Weight kg 12 12
Gross Weight kg 16 16
Operation H/M/L dBA 45/41/35 44/39/33 46/42/37 46/41/34
Sound
Outdoor Unit RY50GAV1A RY60GAV1A
Casing Color Ivory White Ivory White
Type Hermetically Sealed Rotary Type Hermetically Sealed Rotary Type
Compressor Model RC70AV1TRT NH41VMDT
Motor Output W 1,700 2,200
Type SUNISO 4GSD.I. MS-32
Refrigerant Oil
Charge L 1.00 1.20
Type R22 R22
Refrigerant
Charge kg 1.55 1.75
H 35-36.5-38 (1,236-1,288-1,341) 32-33.5-35 (1,130-1,183-1,236) 44-45-46 (1,553-1,589-1,624) 40-41.5-43 (1,412-1,465-1,518)
Air Flow Rate m/min (cfm)
L 16.5-17-17.5 (582-600-618) 15.5-16-16.5 (547-582-618) 38-38.5-39 (1,341-1,359-1,377) 34.5-35-35.5 (1,218-1,236-1,253)
Type Propeller Propeller
Fan
Motor Output W 35 53
Running Current (Rated) A 9.51-10.52-10.53 8.61-9.32-9.33 11.01-10.62-10.63 10.81-10.62-10.63
Power Consumption (Rated) W 1,860-2,040-2,040 1,660-1,880-1,880 2,260-2,420-2,420 2,220-2,430-2,430
Power Factor % 88.9-86.0-82.3 87.6-87.7-84.7 93.3-99.1-94.9 93.3-99.1-95.2
Starting Current A 43-44-45 55-58-60
Dimensions (HWD) mm 685800300 685880350
Packaged Dimensions (WDH) mm 955390732 1040460732
Weight kg 51 75
Gross Weight kg 55 79
Operation Sound dBA 49-50-50 51-52-52 54-56-56 54-56-56
Drawing No. 3D028523 3D028524
Conversion Formulae
Notes: MAX. interunit piping length: 30m
MAX. interunit height difference: 15m kcal/h=kW860
Btu/h=kW3414
Amount of additional refrigerant for piping length exceeding 10m : 30g/m(50class), 60g/m(60class) cfm=m/min35.3
The data are based on the conditions shows in the table below.
Standard Cooling Heating Piping Length Power Source
4. Dimensions
4.1 Heat Pump
4.1.1 Indoor Unit
FTY50GAV1A / FTY60GAV1A
14
22
COOLING DRY HEATING
58 18
DIFFUSER
DAIKIN
175
20
167
20 20
(298)
FLAP 40
15 15
163
30
52
60 75 137
52
40 40
RIGHT/LEFT:(MANUAL) WALL HOLE FOR EMBEDDED PIPING WALL HOLE
80 HOLE 80 HOLE
(ARC423A17) STANDARD LOCATIONS OF WALL HOLES
60 3D028532
WIRELESS REMOTE CONTROLLER 60
RY50GAV1A
HOLES FOR ANCHOR BOLTS
31
(M8 OR M10) 2-DRAIN OUTLET 269
350
330
98
540 130
POWER INTAKE
LIQUID PIPE
645
LIQUID (6.4CuT)
685
STOP VALVE
SERVICE PORT
95 70
GAS
75 STOP VALVE
NAME PLATE 100 GAS PIPE
(15.9CuT)
50
MINIMUM SPACE FOR AIR PASSAGE
50
50
100
100
50 3D004853B
RY60GAV1A
HOLES FOR ANCHOR BOLTS
(M8 OR M10)
90
370
410
128
40
TERMINAL COVER
177
40 120 500 190 15 350 OUTDOOR TEMP. THERMISTOR
3-DRAIN OUTLET EARTH TERMINAL
881 55 (M4)
POWER INTAKE
686
SERVICE PORT
30
NAME PLATE 40
120 110
MINIMUM SPACE FOR AIR PASSAGE
A
100
100
100
A
H
<1000 350
H=
H>1000 600
100 100
A
3D004852A
5. Wiring Diagrams
5.1 Heat Pump
5.1.1 Indoor Unit
FTY50GAV1A / FTY60GAV1A
FIELD WIRING.
1
X1M 2
PCB3 PCB1 PCB2 H1
S25 S24 RED 1 3
Fu outdoor
WHT 2
LED LED LED 3.15A H2 BLK 3
S37 S36 GRN/YLW
H1P H2P H3P
H3
S8W
FG : FRAME GROUND
Fu : FUSE
H1~H3 : HARNESS
H1P~H3P : PILOT LAMP
FG M1F : FAN MOTOR
HA
M1S : SWING MOTOR
PCB4 PCB1~PCB4 : PRINTED CIRCUIT BOARD
S21 S201 R1T,R2T : THERMISTOR
S1W S6~S201 : CONNECTOR
S6
S27 S26 S1W : OPERATION SWITCH
S8W : CLEANING INDICATOR RESET
SIGNAL SWITCH
RECEIVER S31 S32 M M1S
X1M : TERMINAL STRIP
: PROTECTIVE EARTH
t t
NOTE
R1T R2T M ADDRESS JUMPER IS MARKED "JA" ON PCB.
WIRELESS M1F
REMOTE indoor
CONTROLLER
3D027719
RY50GAV1A
RED
MRCW MRCC MRRH MRRL MRC MR2 T1R
2 2 WHT
135C
3 3 BLK S5 t
BLU
GRN/YLW SA
5A F1U
POWER SUPPLY
5A F2U
RED
AC220-240V GRN/YLW S3
~50Hz L L YLW
BLU
MRC
PNK
BLU X11A MRRL
N N RTH1
MRRH
RED
BRN
BRN
BLK
ORG
RED
BLU
PPL
2 6 A2 BRN C2R
t t
BRN
BLU
BLU
BLK
BLK
WHT
RED
BLK
ORG
BLU
YLW
RED
RY60GAV1A
X1M
TO INDOOR UNIT
1 RED
PCB
RED
1
2 WHT MRCW MRCC MRRH MRRL MRC MR1 MR2
2
3 3 BLK
BLU
S1
GRN/YLW 5A F1U
POWER SUPPLY
5A F2U T1R
RED
AC220-240V
~50Hz 135C
S5
BLU
L L t
N N
SA
EARTH
GRN/YLW
RED
BLU
YLW YLW S3
PNK MRC
YLW
1 5 A1 K1M X11A MRRL
C11R,C12R : RUNNING CAPACITOR MRRH
2 6 A2 GRN/YLW
F1U,F2U : FUSE RTH1 MRCC
BRN
BLK
BRN
BRN
ORG
GRY
RED
BLU
PPL
YLW
BRN
M
R1T,R2T : THERMISTOR 1~
WHT
BLU
BLU
BLK
BLU
BLU
YLW
BLK
6. Piping Diagrams
6.1 Heat Pump
6.1.1 Indoor Unit
FTY50GAV1A / FTY60GAV1A
INDOOR UNIT
HEAT EXCHANGER
THERMISTOR
ON HEAT EXCH.
FIELD PIPING
(6.4CuT) CROSS FLOW FAN
FAN MOTOR
FIELD PIPING
(15.9CuT)
REFRIGERANT FLOW
COOLING
HEATING 4D003943A
RY50GAV1A
OUTDOOR UNIT
OUTDOOR TEMPERATURE
HEAT THERMISTOR
HEAT EXCHANGER
EXCHANGER
THERMISTOR
CAPILLARY TUBE(2)
CAPILLARY TUBE(3)
M FAN MOTOR
PROPELLER
FAN FILTER LIQUID LINE
STOP VALVE
(6.4CuT)
FIELD
PIPING
(15.9CuT)
4-WAY VALVE
GAS LINE STOP VALVE
WITH SERVICE PORT
CAPILLARY
SV TUBE(6)
SOLENOID
VALVE
REFRIGERANT FLOW
ACCUMULATOR
COOLING
ACCUMULATOR
HEATING
FLOW DIRECTION
COMPRESSOR
C : 3D028561
RY60GAV1A
OUTDOOR UNIT
OUTDOOR TEMPERATURE
HEAT THERMISTOR
EXCHANGER HEAT EXCHANGER
THERMISTOR
CAPILLARY TUBE(2)
CAPILLARY TUBE(3)
M FAN MOTOR
PROPELLER
FAN SOLENOID LIQUID LINE
SV VALVE (6.4CuT)
STOP VALVE FIELD
PIPING
FILTER (15.9CuT)
SOLENOID
VALVE
REFRIGERANT FLOW
ACCUMULATOR
COOLING
ACCUMULATOR
HEATING
C : 3D028562
7. Capacity Tables
7.1 Heat Pump
Heating
AFR 16.3
Symbols NOTES:
AFR : Air flow rate (m/min.) 1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat.
BF : Bypass factor 2. shows nominal capacities and power input.
EWB : Entering wet bulb temp. (C) 3. TC,PI and SHC must be calculated by interpolation using the figures
in the above tables. (Figures out of the tables should not be used for
EDB : Entering dry bulb temp. (C) calculation.)
TC : Total capacity (kW) 4. SHC is based on each EWB and EDB.
SHC=SHC correction for other dry bulb.
SHC : Sensible heat capacity (kW) =0.3460AFR(m/min.)(1-BF)(DB-EDB)
PI : Power input (kW) Add SHCTO SHC.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m at <AS / NZS3823.1>
Level difference : 0m
6. Maximum entering air temp. to condenser is 46C (115F)
7. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
Heating
AFR 16.3
Symbols NOTES:
AFR : Air flow rate (m/min.) 1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat.
BF : Bypass factor 2. shows nominal capacities and power input.
EWB : Entering wet bulb temp. (C) 3. TC,PI and SHC must be calculated by interpolation using the figures
in the above tables. (Figures out of the tables should not be used for
EDB : Entering dry bulb temp. (C) calculation.)
TC : Total capacity (kW) 4. SHC is based on each EWB and EDB.
SHC=SHC correction for other dry bulb.
SHC : Sensible heat capacity (kW) =0.3460AFR(m/min.)(1-BF)(DB-EDB)
PI : Power input (kW) Add SHCTO SHC.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m at <AS / NZS3823.1>
Level difference : 0m
6. Maximum entering air temp. to condenser is 46C (115F)
7. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
Note: The capacity in the range of the refrigerant additional charge shows when the additional refrigerant is
charged properly.
8. Operation Limit
8.1 Heat Pump
RY50GAV1A / RY60GAV1A
Cooling Heating
(50Hz)
50
46 20
40 15
Continuous operation
10
Pull-down period
Continuous operation
30
5
Warming up period
20 0
19.4
0 -10
(-10CDB)
10 14 20 23 28 30 10 14 20 28 30
Indoor temp. (CWB) Indoor temp. (CDB)
Notes:
The graphs are based on the following conditions.
Equivalent piping length 5m
Level difference 0m
Air flow rate High 3D006204B
9. Sound Level
9.1 Overall Sound Level
9.1.1 Indoor Units (dBA)
0.8m
FTY60GAV1A 46 37 46 34
1m
RY50GAV1A 49-50-50 51-52-52
NC-50 NC-50
dB(0dB=0.0002 bar)
dB(0dB=0.0002bar)
50 50
NC-40 NC-40
40 40
NC-30 NC-30
30 30
NC-20 NC-20
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
3D005357A 3D005357A
NC-60 NC-60
60 60
NC-50 NC-50
50 50
dB(0dB=0.0002bar)
dB(0dB=0.0002bar)
NC-40 NC-40
40 40
NC-30 NC-30
30 30
NC-20 NC-20
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
3D005359A 3D005359A
NC-50 NC-50
dB(0dB=0.0002 bar)
dB(0dB=0.0002bar)
50 50
NC-40 NC-40
40 40
NC-30 NC-30
30 30
NC-20 NC-20
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
3D028537 3D028537
NC-60 NC-60
60 60
NC-50 NC-50
dB(0dB=0.0002bar)
dB(0dB=0.0002bar)
50 50
NC-40 NC-40
40 40
NC-30 NC-30
30 30
NC-20 NC-20
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
3D028538 3D028538
SYMBOLS: NOTES:
MCA : MIN. CIRCUIT AMPS (A) 1. RLA is based on the following conditions.
Indoor temp. 27CDB/19CWB
MFA : MAX. FUSE AMPS (A) Outdoor temp. 35CDB.
LRA : LOCKED ROTOR AMPS (A) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
RLA : RATED LOAD AMPS (A) 4. Instead of fuse, use circuit breaker.
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)
3D029053
3D029055
SAFETY PRECAUTIONS
Read these SAFETY PRECAUTIONS carefully to ensure correct installation.
This manual classifies the precautions into WARNINGS and CAUTIONS.
Be sure to follow all the precautions below: they are all important for ensuring safety.
WARNINGS Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTIONS Failure to follow any of CAUTION may in some cases result in grave consequences.
The following safety symbols are used throughout this manual:
Be sure to observe this instruction. Be sure to establish an earth connection. Never attempt.
After completing installation, test the unit to check for installation errors. Give the user adequate instructions
concerning the use and cleaning of the unit according to the Operation Manual.
WARNINGS
Installation should be left to the dealer or another professional.
Improper installation may cause water leakage, electrical shock, or fire.
Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, or fire.
Be sure to use the supplied or specified installation parts.
Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire.
Install the air conditioner on a solid base that can support the units weight.
An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring
rules or code of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
For wiring, use a cable long enough to cover the entire distance with no connection.
Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock or fire.)
Use the specified types of wires for electrical connections between the indoor and outdoor units.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.
After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the
electrical covers or panels. Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.
When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified
refrigerant (R22), such as air. (Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)
The unit is out of reach of children at least 1.8m above the floor.
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)
After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)
Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.
Incomplete earth may cause electrical shock. A high surge current from lightning or other sources may cause damage to the air conditioner.
An earth leakage circuit breaker may be required depending on site condition to prevent electrical shock.
Failure to do so may cause electrical shock.
CAUTIONS
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.
Establish drain piping according to the instructions of this manual.
Inadequate piping may cause flooding.
Note for installing the outdoor unit. (For heat pump model only.)
In cold area where the outside air temperature keep below or around freezing-point for a few days, the outdoor units drain may freeze.
If so, it is recommended to install an electric heater in order to protect drain from freezing.
ACCESSORIES
A Mounting plate 1 E Remote controller holder 1 J Insulation tape 1
B Mounting plate fixing screw F Fixing screw for remote controller
M4 X 25L
10 holder M3 X 20L
2 K Operation manual 1
CHOOSING A SITE
Before choosing the installation site, obtain user approval.
Indoor unit Outdoor unit
The indoor unit should be sited in a place where: The outdoor unit should be sited in a place where:
the restrictions on installation specified in the the restrictions on installation specified in the outdoor unit installation diagram are
indoor unit installation drawings are met, met,
both air intake and exhaust have clear paths met, drain water causes no trouble or problem in particular,
the unit is not in the path of direct sunlight, both air intake and exhaust have clear paths of air (they should be free of snow in
the unit is away from the source of heat or steam, snowy districts),
there is no source of machine oil vapour (this may the unit is in a clear path of air but not directly exposed to rain, strong winds, or direct
shorten indoor unit life), sunlight,
cool (hot) air is circulated throughout the room, there is no fear of inflammable gas leakage,
the unit is away from electronic ignition type the unit is no directly exposed to salt, sulfidized gases, or machine oil vapour (they
fluorescent lamps (inverter or rapid start type) as may shorten outdoor unit life).
they may shorten the remote control range, operation noise or hot (cold) air flow does not cause trouble to neighbours, and
the unit is at least 1 metre away from any television the unit is at least 3 metres away from any television or radio antenna.
or radio set (unit may cause interference with the
picture or sound). Wireless Remote Controller
Turn on all the fluorescent lamps in the room, if any, and find the site where remote
control signals are properly received by the indoor unit (within 7 metres).
INSTALLATION TIPS
* The pipe port for left-side piping or in-wall piping can be * The removed pipe port cover can be Removed
accessed by removing the bottom cover from the bottom frame. kept in the mounting plate pocket. pipe port
cover
For easier piping work, you may
want to cut this bar away.
Cut here. Interconnecting wires Cut here.
C Mounting plate
Drain
hose A Mounting plate
Caulk this hole * When filling additional refrigerant, see the
with putty or
caulking material. Wrap insulating tape to the bent
Bind with plastic tape. portion of refrigerant pipe while
"INDOOR/OUTDOOR UNIT INSTALLATION DRAWINGS".
making a half lap or greater. * Be sure to use the vacuum pump for air purging.
Bottom cover
* When two indoor units are installed in one room, the two
* Indoor unit's lift from mounting plate surface is eliminated wireless remote controllers can be easily set for different
by screwing the bottom frame to the mounting plate. addresses.
* Indoor unit's terminal block can be accessed for wiring
just by removing the front grille (without having to remove
the front panel). J4
Wireless
remote
controller
J4 ADDRESS
EXIST 1 ADDRESS J2/JA
CUT 2 EXIST 1
CUT 2
E
Service lid
Remote
1 Insert. controller holder
Stop valve cover
F 250 mm
(M3 X 20L) from w
all
INDOOR UNIT
Outdoor Unit Installation Guidelines
Where a wall or other obstacle is in the path of outdoor
1 INSTALLING THE MOUNTING PLATE
units intake or exhaust airflow, follow the installation The mounting plate should be installed on a wall which can support the weight of the indoor unit.
guidelines below. (1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely
level, and mark the boring points on the wall.
Wall facing one side Walls facing two sides (2) Secure the mounting plate to the wall with screws.
More than
Details of Mounting Plate and Dimensions Leveling mounting plate
Dangle a weighted thread
A
More than a and align thread with (Bolt size : M10)
B Use tape measure as shown vertical arrow.
70 Place a leveler 125
Position the end of tape b
on raised tab.
measure at
Exhaust
40
40
More than
Side view C Top view
299
130
Walls facing three sides
75
More than
E
52
52
More than
D More than 75 105 Gas pipe end
H 389 53 80 137
Liquid pipe end
1050
More than
More than E Through-the-wall Keep here the piece cut out from the unit for piping
F hole 80mm Recommended mounting-plate
Drain hose position retention spots (8 spots in all) (unit: mm)
Top view Side view
(mm) (mm)
2 BORING A WALL HOLE AND INSTALLING WALL EMBEDDED PIPE
For walls containing metal frame or metal board, be sure to use a wall embedded pipe and
A B C D E F note 1 wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
H 1000 350 Be sure to caulk the gaps around the pipes with caulking Inside Outside
Wall embedded pipe
RY50G 50 50 100 50 100 50 material to prevent water leakage. (field supply)
Caulking
H 1000 600 (1) Bore a feed-through hole of 80mm in the wall so
RY60G 100 100 100 100 note 1 100 it has a down slope toward the outside.
(2) Insert a wall pipe into the hole. 80
note 2 Wall hole cover
(3) Insert a wall cover into wall pipe. (field supply)
R50G 50 100 50 150 note 2 50
H 1000 300 (4) After completing refrigerant piping, wiring, and drain Wall embedded pipe
(field supply)
piping, caulk pipe hole gap with putty.
R60G 50 100 50 150 note 2 50 H 1000 600
Inner wall
Insert drain hose to this
(4) Open the front grille, then open the service lid. Wall Embedded Piping depth so it wont be
pulled out of drain pipe.
Service
Hook Follow the instructions given under
Left-Side, Left-Back, or Left Bottom Piping . 50 mm Drain hose
or more
(1) Insert the drain hose to this depth so it wont be Vinyl chloride
drain pipe
pulled out of the drain pipe. Outer wall (VP-30)
4 WIRING
(1) Strip wire ends (15 mm).
(5) Pass the interconnecting wires from the outdoor unit
(2) Match wire colours with terminal numbers on indoor and outdoor units' terminal blocks and
through the feed-through wall hole and then through the Hang indoor unit's hook here.
firmly screw wires to the corresponding terminals.
back of the indoor unit. Pull them through the front side.
(3) Connect the earth wires to the corresponding terminals.
Bend the ends of tie wires upward in advance for easier
work. (If the interconnecting wire ends are to be stripped
first, bundle wire ends with adhesive tape.) Terminal block
(6) Press the indoor units bottom panel with both hands Electrical component box
to set it on the mounting plate hooks. Make sure the When stripping the
ends of interconnecting
Wire retainer
Interconnecting Firmly secure wire retainer so that wires
wires do not catch on the edge of the indoor unit. wires in advance, bind wires sustain no external stress.
right ends of wires with Wire guide
insulating tape.
Shape wires so that the service
lid will fit securely. Use the specified wire type.
Left-Side, Left-Back, or Left Bottom Piping
(1) Attach the drain hose to the underside of (4) Pull wires to make sure that they are securely latched up, then retain wires with wire retainer.
the refrigerant pipes with adhesive vinyl tape. Remove pipe
port cover here (5) Shape the wires so that the service lid fits securely, then close service lid.
for left-side
piping
Left-side
piping
Remove pipe port cover here for left-bottom piping Left-back
Warning
Outdoor unit
piping Do not use tapped
Left-bottom piping Firmly fix the wires with the terminal screws. 1 23 LN
The earth leakage circuit wires,stand wires,
When wire length exceeds
(2) Be sure to connect the drain hose to the drain How to set drain plug 10 m, use 2.0-mm wires.
breaker is required depending
on site environment.
extensioncords, or
port in place of a drain plug. starbust connections,
ap as they may cause
No g Do not apply lubricating
Indoor
unit
1
2
Safety Earth leakage Power overheating, electrical
oil (refrigerant machine breaker circuit breaker supply
3 20A shock,or fire.
oil) when inserting 50Hz 220-240V
H05VV 60Hz 220-230V
Application of causes Firmly fix the wires with the terminal screws. Earth
deterioration and drain
leakage of the plug
Insert a hexagon wrench (4 mm)
(3) Shape the refrigerant pipe along the pipe path marking on the mounting plate. 5 DRAIN PIPING
(4) Pass drain hose and refrigerant pipes through the wall hole, then set the indoor unit on Connect the drain hose, as described below Remove the air filters and pour some
mounting plate hooks, using the markings at the top of indoor unit as a guide. The drain hose should water into the drain pan to check
(5) Pull in the interconnecting wires. be inclined downward.
the water flows smoothly.
(6) Remove the bottom cover and cut the bar away to gain better access for piping work.
For easier piping work, you may
Cut here. want to cut this bar away. Cut here. No trap is permitted.
Interconnecting wires
Do not put the end
of the hose in water.
Drain
hose
(A) Mounting plate
When drain hose requires extension, obtain Indoor unit Extension drain hose
Caulk this hole drain hose
with putty or Wrap insulating tape around the bent portion of refrigerant pipe.
an extension hose commercially available.
caulking material. Bottom cover Bind with plastic tape. Overlap at least half the width of the tape with each turn. Be sure to thermally insulate the indoor
section of the extension hose. Heat insulation tube
(Field supply)
(7) Wrap the refrigerant pipes and drain hose together with Drain hose
insulation tape. When connecting a rigid polyvinyl chloride pipe (nominal diameter 13 mm) directly to the drain
(8) While exercising care so that the interconnecting wires hose attached to the indoor unit as with embedded piping work, use any commercially available
do not catch indoor unit, press the bottom edge of indoor drain socket (nominal diameter 13 mm) as a joint.
unit with both hands until it is firmly caught by the
mounting plate hooks. Secure indoor unit to the
Commercially available Commercially available rigid
mounting plate with screws (M4 x 12L). Hitch indoor unit to
Drain hose supplied with
the indoor unit drain socket polyvinyl chloride pipe
this hook (3 hooks). M4 x 12L (nominal diameter 13 mm) (nominal diameter 13 mm)
OUTDOOR UNIT
1 INSTALLING OUTDOOR UNIT 4 PURGING AIR AND CHECKING GAS LEAKAGE
For outdoor unit installation, see CHOOSING A SITE , Outdoor unit Warning Warning
and INDOOR/OUTDOOR UNIT INSTALLATION DRAWINGS . Do not mix any substance other than the specified Refrigerant gas leaks during air purging, ventilate
refrigerant (R22) into the refrigeration cycle. the room as soon as possible.
2 FLARING THE PIPE END To prevent air pollution, a vacuum pump should be used for air purging wherever possible.
1. Cut the pipe end with a pipe cutter. Compound Pressure meter
(Cut exactly at If using additional refrigerant, perform air purging from
2. Remove burrs with the cut surface facing downward right angles.) Remove burrs
pressure gauge
the refrigerant pipes and indoor unit using a vacuum
so that the chips do not enter the pipe. Flaring
Gauge
pump, then charge additional refrigerant. manifold
3. Put the flare nut on the pipe. Set exactly at the position shown below.
A A Use a hexagonal wrench (4 mm) to operate the shut-off valve rod. High-pressure Liquid
4. Flare the pipe.
RIGID 0.5 mm All refrigerant pipe joints should be tightened with a torque valve Valve lids shut-off
5. Check that the flaring is properly made. Low-pressure valve
Die IMPERIAL 1.0 mm wrench at the specified tightening torque. valve
Check Charging
Warning The pipe end must hoses Gas
Flare's inner surface be evenly flared in
Incomplete flaring may cause refrigerant gas leakage. must be flaw-free. shut-off
a perfect circle.
Vacuum pump Service port valve
Make sure that the *1. Pipe length vs. vacuum pump run time
flare nut is fitted. *2. If the compound pressure gauge pointer swings back, refrigerant
Pipe length Up to 15 metres More than 15 metres may have water content or a loose pipe joint may exists. Check
all pipe joints and retighten nuts as needed, then repeat steps (2)
Run time Not less than 10 min. Not less than 15 min. through (4).
3 REFRIGERANT PIPING
(1) Connect projection side (on which worm pin is pressed) of charging hose (which comes from gauge manifold) to
1. Align the centres of both flares and tighten the flare Flare nut tightening torque gas shut-off valve's service port.
Gas side(5/8 inch) Liquid side(1/4 inch)
nuts 3 or 4 turns by hand. Then tighten them fully
6180~7540Ncm 1420~1720Ncm
with the torque wrenches. (630~770kgfcm) (144~176kgfcm) (2) Fully open gauge manifold's low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
Use torque wrenches when tightening the flare nuts to (High-pressure valve subsequently requires no operation.)
prevent damage to the flare nuts and escaping gas. Valve cap tightening tolque
Cautions on Pipe Handling (4) Close gauge manifold's low-pressure valve (Lo) and stop vacuum pump.
Protect the open end of the pipe against Wall (Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.
Be sure to
dust and moisture. place a cap.
Rain
All pipe bends should be as gentle as If no flare cap is (5) Remove covers from liquid shut-off value and gas shut-off valve.
possible. Use a pipe bender for bending. available, cover
the flare mouth
(Bending radius should be 30 to 40 mm or larger.) with tape to keep
dirt or water out.
(6) Turn the liquid shut-off valves rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit's flare and outdoor unit's flare and valve rods.
Selection of Copper and Heat Insulation materials After the check is complete, wipe all soapy water off.
When using commercial copper pipes and fittings, observe the following:
Insulation material: Polyethylene foam (7) Disconnect charging hose from gas shut-off valve's service port, then fully open liquid and gas shut-off valves.
Heat transfer rate: 0.041 to 0.052kW/mK (0.035 to 0.045 kcal/mhC) (Do not attempt to turn valve rod beyond its stop.)
Refrigerant gas pipe's surface temperature reaches 110C max.
Choose heat insulation materials that will withstand this temperature.
(8) Tighten valve lids and service port caps for the liquid and gas shut-off valves with a torque wrench at the specified torques.
Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation
O.D. 15.9mm
Thickness 1.0mm
O.D. 6.4mm
Thickness 0.8mm
I.D. 16-20mm
Thickness 10mm Min.
I.D. 8-10mm
Thickness 10mm Min.
5 WIRING
For interconnecting wire connections, see INDOOR UNIT , 4. WIRING .
Use separate thermal insulation pipes for gas and liquid Gas pipe Firmly tighten terminal Terminal block
Inter-unit wiring
refrigerant pipes. screws.
Supply Interconnecting wire
Firmly secure wire
retainer so wire
Liquid pipe
For wire termination at terminal block terminal block teminations will
terminal block, see the Wire not receive
figure at right. external stress.
For wire stripping, see
the figure at rigth. Use the specified
wire type for all
connecitions.
Gas pipe Wire retaine
insulation Liquid pipe Strip wire and this point.
insulation Excessive strip length may cause
Finishing tape Drain hose electrical shock or leskage. Shape wires so that the
service lid fits securely.
Be sure to estabish. Do not earth the utiilty pipe, arrester, or telephone earth.
6 DRAIN WORK
If the drain port is covered by a mounting base or floor surface, place additional foot bases
of at least 30 mm in height under the outdoor unit's feet.
In cold areas, do not use a drain hose with the outdoor unit. (Otherwise, drain water may
freeze, impairing heating performance.)
After trial operation is complete, set the temperature to a normal level (26 to 28C).
For protection, the unit disables restart operation for 3 minutes after it is turned off.
(3) Carry out the test operation in accordance with the Operation Manual to ensure that
all functions and parts, such as louver movement, are working properly.
* The air conditioner requires a small amount of power in its standby mode. If the system
is not to be used for some time after installation, shut off the circuit breaker to eliminate
unnecessary power consumption.
* Ifrestore
the circuit breaker trips to shut off the power to the air conditioner, the system will
the original operation mode when the circuit breaker is opened again.
Test Items
Symptom
Test Items (diagnostic display on RC) Check
Indoor and outdoor units are installed properly on solid bases. Fall, vibration, noise
No refrigerant gas leaks. Incomplete cooling/
heating function
Refrigerant gas and liquid pipes and indoor drain hose Water leakage
extension are thermally insulated.
Draining line is properly installed. Water leakage
System is properly earthed. Electrical leakage
The specified wires are used for interconnecting wire Inoperative or burn
connections. damage
Indoor or outdoor unit's air intake or exhaust has clear path of air. Incomplete cooling/
Shut-off valves are opened. heating function
Indoor unit properly receives remote control commands. Inoperative
1P064018-1B
Safety Precautions
Read the following warnings and cautions
carefully before operating the system and
WARNING
use it correctly. Failure to follow a warning is very likely to
This manual classifies the precautions to the result in such grave consequences as death or
serious injury.
user into two categories on the right.
Be sure to follow all as they are all important
to ensure safety. CAUTION
After reading this manual, keep it in a place Failure to follow a caution may result in
easily accessible to the user for future serious injury or property damage, and in
reference. certain conditions, may result in a grave
consequence.
WARNING
Do not expose your body to the cool (heat) air for a long time, do not cool (heat) the room too much.
It will affect your physical conditions and cause health problems.
Do not put a finger, a rod or other objects into the air outlet or inlet.
As the fan is rotating at a high speed, it will cause injury.
Do not attempt to repair, relocate, modify or reinstall the air conditioner by yourself.
Incorrect work will cause electric shocks, fire etc. For repairs and reinstallation, consult the shop
where you bought the air conditioner.
If anything abnormal such as a burning smell occurs, stop the operation immediately
and turn the breaker OFF.
Continued abnormal operation will cause troubles, electric shocks, fire etc. If anything is
abnormal, consult the shop where you bought the air conditioner.
If the air conditioner is not cooling or heating properly, the refrigerant may be leaking,
so see the dealer where the unit was purchased. Check with a qualified repairman
before attempting any repairs, which might accompany addition of refrigerant.
The refrigerant used in the air conditioner is safe. Although leaks should not occur, if for some
reason any refrigerant happens to leak into the room, make sure it does not come in contact with
any flame, such as fan heaters, kerosene heaters, or gas ranges, as this may result noxious
substances being generated.
CAUTION
Do not use the air conditioner for preservation purposes.
Do not use it for preserving precision instruments, foods, plants, animals, works of fine arts etc.
Performance or quality may deteriorate and animal or plant life may be shorter.
Before cleaning, be sure to stop the operation and turn the breaker OFF.
As a fan is rotating at a high speed, cleaning during operation may cause injury.
After a long use, check the unit stand and fittings for damage.
The unit may drop and cause injury if damage is left unrepaired.
Do not stand or sit on the outdoor unit. Do not place any object on the unit.
The object or the person may fall down or drop, causing injury.
Do not place under the indoor or outdoor unit anything which must be kept away from moisture.
Indoor unit : moisture in the air may condense and drip in certain conditions.
outdoor : during cooling operation, condensation may drip from the piping connections.
Do not place a burning appliance in places exposed to the air flow from the unit or
under the indoor unit.
It may cause incomplete combustion or deformation of the unit from heat.
Do not allow children to mount on the outdoor unit or avoid placing any object on it.
Falling or tumbling may result in injury.
Installation
WARNING
Do not attempt to install the air conditioner by yourself.
Consult the service shop or a qualified technician.
Incorrect work will result in water leakage, electric shocks or fire. For installation, consult the
service shop where you bought the unit or a qualified technician.
CAUTION
Depending on the environment, an earth leakage breaker must be installed.
Lack of an earth leakage breaker may result in electric shocks.
Do not install the air conditioner in places where flammable gas may leak.
If leaked gas should accumulate near the unit, fire may occur.
Do not connect the air conditioner to a power supply different from the specification.
It may cause trouble or fire.
Installation site
To install the air conditioner in the following types of environments, consult the shop.
Places with an oily ambient or where steam or soot occurs.
Salty environment such as coastal areas.
Places where sulfide gas occurs such as hot springs.
Places where snow may block the outdoor unit.
The drain from the outdoor unit must be discharged to a place of good drainage.
Electrical work
For power supply, be sure to use a separate power circuit dedicated to the air
conditioner.
System relocation
Relocating the air conditioner requires specialized knowledge and skills. Please
consult the shop where you bought the air conditioner if relocation is necessary for
moving or remodeling.
Names of Parts
Indoor unit
Air purifying filter Air inlet
Air purifying filters are
attached to the inside
of the air filters.
Front grille
Grille tab
DAIKIN
Diffuser
Control panel
Opening the front grille
Cleaning lamp
How to open the front grille : (See page 8.) reset button
Push this button
CAUTION to turn the
CLEANING lamp
Before opening the front grille, be sure to off.
stop the operation and turn the breaker
OFF. If the power is on, the fan may rotate
inside and may cause injury. Receiver:
It receives signals from the remote controller.
When the unit receives a signal, you will hear
a short beep.
ON/OFF switch
Push this switch once to start operation. Push once again
to stop it.
The operation mode refer to the following table.
Mode Temperature setting Air flow rate
FT COOL 22C AUTO
FTY AUTO 25C AUTO
This switch is useful when the remote controller is missing.
Names of Parts
Remote controller
Transmitter
Display It sends signals to the indoor unit.
Open It displays the
the current settings.
cover. (In this illustration,
each section is
shown with all its
displays ON for the
ON
purpose of
explanation. Some
C
TEMPERATURE
models may not
adjustment buttons
show all its
indications.) It changes the temperature
setting.
AMPM AMPM
POWERFUL button
(See page 11 ON/OFF button
POWERFUL Operation) Press it once to start operation.
ON/OFF To stop it, press it once again.
MODE selector button POWERFUL TEMP
It selects the operation mode. FAN setting button
<FT> <FTY> It selects the air flow rate setting.
: DRY : AUTO MODE FAN SWING
: COOL : DRY SWING button
: FAN : COOL (See page 10 Adjusting the Air
: HEAT Flow Direction)
ON CANCEL
ON TIMER button TIMER CANCEL button
OFF
(See page 12 Timer Operation)
TIMER It cancels the timer setting.
<ARC423A17, ARC423A18>
Outdoor unit
Air inlet Earth terminal
(Back and side) It is inside of this part.
Refrigerant piping
and inter-unit cable
3 Receiver
1
To fix the remote controller
holder on the wall
1 Choose a place from where the signals
reach the unit.
1 Press with a finger and slide the front
cover to take it off.
2 Fix the holder to a wall, a pillar, etc. with
the screws supplied with the holder.
2 Set two dry batteries (AAA). 3 Place the remote control in the remote
control holder.
3 Set the front cover as before.
This will cause the figures on the display
to flash. Set the clock at this point. Remote
controller
Set. holder
ATTENTION
About batteries
When replacing the batteries, use
batteries of the same type, and replace
To remove, pull it upwards.
the two old batteries together.
When the system is not used for a long
time, take the batteries out. ATTENTION
When the operation display screen of the About the remote controller
remote controller is hard to see and the Never expose the remote controller to
reception become hard, replace the direct sunlight.
batteries with new AAA batteries. Dust on the signal transmitter or receiver
The attached batteries are provided for the will reduce the sensitivity. Wipe off dust
initial use of the system. with soft cloth.
Signal communication may be disabled if
The usable period of the batteries may be an electronic-starter-type fluorescent lamp
short depending on the manufactured date (such as inverter-type lamps) is in the
of the air conditioner. room. Consult the shop if that is the case.
If the remote control signals happen to
operate another appliance, move that
appliance to somewhere else, or consult
the shop.
Display
AM
blinks.
Display
PM
Display
variable. available.
Display
<FT> <FTY>
Each pressing of the button advances the
mode setting in sequence. At smaller air flow rates, the cooling effect is
<FT> also smaller.
<FTY>
NOTE
<Note on HEAT mode operation>
Since this air conditioner heats the room by
ON/OFF taking heat from outdoor air to indoors, the
2 Press . heating capacity becomes smaller in lower
outdoor temperatures. If the heating effect is
insufficient, it is recommended to use another
heating appliance in combination with the air
Then OPERATION conditioner.
lamp lights up. The heat pump system heats the room by
circulating hot air around all parts of the room.
After the start of heating operation, it takes
some time before the room gets warmer.
To stop: In heating operation, frost may occur on the
outdoor unit and lower the heating capacity. In
ON/OFF that case, the system switches into defrosting
Press once again.
operation to take away the frost.
During defrosting operation, hot air does not
Then OPERATION lamp goes off. flow out of indoor unit.
<Note on DRY mode operation>
To change the temperature setting:
This operation dehumidifies the indoor air when
DRY or FAN mode AUTO or HEAT or COOL mode it is humid.
<Note on AUTO operation>
Press to raise the temperature and In AUTO operation, the system selects a
temperature setting and an appropriate mode
The temperature press to lower the temperature. (COOL or HEAT) based on the room
temperature at the start of the operation.
setting is not
Set to the temperature you like. The system automatically reselects setting at a
variable.
regular interval to bring the room temperature
to user-seetting level.
Display
Press SWING .
HEAT
Adjusting the
vertical blade (louvre)
10
POWERFUL
Operation
POWERFUL operation quickly maximizes the
cooling (heating) effect in any operation mode.
You can get the maximum capacity with a touch
of a button.
Pressing the (POWERFUL) button during
operation starts POWERFUL operation.
POWERFUL operation ends in 20 minutes.
Then the system automatically operates
again with the settings which were used
before POWERFUL operation.
During you use POWERFUL operation, the
other functions will not go on.
1 Press .
Display
Press .
11
Timer Operation
Timer functions are useful for automatically ON TIMER operation
switching the air conditioner on or off at night or in
the morning. You can also use OFF TIMER and Check that the clock is correct. If not, set the
ON TIMER in combination. clock to the present time (See page 8).
Display
If not, set the clock to the present time. (See page 8.)
AM
blinks.
1 Press OFF while the air conditioner
* Previous time setting
is operating. appears on display.
AM TIMER
blinks.
reaches the point you like.
* Previous time setting Every pressing of either button increases or
appears on display. decreases the time setting by 10 minutes.
Holding down either button changes the
2 Press until the time setting setting rapidly.
TIMER
3 Press ON once again.
reaches the point you like.
Every pressing of either button
Display
Press CANCEL . AM AM
12
13
<FTY>
14
Trouble Shooting
These cases are not troubles.
The following cases are not air conditioner troubles but have some reasons. You may just continue
using it.
Case Explanation
Operation does not start soon. This is to protect the air conditioner.
When ON/OFF button was You should wait for about 3 minutes.
pressed soon after operation
was stopped.
When the mode was reselected.
Hot air does not flow out soon The air conditioner is warming up. You should wait for 1 to 4 minutes.
after the start of heating (The system is designed to start discharging air only after it has reached
operation. a certain temperature.)
The heating operation stops The system is taking away the frost on the outdoor unit.
suddenly and a flowing sound is You should wait for about 3 to 10 minutes.
heard.
Mists come out of the indoor unit. This happens when the air in the room is cooled into mist by the cold
air flow during cooling operation.
The indoor unit gives out odour. This happens when smells of the room, furniture, or cigarettes are
absorbed into the unit and discharged with the air flow.
(If this happens, we recommend you to have the indoor unit washed
by a technician. Consult the service shop where you bought the air
conditioner.)
The operation stopped suddenly. For system protection, the air conditioner may stop operating on a
(OPERATION lamp is on) sudden large voltage fluctuation.
It automatically resumes operation in about 3 minutes.
15
Trouble Shooting
Check again
Please check again before calling a repair person.
Case Check
The air conditioner does not Hasnt a breaker turned OFF or a fuse blown?
operate. Isnt it a power failure?
(OPERATION lamp is off) Are batteries set in the remote controller?
Is the timer setting correct?
An abnormal functioning The air conditioner may malfunction with lightening or radio waves. Turn the
happens during operation. breaker OFF, turn it ON again and try operating the air conditioner with the
remote controller.
16
Trouble Shooting
Call the service shop immediately.
WARNING
When an abnormality (such as a burning smell) occurs, stop operation
and turn the breaker OFF.
Continued operation in an abnormal condition may result in troubles,
electric shocks or fire.
Consult the service shop where you bought the air conditioner.
If one of the following symptoms takes place, call the service shop immediately.
The power cord is abnormally hot or damaged.
An abnormal sound is heard during operation.
The safety breaker, a fuse, or the earth leakage
breaker cuts off the operation frequently. Turn the breaker
OFF and call the
A switch or a button often fails to work service shop.
properly.
There is a burning smell.
Water leaks from the indoor unit.
17
3P062628-7J
Installation
This product is available in two types. The KRP413A1S is for installation in a case independent of the indoor unit, and the KRP413A1 is for
installation within the indoor unit.
Local inter-unit Install the adaptor case assy as close to the indoor unit as possible.
Relay harness power cord, etc.
Removing case front
Case front
2 Components
Screw
Adaptor case assy Relay harness (approx. 0.8 m)
Adaptor PCB
(Adaptor (PCB) is attached in the adaptor case.) Screw cover
Installation manual
Wiring
2. KRP413A1
For this type, install the adaptor PCB within the indoor unit. The method of
installation and connection vary depending on the model of the air Screw
conditioner. See your air conditioner installation manual for details.
Screw cover
1 Components
Adaptor PCB Relay harness (approx. 0.25 m) 2 Using Velcro (to attach on the indoor unit)
Indoor unit
To prevent the adaptor case assy from falling, do not use the Velcro for
attaching it to a wall or other surface.
The specifications, designs, and information in this brochure are subject to change without notice.
ED 01-214A
Printed in Japan 05/2004 B AK