You are on page 1of 6

Rashid Mubarak Zaid Al-Kuari

ALSAD
Proposed B+G+4 Residential Apartments
Emergency Light Lux Tets reading report
Location Time Average reading Measured at G.F Level

BF Parking area 00:05 11

GF Lobby 00:15 11

GF Stair Case 00:20 10.9

1st Floor Lobby 00:25 10.9

1st Floor Stair Case 00:30 10.9

2nd Floor Lobby 00:35 10.8

2nd Floor Stair Case 00:40 10.8

3rd Floor Lobby 00:45 10.8

3rd Floor Stair Case 00:50 10.8

4th Floor Lobby 00:55 10.9


4th Floor Stair Case 01:00 10.9

Tested By Witnessed by Witnessed/Approve By


Company Fire Safety Distance Studio - Arts engineering consulting Abd Elrahman Adel Shehata
Name Mohsen Saad
Sign
Date
INITIATING DEVICE
SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

This form is a supplement to the System Record of Inspection and Tes


It includes an initiating device test record.
This form is to be completed by the system inspection and testing contractor at the time of the inspect
it shall be permitted to modify this form as needed to provide a more complete and/or c
Insert N/A in all unused lines.
Inspection/Test Start Date/Time: __21/11/2016____ Inspection/Test Completion Date/Time: ___
Number of Supplemental Pages Attached: ________________

1. PROPERTY INFORMATION
Name of property: Rashid Mubarak Zaid Al-Kuari / Proposed B+G+4 Residential Apartments
Address: __________________________ALSAD__________________________

2. INITIATING DEVICE TEST RESULTS


Device Type Address Location
MCPs Loop 1 Basement Floor
Heat Detectors Loop 1 Basement Floor
Smoke Detectors Loop 1 Basement Floor
MCPs Loop 1 Ground Floor
Heat Detectors Loop 1 Ground Floor
Smoke Detectors Loop 1 Ground Floor
MCPs Loop 1 First Floor
Heat Detectors Loop 1 First Floor
Smoke Detectors Loop 1 First Floor
MCPs Loop 2 Second Floor
Heat Detectors Loop 2 Second Floor
Smoke Detectors Loop 2 Second Floor
MCPs Loop 2 Third Floor
Heat Detectors Loop 2 Third Floor
Smoke Detectors Loop 2 Third Floor
MCPs Loop 2 Fourth Floor
Heat Detectors Loop 2 Fourth Floor
Smoke Detectors Loop 2 Fourth Floor
MCPs Loop 2 Roof Floor
Heat Detectors Loop 2 Roof Floor
Smoke Detectors Loop 2 Roof Floor

See Main System Record of Inspection and Testing for additional information, certi
NITIATING DEVICE
ECORD OF INSPECTION AND TESTING

s a supplement to the System Record of Inspection and Testing.


It includes an initiating device test record.
inspection and testing contractor at the time of the inspection and/or test.
fy this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
__21/11/2016____ Inspection/Test Completion Date/Time: ___21/11/2016_
Number of Supplemental Pages Attached: _________________

Test Results
Basement Floor
Basement Floor
Basement Floor
Ground Floor
Ground Floor
Ground Floor
First Floor
First Floor
First Floor
Second Floor
Second Floor
Second Floor
Third Floor
Third Floor
Third Floor
Fourth Floor
Fourth Floor
Fourth Floor
Roof Floor
Roof Floor
Roof Floor

and Testing for additional information, certifications, and approvals.


NOTIFICATION APPLIANCE
SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

This form is a supplement to the System Record of Inspection and Testing.


It includes a notification appliance test record.
This form is to be completed by the system inspection and testing contractor at the time of the inspection and/or test.
it shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Inspection/Test Start Date/Time: __21/11/2016____ Inspection/Test Completion Date/Time: ___21/11/2016_
Number of Supplemental Pages Attached: _________________

1. PROPERTY INFORMATION
Name of property: Rashid Mubarak Zaid Al-Kuari / Proposed B+G+4 Residential Apartments
Address: __________ALSAD______

2. NOTIFICATION APPLIANCE TEST RESULTS


Appliance Type Location/Identifier Test Results
Horn&Strobe 1 BF Parking Area
Horn&Strobe 2 BF Parking Area
Horn&Strobe 3 BF Parking Area
Horn&Strobe 4 GF Lobby
Horn&Strobe 5 GF Flat 1
Horn&Strobe 6 GF Flat 2
Horn&Strobe 7 GF Flat 3
Horn&Strobe 8 First Floor Lobby
Horn&Strobe 9 First Floor Flat 1
Horn&Strobe 10 First Floor Flat 2
Horn&Strobe 11 First Floor Flat 3
Horn&Strobe 12 First Floor Flat 4
Horn&Strobe 13 Second Floor Lobby
Horn&Strobe 14 Second Floor Flat 1
Horn&Strobe 15 Second Floor Flat 2
Horn&Strobe 16 Second Floor Flat 3
Horn&Strobe 17 Second Floor Flat 4
Horn&Strobe 18 Third Floor Lobby
Horn&Strobe 19 Third Floor Flat 1
Horn&Strobe 20 Third Floor Flat 2
Horn&Strobe 21 Third Floor Flat 3
Horn&Strobe 22 Third Floor Flat 4
Horn&Strobe 23 Fourth Floor Lobby
Horn&Strobe 24 Fourth Floor Flat 1
Horn&Strobe 25 Fourth Floor Flat 2
Horn&Strobe 26 Fourth Floor Flat 3
Horn&Strobe 27 Fourth Floor Flat 4
Horn&Strobe 28 Roof Floor

See Main System Record of Inspection and Testing for additional information, certifications, and approvals.
INTERFACE COMPONENT
SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

This form is a supplement to the System Record of Inspection and Testin


It includes an interface component test record for circuit interfaces, signaling line circuit int
fire alarm control interfaces.
This form is to be completed by the system inspection and testing contractor at the time of the insp
it shall be permitted to modify this form as needed to provide a more complete and/or cl
Insert N/A in all unused lines.
Inspection/Test Start Date/Time: __21/11/2016____ Inspection/Test Completion Date/Time: ___
Number of Supplemental Pages Attached: _________________

1. PROPERTY INFORMATION
Name of property: Rashid Mubarak Zaid Al-Kuari / Proposed B+G+4 Residential Apartments
Address: __________________________ALSAD___________________________________________

2. INTERFACE COMPONENT TEST RESULTS


Interface Component Type Address Location
Relay Module Elevator to Ground Floor Machine Room
Relay Module Elevator to First Floor Machine Room
Monitor Module Electrical Motor Pump Run Pump Room
Monitor Module Electrical Motor Pump Fault Pump Room
Monitor Module Electrical Motor Pump Reverse Pump Room
Monitor Module Diesel Motor Pump Run Pump Room
Monitor Module Diesel Motor Pump Fault Pump Room
Monitor Module Diesel Motor Pump Battery Failure Pump Room
Monitor Module Flow Switch Hose Reel Cabinet 1st Floor
Monitor Module Flow Switch Hose Reel Cabinet 2nd Floor
Monitor Module Flow Switch Hose Reel Cabinet 3th Floor
Monitor Module Flow Switch Hose Reel Cabinet 4th Floor
Monitor Module Flow Switch Hose Reel Cabinet Roof Floor

See Main System Record of Inspection and Testing for additional information, certifications, and approvals.
AND TESTING

of Inspection and Testing.


signaling line circuit interfaces, and

r at the time of the inspection and/or test.


more complete and/or clear record.

etion Date/Time: ___21/11/2016_


__________

Test Results
ine Room
ine Room
mp Room
mp Room
mp Room
mp Room
mp Room
mp Room
abinet 1st Floor
abinet 2nd Floor
abinet 3th Floor
abinet 4th Floor
abinet Roof Floor