You are on page 1of 33

Sabre

Vacuum circuit breaker ring


main unit up to 24kV
with automation and remote control options

providing intelligent solutions


Sabre catalogue Introduction to Lucy Switchgear
Table of contents
Introduction to Lucy Switchgear 3 Lucy Switchgear is a global leader in companies that can offer truly bespoke solutions. With
switching, protection and automation the capability to manufacture equipment to suit almost
Product panorama 4
any location, climate or situation, Lucy Switchgear
solutions for electrical distribution
Introduction to Sabre 5 can also offer maintenance packages and dedicated
systems with over 100 years industry
after sales support throughout the product lifecycle. A
Installation and operating conditions 6 experience. From its modest beginnings specialist UK based research and development facility
Safety features 6 in street lighting, the company today is a ensures that Lucy Switchgears products are always at
specialist in secondary power distribution, the cutting edge of technology enabling rapid response
Application example 9
engineering high-performance medium to evolving technical and market demands of customers.
Standards 9 voltage switchgear for utility, industrial All of our purpose built, state of the art manufacturing
and commercial applications with a facilities espouse the latest international Quality and
The Sabre range 10
Environmental standards. The global profile of Lucy
broad product portfolio that includes
Non extensible range 10 Switchgear is emphasised through manufacturing
overhead line equipment and retrofit and facilities in the United Arab Emirates, Saudi Arabia
Extensible range 12 automation solutions. and India, offices in China, Dubai, Malaysia and South
Mounting style 16 Africa and an established global network of industrial
Engineering excellence coupled with state of the art partners and contractors operating in over 50 countries
Product characteristics 18 technology make Lucy Switchgear one of the few worldwide.
i. Product presentation 18
ii. User interface and interlocking mechanism 19
iii. Ring switch 20 Ring main unit range evolution
iv. Vacuum circuit breaker 20
v. Circuit breaker protection 21
a. TLF 21
b. Protection relays 23
TRIDENT
vi. Protection CTs for TLF and relays 26
vii. Bushings 26

Options and accessories 27


i. Secondary injection 27
ii. Actuators (motors) 27
iii. Cable boxes, glands and accessories 28
iv. Bus bar couplings 29 SCIMITAR
v. MV sensors 29
vi. Watchdog for relays 29
vii. Operation counter 29
viii. Castell locks 29
ix. Protection trip remote indicator 29
x. Shunt trip coils 30 SABRE
xi. Earth fault indicators (EFI) 30

Cable terminations 31

Air metering unit (AMU) 32

Remote terminal unit (RTU) 33


AEGIS
Technical data sheet 35

Dimensions 37
Models, options and accessories 47

Order forms 54 1965 1970 1975 1980 1985 1990 1995 2000 2005 2010 2015

Page 2 Page 3
Product panorama Introduction to Sabre
Lucy medium voltage and high voltage range

Sabre ring main units are designed for secondary


distribution networks up to 24kV. The range is
an ideal solution for indoor/outdoor compact
substations and is available in non-extensible,
extensible and modular formats to suit various
Range name Trident Scimitar Sabre Aegis Rapier GX Rapier AX Rapier DSB application requirements. All of the switching
functions are insulated with SF6 gas and sealed
in a stainless steel tank with a leakage rate of less
Type Ring main unit Switch disconnector
than 0.1% per year.

Rated voltage The structural tank welding is performed by a


15.5kV 17.5kV 24kV 24kV 38kV 36kV 145kV
(up to) robotic welding process ensuring high reliability
with a product life expectancy of more than 30
Mode of years. The housing is fully treated using zinc
fault current Fuse Fuse Vacuum Vacuum - - - coated steel and electrostatically applied oven
interruption cured paint to resist degradation from pollution
and harsh climatic conditions.
Insulation
Oil SF6 Air Air The transformer protection is by vacuum
medium
circuit breaker. On request, the units can be
supplied with integrated automation for remote
Rated current
630A 800A 2500A monitoring and control functions.
(up to)

Mounting Ground / Transformer Ground Pole Pole Structure

Installation Indoor / Outdoor Outdoor Characteristics:


Up to 24kV and 630Amps ratings Anti-reflex mechanism to prevent load break switch
Operation Local / Remote
opening under fault conditions
Non extensible, extensible and modular range
Fully interlocked operation with padlocking facility
Switching functions enclosed in a SF6 gas insulated
for maximum operator protection
steel tank, sealed for life
Freestanding and transformer mounted units
Intuitive single line mimic diagram for simple and
safe operation Actuators (motorised) for ring switches and
circuit breakers
Integrated earth and test facility for easy and safe
cable test without removing cable connections Seamless integration with SCADA network for
remote operation and control
Choice of TLF (time limit fuses) or self/auxiliary
powered relay protection Maintenance free with 30 years life expectancy

Page 4 Page 5
Installation and operating conditions

IP54 outdoor installation (kiosk not necessary) Cable earth and test facility (E&T) Ring switches: E&T is a standard feature
located at the bottom of the unit.
Ambient temperature for operation: E&T feature is used for testing cable insulation and to
-25C to 40C (50C optional) locate faults in the circuit without the need to remove
the main cables from the cable box.
Average value over 24 hours max: 40C
The cable test access cover is fully interlocked and cannot
Maximum altitude for operation without derating:1000m be opened until the ring switch or circuit breaker switch
Insulation medium: SF6 Gas is in the Earth ON position. The test bushings are earthed
with a star bar which has to be removed for cable tests.
Interruption medium: Vacuum

Safety features Vacuum circuit breakers: E&T is an optional feature


only on 630A VCB and is located at the top of the unit

Operation mechanism
The operating mechanism of the ring switches and
circuit breaker incorporates mechanical interlocks
and padlocking facilities which make it impossible to
simultaneously close the ring switch/circuit breaker and
the earth switch.

Anti-reflex mechanism
Anti-reflex mechanisms on ring switches ensure a time
delay between switching operations.

Internal arc withstand


Sabre gas tanks are fully internal arc rated and this Cable boxes
feature is also available on the cable boxes (optional) to
The cable boxes are located laterally or at the rear of
ensure maximum operator safety in the event of internal
the ring main unit. Factory mounted protection CTs
faults. The gas tanks are available in AF (front), AFL (front
are provided on the circuit breaker cable bushings for
and lateral) and AFLR (front, lateral and rear) ratings.
ease of installation and to avoid any potential damage
For more details on internal arc classification (IAC) to the CT during transit and connection. For additional
ratings, please refer to the technical data sheet. operator safety, the cable boxes are earthed and can be
interlocked to allow access to the operator only if the
function is in the Earth ON position. There is an option
to supply these cable boxes with internal arc rating as
per IEC standards (for further information, please refer
to the cable box, gland and accessories section).

Page 6 Page 7
Safety features Application examples

VPIS The key areas of application are


VPIS (Voltage Presence Indication System) is an optional Energy Commercial buildings: hospitals, shopping centres,
feature in the Sabre range. The VPIS receives a voltage i. Generation: wind power, solar power hotels, office buildings, data centres
signal through the voltage divider built into the cable ii. Distribution: compact substations
bushings. They can also be fitted with neon lights and Industries: water and waste water, mining, minerals,
Infrastructure: tunnels, airports, ports, automotive, iron and steel, paper and pulp, cement
momentary latching push buttons to show voltage
underground railway stations and petroleum
presence without needing external testing probes.

Two types of voltage presence indication devices


Pfisterer sockets
are offered:
Pfisterer sockets
Neon indicators with push-to-test buttons and
phase comparator sockets

Neon indicator with


push-to-test buttons

Gas pressure indicator


A gas pressure indicator is fitted to the tank which
has green and red sectors to indicate the minimum
permissible pressure for safe operation

An optional remote gas pressure alarm (1N/O) can


be specified to alert the operator in the event of gas
pressure falling below the permissible operable limit

Standards
International Standards
IEC 62271-1 IEC 62271-100 IEC 62271-102 IEC 62271-103 IEC 62271-200 ENA TS 41-36

Page 8 Page 9
The Sabre range

Non extensible range


VRNFS
Non extensible ring main units are an ideal solution for compact outdoor substations. Along with low voltage 17.5KV, 2 ring switches 630A + 1VCB 400A
distribution cabinets, these units can be easily coupled to the distribution transformer, forming a compact outdoor
package substation.

Modular non-extensible ring switches are an ideal solution for making a switching point in the network.

Ring main units


VRN2a
12/15.5kV, 2 ring switches 630A + 1 VCB 250A

VRN24
24kV, 2 ring switches 630A + 1 VCB 400A

VRN6a:
12/15.5kV, 2 ring switches 630A + 1 VCB 250/630A

Page 10 Page 11
The Sabre range

Modular ring switch Ring main units


DSN6a VRE2a
12/15.5kV, 2 ring switches 630A 12/15.5kV, 2 ring switches 630A + 1 VCB 250A

Extensible range
The extensible range is used to add another function The units are extended as shown in the diagram below:
on the left, right or both sides of switchgear installed VRE6a
in secondary networks. This is an ideal solution to All the extensible units are available in the 12/15.5kV, 2 ring switches 630A + 1 VCB 250/630A
allow future upgrades to systems when extra capacity following configurations;
is required. The units can be easily extended in any Left hand
combination on site without specific tooling or floor Right hand
preparation and without the need to transfer SF6 Both sides
gas. The extensible range is designed to be mounted
outdoors without needing a kiosk.

Page 12 Page 13
The Sabre range

Modular ring switch Modular circuit breakers


SSE6a VCE2a
12/15.5kV, 1 ring switch 630A 12/15.5kV, 1 VCB 250A

DSE6a VCE6a
12/15.5kV, 2 ring switches 630A 12/15.5kV, 1 VCB 630A

Page 14 Page 15
Mounting style

Freestanding units Transformer mounted unit

Outdoor free standing with Indoor free standing with


bottom entry cable box top entry cable box The Sabre ring main unit along with the low voltage
distribution cabinet is mounted on the distribution
transformer to form a low cost outdoor package
substation to be used in distribution networks.

Page 16 Page 17
Product characteristics

i. Product presentation ii. User interface and interlocking mechanism


VRE6a RMU parts labeled. For other products please Safety interlocking
refer to their respective IOM. Ring switch and circuit breaker mechanisms are fitted with safety interlocks to
protect the operator and equipment from unintentional operation
1 Fascia / front panel

2 Optional pull to trip knob & Position Interlock status


tripped on fault indicator blanks 1 Ring switch Selector Cable box Earth & test
3 Circuit breaker/Tee-off operation slot (optional) interlock
2 ON Main ON Locked
4 Circuit breaker/Tee-off indicator 3
21 OFF Main ON Locked
5 Circuit breaker/Tee-off selector 4
OFF Earth ON Locked
6 Disconnector operation slot
5 Earth ON Earth OFF Unlocked
7 Disconnector indicator (service/earth) 8

8 Disconnector padlock flap 20 6 Ring switch mechanism


7
9 Ring switch 2 indicator
19
10 Ring switch 2 selector 18

11 Ring switch 2 motor pack Position Interlock status


12 Ring switch cable test access cover Circuit Selector Cable Earth & test
breaker compartment interlock
13 Ring switch 1 selector interlock (optional)
(optional)
14 Door 17
ON Main Locked Locked
15 Ring switch 1 indicator
OFF (Tripped) Main Locked Locked
16 Ring switch 1 operating aperture 16
14 15 OFF (Reset) Earth Locked Locked
9
17 Circuit label - customer customization Earth ON Earth Unlocked Unlocked

18 Optional VPIS plates for LH/RH 11 10 Earth ON Earth Locked Locked


Ring switches & CB/T-Off 13 OFF (Tripped) Earth Locked Locked
19 SF6 top up valve - Hansen coupling
12
20 Pressure indicator

21 TLF

Circuit breaker
mechanism

Page 18 Page 19
iii. Ring switch Single mechanism with two independent operating v. Circuit breaker protection
shafts, one for circuit breaker ON/OFF position and
Standard features another for selecting disconnector in Mains or Earth
(isolation) Two types of protection devices are offered
Three function ON, OFF & Earth spring loaded
Interlocked disconnector selector, locked from
to protect the circuit breaker
mechanism, independent manual operation
operation when circuit breaker is in ON position TLF : Time limit fuses
Single mechanism with rotary moving shaft for
switching ON/OFF/Earth positions Trip coil for receiving tripping signal from relay or Protection relays
TLF devices
Interlocked selector with padlocking facility for
selecting Mains or Earth ON position Protection function TLF or relay (customer specific) a. TLF
Single line intuitive mimic diagram with clear When utilised in conjunction with circuit breaker type
Single line intuitive mimic diagram with clear ring main units, time limit fuses (TLF) are a cost effective
indication of switch status (ON, OFF or Earth position) indication of switch status (ON, OFF or Earth position)
method of providing fault protection for overcurrent and
Gas pressure indicator earth faults (optional) to a transformer of 2MVA or less.
Fully interlocked cable earth and test (E&T) facility
Horizontal cable terminations at rear of the unit with
Gas pressure indicator parallel or DIN 400 type C bushings It is a recognised method of protection and was
Lateral cable terminations with DIN400 type C developed to comply with EA 41-26 (now superseded by
Protection CTs (current transformers) mounted on ENA TS 41-36) with fuse links in accordance with ENA TS
bushings cable bushings (customer specific ratios) 12-6.
Padlock facility (8.5mm diameter hole) for all the Padlock facility (8.5mm diameter hole) for all the
operating positions operating positions It should be noted that the TLF protection system is
not a device for limiting overload levels of individual
Optional features, factory fitted transformers. It should be used for fault protection only.
Optional features, factory fitted
Remote low gas pressure alarm,1N/O Remote low gas pressure alarm,1N/O The TLF system provides protection for overcurrent and
VPIS - voltage presence indication system Mechanical (manual) pull-to-trip button for local earth faults between the MV circuit breaker and the LV
operation protection device.
Remote switch position indicator (1N/O,1N/C and
2N/O, 2NC) VPIS (voltage presence indication system - refer to The selected TLF rating should be such that it allows for
VPIS section for more details) discrimination between the MV & LV devices. This will
Short circuit and earth fault current indicators (EFI)
Remote circuit breaker position indicator (1N/O,1N/C ensure that the circuit breaker does not open for faults
Actuator (motor) wiring beyond the LV distributor protection device. Fuse dimensions: Length 57mm x Diameter 13mm
and 2N/O, 2NC)
Castell locks Fully interlocked cable earth and test facility (only on When fitted with TLF, the Lucy RMU can also be
630A VCB) configured to enable tripping of the circuit breaker from
Optional features also available as retrofit Self-powered relay for protection (customer specific) remote devices (Bukholtz, LV CB etc).
Actuator (motor) for ring switch (only if unit is pre
TLF (time limit fuses) for alternative protection Lucy Switchgear customers in Europe, the Middle East,
wired for motorisation)
Wide range of CTs for TLF and relay protection Africa and Asia are currently using TLF protection system
Internal arc rated cable box within their distribution networks.
Remote protection trip output status signal (for TLF
Wide range of cable glands and accessories to
or relay trip status) 1N/O
accommodate 1 and 3 core cables (refer to cable
box section for further information) Shunt trip coils for external tripping
Tripped on fault indication
Watchdog for relays (only available with selective relays)
iv. Vacuum circuit breaker Circuit breaker actuator enabled indication
250A rated vacuum circuit breaker for
transformer protection Actuators (motor) wiring
400A rated vacuum circuit breaker for
transformer/downstream network protection Optional features also available as retrofit
630A rated vacuum circuit breaker for Actuator (motor) for CB (only if unit is pre wired for
transformer/downstream network protection motorisation)
Internal arc rated cable box
Standard features Wide range of cable glands and accessories to
Three functions (ON, OFF & Earth), two position spring accommodate 1 and 3 core cables (refer to cable
loaded mechanism, independent manual operation box section for further information)

Page 20 Page 21
Recommended TLF settings b. Protection relays Woodward WIP 1
Transformer ratings (kVA) Manufacturer Woodward
200 315 500 800 1000 1250 1600 2000 Range WIP1
Rated voltage (kV) TFL fuse rating (A)
Functions
3.3 10A
ct ratio 50/5 Phase overcurrent
6.6 5A 10A 15A
Short circuit protection
Earth fault setting = 25A 11 3A 5A 10A 15A
Number of overcurrent elements 2
(instantaneous trip) 13.8 3A 5A 10A 15A The Sabre range can be fitted with self-powered relays Earth overcurrent
24 3A 5A 7.5A for protecting the transformer or downstream network Number of earth overcurrent elements 2
from fault currents by tripping the circuit breaker. These
relays incorporate many advanced features and have a Characteristics
3.3 5A 10A 15A variety of settings to provide discrimination protection
ct ratio 100/5 6.6 5A 7.5A 12.5A 15A in networks. The self-powered feature eliminates
Display (measuring values and parameters)

reliance on external power sources and increases the Setting via buttons
Earth fault setting = 30A 11 5A 7.5A 10A 12.5A 15A 12.5A
(instantaneous trip)
performance and reliability of the protection function. Standard CT (1A/5A) 1A
13.8 5A 7.5A 10A 12.5A 15A
LED pickup
24 5A 5A 7.5A Below are the technical characteristics of Woodward
WIP1 and Fanox SIAC range. Other manufacturers relays LED trip indicator
can also be incorporated into the units on request. Flag indication output
Advantage of vacuum circuit breaker with TLF Fault memory
compared to HV fuses Clock
Feature VCB with TLF Fuse switch Password protection
Overall cost of units Similar Electro impulse and relay contact output

Approximate fuse replacement cost $5 $50 Number of output relays 3 C/O

Maximum rating of transformer, can be protected 2MVA* 1MVA Input remote tripping

Maximum rated normal current 630A 200A Interface O

Physical size of fuses Small Large RS 485 interface with pro open data protocol O

Possibility of some pollution while changing fuses causing PD and flashover issues No Yes RS-485 interface with Modbus protocol O

Fuse location inside the unit LV side HV side Additional power supply O

Range of fuses required for different rated transformers Very small with multi ratio CT Large
Key Standard O Option
(* No issues with transfer current switching to IEC 62271-105, which minimizes the MVA rating)

Advantage of vacuum circuit breaker with TLF


compared to protection relays
Feature TLF Protection relay
Installation cost of function Low High

Auxiliary power source for operation Not required As required


Delay in activation of trip function due to capacitor charging time lag No delay Delay
Employee training on setting tripping curves Not required Required
Additional training on different manufacturer setting up procedure Not required Required
Maintenance and repair cost Low High
Operating temperature limitations None Up to 70 C
Upstream and downstream discrimination protection of circuit Yes Yes
Overcurrent and Earth fault protection Yes Yes

Page 22 Page 23
Fanox

Manufacturer Fanox Fanox Fanox Manufacturer Fanox Fanox Fanox


Range SIAC*********D SIAC*********B SIAC*********FA Range SIAC*********D SIAC*********B SIAC*********FA

Functions Flag indication output Flags are included in the relay, no Flags are included in the relay, no Flags are included in the relay, no
need of external modules need of external modules need of external modules
Phase overcurrent
Fault memory 20 fault reports (64 events each). 20 fault reports (64 events each). 20 fault reports (64 events each).
Short circuit protection
In WIP 1 are recorded 5 last In WIP 1 are recorded 5 last In WIP 1 are recorded 5 last
Number of overcurrent elements 2 2 3 trip events trip events trip events
50P: 50P: (2) 50P:
Events 500 events in non-volatile 500 events in non-volatile 500 events in non-volatile
Tap:0.130xIn Tap:0.130xIn Tap:0.130xIn
RAM memory RAM memory RAM memory
Time:0,02300 s Time:0,02300 s Time:0,02300 s
51P: 51P: 51P: Characteristics
Tap:0.17xIn Tap:0.17xIn Tap:0.17xIn
Clock
Earth overcurrent
Password protection
Number of earth overcurrent 2 2 3
Electro impulse and relay contact
elements 50N: 50N: (2) 50N:
output Trip contact for striker or coil Trip contact for striker or coil Trip contact for striker or coil
Tap:0.130xIn Tap:0.130xIn Tap:0.130xIn
Time:0,02300 s Time:0,02300 s Time:0,02300 s Number of output relays 2 NO/NC 2 NO/NC 3 NO
51N: 51N: 51N:
Watchdog contact - - -
Tap:0.17xIn Tap:0.17xIn Tap:0.17xIn
Input remote tripping
Pickup level 0,2xIn(single phase) 0,2xIn(single phase) 0,2xIn(single phase)
0,1xIn (three phase) 0,1xIn (three phase) 0,1xIn (three phase) Interface O O O
Startup time (Trip time after fault. 130 ms 130 ms 70 ms RS 485 interface with pro open - - -
single phase) data protocol
RS-485 interface with Modbus O O O
Characteristics protocol Option included in the relay, no Option included in the relay, no Option included in the relay, no
need for an external module need for an external module need for an external module
Display (measuring values and MODBUS MODBUS MODBUS
parameters) (Display 20x2) (Display 20x2) (Display 20x2)
Additional power supply O O O
Setting via buttons Option included in the relay, no Option included in the relay, no Option included in the relay, no
Test menu need for an external module need for an external module need for an external module
The test menu can be used to The test menu can be used to The test menu can be used Battery No need for an internal battery No need for an internal battery No need for an internal battery
check the operation of the check the operation of the to check the operation of the to keep events and faults due to to keep events and faults due to to keep events and faults due to
signaling components (LEDs and signaling components (LEDs and signaling components (LEDs and FRAM memory FRAM memory FRAM memory
magnetic indicators), along with magnetic indicators), along with magnetic indicators), along with
the trip output and the signaling the trip output and the signaling the trip output and the signaling
outputs outputs outputs
Settings groups 1 1 3
Standard CT (1A/5A) 1A or 5A (depending on model) 1A or 5A (depending on model) 1A or 5A (depending on model)
Other manufacturers relays are also available on request, please contact our local Sales Office for more information.
LED pickup The pickup message is shown The pickup message is shown at The pickup message is shown at
at the display. Besides, the SIA-C the display. Besides, the SIA-C the display. Besides, the SIA-C
front panel has three LED pilot front panel has three LED pilot front panel has two LED pilot
lights to show the type of power lights to show the type of power lights to show the type of power
being used: self-power, battery or being used: self-power, battery or being used: self-power or battery
auxiliary power auxiliary power
LED trip indicator To signal the trip, the front panel is To signal the trip, the front panel is To signal the trip, the front panel is
equipped with 1 bistable magnetic equipped with 1 bistable magnetic equipped with 2 bistable magnetic
indicator which indicates a trip indicator which indicates a trip indicators which indicates a trip
has occurred has occurred has occurred

Page 24 Page 25
Options and accessories

vi. Protection CTs for TLF and relays i. Secondary injection


The protection CT is used in conjunction with relays or TLF protection to protect a wide range of distribution Secondary injection is used to test the relays or TLF
transformers. operation without switching on the high voltage supply
to the unit. A low voltage is applied to the secondary
These CTs are mounted on the circuit breaker tee-off bushings inside the cable box to guard them from damage
side of the CT connection (located in terminal box) to
in transportation, installation and adverse weather conditions.
test the operation of the protection devices at the time
A comprehensive range of CTs* is available to suit varied application requirements of commissioning and routine tests.
Dual ratio CT 100/50/-
Dual ratio CT 200:100/-
Triple ratio CT 150:100:50/-
*Please contact our local Sales Office for more information

vii. Bushings DIN400


type C
i. Cable bushings
a. Ring switch: DIN400 type C Marshalling Box
(125mm phase centre distance)
b. Vacuum circuit breaker tee-off:
Parallel bushings (105mm phase centre distance)
ii. Actuators (motors)
Optional adaptor for converting parallel
bushings connection to DIN 400 type C Parallel Sabre units are fitted with 24V DC motors, which can
(105mm phase centre distance) bushings be powered from the Gemini remote terminal unit (RTU)
DIN400 type C (125mm phase centre distance) 24V DC battery in the event of mains AC supply failure.

c. Metering unit: DIN400 type C


(125 mm phase centre distance)

ii. Bus bars extension bushings:


(Obround 125 mm phase centre distance)
Ring switch actuator
iii. Test bushings Obround
bushings

Vaccum
circuit
breaker
actuator
Test bushings

Page 26 Page 27
iii. Cable boxes, glands and accessories iv. Bus bar couplings
Bus bar couplings are used to connect two extensible units.
Cable box
Cable boxes are available for the following:
Bus bar coupling lengths
o Ring switches cable bushings
254mm
o Circuit breakers tee-off bushings
378mm
o Metering units bushings
o Extensible bus bar bushings 453mm
Safety interlocks: The cable boxes can be interlocked with a ring 500mm
switch or circuit breaker mechanism. Interlocked cable boxes can 750mm
only be removed when the circuit is in the Earth ON position
Internal arc rating Bus bar insulation types
o Non internal arc rated cable box as standard Heat shrink (manufactured by SPS)
o Internal arc rated cable boxes 12.5kA 1sec and 20kA Heat shrink (manufactured by Raychem)
1 sec as optional Heat shrink (manufactured by REPL)
Cable box lengths Cold fit rubber boot (manufactured by Pirelli?)
o 450mm
o 610mm
Cable entry v. MV sensors
o Top entry with Bottom entry BMV sensors are used to detect the medium voltage in the cable
IP50 standard (indoor only) and send a signal to the remote control device for auto changeover.
IP54 optional
o Bottom entry with IP54 as standard
Straight vi. Watchdog for relays
Angled They are used to check the healthy operation of relays.

Cable gland and gland plates


Cable gland and gland plates vii. Operation counter
o 1 x 3 core cable
X size They are used to count the number of mechanical operations of
Gland plates the ring switch and circuit breaker mechanisms.
o X size gland plate with earth stud
o X size gland plate with earth bar
Glands
viii. Castell locks
o X tube glands Ring switch: Castell locks are used to prevent closing of the open
o X brass wiping gland point in the ring network.
Y size
Gland plates Top entry cable box Circuit breaker: Key free Earth ON: They are typically used for
o Y size gland with earth stud preventing transformer cubicle access until the circuit breaker is
o Y size gland with earth bar
in the Earth ON position.
Glands
o Y tube glands
o Y brass wiping gland ix. Protection trip remote indicator Castell lock
o 3 x 1 core cable
Gland plates They are used to send a signal to a remote terminal unit if a
3 hole split steel with earth stud protection device relay or TLF has tripped (operated).
3 hole split steel with earth bar
3 hole solid brass with earth stud
3 hole solid brass with earth bar Angled cable box
Glands
Single core compression gland For further information refer to
Single core heat shrink glands the accessories table.

Page 28 Page 29
Cable terminations

x. Shunt trip coils The bushings are accessible by removing the cable box covers at the lateral and rear of the unit.

Shunt trips are magnetic coils that are used to trip circuit breakers The maximum cable sizes that can be used are:
through local push buttons, RTUs or additional transformer 300mm 3 - core
protection devices. 500mm single - core.
The following types of terminations can be used with the Sabre range:
Shunt trips are available in the following voltages:

DC voltage: 12V, 24V, 48V and 110V


AC voltages: 110V, 240V Shunt trip
Multiple voltage range: 24VAC/DC 240VAC/DC.

xi. Earth Fault Indicators (EFI)


Earth fault indicators (EFI) are used for rapid location and isolation
of faults on medium voltage networks in open loop ring main
networks. When the unit detects asymmetrical currents in the 3
phase cable, an earth fault is indicated by means of a flashing LED
or mechanical flag.
Insulating bushing boot Heat shrink
Below is the list of EFIs available for the Sabre range insulating bushing boot

Manufacturer Model: Suparule Sensorform BLZ-50 BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50

Features
3.6V lithium AA 110-240V a.c. CT on current carrying phase
Power source 850mAH battery
1 38kV
Profile C bolted separable
Voltage range
Trip current 50A
Primary indication LED Mech-flag (RED) LED Mech-flag (RED) LED
Flashing duration >1000 hrs - - 10 hrs - 10 hrs DIN type C bushings (cable boxes)
Minimum fault duration 2.5 cycles Insulating bushing boot
Manual reset Push button Heat shrink insulating bushing boot
Automatic timer reset 4 or 8 hrs selectable 10 secs after mains restore Profile C bolted separable
Manual trip test Push button
Obround bushings (bus bar extension)
Operating temperature -40C to +80C
The following cable connections could be used if direct cable connection is required on the bus bar bushings
Operating humidity 0-100% RH
Insulating bushing boot
Ingress protection IP65 Heat shrink insulating bushing boot
Current sensor diameter: CT100: 100mm
CT150: 150mm O O O O O O Parallel bushings (tee-off)
CT300: 300mm O O O O O O The following connectors could be used if cable tee-off direct cable connection is required
Remote flashing LED indicator O O O O O O Insulating bushing boot
Auxiliary relay, 1N/O latching O O O O O O Heat shrink insulating bushing boot
Key Standard O Option Other manufacturers EFIs are also available on request, please contact our local sales office for more information.

Page 30 Page 31
Air metering unit (AMU) Remote terminal unit (RTU)

i. Characteristics The Gemini RTU is an advanced, highly flexible and ultra-


efficient solution for remote operation and control of
Up to 17.5kV and 630Amps ratings electrical distribution networks. Enclosed in a stainless
Freestanding and RMU mounted version steel casing for maximum protection, the Gemini RTU is
Voltage transformer (VT) isolation for HV testing designed to operate in the most demanding environments.
Bus bar metering and tee-off metering options
Trip lock out relay for RMU/AMU combinations for The key features of the Gemini range are:
emergency tripping
Wide range of CT and VT options to suit various Embedded auto change over and auto sectionalizing
application needs Tee-off metering
RMU mounted functions
IP54 for outdoor installation without needing any kiosk Control and monitoring of up to 4 motorized functions
(switches or circuit breakers)
ii. Mounting style Inbuilt earth and fault passage indicators
a. Tee-off metering Advanced monitoring of current, voltage, battery
b. BC: Bus bar connected condition, switching parameters such as open/close
c. FS: Free standing metering status, actuator disabled and gas pressure
Flexible communication through radio, RS232, packet
Free standing data network, GSM, GPRS, PSTN, bluetooth, ethernet
metering unit TCP/IP, optical fibre and SMS messaging
Advanced battery pack to operate under mains AC
input failure
Fully tested to ENATS (Energy Network Association
Technical Standards), EMC and environmental standards

In addition to the above features, remotely monitored


and controlled switchgear provides significant benefits to
customers such as:
RTU enclosure
Reduced time in diagnosing system anomalies as well as
locating and isolating faulty sections of the network
Faster response time and quick network reconfiguration
Optimisation of asset management through the
implementation of customized automation schemes
Reduced operational cost associated with routine
network switching
Increased operator safety

Tee-off metering

Bus bars connected metering Free standing metering

Page 32 Page 33
Technical Data Sheet

Gemini RTU Specification Ring main unit Modular circuit


breaker
Modular ring switch

Non Extensible Extensible Non


Extensible
Gemini RTU Specification
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
General Enclosure Stainless steel
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB 1 VCB 1 VCB 1 RSW 2 RSW 2 RSW
Degree of protection IP54
Operating temperature -25 to 60C General
Rated voltage kV 12 (15.5) 12 (15.5) 17.5 24 12 (15.5) 12 (15.5) 12 (15.5) 12 (15.5) 12 (15.5) 12 (15.5) 12 (15.5)
Relative humidity Up to 95% Rated frequency Hz 50 60 50
Method of mounting Floor, wall, pole or RMU switchgear Rated lightning impulse withstand voltage
Directly earthed kV 75 (95) 95 125 75 (95)
Dimensions H 600mm, W 400mm, D 210mm
Across disconnector kV 85 (110) 110 145 85 (110)
RTU hardware Processor module ARM9 microprocessor Rated power frequency withstand voltage
Power supply 110/230V AC supply - over and under-voltage protection Directly earthed kV 28 (38) 38 50 28 (38)
Across disconnector kV 38 (45) 45 60 38 (45)
Battery type 2 x 12V DC, sealed lead acid or high temperature NiMH
Protection
Battery charger Temperature compensated, fully protected Overall unit IP IP54
Control electronics PIC based processor with expandable I2C bus Tank with HV parts IP IP67
LV control box IP IP54
Inner enclosure Stainless steel
Front face + mechanism IP IP2x
Ventilation Microprocessor controlled, long life fan with baffle Cable box IP IP54
air intake filter Mechanical impact protection IK IK07 (2J) Indoor, IK08 (5J) Outdoor

Inputs / Outputs Digital inputs 14 isolated digital inputs - expandable Internal arc protection
Unit kA 1 sec 20 21 16 20
Digital outputs 8 isolated digital outputs - expandable
cable box (optional) kA 1 sec 12.5/20 12.5 12.5/20
Analogue inputs 3 CT analogue inputs as standard (DIs reduced to 11) Gas tank internal arc ratings
Expansion I/O module 3 AIs / 4 DIs; 7 DIs / 2 DOs AF Standard
AFL Optional
3 RS-232 for control (ethernet option), configuration
Communications Communication interfaces AFLR - Optional - - Optional
and programming plus one expansion bus
SF6 gas
DNP3, IEC 60870-5-101/104 and Modbus Filled pressure Bar (G) 0.4 0.5 0.4
Protocols
(others on request) Minimum operating presure Bar (G) 0 0.3 0

RS-232, UHF / VHF radio, packet data, GSM / GPRS / EDGE, Annual leakage rate 0.1% per annum
Weight Kg 1.46 1.56 1.78 1.05 0.78 0.98
Communication media PTSN, leased or twisted pair lines, optical fibre, ethernet
(TCP/IP) and bluetooth Installation conditions
Ambient air temperature (without derating) C 40/50
Membrane push-button for open / close operations in Maximum altitude (without derating)* M 1000
conjunction with activate push-button, up to four switching Relative humidity (max) - over period of
Switchgear interface Controls 100%
functions (standard 1, 2, 3 or 4 switch control formats), 24hrs (IEC 62271-1, sub-clause 2.1)
selector control for off, local or remote modes
RTU services such as DC / AC supplies, dummy control and Ring main unit Modular circuit Modular ring switch
breaker
debug LEDs
Non
Indications Switch status LEDs for open / closed positions Non Extensible Extensible
Extensible
Control output LEDs (illuminates when active) Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
Configurable LED indications 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB 1 VCB 1 VCB 1 RSW 2 RSW 2 RSW
Cables Plug-in, multi-core umbilicals to switchgear
Bus bars
Windows-based software for configuration of: Rated normal current A 630 400/630 630
Protocol parameters including device and I/O addresses Rated short time withstand current 20 kA 3s 21kA 1s 16kA 3s 20kA 3s
Parameters for the communications device Rated peak withstand current kA 50 54.6 40 50
Software Configuration Parameters for digital, analogue and counter points
Automation sequences
Power saving routines * for higher altitude applications please contact our local Lucy Switchgear sales office
Battery tests

Page 34 Page 35
Dimensions

Ring main unit Modular circuit Modular ring switch Dimensions & floor:
breaker VRN2A
Non Extensible Extensible Non
Extensible
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB 1 VCB 1 VCB 1 RSW 2 RSW 2 RSW

Ring switch
Rated normal current A 630 400/630 630 630 630
Rated active load breaking current A 630 400/630 630 630 630
Rated short circuit making current
Ring switch kA 50 54.6 40 50 50
Earth switch kA 50 54.6 40 50 50
Rated cable charging breaking current A 25 25
Rated short time withstand current
Ring switch 20 kA 3s 21kA 1s 16kA 3s 20kA 3s 20kA 3s
Earth switch 20 kA 3s 21kA 1s 16kA 3s 20kA 3s 20kA 3s
Mechanical endurance class
Ring switch M2 (5000) M2 (5000)
Earth switch M1 (1000) M1 (1000)
Electrical endurance class short circuit making
Ring switch E3 (5 times) E1 (2 times) E3 (5 times) E3 (5 times)
Earth switch E2 (3 times) E1 (2 times) E2 (3 times) E2 (3 times)
Operating mechanism
Local: close/open Handle Handle
Remote: close/open Actuator (Motor) Actuator (Motor)

Ring main unit Modular circuit Modular ring switch


breaker
Non Extensible Extensible Non
Extensible
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB 1 VCB 1 VCB 1 RSW 2 RSW 2 RSW

Vacuum circuit breaker


Rated normal current A 250 630 400 400 250 630 250 630
Rated active load breaking current A 250 630 400 400 250 630 250 630
Rated short circuit breaking current kA 20 21 16 20
Rated short circuit making current
Circuit breaker kA 50 54.6 40 50
Earth switch kA 7.9 50 54.6 40 7.9 50 50 50
Rated cable charging breaking current A 25
Rated short time withstand current
Main electrical circuit 20 kA 3s 21kA 1s 16kA 3s 20kA 3s
Earthing circuit 3.15kA 3s 20kA 3s 21kA 1s 16kA 3s 3.15kA 3s 20kA 3s 3.15kA 3s 20kA 3s
Mechanical endurance class
Circuit breaker M1 (2000)
Earth switch M1 (1000)
Electrical endurance class Dim A Dim B Dim B Dim C Dim D Dim E
(Ring bushing (450mm Tail length (570mm Tail length (Tee-off bushing
Circuit breaker E2 height in mm) cable box in mm) cable box in mm) (mm) (mm) height in mm)
Earth switch E2
1052 600 480 1715 817 1402
Operating mechanism
970 518 398 1633 735 1320
Tripping time ms >80ms
Operating sequence for mechanism 0-3min-CO-3min-CO 750 298 178 1413 515 1100
Local: close/open Handle
Remote: close/open Actuator (Motor)

Page 36
NOTE: All the dimensions are in mm Page 37
Dimensions - continued

Dimensions & floor: Dimensions & floor:


VRN6A VRNFS

Dim A Dim B Dim C Dim D Dim E Dim F Dim F


(Ring bushing (Tee-off bushing (450mm Tail length (570mm Tail length
height in mm) (mm) (mm) (mm) height in mm) cable box in mm) cable box in mm)

1052 2163 1773 817 1402 600 480


970 2081 1691 735 1320 518 398
750 1861 1471 515 1100 298 178

Page 38
NOTE: All dimensions are in mm Page 39
Dimensions - continued

Dimensions & floor: Dimensions & floor:


VRN24 DSN6A

Page 40
NOTE: All dimensions are in mm Page 41
Dimensions - continued

Dimensions & floor: Dimensions & floor:


VRE2A / VRE6A SSE6A

Page 42
NOTE: All dimensions are in mm Page 43
Dimensions - continued

Dimensions & floor: Dimensions & floor:


DSE6A VCE2A / VCE6A

Page 44
NOTE: All dimensions are in mm Page 45
Dimensions - continued

Dimensions & floor: Dimensions:


AMU Free standing Tee-off AMU (RMU mounted)

Page 46
NOTE: All dimensions are in mm Page 47
Sabre models and options
Modular units Extensibility Non extensible Extensible Extensible
Non
extensible
Range Ring main units Modular Modular ring
circuit Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
breaker switches
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Non Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW
Extensibility Non extensible Extensible Extensible
extensible
Vacuum circuit breaker
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
Bushings type
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW Parallel bushings - - - - -
General Adaptor to covert parallel bushings to DIN 400 type C bushing o o - - o o o o - - -
Extensibility DIN 400 type C - - - - - - - - -
Non extensible - - - - - - Rated normal current
LH extensible - - - - o o o o o o - 250A o - - o - - - -
RH extensible - - - - o o o o o o - 400A - - - - - - - - -
Both sides extensible - - - - o o o o o o - 630A - o - - - - - -
Impulse withstand voltage (BIL) kVP Earth & test facility - o - - - o - o - - -
(choose one from below) Circuit breaker protection
12kV at 75KVP BIL o o - - o o o o o o o TLF o o - o o o o o - - -
15.5kV at 95KVP BIL o o - - o o o o o o o Relay (choose one from below)
17.5kV at 95KVP BIL - - o - - - - - - - - WIP1 relay o o o o o o o o - - -
24kV at 125kVP BIL - - - o - - - - - - - Fanox relay o o o o o o o o - - -
24kV at 145kVP BIL - - - o - - - - - - - Any other* o o o o o o o o - - -
Low gas pressure alarm auxiliary contact 1NO o o o o o o o o o o o Protection (CT) current transformers
Pressure indicator gauge with Hanson coupling Dual (Primary) ratio CT 100/50/- o o o o o o o o - - -
Mounting style Dual (Primary) ratio CT 200/100/- o o o o o o o o - - -
Transformer mounted unit (fitted with ESI flange) o - - - - - o - - - - Triple (Primary) ratio CT 150/100/50/- o o o o o o o o - - -
Freestanding unit o o Dual (Primary) ratio CT 400/200/- - o o o - o - o - - -
No ESI flange (with cable box)1 o o o o o o o o - - - Dual (Primary) ratio CT 150/100/- o o o o o o o o - - -
ESI Transformer flange fitted (with/without cable box)1 o o o o o o o o - - - Dual (Primary) ratio CT 600/200/- - o o - - o - o - - -
Height of tee-off bushing from floor Manual "Pull to trip" o o o o o o - - -
(applicable to freestanding units) Remote shunt trip
1100mm o - - o - - - - - - - 12V DC o o o o o o o o - - -
1320mm o o - o - - - - - - - 24V DC o o o o o o o o - - -
1348mm - - - - - - - - - - 48V DC o o o o o o o o - - -
1402mm o o - o - - - - - - - 110V DC o o o o o o o o - - -
Height of extension bushings from floor 110V AC o o o o o o o o - - -
(applicable to free standing units) 240V AC o o o o o o o o - - -
1072 mm - - - - Multi voltage (24V AC/DC- 240V AC/DC) o o o o o o o o - - -
Any other (available on request) - - - - o o o o o o o Indication / auxiliary switches
Internal arc protection for gas chamber (tank) Remote protection trip output signal
(for TLF or relay trip status) 1N/O
o o o o o o o o - - -
AF
Watchdog for relays (only available with selective relays) o o o o o o o o - - -
AFL o o o o o o o o o o o
Tripped on fault indication o o o o o o o o - - -
AFLR o o - o o o o o o o o
Circuit breaker actuator enabled indication o o o o o o o o - - -
Tank exhaust at top - -
Circuit breaker service indication
Tank exhaust at rear - - - - - - - - -
1NO, 1NC o o o o o o o o - - -
Extensible bus bar bushings: Obround (Hysol) - - - - -
2NO, 2NC o o o o o o o o - - -
Vacuum circuit breaker
Short circuit breaking current Circuit breaker earth indication
16kA RMS - - - - - - - - - - 1NO, 1NC o o o o o o o o - - -
20kA RMS - - - - - 2NO, 2NC o o o o o o o o - - -
Secondary injection terminals o o o o o o o o - - -
21kA RMS - - - - - - - - - -
25KA RMS 2 - o o - - o - o - - - Key Standard 1: Refer to cable box, cable gland and gland plate table for more information
o Options 2: Available soon
- Not applicable

Page 48 Page 49
Sabre models and options - continued

Non Non
Extensibility Non extensible Extensible Extensible
extensible
Extensibility Non extensible Extensible Extensible
extensible
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW

Vacuum circuit breaker Ring switch 2 (Right hand side)


VPIS Actuators (motors)
Neon indication push button o o o o o o o o - - - Actuators wiring only o o o o o o - - - o o
Neon indication pfisterer socket o o o o o o o o - - - Actuators (24V DC motor) for remote control o o o o o o - - - o o
Operation counter o o o - o o o o - - - VPIS
Castell locks Neon indication push button o o o o o o - - - o o
Key free earth on o o o o o o o o - - - Neon indication pfisterer socket o o o o o o - - - o o
Key trapped disconnector service CB ON o o o o o o o o - - - MV sensor o o o o o o - - - o o
Actuators (motors) Auxiliary switches
Actuators wiring only o o o o o o o o - - - 1NO, 1NC o o o o o o - - - o o
Actuators (24V DC motor) for remote control o o o o o o o o - - - 2NO, 2NC o o o o o o - - - o o
Ring switch 1 (Left hand side) Castell locks
Rated current Key free in off position o o o o o o - - - o o
400A - - - - - - - - - - Earth fault indication
630A o - - BFZ-50 o o o o o o - - - o o
Earth & test facility - - MFZ-50 o o o o o o - - - o o
Bushings type MLZ-50 o o o o o o - - - o o
DIN 400 type C - - CFZ-50 o o o o o o - - - o o
Operation counter o o o - o o - - o o o CLZ-50 o o o o o o - - - o o
Actuators (motors) BLZ-50 o o o o o o - - - o o
Actuators wiring only o o o o o o - - o o o Any other(*) o o o o o o - - - o o
Actuators (24V DC motor) for remote control o o o o o o - - o o o
VPIS
Neon indication push button o o o o o o - - o o o
Neon indication pfisterer socket o o o o o o - - o o o
MV sensor o o o o o o - - o o o
Auxiliary switches
1NO, 1NC o o o o o o - - o o o
2NO, 2NC o o o o o o - - o o o
Castell locks
Key free in off position o o o o o o - - o o o
Earth fault indication
BFZ-50 o o o o o o - - o o o
MFZ-50 o o o o o o - - o o o
MLZ-50 o o o o o o - - o o o
CFZ-50 o o o o o o - - o o o
CLZ-50 o o o o o o - - o o o
BLZ-50 o o o o o o - - o o o
Any other(*) o o o o o o - - o o o
Ring switch 2 (Right hand side)
Rated current
400A - - - - - - - - - -
630A o - - -
Earth & test facility - - -
Bushings type
DIN 400 type C - - - Key Standard 1: Refer to cable box, cable gland and gland plate table for more information
Operation counter o o o - o o - - - o o o Options 2: Available soon
- Not applicable

Page 50 Page 51
Air metering unit (AMU)

Metering units
General Accessories
Impulse withstand voltage (BIL) kVP (choose one from below) Shunt trip supply (110VAC to power shunt trip on RMU) o
12kV at 75KVP BIL o Trip lock out relay o
15.5kV at 95KVP BIL o MCB o
17.5kV at 95KVP BIL o Secondary wiring protection
Fuses o
Rated current
Power meters
250A o
630A o
Mounting style Metering wiring Wiring for single meter
FS: Freestanding (select incoming and outgoing cable boxes from table no: ) o Wiring for 2 meters o
BC: Bus bar connected (select the length of bus bar connections from table: ) o Circutor o
TC: Ring main unit (tee-off ) mounted (select the outgoing cable box) o
Meter type Actaris o
Bushings type
FS: Freestanding Any other (*) o
Incoming DIN type C 1 o
Number of meters
Outgoing DIN type C 2 o
BC: Bus bar connected
Door mounted o
Incoming DIN type C Meter mounting style
Din mounted (window on the door) o
Outgoing DIN type C
TC: Ring main unit (tee-off ) mounted Marshalling box gland plates
Incoming direct coonection to RMU Blank gland plate o
Outgoing DIN type C 20mm o
Gland plate with 1 hole (hole size)
25mm o
CT - Current transformer 20mm and 25mm o
CT ratio change over link o 16mm and 25mm o
CT type Number of CT Gland plate with 2 holes (hole sizes)
20mm and 20mm o
Dual (Primary) ratio CT 100/50/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 o
25mm and 25mm o
Dual (Primary) ratio CT 200/100/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 o
Dual (Primary) ratio CT 400/200/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 o Any other hole sizes / combination(*) o
Triple (Primary) ratio CT 400/200/100/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 o

VT - Voltage transformer
VT primary fused protection
Unfused primary VT with tool free bus bar isolation for VT testing (only for 630A) o
Fused primary VT o
VT type Number of VT
Dual (Primary) ratio 3 Ph - 3 limb 11000/6600/110V, class 1, 50VA/PH 1 o
Single (Primary) ratio 3 Ph - 3 limb 11000/110V, class 1, 50VA/PH 1 o
Single (Primary) ratio 3 Ph - 3 limb 6600/110V, class 1, 50VA/PH 1 o
2 o
Single (Primary) ratio 1 Ph - 1 limb 13800/110V, class 0.5, 50VA/PH
3 o
2 o
Dual (Primary) ratio 1 Ph - 1 limb 11000/6600/110V, class 0.2, 50VA/PH
3 o

Key Standard o Options

Page 52 Page 53
Accessories

Cable box, cable gland and gland plate selection table Cable box, cable gland and gland plate selection table
Circuit Circuit
Ring Ring Extensible Ring Ring Extensible
breaker Metering unit breaker Metering Unit
switch 1 switch 2 bus bars Switch 1 Switch 2 bus bars
tee-off tee-off
Outgoing Outgoing
(Not to be Incoming (Not to be Incoming
side side
used with VRE side used with VRE side
(for FS and (for FS and
and DSE) (for FS only) and DSE) (for FS only)
TC only) TC only)
Interlocked cable box o o o - - - 3 x 1C cable gland and gland plates
Cable box internal arc rated (AFL) Gland plates
Top entry 3 hole split steel with earth stud o o o o o o
IP50 (standard) 3 hole split steel with earth bar o o o o o o
IP54 (optional) o o o o o o 3 hole solid brass with earth stud o o o o o o
450mm bushings to gland height,12.5KA IAC o o o o o o 3 hole solid brass with earth bar o o o o o o
610 mm bushings to gland height,12.5KA IAC o o o o o o Glands
Bottom entry (IP54) Single core compression gland o o o o o o
450mm bushings to gland height, 12.5 kA IAC o o o o o o Single core heat shrink glands o o o o o o
610mm bushings to gland height, 12.5 kA IAC o o o o o o
450mm bushings to gland height, 20KA IAC o o o o o o
610mm bushings to gland height, 20KA IAC o o o o o o
Bottom entry angled, 12.5KA IAC o o o o - -
Bottom entry deep, 12.5KA IAC o o o o - - Bus bar coupling selection table
Cable box non IAC rated
Bus bar coupling kits (length mm) 241 378 453 500 750
Top entry
Insulation for bus bar coupling
IP50 (standard)
Heat shrink manufactured by SPS o - o o o
IP54 (optional) o o o o o o
Heat shrink manufactured by Raychem o - o o o
450mm bushings to gland height o o o o o o
Heat shrink manufactured by REPL -
610mm bushings to gland height o o o o o o
Cold fit rubber boot manufactured by Pirelli - - - -
Bottom entry (IP54)
450mm bushings to gland height o o o o o o
610mm bushings to gland height o o o o o o Other accessories Quantity
Bottom entry angled o o o o - - Padlocks
Bottom entry deep o o o o - -
TLF fuses (specify quantity and Amp rating)
1 X 3C cable gland and gland plates
X size Foundation bolts (not required for transformer mounting)
Gland plates Adaptor for converting parallel bushings to DIN400
X size gland plate with earth stud o o o o o o type C connection
X size gland plate with earth bar o o o o o o
Glands
X tube glands o o o o o o
X brass wiping gland o o o o o o
Y size
Gland plates
Y size gland with earth stud o o o o o o
Y size gland with earth bar o o o o o o
Glands
Y tube glands o o o o o o
Y brass wiping gland o o o o o o

Key Standard o Options - Not applicable

Page 54 Page 55
Sabre models and options order form
To use this form, please photocopy and return the completed form to your nearest Lucy Switchgear office
Tick the boxes with your required order (addresses can be found on the back cover)
Non
Extensibility Non extensible Extensible Extensible
extensible
Name: Company:
Address: Tel No: Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Fax No: Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW

Email: Vacuum circuit breaker


Order number: Short circuit breaking current
16kA RMS - - - - - - - - - -
Order quantity / number of units (please fill separate form for each type)
20kA RMS - - - - -
21kA RMS - - - - - - - - - -
Modular units 25KA RMS - - - - - - -
Range Ring main units Modular Modular ring Bushings type
circuit switches
breaker Parallel bushings - - - - -
Non
Extensibility Non extensible Extensible Extensible
extensible Adaptor to covert parallel bushings to DIN 400 type C bushing - - - - -
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a DIN 400 type C - - - - - - - - -
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ Rated normal current
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW
250A - - - - - -
General
Extensibility
400A - - - - - - - - -
Non extensible - - - - - - 630A - - - - - - -
LH extensible - - - - - Earth & test facility - - - - - - - -
RH extensible - - - - - Circuit breaker protection
Both sides extensible - - - - - TLF - - - -
Relay (choose one from below)
Impulse withstand voltage (BIL) kVP (choose one from below)
WIP1 relay - - -
12kV at 75KVP BIL - -
15.5kV at 95KVP BIL - - Fanox realy - - -
17.5kV at 95KVP BIL - - - - - - - - - - Any other* - - -
Protection (CT) current transformers
24kV at 125kVP BIL - - - - - - - - - -
24kV at 145kVP BIL - - - - - - - - - - Dual (Primary) ratio CT 100/50/- - - -
Low gas pressure alarm auxillary contact 1NO Dual (Primary) ratio CT 200/100/- - - -
Pressure indicator gauge with Hanson coupling Triple (Primary) ratio CT 150/100/50/- - - -
Mounting style Dual (Primary) ratio CT 400/200/- - - - - - -
Transformer mounted unit (fitted with ESI flange) - - - - - - - - - Dual (Primary) ratio CT 150/100/- - - -
Freestanding unit Dual (Primary) ratio CT 600/200/- - - - - - - -
No ESI flange (with cable box) - - - Manual "Pull to trip" - - -
ESI transformer flange fitted (with/without cable box) - - - Remote shunt trip
Height of tee-off bushing from floor (applicable to freestanding units) 12V DC - - -
1100mm - - - - - - - - - 24V DC - - -
1320mm - - - - - - - - 48V DC - - -
1348mm - - - - - - - - - - 110V DC - - -
1402mm - - - - - - - - 110V AC - - -
Height of extension bushings from floor (applicable to free standing units) 240V AC - - -
- - - - Multi voltage (24V AC/DC- 240V AC/DC) - - -
1072 mm
Indication/ Auxilliary switches
Any other (available on request) - - - -
Internal arc protection for gas chamber (tank) Remote protection trip out put signal - - -
(for TLF or relay trip status) 1N/O
AF Watchdog for relays (only available with selective relays) - - -
AFL
Tripped on fault indication - - -
AFLR -
Circuit breaker actuator enabled indication - - -
Tank exhaust at top - -
Circuit breaker service indication
Tank exhaust at rear - - - - - - - - -
1NO, 1NC - - -
Extensible bus bar bushings: Obround (Hysol) - - - - -
2NO, 2NC - - -
Page 56 Page 57
Sabre models and options order form - continued

Non Non
Extensibility Non extensible Extensible Extensible
extensible
Extensibility Non extensible Extensible Extensible
extensible
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW

Circuit breaker earth indication Ring switch 2 (Right hand side)


1NO, 1NC - - - Earth & test facility - - -
2NO, 2NC - - - Bushings type
Secondary injection terminals - - - DIN 400 type C - - -
VPIS Operation counter - - - -
Neon indication push button - - - Actuators (motors)
Neon indication pfisterer socket - - - Actuators wiring only - - -
Operation counter - - - - Actuators (24V DC motor) for remote control - - -
Castell locks VPIS
Key free earth on - - - Neon indication push button - - -
Key trapped disconnector service CB ON - - - Neon indication pfisterer socket - - -
Actuators (motors) MV sensor - - -
Actuators wiring only - - - Auxilliary switches
Actuators (24V DC motor) for remote control - - - 1NO, 1NC - - -
Ring switch 1 (Left hand side) 2NO, 2NC - - -
Rated current Castell locks
400A - - - - - - - - - - Key free in off position - - -
630A - - Earth fault indication
Earth & test facility - - BFZ-50 - - -
Bushings type MFZ-50 - - -
DIN 400 type C - - MLZ-50 - - -
Operation counter - - - CFZ-50 - - -
Actuators (motors) CLZ-50 - - -
Actuators wiring only - - BLZ-50 - - -
Actuators (24V DC motor) for remote control - - Any other(*) - - -
VPIS
Neon indication push button - -
Neon indication pfisterer socket - -
MV sensor - -
Auxilliary switches
1NO, 1NC - -
2NO, 2NC - - * Please fill the details in comments section below.
Castell locks
Comments
Key free in off position - -
Earth fault indication
BFZ-50 - -
MFZ-50 - -
MLZ-50 - -
CFZ-50 - -
CLZ-50 - -
BLZ-50 - -
Any other(*) - -
Ring switch 2 (Right hand side)
Rated current
400A - - - - - - - - - -
630A - - -

Page 58 Key Standard Option select - Not applicable Page 59


Air metering unit (AMU) order form
To use this form, please photocopy and return the completed form to your nearest Lucy Switchgear office
Tick the boxes with your required order (addresses can be found on the back cover)

VT - Voltage transformer
Name: Company:
Address: Tel No: VT Primary fused protection
Fax No: Unfused primary VT with tool free bus bar isolation for VT testing (only for 630A)
Email: Fused primary VT
Order number:
VT Type Number of VT
Order quantity / number of units (please fill separate form for each type) Dual (Primary) ratio 3 Ph - 3 limb 11000/6600/110V, class 1, 50VA/PH 1
Single (Primary) ratio 3 Ph - 3 limb 11000/110V, class 1, 50VA/PH 1

Metering units Single (Primary) ratio 3 Ph - 3 limb 6600/110V, class 1, 50VA/PH 1

General 2
Single (Primary) ratio 1 Ph - 1 limb 13800/110V, class 0.5, 50VA/PH
Impulse withstand voltage (BIL) kVP (choose one from below) 3
12kV at 75KVP BIL 2
Dual (Primary) ratio 1 Ph - 1 limb 11000/6600/110V, class 0.2, 50VA/PH
15.5kV at 95KVP BIL 3
17.5kV at 95KVP BIL Accessories
Rated current
Shunt trip supply (110VAC to power shunt trip on RMU)
250A
Trip lock out relay
630A
MCB
Mounting style Secondary wiring protection
Fuses
FS: Freestanding (select incoming and outgoing cable boxes from table no: )
BC: Bus bar connected (select the length of bus bar connections from table: ) Power meters

TC: Ring main unit (tee-off ) mounted (select the outgoing cable box:)
Wiring for single meter
Bushings type Metering wiring
Wiring for 2 meters
FS: Freestanding
Circutor
Incoming DIN type C Meter type Actaris
Outgoing DIN type C Any other (*)
BC: Bus bar connected
1
Incoming DIN type C Number of meters
2
Outgoing DIN type C Door mounted
TC: Ring main unit (tee-off ) mounted Meter mounting style
Din mounted (window on the door)
Incoming direct coonection to RMU Marshalling box gland plates
Outgoing DIN type C Blank gland plate
20mm
CT - Current transformer Gland plate with 1 hole (hole size)
25mm
CT Ratio change over link
20mm and 25mm
CT Type Number of CT
16mm and 25mm
Dual (Primary) ratio CT 100/50/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 Gland plate with 2 holes (hole sizes)
20mm and 20mm
Dual (Primary) ratio CT 200/100/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2
25mm and 25mm
Dual (Primary) ratio CT 400/200/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2
Any other hole sizes/ combination(*)
Triple (Primary) ratio CT 400/200/100/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2

Key Standard Option select

Page 60 Page 61
Sabre accessories order form
To use this form, please photocopy and return the completed form to your nearest Lucy Switchgear office
Tick the boxes with your required order (addresses can be found on the back cover)

Cable box, cable gland and gland plate selection table


Name: Company:
Circuit
Address: Tel No: Ring Ring Extensible
breaker Metering unit
Fax No: switch 1 switch 2 bus bars
tee-off
Email:
(Not to be Incoming Outgoing
Order number: side
used with VRE side (for FS and
and DSE) (for FS only) TC only)
Order quantity / number of units (please fill separate form for each type)
1 X 3C cable gland and gland plates
Glands
Cable box, cable gland and gland plate selection table
X tube glands
Circuit X brass wiping gland
Ring Ring Extensible
breaker Metering unit
switch 1 switch 2 bus bars Y size
tee-off
Outgoing Gland plates
(Not to be Incoming
side Y size gland with earth stud
used with VRE side (for FS and Y size gland with earth bar
and DSE) (for FS only) TC only)
Glands
Interlocked cable box - - -
Y tube glands
Cable box internal arc rated (AFL)
Y brass wiping gland
Top entry
3 x 1C cable gland and gland plates
IP50 (standard)
Gland plates
IP54 (optional)
3 hole split steel with earth stud
450mm bushings to gland height,12.5KA IAC
3 hole split steel with earth bar
610 mm bushings to gland height,12.5KA IAC
3 hole solid brass with earth stud
Bottom entry (IP54)
3 hole solid brass with earth bar
450mm bushings to gland height, 12.5 kA IAC
Glands
610mm bushings to gland height, 12.5 kA IAC
Single core compression gland
450mm bushings to gland height, 20KA IAC
Single core heat shrink glands
610mm bushings to gland height, 20KA IAC
Bottom entry angled, 12.5KA IAC - -
Bottom entry deep, 12.5KA IAC - - Bus bar coupling selection table
Cable box non IAC rated Bus bar coupling kits (length mm) 241 378 453 500 750
Top entry Insulation for bus bar coupling
IP50 (standard) Heat shrink manufactured by SPS -
IP54 (optional) Heat shrink manufactured by Raychem -
450mm bushings to gland height Heat shrink manufactured by REPL -
610mm bushings to gland height Cold fit rubber boot manufactured by Pirelli - - - -
Bottom entry (IP54)
450mm bushings to gland height
Other accessories Quantity
610mm bushings to gland height
Padlocks
Bottom entry angled - -
Bottom entry deep - - TLF fuses (specify quantity and amp rating)
1 X 3C cable gland and gland plates Foundation bolts (not required for transformer mounting)
X size Adoptor for converting parallel bushings to DIN400
Gland plates type C connection
X size gland plate with earth stud
X size gland plate with earth bar

Key Standard Option select - Not applicable

Page 62 Page 63
Disclaimer
Lucy Switchgear has a policy of continuous research and development
and accordingly reserves the right to change the design and
specification of its products without prior notice or liability.

Lucy Switchgear worldwide offices

Lucy Switchgear Ltd. Lucy Switchgear Arabia Co. Ltd. Lucy Asia Pacific Sdn Bhd
Howland Road, Thame, Oxfordshire, Novotel Business Centre, L13A-03-03A, PJX-HM Shah Tower,
OX9 3UJ, United Kingdom P.O. Box 35340, Dammam 31488, No16A Jalan Persiaran Barat,
Tel: +44 1844 267 267 General Saudi Arabia 46050 Petaling Jaya, Selangor, Malaysia
Tel: +44 1844 267 222 Sales Tel: +966 3 8147 910 Tel: +603 74910700
Fax: +44 1844 267 223 Fax: +966 3 8147 914 Fax: +603 79316923
Email: salesuk@lucyswitchgear.com Email: salessa@lucyswitchgear.com Email: salesmy@lucyswitchgear.com

Lucy Middle East FZE Lucy Switchgear (South Africa) Lucy Electric (Beijing) Co. Ltd.
PO Box 17335, Jebel Ali, Dubai, Unit 2, Cranberry Industrial Park, Cranberry Street
United Arab Emirates Laser Park, Honeydew, 2170, South Africa
Tel: +97 148 129 999 Tel: +27 11 025 7490 18A1122
Fax: +97 148 129 900 Fax: +27 11 794 3277 : 100027
Email: salesme@lucyswitchgear.com Email: salesza@lucyswitchgear.com : +86 1059 231 176
: +86 1059 231 177
Postal Address:
: salescn@lucyswitchgear.com
P.O. Box 1078, Honeydew, 2040

To find out more about us, visit:


www.lucyswitchgear.com

You might also like