Cable terminations 31
Dimensions 37
Models, options and accessories 47
Order forms 54 1965 1970 1975 1980 1985 1990 1995 2000 2005 2010 2015
Page 2 Page 3
Product panorama Introduction to Sabre
Lucy medium voltage and high voltage range
Page 4 Page 5
Installation and operating conditions
IP54 outdoor installation (kiosk not necessary) Cable earth and test facility (E&T) Ring switches: E&T is a standard feature
located at the bottom of the unit.
Ambient temperature for operation: E&T feature is used for testing cable insulation and to
-25C to 40C (50C optional) locate faults in the circuit without the need to remove
the main cables from the cable box.
Average value over 24 hours max: 40C
The cable test access cover is fully interlocked and cannot
Maximum altitude for operation without derating:1000m be opened until the ring switch or circuit breaker switch
Insulation medium: SF6 Gas is in the Earth ON position. The test bushings are earthed
with a star bar which has to be removed for cable tests.
Interruption medium: Vacuum
Operation mechanism
The operating mechanism of the ring switches and
circuit breaker incorporates mechanical interlocks
and padlocking facilities which make it impossible to
simultaneously close the ring switch/circuit breaker and
the earth switch.
Anti-reflex mechanism
Anti-reflex mechanisms on ring switches ensure a time
delay between switching operations.
Page 6 Page 7
Safety features Application examples
Standards
International Standards
IEC 62271-1 IEC 62271-100 IEC 62271-102 IEC 62271-103 IEC 62271-200 ENA TS 41-36
Page 8 Page 9
The Sabre range
Modular non-extensible ring switches are an ideal solution for making a switching point in the network.
VRN24
24kV, 2 ring switches 630A + 1 VCB 400A
VRN6a:
12/15.5kV, 2 ring switches 630A + 1 VCB 250/630A
Page 10 Page 11
The Sabre range
Extensible range
The extensible range is used to add another function The units are extended as shown in the diagram below:
on the left, right or both sides of switchgear installed VRE6a
in secondary networks. This is an ideal solution to All the extensible units are available in the 12/15.5kV, 2 ring switches 630A + 1 VCB 250/630A
allow future upgrades to systems when extra capacity following configurations;
is required. The units can be easily extended in any Left hand
combination on site without specific tooling or floor Right hand
preparation and without the need to transfer SF6 Both sides
gas. The extensible range is designed to be mounted
outdoors without needing a kiosk.
Page 12 Page 13
The Sabre range
DSE6a VCE6a
12/15.5kV, 2 ring switches 630A 12/15.5kV, 1 VCB 630A
Page 14 Page 15
Mounting style
Page 16 Page 17
Product characteristics
21 TLF
Circuit breaker
mechanism
Page 18 Page 19
iii. Ring switch Single mechanism with two independent operating v. Circuit breaker protection
shafts, one for circuit breaker ON/OFF position and
Standard features another for selecting disconnector in Mains or Earth
(isolation) Two types of protection devices are offered
Three function ON, OFF & Earth spring loaded
Interlocked disconnector selector, locked from
to protect the circuit breaker
mechanism, independent manual operation
operation when circuit breaker is in ON position TLF : Time limit fuses
Single mechanism with rotary moving shaft for
switching ON/OFF/Earth positions Trip coil for receiving tripping signal from relay or Protection relays
TLF devices
Interlocked selector with padlocking facility for
selecting Mains or Earth ON position Protection function TLF or relay (customer specific) a. TLF
Single line intuitive mimic diagram with clear When utilised in conjunction with circuit breaker type
Single line intuitive mimic diagram with clear ring main units, time limit fuses (TLF) are a cost effective
indication of switch status (ON, OFF or Earth position) indication of switch status (ON, OFF or Earth position)
method of providing fault protection for overcurrent and
Gas pressure indicator earth faults (optional) to a transformer of 2MVA or less.
Fully interlocked cable earth and test (E&T) facility
Horizontal cable terminations at rear of the unit with
Gas pressure indicator parallel or DIN 400 type C bushings It is a recognised method of protection and was
Lateral cable terminations with DIN400 type C developed to comply with EA 41-26 (now superseded by
Protection CTs (current transformers) mounted on ENA TS 41-36) with fuse links in accordance with ENA TS
bushings cable bushings (customer specific ratios) 12-6.
Padlock facility (8.5mm diameter hole) for all the Padlock facility (8.5mm diameter hole) for all the
operating positions operating positions It should be noted that the TLF protection system is
not a device for limiting overload levels of individual
Optional features, factory fitted transformers. It should be used for fault protection only.
Optional features, factory fitted
Remote low gas pressure alarm,1N/O Remote low gas pressure alarm,1N/O The TLF system provides protection for overcurrent and
VPIS - voltage presence indication system Mechanical (manual) pull-to-trip button for local earth faults between the MV circuit breaker and the LV
operation protection device.
Remote switch position indicator (1N/O,1N/C and
2N/O, 2NC) VPIS (voltage presence indication system - refer to The selected TLF rating should be such that it allows for
VPIS section for more details) discrimination between the MV & LV devices. This will
Short circuit and earth fault current indicators (EFI)
Remote circuit breaker position indicator (1N/O,1N/C ensure that the circuit breaker does not open for faults
Actuator (motor) wiring beyond the LV distributor protection device. Fuse dimensions: Length 57mm x Diameter 13mm
and 2N/O, 2NC)
Castell locks Fully interlocked cable earth and test facility (only on When fitted with TLF, the Lucy RMU can also be
630A VCB) configured to enable tripping of the circuit breaker from
Optional features also available as retrofit Self-powered relay for protection (customer specific) remote devices (Bukholtz, LV CB etc).
Actuator (motor) for ring switch (only if unit is pre
TLF (time limit fuses) for alternative protection Lucy Switchgear customers in Europe, the Middle East,
wired for motorisation)
Wide range of CTs for TLF and relay protection Africa and Asia are currently using TLF protection system
Internal arc rated cable box within their distribution networks.
Remote protection trip output status signal (for TLF
Wide range of cable glands and accessories to
or relay trip status) 1N/O
accommodate 1 and 3 core cables (refer to cable
box section for further information) Shunt trip coils for external tripping
Tripped on fault indication
Watchdog for relays (only available with selective relays)
iv. Vacuum circuit breaker Circuit breaker actuator enabled indication
250A rated vacuum circuit breaker for
transformer protection Actuators (motor) wiring
400A rated vacuum circuit breaker for
transformer/downstream network protection Optional features also available as retrofit
630A rated vacuum circuit breaker for Actuator (motor) for CB (only if unit is pre wired for
transformer/downstream network protection motorisation)
Internal arc rated cable box
Standard features Wide range of cable glands and accessories to
Three functions (ON, OFF & Earth), two position spring accommodate 1 and 3 core cables (refer to cable
loaded mechanism, independent manual operation box section for further information)
Page 20 Page 21
Recommended TLF settings b. Protection relays Woodward WIP 1
Transformer ratings (kVA) Manufacturer Woodward
200 315 500 800 1000 1250 1600 2000 Range WIP1
Rated voltage (kV) TFL fuse rating (A)
Functions
3.3 10A
ct ratio 50/5 Phase overcurrent
6.6 5A 10A 15A
Short circuit protection
Earth fault setting = 25A 11 3A 5A 10A 15A
Number of overcurrent elements 2
(instantaneous trip) 13.8 3A 5A 10A 15A The Sabre range can be fitted with self-powered relays Earth overcurrent
24 3A 5A 7.5A for protecting the transformer or downstream network Number of earth overcurrent elements 2
from fault currents by tripping the circuit breaker. These
relays incorporate many advanced features and have a Characteristics
3.3 5A 10A 15A variety of settings to provide discrimination protection
ct ratio 100/5 6.6 5A 7.5A 12.5A 15A in networks. The self-powered feature eliminates
Display (measuring values and parameters)
reliance on external power sources and increases the Setting via buttons
Earth fault setting = 30A 11 5A 7.5A 10A 12.5A 15A 12.5A
(instantaneous trip)
performance and reliability of the protection function. Standard CT (1A/5A) 1A
13.8 5A 7.5A 10A 12.5A 15A
LED pickup
24 5A 5A 7.5A Below are the technical characteristics of Woodward
WIP1 and Fanox SIAC range. Other manufacturers relays LED trip indicator
can also be incorporated into the units on request. Flag indication output
Advantage of vacuum circuit breaker with TLF Fault memory
compared to HV fuses Clock
Feature VCB with TLF Fuse switch Password protection
Overall cost of units Similar Electro impulse and relay contact output
Maximum rating of transformer, can be protected 2MVA* 1MVA Input remote tripping
Physical size of fuses Small Large RS 485 interface with pro open data protocol O
Possibility of some pollution while changing fuses causing PD and flashover issues No Yes RS-485 interface with Modbus protocol O
Fuse location inside the unit LV side HV side Additional power supply O
Range of fuses required for different rated transformers Very small with multi ratio CT Large
Key Standard O Option
(* No issues with transfer current switching to IEC 62271-105, which minimizes the MVA rating)
Page 22 Page 23
Fanox
Functions Flag indication output Flags are included in the relay, no Flags are included in the relay, no Flags are included in the relay, no
need of external modules need of external modules need of external modules
Phase overcurrent
Fault memory 20 fault reports (64 events each). 20 fault reports (64 events each). 20 fault reports (64 events each).
Short circuit protection
In WIP 1 are recorded 5 last In WIP 1 are recorded 5 last In WIP 1 are recorded 5 last
Number of overcurrent elements 2 2 3 trip events trip events trip events
50P: 50P: (2) 50P:
Events 500 events in non-volatile 500 events in non-volatile 500 events in non-volatile
Tap:0.130xIn Tap:0.130xIn Tap:0.130xIn
RAM memory RAM memory RAM memory
Time:0,02300 s Time:0,02300 s Time:0,02300 s
51P: 51P: 51P: Characteristics
Tap:0.17xIn Tap:0.17xIn Tap:0.17xIn
Clock
Earth overcurrent
Password protection
Number of earth overcurrent 2 2 3
Electro impulse and relay contact
elements 50N: 50N: (2) 50N:
output Trip contact for striker or coil Trip contact for striker or coil Trip contact for striker or coil
Tap:0.130xIn Tap:0.130xIn Tap:0.130xIn
Time:0,02300 s Time:0,02300 s Time:0,02300 s Number of output relays 2 NO/NC 2 NO/NC 3 NO
51N: 51N: 51N:
Watchdog contact - - -
Tap:0.17xIn Tap:0.17xIn Tap:0.17xIn
Input remote tripping
Pickup level 0,2xIn(single phase) 0,2xIn(single phase) 0,2xIn(single phase)
0,1xIn (three phase) 0,1xIn (three phase) 0,1xIn (three phase) Interface O O O
Startup time (Trip time after fault. 130 ms 130 ms 70 ms RS 485 interface with pro open - - -
single phase) data protocol
RS-485 interface with Modbus O O O
Characteristics protocol Option included in the relay, no Option included in the relay, no Option included in the relay, no
need for an external module need for an external module need for an external module
Display (measuring values and MODBUS MODBUS MODBUS
parameters) (Display 20x2) (Display 20x2) (Display 20x2)
Additional power supply O O O
Setting via buttons Option included in the relay, no Option included in the relay, no Option included in the relay, no
Test menu need for an external module need for an external module need for an external module
The test menu can be used to The test menu can be used to The test menu can be used Battery No need for an internal battery No need for an internal battery No need for an internal battery
check the operation of the check the operation of the to check the operation of the to keep events and faults due to to keep events and faults due to to keep events and faults due to
signaling components (LEDs and signaling components (LEDs and signaling components (LEDs and FRAM memory FRAM memory FRAM memory
magnetic indicators), along with magnetic indicators), along with magnetic indicators), along with
the trip output and the signaling the trip output and the signaling the trip output and the signaling
outputs outputs outputs
Settings groups 1 1 3
Standard CT (1A/5A) 1A or 5A (depending on model) 1A or 5A (depending on model) 1A or 5A (depending on model)
Other manufacturers relays are also available on request, please contact our local Sales Office for more information.
LED pickup The pickup message is shown The pickup message is shown at The pickup message is shown at
at the display. Besides, the SIA-C the display. Besides, the SIA-C the display. Besides, the SIA-C
front panel has three LED pilot front panel has three LED pilot front panel has two LED pilot
lights to show the type of power lights to show the type of power lights to show the type of power
being used: self-power, battery or being used: self-power, battery or being used: self-power or battery
auxiliary power auxiliary power
LED trip indicator To signal the trip, the front panel is To signal the trip, the front panel is To signal the trip, the front panel is
equipped with 1 bistable magnetic equipped with 1 bistable magnetic equipped with 2 bistable magnetic
indicator which indicates a trip indicator which indicates a trip indicators which indicates a trip
has occurred has occurred has occurred
Page 24 Page 25
Options and accessories
Vaccum
circuit
breaker
actuator
Test bushings
Page 26 Page 27
iii. Cable boxes, glands and accessories iv. Bus bar couplings
Bus bar couplings are used to connect two extensible units.
Cable box
Cable boxes are available for the following:
Bus bar coupling lengths
o Ring switches cable bushings
254mm
o Circuit breakers tee-off bushings
378mm
o Metering units bushings
o Extensible bus bar bushings 453mm
Safety interlocks: The cable boxes can be interlocked with a ring 500mm
switch or circuit breaker mechanism. Interlocked cable boxes can 750mm
only be removed when the circuit is in the Earth ON position
Internal arc rating Bus bar insulation types
o Non internal arc rated cable box as standard Heat shrink (manufactured by SPS)
o Internal arc rated cable boxes 12.5kA 1sec and 20kA Heat shrink (manufactured by Raychem)
1 sec as optional Heat shrink (manufactured by REPL)
Cable box lengths Cold fit rubber boot (manufactured by Pirelli?)
o 450mm
o 610mm
Cable entry v. MV sensors
o Top entry with Bottom entry BMV sensors are used to detect the medium voltage in the cable
IP50 standard (indoor only) and send a signal to the remote control device for auto changeover.
IP54 optional
o Bottom entry with IP54 as standard
Straight vi. Watchdog for relays
Angled They are used to check the healthy operation of relays.
Page 28 Page 29
Cable terminations
x. Shunt trip coils The bushings are accessible by removing the cable box covers at the lateral and rear of the unit.
Shunt trips are magnetic coils that are used to trip circuit breakers The maximum cable sizes that can be used are:
through local push buttons, RTUs or additional transformer 300mm 3 - core
protection devices. 500mm single - core.
The following types of terminations can be used with the Sabre range:
Shunt trips are available in the following voltages:
Manufacturer Model: Suparule Sensorform BLZ-50 BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50
Features
3.6V lithium AA 110-240V a.c. CT on current carrying phase
Power source 850mAH battery
1 38kV
Profile C bolted separable
Voltage range
Trip current 50A
Primary indication LED Mech-flag (RED) LED Mech-flag (RED) LED
Flashing duration >1000 hrs - - 10 hrs - 10 hrs DIN type C bushings (cable boxes)
Minimum fault duration 2.5 cycles Insulating bushing boot
Manual reset Push button Heat shrink insulating bushing boot
Automatic timer reset 4 or 8 hrs selectable 10 secs after mains restore Profile C bolted separable
Manual trip test Push button
Obround bushings (bus bar extension)
Operating temperature -40C to +80C
The following cable connections could be used if direct cable connection is required on the bus bar bushings
Operating humidity 0-100% RH
Insulating bushing boot
Ingress protection IP65 Heat shrink insulating bushing boot
Current sensor diameter: CT100: 100mm
CT150: 150mm O O O O O O Parallel bushings (tee-off)
CT300: 300mm O O O O O O The following connectors could be used if cable tee-off direct cable connection is required
Remote flashing LED indicator O O O O O O Insulating bushing boot
Auxiliary relay, 1N/O latching O O O O O O Heat shrink insulating bushing boot
Key Standard O Option Other manufacturers EFIs are also available on request, please contact our local sales office for more information.
Page 30 Page 31
Air metering unit (AMU) Remote terminal unit (RTU)
Tee-off metering
Page 32 Page 33
Technical Data Sheet
Inputs / Outputs Digital inputs 14 isolated digital inputs - expandable Internal arc protection
Unit kA 1 sec 20 21 16 20
Digital outputs 8 isolated digital outputs - expandable
cable box (optional) kA 1 sec 12.5/20 12.5 12.5/20
Analogue inputs 3 CT analogue inputs as standard (DIs reduced to 11) Gas tank internal arc ratings
Expansion I/O module 3 AIs / 4 DIs; 7 DIs / 2 DOs AF Standard
AFL Optional
3 RS-232 for control (ethernet option), configuration
Communications Communication interfaces AFLR - Optional - - Optional
and programming plus one expansion bus
SF6 gas
DNP3, IEC 60870-5-101/104 and Modbus Filled pressure Bar (G) 0.4 0.5 0.4
Protocols
(others on request) Minimum operating presure Bar (G) 0 0.3 0
RS-232, UHF / VHF radio, packet data, GSM / GPRS / EDGE, Annual leakage rate 0.1% per annum
Weight Kg 1.46 1.56 1.78 1.05 0.78 0.98
Communication media PTSN, leased or twisted pair lines, optical fibre, ethernet
(TCP/IP) and bluetooth Installation conditions
Ambient air temperature (without derating) C 40/50
Membrane push-button for open / close operations in Maximum altitude (without derating)* M 1000
conjunction with activate push-button, up to four switching Relative humidity (max) - over period of
Switchgear interface Controls 100%
functions (standard 1, 2, 3 or 4 switch control formats), 24hrs (IEC 62271-1, sub-clause 2.1)
selector control for off, local or remote modes
RTU services such as DC / AC supplies, dummy control and Ring main unit Modular circuit Modular ring switch
breaker
debug LEDs
Non
Indications Switch status LEDs for open / closed positions Non Extensible Extensible
Extensible
Control output LEDs (illuminates when active) Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
Configurable LED indications 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB 1 VCB 1 VCB 1 RSW 2 RSW 2 RSW
Cables Plug-in, multi-core umbilicals to switchgear
Bus bars
Windows-based software for configuration of: Rated normal current A 630 400/630 630
Protocol parameters including device and I/O addresses Rated short time withstand current 20 kA 3s 21kA 1s 16kA 3s 20kA 3s
Parameters for the communications device Rated peak withstand current kA 50 54.6 40 50
Software Configuration Parameters for digital, analogue and counter points
Automation sequences
Power saving routines * for higher altitude applications please contact our local Lucy Switchgear sales office
Battery tests
Page 34 Page 35
Dimensions
Ring main unit Modular circuit Modular ring switch Dimensions & floor:
breaker VRN2A
Non Extensible Extensible Non
Extensible
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB 1 VCB 1 VCB 1 RSW 2 RSW 2 RSW
Ring switch
Rated normal current A 630 400/630 630 630 630
Rated active load breaking current A 630 400/630 630 630 630
Rated short circuit making current
Ring switch kA 50 54.6 40 50 50
Earth switch kA 50 54.6 40 50 50
Rated cable charging breaking current A 25 25
Rated short time withstand current
Ring switch 20 kA 3s 21kA 1s 16kA 3s 20kA 3s 20kA 3s
Earth switch 20 kA 3s 21kA 1s 16kA 3s 20kA 3s 20kA 3s
Mechanical endurance class
Ring switch M2 (5000) M2 (5000)
Earth switch M1 (1000) M1 (1000)
Electrical endurance class short circuit making
Ring switch E3 (5 times) E1 (2 times) E3 (5 times) E3 (5 times)
Earth switch E2 (3 times) E1 (2 times) E2 (3 times) E2 (3 times)
Operating mechanism
Local: close/open Handle Handle
Remote: close/open Actuator (Motor) Actuator (Motor)
Page 36
NOTE: All the dimensions are in mm Page 37
Dimensions - continued
Page 38
NOTE: All dimensions are in mm Page 39
Dimensions - continued
Page 40
NOTE: All dimensions are in mm Page 41
Dimensions - continued
Page 42
NOTE: All dimensions are in mm Page 43
Dimensions - continued
Page 44
NOTE: All dimensions are in mm Page 45
Dimensions - continued
Page 46
NOTE: All dimensions are in mm Page 47
Sabre models and options
Modular units Extensibility Non extensible Extensible Extensible
Non
extensible
Range Ring main units Modular Modular ring
circuit Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
breaker switches
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Non Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW
Extensibility Non extensible Extensible Extensible
extensible
Vacuum circuit breaker
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
Bushings type
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW Parallel bushings - - - - -
General Adaptor to covert parallel bushings to DIN 400 type C bushing o o - - o o o o - - -
Extensibility DIN 400 type C - - - - - - - - -
Non extensible - - - - - - Rated normal current
LH extensible - - - - o o o o o o - 250A o - - o - - - -
RH extensible - - - - o o o o o o - 400A - - - - - - - - -
Both sides extensible - - - - o o o o o o - 630A - o - - - - - -
Impulse withstand voltage (BIL) kVP Earth & test facility - o - - - o - o - - -
(choose one from below) Circuit breaker protection
12kV at 75KVP BIL o o - - o o o o o o o TLF o o - o o o o o - - -
15.5kV at 95KVP BIL o o - - o o o o o o o Relay (choose one from below)
17.5kV at 95KVP BIL - - o - - - - - - - - WIP1 relay o o o o o o o o - - -
24kV at 125kVP BIL - - - o - - - - - - - Fanox relay o o o o o o o o - - -
24kV at 145kVP BIL - - - o - - - - - - - Any other* o o o o o o o o - - -
Low gas pressure alarm auxiliary contact 1NO o o o o o o o o o o o Protection (CT) current transformers
Pressure indicator gauge with Hanson coupling Dual (Primary) ratio CT 100/50/- o o o o o o o o - - -
Mounting style Dual (Primary) ratio CT 200/100/- o o o o o o o o - - -
Transformer mounted unit (fitted with ESI flange) o - - - - - o - - - - Triple (Primary) ratio CT 150/100/50/- o o o o o o o o - - -
Freestanding unit o o Dual (Primary) ratio CT 400/200/- - o o o - o - o - - -
No ESI flange (with cable box)1 o o o o o o o o - - - Dual (Primary) ratio CT 150/100/- o o o o o o o o - - -
ESI Transformer flange fitted (with/without cable box)1 o o o o o o o o - - - Dual (Primary) ratio CT 600/200/- - o o - - o - o - - -
Height of tee-off bushing from floor Manual "Pull to trip" o o o o o o - - -
(applicable to freestanding units) Remote shunt trip
1100mm o - - o - - - - - - - 12V DC o o o o o o o o - - -
1320mm o o - o - - - - - - - 24V DC o o o o o o o o - - -
1348mm - - - - - - - - - - 48V DC o o o o o o o o - - -
1402mm o o - o - - - - - - - 110V DC o o o o o o o o - - -
Height of extension bushings from floor 110V AC o o o o o o o o - - -
(applicable to free standing units) 240V AC o o o o o o o o - - -
1072 mm - - - - Multi voltage (24V AC/DC- 240V AC/DC) o o o o o o o o - - -
Any other (available on request) - - - - o o o o o o o Indication / auxiliary switches
Internal arc protection for gas chamber (tank) Remote protection trip output signal
(for TLF or relay trip status) 1N/O
o o o o o o o o - - -
AF
Watchdog for relays (only available with selective relays) o o o o o o o o - - -
AFL o o o o o o o o o o o
Tripped on fault indication o o o o o o o o - - -
AFLR o o - o o o o o o o o
Circuit breaker actuator enabled indication o o o o o o o o - - -
Tank exhaust at top - -
Circuit breaker service indication
Tank exhaust at rear - - - - - - - - -
1NO, 1NC o o o o o o o o - - -
Extensible bus bar bushings: Obround (Hysol) - - - - -
2NO, 2NC o o o o o o o o - - -
Vacuum circuit breaker
Short circuit breaking current Circuit breaker earth indication
16kA RMS - - - - - - - - - - 1NO, 1NC o o o o o o o o - - -
20kA RMS - - - - - 2NO, 2NC o o o o o o o o - - -
Secondary injection terminals o o o o o o o o - - -
21kA RMS - - - - - - - - - -
25KA RMS 2 - o o - - o - o - - - Key Standard 1: Refer to cable box, cable gland and gland plate table for more information
o Options 2: Available soon
- Not applicable
Page 48 Page 49
Sabre models and options - continued
Non Non
Extensibility Non extensible Extensible Extensible
extensible
Extensibility Non extensible Extensible Extensible
extensible
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW
Page 50 Page 51
Air metering unit (AMU)
Metering units
General Accessories
Impulse withstand voltage (BIL) kVP (choose one from below) Shunt trip supply (110VAC to power shunt trip on RMU) o
12kV at 75KVP BIL o Trip lock out relay o
15.5kV at 95KVP BIL o MCB o
17.5kV at 95KVP BIL o Secondary wiring protection
Fuses o
Rated current
Power meters
250A o
630A o
Mounting style Metering wiring Wiring for single meter
FS: Freestanding (select incoming and outgoing cable boxes from table no: ) o Wiring for 2 meters o
BC: Bus bar connected (select the length of bus bar connections from table: ) o Circutor o
TC: Ring main unit (tee-off ) mounted (select the outgoing cable box) o
Meter type Actaris o
Bushings type
FS: Freestanding Any other (*) o
Incoming DIN type C 1 o
Number of meters
Outgoing DIN type C 2 o
BC: Bus bar connected
Door mounted o
Incoming DIN type C Meter mounting style
Din mounted (window on the door) o
Outgoing DIN type C
TC: Ring main unit (tee-off ) mounted Marshalling box gland plates
Incoming direct coonection to RMU Blank gland plate o
Outgoing DIN type C 20mm o
Gland plate with 1 hole (hole size)
25mm o
CT - Current transformer 20mm and 25mm o
CT ratio change over link o 16mm and 25mm o
CT type Number of CT Gland plate with 2 holes (hole sizes)
20mm and 20mm o
Dual (Primary) ratio CT 100/50/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 o
25mm and 25mm o
Dual (Primary) ratio CT 200/100/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 o
Dual (Primary) ratio CT 400/200/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 o Any other hole sizes / combination(*) o
Triple (Primary) ratio CT 400/200/100/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 o
VT - Voltage transformer
VT primary fused protection
Unfused primary VT with tool free bus bar isolation for VT testing (only for 630A) o
Fused primary VT o
VT type Number of VT
Dual (Primary) ratio 3 Ph - 3 limb 11000/6600/110V, class 1, 50VA/PH 1 o
Single (Primary) ratio 3 Ph - 3 limb 11000/110V, class 1, 50VA/PH 1 o
Single (Primary) ratio 3 Ph - 3 limb 6600/110V, class 1, 50VA/PH 1 o
2 o
Single (Primary) ratio 1 Ph - 1 limb 13800/110V, class 0.5, 50VA/PH
3 o
2 o
Dual (Primary) ratio 1 Ph - 1 limb 11000/6600/110V, class 0.2, 50VA/PH
3 o
Page 52 Page 53
Accessories
Cable box, cable gland and gland plate selection table Cable box, cable gland and gland plate selection table
Circuit Circuit
Ring Ring Extensible Ring Ring Extensible
breaker Metering unit breaker Metering Unit
switch 1 switch 2 bus bars Switch 1 Switch 2 bus bars
tee-off tee-off
Outgoing Outgoing
(Not to be Incoming (Not to be Incoming
side side
used with VRE side used with VRE side
(for FS and (for FS and
and DSE) (for FS only) and DSE) (for FS only)
TC only) TC only)
Interlocked cable box o o o - - - 3 x 1C cable gland and gland plates
Cable box internal arc rated (AFL) Gland plates
Top entry 3 hole split steel with earth stud o o o o o o
IP50 (standard) 3 hole split steel with earth bar o o o o o o
IP54 (optional) o o o o o o 3 hole solid brass with earth stud o o o o o o
450mm bushings to gland height,12.5KA IAC o o o o o o 3 hole solid brass with earth bar o o o o o o
610 mm bushings to gland height,12.5KA IAC o o o o o o Glands
Bottom entry (IP54) Single core compression gland o o o o o o
450mm bushings to gland height, 12.5 kA IAC o o o o o o Single core heat shrink glands o o o o o o
610mm bushings to gland height, 12.5 kA IAC o o o o o o
450mm bushings to gland height, 20KA IAC o o o o o o
610mm bushings to gland height, 20KA IAC o o o o o o
Bottom entry angled, 12.5KA IAC o o o o - -
Bottom entry deep, 12.5KA IAC o o o o - - Bus bar coupling selection table
Cable box non IAC rated
Bus bar coupling kits (length mm) 241 378 453 500 750
Top entry
Insulation for bus bar coupling
IP50 (standard)
Heat shrink manufactured by SPS o - o o o
IP54 (optional) o o o o o o
Heat shrink manufactured by Raychem o - o o o
450mm bushings to gland height o o o o o o
Heat shrink manufactured by REPL -
610mm bushings to gland height o o o o o o
Cold fit rubber boot manufactured by Pirelli - - - -
Bottom entry (IP54)
450mm bushings to gland height o o o o o o
610mm bushings to gland height o o o o o o Other accessories Quantity
Bottom entry angled o o o o - - Padlocks
Bottom entry deep o o o o - -
TLF fuses (specify quantity and Amp rating)
1 X 3C cable gland and gland plates
X size Foundation bolts (not required for transformer mounting)
Gland plates Adaptor for converting parallel bushings to DIN400
X size gland plate with earth stud o o o o o o type C connection
X size gland plate with earth bar o o o o o o
Glands
X tube glands o o o o o o
X brass wiping gland o o o o o o
Y size
Gland plates
Y size gland with earth stud o o o o o o
Y size gland with earth bar o o o o o o
Glands
Y tube glands o o o o o o
Y brass wiping gland o o o o o o
Page 54 Page 55
Sabre models and options order form
To use this form, please photocopy and return the completed form to your nearest Lucy Switchgear office
Tick the boxes with your required order (addresses can be found on the back cover)
Non
Extensibility Non extensible Extensible Extensible
extensible
Name: Company:
Address: Tel No: Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Fax No: Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW
Non Non
Extensibility Non extensible Extensible Extensible
extensible
Extensibility Non extensible Extensible Extensible
extensible
Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a SSE6a DSE6a DSN6a
2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+
Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW Description 1VCB 1VCB 1VCB 1VCB 1VCB 1VCB
1VCB 1VCB 1 RSW 2 RSW 2 RSW
VT - Voltage transformer
Name: Company:
Address: Tel No: VT Primary fused protection
Fax No: Unfused primary VT with tool free bus bar isolation for VT testing (only for 630A)
Email: Fused primary VT
Order number:
VT Type Number of VT
Order quantity / number of units (please fill separate form for each type) Dual (Primary) ratio 3 Ph - 3 limb 11000/6600/110V, class 1, 50VA/PH 1
Single (Primary) ratio 3 Ph - 3 limb 11000/110V, class 1, 50VA/PH 1
General 2
Single (Primary) ratio 1 Ph - 1 limb 13800/110V, class 0.5, 50VA/PH
Impulse withstand voltage (BIL) kVP (choose one from below) 3
12kV at 75KVP BIL 2
Dual (Primary) ratio 1 Ph - 1 limb 11000/6600/110V, class 0.2, 50VA/PH
15.5kV at 95KVP BIL 3
17.5kV at 95KVP BIL Accessories
Rated current
Shunt trip supply (110VAC to power shunt trip on RMU)
250A
Trip lock out relay
630A
MCB
Mounting style Secondary wiring protection
Fuses
FS: Freestanding (select incoming and outgoing cable boxes from table no: )
BC: Bus bar connected (select the length of bus bar connections from table: ) Power meters
TC: Ring main unit (tee-off ) mounted (select the outgoing cable box:)
Wiring for single meter
Bushings type Metering wiring
Wiring for 2 meters
FS: Freestanding
Circutor
Incoming DIN type C Meter type Actaris
Outgoing DIN type C Any other (*)
BC: Bus bar connected
1
Incoming DIN type C Number of meters
2
Outgoing DIN type C Door mounted
TC: Ring main unit (tee-off ) mounted Meter mounting style
Din mounted (window on the door)
Incoming direct coonection to RMU Marshalling box gland plates
Outgoing DIN type C Blank gland plate
20mm
CT - Current transformer Gland plate with 1 hole (hole size)
25mm
CT Ratio change over link
20mm and 25mm
CT Type Number of CT
16mm and 25mm
Dual (Primary) ratio CT 100/50/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2 Gland plate with 2 holes (hole sizes)
20mm and 20mm
Dual (Primary) ratio CT 200/100/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2
25mm and 25mm
Dual (Primary) ratio CT 400/200/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2
Any other hole sizes/ combination(*)
Triple (Primary) ratio CT 400/200/100/5A, burden 10VA, class 0.5s, STC 16kA/3sec 2
Page 60 Page 61
Sabre accessories order form
To use this form, please photocopy and return the completed form to your nearest Lucy Switchgear office
Tick the boxes with your required order (addresses can be found on the back cover)
Page 62 Page 63
Disclaimer
Lucy Switchgear has a policy of continuous research and development
and accordingly reserves the right to change the design and
specification of its products without prior notice or liability.
Lucy Switchgear Ltd. Lucy Switchgear Arabia Co. Ltd. Lucy Asia Pacific Sdn Bhd
Howland Road, Thame, Oxfordshire, Novotel Business Centre, L13A-03-03A, PJX-HM Shah Tower,
OX9 3UJ, United Kingdom P.O. Box 35340, Dammam 31488, No16A Jalan Persiaran Barat,
Tel: +44 1844 267 267 General Saudi Arabia 46050 Petaling Jaya, Selangor, Malaysia
Tel: +44 1844 267 222 Sales Tel: +966 3 8147 910 Tel: +603 74910700
Fax: +44 1844 267 223 Fax: +966 3 8147 914 Fax: +603 79316923
Email: salesuk@lucyswitchgear.com Email: salessa@lucyswitchgear.com Email: salesmy@lucyswitchgear.com
Lucy Middle East FZE Lucy Switchgear (South Africa) Lucy Electric (Beijing) Co. Ltd.
PO Box 17335, Jebel Ali, Dubai, Unit 2, Cranberry Industrial Park, Cranberry Street
United Arab Emirates Laser Park, Honeydew, 2170, South Africa
Tel: +97 148 129 999 Tel: +27 11 025 7490 18A1122
Fax: +97 148 129 900 Fax: +27 11 794 3277 : 100027
Email: salesme@lucyswitchgear.com Email: salesza@lucyswitchgear.com : +86 1059 231 176
: +86 1059 231 177
Postal Address:
: salescn@lucyswitchgear.com
P.O. Box 1078, Honeydew, 2040