Professional Documents
Culture Documents
3, March 1981
A NEW ALGORITHM OF AN ACCURATE FAULT LOCATION FOR EHV/UHV TRANSMISSION LINES:
PART I - FOURIER TRANSFORMATION METHOD
Abstract - A fault location algorithm based on the Digital computer simulations of the fault location
Fourier analysis of a faulted network is presented. are extensively carried out to study the effects of
The algorithm embodies an accurate location by measur- such factors as a transmission line loss, load
ing only a local end data. Its fundamental theory is characteristics and waveform distortion on the algo-
studied through digital computer simulations on a model rithm. With the practical applications in mind, fast
power system. With the practical applications in mind, algorithms such as a half-cycle and a truncated Fourier
fast algorithms are then examined. Finally, the transform, and a Walsh transform are then examined.
experimental results of a computerized fault locator Finally, a computerized fault locator is tested on an
applied to a laboratory system are presented. artificial transmission line connected to a 4 kVA
generator. The experimental results are also discussed.
INTRODUCTION In the first part of the paper, the superposition
law is applied to the steady-state fault analysis. As
The fault location scheme widely used now relies the law is also applied to the transient-state fault
its operating principle on the traveling wave propaga- analysis, another solution based on the Laplace trans-
tion ona transmission line. One approach is to observe formation is possible to the fault location problem.
the time at which a locator of each terminal detects The Laplace transformation method will be fully analyz-
the first incoming fault surge from a faulted point. ed in the part II of the paper.
Another one is to transmit an electrical pulse into the
line, and to measure the period from emission to return FUNDAMENTAL THEORY
of the pulse, thus known as a pulse radar method. Both Single-Phase Line
methods depend upon the traveling wave propagation,
which is a complex phenomena difficult to analyze per- Consider a midway fault at the point F which is x
fectly. The propagations are affected by the system km away from S on a transmission line SR in Fig. 1 (a).
parameters and network configurations. Therefore, The law of superposition in the linear network theory
those fault locators would have to solve problems in separates a faulted network into a pre-fault and pure-
order to get a higher accuracy than they have now. fault ones, which are given in Fig. 1 (b) and (c) res-
Computer relays for distance protection [1][2] can pectively. Let VF be the voltage vector at F, and let
be applied to the fault location, since they directly IF be the current vector at the fault resistance RF in
measure an impedance, R + jX, to a faulted point. The the faulted network. Then,
measured reactance provides an exact distance to the
faulted point, when a fault resistance is zero. The VF = RF.IF
fault resistance, however, is not zero in actual faults,
causing the impedance R+jX to deviate from its true = -RF(IiS + ItR) (1)
value. Therefore, the computerized distance relays
would be susceptible to failure in measuring the exact where IFS is the line current at F flowing to S and I"R
impedance to the fault. is that to R, both of which are defined in the pure-
S. E. Westlin and J. A. Bubenko recently presented fault network. Define a new variable K(x) by
an algorithm for the fault location [3]. They applied
the Newton-Raphson method to the non-linear algebraic
equations to solve the distance to the fault. Their s R
scheme is superior to the others, since all variables Zs Vs lVR ZR ER
they use are locally available except the source imped- is IFS IFR
ance at the remote end. Their theory is sound and
correct, but it seems impractical to update the source IF RF
impedance of the remote end every time a system change
occurs.
(a) a faulted netwvork
Applying the law of superposition to the steady-
state fault analysis, the authors obtain an algebraic s F R
Distance(Km)
[Primary' Digita I Orthogonal Solution of fLocated'
Data Filter
Non -lIinear jDistance,-
Transform
Equation 67.
<-1.0 Hz
33. T
-100- I
10.
Iteration
f (Hz) 2 3
the fault resistance, and the characteristic has been .40.44 48 .52 .56 .60 .64 .68 72 .76 .80
confirmed through the digital simulation. -33., Ti me
xlOsec
Effect of Line Loss -67
The algorithm assumes that K(x) of the eqn. (2) be
a real value. The assumption seems unsatisfied when a -1009
transmission line loss is taken into account. Fig. 8
compares the result of a loss-less line case with that
of a lossy line. For the lossy case, x is 10.85 km and Fig. 8 Distance located in a lossy line case and its
a is 0.32 km. This is a single-phase fault case, in comparison with a loss-less line case
which the R/X ratio of mode 0 is larger than that of
any other mode. The mode 0 circuit is not related in a
multiple-phase short circuit fault. Therefore, the
line loss will not affect the accuracy of the fault
location significantly. Distance (Kin)
Effect of Load Characteristic
100 -
zJ Xi nductive oad
The source impedance must be purely inductive to 67. resistivelood
ensure an accurate fault location. A resistive load
(= RL + jXL) at the remote end is studied. The located 33.
distance converges to the value slightly different from Fault
the true one. Fig. 9 illustrates it. For the double- O. 404, .4 .8
phase fault of Fig. 9, x is 12.92 km and a is 0.35 km. 40 44 48 .52 .56 .60 .64 .68 .72 76 .80
Thus, the type of source impedance at the local and Time
remote end must be carefully studied whether they -33.-
satisfy the condition on K(x) or not, prior to applying xlOsec
the algorithm to the fault location. -67
Effect of Waveform Distortion -100O
The waveform distortion is created by non funda-
mental frequency components in the voltage and current, Fig. 9 Effect of load characteristic on location accu-
which are caused by the transient phenomena due to a racy
fault. The pre-filters of different cut off frequen-
cies {fCI are used to study the effect. Fig. 10 shows
the correlation of x and a for the cutoff frequency.
As predicted, x is uncorrelated with fc but a increases
along with fc The filtered data is sampled every 1.0
msec for the Fourier transformation. According to Fig.
10, the instability of x appears beyond 500 Hz, which (Km) (Km)
is the half of the sampling frequency. Therefore, it
is caused by the frequency folding error in digital
signal processing. The stability will be guaranteed by
choosing a pre-filter appropriately.
10.- 2.
Distance(Km) 0'
100-
'1
RFz00=RlOf
67.- 5. 1.
33.-
Fault /y
I00-
4044 .48 .52 .56 .60 .64 68 72 .76 .80
-33. Time -0 f (Hz)
xlOsec 0. 2 3 4 5 6 789 23
lev
4 5 6789
-67- 02
-100.J
Fig. 10 Correlation of x (average distance) and a
Fig. 7 Distance located for a single phase fault with (standard deviation) versus fc (cutoff fre-
RF = 10.0 ohm at F3 quency)
1320
FAST ALGORITHMS where we (= 2f e) is an arbitrary angular frequency,
and T (= L/R) is the time constant of a transmission
The developed algorithm basically consists of two line. As shown in the eqn. (21), the integral inter-
numerical computations. One is the Fourier transforma- val is chosen as a half cycle.
tion of voltage and current waveforms, and the other is It. should be noted that the angular frequency we
the solution of non-linear algebraic equations. Among is selected at an arbitrary value. In the paper, we is
them, fast algorithms of the Fourier transformation are set to 80 (namely fe = 40.0 Hz). The TFT algorithm is
studied through the digital computer simulations. used for the Fourier transformation. Fig. 12 illus-
trates a simulation result. The solution by the TFT
Half-cycle Fourier Transformation converges within a half cycle to the final value, which
is also the solution by the OFT. As the TFT algorithm
One cycle Fourier transformation (- OFT) defined provides an accurate and stable solution, it also con-
by the eqn. (17) has been used in the digital computer tributes to the acceleration of the fault location.
simulations of the paper. F(jwo) of the eqn. (17) has
been evaluated at the angular frequency of wo = 2wfo,
where fo is the system frequency. A half-cycle.Fourier .Distance(Km)
transformation (=HFT) is defined here by the eqn. (19). IOQ " OFT
t TFT \/
F(jOW) = f f(u)eJ du (19)
T 33.]
t-2-
Fault
T = 2n/wo (20) 40 44 .48 .52 .56 .60 .64 .68 .72 .76 .80
The HFT algorithm is substituted into the Fourier -33. Time
-I
transformation block of Fig. 2. In Fig. 11, the result xK0sec
of the HFT algorithm is compared with that of the OFT -67
one. While the distance to which both algorithms con-
verge are almost equal with each other, the HFT algori-
thm converges two times faster than the OFT does. As
any other differences are not noticed, the HFT algori-
thm is effective to speed up the fault location. Fig. 12 Distance located by TFT algorithm and its com-
parison with OFT algorithm
Distance(Km)
100 r--
I OfT
67- H Walsh Transformation
HFT\,
33- \ To speed up the orthogonal transformation, the
Fault Walsh function is frequently used. In the relaying
_ |
field, it was applied to the distance protection [6].
40 44 .48 .52 .56 .60 .64 .68 72 .76 .80 An arbitrary function f(t) is expanded as follows:
-33. Time
xI co
xl0sec f(t) = E wk wal(k,t) (23)
-67 k=O
-oo J
For fault location, the voltage and current are expand-
ed by wal(1,t) and wal(2,t). The two functions are
Fig. 11 Distance located by HFT algorithm and its com- shown in Fig. 13. As no multiplications are needed and
parison with OFT algorithm only additions are used, the computation time for the
orthogonal transformation is greatly reduced. The
solution by the Walsh method is shown in Fig. 14. It
t
Q0
V(iwe) = f v (u) e eu du (21) .0 .05 .10 .15 .20 Time
T -xs
X10sec
and for a current i(t), - I
t
T WOI ( 2. )
I (i We) = f, i(u)ei e du -r[i(t -)e -.,e (t )
-
- -
LF_ _T
-
i(t)e-jwet Ml + iw e T) (22) Fig. 13 Curves of wal(l,t) and wal(2,t)
1321
67.- 1
x(o) = uOA/Q)-c(O) = 1.135 x 10 3 rad/km
*1
OFT (1) = w0/o().c(l) = 0.996 x 10 -3 rad/km
,Fault Z(0) = A (0)/c () = 251.0 ohm
v.- 40
4044 48 52 .56
.52 6'0 64 6~8 .76 80 z(i) = Vk(l)/c(l) = 114.0 ohm
-33. Time
Fig. 16 shows a location process, in which a fault is
xVsec initiated at t = 0.0 sec. The located distance con-
-67 verges to 48.7 km for a fault which is actually 50.0 km
away from the relaying point. The oscillogram recorded
-I00.j in this case is shown in Fig. 17. Other faults have
been located within the same degree of accuracy as the
case presented here.
Fig. 14 Distance located by Walsh algorithm and its
comparison with OFT algorithm CONCLUSIONS
An algorithm based on the Fourier analysis has
been developed for an 'accurate fault location in an
EHV/UHV transmission line. The algorithm has made it
is almost the same distance as one by the OFT algori- possible to locate a fault accurately with locally
thm. The standard deviation a is 0.64 km and slightly available data set, and without being affected by a
large, since the first two coefficients w, and w2 of fault resistance. Digital computer simulations and
the eqn. (23) are used, and the other coefficients are -laboratory tests have confirmed'these properties. With
neglected. It is expected that the expansion to the practical applications in mind, fast algorithms such as
higher order will make the solution more stable. The a half-cycle Fourier, a 'truncated Fourier, and a Walsh
optimum order should be 'determined in a trade off transformation have been studied, providing promising
between accuracy and computation'time. results.
The scheme has needed a strong power tor numerical
calculations, and it therefore will be suitable for
digital processor use, that is computer relaying use.
LABORATORY TESTS
Outline of Laboratory
A series of experiments in a mini-scale power 25Kml 25Km 25Kmn '25Km' 220V
Lin' Lin9 Line Lino Bus Line
system is carried out to test the basic algorithm for Unit Unit 'Unit Unit
actual fault locations. Fig. 15 shows the facilities
for the experiment. A three-phase single-circuit line 220V 2M020 l220/220V
is connected at each end to a 10 kVA power transformer, 4kVA lOkVA AMP ------------ lOkY.A
whose rated voltage is 220/220 V. One transformer is Generator Tran. Transformer
. _
_ _._ _ __ - 1 4-- _ _ _ ... . _._ _'.
APPENDIX
---- l< - /-I \) ---tm-v-
lOse -- -
Proof of the Real Property of K(x)
Consider a loss-less transmission line. Let Q be
the inductance per unit length and let c be the capaci-
tance per unit length. Fig. A.1 shows a transmission
line connected to a source impedance jwLS, and also
shows a fault at F x km away from the local end S. The
total impedance ZFS viewing one side of the network
from the faulted point becomes
Fig. 17 Oscillogram of voltages and currents recorded
at the laboratory experiment ZFS = Z tanh(Xx + OS) (A. 1)
where Z = It/c (A. 2)
REFERENCES X = ju/S (A. 3)
( yoLS
[1] A.D. McInnes and I.F. Morrison, "Real-Time Calcu- _1
OS A aS +jS tanh (A. 4)
z )
=
lation of Resistance and Reactance for Transmis-
sion Line Protection by Digital Computer", EE
Substituting the eqn. (A.2) to (A.4) into the eqn.
Trans., Inst. of Engineers, Australia, EE-7 No. 1, (A.1) obtains
pp. 1623, 1971.
[2] A.M. Ranjbar and B.J. Cory, "An Improved Method (A. 5)
for the Digital Protection of High Voltage Trans- ZFS =
iZ tan(wI@x + OS)
mission Line", IEEE Trans. PAS-94, No. 2, pp. 554- In a similar way, the total impedance ZFR viewing the
560, 1975. other side of the network becomes
[3] S.E. Westlin and J.A. Bubenko, "Newton-Raphson
Technique Applied to the Fault Location Problem", (A. 6)
IEEE PES Summer Meeting, A76 334-3, 1976. ZFR = jZ tan(w/kc(d-x) + SR)
[4] EMTP User's Manual, Bonneville Power Administra-
The ratio K(x) is defined by the eqn. (A.7).
tion, Branch of System Engineering, Portland,
Oregon, November, 1977. it
[5] A.T. John and M.A. Martin, "Fundamental Digital
K(x) A Ii,R ZFS (A. 7)
Approach to the Distance Protection of EHV Trans- -IjF ZFR
mission Lines", Proc. IEE Vol. 125, No. 5, pp. 377
-384, 1978.
[6] J.W. Horton, "The Use of Walsh Functions for High- Therefore, K(x) is represented by
Speed Relaying", IEEE PiES Summer Meeting, A75
582-7, 1975. tan(wv/Zcx + S) (A. 8)
K(x) =
[7] T. Takagi, J. Baba, K. Uemura and T. Sakaguchi, tan(uv'r(d-x) + k)
"Fault Protection Based on Travelling Wave Theory:
Part I - Theory", IEEE PES Summer Meeting, A77 which means that K(x) be a real variable. Q .E.D .
750-3, 1977.
1323
Discussion without much loss of accuracy for most medium length over-
head lines. Note that the equations derived above are no dif-
0. P. Malik (The University of Calgary, Calgary, Alberta, Canada): I ferent from the conventional line models used in most relay-
would like to congratulate the authors for a very interesting application ing applications.
of the Fourier Transform technique to fault location on EHV transmis- In view of these considerations, would the authors comment on
sion lines. the need to use equation (13) for overhead lines also?
It is interesting to note that the authors have chosen to sample Is it the authors' intention that these techniques be used for cable
every 30 electrical degrees. I would like to ask the authors to clarify faults?
whether the sampling rate is fixed at 12 samples per cycle at the nominal 4) Considering the relatively inaccurate result obtained (a of
frequency or whether the sampling is synchronized to the waveform to 0.28 km for a fault at 11 km), is the use of the Newton-Raphson pro-
produce samples every 30 electrical degrees. Under fault or heavy load cedure on equation (13) justified? It would seem that a more accurate
conditions, these two may not be the same because of the deviations in result would be obtained (for fault location purposes, NOT for relay-
frequency from the nominal. ing) if the data from the remote end is used.
Use of Fourier series techniques to distance protection of trans-
mission lines has been advocated and demonstrated before [A, B]. It Manuscript received August 4, 1980.
has also been shown [B] that the computation of the fault location can
be incorporated into the main fault detection and trip decision algo-
rithm. Because a little more time can be used to compute the fault loca-
tion, results described in reference B showed that the distance to fault T. Takagi, Y. Yamakoshi, J. Baba, K. Uemura, and T. Sakaguchi: The
could be computed very accurately. Will the authors please comment on authors would like to express their thanks to Messrs. Malik, Phadke, and
the feasibility of extending their algorithm to the detection of faults so Thorp for their interests in our paper.
that the fault detection, fault discrimination and fault location can be In reply to the first comment by Mr. Malik, the data sampling is
combined into one algorithm? assumed to be made at 12 samples per cycle at the nominal frequency,
or in other words sampling is not synchronized to the waveform of the
REFERENCES system voltage. Attempts were made to estimate the system frequency
deviation not only in normal operating state but in emergency state.
[A] P. G. Mclaren and M. A. Redfern, "Fourier series techniques ap- The maximum deviation is limited to within 0.2Hz in normal state.
plied to distance protection", Proc. IEE, Vol. 122, 1975, pp. Although it might be expected that the system frequency will deviate
1301-1305. during a severe faulted period, the deviation is very small in the first few
[B] G. S. Hope, 0. P. Malik and M. E. Rasmy, "Digital transmission cycles that are critical to estimate a location because of the large gener-
line protection in real-time", ibid, Vol. 123, 1976, pp. 1249-1254. ating capacity. The efforts to synchronize the sampling to the wave-
form would be large, but the benefits would be small. Therefore, the
Manuscript received July 25, 1980. authors have come to the conclusion that the sampling is made to the
nominal system frequency.
In reply to his second comment, we would like to emphasize that
A. G. Phadke (A.E.P. Service Corp.) and J. S. Thorp (Cornell University): the reactance measured by the distance relay is not necessarily a good
The authors present an interesting technique for calculating the distance indicator for fault location. There are some factors that might affect
to a fault on a transmission line. We would like to have the authors' the correct reactance measurement: fault resistance, and pre-fault power
comments on the following points: flow. These are primary reasons to make the distance relay succeptible
1) It was not clear from the paper whether the fault location to failure in measuring correct impedance. However, if we had an ac-
procedure is intended as a relaying algorithm. If this is so, the curate fault locator that would be fast enough to real time application,
question of being able to do it in real-time is of paramount it would become an ideal relay in which the fault detection, the fault
importance. It does not seem likely that the Newton proce- discrimination, and the fault location were combined together. This is
dure used for solving equation ( 13) is well suited for real-time one of the authors' motivations to start the research for a computerized
solution on a micro-computer. Also, if this is intended to be fault locator. At the present time, the time has not yet come.
a relay, its speed (at the quoted accuracy) seems to be 11/2 In reply to the first comment by Messrs. Phadke and Thorp, our
cycles, which is somewhat slower than most other currently efforts are basically made to develop a relaying algorithm. The present
available relaying algorithms. algorithm, however, is considered so complex and long to be applied to
2) How is the dc offset in the currents handled in the "Half- real time calculation. At this time our algorithm should be understood
Cycle Fourier Transformation" method? in terms of a fault location application, not a relaying one.
3) We wonder whether the use of hyperbolic functions in equa- On their second comment, no efforts were made to handle the DC
tions (6) - (13) is really necessary for overhead lines. For lines offset current in our theoretical and experimental studies. There are
as long as 300 miles, the quantity Xx is of the order of 1/10 some methods applicable to the DC offset current problem: the use of
of one radian (using the authors assumption of loss-less lines). a mimic impedance, the use of band pass filter, and so on.
One could use the approximations: In reply to their third comment, we agree with the use of approx-
cosh Xx 1 imate forms for hyperbolic functions. Some efforts have been made
sinh Xx Xx
- along this direction and results have encouraged the use of approxima-
tions. This consideration will benefit us in applying to the Japanese
so that equations (4) and (5) become power system, because most high voltage transmission lines are relatively
short. It is not our intention that these techniques be used for cable
VF = Vs - jXR Is faults. The key thing is that the technique be applied to a line where the
system has large short circuit levels toward a faulted point.
- ~~~IFS= -Is + jXcS- In reply to their last comment, it is reasonable to expect that more
accuracy will be obtained if the data from the remote end is used. Then,
where XR and Xc is the inductive and capacitive reactance of the problem will be solved almost trivially, and this is not our intention.
the line. One of our objectives was to explore the possibility to locate a fault
The last of these two equations can usually be replaced by without depending on the remote end data.
IFS Is Manuscript received September 8, 1980.