Professional Documents
Culture Documents
currently varying the grid resistance (from resistance. At 10.0 ohms grid resistance, the
0.1 ohm to 10 ohms) and one of the other pa- percent grid current ranged from 8.94% to
rameters. For each parametric analysis, the 8.98%.
maximum grid current was expressed as a per-
centage of the total substation bus ground Table 2
fault current.
Effects of Conductor Configuration
The effects of varying the conductor size Grid Current/Total Fault
and type of overhead ground wires and feeder Current (%)
Grid Resistance (ohms)
neutrals on grid current were studied in two Configuration 0.1 10.0
parts. In part 1, using a typical feeder neu- 10.64
86.87
tral of of 4/0 ACSR, the overhead ground wire D
(OHGW) was varied for conductor sizes and
types typical of transmission overhead ground
wires. As shown in Table 1, the percent grid
current ranged from 91.04% for a 3/8 HSS OHGW
at 0.1 ohm grid resistance, to 75.97% for a V1., 87 .27 10.74
7#8 CW OHGW at the same grid resistance. At
10.0 ohms grid resistance, the percent grid
current ranged from 12.06% for 3/8 HSS, to
8.19% for 7#8 CW. The range of conductor size
and type between 3/8 HSS and 7#8 CW is wide,
and the typical conductor currently used for a V2,i 87 .44 10.76
transmission line OHGW is usually in the range
of 3/8 HSS to 7#8 ALW.
Table 1
Effects of Overhead Ground Wire or Feeder Neutral
Conductor Size and Type Hil 81.47 8.94
from 7.50% for transmission spans of 80.47 m, tribution. Although not explicitly modelled,
to 10.64% for transmission span lengths of a variation of the soil resistivity is implied
482.8 m. For a transmission span length of in the variation of the grid and tower footing
482.8 m and a grid resistance of 10.0 ohms, resistances. All other parameters were based
the percent grid resistance ranged from 9.26% on typical data and/or choices which would
for a distribution feeder span length of 60.99 minimize the error introduced by not varying
m to 16.06% for a distribution feeder span of each paramater. Table 6 shows the assumed
321.87 m. For the same combinations of trans- values for the parameters not explicitly
mission line and distribution feeder span varied in the graphical analysis.
lengths and a grid resistance of 0.1 ohm, the
effect on the grid current was negligible. Table 6
on the ratio of the maximum grid current (IG) pute the ratio of local versus remote contrib-
to the total substation bus ground fault cur- utions for a fault at each voltage level and
rent (i.e., IT). use the case that results in the highest re-
mote or local fault current in amperes.
Using the Graphs
100.0
A
50.0 5.180
5.0
_
i[
Sl
I'-t4t
OLOCAL CONTRIBUTION j4t
A TOIER FOOTING RESISTANCE: '/4
10.0 . B TRANSM4ISSION -150.
FEEDER - 25n /6
IA/B A - TRANSMISSION LINES /8
a/8 - FEEDER LINES
/10
1/2
5.0 . 2/2 1.0
100.0
1.0
).5 1.0
Rg - GRID RESISTANCE ( n)
50.0
Figure 2. Percent grid current versus
substation grid resistance.
100.0 .
S
iF
50.0
10.0
A J/4
B XA /6
Ut /8
i/10
1/2
2/2 g
1/4 o
10.0 2/4. o
I TRA INSISSION 1001ja:
FEEDER 200
2/6
A/B A - # TRANSIRISSION LINES
2/8 -ll B - II FEEDER LIN4ES .i,i,i
5.0
1.0
O 0.5 1.0 5.0 10.0
R - GRID RESISTANCE (i)
l1;L
1l1
IV A
L For
Next,
distribution substations or
determine the appropriate
transmission
graph.
100.0
50.0
10.0
A
B
C.0
A
10.0
B
/2
3/4
t_7 5 |A/B 1/6
3/8
3/10
5.0o 1001
CONTRIBUTION
REMOTE CONIRIBUTION 1.0 X11
e 01 FOOSTINGRESISTANCE:
!TWER
LOCAL
TRANSMISSION *1
15.11
5/4 5.0 10.0
FEEDER -
2511 T" 5/6
A/B A - TRANSMISSION LINES
1
6/8
- IFEEDERLINES
6/10 Figure 8. Percent grid current versus
substation grid resistance.
0.5 .0 5.0
RG - GRID RESISTANCE (i;)
100.0
100.0
;z
50.0 a:
g
B
A -'-
10.0
,,
E 1g B/2 4
5.0
10.0 6/0
cc
/10
6/2
6/4
6/6
'5.0 t 6/8
6/10
-1-ft0101
1.0
TOI
R9 - GR1D RESISTANCE (}
AIE
50 R0l
It should be noted that
the use of current division results in a com-
puted GPR of only 2775.3*1.0 = 2775.3 volts,
instead of 9251 volts computed using the total
fault current.
O0A -IN
TRAN.4SSON
8lll,lj:,lliQ
501 1 AL COTIBTO
150
l,i, ,,:
100.0
50.0
substation grid resistance.
l il,l0yilj, i]'
16/0
/0
cause the average tower footing resistance is
75 ohms for transmission lines and 150 ohms
for distribution feeders, Figure 11 was used.
50.0
10.0
5.0
1.0
0n
I r
-
O.
I
1X00 REMOTE COTRIBUTION
750 LOCAL
TOWER FOOTING
A/B AAX I
7
CONTRIBUJTION
TRANSMISSION
AESISTANCE.
1fk
TRANSMISSION
FEEDER LINES
100.0
substation grid resistance.
ft
LINES
li.
0.5
Rg
. .....
....
-
STI+{!F-1H.t
t.,',!:,1, r!
|i"
1,
6'.
!t,,ilj,
,'
114fl1:,41 'I
GRID RESISTANC
Si
,,
1l'}';z0l'1 1'II
fl
1.0
i,
I,
1'
(l)
:,
H
"
v1,q,i
'
'.'N
K
5.0
IW
I
lA
i B
I
2/0
4/0
6/0
100/0
i,Ns,.,}. 1o0/
10.0
14/0
16/0
10.0
11/0
25% REMOTE CONTRIAUITON ,
5.0
750 LODCAL CONTRIBO0TION O/
TOWER FOOTING RESISTANCE.
I TRANSMISSION -100, 12
A/B A TRAO4SMISSION LINES
A - I FEEDER LINES
S4
1.0
Figure 13. Percent grid current versus
substation grid resistance.
Figure 11. Percent grid current versus Figure 11 was the closest available curve
substation grid resistance. which included the effects of both remote and
local fault current contributions. In this
Next, consider the more complex example case, the four feeder neutrals are assumed to
of Figure 15, which contains both remote and have the same effect as transmission line
local sources of zero-sequence fault current. overhead ground wires on the ground fault cur-
Assume that a conventional fault analysis re- rent division. Thus, for a grid resistance of
sults in a total 230kV bus ground fault cur- 5.0 ohms the appropriate curve gives IG/IT =
rent of 9183.5A, with 7162.5 amperes 15%. Then,
contributed by remote sources and 2035.1 am- IG = (9183.5)(0.15) = 1378 amperes.
peres contributed by the local source (trans- This compares with the value of 1220.0 amperes
former). Because the ratio of remote vs local determined using SMECC and the actual system
fault current contribution is 78/22, and be- parameters.
731
Summary
A parametric analysis was performed on the
parameters affecting ground fault current di-
115kV vision in order to determine the critical pa-
A rameters. Then, a method of graphically
cY-f determining the maximum grid current for use
1 in designing substation grounding systems was
_- 12.47kV developed. The curves were based on results
using the SMECC program developed for EPRI.
The graphical analysis is not intended as an
accurate replacement for computer program
analysis (such as SMECC), but rather it is in-
tended as a means for quickly determining a
Figure 14. System configuration for reasonable approximation of the maximum grid
Example 1. current for the preliminary grounding system
design. In some cases, the graphical analysis
will result in sufficient accuracy to make
more exact analysis unnecessary.
Conclusions References
In addition to the observations made in
the parametric analysis, three significant ob- 1. IEEE Standard 80-1986, IEEE Guide for
servations were made during the split factor Safety in Substation Grounding by Insti-
analysis: tute of Electrical and Electronic Engi-
neers, Inc., New York, 1986.
1. The first, and most obvious observation is 2. "Analysis Techniques for Power Substation
that the system and conductor parameters Grounding Systems," EPRI Final
have more influence on the split factor Report
EL-2682, Vol. 1, October 1982.
IG/IT for higher grid resistances. For
very small grid resistances, most of the 3. "Transmission Line Grounding," EPRI Final
ground fault current not circulating Report EL-2699, Vol. 1, October 1982.
through the grid to a local source returns
to its source through the grounding system 4. S. A. Sebo, "Zero-Sequence Current Dis-
regardless of how many alternate ground tribution Along Transmission Lines," IEEE
return paths exist. Transaction Power Apparatus and Systems,
Vol. PAS-88, pp. 910-919, June 1969.
2. An unexpected observation was that, in
some cases, the fault location resulting 5. F. Dawalibi, "Ground Fault Current Dis-
in the maximum grid current changed from tribution Between Soil and Neutral Conduc-
being a line fault to a substation bus tors," IEEE Transactions Power Apparatus
fault. This was apparently due, in large and System, Vol. PAS-99, No. 2, pp.
part, to the effect of current which is 452-461, March/April 1980.
mutually induced in the alternate ground
return path from fault current flowing in 6. F. Dawalibi, D. Mukhedkar and D. Bensted,
the phase conductor of the faulted line. "Soil Effects on Ground Fault Currents,"
IEEE Transactions Power Apparatus and Sys-
3. Finally, for the range of grid resistances tems, Vol. PAS-100, pp. 3442, July 1982.
studied, the substation grid resistance
had negligible effect on the total ground 7. F. Dawalibi and D. Mukhedkar, "Ground
fault current. It is expected that this Fault Current Distribution in Power
observation might not hold true for lower Systems-The Necessary Link", paper A77
voltage levels where a specific resistance 754-5 presented at the IEEE Summer Power
value would be a more significant portion Meeting, Mexico City, 1977.
732
8. R. Rudenberg, "Grounding Principles and SHASHI G. PATEL (SM'84) was born in Varoka
Practices-i, Fundamental Considerations on Ba, Fiji Islands on March 12, 1943. He re-
Grounding Currents", Electrical Engineer- ceived the B. S. degree in Electrical Engi-
ing, Vol. 64/No. 1, pp. 1-13, January neering from M. S. University of Baroda,
1945. India and M. S. degree in Electrical Engineer-
ing from Georgia Institute of Technology,
9. P. G. Laurent, "Les Bases Generales de la Atlanta, Georgia in 1965 and 1975, respec-
Technique des Mises a la Terre Dans les tively.
Installations Electriques", Blltn. de la
Societe Francaise des Electriciens, Vol. From 1965 1967 he was with Gujarat Elec-
to
1, Ser. 7, pp. 368-402, July 1951; (Eng- tricity Board, India as Deputy Engineer. He
lish translation available in Appendix was employed as Power System Engineer by
9.2). Bonneville Power Administration, Portland,
Oregon during summer of 1969. Since 1970, he
10. Reinhold Rudenberg, "Distribution of has been employed by Georgia Power Company and
Short-Circuit Currents in Ground", is presently a staff service engineer.
11. "Computation of Zero-Sequence Impedances Mr. Patel is a senior member of IEEE Power En-
of Power Lines and Cables Engineering Re- gineering Society. He is also a member of Eta
port No. 37," Joint Subcommittee on Devel- Kappa Nu. He is presently serving actively in
opment and Research of EEI and Bell several grounding related working groups of
Telephone System, July 22, 1936. IEEE Substation Committee. He is a registered
Professional Engineer in the state of Georgia.
12. Luke Yu, "Determination of Induced Cur-
rents and Voltages in Earth Wires During
Faults," Proceeding of IEEE, Vol. 120, No. JENNIFER G. MYERS Was born in Muncie,
6, June 1973, pp. 689-692. Indiana, on October 28, 1958. She received an
A. S. degree in Electrical Engineering Tech-
13. J. E. Clem, "Reactance of Transmission nology from Murray State University in Murray,
Lines With Ground Return," AIEE Trans- Kentucky in 1979. She is currently attending
actions Power Apparatus and Systems, Vol. the University of Alabama in Birmingham work-
50, pp. 901-918, September 1931. ing toward a B. S. degree in Electrical Engi-
neering.
14. C. F. DeSieno, P. P. Marchenko and G. S.
Nassell, "General Equations for Fault Cur- Mrs. Meyers joined Southern Company Services
rents in Transmission Line Ground Wires," in 1979 as a technical aide in the System
IEEE Transactions Power Apparatus and Planning Department. She is presently em-
tems, Vol. PAS-89, pp. 1891-1900, ployed as an assistant engineering analyst in
November/December 1970. the Transmission Systems Applications Section
of the Electrical Design Technical Services
15. "Currents in Earth Wires at the Top of Department.
Pylons and Their Effect on the Potentials
of the Pylons and Stations in the Neigh-
borhood of a Point of Short-Circuit to DAVID LANE GARRETT (S'75-M'76) was born in
Earth," Contribution No. 78, CCITT, Study Birmingham, Alabama on January 10, 1954. He
Group V, November 1963. received the B. S. and M. S. degrees in Engi-
neering from the University of Alabama in
16. J. R. Carson, "Wave Propagation in Over- Birmingham (UAB) in 1976 and 1978, respec-
head Wires with Ground Return," Bell Sys- tively.
tem Technical Journal, Vol. 5, 1926.
In 1974 he joined Southern Company Services as
17. J. Endrenyi, "Analysis of Transmission a co-operative education student and as an en-
Tower Potentials During Ground Faults," gineer in 1976. He is presently a senior en-
IEEE Transactions Power aratus and gineer in the Transmission Systems
tems, Vol. PAS-86, pp. 1274-1283, October Applications Section of the Electrical Design
1967. Technical Services Department.
18. J. Endrenyi, "Fault Current Analysis for Mr. Garrett is a registered Professional Engi-
Substation Grounding Design," Ontario neer in the State of Alabama and is presently
Hydro Research Quarterly, 2nd Quarter, secretary of the IEEE Working Group to revise
1967. the Guide for Safety in A-C Substations
(IEEE-80).
19. R. Verma and D. Mukhedkar, "Ground Fault
Current Distribution in Substation, Towers
and Ground Wire," IEEE Transactions Power
Apparatus and Systems, Vol. PAS-98, pp.
724-730, May/June 1979.